Page 1: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:
Page 2: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

Inspection ReportJohn Doe

Property Address:123 Main St.

Anytown AZ 85298

123 Main St. Anytown, AZ USA 85298

360 Degree Home Inspections, LLC

Derreck Weatherford 64330www.360inspectionsaz.com

Gilbert, AZ 85298480-818-6323

360 Degree Home Inspections, LLC Doe

123 Main St. Page 2 of 54

Page 3: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

Table of Contents

Cover Page.................................................................1

Table of Contents........................................................3

Intro Page ...................................................................4

1 Roof .........................................................................5

2 Exterior.....................................................................8

3 Electrical System ...................................................13

4 Plumbing System...................................................17

5 Basement, Foundation, Crawlspace andStructure ...................................................................20

6 Garage...................................................................23

7 Heating / Cooling ...................................................25

8 Doors, Windows and Interior..................................27

9 Insulation and Ventilation.......................................30

10 Built-In Kitchen Appliances ..................................31

12 Swimming Pools, Equipment and Safety .............32

General Summary.....................................................35

Invoice.......................................................................53

360 Degree Home Inspections, LLC Doe

123 Main St. Page 3 of 54

Page 4: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

Date: 9/21/2017 Time: 09:00 AM Report ID: 20170921-1Property:123 Main St.Anytown AZ 85298

Customer:John Doe

Real Estate Professional:

Comment Key or Definitions

The following definitions of comment descriptions represent this inspection report. All comments by the inspector should beconsidered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a secondopinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair orreplacement of item, component or unit should be considered before you purchase the property.

Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it appeared to befunctioning as intended allowing for normal wear and tear.

Functioning (OK) = This item, component or unit is functioning as intended.

Repair or Replace (RR) = The item, component or unit is not functioning as intended, or needs further inspection by aqualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.

Comment Key or Definitions

The following definitions of comment descriptions represent this inspection report. All comments by the inspector should beconsidered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a secondopinion or further inspection by a qualified contractor and all costs associated with further inspection fees and repair orreplacement of item, component or unit should be considered before you purchase the property.

Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it appeared to befunctioning as intended allowing for normal wear and tear.

Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whether or not it wasfunctioning as intended and will state a reason for not inspecting.

Not Present (NP) = This item, component or unit is not in this home or building.

Year the home was built:1996

Home Faces:North

Client Is Present:Yes

Weather:Clear

Temperature:Over 65

Rain in last 3 days:No

Home is occupied:No

360 Degree Home Inspections, LLC Doe

123 Main St. Page 4 of 54

Page 5: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

1. Roof

The inspector shall inspect from ground level or eaves: The roof covering. The gutters. The downspouts. The vents, flashings, skylights, chimney andother roof penetrations. The general structure of the roof from the readily accessible panels, doors or stairs.

The inspector is not required to: Walk on any roof surface, predict the service life expectancy, inspect underground downspout diverter drainage pipes,remove snow, ice, debris or other conditions that prohibit the observation of the roof surfaces, inspect antennae, lightning arresters, or similar attachments.

Styles & MaterialsRoof Covering:

Concrete tilesViewed roof covering from:

GroundLadderWalked roof

Roof-Type:GableHip

Roof Structure:Engineered wood trussesOSB roof deck

Method used to observe attic:Partially inaccessible (storage, ductwork, low clearance)

Attic info:Attic accessScuttle hole

IN RR OK

1.0 ROOF COVERINGS • •

1.1 FLASHINGS • •

1.2 SKYLIGHTS, CHIMNEYS AND ROOF PENETRATIONS • •

1.3 ROOF DRAINAGE SYSTEMS (Gutters and Downspouts) • •

1.4 ROOF STRUCTURE AND ATTIC • •

IN= Inspected, RR= Repair or Replace, OK= Functioning IN RR OK

Comments:

1.0 (1) Identified roof tiles are damaged/displaced and leave roof decking exposed to potential moisture penetration/damage. Recommend repair/evaluation by a qualified expert.

1.0 Item 1(Picture) NE corner of house 1.0 Item 2(Picture) Over garage

360 Degree Home Inspections, LLC Doe

123 Main St. Page 5 of 54

Page 6: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

1.0 Item 3(Picture) South side of house

1.0 (2) Mudcap is damaged. Recommend repair/evaluation by a qualified expert.

1.0 Item 4(Picture) Center of house.

1.1 Identified valley flashing has some built up debris that could lead to issues with water drainage and potential waterponding. Recommend removal of debris by a qualified person.

1.1 Item 1(Picture) NW valley of roof. 1.1 Item 2(Picture) NW valley of roof

360 Degree Home Inspections, LLC Doe

123 Main St. Page 6 of 54

Page 7: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

1.4 Roof decking is damaged and showing signs of moisture damage/penetration. Recommend repair/evaluation by aqualified expert.

1.4 Item 1(Picture) South part of attic

The roof of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, someareas can go unnoticed. Roof coverings and skylights can appear to be leak proof during inspection and weather conditions. Our inspection makes anattempt to find a leak but sometimes cannot. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this reportshould be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to thecomments in this inspection report.

360 Degree Home Inspections, LLC Doe

123 Main St. Page 7 of 54

Page 8: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

2. Exterior

The inspector shall inspect: The siding, flashing and trim. All exterior doors, decks, stoops, steps, stairs, porches, railings, eaves, soffits and fascias. Andreport as in need of repair any spacing between intermediate balusters, spindles, or rails for steps, stairways, balconies, and railings that permit thepassage of an object greater than four inches in diameter. A representative number of windows. The vegetation, surface drainage and retaining walls whenthese are likely to adversely affect the structure. And describe the exterior wall covering.

The inspector is not required to: Inspect or operate screens, storm windows, shutters, awnings, fences, outbuildings, or exterior accent lighting, Inspectitems, including window and door flashings, which are not visible or readily accessible from the ground, Inspect geological, geotechnical, hydrological and/orsoil conditions, Inspect recreational facilities, Inspect seawalls, break-walls and docks, Inspect erosion control and earth stabilization measures, Inspect forsafety type glass, Inspect underground utilities, Inspect underground items, Inspect wells or springs, Inspect solar systems, Inspect swimming pools orspas, Inspect septic systems or cesspools, Inspect playground equipment, Inspect sprinkler systems, Inspect drain fields or drywells, Determine the integrityof the thermal window seals or damaged glass.

