1404-IN007E-EN-P20061001

64
Publication 1404-IN007E-EN-P - October 2006 Installation Instructions Powermonitor 3000 Master Module Catalog Numbers 1404-M4, 1404-M5, 1404-M6, 1404-M8 Topic Page Important User Information 2 About This Publication 3 Safety Considerations 4 About Power Monitor 6 Catalog Number Explanation 10 Quick Start Guidelines 10 Install the Powermonitor 3000 Unit 12 Interpret the LED Indicators 47 Specifications 57 Additional Resources 62

Transcript of 1404-IN007E-EN-P20061001

  • Installation Instructions

    Powermonitor 3000 Master Module

    Catalog Numbers 1404

    Topic

    Important User Information

    About This Publication

    Safety Considerations

    About Power Monitor

    Catalog Number Explanation

    Quick Start Guidelines

    Install the Powermonitor 3000 Un

    Interpret the LED Indicators

    Specifications

    Additional ResourcesPublication 1404-IN007E-EN-P - October 2006

    -M4, 1404-M5, 1404-M6, 1404-M8

    Page

    2

    3

    4

    6

    10

    10

    it 12

    47

    57

    62

  • 2 Powermonitor 3000 Master Module

    Publication 1404-IN007E-EN-P

    Important User Information

    Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the ApplicaSGI-1.1 available from your local http://literature.rockwellautomatequipment and hard-wired electrowide variety of uses for solid statsatisfy themselves that each inte

    In no event will Rockwell Automaresulting from the use or applicat

    The examples and diagrams in thvariables and requirements assocassume responsibility or liability

    No patent liability is assumed by equipment, or software described

    Reproduction of the contents of tAutomation, Inc., is prohibited.

    Throughout this manual, when ne

    WARNINGIdentifies a hazardoudamage, o

    IMPORTANT Identifies the produc

    ATTENTIONIdentifies or death, pavoid a ha

    SHOCK HAZARD

    Labels mapeople tha

    BURN HAZARD

    Labels mapeople tha- October 2006

    tion, Installation and Maintenance of Solid State Controls (publication Rockwell Automation sales office or online at ion.com) describes some important differences between solid state mechanical devices. Because of this difference, and also because of the

    e equipment, all persons responsible for applying this equipment must nded application of this equipment is acceptable.

    tion, Inc. be responsible or liable for indirect or consequential damages ion of this equipment.

    is manual are included solely for illustrative purposes. Because of the many iated with any particular installation, Rockwell Automation, Inc. cannot

    for actual use based on the examples and diagrams.

    Rockwell Automation, Inc. with respect to use of information, circuits, in this manual.

    his manual, in whole or in part, without written permission of Rockwell

    cessary, we use notes to make you aware of safety considerations.

    information about practices or circumstances that can cause an explosion in s environment, which may lead to personal injury or death, property r economic loss.

    information that is critical for successful application and understanding of t.

    information about practices or circumstances that can lead to personal injury roperty damage, or economic loss. Attentions help you to identify a hazard, zard, and recognize the consequences.

    y be on or inside the equipment, for example, a drive or motor, to alert t dangerous voltage may be present.

    y be on or inside the equipment, for example, a drive or motor, to alert t surfaces may reach dangerous temperatures.

  • Powermonitor 3000 Master Module 3

    About This PublicationThese installation instructions do not contain the following information. Except as noted, refer to the Powermonitor 3000 Unit User Manual, publication 1404-UM001, for detailed information o

    Information on me

    Use of the display

    Discussion of commoperation

    Setpoint configurat

    Discrete I/O config

    Data logging includLog

    Advanced features Transient Detection

    Powermonitor 3000

    Sample ladder diagunit using various

    Display Module Ins

    This manual does nPowermonitor 3000Ethernet series A, arevisions 2.0 earlie1404-UM001D-EN-Phttp://www.rockw

    Terms and ConventionsIn this manual, the follow

    Abbreviation

    AWG

    CSA

    CT

    DM

    EMI

    ID

    IECPublication 1404-IN007E-EN-P - October 2006

    n the topics in this list.

    tering functionality and measurements

    module for configuration, monitoring and commands

    unication options, functionality, configuration, and

    ion and operation

    uration and operation

    ing Event Log, Trend Log, Min/Max Log, and Load Factor

    including Oscillography, Harmonic Analysis, and

    data tables

    rams for communicating with the Powermonitor 3000 communication options

    tallation Instructions, publication 1404-IN005

    ot provide information on functionality found in the master module, firmware revisions 3.0 and earlier, or ll firmware revisions, or Ethernet series B firmware r. Please refer to publications 1404-IN007D-EN-P and , available as downloads from

    ellautomation.com.

    ing terms and conventions are used.

    Term

    American Wire Gauge

    Canadian Standards Association

    Current Transformer

    Display Module

    Electromagnetic Interference

    Identification

    International Electrotechnical Commission

  • 4 Powermonitor 3000 Master Module

    Publication 1404-IN007E-EN-P

    Safety Consideratio

    LED Light Emitting Diode

    NEMA National Electrical Manufacturers Association

    PLC

    PT

    RAM

    RFI

    R I/O

    RMS

    SLC

    SPDT

    UL

    VA

    VAR

    CIP

    NAP

    ATTENTION Only qualiwire, and Before beare de-enin persona

    ATTENTION Never opeapplied. Winclude a secondaryremoved iproduces property d

    Abbreviation Term- October 2006

    ns

    Programmable Logic Controller

    Potential Transformer (Also known as VT in some countries)

    Random Access Memory

    Radio Frequency Interference

    Remote Input/Output

    Rootmeansquare

    Small Logic Controller

    Single Pole Double Throw

    Underwriters Laboratories

    Voltampere

    Voltampere Reactive

    Control and Information Protocol

    Network Access Port

    fied personnel, following accepted safety procedures, should install, service the Powermonitor 3000 unit and its associated components. ginning any work, disconnect all sources of power and verify that they ergized and locked out. Failure to follow these instructions may result l injury or death, property damage, or economic loss.

    n a current transformer (CT) secondary circuit with primary current iring between the CTs and the Powermonitor 3000 unit should

    shorting terminal block in the CT secondary circuit. Shorting the with primary current present allows other connections to be f needed. An open CT secondary with primary current applied a hazardous voltage, which can lead to personal injury, death, amage, or economic loss.

  • Powermonitor 3000 Master Module 5

    IMPORTANT The Powermonitor 3000 unit is not designed for nor intended for use as a circuit protective device. Do not use this equipment in place of a motor overload relay or circuit p

    IMPORTANT The relay Powermoncontrol orfailure is c

    Refer to p

    Be sure toor process

    ATTENTION ElectrostaFollow the

    Touch a

    Wear a

    Do not

    Use a s

    Keep thPublication 1404-IN007E-EN-P - October 2006

    rotective relay.

    output contacts and solid-state KYZ output contacts on the itor 3000 unit may be used to control other devices through setpoint

    communication. The response of these outputs to a communication onfigurable by the user.

    ublication 1404-UM001 for information on configuring the outputs.

    evaluate the safety impact of the output configuration on your plant .

    tic discharge can damage integrated circuits or semiconductors. se guidelines when you handle the module.

    grounded object to discharge static potential.

    n approved wrist strap-grounding device.

    open the module or attempt to service internal components.

    tatic safe workstation, if available.

    e module in its static shield bag when not in use.

  • 6 Powermonitor 3000 Master Module

    Publication 1404-IN007E-EN-P

    About Power MonitorThe Bulletin 1404 Powermonitor 3000 unit is uniquely designed and developed to meet the needs of both producers and users of electric power. A power monitor system consists of:

    master module tha

    optional display m

    optional communicnetworks.

    optional external dreporting, control,

    The Powermonitor 3000 udevice ideally suited for a

    Load Profiling - Usparameters such aspower usage by lo

    Demand Managemoccur lets you makcosts.

    Cost Allocation - Kefficiencies.

    Distribution Systemflow, system topolo

    Emergency Load Shstability in the even

    Power System Conpower factor.

    The power monitor is a soelectro-mechanical meteriindividual transducers andunderstand, accurate infor

    Powermonitor 3000 MaThe master module containcluding terminations fora native RS-485 communic- October 2006

    t provides metering and native RS-485 communication.

    odule for configuration, commands, and data display.

    ation port to serve data to other devices using a choice of

    evices and applications that display and utilize data for and management of power and energy usage.

    nit is a microprocessor-based monitoring and control variety of applications including these:

    ing the configurable trending utility to log power real power, apparent power, and demand, for analysis of ads over time.

    ent - Understanding when and why demand charges e informed decisions that reduce your electrical power

    nowing your actual energy costs promotes manufacturing

    Monitoring - Using power parameters to show power gy, and distribution equipment status.

    edding - Monitoring power usage to preserve system t of sudden utility outage.

    trol - Managing system voltage, harmonic distortion, and

    phisticated modern alternative for traditional ng devices. A single power monitor can replace many meters. The power monitor provides you with easy to mation in a compact economical package.

    ster Moduleins the main microprocessor-based monitoring functions, power system connections, status inputs, control outputs, ation port, and a port for the display module.

  • Powermonitor 3000 Master Module 7

    Configuration

    Although the power monitor ships from the factory with default settings, you need to configure it for your particular requirements. You may configure the power monitor using the optionadevice or application to wto the master module thro

    Refer to the Powermonitoadditional detail.

    Optional external applicatinclude RSPower, RSPowepersonal computer. Contadistributor, or visit http://wavailable software packag

    Communication

    Every Powermonitor 3000The native port is suitable

    PLC-5, SLC 500, an

    RSLinx software wi

    Modbus RTU Maste

    other third-party de

    software that you d

    You may also specify Powincluding:

    serial RS-232.

    remote I/O.

    DeviceNet.

    EtherNet/IP.

    ControlNet.

