125VDC 48VDC Converter Manual 296

download 125VDC 48VDC Converter Manual 296

of 73

description

konvertor

Transcript of 125VDC 48VDC Converter Manual 296

  • Operating instructions

    Date Name No. 4640 en Issued on: 22/05/2010 BGOE TTS Bl. 1/73 Bl. Revised: 10.11.10 BGOE/COBS Checked: 10.11.10 EW/Strohbach

    Y:\Dave Almond\DC_DC Converter\4640 EN Description.doc

    DC-DC Converter

    TEBECHOP 3000 HDI DC

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 2/73 4640 en

    Contents

    1 Preface ....................................................................................................... 6

    2 Safety notes and explanation of symbols .................................................. 7

    3 Connection ................................................................................................ 9

    4 General .................................................................................................... 11

    5 Principle of operation .............................................................................. 13

    6 Components ............................................................................................ 14

    6.1 Power modules: .................................................................................... 14

    6.2 MCU 2500 HDI remote monitoring system: .......................................... 14

    6.3 Equipment racks: .................................................................................. 15

    6.4 Blank insert 1/5 ..................................................................................... 16

    7 Recommended installation, minimum distances..................................... 17

    8 Fitting equipment racks ........................................................................... 18

    9 Connecting equipment racks ................................................................... 20

    9.1 Equipment rack 5-way, rear view.......................................................... 20

    9.2 Connection diagram, equipment rack 5-way ........................................ 22

    9.3 Connection diagram, equipment rack 5-way, incl. MCU ....................... 23

    10 MCU 2500 HDI remote monitoring system ........................................... 24

    10.1 General ................................................................................................. 24

    10.2 MCU 2500 HDI remote monitoring system: .......................................... 24

    10.3 Bus systems / interfaces ....................................................................... 24

    10.4 Components of the MCU 2500 HDI remote monitoring system ............ 26

    10.5 ADBUS components ............................................................................. 27

    10.6 SAT-Bus components ........................................................................... 28

    10.7 RS232 components .............................................................................. 28

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 3/73 4640 en

    10.8 Graphical display .................................................................................. 28

    11 Installation and commissioning .............................................................. 30

    11.1 Using the graphical display ................................................................... 30

    11.2 The main window.................................................................................. 32

    11.3 Passwords ............................................................................................ 32

    11.4 Menu structure ..................................................................................... 32

    12 Main menu .............................................................................................. 44

    13 Measured values .................................................................................. 45

    14 Log file ................................................................................................ 46

    15 Test ...................................................................................................... 47

    16 Status request ....................................................................................... 48

    17 Setup menu .......................................................................................... 49

    17.1 The System configuration menu......................................................... 49

    17.2 Changing characteristics menu .......................................................... 49

    17.3 Normal operation .................................................................................. 49

    17.4 Standby operation ................................................................................ 49

    17.5 Voltage settings menu ........................................................................ 50

    17.6 Shunt values menu ............................................................................ 50

    17.7 Hold functions menu .......................................................................... 51

    18 Times menu ......................................................................................... 53

    19 Boundary value monitoring menu ....................................................... 55

    20 Configuration menu ............................................................................. 57

    21 Display configuration menu ................................................................ 61

    22 Expert mode menu ............................................................................... 62

    23 Commissioning ....................................................................................... 63

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 4/73 4640 en

    24 Operating modes ..................................................................................... 64

    24.1 Normal .................................................................................................. 64

    24.2 Standby) ............................................................................................... 64

    25 Parallel operation .................................................................................... 65

    26 Satellite .................................................................................................... 66

    26.1 Standard function ................................................................................. 66

    26.2 LEDs, power modules .......................................................................... 67

    26.3 LEDs, MCU 2500 HDI remote monitoring system ................................ 68

    27 Alarms ..................................................................................................... 69

    27.1 Alarm contacts ...................................................................................... 69

    27.2 Urgent alarm (unit fault SV1) ................................................................ 69

    27.3 Non-urgent alarm (mains fault SV2) ..................................................... 69

    27.4 Overload detection/Overload behaviour ............................................... 70

    27.5 Temperature monitoring ....................................................................... 71

    27.6 Overvoltage protection ......................................................................... 71

    27.7 Fuse monitoring .................................................................................... 72

    27.8 Incorrect polarity ................................................................................... 72

    27.9 Fan fault ............................................................................................... 72

    28 Fuses ........................................................................................................ 73

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 5/73 4640 en

    Abbildungsverzeichnis

    Figure 1: Power modules ...................................................................................................... 14

    Figure 2: MCU 2500 HDI ..................................................................................................... 14

    Figure 3: Equipment rack (without power modules) ............................................................ 15

    Figure 4: Equipment rack (without power modules with MCU) .......................................... 15

    Figure 5: Blank insert ............................................................................................................ 16

    Figure 6: Recommended installation .................................................................................... 17

    Figure 7: Fitting equipment racks ......................................................................................... 19

    Figure 8: Equipment rack 5-way, rear view .......................................................................... 20

    Figure 9: Connection diagram, equipment rack 5-way ......................................................... 22

    Figure 10: Connection diagram, equipment rack 5-way, incl. MCU ...................................... 23

    Figure 11: Basic structure of the remote monitoring system .................................................. 26

    Figure 12: Graphical display ................................................................................................... 29

    Figure 13: Display with function keys .................................................................................... 30

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 6/73 4640 en

    1 Preface

    These operating instructions provide information for the correct operation of

    the unit. To ensure the safe and correct operation of the unit, the user should

    study these instructions carefully. All the information contained therein must

    be observed.

    This avoids:

    Risks during operation

    Risks to the operator

    Downtime, and enhances the reliability and lifespan of the unit.

    These instructions should be kept in a safe place for later use.

    BENNING specialises in the development and manufacture of power supply

    systems.

    The criteria and methods applied by BENNING for development and

    production comply with the strictest quality standards.

    BENNING has been certified in all areas in accordance with the international

    quality standard ISO9001/EN29001.

    Service Centre

    For reasons of operational safety and operational availability, we recommend

    that the units be regularly maintained.

    For more detailed information call our service centre. In addition, our helpdesk

    team is at your disposal 24 hours a day for technical support under the phone

    number

    +49 2871 / 93-555

    BENNING Elektrotechnik und Elektronik GmbH & Co. KG

    D 46397 Bocholt

    Mnsterstrae 135 - 137

    Telephone +49-2871 / 93-0 - Telefax +49-2871 / 93-417

    http://www.benning.de/

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 7/73 4640 en

    2 Safety notes and explanation of symbols

    The following international electrical symbols are marked on the DC-DC

    converter (also referred to in the following as "unit" or "power module") or are

    used in its operating and display systems:

    Caution! See documentation.

    Alternating current

    Direct current

    Earth (Ground)

    Operation, see instructions

    Fault, see instructions

    List of abbreviations

    A Current

    b.-Art Operating mode

    DC Direct current

    EndE End

    i-MA Setting current limitation

    INenn Rated current

    I-rEG Following current limitation

    Normal Standard output voltage

    Po.MA Power management

    Standby 2nd voltage level, switchable

    SAT-Bus Satellite bus

    T Temperature

    tESt Test

    U Voltage

    U-rEG Following voltage

    W Watt

    e.g. for example

    Certain parts of the text in these instructions are highlighted by the following

    symbols.