Styles & MaterialsSiding Material:

StuccoTypical cracks present

Exterior Entry Doors:Solid core wood front doorMetal clad insulated side entry doorDual pane sliding glass door

Driveway & sidewalks:ConcreteGood condition

IN RR OK

2.0 SIDING, FLASHING AND TRIM • •

2.1 EAVES, SOFFITS AND FASCIAS • •

2.2 DOORS (Exterior) • •

2.3 DECKS, BALCONIES, STOOPS, STEPS, AREAWAYS, PORCHES, PATIO/ COVER AND APPLICABLERAILINGS

• •

2.4 VEGETATION, GRADING, DRAINAGE, DRIVEWAYS, PATIO FLOOR, WALKWAYS AND RETAINING WALLS(With respect to their effect on the condition of the building)

• •

2.5 FENCES AND GATES • •

IN= Inspected, RR= Repair or Replace, OK= Functioning IN RR OK

Comments:

2.0 Stucco siding is damaged. Recommend repair/evaluation by a qualified person.

2.0 Item 1(Picture) Backyard patio

360 Degree Home Inspections, LLC Doe

123 Main St. Page 8 of 54

Page 9: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

2.1 (1) Fascia wood directly exposed to elements in several areas on all sides of house. It is recommended to paint allexposed wood to prevent damage/deterioration from elements. Recommend paint as needed by a qualified person.

2.1 Item 1(Picture) NW corner of house 2.1 Item 2(Picture) NW corner of house

2.1 Item 3(Picture) NW corner of house 2.1 Item 4(Picture) NE corner of house

2.1 Item 5(Picture) North side of house 2.1 Item 6(Picture) East side of house

360 Degree Home Inspections, LLC Doe

123 Main St. Page 9 of 54

Page 10: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

2.1 Item 7(Picture) East side of house 2.1 Item 8(Picture) Saw corner of house

2.1 (2) Bird block screen is missing/damaged in identified areas. Recommend repair/evaluation by a qualified person.

2.1 Item 9(Picture) North side of house 2.1 Item 10(Picture) North side of house

2.2 Rear sliding door doesn't lock properly. Recommend repair/evaluation by a qualified person.

2.2 Item 1(Picture) Sliding rear door

360 Degree Home Inspections, LLC Doe

123 Main St. Page 10 of 54

Page 11: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

2.4 It is recommended to trim all vegetation/plants/trees at least 1 foot from any portion of the house to prevent anydamage/moisture penetration to the house. Recommend trimming as needed.

2.4 Item 1(Picture) NW corner of house 2.4 Item 2(Picture) SW corner of house

2.5 (1) Fence block is loose. Recommend repair/evaluation by a qualified person.

2.5 Item 1(Picture) West side of house

2.5 (2) Side gate doesn't self close. Recommend complying with City of Phoenix for barrier protection when there is apool in the backyard.

2.5 Item 2(Picture) East side of house

360 Degree Home Inspections, LLC Doe

123 Main St. Page 11 of 54

Page 12: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

The exterior of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern,some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should beconsidered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments inthis inspection report.

360 Degree Home Inspections, LLC Doe

123 Main St. Page 12 of 54

Page 13: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

3. Electrical System

The inspector shall inspect: The service line. The meter box. The main disconnect. And determine the rating of the service amperage. Panels, breakersand fuses. The service grounding and bonding. A representative sampling of switches, receptacles, light fixtures, AFCI receptacles and test all GFCIreceptacles and GFCI circuit breakers observed and deemed to be GFCI's during the inspection. And report the presence of solid conductor aluminumbranch circuit wiring if readily visible. And report on any GFCI-tested receptacles in which power is not present, polarity is incorrect, the receptacle is notgrounded, is not secured to the wall, the cover is not in place, the ground fault circuit interrupter devices are not properly installed or do not operateproperly, or evidence of arcing or excessive heat is present. The service entrance conductors and the condition of their sheathing. The ground fault circuitinterrupters observed and deemed to be GFCI's during the inspection with a GFCI tester. And describe the amperage rating of the service. And report theabsence of smoke detectors. Service entrance cables and report as in need of repair deficiencies in the integrity of the insulation, drip loop, or separation ofconductors at weatherheads and clearances.

The inspector is not required to: Insert any tool, probe or device into the main panel, sub-panels, downstream panel, or electrical fixtures. Operateelectrical systems that are shut down. Remove panel covers or dead front covers if not readily accessible. Operate over current protection devices. Operatenon-accessible smoke detectors. Measure or determine the amperage or voltage of the main service if not visibly labeled. Inspect the alarm system andcomponents. Inspect the ancillary wiring or remote control devices. Activate any electrical systems or branch circuits which are not energized. Operateoverload devices. Inspect low voltage systems, electrical de-icing tapes, swimming pool wiring or any time-controlled devices. Verify the continuity of theconnected service ground. Inspect private or emergency electrical supply sources, including but not limited to generators, windmills, photovoltaic solarcollectors, or battery or electrical storage facility. Inspect spark or lightning arrestors. Conduct voltage drop calculations. Determine the accuracy of breakerlabeling.

Styles & MaterialsElectrical Service Conductors:

Underground service lateralCopper220 voltsAppears satisfactory

Panel ground:Stranded copperPresumed UFER

Panel capacity:200 AMP

Panel Type:Circuit breakersAppears satisfactory

Branch wire 15 and 20 AMP:CopperAppears satisfactory

Wiring Methods:Conduit

Smoke detectors:Interconnected electricElectric with battery back upRecommend installing for safety reasons

IN RR OK

3.0 SERVICE ENTRANCE LINES • •

3.1 METER BOX, MAIN DISCONNECT, SERVICE GROUNDING/BONDING and MAIN and DISTRIBUTION PANELS • •

3.2 BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF THEIR AMPERAGEAND VOLTAGE

• •

3.3 SWITCHES, RECEPTACLES, LIGHT FIXTURES AND VISIBLE WIRING (observed from a representative number) • •

3.4 POLARITY AND GROUNDING OF RECEPTACLES WITHIN 6 FEET OF INTERIOR PLUMBING FIXTURES, ANDALL RECEPTACLES IN GARAGE, CARPORT, EXTERIOR WALLS OF INSPECTED STRUCTURE

• •

3.5 OPERATION OF GFCI or AFCI (GROUND/ARC FAULT CIRCUIT INTERRUPTERS) • •

3.6 LOCATION OF MAIN AND DISTRIBUTION PANELS • •

3.7 SMOKE DETECTORS • •

IN= Inspected, RR= Repair or Replace, OK= Functioning IN RR OK

Comments:

360 Degree Home Inspections, LLC Doe

123 Main St. Page 13 of 54

Page 14: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

3.1 It is recommended that electrical panel be completely enclosed to prevent any possible damage to wiring/breakers.Recommend repair/evaluation by a qualified person.

3.1 Item 1(Picture) Main electrical panel

3.2 Identified breakers are on but do not have any wiring running to it at time of inspection. Recommend evaluation prior toclosing. FYI only.