    A power monitor may be computer-based control amethods listed above.Publication 1404-IN007E-EN-P - October 2006

    l display module. Alternately, you may use an external rite configuration, operational parameters and commands ugh its native or optional communication port.

    r 3000 User Manual, publication 1404-UM001, for

    ions that you may use for power monitor configuration rPlus, and RSEnergyMetrix software operating on a ct your local Rockwell Automation sales office or ww.software.rockwell.com/ for more information on

    es.

    unit comes with a native RS-485 communication port. for communicating to devices including:

    d ControlLogix processors.

    th DDE/OPC server functionality.

    r devices.

    vices.

    evelop.

    ermonitor 3000 units with optional communication ports

    easily integrated into a programmable controller or nd monitoring system, using any of the communication

  • 8 Powermonitor 3000 Master Module

    Publication 1404-IN007E-EN-P

    Master Module with Communication Options

    Powermonitor 3000Powermonitor 3000wermonitor 3000

    Removable Status Input Connector

    Terminal Blocks

    Optional RS-232 Port

    OptiRem- October 2006

    Powermonitor 3000wermonitor 3000 Powermonitor 3000 Powermonitor 3000

    LED Indicators

    Display Module Port

    RS-485 (Native) Communication Port

    onal ote I/O Port

    Optional DeviceNet Port

    Optional Ethernet 10BaseT Port

    NAP Port

    ControlNet Channel A

    ControlNet Channel B

  • Powermonitor 3000 Master Module 9

    Powermonitor 3000 Display ModuleThe display module is an optional user-interface device. The display module provides the most economical and simplest method for setting up and configuring the master module for op

    The display module has abuttons with tactile feedbaseries of menus for config

    The display module is shiprovides power and serialdisplay module. The displmeter cutout for panel momaster module, although monitor any number of m

    Display ModulePublication 1404-IN007E-EN-P - October 2006

    eration.

    highly visible, two-line LED display and four operator ck. Use the buttons and display to navigate through a uration, commands and data display.

    pped with a 3 m (10 ft) long, shielded 4-pair cable that communication between the master module and the ay module fits into a standard ANSI four inch analog unting. Only one display module may be connected to a you may use one display module to configure and aster modules; one at a time.

  • 10 Powermonitor 3000 Master Module

    Publication 1404-IN007E-EN-P

    Catalog Number ExplanationThe Powermonitor 3000 unit has the following catalog number possibilities.

    Quick Start GuidelinThe Powermonitor 3000 ucontrol systems. Whether monitor or a component ithere are a few basic step

    1. Install your Powerm

    Refer to Install the

    140

    Bulletin Number

    1404 = Power Monitoring and Management Products

    Type o

    M4 = Master Mthree-phase msetpoints, I/O,logging.

    M5 = M4 funcfirmware upgrM6 or M8

    M6 = M5 funcoscillography, detection, harmeasurement,setpoints and firmware upgr

    M8 = M6 functransient captanalysis, harmmeasurement transducer andmodes

    (1) In addition to Native RS-485 port.- October 2006

    esnit may be used in many electric power monitoring and your power monitor is a complete power and energy n a plant- or enterprise-wide energy management system, s to follow to make your unit operational.

    onitor 3000 master module within a suitable enclosure.

    Powermonitor 3000 Unit on page 12.

    4 - M4 05 A - ENT - 02

    f Device

    odule with etering, and data

    tionality, adeable to an

    tionality plus sag/swell monics 141 additional logging, adeable to M8.

    tionality plus ure and onics up to 63rd, energy meter

    Current Inputs05 = 5 A

    Power Supply

    A = 120240V ac 5060 Hz or 125250V dcB = 24V dc

    000 = None232 = RS-232 SerialDNT = DeviceNetRIO = Remote I/OENT = EthernetCNT = ControlNet

    Communication

    Options(1)Revenue Accuracy Class

    Blank = Class 1 or Class 0.5

    02 = Class 0.2

  • Powermonitor 3000 Master Module 11

    2. Install your optional display module.

    Refer to the Bulletin 1404 Display Module Installation Instructions, publication 1404-IN005.

    3. Determine your wiand your power sy

    4. Connect control popower.

    5. If used, connect wsolid-state outputs.

    Refer to Wiring and

    6. Configure the poteto match those use

    7. Configure the Voltasystem configuratio

    8. Configure power m

    This step varies deselected.

    9. Configure the pow

    10. Configure other opdata logging.

    Refer to the Powermonitocomplete information on Publication 1404-IN007E-EN-P - October 2006

    ring mode and install wiring between the power monitor stem.

    wer wiring, preferably from a separate source of control

    iring to the status inputs, Form C control relay, and KYZ

    Connecting the Power Monitor on page 18.

    ntial transformer (PT) and current transformer (CT) ratios d in your power system connections.

    ge mode of the power monitor to match your power n.

    onitor communication.

    pending upon the communication option you have

    er monitor date and time.

    tional performance features such as setpoint control and

    r 3000 User Manual, publication 1404-UM001, for configuring and operating your power monitor.

  • 12 Powermonitor 3000 Master Module

    Publication 1404-IN007E-EN-P

    Install the Powermonitor 3000 UnitOnly qualified personnel should install, wire, service, and maintain this equipment. Refer to and follow the safety guidelines and pay attention to all warnings and notices in these instruction

    See Product Dimensions o

    Mount the master modulewashers and lock washers

    Mounting ConsideratioMount the Powermonitor Select an enclosure that prsuch as oil, water, moistursubstances. The enclosureenergized circuits.

    The ambient temperature in the Specifications, page

    Select an enclosure that pthe power monitor and ot

    See Product Dimensions opower monitor.

    When installed within a supower monitor be mounteand high-voltage circuits.

    ATTENTION ElectrostaFollow the

    Touch a

    Wear a

    Do not

    Use a s

    Keep th- October 2006

    s.

    n page 14 for mounting hole dimensions.

    with four (4) No. 8-32 UNC or M4 screws with flat .

    n3000 master module in a suitable protective enclosure. otects the master module from atmospheric contaminants e, dust corrosive vapors and other harmful airborne should also protect against personnel contact with

    within the enclosure must remain within the limits listed 57.

    rovides adequate clearance for ventilation and wiring for her equipment to be installed within the enclosure.

    n page 14 for dimensions and spacing guidelines for the

    bstation or switchgear lineup, we recommend that the d within a low-voltage cubicle, isolated from medium-

    tic discharge can damage integrated circuits or semiconductors. se guidelines when you handle the module.

    grounded object to discharge static potential.

    n approved wrist strap grounding device.

    open the module or attempt to service internal components.

    tatic safe work station, if available.

    e module in its static shield bag when not in use.

  • Powermonitor 3000 Master Module 13

    Mount the master module so that the metal grounding clips on the bottom of the mounting feet make direct contact with the enclosure mounting panel. If the mounting panel is painted, scrape or sand the paint down to bare metal. Use star washers to assure good long-term electrical contact with the mounting panel. Be sure that the mounting paground.

    Mount the enclosure in a Install the master module unobstructed to assure adcomponents.

    IMPORTANT Use cautioand otherbottom ofPublication 1404-IN007E-EN-P - October 2006

    nel is properly connected to a low-impedance earth

    position that allows full access to the master module. with the ventilation slots in the bottom and top of the unit equate free convection cooling of its internal electronic

    n not to block the ventilation slots of the master module. All wiring obstructions must be a minimum of 50 mm (2.0 in.) from the top and the unit.

  • 14 Powermonitor 3000 Master Module

    Publication 1404-IN007E-EN-P

    Product DimensionsUse the dimensions in these drawings when mounting the master module.

    Master Module Dimensions

    14.66(0.577)

    5.35(0.211)

    125.0(4.921)

    Mounting114.30(4.50)

    163.17 (6Used Wit

    Display M

    All dimensions are in mm (inches)- October 2006

    203.2 (8.000)Used With -232

    CommunicationsOptions

    Powermonitor 3000

    114.30(4.50)85.0

    (3.346)Mounting

    4.57 (0.180)4 Places

    10.43(0.411)

    135.15(5.321)

    184.15 (7.250)Used With

    Display Module.424)houtodule

    5.60(0.22)

    .

  • Powermonitor 3000 Master Module 15

    Master Module Spacing

    50.8(2.00)

    215.9 (8.50)

    215.9 (8.50)

    General Notes:

    Recommended spacing

    Maintain approximateelectrical equipment.

    Do not block cooling vefrom top and bottom o

    Mount with ventilation

    Refer to Specification

    All dimensions are in mm (inches).Publication 1404-IN007E-EN-P - October 2006

    Powermonitor 3000Powermonitor 3000

    Powermonitor 3000 Powermonitor 3000

    50.8(2.00)

    50.8 (2.00)Minimum

    50.8 (2.00)Minimum

    101.6 (4.00)

    101.6 (4.00)

    provides reasonable wiring clearance and ventilation.

    ly 102 mm (4.00 in.) clearance between master modules and other

    nts. Wiring and other obstructions must be 50 mm (2.00 in.) minimum f unit.

    opening in top and bottom to provide optimum free convection cooling.

    for amibient temperature requirements.

  • 16 Powermonitor 3000 Master Module

    Publication 1404-IN007E-EN-P

    System Accuracy ConsiderationsUser-supplied potential transformers (PTs) and current transformers (CTs), as well as wiring from the CTs to the power monitor, may reduce the accuracy of your power monitor system. Thno better than the quality responsibility to select traaccuracy.

    ANSI/IEEE C57.13, Requirof transformer accuracy: cdictate the transformer acc

    PTs and CTs may introducbandwidth errors.

