13_KRUEGER_Cond Assess HV Bushings.pdf
Transcript of 13_KRUEGER_Cond Assess HV Bushings.pdf
-
Advanced Diagnostic Tests on High Voltage Bushings Dr. Michael Krger, OMICRON Austria
-
Cigre A2.37 Transformer Failure Statistics Failure Locations of Substation Transformers >100kV
Source: No. 261 - April 2012 ELECTRA
PAGE 2
-
Insulation Systems of High Voltage Bushings
RBP Resin Bonded Paper
RIP Resin Impregnated Paper
OIP Oil Impregnated Paper
PAGE 10
-
RBP RIP OIP
1913 to 1974 since 1950 since 1960
Recommended measures
Time schedule
Visual check leakage and mechanical damage
In case of maintenance work
Measurement of capacitance and dielectric dissipation factor
- after installation as reference for later measurements (fingerprint) - 10 years after commissioning
- dependend on results after each 5 years (uncritical values) or shorter
Insulation Systems of High Voltage Bushings
Source: B. Heil (HSP Troisdorf, Germany), Diagnose und Bewertung von Durchfhrungen, OMICRON AWT Germany 2010
PAGE 11
-
Capacitive Bushings (1)
Emax= high
A
Emax= smaller
A
without capacitive
layers
with capacitive
layers Earthing Cap
PAGE 17
-
Capacitive Bushings (2)
PAGE 18
Aluminium foils with equal areas
Aluminium foil Paper
Aluminium foil Conductor
-
Capacitive Bushings (3)
PAGE 19
Current at the Measurement Tap
50 = = 10 100 1.2 = / = 200
-
Bushing Measuring Tap
PAGE 25
-
Measuring Taps
MICAFIL
ABB
PAGE 26
-
Measuring Taps
HSP
PAGE 27
-
Measuring Taps
GE
PAGE 28
-
Arcing at the Measurement Tap
PAGE 29
Source: Norbert Koch Diagnoseverfahren an Hochspannungsdurchfhrungen aus Herstellersicht, Diagnoseverfahren an Schaltanlagen und Transformatoren, HdT Essen 2013
-
Partly Burned Measurement Tap of a 245kV-RIP Busing
PAGE 30 Source: Hubert Goebel GmbH
-
Partly Burned Measurement Tap of a 400kV-OIP Busing
PAGE 31 Source: Hubert Goebel GmbH
-
Diagnostic Methods
PAGE 32
Type of FaultMoisture AgeingContact problems and high impedance faults between layersShorted grading layersLeakagePartial discharges Diagnostic Technique
OIP 5 1 5 5 5 5RBP 5 1 5 5 5 5RIP 5 1 5 5 5 5OIP 4 5 4 3 4 5RBP 4 5 4 3 4 5RIP 4 5 4 3 4 5OIP 5 4* 1 3 4 4RBP 5 4* 1 3 4 4RIP 5 4* 1 3 4 4OIP 3 5 3 1** 2 2RBP 3 5 3 1** 2 2RIP 3 5 3 1** 2 2OIP 3 5 1 1 1 1RBP 3 5 1 1 1 1RIP 3 5 1 1 1 1OIP 1 5 3 1 5 4RBP 1 5 3 1 5 4RIP 1 5 3 1 5 4
Dissolved gas analysis 1 5 1 1 4 5Moisture in oil 5 5 4 5 3 1DF/PF 4 5 4 3 2 2Conductivity of oil (IEC 61620) 4 5 4 3 2 2Particles in oil 5 5 5 5 2 5Analysis of Furanic components 5 5 5 5 1 5Test for corrosive Sulfur 5 5 5 5 2 51=very good, 2=good 3=fair 4=poor 5=not applicable*big leakages can be detected with hot collar test **DF/PF from 2-12kV
OIP
Gen
eral
Ele
ctric
al B
asic
Dielectric Responsewith FDS / PDC
Partial discharge measurementEle
ctric