3.2 Item 1(Picture) Main electrical panel

3.3 (1) Identified outlets are loose. Recommend repair/evaluation by a qualified person.

3.3 Item 1(Picture) Garage 3.3 Item 2(Picture) Front room

360 Degree Home Inspections, LLC Doe

123 Main St. Page 14 of 54

Page 15: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

3.3 Item 3(Picture) Master bathroom

3.3 (2) Outlet cover not properly attached. Recommend repair/evaluation by a qualified person.

3.3 Item 4(Picture) Master bedroom

3.6 NE corner of house

3.7 Smoke detectors are not operating appropriately/missing at the time of inspection. It is recommended that smokedetectors are replaced every 7-10 years and to have a CO detector with gas appliances. Recommend repair/evaluation by aqualified person.

3.7 Item 1(Picture) Bedroom 1 3.7 Item 2(Picture) Master bedroom

360 Degree Home Inspections, LLC Doe

123 Main St. Page 15 of 54

Page 16: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

The electrical system of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas ofconcern, some areas can go unnoticed. Outlets were not removed and the inspection was only visual. Any outlet not accessible (behind the refrigerator forexample) was not inspected or accessible. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this reportshould be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to thecomments in this inspection report.

360 Degree Home Inspections, LLC Doe

123 Main St. Page 16 of 54

Page 17: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

4. Plumbing System

The inspector shall: Verify the presence of and identify the location of the main water shutoff valve. Inspect the water heating equipment, includingcombustion air, venting, connections, energy sources, seismic bracing, and verify the presence or absence of temperature-pressure relief valves and/orWatts 210 valves. Flush toilets. Run water in sinks, tubs, and showers. Inspect the interior water supply including all fixtures and faucets. Inspect the drain,waste and vent systems, including all fixtures. Describe any visible fuel storage systems. Inspect the drainage sump pumps testing sumps with accessiblefloats. Inspect and describe the water supply, drain, waste and main fuel shut-off valves, as well as the location of the water main and main fuel shut-offvalves. Inspect and determine if the water supply is public or private. Inspect and report as in need of repair deficiencies in the water supply by viewing thefunctional flow in two fixtures operated simultaneously. Inspect and report as in need of repair deficiencies in installation and identification of hot and coldfaucets. Inspect and report as in need of repair mechanical drain-stops that are missing or do not operate if installed in sinks, lavatories and tubs. Inspectand report as in need of repair commodes that have cracks in the ceramic material, are improperly mounted on the floor, leak, or have tank componentswhich do not operate.

The inspector is not required to: Light or ignite pilot flames. Determine the size, temperature, age, life expectancy or adequacy of the water heater.Inspect interiors of flues or chimneys, water softening or filtering systems, well pumps or tanks, safety or shut-of valves, floor drains, lawn sprinkler systemsor fire sprinkler systems. Determine the exact flow rate, volume, pressure, temperature, or adequacy of the water supply.Determine the water quality or potability or the reliability of the water supply or source. Open sealed plumbing access panels. Inspect clothes washingmachines or their connections. Operate any main, branch or fixture valve. Test shower pans, tub and shower surrounds or enclosures for leakage. Evaluatethe compliance with local or state conservation or energy standards, or the proper design or sizing of any water, waste or venting components, fixtures orpiping. Determine the effectiveness of anti-siphon, back-flow prevention or drain-stop devices. Determine whether there are sufficient clean-outs foreffective cleaning of drains. Evaluate gas, liquid propane or oil storage tanks. Inspect any private sewage waste disposal system or component of. Inspectwater treatment systems or water filters. Inspect water storage tanks, pressure pumps or bladder tanks. Evaluate time to obtain hot water at fixtures, orperform testing of any kind to water heater elements. Evaluate or determine the adequacy of combustion air. Test, operate, open or close safety controls,manual stop valves and/or temperature or pressure relief valves. Examine ancillary systems or components, such as, but not limited to, those relating tosolar water heating, hot water circulation.

Styles & MaterialsPlumbing Water Supply (into home):

CopperSatisfactory where visibleBuried underground

Plumbing Water Distribution (inside home):CopperSatisfactory where visible

Washer Drain Size:2" Diameter

Plumbing Waste:ABS

Water Heater Power Source:Gas (quick recovery)

Water Heater Capacity:50 Gallon

Manufacturer:A.O. SMITH

Water Heater Location:Garage

Manufactured year:1996Extra Info : Serial #GH96-3213526-S45

IN RR OK

4.0 PLUMBING DRAIN, WASTE AND VENT SYSTEMS • •

4.1 PLUMBING WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES AND ANY LEAKS • •

4.2 HOT WATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND VENTS • •

4.3 TPR VALVE • •

4.4 CROSS CONNECTIONS • •

4.5 FUNCTIONAL FLOW AND FUNCTIONAL DRAINAGE • •

4.6 MAIN WATER SHUT-OFF DEVICE (Describe location) • •

4.7 FUEL STORAGE AND DISTRIBUTION SYSTEMS (Interior fuel storage, piping, venting, supports, leaks) • •

4.8 MAIN FUEL SHUT OFF (Describe Location) • •

IN= Inspected, RR= Repair or Replace, OK= Functioning IN RR OK

Comments:

360 Degree Home Inspections, LLC Doe

123 Main St. Page 17 of 54

Page 18: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

4.1 (1) Valve won't divert water from bath fixture to shower fixture properly. Recommend repair/evaluation by a qualifiedperson.

4.1 Item 1(Picture) Upstairs hall bathroom

4.1 (2) Shower head is leaking from area indicated. Recommend repair/evaluation by a qualified person.

4.1 Item 2(Picture) Master bathroom shower

4.1 (3) Master bathtub handle is broken/damaged. Recommend repair/replacement.

4.1 Item 3(Picture) Master bathtub

360 Degree Home Inspections, LLC Doe

123 Main St. Page 18 of 54

Page 19: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

4.4 The rear hose bib does not have a vacuum breaker installed to prevent cross contamination of the domestic watersupply from an attached garden hose. Recommend having these devices installed.

4.4 Item 1(Picture) Backyard hose bib

4.6 NE corner of house

The water meter was observed for 5 minutes with all the plumbing fixtures in the off position and there were no indications ofwater movement. This is a good indicator, but not definitive, that there are no major leaks when all plumbing fixture are in theoff position. FYI only.