    Ratio Errors

    The voltage ratio of a PT number of secondary turnslightly different than the input to the power monito

    Likewise, the current ratioof wire on the primary ancommercial grade PTs and

    Other errors include magnload, on the transformer sRatio Error. You may comConfiguration entries for P

    For a PT, the Ratio Error intotal load impedance shouincreases as the voltage sutotal load impedance, incl

    the metering device, shoularger is usually recomme- October 2006

    e quality of the power monitors measurements can be of the signals presented to its input terminals. It is your nsformers that are adequate for the desired metering

    ements for Instrument Transformers, defines three classes lass 1.2, class 0.6, and class 0.3. The application should uracy class used.

    e errors in three areas: ratio errors, phase errors, and

    is the number of primary turns of wire divided by the s. Manufacturing tolerances may cause the ratio to be design specifies, causing an error affecting the voltage r.

    of a CT is a function of the ratio of the number of turns d secondary. Some error in this ratio is quite common in CTs.

    etic core losses, winding impedance, and the burden, or econdary. The combination of these errors is known as pensate for Ratio Error, if known, by adjusting the Basic T and CT primary or secondary voltages.

    creases as the transformers load current increases, so its ld be as high as possible. Conversely, a CTs Ratio Error pported by the transformer secondary increases, so its uding the impedance of the wire connecting the CTs to

    ld be as low as possible. This is why 4 mm2 (12 AWG) or nded for wiring CTs with a 5 Amp secondary rating.

  • Powermonitor 3000 Master Module 17

    Phase Error

    Phase shift between the primary to secondary signals is another source of inaccuracy introduced by the user-supplied PTs and CTs. Phase shift is generally not of concern for simple combined, for instance wheffect of phase shift can bdifferent transformers caua 5 phase shift, there wouhand the PTs had a phasewould be a 5 phase errorfactor and reactive poweradjusting the power monitconditions of the power s

    A typical PT phase error vclass. Applying higher thasaturate the transformer a

    The phase error in a CT incurrent is greater than 80%occur when CT current is not perform well when us

    The phase error of both Pload on the secondary. Foas high as possible and CT

    Bandwidth Error

    For fundamental 50 or 60 accuracy. However, for wCTs you supply may attena flat frequency response Current transformers, espeflat response only out to 3instrument CTs are availabcannot be corrected by ad

    In addition, operation of ealso cause saturation and

    For more detailed informameasurement, refer to Bul1403-1.0.2.Publication 1404-IN007E-EN-P - October 2006

    voltage or current measurements. When these signals are en calculating line to line voltage or phase power, the

    ecome significant. The difference in phase error among ses measurement errors. If all the PTs and CTs introduced ld be no error in the measured quantities. If on the other error of 1 and the CTs had a phase error of 6, there in the power calculation. This would show up as power (VAR) errors. Phase errors cannot be corrected by or configuration since the errors change based on varying ystem.

    aries from 10.25, depending on the PTs accuracy n rated voltage increases the phase error and may nd cause even larger errors.

    creases as its current decreases, and is lowest when the of the CT rating. Because significant phase error can

    less than 20% of rated current, CTs sized for protection do ed for metering.

    Ts and CTs are also affected by the power factor of the r best accuracy, loads should be resistive, with PT loads loads as low as possible.

    Hz measurements, bandwidth error has no affect on aveforms with significant harmonic content, the PTs and uate higher harmonics. Most instrument quality PTs have out to 3 kHz, or the 50th harmonic on a 60 Hz system. cially older, existing units, tend to be less linear, with a 00 Hz, or the fifth (60 Hz) harmonic. Wide-band le for improved frequency response. Bandwidth error justing the power monitor configuration.

    ither the PTs or CTs at extremely low frequencies may resulting magnitude and phase errors.

    tion on instrument transformer accuracy and power letin 1403 Powermonitor II Tutorial, publication

  • 18 Powermonitor 3000 Master Module

    Publication 1404-IN007E-EN-P

    Wiring and Connecting the Power Monitor

    Wiring of the power mon

    Connection of volt

    Connection of cont

    Connection of statu

    Communication wi

    Follow these guidelines topower monitor.

    Install and connectwiring neatly and mmaster module ven

    Furnish and install power.

    Use 600 volt wiringrecommend the usLaboratories.

    Use a shorting termservicing connectedmodule, without de

    Use ring lugs or loprovide additional

    Pay careful attentio

    Connect the mastergrounding terminalargest current-carrgrounding wiring athe master modulemounting panel.

    Refer to Mounting

    Connect all equipmsecondary) to a sin

    ATTENTION Only qualiwire, and beginningde-energipersonal i- October 2006

    itor includes the following steps:

    age and current signals from PTs and CTs

    rol power

    s inputs and status/control outputs

    ring

    help assure reliable, trouble-free operation of your

    all wiring. Use wire tags to identify connections. Bundle aintain a minimum of 50 mm (2.0 in.) clearance from the tilation slots to avoid a buildup of heat within the unit.

    properly-selected fuses for voltage signals and control

    rated at 75 C (167 F) or higher. We strongly e of flame-retardant wire rated VW-1 by Underwriters

    inal block (you provide) for CT wiring, to permit equipment, such as the Powermonitor 3000 master -energizing the power system.

    cking spade lugs for voltage and current connections to wiring security and safety.

    n to correct phasing and polarity for proper operation.

    module to a low-impedance earth ground using its l and a dedicated grounding wire at least as large as the ying wire connected to the master module. Keep s short as possible. To obtain maximum EMI immunity, mounting feet should make electrical contact with the

    Consideration on page 12 for additional information.

    ent ground terminals (master module, PT and CT gle point, low-impedance earth ground

    fied personnel, following accepted safety procedures, should install, service the power monitor and its associated components. Before any work, disconnect all sources of power and verify that they are zed and locked out. Failure to follow these instructions may result in njury or death, property damage, or economic loss.

  • Powermonitor 3000 Master Module 19

    For information on wire sizes and types for grounding electrical equipment, refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, or the National Electric Code published by National Fire Protection Association (NFPA).

    Wiring the Master ModObserve all wire lug sizesscrew torques.

    Refer to Specifications on

    Voltage and Current InpThe following sections giv

    Voltage Input and PT Select

    The power monitor is des600 Volts line-to-line (347 use of user-supplied PTs. PT primary voltage to mat

    Connect short circuit protthe power monitor. If PTshigh-voltage side of the P

    Current Inputs and Current T

    The current input on the psignal. User-supplied CTs of the power monitor. Selof your power system.

    ATTENTION Never opeapplied. Wshorting tprimary cuopen CT swhich canPublication 1404-IN007E-EN-P - October 2006

    ule and screw torques for terminal blocks wire sizes and

    page 57.

    utse information on the selection of PTs and CTs.

    ion

    igned to connect directly to a power system rated up to Volts line-to-neutral). Higher system voltages require the Typical secondary voltage on a PT is 120V ac. Select the ch the nominal voltage of your power system.

    ection, that you supply, between the power system and are used, install short circuit protection on the Ts.

    ransformer (CT) Selection

    ower monitor is designed for a 5 Amp nominal current are required to connect your power system to the input ect the CT primary current to match the nominal current

    n a current-transformer secondary circuit with primary current iring between the CTs and the power monitor should include a

    erminal block in the CT secondary circuit. Shorting the secondary with rrent present allows other connections to be removed if needed. An

    econdary with primary current applied produces a hazardous voltage, lead to personal injury, death, property damage, or economic loss.

  • 20 Powermonitor 3000 Master Module

    Publication 1404-IN007E-EN-P

    The shorting terminal block should be located adjacent to the Powermonitor 3000 master module so that it is readily accessible should service be needed. Use

    2.5 mm2 (14 AWG) wire for the short run between the power monitor and the

    shorting terminal block. Use wiring of 4 mm2 (12 AWG) or larger between the shorting terminal block annot overload the CT and r

    Do not install fuses or oth

    Refer to System Accuracy selection.

    Refer to Technical Specificlevels and wire terminatio

    The wiring diagrams depiconfigurations. You need system configuration for c

    Refer to the Powermonitodetailed instructions on un

    IMPORTANT You may ior voltage

    Refer to thconfigurat

    Whether twiring.

    Refer to th- October 2006

    d the CT so that the additional load of the wiring does educe its accuracy.

    er overcurrent protection in the secondary circuit of a CT.

    Considerations on page 16 for guidelines on PT and CT

    ations on page 59 for information on voltage isolation n recommendations.

    ct wiring methods for a variety of power system to configure your power monitor to match the power orrect operation.

    r 3000 Unit User Manual, publication 1404-UM001, for it configuration.

    nstall either two or three CTs for any of the Delta or Open Delta wiring modes.

    e wiring diagrams on pages 28, 30, and 33 for wiring of a two CT ion.

    here are two or three CTs in a circuit does not affect the voltage

    e Powermonitor 3000 Unit User Manual, publication 1404-UM001.