al
Adv
ance
dO
il
Capacitance
DF/PF
Visual Inspection
Thermography
-
Infrared Thermography
PAGE 33
Source: ABB Brochure Bushing diagnostics and conditioning, 2750 515-142 en
-
C-Tan Progression of a Bushing
Source: RWE
PAGE 34
Source: Volker Seitz: Vorbeugende Instandhaltung an Leistungstransformatoren, OMICRON Anwendertagung 2003, Friedrichshafen
-
Bushing Fault
Source: RWE
PAGE 35
Source: Volker Seitz: Vorbeugende Instandhaltung an Leistungstransformatoren, OMICRON Anwendertagung 2003, Friedrichshafen
-
Definitions of Dielectric Losses
Dielectric losses are caused by Conductive losses
Polarization losses
Partial discharges
0.00E+00
5.00E-04
1.00E-03
1.50E-03
2.00E-03
2.50E-03
0 50 100 150 200 250 300 350 400
Parallel
Parallel
Parallel circuit Serial circuit
RP CP RS
CS totR
SSC
R
UU
CRUU
=
==
cos:PF
tan:DF
||||cos:PF
1||||tan:DF
tot
RP
PPCP
RP
II
CRII
=
==
0.00E+00
5.00E-04
1.00E-03
1.50E-03
2.00E-03
2.50E-03
0 50 100 150 200 250 300 350 400
Serial
Serial
0.00E+00
5.00E-04
1.00E-03
1.50E-03
2.00E-03
2.50E-03
0 50 100 150 200 250 300 350 400
SerialParallelSum
PAGE 38
-
Standards
Type RIP OIP RBP Main insulation Resin
impregnated paper
Oil impregnated paper
Resin bonded paper
DF / tan delta (20C, IEC60137)
< 0.7 % < 0.7 % < 1.5 %
PF cos phi (20C, IEEE C57.19.01)
< 0.85 % < 0.5 % < 2 %
Typical new values 0.3-0.4 % 0.2-0.4 % 0.5-0.6 %
PD (IEC60137) at Um 1.5 Um /3 1.05 Um /3
< 10 pC < 5 pC < 5 pC
< 10 pC < 5 pC < 5 pC
< 300 pC
PAGE 39
-
Cigre WG A2.34 Brochure 445 Guide for Transformer Maintenance
www.e-cigre.org
PAGE 43
Frequency
-
Not free of cavities Partial Discharges possible also at rated voltage
Higher dielectric losses can feed to thermal instability
RPB has cavities and cracks in the paper which are normally filled with the surrounding oil
Increase of capacitance
After a longer storage period this oil is running out. The PD level is increasing and the capacitance is getting smaller
RBP - Bushings
PAGE 44
-
RBP Bushings Cracks in the Insulation
PAGE 45
-
Micafil Bushings RBP Superresocel RBP Drysomic OIP and RIP Tan = f(T)
PAGE 49
Source: Karl Frey, Micafil
-
Measurement on 220kV RBP Bushings (1971)
PAGE 52
-
TanDelta 15-400Hz
PAGE 53
-
RBP Bushing Oil-Filled Cracks Oil Ingress by Capillare Effect
PAGE 54
-
RBP Bushing 123kV (1963)
PF (f) A, B, C
0.0%
0.2%
0.4%
0.6%
0.8%
1.0%
1.2% 0.
0Hz
50.0
Hz
100.
0Hz
150.
0Hz
200.
0Hz
250.
0Hz
300.
0Hz
350.
0Hz
400.
0Hz
450.
0Hz
A
Influence of Moisture
PAGE 55
-
Micafil UTXF 24 (Drysomic) RBP Bushings
A,B,N humid after wrong storage
C dried
PAGE 56
-
Micafil UTXF 24 RBP Bushings A,B,N never used, wrongly stored, C dried
Messung bei 20C DF (f) A, B, C, N
0.0%
1.0%
2.0%
3.0%
4.0%
5.0%
6.0%
0.0H
z
50.0
Hz
100.
0Hz
150.
0Hz
200.
0Hz
250.
0Hz
300.
0Hz
350.
0Hz
400.