4.6 Item 1(Picture) NE part of property by sidewalk

4.8 NE corner of house

The plumbing in the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern,some areas can go unnoticed. Washing machine drain line for example cannot be checked for leaks or the ability to handle the volume during drain cycle.Older homes with galvanized supply lines or cast iron drain lines can be obstructed and barely working during an inspection but then fails under heavy use.If the water is turned off or not used for periods of time (like a vacant home waiting for closing) rust or deposits within the pipes can further clog the pipingsystem. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase.It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

360 Degree Home Inspections, LLC Doe

123 Main St. Page 19 of 54

Page 20: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

5. Basement, Foundation, Crawlspace and Structure

The inspector shall inspect: The basement. The foundation. The crawlspace. The visible structural components. Any present conditions or clearindications of active water penetration observed by the inspector. And report any general indications of foundation movement that are observed by theinspector, such as but not limited to sheetrock cracks, brick cracks, out-of-square door frames or floor slopes.

The inspector is not required to: Enter any crawlspaces that are not readily accessible or where entry could cause damage or pose a hazard to theinspector, Move stored items or debris, Operate sump pumps with inaccessible floats, Identify size, spacing, span, location or determine adequacy offoundation bolting, bracing, joists, joist spans or support systems, Provide any engineering or architectural service, Report on the adequacy of any structuralsystem or component.

Styles & MaterialsFoundation:

Poured concretesatisfactory where visible

Floor Structure:Concrete slabSatisfactory where visible

Wall Structure:Wood frameSatisfactory where visible

Columns or Piers:Wood frame & stucco

Ceiling Structure:Satisfactory where visible2X4

IN RR OK

5.0 FOUNDATIONS, BASEMENTS AND CRAWLSPACES (Report signs of abnormal or harmful water penetration intothe building or signs of abnormal or harmful condensation on building components.)

• •

5.1 WALLS (Structural) • •

5.2 COLUMNS OR PIERS • •

5.3 FLOORS (Structural) • •

5.4 CEILINGS (structural) • •

IN= Inspected, RR= Repair or Replace, OK= Functioning IN RR OK

Comments:

5.0 Stem was is exposed in indicated areas. It is recommended to paint all exposed portions of stem wall to preventdamage from elements. Recommend painting as necessary.

5.0 Item 1(Picture) Front entry way 5.0 Item 2(Picture) NE corner of house

360 Degree Home Inspections, LLC Doe

123 Main St. Page 20 of 54

Page 21: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

5.0 Item 3(Picture) NE corner of house 5.0 Item 4(Picture) NE corner of house

5.0 Item 5(Picture) South side of house 5.0 Item 6(Picture) SW side of house

5.2 Backyard patio cover columns have exposed aggregate on all 4 sides. Recommend repair/painting to prevent andamage/deterioration.

5.2 Item 1(Picture) East column 5.2 Item 2(Picture) West column

360 Degree Home Inspections, LLC Doe

123 Main St. Page 21 of 54

Page 22: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

5.3 Indicated part of backyard patio concrete slab has exposed aggregate. Recommend repair to prevent damagedeterioration.

5.3 Item 1(Picture) Backyard patio

The structure of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern,some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should beconsidered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments inthis inspection report.

360 Degree Home Inspections, LLC Doe

123 Main St. Page 22 of 54

Page 23: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

6. Garage

Styles & MaterialsGarage Door Material:

MetalLight inserts

Garage Door Type:Two car garage with opener

Auto-opener Manufacturer:LIFT-MASTER

IN RR OK

6.0 GARAGE DOOR OPERATORS (Report whether or not doors will reverse when met with resistance) • •

6.1 OCCUPANT DOOR FROM GARAGE TO INSIDE HOME (FIRE SEPARATION DOOR) • •

6.2 GARAGE CEILINGS • •

6.3 GARAGE WALLS (INCLUDING FIREWALL SEPARATION) • •

6.4 GARAGE FLOOR • •

6.5 GARAGE DOOR (S) • •

IN= Inspected, RR= Repair or Replace, OK= Functioning IN RR OK

Comments:

6.2 Unable to view all portions of garage ceiling, walls, floor due to occupant's belongings. Recommend evaluation prior toclosing.

6.2 Item 1(Picture) Garage

360 Degree Home Inspections, LLC Doe

123 Main St. Page 23 of 54

Page 24: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

6.3 Unable to view all portions of garage ceiling, walls, floor due to occupant's belongings. Satisfactory where visible.Recommend evaluation prior to closing.

6.3 Item 1(Picture) Garage

6.4 Unable to view all portions of garage ceiling, walls, floor due to occupant's belongings. Satisfactory where visible.Recommend evaluation prior to closing.

6.4 Item 1(Picture) Garage

360 Degree Home Inspections, LLC Doe

123 Main St. Page 24 of 54

Page 25: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

7. Heating / Cooling

The inspector shall inspect: The heating system and describe the energy source and heating method using normal operating controls. And report as inneed of repair electric furnaces which do not operate. And report if inspector deemed the furnace inaccessible. The central cooling equipment using normaloperating controls.

The inspector is not required to: Inspect or evaluate interiors of flues or chimneys, fire chambers, heat exchangers, humidifiers, dehumidifiers, electronicair filters, solar heating systems, solar heating systems or fuel tanks. Inspect underground fuel tanks. Determine the uniformity, temperature, flow, balance,distribution, size, capacity, BTU, or supply adequacy of the heating system. Light or ignite pilot flames. Activate heating, heat pump systems, or otherheating systems when ambient temperatures or when other circumstances are not conducive to safe operation or may damage the equipment. Overrideelectronic thermostats. Evaluate fuel quality. Verify thermostat calibration, heat anticipation or automatic setbacks, timers, programs or clocks. Determinethe uniformity, temperature, flow, balance, distribution, size, capacity, BTU, or supply adequacy of the cooling system. Inspect window units, through-wallunits, or electronic air filters. Operate equipment or systems if exterior temperature is below 60 degrees Fahrenheit or when other circumstances are notconducive to safe operation or may damage the equipment. Inspect or determine thermostat calibration, heat anticipation or automatic setbacks or clocks.Examine electrical current, coolant fluids or gasses, or coolant leakage.

