1200 sales en - · PDF fileSIMATIC S7-1200 It’s the Interplay ... USS and Modbus RTU...
Transcript of 1200 sales en - · PDF fileSIMATIC S7-1200 It’s the Interplay ... USS and Modbus RTU...
© Siemens AG 2010. All Rights Reserved.
SIMATIC S7-1200
It’s the Interplay that makes the difference
© Siemens AG 2010. All Rights Reserved.Industry Sector
SIMATIC S7-1200 Controller
DC/DC/DC, AC/DC/RLY, DC/DC/RLY3 configurations per CPU
110 x 100 x 75
CPU 1214C
90 x 100 x 75
CPU 1211C
90 x 100 x 75Dimensions W x H x D (mm)
CPU 1212CSIMATIC S7-1200 CPUs
© Siemens AG 2010. All Rights Reserved.Industry Sector
SIMATIC S7-1200 Controller
2 Inputs2 Inputs2 InputsIntegrated Analog I/O
1024 Bytes for Inputs / 1024 Bytes for OutputsProcess Image Size
67193Max. Local I/O – Analog
284
14 Inputs / 10 Outputs
CPU 1214C
14
6 Inputs / 4 Outputs
CPU 1211C
82Max. Local I/O – Digital
8 Inputs / 6 OutputsIntegrated Digital I/O
CPU 1212CIntegrated I/O
© Siemens AG 2010. All Rights Reserved.Industry Sector
SIMATIC S7-1200 Controller
8 KB4 KB4 KBBit Memory (M)
2 MB1 MB1 MBLoad Memory
50 KB25 KB25 KBWork Memory
2 KB2 KB2 KBRetentive Memory
CPU 1214CCPU 1211C CPU 1212CIntegrated user memory
© Siemens AG 2010. All Rights Reserved.Industry Sector
SIMATIC S7-1200 Controller
Memory card
The memory card can be configured for various operations:
� Program card – To use the memory card as external load memory for the CPU and to provide a larger load memory storage area for use with Data logging and User defined Web pages.
� Transfer card – To copy a program to the internal load memory of one or more CPUs without using the STEP 7 Basic engineering system.
� Firmware update card – To update the firmware of the CPU and all connected S7-1200 hardware.
© Siemens AG 2010. All Rights Reserved.Industry Sector
SIMATIC S7-1200 Controller
24 MB2 MBCapacity
SIMATIC Memory Card SIMATIC Memory CardMemory cards
© Siemens AG 2010. All Rights Reserved.Industry Sector
Scalable and Flexible Design
111Signal Board (SB) or Communication Board (CB)
82noneSignal Module (SM)
333Communication Module (CM) or Communication Processor (CP)
CPU 1214CCPU 1211C CPU 1212CCPU Expansion
© Siemens AG 2010. All Rights Reserved.Industry Sector
Scalable and Flexible Design
DI 8 x 24 V DC DO 8 x RLY 30 V DC /
250 V AC 2 A
SM 1223
DC/RLY
DO 8 x RLY 30 V DC /
250 V AC 2 A
SM 1222 RLY SM 1222 RLYSM 1222 DCSM 1222 DCSignal Modules
DI 16 x 24 V DCDI 8 x 24 V DCDigital Input
DO 16 x RLY 30 V DC /
250 V AC 2 A
DO 16 x 24 V DC 0.5 A
DO 8 x 24 V DC 0.5 A
Digital Output
SM 1223
DC/RLY
SM 1223 DC/DC
SM 1223 DC/DC
Signal Modules
DI 16 x 24 V DC DO 16 x RLY
30 V DC / 250 V AC 2 A
DI 8 x 24 V DC DO 8 x 24 V DC
0.5 A
SM 1221 DC
DI 16 x 24 V DC DO 16 x 24 V
DC 0.5 A
Digital Input / Output
SM 1221 DCSignal Modules
© Siemens AG 2010. All Rights Reserved.Industry Sector
Scalable and Flexible Design
SM 1223 AC/RLYSignal Modules
DI 8 x 120/230 V AC DO 8 x RLY 30 V DC / 250 V AC 2 A
Digital Input / Output
© Siemens AG 2010. All Rights Reserved.Industry Sector
Scalable and Flexible Design
SM 1232 AQSM 1232 AQSignal Modules
AO 4 x 14 Bit ±10V DC or 0-20 mA
AO 2 x 14 Bit ±10V DC or 0-20 mA
Analog Output
SM 1231 AISM 1231 AISignal Modules
AI 8 x 13 Bit ± 10 V DC, ± 5 V DC,
± 2.5 V DC or 0-20 mA
AI 4 x 13 Bit ± 10 V DC, ± 5 V DC,
± 2.5 V DC or 0-20 mA
Analog Input
© Siemens AG 2010. All Rights Reserved.Industry Sector
Scalable and Flexible Design
SM 1234 AI/AQSignal Modules
AI 4 x 13 Bit ± 10 V DC, ± 5 V DC, ± 2.5 V DC or 0-20 mA
AO 2 x 14 Bit ±10 V DC or 0-20 mA
Analog Input / Output
© Siemens AG 2010. All Rights Reserved.Industry Sector
Scalable and Flexible Design
SM 1231 TCSM 1231 TCSignal Modules
AI 8 x TC x 16 Bit Types: J, K, T, E, R&S, N, C,