  • Powermonitor 3000 Master Module 21

    Wiring Diagrams

    Single-phase Direct Connection Wiring Diagram (Systems < 600 Volts Nominal L-L)

    Load

    CustomeCT Shortin

    Test

    Fuse

    Fuse

    NL1 L2

    LinePublication 1404-IN007E-EN-P - October 2006

    CustomerChassisGround

    r Suppliedg Switch or

    Block

    Powermonitor 3000Master Module

    R14

    R11

    R12

    N/C N/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    L1(+)L2(-)

    GRD

    V1

    V2

    V3

    N

    Voltage Mode = Single Phase

    Y K ZR14 R11 R12

  • 22 Powermonitor 3000 Master Module

    Publication 1404-IN007E-EN-P

    Single-phase with PTs Wiring Diagram

    Load

    CustomeCT Shortin

    Test

    Fuse

    Fuse

    NL1 L2

    LineVoltage Mode = Single Phase- October 2006

    CustomerChassisGround

    r Suppliedg Switch or

    Block

    Powermonitor 3000Master Module

    R14

    R11

    R12

    N/C N/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    L1(+)L2(-)

    GRD

    V1

    V2

    V3

    N

    Y K ZR14 R11 R12

  • Powermonitor 3000 Master Module 23

    Three-phase Four-wire Wye Direct Connect Wiring Diagram(Systems < 600 Volts Nominal L-L)

    Load

    Customer CT Shorting

    Test B

    Fuse

    Fuse

    Fuse

    NL1 L2 L3

    LineVoltage Mode = WyePublication 1404-IN007E-EN-P - October 2006

    CustomerChassisGround

    Supplied Switch orlock

    Powermonitor 3000Master Module

    R14

    R11

    R12

    N/C N/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    L1(+)L2(-)

    GRD

    V1

    V2

    V3

    N

    Y K ZR14 R11 R12

  • 24 Powermonitor 3000 Master Module

    Publication 1404-IN007E-EN-P

    Three-phase Four-wire with PTs Wiring Diagram

    Load

    Customer CT Shorting

    Test B

    Fuse

    Fuse

    Fuse

    NL1 L2 L3

    LineVoltage Mode = Wye- October 2006

    CustomerChassisGround

    Supplied Switch orlock

    Powermonitor 3000Master Module

    R14

    R11

    R12

    N/C N/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    L1(+)L2(-)

    GRD

    V1

    V2

    V3

    N

    Y K ZR14 R11 R12

  • Powermonitor 3000 Master Module 25

    Three-phase Three-wire Grounded Wye Direct Connection Wiring Diagram (Systems < 600 Volts Nominal L-L)

    Load

    Customer CT Shorting

    Test B

    Fuse

    Fuse

    Fuse

    L1 L2 L3

    LineVoltage Mode = WyePublication 1404-IN007E-EN-P - October 2006

    CustomerChassisGround

    Supplied Switch orlock

    Powermonitor 3000Master Module

    R14

    R11

    R12

    N/C N/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    L1(+)L2(-)

    GRD

    V1

    V2

    V3

    N

    Y K ZR14 R11 R12

  • 26 Powermonitor 3000 Master Module

    Publication 1404-IN007E-EN-P

    Three-phase Three-wire Grounded Wye with PTs Wiring Diagram

    Load

    Customer SCT Shorting

    Test B

    Fuse

    Fuse

    Fuse

    L1 L2 L3

    LineVoltage Mode = Wye- October 2006

    CustomerChassisGround

    upplied Switch orlock

    Powermonitor 3000Master Module

    R14

    R11

    R12

    N/C N/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    L1(+)L2(-)

    GRD

    V1

    V2

    V3

    N

    Y K ZR14 R11 R12

  • Powermonitor 3000 Master Module 27

    Three-phase Three-wire Delta with Three PTs and Three CTs Wiring Diagram

    Load

    Customer CT Shorting

    Test B

    Fuse

    Fuse

    Fuse

    L1 L2 L3

    LineVoltage Mode = Delta 3 CTPublication 1404-IN007E-EN-P - October 2006

    CustomerChassisGround

    Supplied Switch orlock

    Powermonitor 3000Master Module

    R14

    R11

    R12

    N/C N/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    L1(+)L2(-)

    GRD

    V1

    V2

    V3

    N

    Y K ZR14 R11 R12

  • 28 Powermonitor 3000 Master Module

    Publication 1404-IN007E-EN-P

    Three-phase Three-wire Delta with Three PTs and Two CTs Wiring Diagram

    Load

    Customer CT Shorting

    Test B

    L1 L2 L3

    Line Voltage Mode = Delta 2 CT

    Fuse

    Fuse

    Fuse- October 2006

    CustomerChassisGround

    Supplied Switch orlock

    Powermonitor 3000Master Module

    R14

    R11

    R12

    N/C N/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    L1(+)L2(-)

    GRD

    V1

    V2

    V3

    N

    Y K ZR14 R11 R12

  • Powermonitor 3000 Master Module 29

    Three-phase Three-wire Open Delta with Two PTs and Three CTs Wiring Diagram

    Load

    Customer SCT Shorting

    Test B

    Fuse

    Fuse

    L1 L2 L3

    Line Voltage Mode = Open Delta 3 CTPublication 1404-IN007E-EN-P - October 2006

    CustomerChassisGround

    upplied Switch orlock

    Powermonitor 3000Master Module

    R14

    R11

    R12

    N/C N/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    L1(+)L2(-)

    GRD

    V1

    V2

    V3

    N

    Y K ZR14 R11 R12

  • 30 Powermonitor 3000 Master Module

    Publication 1404-IN007E-EN-P

    Three-phase Three-wire Open Delta with Two PTs and Two CTs Wiring Diagram

    Load

    Customer CT Shorting

    Test B

    Fuse

    Fuse

    L1 L2 L3

    Line Voltage Mode = Open Delta 2 CT- October 2006

    CustomerChassisGround

    Supplied Switch orlock

    Powermonitor 3000Master Module

    R14

    R11

    R12

    N/C N/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    L1(+)L2(-)

    GRD

    V1

    V2

    V3

    N

    Y K ZR14 R11 R12

  • Powermonitor 3000 Master Module 31

    Three-phase Three-wire Grounded L2(B) Phase Open Delta Direct Connect with Three CTs Wiring Diagram(Systems < 600 Volts Nominal L-L)

    Load

    CustomCT Shor

    Tes

    F

    F

    L1 L3

    Line Voltage Mode = Open Delta 3 CT

    DistributionGround

    Voltaexceed(otherw

    transformPublication 1404-IN007E-EN-P - October 2006

    CustomerChassisGround

    er Suppliedting Switch ort Block

    Powermonitor 3000MasterModule

    R14

    R11

    R12

    N/C N/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    L1(+)L2(-)

    GRD

    V1

    V2

    V3

    N

    use

    use

    Y K ZR14 R11 R12

    ge must not 347 Volts L-Lise, step downers are required).

  • 32 Powermonitor 3000 Master Module

    Publication 1404-IN007E-EN-P

    Three-phase Three-wire Delta Direct Connect with Three CTs Wiring Diagram (Systems < 600 Volts Nominal L-L)

    Load

    Customer CT Shorting

    Test B

    Fuse

    Fuse

    Fuse

    L1 L2 L3

    Line Voltage Mode = Direct Delta 3 CT- October 2006

    CustomerChassisGround

    Supplied Switch orlock

    Powermonitor 3000MasterModule

    R14

    R11

    R12

    N/C N/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    L1(+)L2(-)

    GRD

    V1

    V2

    V3

    N

    Y K ZR14 R11 R12

  • Powermonitor 3000 Master Module 33

    Three-phase Three-wire Delta Direct Connect with Two CTs Wiring Diagram(Systems < 600 Volts Nominal L-L)

    Load

    Customer SCT Shorting S

    Test Blo

    Fuse

    Fuse

    Fuse

    L1 L2 L3

    LineVoltage Mode = Direct Delta 2 CTPublication 1404-IN007E-EN-P - October 2006

    CustomerChassisGround

    uppliedwitch orck

    Powermonitor 3000MasterModule

    R14

    R11

    R12

    N/C N/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    L1(+)L2(-)

    GRD

    V1

    V2

    V3

    N

    Y K ZR14 R11 R12

  • 34 Powermonitor 3000 Master Module

    Publication 1404-IN007E-EN-P

    Control PowerThe power monitor draws a nominal 15V A control power. Catalog numbers 1404-MxxxA-xxx require nominal control power of 120240V ac or 125250V dc. The power supply is self-snominal control power of

    Control Power

    Refer to Specifications on termination information.

    It is strongly recommend power system being moniis critical, consider the usethe power monitor continsignificant sags, swells, an

    It is required to connect ydisconnecting means and

    Status Inputs

    ATTENTIONDo not apinternal somay dama- October 2006

    caling. Catalog number 1404-MxxxB-xxx requires 24V dc.

    page 57 for acceptable control voltage ranges and wiring

    that you use a separate source of control power from the tored. For applications where power system information of a user-supplied uninterruptible power supply so that ues to operate during power system events such as d transient disturbances.

    our power-monitor control power through user-supplied overcurrent protection.

    ply an external voltage to a Status Input. These inputs have an urce and are intended for dry contact input only. Applying a voltage ge the associated input or internal power supply.

    L1

    N/L2

    LocalFrameGround

    Powermonitor 3000Master Module

    R14

    R11

    R12

    N/CN/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    R14 R11 R12 Y K Z

    L1(+)L2(-)

    GRD

    V1

    S1

    S2

    SCOM

    V2

    V3

    N

    DISPLAYMODULE

    SHLD

    RS-485

  • Powermonitor 3000 Master Module 35

    All Status Inputs are common to an internal 24V dc source on the SCOM terminal. Status input terminals S1 and S2 are positive polarity and SCOM is negative polarity.

    For optimal EMC performance, we recommend wiring the status inputs using shielded cable, Belden 8771 or equivalent, with the cable shield grounded at both ends where possible.

    Status Input Connections

    Isolation Voltage 500V stacircuitry.

    Relay and KYZ OutputsControl Relay Connectionand an example of customR11 is the common connenormally-closed connectioprotection for the circuit c

    Refer to Specifications on

    Parameter

    Applied resistance verses status

    TIP Status InpPowermoninformatioPublication 1404-IN007E-EN-P - October 2006

    tus input to case; 500V status input to internal digital

    s on page 36 shows the Form C relay output connections er wiring to a supply voltage and two loads. Terminal

    ction, R14 is the normally-open connection and R12 is the n. You must supply the wetting voltage and overcurrent onnected to the relay output.

    page 57 for further information.

    Condition 1 Condition 2

    state 3.5 k or less = ON 5.5 k or greater = Off

    ut S2 can be configured for external demand pulse input. See itor 3000 User Manual, publication 1404-UM001, for more n.

    Powermonitor 3000Master Module

    -

    +

    R14

    R11

    R12

    N/CN/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    R14 R11 R12 Y K Z

    L1(+)L2(-)

    GRD

    V1

    S1

    S2SCOM

    V2

    V3

    N

    DISPLAYMODULE

    SHLD

    RS-485

    N.O.Contact

    N.O.Contact

  • 36 Powermonitor 3000 Master Module

    Publication 1404-IN007E-EN-P

    The KYZ output is a solid-state relay designed for low-current switching and long life. Its normal application is to provide a pulse based on energy usage (or one of five other parameters) to an external pulse accumulator. Terminal K is common, Y is normally-open, and Z is normally-closed.