0Hz
450.
0Hz
ABCN
dried
humid
PAGE 57
-
RBP Bushing 123kV
?
PAGE 60
-
RBP Bushing 123kV
PF (V) A, B, C
0.5%
0.6%
0.7%
0.8%
0.9%
1.0%
1.1% 0.
0V
2000
.0V
4000
.0V
6000
.0V
8000
.0V
1000
0.0V
1200
0.0V
1400
0.0V
A B C
PAGE 61
-
RBP Bushing 123kV
PF (f) A, B, C
0.0%
0.5%
1.0%
1.5%
2.0%
2.5% 0.
0Hz
50.0
Hz
100.
0Hz
150.
0Hz
200.
0Hz
250.
0Hz
300.
0Hz
350.
0Hz
400.
0Hz
450.
0Hz
A B C
PAGE 62
-
RBP Bushing 123kV
Bushing has to be exchanged defective contact on the measuring tap or
defective connection between the innermost layer and the HV conductor or
partial breakdown between layers
PAGE 63
-
Measurement Tap O.K.
PAGE 64
-
Innermost Layer was not Properly Connected to the HV Conductor.
PAGE 65
-
123kV RBP Bushing
PAGE 66
-
Dissipation Factor Measurement
0.0%
1.0%
2.0%
3.0%
4.0%
5.0%
6.0%
7.0%
8.0%0.
0Hz
50.0
Hz
100.
0Hz
150.
0Hz
200.
0Hz
250.
0Hz
300.
0Hz
350.
0Hz
400.
0Hz
450.
0Hz
DF (f) A, B, C
A
B
C
PAGE 67
-
Measurement of the Removed Bushing
PAGE 68
-
Measurement of the Removed Bushing
0.0%
2.0%
4.0%
6.0%
8.0%
10.0%
12.0%
14.0%
16.0%0.
0Hz
50.0
Hz
100.
0Hz
150.
0Hz
200.
0Hz
250.
0Hz
300.
0Hz
350.
0Hz
400.
0Hz
450.
0Hz
DF (f)
C1
PAGE 69
-
Aktivteil
PAGE 70
-
OIP Bushings
Paper of the OIP bushings ages particularly at high temperatures
Through aging the dielectric losses will increase -> this increases the power factor
Temperature dependent aging decomposes the Paper and produces additional water -> this accellerates the aging
PAGE 73
-
OIP Bushing Fault
PAGE 80 Source: Hubert Goebel GmbH
-
OIP Bushing Fault
PAGE 81 Source: Hubert Goebel GmbH
-
OIP Bushing Fault
PAGE 82 Source: Hubert Goebel GmbH
-
OIP Bushing
PAGE 90 Source: Hubert Goebel GmbH
-
OIP Bushing Breakdown at the Sharp Edge of the Foil
PAGE 91 Source: Hubert Goebel GmbH
-
OIP Bushing
PAGE 94 Source: Hubert Goebel GmbH
-
33kV OIP Bushings
New bushings
Removed bushings
C-Tan-Delta Meas.