TXK/XK(L) Voltage range: ± 80 mV
AI 4 x TC x 16 Bit Types: J, K, T, E, R&S, N, C,
TXK/XK(L) Voltage range: ± 80 mV
Analog Input
SM 1231 RTDSM 1231 RTDSignal Modules
AI 8 x RTD x 16 Bit Types: Platinum (Pt), Copper (Cu), Nickel (Ni & LG-Ni) or
Resistance
AI 4 x RTD x 16 Bit Types: Platinum (Pt), Copper (Cu), Nickel (Ni & LG-Ni) or
Resistance
Analog Input
© Siemens AG 2010. All Rights Reserved.Industry Sector
Scalable and Flexible Design
Signal Module Expansion Cable
With the 2 meter Signal Module Expansion Cable, it is possible to mount the CPU and Signal Modules on two separate rows which provides additional flexibility during configuration and installation.
© Siemens AG 2010. All Rights Reserved.Industry Sector
Scalable and Flexible Design
Communication Modules and Communication Processors
With the Communication Modules and the Communication Processor, you can add the appropriate interfaces to meet your communication requirements.
� The RS232 and RS485 Communication Modules provide support for Point-to-Point, USS and Modbus RTU communication
� The PROFIBUS Communication Module provide support for PROFIBUS communication
� The GPRS Communication Processor provides support for remote monitoring and control
© Siemens AG 2010. All Rights Reserved.Industry Sector
Scalable and Flexible Design
CP 1242-7 GPRSCommunication Processor
1 x SMA antenna connector 1 x SIM card slot
GPRS Communication
CM 1243-5 PROFIBUS MasterCM 1242-5 PROFIBUS SlaveCommunication Modules
1 x 9-pin D-sub female connector
1 x 9-pin D-sub female connector
PROFIBUS Communication
1 x 9-pin D-sub male connector
CM 1241 RS232 CM 1241 RS485Communication Modules
1 x 9-pin D-sub female connector
Serial Communication
© Siemens AG 2010. All Rights Reserved.Industry Sector
Scalable and Flexible Design
Signal Boards and Communication Boards
With the Signal Boards and the Communication Board, you can cost effectively “customize” the CPU with additional functionality without affecting the amount of panel space required.
� The digital Signal Boards provide additional digital I/O channels
� The analog and temperature measurement Signal Boards provide additional analog I/O channels
� The Communication Board provides an additional communication interface
© Siemens AG 2010. All Rights Reserved.Industry Sector
Scalable and Flexible Design
DI 2 x 24 V DCDO 2 x 24 V DC 0.1 A
DI 2 x 5 V DCDO 2 x 5 V DC 0.1 A
DI 2 x 24 V DCDO 2 x 24 V DC 0.5 A
Digital Input / Output
SB 1223 DC/DC 200 kHz 4)
SB 1223 DC/DC 200 kHz 4)
SB 1223 DC/DC 3)Signal Boards
SB 1222 DC 200 kHz 2)
SB 1222 DC 200 kHz 2)
Signal Boards
DI 4 x 24 V DCDI 4 x 5 V DCDigital Input
DO 4 x 24 V DC 0.1 ADO 4 x 5 V DC 0.1 ADigital Output
SB 1221 DC 200 kHz 1)
SB 1221 DC 200 kHz 1)
Signal Boards
1) Input type: Source2) Output type: Sink and Source3) Input type: Sink, Output type: Sink and Source4) Input type: Source, Output type: Sink and Source
© Siemens AG 2010. All Rights Reserved.Industry Sector
Scalable and Flexible Design
1 x 6 terminal screw connector
Serial Communication
CB 1241 RS485Communication Boards
AO 1 x 12 Bit ±10 V DC or 0-20 mA
Analog Output
SB 1232 AQSignal Boards
AI 1 x TC x 16 Bit Types: J, K
Voltage range: ± 80 mV
AI 1 x RTD x 16 Bit Type: Platinum (Pt)
AI 1 x 12 Bit± 10 V DC, ± 5 V DC,
± 2.5 V DC or 0-20 mA
Analog Input
SB 1231 TCSB 1231 RTDSB 1231 AISignal Boards
© Siemens AG 2010. All Rights Reserved.Industry Sector
Scalable and Flexible Design
Compact Switch Module
With the CSM 1277 Compact Switch Module, you can easily configure a uniform or mixed network consisting of line, tree or star topologies while minimizing cabling and providing maximum networking flexibility.