    Indicates a remark pointing out that observing it will facilitate working with the unit.

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 8/73 4640 en

    Indicates a remark pointing out the process or operation of a device

    or giving an instruction.

    Indicates a remark pointing out that life and body of persons could

    be directly endangered.

    The unit is an electronic device which carries dangerous levels of

    voltage and current. The following instructions must therefore be

    strictly observed at all times:

    1. Installation, operation, maintenance and repair of the unit must

    always be carried out in accordance with these instructions.

    2. Ensure that only fully trained and qualified personnel have access

    to the unit. Only these personnel shall be permitted to open the

    housing.

    3. Even when the unit is completely switched off, certain internal

    components remain live as long as it is connected to the mains

    supply or the battery.

    4. Integrated capacitors may still be charged even when the entire unit

    is completely free of voltage. Ensure that the capacitors are

    properly discharged by a qualified electrician before touching the

    connections.

    5. When working with the unit, use only properly insulated tools.

    6. All persons working with the unit must be familiar with first-aid

    procedures for accidents involving electricity.

    7. Always comply with the regulations of the local power-supply

    company or authority as well as any other relevant safety

    regulations.

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 9/73 4640 en

    3 Connection

    The following standards and regulations are applicable to the unit:

    EN 60950 EN 55022

    EN 61000-3-2 EN 61000-3-3 EN 61000-4-2

    EN 61000-4-3 EN 61000-4-4 EN 61000-4-5

    In the standard version, the device and the insulating transformer correspond to

    protection class I. The transformer corresponds to the regulation EN 61558 and

    the test voltage primary/secondary is 4 kV alternating voltage.

    The unit as delivered is ready for operation.

    Installation and trouble-free operation are only guaranteed in the special

    equipment rack.

    This device (protection type: IP 20) must be installed in a dry and dust-

    protected environment. The cooling air must not be obstructed.

    Pay attention to the block circuit diagram. The supply circuit must be fitted with an isolating device which

    must be easily accessible if permanently connected;

    must be easily accessible and provided close to the device if it is a plug connection.

    Provide appropriate fuses for mains and output cables (size of fuse,

    characteristic, see technical data).

    Access to the input and output fuses is only possible after opening the unit.

    Before connecting up, compare the information on the rating plate and data

    sheet with the actual input and output voltages.

    The details on the rating plate and in the data sheet with regard to power

    consumption apply to rated conditions of input voltage and the Normal operating mode. The value in brackets is the maximum input current with

    maximum input voltage tolerance.

    Connect only when the voltage is switched off.

    The unit must be connected to the neutral conductor of the supply power circuit

    according to local regulations.

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 10/73 4640 en

    Because of the high energy of the battery to be connected, special safety

    precautions must be taken.

    To protect the unit from overvoltages (e.g. due to lightning strikes), carry out

    potential equalisation using an adequate cable cross section (e.g. 6

    mm2/AWG10) on the rack if no other measures to protect the unit are provided,

    e.g. building protection.

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 11/73 4640 en

    4 General

    The power modules described below (also referred to as unit or Dc-DC

    converter) are designed using pulse technology.

    This technology results in a good efficiency and good dynamic control

    characteristics in the event of input voltage changes and load steps.

    As these power modules have a very compact design and can be connected in

    parallel, powerful supply systems can be built up in conjunction with

    equipment racks.

    The primary switched DC-DC converters of the TEBECHOP series were

    developed to generate output voltages of 24V DC, 48V DC, 60V DC, 110V

    DC or 220V DC from a central 110V DC or 220V DC supply.

    They are mainly used for the decentralised 24V DC supply in energy supply

    companies or for supplying telecommunication systems with 48V DC and/or

    60V DC.

    By connecting several devices in parallel, the required load power can be

    adjusted individually.

    The main components of these modular power supply systems are the power

    modules (output voltages: 24V, 48V, 60V, 110V or 220V) with racks (19" 5-

    way without MCU 2500 HDI remote monitoring system and 19" 4-way with

    integral MCU 2500 HDI remote monitoring system).

    The power modules are connected in parallel within the rack. The output power

    can also be flexibly scaled (even retrospectively) and several racks can be

    connected in parallel. This enables redundant power supplies (e.g. n+1

    redundancy) to be implemented in a compact unit.

    Only 3 height units are required for installation in appropriate system cabinets.

    Racks with integral MCU 2500 HDI remote monitoring system enable 4

    power modules to be fitted.

    Further racks can easily be connected in parallel by connecting the +/- outputs

    of the parallel-running connector and the SAT-Bus.

    Up to 24 units: direct addressing

    Further units: SAT-Bus connection via bus converter (Part No. 525886, see

    description: 4553), see also Chapter 15 of these operating instructions. The

    maximum number of controllable DC-DC converters is limited to 99 units by

    the MCU 2500 HDI remote monitoring system.

    The DC-DC converters have an IU-characteristic

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 12/73 4640 en

    The output voltage is kept constant with an accuracy of 1 %. On reaching the

    current limit, control changes electronically from voltage to current control.

    When the output of the DC-DC converter is overloaded or a short circuit

    occurs, the 2-way rated current can be supplied for 2 seconds. During this time,

    the short-circuit should be isolated through activating a fuse. The consequence

    of current limitation if applicable is a drop of the output voltage in the event of

    a short circuit to < 1 V.

    If after this time the output current does not drop to 100%, after approx. 5

    seconds the output voltage is switched off.

    Note: The rating of the fuse must be observed.

    This measure makes the device continuously short-circuit proof.

    Fluctuations of input voltage (see technical data sheet) and load changes have

    no effect on the quality of the voltage and current constancy and are regulated.

    The DC-DC converter is equipped with a so-called satellite. This assembly

    integrated in the DC-DC converter enables a remote monitoring system to be

    set up using the MCU 2500 HDI remote operating system.

    Faults can be transmitted by means of voltage-free contacts using the MCU

    2500 HDI remote monitoring system.

    Note: Always operate DC-DC converters with a standalone MCU, i.e. do

    not establish a SAT connection with other systems, e.g. rectifiers or

    inverters.

    For further information on the task of the satellite, see chapter 16.

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 13/73 4640 en

    5 Principle of operation

    The voltage fed in through the input filter is supplied to a step-up converter

    through the DC-DC converter. A special control method provides a constant

    DC voltage for the main converter at the output of the step-up converter.

    Rapid MOSFET power transistors in the main converter convert the DC

    voltage into a rectangular voltage. Control is effected by changing the switch-

    on time at constant frequency. The power transmitter provides potential

    isolation and transforms the rectangular voltage to the desired output value.

    Diodes rectify the voltage and an LC filter is used to smooth the output voltage.

    The unit is equipped with a hardware overvoltage cut-out.

    DC-DC converters with an output voltage of 24-60V are additionally equipped

    with a surge disconnect threshold that is configurable by the software.

    After a fault has been repaired, the unit can be restarted when it has been

    isolated from the mains for about 10 seconds or if it has been reset via the

    MCU 2500 HDI remote monitoring system.

