2012 Edition Redbook 41 11.0 GENERAL DRAWINGS AND STANDARDS Minimum Vertical Clearances Above Ground and Roofs ………………………………… D1 Minimum Pool Clearances …………………………………………………………………… D2 Minimum Clearances of Wires Adjacent to Buildings and Other Structures …………… D3 O.H. 100 – 400 Amp Mast Services ………………………………………………………… D4 O.H. 100 – 400 Amp Mast Service General Notes ……………………………………….. D5 Drop Swing Service for Inaccessible Service Entrance Attachment ……………………. D6 Pole Mounted Service 100 – 320 Amps ……………………………………………………. D7 Pole Mounted Service 400 Amps …………………………………………………………… D8 LIPA Connects Program Connector Installation …………………………………………… D9 400 – 600 Amp Open Wire Services ……………………………………………………….. D10 Customer Installed Cable Riser …………………………………………………………….. D11 Customer Installed Cable Riser General Notes …………………………………………… D12 Customer Installed Pull Box and Manhole Specifications ……………………………….. D13 U.G. Service 100 – 800 Amp Single or Three Phase by Builder/Applicant ……………. D14 U.G. Service 100 – 800 Amp Single or Three Phase by Builder/Applicant ……………. D15 LIPA Installed Single Phase RUD Service ………………………………………………… D16 Customer Installed Single Phase Residential RUD Service …………………………….. D17 O.H. Single Phase Self Contained Meter Outdoor Socket Meter Installation …………. D18 U.G. Single Phase Self Contained Meter Outdoor Socket Meter Installation …………. D19 O.H. & U.G. Single Phase Self Contained Multi-meter Installation …………………….. D20 O.H. & U.G. Single Phase Self Contained Multi-meter Installation …………………….. D21 O.H. Service Poly-Phase Self Contained Meter Installation …………………………….. D22 U.G. Service Poly-Phase Self Contained Meter Installation …………………………….. D23 Clearances Between Electric & Gas Meters ……………………………………………… D24 Trough Supply Single and Poly-Phase Self Contained Meter Installations ……………. D25 Meter H-Frame Construction ……………………………………………………………….. D26 Electric Meter Room Equipment Clearances ……………………………………………… D27 400 – 800 Amp Trans-S Cabinet Installation ……………………………………………… D28 400 – 800 Amp Trans-S Cabinet Installation Notes & Bonding Diagram ……………… D29 Transformer Rated Meter Socket and Current Transformer Cabinet Installation …….. D30 400 – 1200 Amp Service Current Transformer Compartment Installation …………….. D31 1600 Amp Service and Above Current Transformer Compartment Installation ………. D32 Typical Grounding Requirements Single Meter and Main Installation ………………….. D33 Typical Grounding Details Multi-Meter & Multi-Main Installation ………………………… D34 Standby Generators ………………………………………………………………………….. D35

Transcript of 11.0 GENERAL DRAWINGS AND · PDF file11.0 general drawings and standards ... pole mounted...

Page 1: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

2012 Edition Redbook

41

11.0 GENERAL DRAWINGS AND STANDARDS

Minimum Vertical Clearances Above Ground and Roofs ………………………………… D1

Minimum Pool Clearances …………………………………………………………………… D2

Minimum Clearances of Wires Adjacent to Buildings and Other Structures …………… D3

O.H. 100 – 400 Amp Mast Services ………………………………………………………… D4

O.H. 100 – 400 Amp Mast Service General Notes ……………………………………….. D5

Drop Swing Service for Inaccessible Service Entrance Attachment ……………………. D6

Pole Mounted Service 100 – 320 Amps ……………………………………………………. D7

Pole Mounted Service 400 Amps …………………………………………………………… D8

LIPA Connects Program Connector Installation …………………………………………… D9

400 – 600 Amp Open Wire Services ……………………………………………………….. D10

Customer Installed Cable Riser …………………………………………………………….. D11

Customer Installed Cable Riser General Notes …………………………………………… D12

Customer Installed Pull Box and Manhole Specifications ……………………………….. D13

U.G. Service 100 – 800 Amp Single or Three Phase by Builder/Applicant ……………. D14

U.G. Service 100 – 800 Amp Single or Three Phase by Builder/Applicant ……………. D15

LIPA Installed Single Phase RUD Service ………………………………………………… D16

Customer Installed Single Phase Residential RUD Service …………………………….. D17

O.H. Single Phase Self Contained Meter Outdoor Socket Meter Installation …………. D18

U.G. Single Phase Self Contained Meter Outdoor Socket Meter Installation …………. D19

O.H. & U.G. Single Phase Self Contained Multi-meter Installation …………………….. D20

O.H. & U.G. Single Phase Self Contained Multi-meter Installation …………………….. D21

O.H. Service Poly-Phase Self Contained Meter Installation …………………………….. D22

U.G. Service Poly-Phase Self Contained Meter Installation …………………………….. D23

Clearances Between Electric & Gas Meters ……………………………………………… D24

Trough Supply Single and Poly-Phase Self Contained Meter Installations ……………. D25

Meter H-Frame Construction ……………………………………………………………….. D26

Electric Meter Room Equipment Clearances ……………………………………………… D27

400 – 800 Amp Trans-S Cabinet Installation ……………………………………………… D28

400 – 800 Amp Trans-S Cabinet Installation Notes & Bonding Diagram ……………… D29

Transformer Rated Meter Socket and Current Transformer Cabinet Installation …….. D30

400 – 1200 Amp Service Current Transformer Compartment Installation …………….. D31

1600 Amp Service and Above Current Transformer Compartment Installation ………. D32

Typical Grounding Requirements Single Meter and Main Installation ………………….. D33

Typical Grounding Details Multi-Meter & Multi-Main Installation ………………………… D34

Standby Generators ………………………………………………………………………….. D35

Page 2: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

MINIMUM VERTICAL CLEARANCES

ABOVE GROUND AND ROOFS

NOT ACCEPTABLE - SEE NOTE 2

NOTES

1. POINT OF SERVICE ATTACHMENT ON BUILDING WALL SHALL NOT BE LESS THAN 15'-0"

ABOVE GRADE OR GREATER THAN 21'-0" WITHOUT ELECTRIC DESIGN AND CONSTRUCTION

EXPLICIT APPROVAL IN WRITING (SEE SECTION 4.2.2).

2. SERVICE CONNECTIONS LOCATED ABOVE GARAGE OR OTHER BUILDING EXTENSION AS REPRESENTED

IN FIGURE 1 ARE NOT ACCEPTABLE BECAUSE THE SERVICE CONNECTION CAN NOT BE DIRECTLY

REACHED FROM A LADDER PLACED ON THE GROUND.

3. CLEARANCES BETWEEN LIPA SERVICES AND VERIZON SERVICE LATERALS SHALL BE 2' MINIMUM.

4. FOR COMMERCIAL DRIVEWAYS AND ANY OTHER LOCATIONS SUBJECT TO TRUCK TRAFFIC MINIMUM

CLEARANCE SHALL BE 18'-0".

6. ADD 6" TO ALL MINIMUM CLEARANCES FOR ANY OPEN WIRE CONSTRUCTION.

OVER ROOF SURFACE IF ROOF CANNOT

BE READILY WALKED UPON.

SERVICE DROP, DRIP LOOP AND CONNECTION MUST

BE 3' MINIMUM FROM WINDOWS.

3' MIN. FROM WEATHERHEAD, SERVICE DROP

15' CLEARANCE

OVER

DRIVEWAYS

ROOF CAN BE READILY

WALKED UPON.

18'

CLEARANCE

OVER

STREETS

12'

OVER

SIDE-

WALKS

12' OVER

SPACES

ACCESSIBLE

PEDESTRIAN

12'

FIGURE 1

SERVICE DROP MUST BE 3' OR MORE

10' IF

FIGURE 2

5. A 3' CLEARANCE IS REQUIRED FROM THE WEATHERHEAD AND/OR SERVICE DROP CONNECTIONS TOALL WINDOWS, DOORS, AND MOUNTINGS ON THE BUILDING WALL. POINT OF ATTACHMENT IS NOT

RESIDENTIAL

AND CONNECTIONS

POINT OF ATTACHMENT NOT

PERMITTED BELOW WINDOW

PERMITTED BELOW A WINDOW.

DWG. BASED ON

LIPA CS 2701

D1

Section 11 - Drawings

Page 3: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

LIPA BASES ITS REQUIRED CLEARANCES FROM SWIMMING POOLS AND ASSOCIATED STRUCTURES

UPON THE REQUIREMENTS OF THE NATIONAL ELECTRICAL SAFETY CODE (NESC). WHERE WIRESCONDUCTORS OR CABLES CROSS OVER A SWIMMING POOL OR THE SURROUNDING AREA THE

MINIMUM POOL CLEARANCES

THESE CLEARANCE REQUIREMENTS DO NOT APPLY TO TYPE 1 AND TYPE 2 CABLES DESCRIBED ABOVE

THAT ARE 10 FEET OR MORE HORIZONTALLY FROM THE EDGE OF THE POOL OR DIVING PLATFORM.

DWG. BASED ON

LIPA CS 2035

AA

B B

AVV

SUPPLY CABLES 0 TO 750v

(OVERHEAD TRIPLEX ORQUADRAPLEX SECONDARY

OR SERVICE WIRE)

OPEN SUPPLY CABLES

0 TO 750v (OVERHEADOPEN WIRE SECONDARY

OR SERVICE)

OPEN SUPPLY CABLES

750v TO 22 kv

(PRIMARY WIRE, BAREAND COVERED)

MESSENGERS; SURGE

PROTECTION WIRES;

GROUNDED GUYS;GROUNDED NEUTRAL

CONDUCTORS

CLEARANCE IN ANY DIRECTION

FROM THE WATER LEVEL, EDGE

OF POOL, BASE OF DIVINGPLATFORM OR ANCHORED RAFT

CLEARANCE IN ANY DIRECTION

TO THE DIVING PLATFORM OR

TOWER

VERTICAL CLEARANCE OVER

ADJACENT LAND

2012 Edition Redbook

D2

(FEET) (FEET) (FEET) (FEET)

A:

B:

V:CLEARANCE SHALL BE AS SHOWN ON DRAWING D1

22.0 22.5 23.0 25.0

14.0 14.5 15.0 17.0

FIG. 1

(NESC FIG. 234-3)SWIMMING POOL CLEARANCES

TABLE 1

CLEARANCES IN ALL DIRECTIONS SHALL NOT BE LESS THAN THOSE SHOWN IN TABLE 1 AND

ILLUSTRATED IN FIG. 1, AND AS DESCRIBED IN THE NESC. LOCAL MUNICIPALITY MAY HAVE STRICTER

POOL CLEARANCE REQUIREMENTS. FOR ADDITIONAL PUBLIC POOL REQUIREMENTS SEE SECT. 3.4

HORIZONTALLY FROM THE INSIDE WALL OF A POOL, HOT TUB OR SPA.