This 4-port unmanaged switch allows you to connect up to 3 additional Ethernet devices to your S7-1200 control station.
© Siemens AG 2010. All Rights Reserved.Industry Sector
Scalable and Flexible Design
Power Supply
With the PM 1207 Power Module you can easily provide 24 V DC power to components in the S7-1200 control systems which cannot be supplied by the CPU’s integrated sensor power supply.
The PM 1207 provides a wide input voltage range (8…132/176...264 V AC) for worldwide use and a stabilized 24 V DC output with a rated for 2.5 A.
© Siemens AG 2010. All Rights Reserved.Industry Sector
Scalable and Flexible Design
PM 1207Accessories
Input: 120/230 V AC 50/60 Hz, 1.2A/0.7AOutput: 24 V DC / 2.5 A
Power Supply
4 x RJ45 sockets 10/100 Mb/s
Compact Switch Module
CSM 1277Accessories
© Siemens AG 2010. All Rights Reserved.Industry Sector
Industrial Communication
… to satisfy all your networking requirements
Point-to-Point,USS, Modbus RTU
GPRS
© Siemens AG 2010. All Rights Reserved.Industry Sector
Industrial Communication
Open communication at every level
The S7-1200 family provides a variety of communication options to satisfy all your networking requirements.
� PROFINET
� PROFIBUS
� Point-to-Point (PtP) Communication
� Universal Serial Interface (USS)
� Modbus RTU (Modbus TCP/IP in preparation)
� Telecontrol Communication
© Siemens AG 2010. All Rights Reserved.Industry Sector
Industrial Communication
Integrated PROFINET Interface
The S7-1200 CPU has an integrated PROFINET interface which supports TCP/IP-based communication standards.
The following application protocols are supported by the S7-1200 CPU:
� PROFINET –Basic Services and I/O Controller
� Open user communication –TCP, ISO on TCP and UDP
© Siemens AG 2010. All Rights Reserved.Industry Sector
Industrial Communication
PROFINET communication
The S7-1200 CPU can communicate:
� with a programming device
� and with HMI devices
Using the Open user communication and Distributed I/O instructions, the S7-1200 CPU can communicate:
� with other CPUs
� with PROFINET I/O devices (e.g. ET 200 and SINAMICS)
� and with devices using standard TCP communications protocols
PROFINET
© Siemens AG 2010. All Rights Reserved.Industry Sector
Industrial Communication
PROFINET communication
The PROFINET interface on the S7-1200 CPU supports the following simultaneous communication connections:
� 3 connections for HMI to CPU communication
� 1 connection for programming device to CPU communication
� 8 connections for active communication using the open user communication and distributed I/O instructions
� 3 connections for passive communication using the S7 communication instructions
© Siemens AG 2010. All Rights Reserved.Industry Sector
Industrial Communication
PROFIBUS communication
Together with the PROFIBUS Master and Slave communication modules, the S7-1200 CPUs supports the PROFIBUS communication standard.
© Siemens AG 2010. All Rights Reserved.Industry Sector
Industrial Communication
PROFIBUS DP
PROFIBUS DP Master
With the PROFIBUS DP Master communication module CM 1243-5, the S7-1200 can communicate:
� with other CPUs
� with a programming device 1
� with HMI devices
� and with PROFIBUS DP slaves(e.g. ET 200 and SINAMICS)
1 the hardware conf iguration must be initially downloaded using the integrated PROFINET interf ace or a SIMATIC Memory Card
© Siemens AG 2010. All Rights Reserved.Industry Sector
Industrial Communication
PROFIBUS DP Master
The interface on the PROFIBUS Master communication module supports the following simultaneous communication connections:
� 3 connections for HMI to CPU communication
� 1 connection for programming device to CPU communication
� 8 connections for active communication using the distributed I/O instructions
� 3 connections for passive communication using the S7 communication instructions
© Siemens AG 2010. All Rights Reserved.Industry Sector
Industrial Communication
PROFINET
PROFIBUS DP
PROFIBUS DP Slave
With the PROFIBUS DP Slave communication module CM 1242-5, the S7-1200 can communicate as an intelligent DP slave with any PROFIBUS DP master.
© Siemens AG 2010. All Rights Reserved.Industry Sector
Industrial Communication
Point-to-Point communication
Together with the RS232 and RS485 communication modules and the RS485 communication board, the S7-1200 CPU supports Point-to-Point communication (PtP) for character-based serial protocols.