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 14/73 4640 en

    6 Components

    6.1 Power modules:

    Figure 1: Power modules

    G110-220 G24/50 BWru-PCT: Part no. 120961

    G110-220 G48/40 BWru-PCT: Part no. 120962

    G110-220 G60/40 BWru-PCT: Part no. 120963

    G110-220 G110/20 BWru-PCT: Part no. 120965

    G110-220 G220/10 BWru-PCT: Part no. 120964

    6.2 MCU 2500 HDI remote monitoring system:

    Figure 2: MCU 2500 HDI

    Remote monitoring system MCU 2500 HDI 24 60V, Part No. 10001246 Remote monitoring system MCU 2500 HDI 110/220V, Part No. 121049

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 15/73 4640 en

    6.3 Equipment racks:

    Figure 3: Equipment rack (without power modules)

    Equipment rack 5-way, 24 60V, Part No. 10007408

    Equipment rack 5-way, 110/220V, Part No. 10012301

    Figure 4: Equipment rack (without power modules with MCU)

    Equipment rack 5-way, 24 60V, 4x power modules ( incl. remote monitoring system MCU 2500 HDI), Part No. 10012279

    Equipment rack 5-way, 110/220V, 4x power modules

    ( incl. remote monitoring system MCU 2500 HDI), Part No. 10012302

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 16/73 4640 en

    6.4 Blank insert 1/5

    Figure 5: Blank insert

    Blank insert 1/5, Part No. 514414, for fitting to empty slots.

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 17/73 4640 en

    7 Recommended installation, minimum distances

    Vorderseite

    >=0 >600mm (24")

    >600mm (24")

    Figure 6: Recommended installation

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 18/73 4640 en

    8 Fitting equipment racks

    Cabinet dimensions required:

    - 19" system

    - Width, internal >436mm

    - Height 133mm (3U)

    - Depth >390mm

    Fixing options:

    - 2x M3 countersinks on each side (from the inside)

    - Front, right and left, 2x countersinks M4

    Fixing parts required,

    - PSJ XX65:

    2x slide rails Part No. 10000368 and 2x plate Part No. 10001390

    - PSJ XX66: 2x slide rails Part No. 10000368 and 2x plate Part No. 10000369

    - PSJ XX68: 2x slide rails Part No. 10000368 and 2x plate Part No. 10001391

    - TC XX66: Slide rails 1x right Part No. 10002487,

    Slide rails 1x left Part No. 10002488

    and 2x side strips Part No. 10003281

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 19/73 4640 en

    Equipment rack - cabinet:

    2x countersunk screws M4 x 10, each side

    Part No. 786545o

    TC cabinet:

    additional 2x side strips,

    Part No.10003281

    Equipment rack - slide rails:

    2x countersunk screws M3x10,

    each side

    Part No. 786041

    Figure 7: Fitting equipment racks

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 20/73 4640 en

    9 Connecting equipment racks

    9.1 Equipment rack 5-way, rear view

    24 60V, Part No. 10012279 ( for 4x power modules, incl. MCU 2500 HDI remote monitoring system)

    24 60V, Part No. 10007408 ( for 5x power modules, without plugs X102,X104,X105,X106 )

    110/220V, Part No. 10012302

    ( for 4x power modules, incl. MCU 2500 HDI remote monitoring system)

    110/220V, Part No. 10012301

    ( for 5x power modules, without plugs X102,X104,X105,X106 )

    X102

    X9 X10X45 X44 X43 X42 X41

    X17 X18

    X19

    X105

    X104X106

    +

    -

    PE

    X9, X10: SAT-Bus

    X102: Benning-Net (SAT-/AD-Bus)

    -

    +

    6,5mm/ 0,26"

    1

    1 2 3

    -X25

    +X35

    -X24

    -X23

    -X22

    -X21

    +X34

    +X33

    +X32

    +X311 2 3

    +

    -

    PE

    +

    -

    PE

    +

    -

    PE

    +

    -

    PE

    1 1

    1

    Figure 8: Equipment rack 5-way, rear view

    Connection DC input ( +,-,PE ) X41 - X45:

    Screw terminals 4mm / AWG 12

    BENNING-Net, SAT-Bus, connector X9,X10,X102:

    Western plug RJ45, 8-pin

    Output DC +/- : Studs M8 x 20

    Alarm terminals, Relay 1 (X104), Relay 2 (X106):

    Screw terminals 1mm / AWG 18

    Parallel-running connector X17/1+2: Screw terminals 1mm/ AWG 18

    (Must be connected when equipment racks are connected in parallel,

    incl. SAT connection.)

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 21/73 4640 en

    Auxiliary supply connector + Vo, X18: 1 / screw terminal 1mm/ AWG 18

    External supply required in the event of a fault for the satellite and the interface

    of each DC-DC converter.

    Supply: +Vo (max. 100mA)

    Remote ON/OFF (contact closed, unit OFF) X19:

    Mating plug Part No. 710700, 2x contact Part No. 761598 (0.5-0.8mm/AWG

    22-18)

    (Note: individual contact for each equipment rack, control inhibit)

    Additional supply to MCU, X105/1 : Screw terminal 1mm / AWG 18 (-Vo)

    Potential equalisation cable connector, earth lug with 6.5mm/ 0.26 inch diameter hole.

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 22/73 4640 en

    9.2 Connection diagram, equipment rack 5-way

    for 5x power modules:

    A1.1 A1.2 A1.3 A1.4

    X41: X42: X43: X44: PEPEPE+ - PE

    - DC + - DC + - DC + - DC +

    X21:1 X31:1 X22:1 X32:1 X23:1 X33:1 X24:1 X34.1

    + DC

    - DC

    + - + - + -

    + -

    A1.5

    X45: PE

    - DC +

    X25.1 X35.1

    + DC

    - DC

    X9:

    X10:

    X17:

    X19:

    1

    2

    1

    2

    X18: 1

    Figure 9: Connection diagram, equipment rack 5-way

    SAT-Bus

    Parallel operation connection

    off on

    Remote ON/OFF

    Secondary power supply

    Output

    Input

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 23/73 4640 en

    9.3 Connection diagram, equipment rack 5-way, incl. MCU

    for 4x power modules, incl. MCU 2500 HDI remote monitoring system:

    A1.1 A1.2 A1.3 A1.4

    X41: X42: X43: X44: PEPEPE+ - PE

    - DC + - DC + - DC + - DC +

    X21:1 X31:1 X22:1 X32:1 X23:1 X33:1 X24:1 X34.1

    + DC

    - DC

    + - + - + -

    1

    A1.5

    - DC +

    X25.1 X35.1

    X9:

    X10:

    X17:

    X19:

    1

    2

    1

    2

    X45: + -PE

    + DC

    - DC

    3 2 1X104: 3 2 1X106:

    (K100) (K101)

    LC-Display

    MCU 2500 HDI X102:

    X105:1

    Benning Net

    -Ubatt

    SAT

    par.

    remoteon/off

    ServiceModem

    X110 RS 232

    X18:

    Figure 10: Connection diagram, equipment rack 5-way, incl. MCU

    SAT-Bus

    BENNING Net

    Messages,

    Relay 1 Relay 2

    2nd supply MCU - Vo

    Parallel operation connection

    off on

    Remote ON/OFF

    Secondary power supply

    Output

    Input

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 24/73 4640 en

    10 MCU 2500 HDI remote monitoring system

    10.1 General

    The MCU 2500 HDI remote monitoring system is a microprocessor-

    controlled monitoring and control unit. With this system, it is possible to

    monitor and control all the main components of a power supply system.