UNDERGROUND WIRING SHALL NOT BE LOCATED UNDER OR WITHIN AN AREA EXTENDING 5'

TYPE 1: TYPE 2: TYPE 3: TYPE 4:

WARNING: UNDER ON CIRCUMSTANCES SHOULD ANYONE, OTHER THAN LIPA PERSONAL

ATTEMPT TO MEASURE CLEARANCES TO LIPA'S DISTRIBUTION SYSTEM.

Page 4: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

BUT NOT ATTACHED TO BUILDINGS AND OTHER STRUCTURES

MINIMUM CLEARANCES OF WIRES ADJACENT TO

1. BUILDINGS:

A. HORIZONTAL

(1) TO WALLS, PROJECTIONS

AND GUARDED WINDOWS

(2)

TO U

NGUA

RDED

WIN

DOWS

(3)

TO B

ALCO

NIES

AND

ARE

AS

READILY ACCESSIBLE TO

(1) OVER OR UNDER ROOFS OR

PROJECTIONS NOT READILY

ACCESSIBLE TO PEDESTRIANS

(3)

OVER

ROO

FS A

CCES

SIBL

E TO

VEHICLES BUT NOT SUBJECT

TO TRUCK TRAFFIC

(4)

OVER

ROO

FS A

CCES

SIBL

E TO

TRUCK TRAFFIC

ACCESSIBLE TO PEDESTRIANS

DECKS AND ROOFS READILY

(2)

OVER

OR

UNDE

R BA

LCON

IES

B. VERTICAL

2. SIGNS, CHIMNEYS, BILLBOARDS,

RADIO AND TELEVISION ANTENNAS,

TANKS AND OTHER INSTALLATIONS

NOT CLASSIFIED AS BUILDINGS

(1) READILY ACCESSIBLE TO

(2)

OVER

OR

UNDE

R PO

RTIO

NS O

F

PEDESTRIANS

MESSENGERS, SURGE PROTECTION

WIRES, GROUNDED GUYS,

GROUNDED NEUTRAL CONDUCTORS

SUPPLY CABLES OF 0 TO 750V

(OVE

RHEA

D TR

IPLE

X OR

QUADRUPLEX)

OPEN SUPPLY CONDUCTORS

0 TO 750V

(OVERHEAD OPEN WIRE)

OPEN SUPLY CONDUCTORS OVER

750V TO 22kV

(PRIMARY BARE OR TREE WIRE)

CLEARANCE OF

4.5

4.5

4.5

3.0

10.5

10.5

15.5

4.5

3.0

3.5

5.0

16.0

11.0

11.0

3.5

5.0

5.0

5.0

6.0

5.5

16.5

11.5

11.5

10.5

5.5

5.5

5.5

7.5

7.5

7.5

12.5

13.5

13.5

18.5

7.5

8.0

VOLTAGES ARE PHASE TO GROUND FOR EFFECTIVELY GROUNDED CIRCUITS AND THOSE OTHER CIRCUITS WHERE ALL GROUND FAULTS ARE

CLEARED BY PROMPTLY DE-ENERGIZING THE FAULTED SECTION, BOTH INITIALLY AND FOLLOWING SUBSEQUENT BREAKER OPERATIONS.

TABLE IS TAKEN FROM NESC 234-1, SEE NESC FOR DEFINITIONS AND CLARIFYING INFORMATION.

( FT )

( FT )

( FT )

( FT )

DWG. BASED ON

LIPA CS 2034

Section 11 - Drawings

D3

(2) NOT READILY ACCESSIBLE TO

3.0

3.5

5.5

7.5

A. HORIZONTAL

PEDESTRIANS

(1) OVER OR UNDER SURFACE UPON

10.5

11.0

11.5

13.5

PERSONNEL WALK

B. VERTICAL

SUCH INSTALLATIONS

PEDESTRIANS

OR BRIDGES

Page 5: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

OVERHEAD 100 - 400 AMP SERVICE

USING STRUCTURE SUPPORTED MAST(Sheet 1 of 2)

10" MAX.

6" MIN.

SERVICE MAST HEIGHT TABLE

0' TO 3'-0" 1. 4"x6" TREATED STRUCTURAL LUMBER

3

. 3"

x3"x

1/2"

GAL

V. S

TEEL

ANG

LE

3'-0" TO 5'-0" 1. 6"x6" TREATED STRUCTURAL LUMBER

2. 2 1/2" SCHD. 40 GALV. STEEL PIPE

3. 4"x4"x1/2" GALV. STEEL ANGLE

2. 5"x5"x1/2" GALV. STEEL ANGLE

5'-0" TO 7'-6" 1. 3 1/2" SCHD. 40 GALV STEEL PIPE

2. 6"x6"x1/2" GALV. STEEL ANGLE

7'-6" TO 10'-0" 1. 4" SCHD. 40 GALV STEEL PIPE

MAST LENGTH ABOVE

HIGHEST SUPPORT

STRUCTURAL MEMBER

REQUIRED

IF MINIMUM CLEARANCE CAN NOT BE MET USING ANY OF THE ABOVE

CONTACT THE LIPA ELECTRIC DESIGN & CONSTRUCTION DEPT.

STUD

CONDUIT TO METER

GALV CONDUIT STRAP

EVERY 3'

1/2" BOLTS

THROUGH STUD

BLOCKING BETWEEN

ROOF RAFTERS,

2'-8"

SIDING

SOLIDLY INSTALLED

SEE MAST HEIGHT TABLE

FIGURE 1

FIGURE 2

STUD

CONDUIT TO METER

SIDING

SEE MAST HEIGHT TABLE

2'-6"

THROUGH STUD

1/2" BOLTS

EVERY 3'

GALV CONDUIT STRAP

10" MAX.

6" MIN.

SPACER

STRUCTURE

SUPPORTED MAST

ROOFING

SEE FIGURE 2 GABLE ROOF CONSTRUCTION

HIP ROOF CONSTRUCTION

SEE FIGURE 1

MAINTAIN NOT LESS THAN

(3'-0") VERTICAL

CLEARANCE ABOVE ROOF

OUTS

IDE

OF (

6'-0

")RADIUS FROM THE

SERVICE MAST.

MAINTAIN NOT LESS THAN

(18") VERTICAL

CLEARANCE ABOVE ROOF

INSIDE OF (6'-0") RADIUS

FROM THE SERVICE MAST.

4'MAX

CLEARANCES OF SERVICE DROP TERMINATING ON SUPPORT MAST

4' (MAX) FROM NEAREST EDGE.

6'-0"

18" MIN

SEE

ADDI

TION

AL N

OTES

ON

SHEE

T 2 O

F 2(

D5)

ROOF

PLAN

VIEW

3'-0"

MIN

ELEVATION

6'-0"

2. 2 1/2" SCHD. 40 GALV. STEEL PIPE

DWG. BASED ON

LIPA CS 2721

2012 Edition Redbook

D4

Page 6: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

NOTES:

1. SERVICE ENTRANCE TYPE "SE" CABLE SHALL BE AS APPROVED

BY LIPA AND CAN BE USED WITHOUT BEING ENCASED IN CONDUIT

ON THE LINE SIDE OF THE METER ENCLOSURE, PROVIDING IT

WILL NOT COME INTO CONTACT WITH ANY AWNINGS, SHUTTERS,

OR ANY OTHER OBJECTS THAT MAY CAUSE MECHANICAL INJURY

TO THE CABLE. WHEN INSTALLED ADJACENT TO A DRIVEWAY THE

CABLE SHALL BE ENCASED IN CONDUIT. PROTECTIVE SLEEVING

ON TYPE "SE" CABLE IS REQUIRED TO A HEIGHT OF 8' ABOVE

FINISHED GRADE. FOR ADDITIONAL REQUIREMENTS SEE DWG. D18

2. PVC CONDUIT IS NOT PERMITTED TO BE USED AS A MAST.

3. CUSTOMER SHALL FURNISH MATERIAL AND LABOR FOR ALL WORK

SHOWN, EXCEPT AS NOTED. ALL INSTALLATIONS ARE SUBJECT TO

INSPECTION BY AN APPROVED INSPECTION AGENCY.

4. THROUGH BOLTS ARE REQUIRED FOR ANCHORING ALL SERVICE

MASTS. IN THE EVENT THAT A THROUGH BOLT CANNOT BE

USED AN ADEQUATELY SIZED LAG SCREW MAY BE APPROVED

IF IT CAN BE SHOWN THE SCREW IS SUPPORTED BY A

SOUND STRUCTURAL MEMBER.

5. FOR SOLID BLOCK OR BRICK WALL CONSTRUCTION THROUGH BOLTS

SHALL BE SET IN BLOCK JOINTS THOROUGHLY EMBEDED

IN MORTAR.

6. FOR SELF SUPPORTING MAST SERVICES ALL PIPE COUPLINGS

MUST BE BELOW THE HIGHEST STRUCTURAL ATTACHMENT POINT.

7. MAST MUST BE OF SUFFICIENT STRENGTH TO SUPPORT A

HORIZONTAL TENSION OF 1000LBS. APPLIED TO THE POINT OF

ATTACHMENT. FOR UNUSUAL CIRCUMSTANCES GUYING OF THE MAST

MAY BE PERMITTED. CONTACT LIPA'S ELECTRIC DESIGN & CONSTRUCTION

DEPT. FOR GUYED MAST APPROVAL PRIOR TO INSTALLATION.

USING STRUCTURE SUPPORTED MAST(Sheet 2 of 2)OVERHEAD 100 - 400 AMP SERVICE

DWG. BASED ON

LIPA CS 2721

Section 11 - Drawings

D5

8. NO OTHER UTILITY MAY SUPPORT OR CONNECT AT THE MAST.

Page 7: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

DROP SWING SERVICE FOR

INACCESSIBLE SERVICE ENTRANCE ATTACHMENT

SERVICE MAST

SERVICE ENTRANCE CABLE

GUY WIRE

SPLIT BOLT CONNECTOR, CONNECT

LEAD OF GUY WIRE TO #14 LASHINGWIRE

4" MAX.

