132E
-
Upload
galici2002 -
Category
Documents
-
view
218 -
download
0
Transcript of 132E
-
7/29/2019 132E
1/2
1
Fire
SafeF
lange
Conn
ections
Due to increasing requirements on bolted flange
connections with view to the environment it hasbecome necessary to take into consideration not
only the leak rate of a flange connection but also a
fire. Where fire safe gaskets are required not onlythe gasket itself but also all parts of the flangeconnection must be taken into account.
In case of fire in the vicinity of a flanged connection
flanges - and especially bolts - may be influenced by
the heat and weakend. For this reason British Stan-dard 6755 part 2 (1987) insists on fire tests forvalves.
In Germany the authorities require the same
conditions also for the flange connections of valvesand pipework if inflammable liquids or gases (ofgreat density) are handled and if no total outer
insulation is provided.
Because the latter is a logic conclusion, werecommend to apply this safety philosophy on allbolted flange connections which must be protected
against fire attack.
Remarks on outer insulationThis type of fire protection is safe in case of fire. It has
disadvantages if the flange joint is leaking in servicebefore fire. In this case the inflammable liquid will be
absorbed by the porous insulation material. Theabsorbed inflammable liquid will lead to an extremelydangerous situation which could give rise to fire or
explosion.
Fire safe flange connectionsFire safe flange connections have the following
characteristics:
G The parts, flanges, bolts and gaskets of fire safe
flange joints are not combustible at
650 C. The stability of these parts in ambient air
at 650 C for 30 minutes is given and oxidation aswell as thermal cracking in this time is negligible.
G The fire safe design enables the flange connection
to maintain for thirty minutes a residual surface
pressure, which is high enough to limit theleakage to the allowed maximum in accordance
to BS 6755 part 2.
The problem
The simplest solution would be to design the flangeconnection for 650 C or a higher applicationtemperature. For economical and technical reasons
this is out of question. The economic reason is self-explanatory. The technical reason is that only metal
gaskets can be used at such high temperatures.
The choice is limited to metal gaskets (flat or profile)
and weld type gaskets. The first makes only sense
at high pressures, the latter are not easy to separateand to reweld.
figure 1
figure 2
Fire safe Flange Connection
Gaskets Packings Expansion Joints Rubber and Plastic Parts
-
7/29/2019 132E
2/2
2
Fire
SafeF
lange
Conn
ections
Solution
The way out of this problem is to compromise, as inmany technical solutions. For example, the flangeconnection is designed for 300 C and the used
gasket has a metal support e. g. Kempchen profileB45A with layers of expanded graphite. This
combination withstands temperatures of 650 C for
30 minutes, though its service temperature is limitedto 550 C.
CONVEX-gaskets profile B45A as shown in figure4 in accordance to Work Standard WN 145 for DIN
flanges and WN 146 and WN 147 for ANSIrespectively MSS - SP 44 flanges enable the designer
to determine a fire safe flange joint. One of theadvantageous features is the nearly constant
remaining sealing diameter, even when flangesrotate, and this will obviously happen at temperatures
of about 650 C.
The dimensions of these gaskets are optimized, sothat each gasket seals on the smallest possible
sealing diameter. With this optimization flange
rotation is initiated by the bolting up procedure. Thedegree of rotation will scarcely increase with
increasing pressure and temperature. Therefore thesmall and constant sealing diameter leads to constant
bolt load and maximum residual stress.
MaterialsFor flange connections with fire safe requirements
metal gaskets or gaskets composed of metal andgraphite are useable. In some cases metal gaskets
are not suitable for instance with flanges of low
nominal pressure rate. In cases where a contactbetween the medium and graphite is to avoid gasketswith an inner metal eyelet are recommended.
If extremely tight and clean sealing is required the
inner part of the layers may be made of PTFE, seefigure 4. With this design the medium will be free ofimpurities. The increase of tightness is related to the
factor 100. The PTFE may be destroyed in case of
fire but the graphite part of the layers ensures thatthe joint will be tight.
kempchenfire safe supplement
The latest development in this field are gaskets withouter rings and layers of intumescenting material onboth sides (fig. 1). This compound blows up at about
300 C and turns into an unburnable, porous heatinsulating foam (fig. 2). The space between the
flanges especially between the outside diameter of
flanges and the bolts is filled with the insulating foamand this protects the bolts against heat transmitted
by convection or radiation. This is the best guarantee
for a constant residual gasket surface pressure.
Fire Safe Flange Connections
Gaskets Packings Expansion Joints Rubber and Plastic Parts
kempchen & Co. GmbH
Alleestr. 4 D - 46049 Oberhausen
Tel.: ++49 208 8482-0 Telefax ++49 208 8482-285
E-mail: [email protected]
URL: www.kempchen.de
132e/1201000X
graphite
PTFE
stainless steelfigure 2
T>= 650 0C, 30 min
test valve through-seat external
position leakage leakage[mL/in/min] [mL/in/min]
highpressure closed
low
pressure closedhigh fullypressure open
test requirements accordingBS 6755 : Part 2 : Section three : 1987
figure 3
400 100
40 20
200
All information and technical descriptions contained in this brochure correspond to our state of knowledge at the time of the printing. They are intended as information about our
products and their various applications.Therefore, we will only guarantee certain attributes described in the brochure or the suitability for actual intended purposes according to a written express warranty in the actual individual case. Any industrial proprietary rights must be observed. Orders will only be accepted and completed under our standard terms and conditions, which we will make available on request.