    Refer to Powermonitor 30information on the applic

    Control Relay Connection

    Communication WiringMethods for connecting cosection provides guidelineyour power monitor syste

    ATTENTION You must high grounwith a unimay lead

    IMPORTANT You need

    Refer to thfor detaile- October 2006

    00 Unit User Manual, publication 1404-UM001, for further ation and operation of relay and KYZ outputs.

    s

    mmunication wiring vary from option to option. This s for installing dependable communication wiring for m.

    supply and install special high-level isolation when the possibility of d potential differences exists. This may occur when communicating

    t connected to a power ground mat. Failure to install such isolation to personal injury or death, property damage, or economic loss.

    to configure communication for each communication option.

    e Powermonitor 3000 Unit User Manual, publication 1404-UM001, d communication configuration instructions.

    10AFuse

    L1 N Powermonitor 3000Master Module

    -

    +

    R14

    R11

    R12

    N/CN/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    R14 R11 R12 Y K Z

    L1(+)L2(-)

    GRD

    V1

    S1

    S2SCOM

    V2

    V3

    N

    DISPLAYMODULE

    SHLD

    RS-485

  • Powermonitor 3000 Master Module 37

    Native RS-485 Communication Wiring

    The RS-485 communication standard supports multi-drop communication among as many as 32 stations or nodes.

    The RS-485 port is also us

    RS-485 communication wiWe recommend that you uequivalent. The maximumtopology is not recommenis matched for each spur (

    If required, install suitableFor RS-485, install a 150 diagram). Note that some terminating resistors. Continformation.

    At one end of each cable sthe master module RS-485low-impedance ground foline-frequency signals.

    The RS-485 port in the maRS-485 network, allowing

    Configuration options for address, and the data rate

    auto-detect protoco

    device address = th

    communication rat

    Use of RS-232 to RS-485 Co

    You need a user-suppliedthe power monitor native programmable controller

    B&B Electronics, In

    Allen-Bradley catalPublication 1404-IN007E-EN-P - October 2006

    ed for master module firmware upgrades in the field.

    ring should be installed in a daisy-chain configuration. se Belden 9841 two-conductor shielded cable or cable length is 1219 m (4000 ft). Use of a star or bridging ded and will result in signal distortion unless impedance star topology) or network (bridge topology).

    terminating resistors at the ends of the daisy-chain cable. , 1/4 Watt terminating resistor (refer to the wiring RS-485 conversion devices are equipped with internal act the manufacturer of the converter for additional

    egment, connect the cable shield to the SHLD terminal of port or the converter. The SHLD connection provides a r high-frequency noise while attenuating dc or

    ster module presents a standard load impedance to the the standard 32 nodes on a network.

    the native RS-485 port include the protocol, device . Defaults are:

    l.

    e Device ID assigned at the factory in the range 1254.

    e = 9600 bps.

    nverter

    RS-232 to RS-485 converter for communication between RS-485 port and an external device such as a computer or RS-232 port. Examples include:

    c. part number 485SD9TB (DB-9 connection).

    og number 1761-NET-AIC.

  • 38 Powermonitor 3000 Master Module

    Publication 1404-IN007E-EN-P

    RS-485 Connections

    Shield Connection (See Note 4)

    IBM Compatible PC

    OrPLC Processor

    OrSLC Processor

    OrControlLogix Processor

    Notes:1) 3-device network portrayed. Up to 31 DF1 Slave Devices can be connected to a DF1 Master without the use of a repeater2) Terminating resistors may be required for networks with long distances or high noise environments. Consult the RS-232 to RS-485 converter manufacturer for more information.3) Examples: B & B Electronics Part Number 485SD9TB (DB9). Allen-Bradley Cat. 1761-NET-AIC.4) Shields should be connected at one end only to avoid ground loops.

    External SHLD- October 2006

    150Terminating

    Resistor(See Note 2)

    150Terminating

    Resistor(See Note 2)

    Powermonitor 3000 Device #1

    Powermonitor 3000 Device #2

    Powermonitor 3000 Device #3 (Last)

    RS-485

    RS-485

    RS-485

    RS-232C to RS-485Converter

    (See Note 3)

    SHLD

    _

    +

    SHLD

    _

    +

    SHLD

    _

    +

    A

    B

  • Powermonitor 3000 Master Module 39

    Optional RS-232 Communication

    Powermonitor 3000 units with a catalog number ending in -232 are equipped with an RS-232 serial communication port in addition to the native RS-485 port. The RS-232 communication statwo stations or nodes. Younative RS-485 communica

    The optional RS-232 commequipment (DCE) type deconnect with personal comdata terminal equipment (to a modem or other DCE

    The maximum cable lengtdiagrams for cable pinoutand/or DB-25 connectors.

    Connecting Powermonito

    Powermo

    Or PLC Processor

    Or SLC Processor

    Or ControlLogix Processor

    IBM CompatiblePCPublication 1404-IN007E-EN-P - October 2006

    ndard supports point-to-point communication among must select either optional RS-232 communication or

    tion. The two ports do not operate at the same time.

    unication port is a data communication vice. It requires a straight-through RS-232 cable to puters, programmable controller serial ports, and other

    DTE) devices. It requires a crossover cable for connection devices. No terminating resistor is required.

    h is 15.24 m (50.0 ft). Refer to the following wiring information for constructing your own cable using DB-9

    r 3000 Unit to Computer Communication Port

    nitor 3000

    5

    9 6

    1

    2

    1

    3

    4

    7

    8

    9

    6

    5

    TXD

    no connect

    no connect

    no connect

    RXD

    RTS (See Note 1)

    CTS (See Note 1)

    DSR (See Note 2)

    GND

    3

    2

    4

    5

    7

    3

    2 2

    3

    8

    7 7

    8

    55

    TXD

    RXD

    CTS (See Note 1)

    RTS (See Note 1)

    GND

    TXD

    RXD

    RTS (See Note 1)

    CTS (See Note 1)

    GND

    DB9 Female

    13

    25 14

    1

    DB-25 Female

    5

    9 6

    1

    DB9 Female

    5

    9 6

    1

    DB9 Female

    Powermonitor 3000 IBM PC IBM PC -

    Notes:1) Required only if you have

    enabled hardware handshaking.2) Internally pulled active in this DCE

    device - function not supported.3) Straight-through RS-232 cable required.

    RS-232

    output

    input

    ground

    output

    input

    output

    (See Note 3)

    SLC 500 Ch 0 PLC-5 Ch 0 - DB-25 Male

  • 40 Powermonitor 3000 Master Module

    Publication 1404-IN007E-EN-P

    Optional Remote I/O Communication

    Powermonitor 3000 units with a catalog number ending in -RIO are equipped with a remote I/O port in addition to the native RS-485 port. Allen-Bradley remote I/O is a robust, widely used induphysical media. The poweboth polled I/O and blocknative RS-485 port may bemay be reduced.

    Remote I/O communicatioconfiguration. We recommequivalent. The maximumRates table and varies withrecommended and will reeach spur (star topology)

    Be sure that all devices ondesired communication racommunication rate.

    Install suitable terminating

    At each end of each cableof the remote I/O port conground for high-frequencyrecommend that you folloI/O to differentiate it from

    Remote I/O Communicati

    Communication Rate

    57.6 Kbps

    115.2 Kbps

    230.4 Kbps

    TIP Some reresistors- October 2006

    strial data network that uses twinaxial cable as its r monitor emulates a logical quarter rack and supports transfer communication. The remote I/O port and the used simultaneously, although overall data throughput

    n wiring should be installed in a daisy-chain end that you use Belden 9463 twinaxial cable or cable length is shown in the Remote I/O Communication the data rate. Use of a star or bridging topology is not

    sult in signal distortion unless impendance is matched for or network (bridge topology).

    your remote I/O network are capable of operation at the te. Certain legacy devices may not support a 230.4 Kbps

    resistors at the ends of the remote I/O network.

    segment, connect the cable shields to the SHLD terminal nector. The SHLD connection provides a low-impedance noise while attenuating dc or line-frequency signals. We w the standard blue/shield/clear color scheme for remote Data Highway Plus (clear/shield/blue) cables.

    on Rates

    Maximum Distance Terminating Resistor

    3048 m (10,000 ft) 150 , 1/4 W

    1542 m (5000 ft) 150 , 1/4 W

    762 m (2500 ft) 84 , 1/4 W

    mote I/O devices are equipped with internal terminating .

  • Powermonitor 3000 Master Module 41

    Configuration options for optional remote I/O communication include the logical rack address and module group (the power monitor is always one-quarter rack), and data rate. Defaults are rack 1, group 0, 57.6 Kbps.

    Refer to the Powermonitor 3000 Unit User Manual, publication 1404-UM001.

    Refer to the note at the be

    Connecting PowermonitoIBM CompatiblePC With R I/OInterface Card

    Or

    PLC Processor/PLC R I/O Scanner

    Or

    Or

    SLC R I/O Scanner

    ControlLogix R I/O Scanner

    Notes:1) 3-Device Network portraye

    Up to 32 slave devices canbe connected per masterR I/O channel.

    2) Terminating Resistorsmust be connectedto each end of theR I/O network. Omit theterminating resistor(s)if the device(s) alreadyare equipped with internalterminating resistors.Publication 1404-IN007E-EN-P - October 2006

    ginning of Communication Wiring on page 38.

    r 3000 Unit to Remote I/O Scanner

    2

    SHLD

    1

    2

    SHLD

    1

    2

    SHLD

    1

    2

    SHLD

    1

    82 ohmTerminating

    Resistor(See Note 2)

    82 ohmTerminating

    Resistor(See Note 2)

    BlueShield

    Clear

    d.