#14 SOLID COPPER WIREFOR LASHING SERVICE CABLE

TO GUY WIRESERVICE CABLE TAPED

@ END W/ SELF-SEALINGMATERIAL PER NEC

SERVICE CONNECTORS

TO POLE

AUTOMATIC DEAD END

PARALLEL NEUTRAL

CONNECTOR

GUY GRIP FOR

GUY WIRE

BAIL

CONNECT GUY WIRE & #14LASHING TO NEUTRAL WIRE,EXTEND NEUTRAL FOR SERVICE

CONNECTION

WORK BYCONTRACTOR LIPA

WORK BY

1/2" EYEBOLT

6" MIN.

10" MAX.

22'-6"

TO POLE

H + 2' LIPA CONNECTION

21'-0"

MAX. HEIGHT OF LADDER

ACCESSIBLE SERVICE

H

H = HEIGHT BEYOND

REACH OF SERVICE

LADDER

POOL

NOTE: ONLY TO BE USED WHERE

NORMAL ACCESSIBLE SERVICE

CONNECTION IS IMPOSSIBLE

120' SPAN MAX.

1/0-3/C AL (TYPICAL)3'-2" SAG AT 120' AT 90 F

APPROVAL BY LIPA REQUIREDPRIOR TO INSTALLATION

2012 Edition Redbook

D6

Page 8: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

UNDERGROUND/OVERHEAD 100 - 320 AMPPOLE MOUNTED SERVICE

6" MIN.

10" MAX.

1/2" EYEBOLT

LIPA SERVICE DROP

CONDUIT SECURED

WITH STRAPS

METER SOCKET

MAIN DISCONNECT

PANEL ( MAY BE LOCATED

CUSTOMERS WIRES & POINT

OF ATTACHMENT

SERVICE POLE, MINIMUM25' - 30' CLASS 7

PRESERVATIVE TREATED AND SET

TO A MINIMUM DEPTH OF 6'-0"

(CUSTOMER OWNED AND INSTALLED)

6'-0" MIN.

6'-0" MIN.

1/2" X 8' CU WELD OR 5/8" X 8' CU PLATED

GROUND WIRE, TWO SEPARATE GROUNDINGCONDUCTORS. GROUNDING MUST BE PERFORMED

AT THE MAIN DISCONNECT.

LIPA METER

3'-0" MIN.

6'-0" MAX.

21'-0" MAX.

15'-0" MIN.

NOTE:

SERVICE POLE MUST BE ADEQUATELY GUYED

TO SUPPORT THE LOADS IMPOSED BY THE

LIPA SERVICE DROP. AT A MINIMUM THE

SERVICE POLE MUST BE GUYED WHEN SUPPORTING

SERVICE SIZE

(SINGLE PHASE)

LIPA SERVICE DROP LENGTH

100A NONE REQUIRED

(POLE GUY REQUIRED)

150A - 320A 60' - 100' (MAX)

400A 0' - 60' (MAX)

THE FOLLOWING SERVICE DROP LENGTHS:

GROUND ROD GROUND ROD5/8" X 8' CU PLATED 1/2" X 8' CU WELD OR

UNDERGROUND

LOAD SIDE EXIT

DWG. BASED ON

LIPA CS 2760

Section 11 - Drawings

D7

AT SERVICE ENTRANCE)

ALTERNATE OVERHEAD

GUYWIRE (SEE NOTE)

NOTE: USE OF PLYWOOD TO MOUNT

METER PAN IS NOT APPROVED

USAGE EXAMPLES:

. MOBILE HOME

. CUSTOMER OWNED PERMANENT SERVICE

. TEMPORARY SERVICE

Page 9: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

OVERHEAD 400 AMP

POLE MOUNTED SERVICE

6" MIN.

10" MAX.

LIPA SERVICE DROP

CONDUIT SECURED

WITH STRAPS

TRANS S CABINET

SERVICE POLE, MINIMUM25' - 30' CLASS 7

PRESERVATIVE TREATED AND SET

TO A MINIMUM DEPTH OF 6'-0"

(CUSTOMER OWNED AND INSTALLED)

6'-0" MIN.

LIPA METER

4'-0" MIN.

6'-0" MAX.

POINT OF ATTACHMENT 21'-0" MAX.

SEE DRAWING D1 FOR MINIMUM SERVICE DROP CLEARANCES

NOTE:

SERVICE POLE MUST BE ADEQUATELY GUYED

TO SUPPORT THE LOADS IMPOSED BY THE

LIPA SERVICE DROP. AT A MINIMUM THE

SERVICE POLE MUST BE GUYED WHEN SUPPORTING

SERVICE SIZE

(SINGLE PHASE)

LIPA SERVICE DROP LENGTH

(POLE GUY REQUIRED)

400A 0' - 60' (MAX)

THE FOLLOWING SERVICE DROP LENGTHS:

LOAD SIDE EXIT

DWG. BASED ON

LIPA CS 2760

4" X 6" TREATED

POLE GUY

3'-6" MIN.

LUMBER POST

MOUNT CABINET ON HORIZONTAL

TREATED LUMBER BRACES (3 MINIMUM)WITH LAG BOLTS.

124072

124072

2012 Edition Redbook

D8

USE OF PLYWOOD IS NOT APPROVED

Page 10: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

6" MIN.

10" MAX.

LIPA CONNECTS PROGRAM

CONNECTOR INSTALLATION

1. CLEANING - WIRE BRUSH ALL COPPER AND ALUMINUM CONDUCTORS UNTIL SURFACES ARE BRIGHT

AND CLEAN. COPPER CORROSION PRODUCTS ARE POOR CONDUCTORS AND ALUMINUM OXIDE, WHICH

FORMS RAPIDLY AND IS INVISIBLE, IS AN INSULATOR. WIRE BRUSHING IS A VERY IMPORTANT AND CRITICAL STEP IN MAKING A TROUBLE FREE CONNECTION AND SHOULD NEVER BE NEGLECTED EVEN

IF THE CONDUCTOR APPEARS TO BE CLEAN.

2. INHIBITOR - ALL NEW CONNECTORS ARE PRE-LOADED WITH INHIBITOR. IF ANY CONNECTORS DO NOT

HAVE INHIBITOR, IT MUST BE FIELD APPLIED.

3. RE-USE OF CONNECTORS - WHEN CONNECTORS ARE REMOVED AND RE-INSTALLED IN THE FIELD

(EVEN FOR A SHORT TIME), THE FOLLOWING STEPS SHALL BE TAKEN:

3.1 WIRE BRUSH BOTH THE CONDUCTOR AND THE JAWS OF THE CONNECTOR.

3.2 FOR ALUMINUM TO ALUMINUM AND ALUMINUM TO COPPER CONNECTIONS, APPLY INHIBITOR TO CONDUCTORS AND WIRE BRUSH IN.

3.3 FOR ALUMINUM TO COPPER CONNECTIONS, INSTALL THE ALUMINUM ABOVE THE COPPER CONDUCTOR.

WEATHERHEAD

1/2" EYEBOLT POINT OF ATTACHMENT

LIPA SERVICE WIRE

CONNECTORS, FURNISHED BY LIPA AND

MUST BE NO GREATER THAN 24" HORIZONTALLY

CONNECTOR INSTALLATION:

INSTALLED BY THE CONTRACTOR

USE CONNECTOR TO ATTACH CUSTOMERS

NEUTRAL TO LIPA SERVICE NEUTRAL

4. DO NOT TRANSFER SERVICE TO NEW POINT OF ATTACHMENT.

Section 11 - Drawings

D9

FROM WEATHERHEAD

DWG. BASED ON

LIPA CS 2753

Page 11: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

NOTES:

1. OVERHEAD SERVICES WHICH ARE 400 AMPERES BUT NOT MORE THAN 600

AMPERES SERVED BY OVERHEAD CONDUCTORS SHALL USE OPEN WIRE

CONSTRUCTION. IF THIS IS NOT ACCEPTABLE DUE TO HEIGHT OR

APPEARANCE UNDERGROUND SERVICE SHOULD BE SELECTED.

2. THE CUSTOMER IS TO INSTALL AND SUPPLY WEATHERHEAD, CONDUIT, CONDUIT

STRAPS, SECONDARY RACK AND CABLES IN THE CONDUIT. CABLES SHALL BE SUFFICIENT LENGTH TO PROVIDE 48" OF SLACK CABLE AT WEATHERHEAD

TO MAKE CONNECTIONS TO OVERHEAD SYSTEM.

3. SERVICE ENTRANCE HEIGHT SHALL BE BASED ON 60'(FEET) MAXIMUM SPAN AND MAINTENANCE OF 16.5 FEET MINIMUM CLEARANCE ABOVE GROUND UNDER

THE GREATEST SAG CONDITIONS AS WELL AS AN 18' MINIMUM CLEARANCE FOR

AREAS SUBJECT TO VEHICULAR TRAFFIC. MAXIMUM HEIGHT FOR POINT OF

LOCATION MUST BE APPROVED BY LIPA.

4. SECONDARY RACK ON SUPPORTING STRUCTURE MUST BE THRU-BOLTED; ANY OTHER TYPE FASTENERS MUST BE APPROVED BEFORE INSTALLATION.

OPEN WIRE SERVICES

400 TO 600 AMP

6" MIN.

10" MAX.

60' FEET MAXIMUM

SEE

NOTE 3

124072

124072

124072

UTILITY

POLE

CUSTOMER'S

POINT OF ATTACHMENT

ATTACHMENT IS 21' ABOVE GRADE. INCREASED HEIGHT FOR ANY INDIVIDUAL

8" TYPICAL

DWG. BASED ON

LIPA CS 2765

2012Edition Redbook

D10

IMPORTANT NOTE: 600 AMP OVERHEAD SERVICE MUST FIRST BE APPROVED BY LIPA, AND MAY BE PERMITTED ON A CASE BY CASE BASIS ONLY.

ALL SERVICES OF THIS TYPE MUST BE APPROVED BY LIPA PRIOR TO INSTALLATION.