    There are two options for this system:

    - Equipment rack incl. MCU 2500 HDI remote monitoring system

    - Alternatively, equipment rack with power modules and MCU 2500 HDI

    remote monitoring system as a component for fitting in the system cabinet

    The connection to the outside world is made via the serial interface on the front

    panel (X110, RS 232, 9-pin SUB-D). The MCU 2500 HDI remote

    monitoring system can be directly connected to a personal computer (PC).

    The installed service software (see description: 3293) allows comprehensive

    monitoring and controlling of the power supply system. If the control desk is

    not local, the connection to the computer can be created using a modem and the

    public telephone network or by means of a TCP/IP adapter and the internet.

    The MCU 2500 HDI remote monitoring system therefore allows more

    rational and efficient employment of maintenance and service personnel.

    When developing the components for this new range, the highest priority was

    placed on flexible, user-independent implementation and on a significant

    reduction in volume of each individual system component.

    Components for external connection and their function, see Description 4339

    (MCU 2500 HDI remote monitoring system).

    Note: Always operate DC-DC converters with a standalone MCU, i.e. do not

    establish a SAT connection with other systems, e.g. rectifiers or inverters.

    10.2 MCU 2500 HDI remote monitoring system:

    This unit is the heart of the MCU 2500 HDI remote monitoring system (see

    Figure 2). All other components are connected to this unit. MCU main board,

    LC display and RS232 interface (see front view) are incorporated.

    Included as standard in the design Equipment rack incl. MCU 2500 HDI.

    10.3 Bus systems / interfaces

    The data of the individual components are exchanged via different bus systems,

    depending on the type and task of the respective component.

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 25/73 4640 en

    BENNING Net (ADBUS) (X102) Remote peripheral components are connected to the base unit via the

    BENNING Net (ADBUS). These are units with signalling relay and digital

    inputs, measuring boards with analogue inputs, battery symmetry monitoring

    units or earth fault monitoring units. All these components must be installed in

    the immediate vicinity of the base unit (i.e. in the same cabinet).

    Cabling using commercially available network cable (patch cable).

    Caution!

    No more than 7 users may be connected to the BENNING Net

    (ADBUS).

    SAT-Bus X9, X10 The power supply system DC-DC converters, for example, are connected to the

    MCU 2500 HDI remote monitoring system via the SAT-Bus.

    Communication with other equipment racks also takes place via this SAT-Bus.

    The components can be distributed over several cabinets.

    RS232 interface (SUB-D 9-pin), X110 Communication with the outside world takes place via this interface on the

    front panel. A PC with the appropriate service software is connected either

    directly to this interface or via the telephone network (modem) or the internet /

    network (TCP/IP adapter).

    Caution! The BENNING Net (ADBUS) and the SAT-Bus use the same plug

    on the base unit. Once the first SAT-bus component has been

    connected, it will no longer be possible to connect a further

    BENNING Net (ADBUS) component, as the power supply for

    these components will be interrupted. Cabling using commercially

    available network cable (patch cable).

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 26/73 4640 en

    10.4 Components of the MCU 2500 HDI remote monitoring system

    The MCU 2500 HDI remote monitoring system consists of different

    hardware and software components. Some components are essential, others are

    optional. All components are described in Description 4339 to enable the

    system to be installed and commissioned safely.

    Figure 11: Basic structure of the remote monitoring system

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 27/73 4640 en

    Key:

    1 Measuring board TUII (ADBUS component)

    2 Relay box (SAT-bus component)

    3 Battery symmetry monitoring (ADBUS component)

    4 Digital input box (SAT-Bus component)

    5 RELIO board (ADBUS component)

    6 Measuring box (SAT-Bus component)

    7 Power supply system with suitable components for connection to the

    SAT-Bus (DC-DC converter, inverter, .... )

    10.5 ADBUS components

    ADBUS components can be regarded as hardware expansions. They are

    mounted directly in the cabinet on a DIN rail close to the measuring and

    monitoring locations. This reduces the extent of cabling work.

    The components can be connected to each other and to the base unit with

    commercially available network cables (patch cables). The network cable also

    supplies power to the components. Usually, blue cables are used to distinguish

    them from the SAT-Bus wiring.

    The address assignment and/or the necessary configuration are carried out

    using only two jumpers. This enables a service engineer to replace components

    on site without taking further measures.

    Caution! Some special features must be observed due to the technical

    specification of the ADBUS:

    No more than 7 components may be connected

    The maximum length of the complete ADBUS must not exceed 3m

    An ADBUS component cannot be connected downstream of a SAT-Bus component, as this would interrupt the supply

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 28/73 4640 en

    10.6 SAT-Bus components

    The SAT-Bus components include measured value recording and signalling

    components (relay box, measuring box, digital input box). They can be

    mounted directly in the cabinet on a DIN rail close to the measuring and

    monitoring locations. The necessary mounting rail adapter is pre-fitted in the

    factory. Fitting on a mounting plate is also possible. The fixing dimensions

    required can be found in the dimension diagram.

    The components are connected to one another using SAT-Bus cables or

    commercially available network cables (patch cable).

    The components are configured via an internal programming system which has

    already been implemented in the factory.

    10.7 RS232 components

    The RS232 components are used for external communication. These are

    components which have not been developed specially for use in a remote

    monitoring system. These components are always connected via the 9-pin D-

    SUB plug X110 (front panel) on the base unit.

    External modem

    The remote monitoring system can be connected to the public telephone

    network via an analogue modem. A high-speed modem has been tested and

    approved especially for industrial use.

    (PSTN modem V.90-highspeed; MicroLink 56k; Part No. 787663)

    MCU-TCP/IP adapter

    The remote monitoring system can be connected to a computer network or the

    internet via an appropriate MCU-TCP/IP adapter. (Part No. 520421)

    Service PC

    The TEBE MCU Service software (Part No. 545740) installed on the service

    PC can be used for detailed monitoring of the power supply system and

    changing the system parameters. There are no special hardware requirements.

    A WINDOWS operating system (from WINDOWS 9x) is all that is required.

    10.8 Graphical display

    On the 4 buttons of the graphic display on the front panel, all the release

    statuses and measured values of the power supply system can be displayed or

    set. Critical menu levels are accessible by means of a password only. The

    operation and function of the input buttons and the meaning of the statuses and

    values indicated will be explained later in more detail.

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 29/73 4640 en

    The meaning of the 4 LEDs above the display is fixed.

    Operation No function

    Alarm Urgent alarm

    1 2 3 4 5

    6

    Figure 12: Graphical display

    Key:

    1 Operation LED

    2 LED No function

    3 Alarm LED

    4 Urgent alarm LED

    5 Graphical display

    6 Keys for operating the display menu

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 30/73 4640 en

    11 Installation and commissioning

    After installation, connection and commissioning of the MCU 2500 HDI

    remote monitoring system, all the components are fully ready for operation.

    Caution!

    The safety instructions must be observed at all times during

    installation, connection and commissioning.