Maximum freedom and flexibility is provided using the PtP communication instructions in the user program.
© Siemens AG 2010. All Rights Reserved.Industry Sector
Industrial Communication
Point-to-Point communication
Point-to-Point communication enables a wide variety of possibilities:
� The ability to send information directly to an external device such as a printer
� The ability to receive information from other devices such as barcode readers, RFID readers, and vision systems
� The ability to exchange information, sending and receiving data, with other devices such as GPS devices, radio modems, and many other types of devices
PROFINET
PtP Protocol
© Siemens AG 2010. All Rights Reserved.Industry Sector
Industrial Communication
USS communication
Together with the USS instructions, the S7-1200 CPUs can control the operation of drives which support the universal serial interface (USS) protocol.
The USS instructions can be used to communicate with multiple drives through the CM 1241 RS485 communication module or the CB 1241 RS485 communication board. PROFINET
USS Protocol
© Siemens AG 2010. All Rights Reserved.Industry Sector
Industrial Communication
Modbus RTU communication
Together with the Modbus instructions the S7-1200 can communicate as a Modbus master or slave with devices which support the Modbus RTU protocol.
The Modbus instructions can be used to communicate with multiple devices through either the CM 1241 RS232 communication module the CM 1241 RS485 communication module or the CB 1241 RS485 communication board.
PROFINET
Modbus RTU
© Siemens AG 2010. All Rights Reserved.Industry Sector
Industrial Communication
Telecontrol communication
Together with the GPRS communication processor, the S7-1200 CPU supports simple telecontrol applications for monitoring and control of distributed stations using general packet radio service (GPRS).
© Siemens AG 2010. All Rights Reserved.Industry Sector
Industrial Communication
Telecontrol communication
With the GPRS communication processor CP 1242-7, the S7-1200 can remotely communicate:
� with the central control station
� with other remote stations
� with mobile devices (SMS)
� with a programming device (Teleservice)
� and with other communication partners using open user communication based on UDP
© Siemens AG 2010. All Rights Reserved.Industry Sector
Industrial Communication
Teleservice Communication
The TS Adapter IE Basic with a selection of TS Modules for diverse communication technologies.
� TS Modules: Modem, ISDN, GSM, RS232
� No PG/PC required on-site � No need for specialists to be constantly
on-call on site� No travel expenses for service calls� Full TeleService functions,
Extension of the local bus through the remote PC of the service technician
TS Adapter IE Basic
HMIAnalog, ISDN, GSM
Analog, ISDN, GSM
TIA Portal V11
© Siemens AG 2010. All Rights Reserved.Industry Sector
Integrated Technology and Diagnostics
643Integrated High-speed counters
3 @ 80 kHz3 @ 20 kHz
3 @ 80 kHz1 @ 20 kHz
3 @ 80 kHz– Two phase andAB quadrature
3 @ 100 kHz3 @ 30 kHz
3 @ 100 kHz1 @ 30 kHz
3 @ 100 kHz– Single phase
CPU 1214CCPU 1211C CPU 1212CHigh-speed counters
When the inputs of a high-speed Signal Board are used for the HSCs: CPUs 1211C and 1212C can support up to 2 additional HSCsand all CPUs can support up to 2 HSCs @ 200 kHz (single phase) or 160 kHz (two phase and AB quadrature)
© Siemens AG 2010. All Rights Reserved.Industry Sector
Integrated Technology and Diagnostics
2 @ 100 kHz (DC Outputs) / 2 @ 1 Hz (RLY Outputs)Integrated Pulse generators
CPU 1214CCPU 1211C CPU 1212CPulse generators
When the outputs of a high-speed Signal Board are used f or the Pulse generators: All CPUs can support up to 2 Pulse generators @ 100 kHz
© Siemens AG 2010. All Rights Reserved.Industry Sector
Integrated Technology and Diagnostics
Web server
For accessing information about the CPU and process data within the CPU
� Standard Web pages are included that can be accessed from a PC using any Web browser.
� Support is provided for creating user-defined Web pages that can access CPU data. The development of these pages can be done using standard HTML authoring tools.
© Siemens AG 2010. All Rights Reserved.Industry Sector
Integrated Technology and Diagnostics
Data logs
For storing run-time data values in continuous log files
� DataLog instructions are used in the user program to create the data log files.
� The data log files are stored in CPU flash memory and the data is organized in standard CSV (Comma Separated Value) format.
� It is possible to copy the data log files from the CPU memory using the built-in Web server or by removing the memory card and inserting it into a standard SD (Secure Digital) or MMC (MultiMediaCard) card slot on a PC or PG.