Page 12: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

CABLE RISER

CUSTOMER INSTALLED

COMMUNICATIONS LINE

CURB

TRAFFIC

RISER

RISER LOCATION ON POLE

SEE

NOTE 4

5'

5'

12"

15'

24" MINIMUM COVER FOR SECONDARY

30" MINIMUM COVER FOR PRIMARY

(DIRECT BURIED)

FINAL GRADE

FOR DIRECT BURIED CABLES

IMPORTANT:

UTILITY SPLICING CREW

TO COMPLETE RISER POLE

(SEE NOTE 6)

SEE

NOTE 3

MIN.

SEE SHEET D12 FOR NOTES

FINAL GRADE

PIPE

CONDUIT

"OR"

1-1/2"

10"

MAX.

IF CONDUIT IS USED A MANHOLE / SPLICEBOX

(INCLUDING GROUNDING ANDBONDING MATERIAL)

IS REQUIRED, SEE NOTE 7

WARNING RIBBON

RISER SHALL BE POSITIONED SO THERE IS A

CLEAR VERTICAL PATH UP THE POLE TO

LIPA'S SECONDARY WIRES.

UNDER NO CIRCUMSTANCES SHALL AN

EXISTING OVERHEAD SERVICE BE CONNECTED

TO AN UNDERGROUND SERVICE.

MULTIPLE SETS OF CABLE FEEDING

MULTIPLE SERVICES MUST BE CLEARLY

IDENTIFIED.

DWG. BASED ON

LIPA CS 2403

Section 11 - Drawings

D11

Page 13: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

NOTES:

1. CONTRACTORS SHALL MOUNT ONLY THE UTILITY SPECIFIED RISER MATERIAL ON THE POLE,

TO A HEIGHT OF 9 TO 10 FEET ABOVE GRADE. ONLY ONE RISER IS PERMITTED FOR EACH SERVICE.

U-GUARD - 3" PE OR 3" PVC SCHD. 80 OR 3" DBL. GALV. STEEL - 10' LONG W/ BELL ENDS

SECONDARY CABLE MAX. PRIMARY CABLE MAX

4 - 1/C 350 KCM 3 - 2/C #1/0 AWG

5" DOUBLE GALVANIZED STEEL U-GUARD - 5' LONG W/ BELL ENDS or 5" PE or 5" PVC SCHD.80

SECONDARY CABLE MIN. SECONDARY CABLE MAX. PRIMARY CABLE MAX.

8 - 1/C 4/0 8 - 1/C 500 KCM 3-2/C 750 KCM

2. A) THE LOCATION OF THE U-GUARD ON THE POLE SHALL BE IDENTIFIED FOR THE CONTRACTOR OR THE LIPA REPRESENTATIVE ASSIGNED TO THE JOB PRIOR TO INSTALLATION OF THE CABLE / RISER.

B) THE LENGTH OF THE CABLE REQUIRED FOR LIPA TO MAKE FINAL CONNECTIONS AT THE POLE SHALL BE IDENTIFIED FOR THE CONTRACTOR BY THE LIPA REPRESENTATIVE.

3. A) THE CABLE SUPPLIED BY THE CONTRACTOR FOR USE ON THE POLE SHALL BE INSTALLED AND PROPERLY SECURED TO THE POLE BY THE ELECTRICAL CONTRACTOR TO PREVENT DAMAGE

AND/OR ANY ACTS OF VANDALISM FROM DAMAGING THE CABLE PRIOR TO HOOK-UP. B) CABLE IS TO BE ATTACHED TO THE POLE WELL ABOVE THE TOP OF THE RISER WITH A KELLUMS GRIP BASKET OR LENGTH OF LINE TIED IN A "ROLLING BEND KNOT" TO PROTECT

THE CABLE FROM MECHANICAL BENDING DAMAGE.

4. ALL CABLE SHALL BE PROPERLY END CAPPED AT BOTH ENDS BY THE CONTRACTOR WITH

APPROVED TIGHTFITTING WATERTIGHT SEALING CAPS OR IN STRICT COMPLIANCE WITH

NEC 300-5 (e). **

6. LIPA SHALL COMPLETE THE CONSTRUCTION OF THE RISER PER THE APPROPRIATE CONSTRUCTION

STANDARDS.

7. IF CONDUIT IS USED, MANHOLES ARE REQUIRED, CONTACT LIPA FOR DETAILS.

** THE CONCERN FOR RELIABLE ELECTRIC SERVICE REQUIRES THAT LIPA RESERVE THE RIGHT

TO REFUSE TO ACCEPT OR ENERGIZE ANY CABLES THAT HAVE BEEN LEFT WITH 'ENDS'

UNCAPED. MOISTURE INTRUSION HAS BEEN DETERMINED TO BE A SUBSTANTIAL CAUSE

OF PREMATURE CABLE FAILURES; UNCAPPED CABLE ENDS ARE THE LEADING CAUSE OF

THIS PROBLEM.

CUSTOMER INSTALLED CABLE RISER

GENERAL NOTES

5. POLYETHYLENE AND PVC U-GUARD SHALL BE FASTENED WITH 1/4" X 2 1/2" LAG SCREWS WITH CUSHION. STEEL U-GUARD SHALL BE FASTENED WITH 3/8" X 2 1/2" LAG SCREWS.

DWG. BASED ON

LIPA CS 2403

2012 Edition Redbook

D12

Page 14: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

PULL BOX AND MANHOLE SPECIFICATIONS

CUSTOMER / CONTRACTOR INSTALLED

SERVICE TYPE

SINGLE PHASE

AND

THREE PHASE

MAXIMUM CABLE SIZE

1 SET OF 4/0

BOX DESCRIPTION AND LOCATION

PE SPLICE BOX IN GRASS AND NO

VEHICLE TRAFFIC LOCATION

SPLICE BOX / MANHOLE MINIMUMDIMENSIONS

(LENGTH X WIDTH X DEPTH)(INCHES)

BOX: 25 X 16 X 16

COVER: 22 X 12

BOX: 33 X 20 X 17

COVER: 31 X 17

BOX: 41 X 41 X 18

COVER: 33 XX 33

BOX ID: 42 X 33 X 24

CAST IRON FRAME: 41 X 41

CAST IRON COVER: 32 DIAMETER

BOX ID: 54 X 42 X 48

CAST IRON FRAME: 41 X 41

CAST IRON COVER: 32 DIAMETER

SINGLE PHASE

2 SETS OF 4/0OR

1 SET OF 500 KCMVEHICLE TRAFFIC LOCATION

PE SPLICE BOX IN GRASS AND NO

SINGLE PHASE 2 SETS OF 500 KCM ORVEHICLE TRAFFIC LOCATION

PE SPLICE BOX IN GRASS AND NO

SINGLE PHASE

AND

THREE PHASE

4 SETS OF 4/0OR

2 SETS OF 500 KCM

PRECAST CONCRETE BOX TYPE B 3-6

LOCATED IN GRASS OR VEHICLE

TRAFFIC AREA

THREE PHASE

AND

SINGLE PHASE

1 SET OF 3-2/C 1/0 AL 15KV

OR

6 SETS OF 4/0

TRAFFIC AREA

LOCATED IN GRASS OR VEHICLE

PRECAST CONCRETE BOX TYPE TS

1. BOX / MANHOLE SHALL BE INSTALLED, OWNED AND MAINTAINED BY THE CUSTOMER.

2. BOX / MANHOLE SHALL BE INSTALLED ON THE CUSTOMERS PROPERTY AT THE LOCATION WHERE THE SERVICE EXITS THE CUSTOMERS PROPERTY AND ENTERS THE PUBLIC RIGHT OF WAY OR LIPA EASEMENT AREA.

3. INSTALL BOX / MANHOLE PARALLEL TO THE ROADWAY OR REAR PROPERTY EASEMENT LINE.

4. FOR CONCRETE MANHOLES:

ENTRANCE SHALL BE MADE THROUGH END WALL KNOCKOUTS ONLY.

DUCT SHALL EXTEND A MAXIMUM OF 1" PAST THE INTERIOR FACE OF THE MANHOLE WALL.

ALL PENETRATIONS THOUGH THE CONCRETE WALL SHALL BE SEALED WITH GROUT.

5. FOR PE SPLICE BOXES:

CONDUIT SHALL ENTER THE BOX BENEATH THE SIDE WALLS BY MEANS OF A CONDUIT SWEEP.

CONDUIT SHALL EXTEND 2" ABOVE THE BOTTOM OF THE BOX.

6. ALL CONDUITS SHALL BE SEALED AT THE BOX/MANHOLE AND BUILDING ENTRANCE USING PRODUCT SPECIFICALLY MADE FOR DUCT SEALING APPLICATION.

7. BONDING BUSHING MUST BE SUPPLIED FOR METALLIC CONDUITS.

INSTALLATION REQUIREMENTS:

DWG. BASED ON

LIPA CS 6159

Section 11 - Drawings

D13

THREE PHASE 1 SET OF 500 KCM

BOX: 41 X 41 X 18

COVER: 33 X 33VEHICLE TRAFFIC LOCATION

PE SPLICE BOX IN GRASS AND NO

BOX: 33 X 20 X 17

COVER: 31 XX 17THREE PHASE 1 SET OF 4/0

VEHICLE TRAFFIC LOCATION

PE SPLICE BOX IN GRASS AND NO

OR

3 SETS OF 500 KCM

8. 15KV PRIMARY CABLE INSTALLED IN TS BOX OR 41 X 41 X 18 PE BOX ONLY.