    All components are designed for use in closed dry rooms. The maximum

    permissible ambient temperature is 40C. Attention must be paid that the

    components are not exposed to aggressive substances and the passage of

    cooling air is not hampered.

    The entire power supply system with all the components belonging to the MCU

    must be wired and connected to the power supply system to enable

    commissioning to be carried out. When the initialisation phase is complete, the

    display shows a measured value of the system.

    11.1 Using the graphical display

    Each menu item can be accessed and settings can be made using the four

    function keys below the display. However, some menu items are protected by a

    password. The system automatically returns to the initial state from any menu

    item when no button has been actuated for about 1 minute.

    Figure 13: Display with function keys

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 31/73 4640 en

    Function key assignment for selecting individual menu items

    Confirmation of the selected menu item

    Return to next higher menu level

    Selection of individual menu items within a menu level

    Function key assignment for entering the password

    Selecting a position

    Changing a position

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 32/73 4640 en

    Date Time

    08/01/2010 17:16:42

    Output current 20.8A

    Output voltage 25.1V

    11.2 The main window

    The display is able to show 3 different measured values in the initial state. The

    type of measured value to be displayed is specified in the respective submenu.

    The measured variables and measured values are displayed in clear text. If the

    text has too many characters for it to be displayed in full, a scrolling text

    appears.

    Press the keys to change between the 3 specified measured

    values. Press the key to return to the main menu.

    The symbol indicates that a new log file entry is present, which has

    not yet been viewed and acknowledged. Press the key to jump directly to the

    log file entry.

    11.3 Passwords

    Different menus are accessible by means of a password only.

    The password 1 is set to 001 in the factory, and password 2 is set to 002.

    Caution! For safety reasons, it is important to change this password after

    commissioning the system.

    11.4 Menu structure

    The menu structure and the individual menu levels and menu items are the

    same for all applications. Only the assignment and meaning of the digital

    inputs, the measured values and the type of SAT-Bus users depend on the

    individual user.

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 33/73 4640 de

    Main menu

    Measured values

    Log file

    Test

    Status request

    Setup

    Voltages

    Currents

    Temperatures

    Date and time

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 34/73 4640 de

    Main menu

    Measured values

    Log file

    Test

    Status request

    Setup

    Events

    Error

    Log file complete

    Delete log file

    log file [ 1] 09/10/09 11:31:48 sat-bus status Mains error [ 25]: active

    Delete log file?

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 35/73 4640 de

    LED ( display )

    Relay ( 1 ... 16 )

    Main menu

    Measured values

    Log file

    Test

    Status request

    Setup

    Main menu

    Measured values

    Log file

    Test

    Status request

    Setup

    Digital inputs

    Components

  • Operating instructions

    Rectifier system TEBECHOP 3000 HDI

    10.11.10 BGOE/COBS 36/73 4640 de

    Main menu

    Measured values

    Log file

    Test

    Status request

    Setup

    System setting

    Changing characteristics

    Normal operation

    Standby operation

    Voltage settings

    Normal voltage operation

    Voltage standby

    Shunt values

    Password 1

    ***

    1st Rated shunt value

    2nd Rated shunt value

    Password 1

    ***

    Password 1

    ***

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 37/73 4640 de

    Reset hold function PW0

    Hold functions

    Reset

    Redundancy

    Redundancy

    factor

    LED hold function PW1

    Password 1

    ***

    Relay 1

    .

    .

    Relay 16

    Relay hold function PW1

    Password 1

    ***

    LED 1

    .

    .

    LED 18

    Redundancy

    Password 1

    ***

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 38/73 4640 de

    System time

    Date

    Time

    Times

    Password 1

    ***

    Urgent fault

    Non-urgent fault

    Collective report

    Redundancy

    Relay test

    Delay on request

    Delay if engaged

    Delay times

    Other times

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 39/73 4640 de

    GSR 1

    GSR 2

    GSR 3

    GSR 4

    GSR 5

    Status mask

    Input approved

    Urgent fault

    Non-urgent fault

    Insert in log

    Transmission report

    Collective report MCU input passive

    Hold error message

    Boundary value

    monitoring

    Password 2

    ***

    Analogue input

    Upper limit value

    Lower limit value

    Hysteresis

    Configuration filter

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 40/73 4640 de

    Configuration

    Configuration flags

    Status mask

    Modem available

    Sensor cable operation

    MCU

    Invert 1st I-channel

    Invert 2nd I-channel

    Endless dialling attempt

    Transmit reports Protocol service conn.

    Display ADBUS values

    New prot. unit fault.

    Masks

    Password 2

    ***

    Status mask

    Satellite in self-test

    Module in config. phase

    Watchdog reset

    Bus error

    Master timeout

    Fan fault Received illeg. command

    Network/battery failure

    Temperature sensor failure

    Input voltage failure

    Unit does not respond

    Module failed

    Module overvoltage

    Module overtemperature

    Module switched off

    Fault analysis

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 41/73 4640 de

    Urgent fault

    Status mask

    Fan fault

    Input voltage failure

    Module failed

    Module overvoltage

    Module switched off

    Non-urgent fault

    Collective report

    Status mask

    Fan fault

    Input voltage failure

    Module failed

    Module overvoltage

    Module switched off

    Status mask

    Fan fault

    Input voltage failure

    Module failed

    Module overvoltage

    Module switched off

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 42/73 4640 de

    Password 1

    Password 2

    Passwords

    Display settings

    Language

    Status mask

    German English

    Language 3

    Display

    Standard display

    Display 1

    Output voltage

    Output current

    Date and time

    Display 2

    Display 3

    All measured variables recorded in the system can be

    selected.

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 43/73 4640 de

    Brightness

    = 10-100 %

    = 10-100 %

    Contrast

    Back light time

    = 10-255 s

    Return time

    = 10-255 s

    Expert mode

    Status mask

    Expert mode on

    Expert mode off

  • Operating instructions

    Rectifier system TEBECHOP 3000 HDI

    10.11.10 BGOE/COBS 44/73 4640 de

    12 Main menu

    To switch from the initial state to the main menu, press the key .

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 45/73 4640 de

    13 Measured values

    Here, the three measured values which are displayed in the initial state are

    displayed. All measured values recorded in the system can be selected.

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 46/73 4640 de

    Logbuch [ 1]

    09.02.06 11:31:48 SAT-Bus Status

    Netzfehler

    [ 25]:aktiv

    14 Log file

    An event history of all status changes is stored in the log file. Up to 200 of the

    last status changes can be read out using a circular buffer. A threshold can be

    set to provide a warning for the number of past status changes.

    Sequential log file entry number

    Date and time of log file entry

    Fault class: SAT-Bus status or digital input

    Description of event

    Current status: Active or not active

    Address of the SAT-Bus user or number of the

    digital input

    The complete log file content can be deleted from within each individual log

    file entry.

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 47/73 4640 de

    15 Test

    LED

    All LEDs of the display (4x) and of the LED board (13x) are subjected to a

    function test.

    Relay

    The function of each individual relay ( 1 to 16 ) of all connected RELIO boards

    is tested when selected.

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 48/73 4640 de

    Batteriesicher. ausgelst

    aktiv

    Komponente

    25

    16 Status request

    Components

    The status mask of each SAT-Bus component defined in the system can be

    displayed.

