1.500/2.000 LITRE - austria-email.com

2
Misprints and technical changes reserved! INDIRECT WATER HEATERS Multi-purpose large storage tank VT FRMR 1.500/2.000 LITRE WITH 2 HEAT- EXCHANGERS For inspection and cleaning purposes as well as for combination with a finned tube heat exchanger or a flange-mounted heater, this solar standing tank is equipped with a lateral flange of 240 mm Ø.

Transcript of 1.500/2.000 LITRE - austria-email.com

Page 1: 1.500/2.000 LITRE - austria-email.com

Misprints and technical changes reserved!

INDIRECT WATER HEATERS

Multi-purpose large storage tank

VT FRMR1.500/2.000 LITRE

WITH 2 HEAT-

EXCHANGERS

For inspection and cleaning purposes as well as for combination with a finned tube

heat exchanger or a flange-mounted heater, this solar standing tank is equipped with a

lateral flange of 240 mm Ø.

Page 2: 1.500/2.000 LITRE - austria-email.com

Service telephone +43 (0)3512/700-0 www.austria-email.com

IND

IRE

CT

WAT

ER

H

EAT

ER

S

FLOOR STANDING TANK VACUTHERM SUPER XL

TECHNICAL DATAn Operating pressure: tank max. 8 bar, heating coil max. 10 barn Capacity: 1,500 L, 2,000 Ln 100 mm ECO SKIN insulationn Operating temperature storage tank: 95 °C; operating

temperature heat exchanger: 110 °Cn Enamelled sheet steel inner tank according to DIN 4753 with

built-in external current anoden These stationary solar cylinders have large-surface heat ex- changers for bivalent or trivalent operation with heating, solar,

heat pump or district heating connection. n The lower heat exchanger, which is drawn into the floor,

causes n an improvement in efficiency as well as optimalheating of the floor, which destroys any bacteria (legionella)that may have been introduced with the cold water.

n For control purposes, 3 sensor tubes are fitted along thestorage tank jacket.

n For inspection and cleaning purposes, as well as for combi- nation with a finned tube heat exchanger or built-in heaters,

this multi-purpose heat exchanger storage tank has a lateral flange of 240 mm Ø is provided

n Drainage via cold water pipen Cold and hot water connection 2“ ETn Circulation connection 2“ IT

ACCESSORIES n Supplementary or auxiliary heating Screw-in heating element

6/4“-sleeve

n ATR, screw-in heater SH, reducing flange from 240 mm Ø to180 mm Ø, flange-mounted heater type RDW/RSW, finnedtube heat exchanger RWT

TECHNICAL DATA

Type Article.no.

Dimensions in mm Heat exch-anger

surfacem2

ETEin mm

ETFin mm

Weightin kg

HT DNø A B C D E F G I J K L M N

VT 1500 FRMR A 318 17 2215 1000 565 942 525 320 1115 605 1225 1225 1730 1115 425 1336 1713 2,5/2,5 6/4“/900 240/900 355

VT 2000 FRMR A 319 24 2130 1250 631 1006 591 320 1150 671 1150 1150 1581 1150 491 1203 1579 3,1/3,1 6/4“/900 240/900 590

TypeNL number

according to DIN 4708 Heat loss ccording to EN 12897Tapping profile Energy

efficiency classRegister below Top register in kWh/24h S in watts

VT 1500 FRMR 33,6 19,8 3,81 158,8 3XL C

VT 2000 FRMR 44,3 24,9 4,48 186,7 4XL C

ECO DESIGN-LABELING 2 YEARS WARRANTY ON THE INNER BOILER

ETE: Installation depth Screw-in heating sleeve for SH heating ETF: Flange installation depth (for built-in heating or finned tube heat exchanger)

External cur-rent anode

External cur-rent anode

Sensor tube

Sensor tube

Sensor tube