2 SET OF 3-2/C 1/0 AL 15KV

OR

1 SET OF 1-2/C 1/0 AL 15KV

Page 15: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

SECONDARY CONDUCTORS

GRADE

SUFFICIENT CABLE TO CONNECT

TO LIPA SECONDARY

SERVICE CONNECTION FROM PRIVATE PROPERTY - REAR PROPERTY POLE LINE

DIRECT BURIED CABLE (U.S.E.-2)*INSTALLED -OWNED AND

MAINTAINED BY CUSTOMER

RISER, SEE DWG. D11 & D12

4"

METER PAN *

SLEEVE *

2" MIN

(SEE NOTE 4)2'-0" MIN

COVER

GRADEEASEMENT

LINE

3'-0" MIN

6'-0" MAX

(SEE NOTE 5)

1'-0" MIN1'-6" MAX

UNDERGROUND SERVICE

FOR REQUIREMENTS

* SPLICE BOX REQD. IF

SERVICE IS IN CONDUIT

SERVICE CONNECTION FROM OVERHEAD DISTRIBUTION - NEAR SIDE HIGHWAY POLE LINE

100 - 800 AMP SINGLE OR THREE PHASE BY BUILDER/APPLICANT

5. 400 AMP - 800 AMP WILL REQUIRE 4'-0" MIN. HEIGHT TO TOP

3. OWNED AND MAINTAINED BY LIPA FROM SECONDARY CONDUCTORS

(SEE NOTE 4)

2" MIN

SLEEVE *

METER PAN *

DIRECT BURIED CABLE (U.S.E.-2)*

MAINTAINED BY CUSTOMER

INSTALLED -OWNED AND

ROAD SURFACE

SECONDARY CONDUCTORS

GRADE

FOR REQUIREMENTS

RISER, SEE DWG. D11 & D12

TO LIPA SECONDARY

SUFFICIENT CABLE TO CONNECT

4"

SERVICE IS IN CONDUIT

* SPLICE BOX REQD. IF

CURB

LINE

PROPERTY

3'-0" MIN

1'-6" MAX1'-0" MIN

(SEE NOTE 5)6'-0" MAX

GRADE

2'-0" MIN

COVER

NOTES

TO CUSTOMERS PROPERTY LINE.

1. * INDICATES ITEMS PROVIDED BY CUSTOMER.

2. FIRST 10' OF U-GUARD RISER TO BE INSTALLED BY CONTRACTOR

AND THE REMAINDER TO BE COMPLETED BY LIPA.

5. 400 AMP - 800 AMP WILL REQUIRE 4'-0" MIN. HEIGHT TO

3. OWNED AND MAINTAINED BY LIPA FROM SECONDARY CONDUCTORS

2. FIRST 10' OF U-GUARD RISER TO BE INSTALLED BY CONTRACTOR

AND THE REMAINDER TO BE COMPLETED BY LIPA.

TO EASMENT LINE.

NOTES

1. * INDICATES ITEMS PROVIDED BY CUSTOMER.

4. 2" MINIMUM SLEEVE, RIGID METAL SHALL BE SCHD. 40 GALV., NON-METALLIC SHALL BE SCHD. 80.

4. 2" MINIMUM SLEEVE, RIGID METAL SHALL BE SCHD. 40 GALV., NON-METALLIC SHALL BE SCHD. 80.

WARNING RIBBON

WARNING RIBBON

DWG. BASED ON

LIPA CS 5523

2012 Edition Redbook

D14

TOP OF METER GLASS.

3'-0" MAX

3'-0" MAX

OF METER GLASS.

Page 16: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

SECONDARY CONDUCTORS

NOTES

GRADE ROAD SURFACECURB

SUFFICIENT CABLE TO CONNECT

TO LIPA SECONDARY

SERVICE CONNECTION FROM FAR SIDE - HIGHWAY POLE LINE

CURB

* MIN 2" GI OR

SCHEDULE 40 NON-METALIC

CUSTOMER INSTALLED

DIRECT BURIED CABLE (USE-2)INSTALLED -OWNED AND

MAINTAINED BY CUSTOMER

RISER, SEE DWG. D11 & D12

4"

METER PAN *

SLEEVE *

2" MIN

(SEE NOTE 3)2'-0" MIN

COVER

GRADEPROPERTY

LINE

3'-0" MIN

6'-0" MAX

(SEE NOTE 4)

1'-0" MIN1'-6" MAX

* MIN 2" G.I. SWEEP OR SCHEDULE 80 NON METALIC SWEEP CUSTOMER INSTALLED

DIRECT BURIED CABLE (USE-2)

SLEEVE *

METER PAN *

(SEE NOTE 3)2" MIN

MAINTAINED BY CUSTOMER

1'-6" MAX

1'-0" MIN

INSTALLED -OWNED AND

2'-0" MIN

COVER

LINE

PROPERTY

CURB

NOTES

6'-0" MAX

3'-0" MIN

(SEE NOTE 4)

GRADE LINEROAD SURFACE

SPLICE *

BOX

* SUFFICIENT CABLE TO CONNECT

TO LIPA SECONDARY

(LIPA TO PREPARE CONNECTION)SEE NOTES 1 & 2

UNDERGROUND SERVICE

FOR REQUIREMENTS

1. * INDICATES ITEMS PROVIDED BY CUSTOMER.

2. OWNED AND MAINTAINED BY LIPA FROM

SECONDARY CONDUCTORS TO BASE OF POLE.

4. 400 AMP - 800 AMP WILL REQUIRE 4'-0" MIN. HEIGHT. TO TOP OF METER GLASS.

* SPLICE BOX REQD. IF

SERVICE IS IN CONDUIT

1.CONDUIT AND SPLICE BOX WILL BE REQUIRED IN ZONED

NETWORK AREAS, IN ZONED U.G. AREAS A SPLICE BOX MAY BE

REQUIRED. IF SERVICE IS IN CONDUIT A SPLICE BOX IS REQUIRED.

CONTRACTOR TO LEAVE 4' OF SERVICE CABLE IN SPLICE BOX

2. WHERE NO SPLICE BOX IS REQUIRED, CONTRACTOR TO LEAVE THREE

(3) FEET OF SERVICE CABLE (OR AS DIRECTED BY LIPA) FOR LIPA CONNECTIONS.

4. 400 AMP - 800 AMP WILL REQUIRE 4'-0" MIN. HEIGHT.

5. * INDICATES ITEMS PROVIDED BY CUSTOMER.

FOR LIPA CONNECTIONS.

SERVICE CONNECTION FROM UNDERGROUND DISTRIBUTION - NEAR OR FAR SIDE FACILITIES

100 - 800 AMP SINGLE OR THREE PHASE BY BUILDER/APPLICANT

3. 2" MINIMUM SLEEVE, RIGID METAL SHALL BE

SCHD. 40 GALV., NON-METALLIC SHALL BE SCHD 80.

3. 2" MINIMUM SLEEVE, RIGID METAL SHALL BE

SCHD. 40 GALV., NON-METALLIC SHALL BESCHD 80.

WARNING

RIBBON

WARNING RIBBON

DWG. BASED ON

LIPA CS 5523

Section 11 - Drawings

D15

3'-0" MAX

TO TOP OF METER GLASS.

3'-0" MAX

Page 17: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

METER PAN *

3" WATERTIGHT ADAPTOR *

(CONDUIT TO METER)

OR RIGID GALVANIZED

(TO LIPA SPEC)

3" SCHEDULE 80 PVC *

FINAL GRADE

CABLE-IN-CONDUIT

24" MIN.

6" TO 12"

45*CUT CONDUIT @CONDUIT END

DUCT SEAL

LIPA INSTALLED SINGLE PHASE RESIDENTIAL RUD SERVICE

36" MAX.

NOTES:

1. * INDICATES ITEMS PROVIDED BY CONTRACTOR.

2. 300 AMP AND LARGER SERVICES MAY REQUIRE TWO CONDUITS INTO METER PAN.

CABLE-IN-CONDUIT

24" MIN.

FINAL GRADE

36" MAX.

(CONDUIT TO METER)

2" SCHEDULE 80 PVC *

OR RIGID GALV. STEEL

2" WATERTIGHT ADAPTOR *

(TO LIPA SPEC)

METER PAN *

6"

2" PVC OR RGS COUPLING*

45 SWEEP*

2" MECHANICAL

COUPLING *

AIM IN DIRECTION

OF SPLICE BOX

3 INCH SERVICE RISER 2 INCH SERVICE RISER

3. 2" MECHANICAL COUPLING SHALL BE EITHER ANACO P/N HUSKY SD-4006 OR FERNCO P/N 1056-22/SR-11.

DWG. BASED ON

LIPA CS 6491

2012 Edition Redbook

D16

Page 18: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

SPLICE BOX

IN CONDUIT

COMMON TRENCH

CURB

UTILITY CABLE

IN CONDUIT

CURB

ROAD

ROAD

SERVICE CONDUIT SYSTEM *

COILED & COVERED

WITH 4'x4'x1/2" PLYWOOD

* SEAL CABLE ENDS

SCHD. 40 CONDUIT *

DUCTSEAL CONDUIT *

SEAL CABLE *

ENDS

PLYWOOD *

24" MIN.

SPLICE BOX

PLAN VIEW

UTILITY CABLE

(TEMPORARY)

24"

* TERMINATE CONDUIT

24" AWAY FROM SPLICEBOX ON CENTERLINE.

TEMPORARY 48" x 48" x 1/2"

(MIN. SCHD 40)

10 FOOT MINIMUM CABLE *

ANGLE OF APPROACH TO SPLICE BOX

TO BE DETERMINED BY LOCAL FIELD

CONDITIONS AND APPROVAL BY UTILITY.

SINGLE PHASE RESIDENTIAL RUD SERVICE

CUSTOMER / CONTRACTOR INSTALLED

NOTES:

1. * DENOTES ITEMS PERFORMED BY CONTRACTOR / CUSTOMER.

2. UTILITY CONNECTS CONDUIT TO SPLICE BOX AND MAKES SERVICE CONNECTIONS IN SPLICE BOX.

ELEVATION VIEW

3. 200 AMP SERVICES SHALL BE RUN IN ONE 2" CONDUIT MIN. 320 AMP SERVICES SHALL BE RUN IN A 3 1/2" CONDUITS MIN. . 400 AMP SERVICES SHALL BE RUN IN A SINGLE 4" CONDUIT. ALL SERVICES SHALL BE RUN FROM THE

METER PAN TO A SPLICE BOX AT THE PROPERTY LINE.

4. 600 AND 800 AMP SERVICES SHALL BE RUN IN TWO PARALLEL 4" CONDUITS FROM THE TRANS S CABINET TO A

SPLICE BOX AT THE PROPERTY LINE. 600 AND 800 AMP SERVICES ARE INSTALLED, OWNED AND MAINTAINED BY THE CUSTOMER.

DWG. BASED ON

LIPA CS 6491

Section 11 - Drawings

D17

5. UNDER NO CIRCUMSTANCES SHALL A CUSTOMER / CONTRACTOR ENTER A LIPA SPLICE BOX.

ELECTRIC SERVICE

CABLE IN CONDUIT

COMMUNICATIONS

FACILITIES

GAS SERVICE

12" MIN. 24"

SERVICE TRENCH

Page 19: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

INSIDE WALL

METER SOCKET ENCLOSURE

SECURELY AND LEVEL IN HORIZONTAL

AND VERTICAL PLANES

MAIN DISCONNECT

OVERHEAD SERVICE CONDUIT

CONDUIT STRAP (TYP.)