    R I/O

    Powermonitor 3000 Device #3 (Last)

    R I/O

    Powermonitor 3000 Device #2

    R I/O

    Powermonitor 3000 Device #1

  • 42 Powermonitor 3000 Master Module

    Publication 1404-IN007E-EN-P

    Optional DeviceNet Communication

    Powermonitor 3000 units with a catalog number ending in -DNT are equipped with a DeviceNet port in addition to the native RS-485 port. The DeviceNet network is an open-standard, multi-vof physical media. The Deconnected to the networkused simultaneously, altho

    For detailed DeviceNet syplacement of terminating refer to DeviceNet Cable SDN-6.7.2.

    Refer to the note at the be

    Install suitable terminating

    Configuration options for address (MAC ID) and dat

    Refer to the Powermonito

    TIP Some Dev

    IMPORTANT You must conductor100 mA fr

    DeviceNet Terminal Bloc

    Terminal Signa

    1 COM (

    2 CAN_

    3 SHIEL

    4 CAN_

    5 VDC+ - October 2006

    endor, industrial device data network that uses a variety viceNet network also provides 24V dc power to devices . The DeviceNet port and the native RS-485 port may be ugh overall data throughput may be reduced.

    stem installation information, including cable lengths, the resistors, power supplies, and other media components, ystem Planning and Installation Manual, publication

    ginning of Communication Wiring on page 36.

    resistors at the ends of the DeviceNet cable.

    optional DeviceNet communication include the node a rate. Defaults are node 63 and 125 Kbps.

    r 3000 Unit User Manual, publication 1404-UM001.

    iceNet devices are equipped with internal terminating resistors.

    install and wire a suitable 24V dc power supply to the V+ and V- s in the DeviceNet cable. The power monitor consumes less than om the DeviceNet 24V dc supply.

    k Wiring Connections

    l Function Color

    V-) Common Black

    L Signal Low Blue

    D Shield Uninsulated

    H Signal High White

    (V+) Power Supply Red

  • Powermonitor 3000 Master Module 43

    Connecting Powermonitor 3000 to other DeviceNet Devices

    Optional Ethernet Communi

    Powermonitor 3000 units an industry standard Ethe

    The power monitor is desiand switches using standaconnectors. The Ethernet pin assignments and Powtypical star network topol

    121 ohmTerminating

    Resistor

    IBM Compatible PC With1784 PCDPCMCIA Interface

    Or1770-KFD Interface Box

    OrPLC With

    1771-SDN Scanner

    OrSLC With

    1747-SDN Scanner

    Powermonitor 3000 Device

    V-

    CAN_L

    SHLD

    Or other DeviceNet scanner devicesPublication 1404-IN007E-EN-P - October 2006

    cation

    with catalog numbers ending in -ENT are equipped with rnet 10/100baseT port.

    gned to connect easily to industry-standard Ethernet hubs rd UTP (unshielded twisted-pair) cables with RJ-45 Wiring Connections table shows the cable and connector ermonitor 3000 Ethernet Network Example shows a ogy.

    (See Note 2)

    121 ohmTerminating

    Resistor(See Note 2)

    Card

    Notes:1) Example network protrayed.

    For detailed DeviceNetinstallations, includingcable requirements, refer toPublication DN-6.7.2.

    2) Terminating Resistorsmust be connectedto each end of theDeviceNet network. Omit theterminating resistor(s)if the device(s) alreadyare equipped with internalterminating resistors.

    V+

    CAN_H

    V-

    V+

    CAN_L

    SHLD

    CAN_H

    V-

    V+

    CAN_L

    SHLD

    CAN_H

    V-

    V+

    CAN_L

    SHLD

    CAN_H

    +

    -

    DeviceNet24V dc

    Power Supply

  • 44 Powermonitor 3000 Master Module

    Publication 1404-IN007E-EN-P

    Powermonitor 3000 Ether

    Ethernet Wiring Connections

    Terminal Signal

    1 TX+

    2 TX-

    3 RX+

    4

    5

    6 RX-

    7

    8

    LAN

    Powermonitor 3000Master Module #1

    Powermonitor 3000Master Module #2

    PRR- October 2006

    net Network Example

    Function

    TX+

    TX-

    RX+

    RX-

    Ethernet Switch

    C w/RSLinx and SPower 32 orSEnergyMetrix

    PLC 5 Controller

    ControlLogix Controller

    SLC 500 Controller

  • Powermonitor 3000 Master Module 45

    Refer to the note at the beginning of Communication Wiring on page 36.

    Configuration options for optional Ethernet communication include the IP (Internet Protocol) address, subnet mask, default gateway IP address, and protocol.

    Defaults are:

    IP address: 192.168factory in the range

    subnet mask: 255.2

    default gateway IP

    protocol: CSP (PCC

    Optional ControlNet Commu

    Powermonitor 3000 units a ControlNet communicatconnected in a single medControlNet network using

    Powermonitor 3000 Unit C

    17(in

    Redundant Media(optional)Publication 1404-IN007E-EN-P - October 2006

    .254.xxx where xxx is the Device ID assigned at the 1247.

    55.0.0.

    address: 128.1.1.1.

    C) and CIP (EtherNet/IP).

    nication

    with catalog numbers ending in -CNT are equipped with ion interface. The ControlNet power monitor can be ia or redundant media network. An example of a redundant media is shown here.

    ontrolNet Network Example

    56-CNBR 1756-A4 chassis)

    ControlNetNode

    ControlNet Link

    ControlNetNode

    Powermonitor 3000 Device

    Powermonitor 3000 Device

  • 46 Powermonitor 3000 Master Module

    Publication 1404-IN007E-EN-P

    Refer to the following documentation for ControlNet network wiring requirements and general ControlNet information.

    ControlNet Cable System Planning and Installation Manual, publication 1786-6.2.1

    ControlNet Coax T

    ControlNet Coax MCNET-IN002

    Connecting a Programming

    To connect a programminhave the following option

    Using a 1784-KTC, 1786-CP cable

    Using a 1770-KFC cand a 1786-CP cab

    1Powermonitor 3000 Device

    Powermonitor 3000 Device - October 2006

    ap Installation Instructions, publication 1786-IN007

    edia Planning and Installation Guide, publication

    Terminal to the Network Using a 1786-CP Cable

    g terminal to the network using a 1786-CP cable, you s:

    1784-KTCx, or 1784-PCC communication card and a

    ommunication interface, a serial or parallel connection, le

    786-CP Cable1784-KTC, KTCx,PCIC, or PCC Card

    ControlNet Link

    1786-CP

    ControlNet Link

    Cable

    1770-KFC

    Serial or ParallelConnections

  • Powermonitor 3000 Master Module 47

    The 1786-CP cable can be plugged into any ControlNet products NAP to provide programming capability on the ControlNet network. A programming terminal connected through this cable is counted as a node and must have a unique network address.

    Interpret the LED IndThe power monitor is equindicators.

    The three LED indicators monitor modules with anycommunication only. Theand different indications dshown in the charts below

    Powermonitor 3000 LED I

    ATTENTIONUse a 178through Nnetwork f

    Powermonitor 3000Publication 1404-IN007E-EN-P - October 2006

    icatorsipped with six bi-color light emitting diode (LED)

    on the left display the same information on power communication option including native RS-485

    three LED indicators on the right have different labels epending on the communication option selected, as .

    ndicators

    6-CP cable when connecting a programming terminal to the network APs. Using a commercially available RJ-style cable could result in ailure.

    RX

    TXRS-485

    MODULE STATUS

  • 48 Powermonitor 3000 Master Module

    Publication 1404-IN007E-EN-P

    RS-485 LED Indicators

    All Powermonitor 3000 Models LED Indicators

    LED Indicator

    Module Status

    RS-485 RX

    RS-485 TX

    Native RS-485 Communic

    LED Indicator

    F1

    F2

    F3

    Powermonitor 3000

    F1

    F2

    F3- October 2006

    LED Indicator Color LED Indicator State and Communication Condition

    Off Control power is off or insufficient.

    Steady Red Major fault; internal self-test has failed. If a power cycle does not correct the problem, call customer support.

    Steady Green Power monitor is operating normally.

    Off The RS-485 bus is idle; no active data is present.

    Flashing Green Active data is present on the RS-485 bus.

    Off Power monitor is not transmitting data onto the RS-485 bus.

    Flashing Green Power monitor is transmitting data onto the RS-485 bus.

    ation Only (catalog numbers ending in -000)

    LED Indicator Color LED Indicator State and Communication Condition

    Off Not used.

    Off Not used.

    Off Not used.

  • Powermonitor 3000 Master Module 49

    RS-232 LED Indicators

    Remote I/O LED Indicator

    RS-232 Optional Commun

    LED Indicator

    F1

    RS-232 RX

    RS-232 TX

    Remote I/O Optional Com

    LED Indicator

    F1

    F2

    Powermonitor 3000

    F1

    RX

    TX}RS-2

    Powermonitor 3000

    F1

    F2

    R I/OPublication 1404-IN007E-EN-P - October 2006

    s

    ication (catalog numbers ending in -232)

    LED Indicator Color LED Indicator State and Communication Condition

    Off Not used.

    Off The RS-232 bus is idle; no active data is present.

    Flashing Green Power monitor is receiving data.

    Off The power monitor is not transmitting any data onto the RS-232 bus.

    Flashing Green The power monitor is transmitting data.

    munication (catalog numbers ending in -RIO)

    LED Indicator Color LED Indicator State and Communication Condition

    Off Not used.

    Off Not used.

    32

  • 50 Powermonitor 3000 Master Module

    Publication 1404-IN007E-EN-P

    DeviceNet LED Indicator

    R I/O

    DeviceNet Optional Com

    LED Indicator

    F1

    F2

    Network Status

    Remote I/O Optional Communication (catalog numbers ending in -RIO)

    LED Indicator LED Indicator Color LED Indicator State and Communication Condition

    Powermonitor 3000wermonitor 3000

    F1

    F2

    NETWORSTATUS- October 2006

    s

    Off Remote I/O communication has not been established.