Styles & MaterialsHeat Type:

Forced AirEnergy Source:

Natural gasNumber of Heat Systems (excluding wood):

One

Heat System Brand:CARRIER

Ductwork:Flex duct (insulated)

Filter Type:Very dirtyDisposable

Cooling Equipment Type:Air conditioner unit

Cooling Equipment Energy Source:Electricity

Central Air Manufacturer:CARRIERSerial # : 1696E02378

Number of AC Only Units:One

Number of tons:Unable to read the nomenclature

IN RR OK NI

7.0 HEATING EQUIPMENT • •

7.1 NORMAL OPERATING CONTROLS (Thermostat) • •

7.2 AUTOMATIC SAFETY CONTROLS • •

7.3 DISTRIBUTION SYSTEMS (including fans, pumps, ducts and piping, with supports, insulation, air filters,registers, radiators, fan coil units and convectors)

• •

7.4 PRESENCE OF INSTALLED HEAT SOURCE IN EACH ROOM • •

7.5 CHIMNEYS, FLUES AND VENTS (for gas water heaters or heat systems) • •

7.6 COOLING AND AIR HANDLER EQUIPMENT • •

7.7 NORMAL OPERATING CONTROLS (Thermostat) • •

7.8 PRESENCE OF INSTALLED COOLING SOURCE IN EACH ROOM • •

7.9 AIR FILTER(S) • •

7.10 TEMPERATURE SPLITS WITHIN RECOMMENDED RANGE • •

IN= Inspected, RR= Repair or Replace, OK= Functioning, NI= Not Inspected IN RR OK NI

Comments:

360 Degree Home Inspections, LLC Doe

123 Main St. Page 25 of 54

Page 26: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

7.6 A/C overflow drain pain was clear at the time of inspection and this indicates that A/C condensation is drainingappropriately at the time of inspection. FYI only.

7.6 Item 1(Picture) A\C overflow drain pan

7.9 Air filters are dirty and need to be replaced. Replace as necessary.

The heating and cooling system of this home was inspected and reported on with the above information. While the inspector makes every effort to find allareas of concern, some areas can go unnoticed. The inspection is not meant to be technically exhaustive. The inspection does not involve removal andinspection behind service door or dismantling that would otherwise reveal something only a licensed heat contractor would discover. Please be aware thatthe inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended thatqualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

360 Degree Home Inspections, LLC Doe

123 Main St. Page 26 of 54

Page 27: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

8. Doors, Windows and Interior

The home inspector shall observe: Walls, ceiling, and floors; Steps, stairways, balconies, and railings; Counters and a representative number of installedcabinets; and A representative number of doors and windows. The home inspector shall: Operate a representative number of windows and interior doors;and Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. Thehome inspector is not required to observe: Paint, wallpaper, and other finish treatments on the interior walls, ceilings, and floors; Carpeting; or Draperies,blinds, or other window treatments.

The inspector shall: Open and close a representative number of doors and windows. Inspect the walls, ceilings, steps, stairways, and railings. Inspectgarage doors and garage door openers by operating first by remote (if available) and then by the installed automatic door control. And report as in need ofrepair any installed electronic sensors that are not operable or not installed at proper heights above the garage door. And report as in need of repair anydoor locks or side ropes that have not been removed or disabled when garage door opener is in use. And report as in need of repair any windows that areobviously fogged or display other evidence of broken seals.

The inspector is not required to: Inspect paint, wallpaper, window treatments or finish treatments. Inspect central vacuum systems. Inspect safetyglazing. Inspect security systems or components. Evaluate the fastening of countertops, cabinets, sink tops and fixtures, or firewall compromises. Movefurniture, stored items, or any coverings like carpets or rugs in order to inspect the concealed floor structure. Move drop ceiling tiles. Inspect or move anyhousehold appliances. Inspect or operate equipment housed in the garage except as otherwise noted. Verify or certify safe operation of any auto reverse orrelated safety function of a garage door. Operate or evaluate security bar release and opening mechanisms, whether interior or exterior, includingcompliance with local, state, or federal standards. Operate any system, appliance or component that requires the use of special keys, codes, combinations,or devices. Operate or evaluate self-cleaning oven cycles, tilt guards/latches or signal lights. Inspect microwave ovens or test leakage from microwaveovens. Operate or examine any sauna, steam-jenny, kiln, toaster, ice-maker, coffee-maker, can-opener, bread-warmer, blender, instant hot waterdispenser, or other small, ancillary devices. Inspect elevators. Inspect remote controls. Inspect appliances. Inspect items not permanently installed.Examine or operate any above-ground, movable, freestanding, or otherwise non-permanently installed pool/spa, recreational equipment or self-containedequipment. Come into contact with any pool or spa water in order to determine the system structure or components. Determine the adequacy of spa jetwater force or bubble effect. Determine the structural integrity or leakage of a pool or spa.

Styles & MaterialsCeiling Materials:

DrywallWall Material:

DrywallFloor Covering(s):

CarpetCeramic Tile

Interior Doors:Hollow coreRaised panelWood

Window Types:Dual paneSlidersSingle-hungFixedGlass block

Cabinetry:Wood face frameLaminate

Countertop:Laminate

IN RR OK

8.0 CEILINGS • •

8.1 WALLS • •

8.2 FLOORS • •

8.3 STEPS, STAIRWAYS, BALCONIES AND RAILINGS • •

8.4 COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS • •

8.5 DOORS (REPRESENTATIVE NUMBER) • •

8.6 WINDOWS (REPRESENTATIVE NUMBER) • •

IN= Inspected, RR= Repair or Replace, OK= Functioning IN RR OK

Comments:

360 Degree Home Inspections, LLC Doe

123 Main St. Page 27 of 54

Page 28: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

8.4 Countertop not properly connected at indicated area. Recommend repair/evaluation by a qualified person.

8.4 Item 1(Picture) Kitchen

8.5 (1) Door doesn't lock properly. Recommend repair/evaluation by a qualified person.

8.5 Item 1(Picture) Bedroom 1 8.5 Item 2(Picture) Master bathroom

8.5 (2) Closet sliding doors missing floor guides. Recommend installing them to prevent possible injury when opening/closing closet

8.5 Item 3(Picture) Bedroom 1 8.5 Item 4(Picture) Bedroom 2

360 Degree Home Inspections, LLC Doe

123 Main St. Page 28 of 54

Page 29: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

8.6 Window is damaged and will not operate properly. Recommend repair/evaluation by a qualified person.

8.6 Item 1(Picture) Front room west wall

The interior of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern,some areas can go unnoticed. The inspection did not involve moving furniture and inspecting behind furniture, area rugs or areas obstructed from view.Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It isrecommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

360 Degree Home Inspections, LLC Doe

123 Main St. Page 29 of 54

Page 30: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

9. Insulation and Ventilation

The home inspector shall observe: Insulation and vapor retarders in unfinished spaces; Ventilation of attics and foundation areas; Kitchen, bathroom, andlaundry venting systems; and the operation of any readily accessible attic ventilation fan, and, when temperature permits, the operation of any readilyaccessible thermostatic control. The home inspector shall describe: Insulation in unfinished spaces; and Absence of insulation in unfinished space atconditioned surfaces. The home inspector shall: Move insulation where readily visible evidence indicates the need to do so; and Move insulation wherechimneys penetrate roofs, where plumbing drain/waste pipes penetrate floors, adjacent to earth filled stoops or porches, and at exterior doors. The homeinspector is not required to report on: Concealed insulation and vapor retarders; or Venting equipment that is integral with household appliances.