"LB" CONDULET

GROUND CONDUCTOR

GROUND CLAMP

5/8" X 8' CU PLATED GROUND ROD

FINISHED GRADE

3'-0" MIN / 6'-0" MAX

SEE NOTES 5 & 6

7. A FOUR FOOT CLEARANCE FROM FLOOR TO CEILING SHALL BE MAINTAINED IN FRONT OF THE METER

WITHOUT BEING ENCASED IN CONDUIT ON THE LINE SIDE OF THE METER ENCLOSURE,

8. IN ADDITION TO LIPA's REQUIREMENTS, INSTALLATIONS MAY BE SUBJECT TO THE APPROVAL

THE TOP OF THE METER PAN. WEATHERTIGHT TYPE "SE" CONNECTORS SHALL BE USED FOR

FEET ABOVE FINISHED GRADE. THE SLEEVE SHALL BE SPACED A MINIMUM OF ONE INCH FROM

CONDUIT. PROTECTIVE SLEEVING ON TYPE "SE" CABLE IS REQUIRED TO A HEIGHT OF EIGHT

THE SIDE OF A BUILDING ADJACENT TO A DRIVEWAY THE CABLE SHALL BE ENCASED IN

OTHER OBJECTS THAT CAN CAUSE MECHANICAL INJURY TO THE CABLE. WHEN INSTALLED ON

PROVIDING IT WILL NOT COME IN CONTACT WITH ANY AWNINGS, SHUTTERS, SIGNS, OR ANY

6. SERVICE ENTRANCE TYPE "SE" CABLE SHALL BE AS APPROVED BY LIPA AND CAN BE USED

THE NATIONAL ELECTRIC CODE.

4. GROUNDING SHALL BE IN ACCORDANCE WITH THE APPLICABLE SECTIONS OF ARTICLE 250 OF

2. ALL METER PAN ASSEMBLIES SHALL BE AS APPROVED BY LIPA. METER SOCKETS SHALL BE

1. ALL ITEMS SHOWN SHALL BE FURNISHED AND INSTALLED BY THE CUSTOMER UNLESS OTHERWISE

OF THE AUTHORIZED ELECTRICAL INSPECTION AGENCY AS WELL AS LOCAL MUNICIPALITIES.

CONNECTION TO THE METER ENCLOSURE.

EQUIPPED WITH A FIFTH JAW LOCATED IN THE NINE O'CLOCK POSITION.

INSTALLATION FOR SAFE ACCESS.

NOTES:

STATED.

1/2" x 8' CU WELD OR

FLOOR TO CEILING

4' CLEARANCE

TO NEUTRAL OF

CUSTOMER'S MAIN

DISTRIBUTION PANEL

9. ONLY FACTORY PREFABRICATED KNOCKOUTS ON METER ENCLOSURE SHALL BE USED.

TO CUSTOMER'S

TOP OF METER GLASS

TO BE MOUNTED

OVERHEAD SERVICE

SINGLE PHASE SELF CONTAINED METER

OUTDOOR SOCKET METER INSTALLATION

5. OVERHEAD SERVICE CONDUITS AND PROTECTIVE SLEEVES SHALL BE IN ACCORDANCE WITH THE NATIONAL

ELECTRIC CODE(NEC).

ADEQUATELY SECURED

DWG. BASED ON

LIPA CS 8001

2012 Edition Redbook

D18

3. GAS SERVICE PIPES SHALL NOT BE USED AS A GROUNDING ELECTRODE.

Page 20: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

1/2" x 8' CU WELD OR5/8" X 8' CU PLATED

INSIDE WALL

METER SOCKET

TO CUSTOMER'S

CONDUIT STRAP

"LB" CONDULET

GROUND CONDUCTOR

GROUND CLAMP

MAIN DISCONNECT

ENCLOSURE

SECURELY AND

RIGIDLY MOUNTED

SERVICE ENTRANCE

CONDUIT & CABLE

3'-0" MIN.

6'-0" MAX.

(TYP.)

GROUND ROD

LOCKNUT AND

BONDING

BUSHING (TYP.)

7. IN ADDITION TO LIPA's REQUIREMENTS, INSTALLATIONS MAY BE SUBJECT TO THE APPROVAL

THE NATIONAL ELECTRIC CODE.

4. GROUNDING SHALL BE IN ACCORDANCE WITH THE APPLICABLE SECTIONS OF ARTICLE 250 OF

2. ALL METER PAN ASSEMBLIES SHALL BE AS APPROVED BY LIPA. METER SOCKETS SHALL BE

1. ALL ITEMS SHOWN SHALL BE FURNISHED AND INSTALLED BY THE CUSTOMER UNLESS OTHERWISE

OF THE LOCAL ELECTRICAL INSPECTION AGENCY AS WELL AS LOCAL MUNICIPALITIES.

EQUIPPED WITH A FIFTH JAW LOCATED IN THE NINE O'CLOCK POSITION.

NOTES:

STATED.

TO NEUTRAL OF

CUSTOMER'S MAIN

TOP OF

METER GLASS

A FOUR FOOT CLEARANCE FROM FLOOR TO CEILING SHALL BE MAINTAINED IN FRONT OF THE

METER INSTALLATION FOR SAFE ACCESS.

6.

4' CLEARANCE

FLOOR TO CEILING

12" MIN.

CLEARANCE

FINISHED

GRADE

12" MIN.

CLEARANCE

WALL

WALL

8. ONLY FACTORY PREFABRICATED KNOCKOUTS ON METER ENCLOSURES SHALL BE USED.

DISTRIBUTION

PANEL

UNDERGROUND SERVICE

SINGLE PHASE SELF CONTAINED METER

OUTDOOR SOCKET METER INSTALLATION

LUG

NEUTRAL

MAIN DISCONNECT

METER SOCKET

& LOCKNUT (TYP)

BONDING BUSHING

& CABLE

CONDUIT

LINE SIDE TO CUSTOMER

BYPASS

(TYP)

LEVER

UNDERGROUND

(SEE NOTE 5)

5. RIGID METALLIC CONDUIT (RMC) AND RIGID NON-METALLIC CONDUIT (RNC) (SCHD. 40 OR 80 RESPECTIVELY, AS REQUIRED), ARE APPROVED FOR BELOW GRADE USE. ELECTRIC METALLIC TUBING (EMT) AND INTERMEDIATE METALLIC CONDUIT (IMC) ARE NOT APPROVED FOR BELOW GRADE INSTALLATION.

DWG. BASED ON

LIPA CS 8007

Section 11 - Drawings

D19

9. LINE AND LOAD CONDUCTORS SHALL NOT CROSS WITHIN THE METER ENCLOSURE, RIGHT SIDE OF

METER ENCLOSURE SHALL NOT BE USED AS A RACEWAY EXCEPT FOR ROUTING NEUTRAL CABLE AS

SHOWN. NEUTRAL CABLE SHALL BE NEATLY TRAINED TO PERMIT PROPER OPERATION OF THE LEVEL,

AND SHALL BE COVERED WIRE.

3. GAS SERVICE PIPES SHALL NOT BE USED AS A GROUNDING ELECTRODE.

Page 21: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

SECURELY AND LEVEL IN HORIZ.

AND VERTICAL PLANES

CONDUIT STRAP

GROUND CLAMP

FINISHED GRADE

GROUND

(TYP)OVERHEAD

SERVICE

CONDUIT

CONDUCTOR

SEE NOTES

5 & 6

6'-0" MAX

2'-3" MIN

TOP OF METER GLASS

TOP OF METER GLASS

WITHOUT BEING ENCASED IN CONDUIT ON THE LINE SIDE OF THE METER ENCLOSURE,

8. IN ADDITION TO LIPA's REQUIREMENTS, INSTALLATIONS MAY BE SUBJECT TO THE APPROVAL

THE TOP OF THE METER PAN. WEATHERTIGHT TYPE "SE" CONNECTORS SHALL BE USED FOR

FEET ABOVE FINISHED GRADE. THE SLEEVE SHALL BE SPACED A MINIMUM OF ONE INCH FROM

CONDUIT. PROTECTIVE SLEEVING ON TYPE "SE" CABLE IS REQUIRED TO A HEIGHT OF EIGHT

THE SIDE OF A BUILDING ADJACENT TO A DRIVEWAY THE CABLE SHALL BE ENCASED IN

OTHER OBJECTS THAT CAN CAUSE MECHANICAL INJURY TO THE CABLE. WHEN INSTALLED ON

PROVIDING IT WILL NOT COME IN CONTACT WITH ANY AWNINGS, SHUTTERS, SIGNS, OR ANY

6. SERVICE ENTRANCE TYPE "SE" CABLE SHALL BE AS APPROVED BY LIPA AND CAN BE USED

THE NATIONAL ELECTRIC CODE.

4. GROUNDING SHALL BE IN ACCORDANCE WITH THE APPLICABLE SECTIONS OF ARTICLE 250 OF

3. GAS SERVICE PIPES SHALL NOT BE USED AS A GROUNDING ELECTRODE. WIRES INTENDED TO

2. ALL METER PAN ASSEMBLIES SHALL BE AS APPROVED BY LIPA. METER SOCKETS SHALL BE

1. ALL ITEMS SHOWN SHALL BE FURNISHED AND INSTALLED BY THE CUSTOMER UNLESS OTHERWISE

OF THE LOCAL ELECTRICAL INSPECTION AGENCY AS WELL AS LOCAL MUNICIPALITIES.

CONNECTION TO THE METER ENCLOSURE.

BE USED FOR BONDING SHALL NOT BE PLACED IN CONTACT WITH ANY GAS PIPE.

EQUIPPED WITH A FIFTH JAW LOCATED IN THE NINE O'CLOCK POSITION.

NOTES:

STATED.

6' MAX

A FOUR FOOT CLEARANCE FROM FLOOR TO CEILING SHALL BE MAINTAINED IN FRONT OF THE METER

INSTALLATION FOR SAFE ACCESS.

7.

10. ALL METER PANS AND SERVICE DISCONNECT SWITCHES SHALL BE PERMANENTLY STENCILED INTERNALY

AND EXTERNALLY WITH THE BUILDING AND/OR SUITE NUMBER TO IDENTIFY THE PORTION OF THE PREMISES

9. ONLY FACTORY PREFABRICATED KNOCKOUTS ON METER ENCLOSURES SHALL BE USED.

1/2" x 8' COPPER WELD OR 5/8" X 8' COPPER PLATEDGROUND ROD

4' CLEARANCE

FLOOR TO CEILING

12"MIN.12" MIN

WALLWALL

GROUND

CND. TO

NEUTRAL

BLOCK.