    Flashing Green Remote I/O communication has been established but there are errors.

    Steady Green Remote I/O communication has been established.

    munication (catalog numbers ending in -DNT)

    LED Indicator Color LED Indicator State and Communication Condition

    Off Not used.

    Off Not used.

    Off Power is off or the power monitor is not online.

    Flashing Green Network status is OK, no connections established.

    Steady Green Network status is OK, connections established.

    Flashing Red Recoverable communication failure; port is restarting.

    Steady Red Nonrecoverable communication error; check wiring and configuration parameters.

    K

  • Powermonitor 3000 Master Module 51

    EtherNet/IP LED Indicators

    EtherNet/IP Optional Com

    LED Indicator

    LNK

    ACT

    F1

    F2

    Network Status

    F1

    LNK

    ACT

    F2

    NETWORSTATUS

    Powermonitor 3000Publication 1404-IN007E-EN-P - October 2006

    munication (catalog numbers ending in -ENT)

    LED Indicator Color LED Indicator State and Communication Condition

    Off No valid physical EtherNet connection.

    Steady Green Valid physical EtherNet connection.

    Strobing or Solid Yellow Power monitor transmitting onto the EtherNet/IP network.

    Off Not used.

    Off Not used.

    Off No power.

    Flashing Green No established connections.

    Steady Green Connected; has at least one established connection.

    Flashing Red Connection timeout; one or more connections to this device has timed-out.

    Steady Red Duplicate IP; the IP address assigned to this device is already in use.

    Flashing Green/Red Selftest; this device is performing a power-up self-test.

    K

  • 52 Powermonitor 3000 Master Module

    Publication 1404-IN007E-EN-P

    ControlNet LED Indicators

    ControlNet Optional Com

    LED Indicator

    Chan A and Chan B

    Status

    CHAN A

    CHAN B

    NETWORSTATUS

    Powermonitor 3000- October 2006

    munication (catalog numbers ending in -ENT)

    LED Indicator Color LED Indicator State and Communication Condition

    Off No power or channel disabled.

    Steady Red Faulted unit.

    Alternating Red/Green Self-test.

    Alternating Red/Off Incorrect node configuration.

    Steady Green Normal operation.

    Flashing Green/Off Temporary errors or node is not configured to go online.

    Flashing Red/Off Media fault or no other nodes present on network.

    Flashing Red/Green Incorrect network configuration.

    Off Normal operation.

    Flashing Green Communication card power-up self-test.

    K

  • Powermonitor 3000 Master Module 53

    Access Self-test and Diagnostic Data

    You can access valuable diagnostic information using the optional display module.

    1. Connect the displacable.

    2. Using the four conand select using th

    The display modularrow keys to step

    Display Des

    The

    Disp

    The optio

    Disp

    Show

    ShowusedEthe

    Dispprob

    Indic

    Indic

    Indic

    Indic

    Indic

    Indic

    Indic

    Disp

    Disp

    DispnormPublication 1404-IN007E-EN-P - October 2006

    y module to the master module using the display module

    trol keys, navigate through the menus to Display - Status e Enter key.

    e then displays the following data. Use the up and down through the status data.

    cription

    unit catalog number and series revision letter.

    lays the revenue meter accuracy class.

    units unique Warranty Identification Number (needed for service and nal firmware enhancements).

    lays details of the digital board, analog board, and ASIC revisions.

    s the master module firmware revision.

    s the units device ID number assigned at the factory. This number is also in the default address for native RS-485, and optional RS-232 and rNet/IP communication.

    lays a status code bitfield as a hex number. A non-zero value indicates a lem.

    ates the health of the flash memory code area.

    ates the health of the random access memory.

    ates the health of the flash memory data area.

    ates the health of the super-cap backed non volatile random access memory.

    ates the data acquisition system health.

    ates the system watchdog timer status.

    ates the health of the real-time clock.

    lays the firmware revision of the optional communication card (if applicable).

    lays the optional communication card type.

    lays the optional communication status bitfield as a hex number (0000 hex is al for -232 and -RIO units, and 9001 hex is normal for -DNT and -ENT units).

  • 54 Powermonitor 3000 Master Module

    Publication 1404-IN007E-EN-P

    Refer to the Powermonitoinformation on using the

    CalibrationTo meet general operating

    For special customer requrepresentative for calibrati

    Displays the display module status bitfield as a hex number. A non-zero value may indicate a problem, although a non-zero value may appear if a display module is connected to an operating master module.

    Indic

    Disp

    Disp

    Show

    Show

    Show

    Sho

    Show

    Show

    Disp

    Display Description- October 2006

    r 3000 Unit User Manual, publication 1404-UM001, for display module.

    requirements, regular recalibration is not necessary.

    irements, contact your local Rockwell Automation on or service information.

    ates the display module firmware revision.

    lays the current date.

    lays the current time.

    s the status of the Form 4C relay.

    s the status of the KYZ output.

    s the status of Status Input 1.

    ws the accumulated value of Status Input 1 counter, since last cleared.

    s the status of Status Input 2, since last cleared.

    s the accumulated value of Status Input 2 counter.

    lays the output word bitfield as a hex number.

  • Powermonitor 3000 Master Module 55

    Cleaning Instructions

    1. Turn off all electric

    2. Clean the master m

    a. Remove all dusupper, lower, an

    b. Be sure that the

    3. Clean the display m

    a. Remove all dus

    b. Be sure that theclean and in go

    ATTENTION Electrostatic discharge can damage integrated circuits or semiconductors. Follow the

    Touch a

    Wear a

    Do not

    Use a s

    Keep th

    DisconnsecondpersonaPublication 1404-IN007E-EN-P - October 2006

    al power supplied to the master module.

    odule with a dry, anti-static, lint-free cloth.

    t and any obstructions from the cooling air vents on the d ends of the module.

    nameplate is clean and in good condition.

    odule with a dry, anti-static, lint-free cloth.

    t and foreign materials from the exterior of the module.

    graphic front panel overlay and back nameplate are od condition.

    se guidelines when you handle the module.

    grounded object to discharge static potential.

    n approved wrist strap grounding device.

    open the module or attempt to service internal components.

    tatic safe work station, if available.

    e module in its static shield bag when not in use.

    ect and lock out all power sources and short all current transformer aries before servicing. Failure to comply with these precautions can lead to l injury or death, property damage, or economic loss.

  • 56 Powermonitor 3000 Master Module

    Publication 1404-IN007E-EN-P

    Field Service ConsiderationsIf the power monitor requires servicing, please contact your nearest Rockwell Automation sales office. To minimize your inconvenience, the initial installation should be performed in a

    A CT shorting blocmaster-module curuser-supplied CTs prevent any effect

    All wiring should bpower monitor term

    Firmware UpgradesPower monitor firmware uoccur from time-to-time toare optional firmware enhmaster module to an M6 o

    Service upgrades may be Automation representativehttp://www.ab.com/PEMS

    Product upgrades are avairepresentative for addition

    Master module firmware uRS-485 communication poremoving the power monrequired to connect betwecommunication port. Cyclcomplete the firmware up

    ATTENTION Never opeapplied. Wshorting tprimary cuopen CT swhich can- October 2006

    manner that makes removal easy.

    k should be provided to allow the Powermonitor 3000 rent inputs to be disconnected without making the an open circuit. The shorting block should be wired to on the external protective relays.

    e routed to allow easy maintenance at connections to the inal strips and the power monitor itself.

    pgrades are of two types. Service upgrades are those that improve operation and resolve issues. Product upgrades ancements that you may purchase to convert your M5 r M8, or your M6 to an M8.

    available at no charge. Contact your local Rockwell for information or visit the Internet at .

    lable for purchase. Contact your Rockwell Automation al information.

    pgrades (of either type) are performed using the native rt. Firmware upgrades may be performed without itor from its installation. An RS-485 to RS-232 converter is en the power monitor and your personal computer ing power to the power monitor may be required to grade.

    n a current transformer (CT) secondary circuit with primary current iring between the CTs and the power monitor should include a

    erminal block in the CT secondary circuit. Shorting the secondary with rrent present allows other connections to be removed, if needed. An

    econdary with primary current applied produces a hazardous voltage, lead to personal injury, death, property damage, or economic loss.

  • Powermonitor 3000 Master Module 57

    Factory-installed Communication CardsThe RS-485 communication is integral to the master module and cannot be removed. Adding or changing a second communication card to a power monitor must be done at the facto

    Specifications

    Measurement Accuracy Powermonitor 3000 Mast

    Parameter Accuracy inPower Faca

    1404-M4

    Voltage sense inputs: V1, V2, V3

    0.2%

    Current sense input: I1, I2, I3, I4

    0.2%

    Frequency 0.05 Hz

    Power functions: kW, kVA, kVARDemand functions: kW, kVAEnergy functions: kWH, kVAH

    ANSI C12.16andEN 61036 Cla1 Accuracy

    Metering update rates

    6590 msPublication 1404-IN007E-EN-P - October 2006

    ry and is not field upgradeable.

    and Rangeer Module - 1404-M4, 1404-M5, 1404-M6, 1404-M8

    % of Full Scale at 25 C (77 F) 50/60 Hz Unity tor

    Nominal/Range

    1404-M5 1404-M6 1404-M8

    0.05% 0.05% 0.05% 347V/15399V L-N rms 600V/26691V L-L rms

    0.05% 0.05% 0.05% 5 A/50 mA10.6 A rms

    0.05 Hz 0.05 Hz 0.05 Hz 50 or 60 Hz/4075 Hz

    ss

    ANSI C12.20 andEN 60687 Class 0.5 Accuracy (Class 0.2 is also available)

    ANSI C12.20 andEN 60687 Class 0.5 Accuracy (Class 0.2 is also available)

    ANSI C12.20 andEN 60687 Class 0.5 Accuracy (Class 0.2 is also available)

    5580 ms 5585 ms 50100 ms

  • 58 Powermonitor 3000 Master Module

    Publication 1404-IN007E-EN-P

    Input and Output Ratings

    Attribute

    Control power 1404-xxxxA-xxx

    Control power 1404-xxxxB-xxx

    Voltage sense inputs: V1, V2, V3

    Current sense inputs: I1, I2, I3, I4

    Status inputs

    Control relayKYZ output

    Control Relay(1)

    (1) Meets ANSI/IEEE C37.90-1989 sta

    Rating

    Max resistive load switching

    Min load switching

    UL 508, CSA 22.2, IEC Rating Clas

    Max make values (inductive load)

    Max break values (Inductive Load

    Max motor load switching- October 2006

    Value

    102264V ac 4763 Hz or106275V dc(0.2 A max loading)

    1850V dc (15V A max loading)

    Input impedance: 1 M min, 399V ac max; V1, V2 and V3 to N.