Styles & MaterialsAttic Insulation:

R-30 or better (8" Deep)Blown in fiberglass

Ventilation (attic/crawlspace):Vented Frieze BlocksO'Hagen ventsPassive

Exhaust Fans (Bath/Kitchen):Fan onlyKitchen vent is recirculated

Dryer Power Source:220 Electric

Dryer Vent:Rigid metal pipeSatisfactory where visible

IN RR OK

9.0 INSULATION IN ATTIC • •

9.3 VENTILATION OF ATTIC AND FOUNDATION AREAS • •

9.4 VENTING SYSTEMS (Kitchens, baths and laundry) • •

9.5 COMBUSTION VENTS (GARAGE) • •

IN= Inspected, RR= Repair or Replace, OK= Functioning IN RR OK

The insulation and ventilation of the home was inspected and reported on with the above information. While the inspector makes every effort to find allareas of concern, some areas can go unnoticed. Venting of exhaust fans or clothes dryer cannot be fully inspected and bends or obstructions can occurwithout being accessible or visible (behind wall and ceiling coverings). Only insulation that is visible was inspected. Please be aware that the inspector hasyour best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors beused in your further inspection or repair issues as it relates to the comments in this inspection report.

360 Degree Home Inspections, LLC Doe

123 Main St. Page 30 of 54

Page 31: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

10. Built-In Kitchen Appliances

Styles & MaterialsExhaust/Range hood:

RE-CIRCULATE

IN RR OK

10.0 DISHWASHER • •

10.1 RANGES/OVENS/COOKTOPS • •

10.2 RANGE HOOD • •

10.3 GARBAGE DISPOSAL • •

10.4 MICROWAVE COOKING EQUIPMENT • •

IN= Inspected, RR= Repair or Replace, OK= Functioning IN RR OK

360 Degree Home Inspections, LLC Doe

123 Main St. Page 31 of 54

Page 32: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

12. Swimming Pools, Equipment and Safety

Pools are fun, but children and adults can lose their life quickly. Over 4000 lives annually are lost with one-third under the age of 14. A child can drown inthe time it takes to answer a phone. A swimming pool is 14 times more likely than a motor vehicle to be involved in the death of a child age 4 and under.An estimated 5,000 children ages 14 and under are hospitalized due to near-drownings each year; 15 percent die in the hospital and as many as 20 percentsuffer severe, permanent brain damage. Of all preschoolers who drown, 70 percent are in the care of one or both parents at the time of the drowning and 75percent are missing from sight for five minutes or less. Drowning surpasses all other causes of death to children age 14 and under in Arizona, California,Florida, Hawaii, Montana, Nevada, Oregon, Utah and Washington.

A pool alarm with a loud speaker system to sound outside as well as inside the home could save a life. Even if you do not have children youshould be concerned. 35% of children that drowned did so in someone else's pool. For more info, do an Internet search on pool safety or visitthis website: http://www.ihf.org/foryourhealth/article_children.html

Styles & MaterialsType of pool:

In groundHeated

Interior finish material:Aggregate

Type of filter:DE

Type of child safe barrier:Fence

Type of cleaning system:Installed floor cleaner (arneson, polaris, barracuda)

Energy source for water heating:Natural gas

IN OK NI NP RR No

12.0 SURFACE WALLS AND FLOOR OF POOL • •

12.1 DECK, STEPS AND COPING • •

12.2 PUMPS, MOTORS & BLOWERS • •

12.3 EXTERNAL BONDING OF THE PUMP MOTORS, BLOWERS & HEATERS • •

12.4 IS POOL LIGHT OPERATIONAL? • •

12.5 VERIFY THE ELECTRICAL OUTLET(S) AND ANY LIGHTING FOR POOL IS ON A GROUNDFAULT CIRCUIT (GFCI) & TIMERS

• •

12.6 OVERFLOW SKIMMERS AND DRAINS AND AUTO FILLER • •

12.8 ENTRAPMENT PREVENTION COMPONENTS INSTALLED? • •

12.9 CHILD BARRIERS PRESENT? • •

12.10 ANY CROSS CONNECTIONS? • •

12.11 POOL HEATERS • •

IN= Inspected, OK= OK, NI= Not Inspected, NP= Not Present, RR= Repair or Replace, No= No IN OK NI NP RR No

Comments:

360 Degree Home Inspections, LLC Doe

123 Main St. Page 32 of 54

Page 33: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

12.2 Pool pump leaking at area indicated when operating. Recommend repair/evaluation by a qualified person.

12.2 Item 1(Picture) Pool pump

12.4 Pool and Spa light not operating at time of inspection. Recommend repair/evaluation by a qualified person.

12.5 GFCI not operating properly at time of inspecting. Recommend repair/evaluation by a licensed electrician.

12.8 Recommend installing anti-vortex drain covers to prevent potential entrapment hazard. Recommend installation by aqualified person.

12.8 Item 1(Picture) Pool 12.8 Item 2(Picture) Spa

360 Degree Home Inspections, LLC Doe

123 Main St. Page 33 of 54

Page 34: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

12.9 Swimming pool fence is damaged/deteriorated at areas indicated. Recommend repair/evaluation by a qualifiedperson.

12.9 Item 1(Picture) Pool fence 12.9 Item 2(Picture) Pool fence

12.11 Pool heater is not operating properly at time of inspection. Recommend repair/evaluation by a qualified person.

Unless so mentioned in this report, I did not test water for bacteria or quality. The pool was inspected and reported on with the above information. While theinspector makes every effort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind.Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your furtherinspection or repair issues as it relates to the comments in this inspection report.

360 Degree Home Inspections, LLC Doe

123 Main St. Page 34 of 54

Page 35: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

General Summary

360 Degree Home Inspections, LLC Doe

123 Main St. Page 35 of 54

Page 36: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

360 Degree Home Inspections, LLC Doe

123 Main St. Page 36 of 54

Page 37: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

360 Degree Home Inspections, LLC

www.360inspectionsaz.comGilbert, AZ 85298

480-818-6323

CustomerJohn Doe

Address123 Main St.

Anytown AZ 85298

The following items or discoveries indicate that these systems or components do not function as intended or adverselyaffects the habitability of the dwelling; or warrants further investigation by a specialist, or requires subsequentobservation. This summary shall not contain recommendations for routine upkeep of a system or component to keep it inproper functioning condition or recommendations to upgrade or enhance the function or efficiency of the home. ThisSummary is not the entire report. The complete report may include additional information of concern to the customer. It isrecommended that the customer read the complete report.