FINISHED

GRADE

METER SOCKET ENCLOSURE

TO BE MOUNTED

2'-3"

MIN.

GROUND CONDUCTOR

TO WATER PIPE

BEING SERVED.

OVERHEAD AND UNDERGROUND SERVICE

SINGLE PHASE SELF CONTAINED METER

OUTDOOR SOCKET TROUGH MULTIMETER INSTALLATION

5. OVERHEAD SERVICE CONDUITS AND PROTECTIVE SLEEVES SHALL BE IN ACCORDANCE WITH

THE NATIONAL ELECTRIC CODE(NEC).

UNDERGROUND SERVICE CONDUIT

(SEE NOTE 11)

11. RIGID METALLIC CONDUIT (RMC) AND RIGID NON-METALLIC CONDUIT (RNC) (SCHD. 40 OR 80 RESPECTIVELY, AS REQUIRED), ARE APPROVED FOR BELOW GRADE USE. ELECTRIC METALLIC TUBING (EMT) AND INTERMEDIATE METALLIC CONDUIT (IMC) ARE NOT APPROVED FOR BELOW GRADE INSTALLATION.

SUITE I.D.

SEE NOTE 10

DWG BASED ON

LIPA CS 8005

2012 Edition Redbook

D20

OVERHEAD SERVICE CONDUIT

Page 22: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

1. ALL ITEMS SHOWN SHALL BE FURNISHED AND INSTALLED BY THE CUSTOMER UNLESS OTHERWISE STATED.

2. ALL METER PAN ASSEMBLIES SHALL BE AS APPROVED BY LIPA. METER SOCKETS SHALL BE EQUIPPED WITH A FIFTH JAW

3. GAS PIPES SHALL NOT BE USED AS A GROUNDING ELECTRODE.

4. GROUNDING SHALL BE IN ACCORDANCE WITH THE APPLICABLE SECTIONS OF ARTICAL 250 OF THE NATIONAL ELECTRICAL

CODE.

6. SERVICE ENTRANCE TYPE "SE" CABLE SHALL BE AS APPROVED BY LIPA AND CAN BE USED WITHOUT BEING ENCASED IN

IN CONDUIT ON THE LINE SIDE OF THE METER ENCLOSURE, PROVIDING IT WILL NOT COME IN CONTACT WITH ANY AWNINGS,

SHUTTERS, SIGNS, OR ANY OTHER OBJECTS THAT CAN CAUSE MECHANICAL INJURY TO THE CABLE. WHEN INSTALLED ON THE SIDE OF A BUILDING ADJACENT TO A DRIVEWAY THE CABLE SHALL BE ENCASED IN CONDUIT. PROTECTIVE SLEEVING ON

TYPE "SE" CABLE IS REQUIRED TO A HEIGHT OF EIGHT FEET ABOVE FINISHED GRADE. THE SLEEVE SHALL BE SPACED APPROXIMATELY ONE INCH FROM THE TOP OF THE METER PAN. WEATHER TIGHT TYPE "SE" CONNECTORS SHALL BE USED

7. A FOUR FOOT CLEARANCE FROM FLOOR TO CEILING SHALL BE MAINTAINED IN FRONT OF THE METER INSTALLATION FOR

8. IN ADDITION TO LIPA REQUIREMENTS, INSTALLATIONS, MAY BE SUBJECT TO THE APPROVAL OF THE LOCAL ELECTRICAL INSPECTION AGENCY AS WELL AS LOCAL MUNICIPALITIES HAVING JURISDICTION.

10. ONLY FACTORY PREFABRICATED KNOCKOUTS ON METER ENCLOSURES SHALL BE USED.

9. ALL METER PANS AND SERVICE DISCONNECT SWITCHES SHALL BE PERMANENTLY STENCILED INTERNALLY AND EXTERNALLY

WITH THE BUILDING AND/OR SUITE NUMBER TO IDENTIFY THE PORTION OF THE PREMISES BEING SERVED.

LOCATED IN THE NINE O' CLOCK POSITION.

FOR CONNECTION TO THE METER ENCLOSURE.

NOTES:

SAFE ACCESS.

FINISHED FLOOR OR GRADE

WALL

12" MIN

INTERNAL BUSING

OF METER GLASS

TOP

3'-0" MIN.

6'-0" MAX.

1/2" x 8' CU WELD OR

OVERHEAD ENTRANCE

WALL

12" MIN

UNDERGROUND AND OVERHEAD SERVICE

SINGLE PHASE SELF CONTAINED METERS

OUTDOOR MULTI-METER SOCKET ENCLOSURE

(SEE NOTES 5 & 6)

5. OVERHEAD SERVICE CONDUITS AND PROTECTIVE SLEEVES SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE(NEC).

5/8" X 8' CU PLATED GROUND ROD

ALTERNATE UNDERGROUND

CONDUIT ENTRANCE

(SEE NOTE 11)

11. RIGID METALLIC CONDUIT (RMC) AND RIGID NON-METALLIC CONDUIT (RNC) (SCHD. 40 OR 80 RESPECTIVELY, AS REQUIRED), ARE APPROVED FOR BELOW GRADE USE. ELECTRIC METALLIC TUBING (EMT) AND INTERMEDIATE METALLIC CONDUIT (IMC) ARE NOT APPROVED FOR BELOW GRADE INSTALLATION.

UNIT IDENTIFICATION

SEE NOTE 9

DWG. BASED ON

LIPA CS 8009

Section 11 - Drawings

D21

GROUND CONDUCTOR TO

NEUTRAL OF CUSTOMERS

MAIN DISCONNECT PANEL

12. LINE AND LOAD CONDUCTORS SHALL NOT CROSS WITHIN THE METER ENCLOSURE. RIGHT SIDE OF METER ENCLOSURE

SHALL NOT BE USED AS A RACEWAY EXCEPT FOR ROUTING NEUTRAL CABLE AS SHOWN. NEUTRAL CABLE SHALL

BE NEATLY TRAINED SO AS TO PERMIT PROPER OPERATION OF THE LEVER, AND SHALL BE COVERED WIRE.

Page 23: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

FINISHED GRADE

"LB" CONDULET

INSIDE WALL

MOUNT PLUMB & LEVEL

TO CUSTOMER'S

WITHOUT BEING ENCASED IN CONDUIT ON THE LINE SIDE OF THE METER ENCLOSURE,

THE TOP OF THE METER PAN. WEATHERTIGHT TYPE "SE" CONNECTORS SHALL BE USED FOR

FEET ABOVE FINISHED GRADE. THE SLEEVE SHALL BE SPACED A MINIMUM OF ONE INCH FROM

CONDUIT. PROTECTIVE SLEEVING ON TYPE "SE" CABLE IS REQUIRED TO A HEIGHT OF EIGHT

THE SIDE OF A BUILDING ADJACENT TO A DRIVEWAY THE CABLE SHALL BE ENCASED IN

OTHER OBJECTS THAT CAN CAUSE MECHANICAL INJURY TO THE CABLE. WHEN INSTALLED ON

PROVIDING IT WILL NOT COME IN CONTACT WITH ANY AWNINGS, SHUTTERS, SIGNS, OR ANY

6. SERVICE ENTRANCE TYPE "SE" CABLE SHALL BE AS APPROVED BY LIPA AND CAN BE USED

THE NATIONAL ELECTRIC CODE.

4. GROUNDING SHALL BE IN ACCORDANCE WITH THE APPLICABLE SECTIONS OF ARTICLE 250 OF

2. ALL METER PAN ASSEMBLIES SHALL BE AS APPROVED BY LIPA. METER SOCKET ASSEMBLY

1. ALL ITEMS SHOWN SHALL BE FURNISHED AND INSTALLED BY THE CUSTOMER UNLESS OTHERWISE STATED.

CONNECTION TO THE METER ENCLOSURE.

SHALL BE EQUIPPED WITH A LEVER OPERATED, JAW RELEASE BYPASS MECHANISM.

NOTES:

CONDUIT STRAPS

MAIN DISCONNECT

POINT OF

ATTACHMENT

LEAVE 3'-0" OF CONDUCTOR

FOR CONNECTION. FINAL

CONNECTION BY LIPA.

SERVICE ENTRANCE

WEATHER HEAD

SERVICE DROP CABLE

TOP OF METER GLASS

OUTDOOR POLYPHASE

METER SOCKET

240/120 208Y/120

PHASE B BLACK BLACK

PHASE C ORANGE RED

NEUTRAL WHITE OR GRAY

PHASE A BLUE BLUE

LINE SIDEHUB

NEUTRAL LUG

ALTERNATE POSITION

OF LOAD CONDUIT

BONDING BUSHING

& LOCKNUT

METER SOCKET

LOAD SIDE

15'-0"MIN

6'-0"MAX

6"MIN

10"MAX

3'-0"MIN

CONDUIT

OVERHEAD SERVICE CONDUIT

A

N A

B C

B C

TO NEUTRAL OF

CUSTOMER'S MAIN

DISTRIBUTION PANEL

4' CLEARANCE

FLOOR TO CEILING

1/2" x 8' CU WELD OR5/8" X 8' CU PLATEDGROUND ROD

GROUND CONDUCTOR

PHASE CONDUCTOR IDENTIFICATION

MIN. 2" COLORED TAPE

CONDUCTORS TO BE

IDENTIFIED WITH COLORED

TAPE

DELTA WYE

OVERHEAD SERVICE

POLY-PHASE SELF CONTAINED METERS

200 AMPERE SOCKET METER INSTALLATION

(SEE NOTES 5 & 6)

5. OVERHEAD SERVICE CONDUITS AND PROTECTIVE SLEEVES SHALL BE IN ACCORDANCE WITH THE

NATIONAL ELECTRIC CODE.(NEC)

ADEQUATELY SECURED

DWG. BASED ON

LIPA CS 8207

2012 Edition Redbook

D22

7. A FOUR FOOT CLEARANCE FROM FLOOR TO CEILING SHALL BE MAINTAINED IN FRONT OF THE METER

8. IN ADDITION TO LIPA's REQUIREMENTS, INSTALLATIONS MAY BE SUBJECT TO THE APPROVAL OF THE LOCAL ELECTRICAL INSPECTION AGENCY AS WELL AS LOCAL MUNICIPALITIES.