    Type of SAT-Bus component defined in the

    system

    Address of the SAT-Bus component

    Type of all possible SAT-Bus components:

    MCU main board

    MCU-SAT measuring box

    MCU-SAT I/O box

    MCU-SAT relay box

    DC-DC converter

    STATIC BY-PASS

    DSP adapter

    AC measuring board

    DC-DC converter

    Unknown user

    A maximum of 31 SAT-Bus components can be addressed in one system.

    Digital inputs

    Assignment, description and status of the digital inputs are displayed.

    Type of digital input

    Logical status of digital input

    (active; inactive)

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 49/73 4640 de

    17 Setup menu

    17.1 The System configuration menu

    17.2 Changing characteristics menu

    Submenus are only accessible by means of password 1. The password is set to

    001 in the factory.

    Caution! For safety reasons, it is important to change this password after

    commissioning the system.

    The DC-DC converter has two operating modes or characteristics, which

    can be activated by changing over the operating mode via the satellite bus

    (SAT-Bus) by means of the MCU 2500 HDI remote monitoring system.

    17.3 Normal operation

    Standard operating mode, normal operation setting.

    The output voltage can be set by means of the MCU 2500 HDI remote

    monitoring system.

    17.4 Standby operation

    A changeover to the 2nd voltage level (standby voltage) occurs through the MCU 2500 HDI remote monitoring system (value, see technical data sheet).

    The output voltage can be set by means of the MCU 2500 HDI remote

    monitoring system.

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 50/73 4640 de

    17.5 Voltage settings menu

    Submenus are only accessible by means of password 1. The password is set to

    001 in the factory.

    Caution! For safety reasons, it is important to change this password after

    commissioning the system.

    The DC-DC converter has two operating modes or characteristics, which

    can be activated by changing over the operating mode via the satellite bus

    (SAT-Bus) by means of the MCU 2500 HDI remote monitoring system.

    System setting | Voltage settings

    The output voltage (normal operation) and the 2nd

    voltage level (standby

    operation) can be set individually.

    17.6 Shunt values menu

    Submenus are only accessible by means of password 1. The password is set to

    001 in the factory.

    Caution! For safety reasons, it is important to change this password after

    commissioning the system.

    System setting | Shunt values

    Setting of the first rated shunt value; setting range 0 ... 9999 A

    Setting of the second rated shunt value; setting range 0 ... 9999 A

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 51/73 4640 de

    17.7 Hold functions menu

    System setting | Reset hold function

    In this menu, the hold function can be reset for all LEDs of the LED board and

    the display as well as the relays.

    System setting | LED hold function Submenu only accessible by means of password 1. The password is set to

    001 in the factory.

    Caution! For safety reasons, it is important to change this password after

    commissioning the system.

    A hold function can be set for all LEDs of the LED board and the display.

    When the event which has caused the LED to light up no longer exists, the

    LED switches to flashing status (hold status). The status is reset by pressing the

    Reset button on the LED board or via the menu item

    Reset hold function.

    System setting | Relay hold function

    Submenu is only accessible by means of password 1. The password is set to

    001 in the factory.

    Caution! For safety reasons, it is important to change this password after

    commissioning the system.

    A hold function can be set for all relays. After discontinuation of the event

    which led to the activated status of the relay, the relay remains in this active

    status (hold status). The status is reset by pressing the Reset button on the LED

    board or via the menu item Reset hold function.

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 52/73 4640 de

    System setting | Redundancy

    Submenus are only accessible by means of password 1. The password is set to

    001 in the factory.

    Caution! For safety reasons, it is important to change this password after

    commissioning the system.

    Reset redundancy

    A possibly pending redundancy fault is reset. The maximum value of the

    parallel-running DC-DC converters is re-determined.

    Redundancy factor

    Input of the redundancy value x for n+x monitoring

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 53/73 4640 de

    18 Times menu

    Submenus are only accessible by means of password 1. The password is set to

    001 in the factory.

    Caution! For safety reasons, it is important to change this password after

    commissioning the system.

    System time

    System time | Date

    Input or display of the system date.

    System time | Time

    Input or display of the system time.

    Delays

    Delays | Urgent fault

    Setting of the delay time for the urgent fault message. Setting range: 0 ... 65535 seconds

    Delays | Non-urgent fault

    Setting of the delay time for the non-urgent fault message. Setting range: 0 ... 65535 seconds

    Delays | Collective fault alarm

    Setting of the delay time for the common fault messages. Setting range: 0 ... 65535 seconds

    Delays | Redundancy

    Setting of the delay time after which a redundancy error is signalled.

    Setting range: 0 ... 65535 seconds

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 54/73 4640 de

    Other times

    Other times | Relay test

    Setting of the relay test duration for the menu item Other times | Relay test. Setting range: 0 ... 65535 seconds

    Other times | Delay on request

    Setting of the delay, following which a modem connection between the MCU

    and a control station is to be cut off if the control station does not respond.

    Setting range: 0 ... 65535 seconds

    Other times | Delay if engaged

    Setting of the delay, following which a new connection is to be set up if the

    line is engaged.

    Setting range: 0 ... 65535 seconds

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 55/73 4640 de

    19 Boundary value monitoring menu

    Submenus are only accessible by means of password 2. The password is set to

    002 in the factory.

    Caution! For safety reasons, it is important to change this password after

    commissioning the system.

    GSR 1...5 Relays|

    Each of the 5 limit-value monitoring relays (GSR) can be programmed or read

    out via this menu item.

    Caution! The settings of the limit-value monitoring relays (GSR) should only

    be changed by personnel who have excellent system knowledge.

    GSR 1...5 | Analogue input

    Input of the measuring channel whose measured value is to be monitored.

    GSR 1...5 | Upper limit value

    Input of upper limit value to be monitored.

    GSR 1...5 | Lower limit value

    Input of lower limit value to be monitored.

    GSR 1...5 | Hysteresis

    Input of hysteresis band width. This value applies to the upper and

    lower limit value.

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 56/73 4640 de

    Status mask

    Input approved

    Urgent fault

    Non-urgent fault

    Insert in log

    Transmission report

    Collective report MCU input passive

    Hold error message

    GSR 1...5 | Configuration filter

    This filter mask specifies which statuses or actions are affected or are to be

    triggered if a limit value has not been reached or is exceeded.

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 57/73 4640 de

    Status mask

    Modem available

    Sensor cable operation

    MCU

    Invert 1st I-channel

    Invert 2nd I-channel

    Endless dialling attempt

    Transmit reports Protocol service conn.

    Display ADBUS values

    New prot. unit fault.

    20 Configuration menu

    Submenus are only accessible by means of password 2. The password is set to

    002 in the factory.

    Caution! For safety reasons, it is important to change this password after

    commissioning the system.

    Configuration flags

    The system is configured via this status mask by selecting the individual lines.

    Caution! The settings of this status mask should only be changed by

    personnel who have excellent system knowledge.

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 58/73 4640 de

    Status mask

    Satellite in self-test

    Module in config. phase

    Watchdog reset

    Bus error

    Master timeout

    Fan fault Received illeg. command

    Network/battery failure

    Temperature sensor failure

    Input voltage failure

    Unit does not respond

    Module failed

    Module overvoltage

    Module overtemperature

    Module switched off

    Configuration flags | Masks

    The status masks are used for configuration of the different error messages.