1. Roof

1.0 ROOF COVERINGS

Inspected, Repair or Replace(1) Identified roof tiles are damaged/displaced and leave roof decking exposed to potential moisture penetration/damage. Recommend repair/evaluation by a qualified expert.

1.0 Item 1(Picture) NE corner of house 1.0 Item 2(Picture) Over garage

360 Degree Home Inspections, LLC Doe

123 Main St. Page 37 of 54

Page 38: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

1.0 Item 3(Picture) South side of house

(2) Mudcap is damaged. Recommend repair/evaluation by a qualified expert.

1.0 Item 4(Picture) Center of house.

1.1 FLASHINGS

Inspected, Repair or ReplaceIdentified valley flashing has some built up debris that could lead to issues with water drainage and potential waterponding. Recommend removal of debris by a qualified person.

1.1 Item 1(Picture) NW valley of roof. 1.1 Item 2(Picture) NW valley of roof

360 Degree Home Inspections, LLC Doe

123 Main St. Page 38 of 54

Page 39: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

1.4 ROOF STRUCTURE AND ATTIC

Inspected, Repair or ReplaceRoof decking is damaged and showing signs of moisture damage/penetration. Recommend repair/evaluation by aqualified expert.

1.4 Item 1(Picture) South part of attic

2. Exterior

2.0 SIDING, FLASHING AND TRIM

Inspected, Repair or ReplaceStucco siding is damaged. Recommend repair/evaluation by a qualified person.

2.0 Item 1(Picture) Backyard patio

2.1 EAVES, SOFFITS AND FASCIAS

Inspected, Repair or Replace(1) Fascia wood directly exposed to elements in several areas on all sides of house. It is recommended to paint allexposed wood to prevent damage/deterioration from elements. Recommend paint as needed by a qualified person.

360 Degree Home Inspections, LLC Doe

123 Main St. Page 39 of 54

Page 40: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

2.1 Item 1(Picture) NW corner of house 2.1 Item 2(Picture) NW corner of house

2.1 Item 3(Picture) NW corner of house 2.1 Item 4(Picture) NE corner of house

2.1 Item 5(Picture) North side of house 2.1 Item 6(Picture) East side of house

360 Degree Home Inspections, LLC Doe

123 Main St. Page 40 of 54

Page 41: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

2.1 Item 7(Picture) East side of house 2.1 Item 8(Picture) Saw corner of house

(2) Bird block screen is missing/damaged in identified areas. Recommend repair/evaluation by a qualified person.

2.1 Item 9(Picture) North side of house 2.1 Item 10(Picture) North side of house

2.2 DOORS (Exterior)

Inspected, Repair or ReplaceRear sliding door doesn't lock properly. Recommend repair/evaluation by a qualified person.

2.2 Item 1(Picture) Sliding rear door

360 Degree Home Inspections, LLC Doe

123 Main St. Page 41 of 54

Page 42: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

2.4 VEGETATION, GRADING, DRAINAGE, DRIVEWAYS, PATIO FLOOR, WALKWAYS AND RETAINING WALLS(With respect to their effect on the condition of the building)

Inspected, Repair or ReplaceIt is recommended to trim all vegetation/plants/trees at least 1 foot from any portion of the house to prevent anydamage/moisture penetration to the house. Recommend trimming as needed.

2.4 Item 1(Picture) NW corner of house 2.4 Item 2(Picture) SW corner of house

2.5 FENCES AND GATES

Inspected, Repair or Replace(1) Fence block is loose. Recommend repair/evaluation by a qualified person.

2.5 Item 1(Picture) West side of house

(2) Side gate doesn't self close. Recommend complying with City of Phoenix for barrier protection when there is apool in the backyard.

360 Degree Home Inspections, LLC Doe

123 Main St. Page 42 of 54

Page 43: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

2.5 Item 2(Picture) East side of house

3. Electrical System

3.1 METER BOX, MAIN DISCONNECT, SERVICE GROUNDING/BONDING and MAIN and DISTRIBUTION PANELS

Inspected, Repair or ReplaceIt is recommended that electrical panel be completely enclosed to prevent any possible damage to wiring/breakers.Recommend repair/evaluation by a qualified person.

3.1 Item 1(Picture) Main electrical panel

3.3 SWITCHES, RECEPTACLES, LIGHT FIXTURES AND VISIBLE WIRING (observed from a representativenumber)

Inspected, Repair or Replace(1) Identified outlets are loose. Recommend repair/evaluation by a qualified person.

360 Degree Home Inspections, LLC Doe

123 Main St. Page 43 of 54

Page 44: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

3.3 Item 1(Picture) Garage 3.3 Item 2(Picture) Front room

3.3 Item 3(Picture) Master bathroom

(2) Outlet cover not properly attached. Recommend repair/evaluation by a qualified person.

3.3 Item 4(Picture) Master bedroom

3.7 SMOKE DETECTORS

Inspected, Repair or ReplaceSmoke detectors are not operating appropriately/missing at the time of inspection. It is recommended that smokedetectors are replaced every 7-10 years and to have a CO detector with gas appliances. Recommend repair/evaluation by a qualified person.

360 Degree Home Inspections, LLC Doe

123 Main St. Page 44 of 54

Page 45: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

3.7 Item 1(Picture) Bedroom 1 3.7 Item 2(Picture) Master bedroom

4. Plumbing System

4.1 PLUMBING WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES AND ANY LEAKS

Inspected, Repair or Replace(1) Valve won't divert water from bath fixture to shower fixture properly. Recommend repair/evaluation by a qualifiedperson.

4.1 Item 1(Picture) Upstairs hall bathroom

(2) Shower head is leaking from area indicated. Recommend repair/evaluation by a qualified person.

360 Degree Home Inspections, LLC Doe

123 Main St. Page 45 of 54

Page 46: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

4.1 Item 2(Picture) Master bathroom shower

(3) Master bathtub handle is broken/damaged. Recommend repair/replacement.

4.1 Item 3(Picture) Master bathtub

4.4 CROSS CONNECTIONS

Inspected, Repair or ReplaceThe rear hose bib does not have a vacuum breaker installed to prevent cross contamination of the domestic watersupply from an attached garden hose. Recommend having these devices installed.

4.4 Item 1(Picture) Backyard hose bib

360 Degree Home Inspections, LLC Doe

123 Main St. Page 46 of 54

Page 47: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

5. Basement, Foundation, Crawlspace and Structure

5.0 FOUNDATIONS, BASEMENTS AND CRAWLSPACES (Report signs of abnormal or harmful water penetrationinto the building or signs of abnormal or harmful condensation on building components.)

Inspected, Repair or ReplaceStem was is exposed in indicated areas. It is recommended to paint all exposed portions of stem wall to preventdamage from elements. Recommend painting as necessary.