PAGE 95
-
Tan Delta (T) at 50Hz (OIP DF)
0.10
1.00
10.00
20 30 40 50 60 70 80 90C
[%]0.1-0.3% Water in paper
0.4-0.6% Water in paper
1% Water in paper
Source: ABB, Bushing diagnostics and conditioning
PAGE 96
-
Tan Delta (f) at 30C (33kV OIP DF)
Tan Delta (f) A, B, C
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.80 50 100
150
200
250
300
350
400
450Hz
%
ABCA RemovedB RemovedC Removed
PAGE 97
-
123kV OIP Bushings TanDelta = f(U)
PF (V) A, B, C
0.4%
0.5% 0.6% 0.7%
0.8% 0.9% 1.0%
1.1% 1.2% 1.3%
0.0V
2000
.0V
4000
.0V
6000
.0V
8000
.0V
1000
0.0V
1200
0.0V
1400
0.0V
A B C
PAGE 98
-
123kV OIP Bushings TanDelta = f(f)
PAGE 99
-
123kV OIP DF Corroded Measuring Tap
PAGE 100
-
Ageing of RIP Bushings
Partial breakdowns between capacitive layers are rather seldom
Decrease of the power factor with increasing test voltage can be an indicator for partial breakdowns
Also defective connections of the measurement layer to the test tap or of the innermost layer to the high voltage conductor may be the reason for a decrease of the power factor with increasing test voltage
Increase of the capacitance after a partial breakdown between two layers:
Cnew = Cold x n / (n-1) n= number of layers approx. 4-7 kV per layer
PAGE 101
-
RIP Bushings
PAGE 113
-
RIP Bushing
PAGE 114
-
Partial Breakdown on a RIP Bushing
Source: B. Heil, Diagnose und Bewertung von Durchfhrungen, OMICRON AWT Germany 2010
PAGE 115
-
220kV RIP Bushing, Stored Outside
PAGE 119
-
220kV RIP Bushing, Stored Outside
0.25 %
0.35 %
0.45 %
0.55 %
0.65 %
0.75 %
0.85 %
0.0 Hz 100.0 Hz 200.0 Hz 300.0 Hz 400.0 Hz 500.0 Hz
Tan
Del
ta
after removing from TR 3 months after removing6 months afetr removing
Minimum
Minimum
Minimum
PAGE 120
-
PAGE 121
Influence of Humidity for 123kV Bushings with Silicone Coated Composite Insulators Mounted Horizontally
-
PAGE 122
DF (f)
0.2%
0.3%
0.4%
0.5%
0.6%
0.7%
0.8%
0.9%
1.0%
0.0Hz 50.0Hz 100.0Hz 150.0Hz 200.0Hz 250.0Hz 300.0Hz 350.0Hz 400.0Hz 450.0Hz
T31 2U2(f)T31 2V2(f)T31 2W2(f)T32 2U2(f)T32 2V2(f)T32 2W2(f)T33 2U2(f)T33 2V2(f)T33 2W2(f)
Influence of Humidity for 123kV Bushings with Silicone Coated Composite Insulators Mounted Horizontally
-
PAGE 123
Influence of Humidity for 123kV Bushings with Silicone Coated Composite Insulators Mounted Horizontally
DF (f)
0.2%
0.3%
0.4%
0.5%
0.6%
0.7%
0.8%
0.9%
1.0%
0.0Hz 50.0Hz 100.0Hz 150.0Hz 200.0Hz 250.0Hz 300.0Hz 350.0Hz 400.0Hz 450.0Hz
ABC
DF (f) A, B, C
0.0%
0.1%
0.2%
0.3%
0.4%
0.5%
0.6%
0.0H
z
50.0
Hz
100.
0Hz
150.
0Hz
200.
0Hz
250.
0Hz
300.
0Hz
350.
0Hz
400.
0Hz
450.
0Hz
ABC
Bushings with moss and outer humidity
Bushings cleaned, measured at dry weather
-
PAGE 124
Measurement with Guard Leakage current is bypassing the meter
Meas. tap
Guard
Capacitive layer
Meas. layer
Leakage current
-
PAGE 125
Measurement With High Humidity With and Without Guard
-
PAGE 126
Measurement With High Humidity With and Without Guard
without Guard
with Guard
-
RIP Bushings without Epoxy Tube
before cleaning after cleaning PAGE 128
-
RIP Bushing without Epoxy Tube Inner Moisture
PAGE 129
PresenterPresentation NotesHier der Hinweis, dass es auch satte = niederohmige Teildurchschlge gibt.
-
The oil side of RBP and RIP bushings doesn't need a housing
Cellulose near to the surface can absorb water, if bushings are not stored properly
Incoming water, also from the ambient air reduces the dielectric strength this causes an increase of the dielectric dissipation factor
Moisture in RBP and RIP Bushings
PAGE 130
-
Water in RBP and RIP Bushings
RIP wet RIP dry
Drying of RBP and RIP bushings
is limited
PAGE 131
PresenterPresentation NotesFeuchtigkeit ist nicht in allen Fllen durch erhhten Verlustfaktor erkennbar.