    Caution! The settings of these status masks should only be changed by

    personnel who have excellent system knowledge.

    The status masks of the individual evaluations / messages are regularly

    compared with the status of each SAT-bus user. The appropriate actions are

    triggered depending on the result of the comparison.

    Masks | Fault analysis

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 59/73 4640 de

    Status mask

    Fan fault

    Input voltage failure

    Module failed

    Module overvoltage

    Module switched off

    Masks | Urgent fault

    Masks | Non-urgent fault

    Masks | Collective report

    The status masks are used for configuration of the different error messages.

    Caution! The settings of these status masks should only be changed by

    personnel who have excellent system knowledge.

    The status masks of the individual evaluations / messages are regularly

    compared with the status of each SAT-bus user. The appropriate actions are

    triggered depending on the result of the comparison.

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 60/73 4640 de

    Configuration | Passwords

    The status mask is used for changing the passwords 1 and 2.

    Caution! For safety reasons, it is important to change this password after

    commissioning the system.

    Passwords | Password 1

    The password is set to 001 in the factory. Specification or alteration of the password 1 (000 ... 999)

    Passwords | Password 2

    The password is set to 002 in the factory. Specification or alteration of the password 2 (000 ... 999)

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 61/73 4640 de

    Status mask

    German English

    Language 3

    21 Display configuration menu

    Display configuration | Language

    This menu item is only available when expert mode is switched on.

    In expert mode, only the menu language can be set to German or English. The measured values and texts always appear in the third language set (German,

    English, French, Spanish, .. ) When expert mode is off, the menu language, the measured values and the

    texts are only available in the third language.

    Display | Standard display

    Here, the three measured values which are to be displayed in the initial state

    are defined.

    All measured values recorded in the system can be selected.

    Display | Brightness

    The brightness of the display can be set between 10% and 100%.

    Display | Contrast

    The contrast of the display can be set between 10% and 100%.

    Display | Back light time

    The back light time of the display can be set between 10 and 255 seconds.

    Display | Return time

    The period after which the display reverts back to the initial state once the

    menu is not used can be set between 10 and 255 seconds.

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 62/73 4640 de

    Status mask

    Expert mode on

    Expert mode off

    22 Expert mode menu

    Setup | Expert mode

    When expert mode is switched on, more extensive information about the

    system is available. (Only for service purposes)

    Caution! The settings of this status mask should only be changed by

    personnel who have excellent system knowledge.

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 63/73 4640 de

    23 Commissioning

    With the supply voltage switched off, insert the power modules in the equipment rack.

    Screw power modules in place using countersunk screws M3 x 10, Part No. 786041

    Apart from power module No. 3 fixing is by means of the centre front panel fixing screw

    Screw front panel in place using 5x M3 x 10 Part No. 786042 and contact washer Part No. 787515

    Switch on the supply voltage

    Wait for the end of the initialisation phase of the power modules

    (the end of this period is indicated by the green Operation / LED

    and the red Fault/ LED no longer flashing),

    If the initialisation phase is not completed properly for a particular module, switch off the supply voltage.

    Following a period of approx. 3 minutes which is required for the internal

    discharge of the capacitors, initialisation must be carried out again.

    When the initialisation is complete, the unit will run up to the set

    DC-DC converter output voltage with a time delay; the green

    operation / LED will then be activated.

    If not all the slots in the equipment rack are fitted with DC-DC converters, the empty slots must be covered with a blank insert

    (Part No. 514414).

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 64/73 4640 de

    24 Operating modes

    The DC-DC converter has two operating modes or characteristics, which

    can be activated by changing over the operating mode via the satellite bus

    (SAT-Bus) by means of the MCU 2500 HDI remote monitoring system.

    24.1 Normal

    Standard operating mode, normal operation setting.

    The output voltage can be set by means of the MCU 2500 HDI remote

    monitoring system.

    24.2 Standby)

    A changeover to the 2nd voltage level (standby voltage) occurs through an external contact (value, see technical data sheet).

    The output voltage can be set by means of the MCU 2500 HDI remote

    monitoring system.

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 65/73 4640 de

    25 Parallel operation

    Parallel operation of several equipment racks is also possible without

    decoupling diodes at the rack output.

    Note:

    DC-DC converters with output voltage 110/220V have integral decoupling

    diodes.

    In order to distribute the output current symmetrically, connect the equipment

    racks together by means of contact X17:1 or 2 (parallel-running connector). The SAT-Bus connection (X9 or X10) must also be inserted for parallel

    operation with several equipment racks to enable data to be exchanged between

    the racks (BENNING SAT cable or patch cable with Western plug 8-pin RJ45). An active parallel-running circuit enables a parallel-running tolerance of

    approximately. 5 % of Irated to be achieved on load from 30 - 100%.

    When an additional unit is connected, the voltage and therefore current

    balancing can take up to 5 minutes (10 mV control steps).

    For safe holding of the fault contact, a minimum basic load of >

    5 % is required with parallel operation.

    The SAT-Bus cable must be connected when operating several

    equipment racks in parallel to enable data to be exchanged

    between the racks. In addition to this, the parallel-running connection of the racks must also be connected together.

    Note: Parallel connection, up to 24 units: direct addressing

    Further units, SAT-Bus connection only via bus converter

    (Part No. 525886, see Description: 4553)

    The TEBECHOP bus converter is provided for simultaneously operating more

    than 24 DC-DC converters in parallel with one MCU in conjunction with the

    MCU 2500 HDI remote monitoring system. The maximum number of

    controllable DC-DC converters is limited to 99 units by the MCU 2500.

    The bus converter automatically configures all DC-DC converters associated

    with the group. It is not necessary to set the parameters for each individual DC-

    DC converter.

    Up to 19 TEBECHOP bus converters combine and control up to 12

    TEBECHOP devices in a group. The maximum number of controllable DC-DC

    converters is limited to 99. (by the MCU 2500)

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 66/73 4640 de

    26 Satellite

    The satellite integrated inside the DC-DC converter controls, regulates and

    monitors the unit. For the user the satellite looks like a digital interface to the

    DC-DC converter. The DC-DC converter obtains the required data via this

    interface from other units of the MCU 2500 HDI remote monitoring system

    to establish the desired operating state. This requires that the satellite has the

    complete set of parameters for open and closed loop control as well as all data

    relating to the operating states of the DC-DC converter.

    The satellite is a principal unit in the MCU 2500 HDI remote monitoring

    system, enabling power supply systems to be controlled and monitored via the

    public telephone network.

    The further functions of the satellite include the following:

    (Faults are transmitted by the MCU 2500 HDI remote monitoring system)

    1. Two adjustable operating modes

    2. Unit monitoring with logically combined urgent alarm

    3. Input voltage monitoring with logically combined non-urgent alarm (time delay of the alarms adjustable)

    4. Voltage tracking (UrEG. adaptation)

    5. Power management (Po.MA)

    6. Serial SAT-Bus interface via mating plug and socket system for communication when several DC-DC converters are operating in parallel

    26.1 Standard function

    After switching on the DC-DC converter and an initialisation phase of

    approximately 30 seconds, the unit runs up to the last saved output voltage.