    Overload withstand: 15 A continuous, 200 A for 1 s Burden: 0.05V AImpedance: 0.002 Max crest factor at 5 A is 3Starting current: 5 mA

    Contact closure (internal 24V dc)

    (1) ANSI C37.90-1989 trip duty(1) Solid State KYZ - 80 mA at 240300V dc

    ndards for trip duty.

    50/60 Hz AC rms DC

    10 A at 250V(2500V A)

    10 A at 30V and 0.25 A at 250V

    10 mA at 24V 10 mA at 24V

    s B300 Q300

    30 A at 120V15 A at 240V(3600V A)

    0.55 A at 125V0.27 A at 250V(69V A)

    ) 3 A at 120V1.5 A at 240V(360V A)

    0.55 A at 125V0.27 A at 250V(69V A)

    1/3 HP at 125V1/2 HP at 250V

  • Powermonitor 3000 Master Module 59

    Input and Output Ratings(1)

    (1) Meets ANSI/IEEE C37.90-1989 sta

    Attribute Number of Operations

    Mechanical

    Electrical

    General Specifications

    Attribute

    Dielectric withstand

    Terminal blocks

    (1) Recommended Ring lug: AMP part

    Temperature, operating

    Temperature,storage

    Humidity

    Vibration

    ShockPublication 1404-IN007E-EN-P - October 2006

    ndards for trip duty.

    5 x 106

    1 x 105

    Value

    Control power 2000V

    Voltage inputs 2000V

    Current inputs 2000V

    Status inputs 500V

    Control relays 1600V

    Power supply and voltage input terminals

    4 mm2 (12 AWG) max, 1.02 Nm (9 lb-in) torque,75 C (167 F) or higher copper wire only

    Relay, KYZ outputs, Current input

    terminals(1)

    # 320634.

    2.5 mm2 (14 AWG) max, 1.18 Nm (10.4 lb-in) torque,75 C (167 F) or higher copper wire only

    Status inputs, RS485 2.5 mm2 (14 AWG) max,0.56 Nm (5 lb-in) Torque

    RIO, DNT (when present) 2.5 mm2 (14 AWG) max,0.56 Nm (5 lb-in) Torque

    -2060 C (-40140 F) Cat. No. 1404-DM, 1404-Mxxxx-000, 1404-Mxxxx-DNT055 C (32 131 F) 1404-Mxxxx-232, -RIO, -ENT, -CNT

    -4085 C (-40185 F)

    595%, noncondensing

    10500 Hz: 2 g operational (0.012 in.)

    1/2 sine pulse, 11 ms duration: 30 g operational and nonoperational

  • 60 Powermonitor 3000 Master Module

    Publication 1404-IN007E-EN-P

    Product ApprovalsPowermonitor 3000 units have the following approvals and certifications.

    EtherNet/IP Conformance Te

    All products equipped witshown below. This mark Device Vendor AssociationEtherNet/IP conformance monitor interoperates with(including devices from oPowermonitor 3000 Ether1404-M8805A-ENT B haveTest version A2.8. The ODproducts that have passed

    ControlNet Conformance Te

    All products equipped witbelow. This mark indicateInternational (CI) indepentest. This test provides a lwith other conformance tevendors). Two representafamily of devices; the 140tested by CI using Contro(http://www.ControlNet.oconformance test at one o

    UL/CUL

    UL 508 listed, File E96956- October 2006

    sting

    h an EtherNet/IP communication port bear the mark indicates the power monitor has been tested at an Open (ODVA) independent test lab and has passed the

    test. This test provides a level of assurance that the power other conformance tested EtherNet/IP devices

    ther vendors). Two representative devices from the Net/IP family of devices; the 1404-M405A-ENT B and the been tested by ODVA using EtherNet/IP Conformance VA website (http://www.odva.org) maintains a list of the conformance test at one of their test labs.

    sting

    h a ControlNet communication port bear the mark shown s the power monitor has been tested at a ControlNet dent test lab and has passed the ControlNet conformance evel of assurance that the power monitor interoperates sted ControlNet devices (including devices from other

    tive device from the Powermonitor 3000 ControlNet 4-M405A-CNT A and the 1404-M805A-CNT A have been lNet Conformance Test version 12. The CI website rg) maintains a list of products that have passed the f their test labs.

    , for Industrial Control Equipment and CUL Certified.

  • Powermonitor 3000 Master Module 61

    CE Certification

    If this product bears the CE marking, it is approved for installation within the European Union and EEA regions. It has been designed to meet the following directives.

    EMC Dirrective

    This product is tested to mCompatibility (EMC) and ttechnical construction file

    EN 50081-2 - Gene

    EN 50082-2 - Gene

    This product is intended f

    Low Voltage Directive

    This product is tested to mapplying the safety requirEquipment for Measureme

    This equipment is classifieprovided with environmenenclosures designed for sppublication 250 and IEC pdegrees of protection prov

    International Standard IEC 5

    The Powermonitor 3000 mInternational Standard IEC508.

    The Powermonitor 3000 dInternational Standard IEC

    Follow the recommended

    ANSI/IEEE Tested

    Meets or exceeds the Surgprotective relays and relayPublication 1404-IN007E-EN-P - October 2006

    eet Council Directive 89/336/EEC Electromagnetic he following standards, in whole, documented in a :

    ric Emission Standard, Part 2 - Industrial Environment

    ric Immunity Standard, Part 2 - Industrial Environment

    or use in an industrial environment.

    eet Council Directive 73/23/EEC Low Voltage, by ements of IEC 1010-1, Safety Requirements for Electrical nt, Control, and Laboratory Use.

    d as an open style device. Open style devices must be tal and safety protection by proper mounting in ecific application conditions. See NEMA Standards ublication 529, as applicable, for explanations of the ided by different types of enclosure.

    29 / NEMA / UL 508 Degree of Protection

    aster module is rated as IP10 degree of protection per 529. It is considered an open device per NEMA and UL

    isplay module is rated as IP65 degree of protection per 529. It is rated as Type 4 (Indoor) per NEMA and UL 508.

    installation guidelines to maintain these ratings.

    e Withstand Capability (SWC) C37.90.1 - 1989 for systems on all power connection circuit terminations.

  • 62 Powermonitor 3000 Master Module

    Publication 1404-IN007E-EN-P

    Additional ResourcesFor more information on additional power quality products, refer to the following publications.

    .

    You can view or downloahttp://literature.rockwellaudocumentation, contact yorepresentative.

    For this information

    Powermonitor 3000 User Manual

    Powermonitor 3000 Display ModuInstructions

    Bulletin 1403 Powermonitor II Tut- October 2006

    d publications at tomation.com. To order paper copies of technical ur local Rockwell Automation distributor or sales

    Refer to Publication

    1404-UM001

    le Installation 1404-IN005

    orial 1403-1.0.2

  • Powermonitor 3000 Master Module 63Publication 1404-IN007E-EN-P - October 2006

  • Publication 1404-IN007E-EN-P Supersedes Publication 1404-IN007D-EN-P - Septembe

    Rockwell Automation SupportRockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.

    For an additional level of and troubleshooting, we oinformation, contact your or visit http://support.rock

    Installation AssistanceIf you experience a probleinstallation, please reviewalso contact a special Custmodule up and running.

    New Product SatisfactiRockwell tests all of its prshipped from the manufacfunctioning, it may need t

    Rockwell Automation, Allen-Bradley, SHighway Plus, TechConnect, RSPower,Inc.

    Trademarks not belonging to Rockwell

    United States 1.440.64Monday

    Outside United States

    Please ctechnica

    United States Contact(see phocomplet

    Outside United States

    Please cprocedu- October 2006 PN 40055-212-01(5)r 2004 Copyright 2006 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

    technical phone support for installation, configuration, ffer TechConnect Support programs. For more local distributor or Rockwell Automation representative, wellautomation.com.

    m with a hardware module within the first 24 hours of the information that's contained in this manual. You can omer Support number for initial help in getting your

    on Returnoducts to ensure that they are fully operational when turing facility. However, if your product is not o be returned.

    LC, SLC500, PLC, PLC-5, ControlLogix, Powermonitor 3000, Powermonitor II, Data RSPowerPlus, RSEnergyMetrix, and RSLinx are trademarks of Rockwell Automation,

    Automation are property of their respective companies.

    6.3223 Friday, 8am 5pm EST

    ontact your local Rockwell Automation representative for any l support issues.

    your distributor. You must provide a Customer Support case number ne number above to obtain one) to your distributor in order to e the return process.

    ontact your local Rockwell Automation representative for return re.

    1407-IN007E-EN-P, Powermonitor 3000 Master Module Installation InstructionsImportant User InformationAbout This PublicationSafety ConsiderationsAbout Power MonitorCatalog Number ExplanationQuick Start GuidelinesInstall the Powermonitor 3000 UnitInterpret the LED IndicatorsSpecificationsAdditional ResourcesBack Cover