Die Verlustfaktormessung ist eine integrale Methode, welche das gesamte Volumen und das Streufeld erfasst.
Feuchtigkeit durchdringt selten mehr als 1% des Harzvolumens.
Bei einem Anstieg des Verlustfaktors um beispielsweise 10% ist die Oberflche erheblich strker elektrisch geschwchtals das innere Dielektrikum.
Die hheren Verlustfaktoren sind nicht nur bei hheren Temperaturen besser erkennbar.
Es sind die Betriebstemperaturen. Hier beschleunigen sie auch die Alterung.
-
Measurement of the Dielectric Response with FDS und PDC
PAGE 132
PDC FDS
Combination of PDC und FDS reduces measurement time
-
Combined FDS-PDC Measurement on a RIP Bushing
PAGE 133
-
RBP RIP
OIP
FDS Results on RIP, RBP and OIP Bushings
PAGE 134
-
25C
60C
FDS/PDC on a RIP Bushing at Different Temperatures
50Hz tan
PAGE 135
Source: G. Kopp, Measurement of the dielectric response on HV bushings
-
dry surface
wet surface
FDS/PDC with Dry and Wet Surface
50Hz tan equal
PAGE 136
Source: G. Kopp, Measurement of the dielectric response on HV bushings
-
Questions and Remarks?
Advanced Diagnostic Tests on High Voltage BushingsDr. Michael Krger, OMICRON AustriaCigre A2.37 Transformer Failure StatisticsFailure Locations of Substation Transformers >100kVInsulation Systems of High Voltage BushingsInsulation Systems of High Voltage BushingsCapacitive Bushings (1)Capacitive Bushings (2)Capacitive Bushings (3)Bushing Measuring TapMeasuring TapsMeasuring TapsMeasuring TapsArcing at the Measurement TapSlide Number 30Slide Number 31Diagnostic MethodsInfrared ThermographyC-Tan Progression of a BushingBushing FaultDefinitions of Dielectric LossesStandardsSlide Number 43Slide Number 44Slide Number 45Slide Number 49Measurement on 220kV RBP Bushings (1971) TanDelta 15-400HzRBP Bushing Oil-Filled Cracks Oil Ingress by Capillare EffectRBP Bushing 123kV (1963)Micafil UTXF 24 (Drysomic) RBP BushingsMicafil UTXF 24 RBP Bushings A,B,N never used, wrongly stored, C driedRBP Bushing 123kVRBP Bushing 123kVRBP Bushing 123kVRBP Bushing 123kVMeasurement Tap O.K.Innermost Layer was not Properly Connected to the HV Conductor.Slide Number 66Slide Number 67Slide Number 68Slide Number 69Slide Number 70Slide Number 73Slide Number 80Slide Number 81Slide Number 82Slide Number 90Slide Number 91Slide Number 9433kV OIP BushingsTan Delta (T) at 50Hz (OIP DF)Tan Delta (f) at 30C (33kV OIP DF)123kV OIP Bushings TanDelta = f(U)123kV OIP Bushings TanDelta = f(f) 123kV OIP DF Corroded Measuring TapSlide Number 101RIP BushingsRIP BushingPartial Breakdown on a RIP Bushing220kV RIP Bushing, Stored Outside220kV RIP Bushing, Stored OutsideInfluence of Humidity for 123kV Bushings with Silicone Coated Composite Insulators Mounted HorizontallyInfluence of Humidity for 123kV Bushings with Silicone Coated Composite Insulators Mounted HorizontallyInfluence of Humidity for 123kV Bushings with Silicone Coated Composite Insulators Mounted HorizontallyMeasurement with GuardLeakage current is bypassing the meterMeasurement With High Humidity With and Without GuardMeasurement With High Humidity With and Without GuardSlide Number 128Slide Number 129Slide Number 130Slide Number 131Slide Number 132Slide Number 133Slide Number 134Slide Number 135Slide Number 136Slide Number 169