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 67/73 4640 de

    26.2 LEDs, power modules

    Two LEDs are provided in the front panel of the equipment rack for each

    power module with the following meaning:

    LED: Signal state: Meaning:

    LED green,

    Operation/

    LED, light steady The unit is operating correctly

    LED green,

    Operation/

    LED red,

    Fault/

    Both LEDs, synchronous

    flashing light

    Input voltage failure (with

    external auxiliary supply!)

    LED red,

    Fault/

    LED, light steady Unit fault

    LED red,

    Fault/

    LED, flashing light Output fuse blown

    LED green,

    Operation/

    LED red,

    Fault/

    LED, light steady

    LED, flashing light,

    2 x in succession

    Fan failure

    LED red,

    Fault/

    LED, flashing light,

    2 x in succession

    Temperature too high.

    LED red,

    Fault/

    LED, flashing light,

    3 x in succession

    Overvoltage protection

    tripped

    For error identification, the relevant error code is transmitted via the SAT bus

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 68/73 4640 de

    26.3 LEDs, MCU 2500 HDI remote monitoring system

    (Indicators for BUS activities, for service purposes only)

    1 Fault LED; (red)

    Status Meaning

    lights Fault or initialisation phase

    flashes quickly MCU is not connected to SAT-Bus

    flashes briefly No fault; MCU is SAT-Bus master

    extinguishes briefly Fault; MCU is SAT-Bus master

    off No fault; MCU is user on the SAT-Bus

    2 Running LED; (green)

    Status Meaning

    lights Normal operation

    flashes quickly No SAT-Bus communication detected

    off Severe MCU fault

    3 Combinations of the LED statuses

    Symbol

    lights lights

    Meaning: Initialisation phase; takes a few ms to some seconds

    flashes quickly flashes quickly

    Meaning: MCU has started, SAT-Bus not yet recognised

    lights flashes quickly

    Meaning: SAT-Bus communication recognised, MCU waiting for

    connection

    lights off

    Meaning: Normal operation on the SAT-Bus

    lights flashes briefly

    Meaning: Normal operation with MCU as master

    (also during diagnostic operation via PC)

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 69/73 4640 de

    27 Alarms

    27.1 Alarm contacts

    The following are located on the rear in the version equipment rack 5-way for

    4x power modules, incl. MCU 2500 HDI remote monitoring system:

    2x alarm terminals with voltage-free contacts.

    Configuration by means of the TEBE MCU Service software,

    see Description: 3293

    Relay 1 (X104) and Relay 2 (X106),

    screw terminals 1mm/ AWG 18,

    max. contact loading:

    30 V 2 A, AC/DC

    27.2 Urgent alarm (unit fault SV1)

    The Device fault alarm contact of the MCU 2500 HDI remote monitoring

    system is closed in the event of a fault, and the green Operation / LED

    lamps extinguish and the red Fault/ (unit fault) LED lights.

    These signals are internally delayed by approximately 30 seconds.

    Device fault (urgent alarm) is transmitted under the following conditions:

    - Overvoltage protection has tripped

    - Temperature too high

    - Regulator or power stage defective

    - Output fuse blown

    27.3 Non-urgent alarm (mains fault SV2)

    This signal follows AC undervoltage or mains power failure; the alarm contact

    of the MCU 2500 HDI remote monitoring system is closed.

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 70/73 4640 de

    27.4 Overload detection/Overload behaviour

    When the output of the DC-DC converter is overloaded or a short circuit

    occurs, the 2-way rated current can be supplied for 2 seconds.

    The consequence of current limitation if applicable is a drop of the output

    voltage in the event of a short circuit to < 1 V

    During this time, the short-circuit should be isolated through activating a fuse.

    If after this time the short-circuit or overload are still present and the output

    current does not drop to 100%, after approx. 5 seconds the output voltage is

    switched off.

    After the fault has been repaired, the unit can be restarted when it has been

    isolated from the mains for about 10 s or it has been reset via the MCU 2500

    HDI remote monitoring system.

    Note: The rating of the fuse must be observed.

    2x Inenn

    Inenn

    0 1 2 3 4 5 6 7 8 9 10

    t

    I

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 71/73 4640 de

    27.5 Temperature monitoring

    The DC-DC converter is equipped with a temperature monitor on the heat sink

    which operates as follows:

    Assumption:

    The DC-DC converter is operated at rated current.

    1. Heat sink temperature continues to rise

    2. At T > 122C DC-DC converter power is reduced

    3. At T > 130C DC-DC converter is switched off

    4. Red Fault/ LED (unit fault) illuminates

    5. Green Operation/ LED extinguishes 6. Urgent alarm/Device fault SV1 is transmitted.

    After the heat sink has cooled down, the DC-DC converter is

    automatically reset. The DC-DC converter is then switched on

    again.

    27.6 Overvoltage protection

    In the event of overvoltage (see technical data sheet) the unit is switched off.

    The overvoltage protection is designed to protect the battery and the unit. After

    the fault has been repaired, the unit can be restarted when it has been isolated

    from the mains for about 10 s or it has been reset via the MCU 2500 HDI

    remote monitoring system.

    The red Fault/ LED (UA too high flashing rate 3 x) and urgent alarm are also reset by this action.

    DC-DC converters 24 60V: internal hardware setting, additional shut down value (up to the set hardware shut down value) configurable by the software

    DC-DC converter 110/220V: internal hardware setting (Poti).

    It is not possible to test the overvoltage protection with an externally controlled power supply unit as the DC-DC converter

    recognises an externally fed voltage and fails to switch off as a

    result.

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 72/73 4640 de

    27.7 Fuse monitoring

    An output fuse is already integrated for protecting the unit. The monitoring

    system integrated within the unit initiates an alarm when the output fuse has

    blown.

    The red "Fault"/" " LED (Fault - Fuse, flashing) illuminates, the Device fault alarm contact of the MCU 2500 HDI remote monitoring system is

    closed, and the green Operation / LED lamps extinguish.

    27.8 Incorrect polarity

    Output voltage 24-60V:

    Incorrect polarity at the output is detected and the internal monitoring prevents

    the DC-DC converter from being started.

    Output voltage 110-220V:

    Incorrect polarity at the output activates the integrated fuse.

    27.9 Fan fault

    When the fan is running (temperature- and current-controlled), an air-flow

    monitor monitors the operation of the fan. In the event of a fault, the following

    occurs:

    Red Fault/ LED (Fault - Fan flashing 2 x in succession) illuminates, green "Operation"/ " " LED illuminates continuously

    The fault code is transmitted via the SAT bus

    Non-urgent alarm (SV2) is signalled with a time delay via the SAT-Bus to the MCU 2500 HDI remote monitoring system (for delay time,

    please refer to the technical data sheet).

    The output current is reduced automatically depending on the temperature.

    In this way it is possible to continue to operate the unit (with reduced power).

  • Operating instructions

    DC-DC Converter TEBECHOP 3000 HDI DC

    10.11.10 BGOE/COBS 73/73 4640 de

    28 Fuses

    According to the technical data sheet.

    Access to the input and output fuses is only possible after removing and

    opening the unit.