5.0 Item 1(Picture) Front entry way 5.0 Item 2(Picture) NE corner of house

5.0 Item 3(Picture) NE corner of house 5.0 Item 4(Picture) NE corner of house

360 Degree Home Inspections, LLC Doe

123 Main St. Page 47 of 54

Page 48: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

5.0 Item 5(Picture) South side of house 5.0 Item 6(Picture) SW side of house

5.2 COLUMNS OR PIERS

Inspected, Repair or ReplaceBackyard patio cover columns have exposed aggregate on all 4 sides. Recommend repair/painting to prevent andamage/deterioration.

5.2 Item 1(Picture) East column 5.2 Item 2(Picture) West column

5.3 FLOORS (Structural)

Inspected, Repair or ReplaceIndicated part of backyard patio concrete slab has exposed aggregate. Recommend repair to prevent damagedeterioration.

360 Degree Home Inspections, LLC Doe

123 Main St. Page 48 of 54

Page 49: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

5.3 Item 1(Picture) Backyard patio

7. Heating / Cooling

7.9 AIR FILTER(S)

Inspected, Repair or ReplaceAir filters are dirty and need to be replaced. Replace as necessary.

8. Doors, Windows and Interior

8.4 COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS

Inspected, Repair or ReplaceCountertop not properly connected at indicated area. Recommend repair/evaluation by a qualified person.

8.4 Item 1(Picture) Kitchen

8.5 DOORS (REPRESENTATIVE NUMBER)

Inspected, Repair or Replace(1) Door doesn't lock properly. Recommend repair/evaluation by a qualified person.

360 Degree Home Inspections, LLC Doe

123 Main St. Page 49 of 54

Page 50: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

8.5 Item 1(Picture) Bedroom 1 8.5 Item 2(Picture) Master bathroom

(2) Closet sliding doors missing floor guides. Recommend installing them to prevent possible injury when opening/closing closet

8.5 Item 3(Picture) Bedroom 1 8.5 Item 4(Picture) Bedroom 2

8.6 WINDOWS (REPRESENTATIVE NUMBER)

Inspected, Repair or ReplaceWindow is damaged and will not operate properly. Recommend repair/evaluation by a qualified person.

8.6 Item 1(Picture) Front room west wall

360 Degree Home Inspections, LLC Doe

123 Main St. Page 50 of 54

Page 51: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

12. Swimming Pools, Equipment and Safety

12.2 PUMPS, MOTORS & BLOWERS

Inspected, Repair or ReplacePool pump leaking at area indicated when operating. Recommend repair/evaluation by a qualified person.

12.2 Item 1(Picture) Pool pump

12.4 IS POOL LIGHT OPERATIONAL?

Inspected, Repair or ReplacePool and Spa light not operating at time of inspection. Recommend repair/evaluation by a qualified person.

12.5 VERIFY THE ELECTRICAL OUTLET(S) AND ANY LIGHTING FOR POOL IS ON A GROUND FAULT CIRCUIT(GFCI) & TIMERS

Inspected, Repair or ReplaceGFCI not operating properly at time of inspecting. Recommend repair/evaluation by a licensed electrician.

12.8 ENTRAPMENT PREVENTION COMPONENTS INSTALLED?

Inspected, Repair or ReplaceRecommend installing anti-vortex drain covers to prevent potential entrapment hazard. Recommend installation by aqualified person.

12.8 Item 1(Picture) Pool 12.8 Item 2(Picture) Spa

12.9 CHILD BARRIERS PRESENT?

360 Degree Home Inspections, LLC Doe

123 Main St. Page 51 of 54

Page 52: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

Inspected, Repair or ReplaceSwimming pool fence is damaged/deteriorated at areas indicated. Recommend repair/evaluation by a qualifiedperson.

12.9 Item 1(Picture) Pool fence 12.9 Item 2(Picture) Pool fence

12.11 POOL HEATERS

Inspected, Repair or ReplacePool heater is not operating properly at time of inspection. Recommend repair/evaluation by a qualified person.

Home inspectors are not required to report on the following: Life expectancy of any component or system; The causes of theneed for a repair; The methods, materials, and costs of corrections; The suitability of the property for any specialized use;Compliance or non-compliance with codes, ordinances, statutes, regulatory requirements or restrictions; The market value ofthe property or its marketability; The advisability or inadvisability of purchase of the property; Any component or system thatwas not observed; The presence or absence of pests such as wood damaging organisms, rodents, or insects; or Cosmeticitems, underground items, or items not permanently installed. Home inspectors are not required to: Offer warranties orguarantees of any kind; Calculate the strength, adequacy, or efficiency of any system or component; Enter any area orperform any procedure that may damage the property or its components or be dangerous to the home inspector or otherpersons; Operate any system or component that is shut down or otherwise inoperable; Operate any system or componentthat does not respond to normal operating controls; Disturb insulation, move personal items, panels, furniture, equipment,plant life, soil, snow, ice, or debris that obstructs access or visibility; Determine the presence or absence of any suspectedadverse environmental condition or hazardous substance, including but not limited to mold, toxins, carcinogens, noise,contaminants in the building or in soil, water, and air; Determine the effectiveness of any system installed to control orremove suspected hazardous substances; Predict future condition, including but not limited to failure of components; Sincethis report is provided for the specific benefit of the customer(s), secondary readers of this information should hire a licensedinspector to perform an inspection to meet their specific needs and to obtain current information concerning this property.

Prepared Using HomeGauge http://www.HomeGauge.com : Licensed To Derreck Weatherford

360 Degree Home Inspections, LLC Doe

123 Main St. Page 52 of 54

Page 53: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

INVOICE

360 Degree Home Inspections, LLC Doe

123 Main St. Page 53 of 54

Page 54: 123 Main St. / 360 Degree Home Inspections, LLC / Derreck ... · 360 Degree Home Inspections, LLC Doe 123 Main St. Page 12 of 54. 3. Electrical System The inspector shall inspect:

360 Degree Home Inspections, LLCwww.360inspectionsaz.comGilbert, AZ 85298480-818-6323Inspected By: Derreck Weatherford

Inspection Date: 9/21/2017Report ID: 20170921-1

Customer Info: Inspection Property:

John Doe

Customer's Real Estate Professional:

123 Main St.Anytown AZ 85298

Inspection Fee:Service Price Amount Sub-TotalHeated Sq Ft 2,001 - 2,500 350.00 1 350.00Swimming Pool/Spa Inspection 50.00 1 50.00Termite Inspection 30.00 1 30.00

Tax $0.00Total Price $430.00

Payment Method: CheckPayment Status: Paid At Time Of InspectionNote:

360 Degree Home Inspections, LLC Doe

123 Main St. Page 54 of 54