INSTALLATION FOR SAFE ACCESS.

9. ONLY FACTORY PREFABRICATED KNOCKOUTS ON METER ENCLOSURES SHALL BE USED.

10. LINE AND LOAD CONDUCTORS SHALL NOT CROSS WITHIN THE METER ENCLOSURE. RIGHT SIDE OF METER ENCLOSURE

SHALL NOT BE USED AS A RACEWAY EXCEPT FOR ROUTING NEUTRAL CABLE AS SHOWN. NEUTRAL CABLE SHALL

BE NEATLY TRAINED SO AS TO PERMIT PROPER OPERATION OF THE LEVER, AND SHALL BE COVERED WIRED.

11. CONDUIT SHALL BE RIGID METAL OR SCHEDULE 80 PVC.

3. GAS SERVICE PIPES SHALL NOT BE USED AS A GROUNDING ELECTRODE

Page 24: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

MOUNT SOCKET SECURELY,

TO CUSTOMER'S

6. A FOUR FOOT CLEARANCE FROM FLOOR TO CEILING SHALL BE MAINTAINED IN FRONT OF THE METER

7. IN ADDITION TO LIPA's REQUIREMENTS, INSTALLATIONS MAY BE SUBJECT TO THE APPROVAL

THE NATIONAL ELECTRIC CODE.

4. GROUNDING SHALL BE IN ACCORDANCE WITH THE APPLICABLE SECTIONS OF ARTICLE 250 OF

2. ALL METER PAN ASSEMBLIES SHALL BE AS APPROVED BY LIPA. METER SOCKET ASSEMBLY SHALL BE EQUIPPED

1. ALL ITEMS SHOWN SHALL BE FURNISHED AND INSTALLED BY THE CUSTOMER UNLESS OTHERWISE

OF THE LOCAL ELECTRICAL INSPECTION AGENCY AS WELL AS LOCAL MUNICIPALITIES.

WITH A LEVER OPERATED, JAW RELEASE BYPASS MECHANISM. ONLY NEUTRAL CONDUCTOR IS PERMITTED BEHIND

INSTALLATION FOR SAFE ACCESS.

NOTES:

CONDUIT STRAP

PLUMB & LEVEL

MAIN DISCONNECT

OUTDOOR POLYPHASE

METER SOCKET

DELTA WYE

PHASE B BLACK BLACK

PHASE C ORANGE RED

NEUTRAL WHITE OR GRAY

PHASE A BLUE BLUE

GROUND

FINISHED GRADE

"LB" CONDULET

INSIDE WALL

3'-0"MIN

6'-0"MAX

CONDUCTOR

TOP OF METER GLASS

4' CLEARANCE

FLOOR TO CEILING

TO NEUTRAL OF

CUSTOMER'S MAIN

DISTRIBUTION PANEL

1/2 x 8' CU WELD OR5/8" X 8' CU PLATED GROUND ROD

PHASE CONDUCTOR IDENTIFICATION

MIN. 2" COLORED TAPE

8. ONLY FACTORY PREFABRICATED KNOCKOUTS ON METER ENCLOSURES SHALL BE USED.

STATED.

240/120 208Y/120

UNDERGROUND SERVICE

POLY-PHASE SELF CONTAINED METERS

200 AMPERE SOCKET METER INSTALLATION

LUG

NEUTRAL

DISCONNECT

METER SOCKET

& LOCKNUT (TYP)

BONDING BUSHING

& CABLE

CONDUIT

LINE SIDE

TO CUSTOMER

MAIN

PERMANENT

BYPASSN BA

A B

C

C (TYP)LEVER

NEUTRAL

JUMPER

(TYP)

UNDERGROUND SERVICE CONDUIT

(SEE NOTE 5)

5. RIGID METALLIC CONDUIT (RMC) AND RIGID NON-METALLIC CONDUIT (RNC) (SCHEDULE 40 OR 80 RESPECTIVELY, AS REQUIRED), ARE APPROVED FOR BELOW GRADE USE. ELECTRIC METALLIC TUBING (E.M.T.) AND INTERMEDIATE METALLIC CONDUIT (I.M.C.) ARE NOT APPROVED FOR BELOW GRADE INSTALLATION.

ADEQUATELY SECURED

BYPASS LEVER.

DWG. BASED ON

LIPA CS 8209

Section 11 - Drawings

D23

9. LINE AND LOAD CONDUCTORS SHALL NOT CROSS WITHIN THE METER ENCLOSURE. RIGHT SIDE OF

METER ENCLOSURE SHALL NOT BE USED AS A RACEWAY EXCEPT FOR ROUTING NEUTRAL CABLE AS SHOWN.

NEUTRAL CABLE SHALL BE NEATLY TRAINED SO AS TO PERMIT PROPER OPERATION OF THE LEVER,

3. GAS SERVICE PIPES SHALL NOT BE USED AS A GROUNDING ELECTRODE.

AND SHALL BE COVERED WIRE.

Page 25: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

GAS SERVICE

GAS METER

RIGHT

ALTERNATE

POSITION

LEFT

ALTERNATE

POSITION

2. A FOUR FOOT CLEARANCE FROM FLOOR TO CEILING SHALL BE MAINTAINED IN FRONT OF THE ELECTRIC

3. IN ADDITION TO LIPA's REQUIREMENTS, INSTALLATIONS MAY BE SUBJECT TO THE APPROVAL

1. GAS SERVICE PIPES SHALL NOT BE USED AS A GROUNDING ELECTRODE.

OF THE LOCAL ELECTRICAL INSPECTION AGENCY AS WELL AS LOCAL MUNICIPALITIES.

METER INSTALLATION FOR SAFE ACCESS.

NOTES:

4. A MINIMUM SEPARATION OF 1'-0" MUST BE MAINTAINED BETWEEN GAS METER, REGULATOR, UNIONS

5. SEPARATION OF GAS SERVICE PIPE OR TUBING AND ALL OTHER UNDERGROUND FACILITIES OR

STRUCTURES SHALL BE MAINTAINED IN ACCORDANCE WITH APPROPRIATE CONSTRUCTION

6. NO ELECTRIC METER ENCLOSURE SHALL BE INSTALLED ABOVE THE GAS METER.

MINIMUM

1'-0"

7. NO PROTECTION BOLLARDS SHALL BE PLACED IN FRONT OF THE ELECTRIC METER.

ELECTRIC METER

ENCLOSURE

STANDARDS.

8. VENTING OF GAS REGULATOR SHALL BE PLACED A MINIMUM OF 1'-0" FROM THE NEAREST

PART OF THE ELECTRIC METER INSTALLATION.

CLEARANCES BETWEEN

ELECTRIC & GAS METERS

9. A 1' SEPARATION FROM GAS LOAD PIPE TO THE DISTRIBUTION PANEL IS REQUIRED.

10. FOR EXISTING METER ROOMS WITH GAS METERS, A MINIMUM OF 3' CLEARANCE IS REQUIRED BETWEEENTHE GAS SERVICE PIPING AND METERS AND ANY ELECTRICAL SERVICE EQUIPMENT.

DWG. BASED ON

LIPA CS 8015

2012 Edition Redbook

D24

COUPLINGS, JOINTS, AND VENTS AND ELECTRIC METERING EQUIPMENT.

MINIMUM

1'-0"

GAS METER

GAS SERVICE

GAS METER, REGULATOR, UNIONSAND VENTS NOT PERMITTED IN

SHADED AREA

Page 26: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

7. A FOUR FOOT CLEARANCE FROM FLOOR TO CEILING SHALL BE MAINTAINED IN FRONT OF THE METER INSTALLATION

OF METER ENCLOSURE SHALL NOT BE USED AS A RACEWAY EXCEPT FOR ROUTING NEUTRAL CABLE

8. IN ADDITION TO LIPA's REQUIREMENTS, INSTALLATIONS MAY BE SUBJECT TO THE APPROVAL

AS SHOWN. NEUTRAL CABLE SHALL BE NEATLY TRAINED SO AS TO PERMIT PROPER OPERATION OF LEVER.

6. LINE AND LOAD CONDUIT CONDUCTORS SHALL NOT CROSS WITHIN THE METER ENCLOSURE. RIGHT SIDE

THE NATIONAL ELECTRIC CODE.

4. GROUNDING SHALL BE IN ACCORDANCE WITH THE APPLICABLE SECTIONS OF ARTICLE 250 OF

2. ALL METER PAN ASSEMBLIES SHALL BE AS APPROVED BY LIPA. METER SOCKET ASSEMBLY

1. ALL ITEMS SHOWN SHALL BE FURNISHED AND INSTALLED BY THE CUSTOMER UNLESS OTHERWISE STATED.

OF THE LOCAL ELECTRICAL INSPECTION AGENCY AS WELL AS LOCAL MUNICIPALITIES.

SHALL BE EQUIPPED WITH A LEVER OPERATED, JAW RELEASE BYPASS MECHANISM.

FOR SAFE ACCESS.

NOTES:

9. ALL METER PANS AND SERVICE DISCONNECT SWITCHES SHALL BE PERMANENTLY STENCILED INTERNALLY AND

EXTERNALLY WITH THE BUILDING AND/OR SUITE NUMBER TO IDENTIFY THE PORTION OF THE PREMISES BEING SERVED.

A

A

B

B

C

C

DELTA WYE

PHASE B BLACK BLACK

PHASE C ORANGE RED

NEUTRAL WHITE OR GRAY

PHASE A BLUE BLUE

NEUTRAL LUG

A

A

B

B

C

C

10. LINE CONDUCTORS SHALL ENTER METER ENCLOSURE ON THE TOP OR BOTTOM LEFT.

11. ONLY FACTORY PREFABRICATED KNOCKOUTS ON METER ENCLOSURES SHALL BE USED.

OVERHEAD LINE SIDE TROUGH

POLYPHASE

METER

ENCLOSURE

JUMPER

NEUTRAL

PERMANENT

(TYP)

(TYP)

(TYP)

BYPASS

LEVER

LINE SIDE

CONDUIT & CABLE

CONDUIT

LINE SIDE TO CUSTOMER

MAIN DISCONNECT DISCONNECTMAIN

TO CUSTOMERTO CUSTOMER

MAIN DISCONNECT

ENCLOSURE

SINGLE PHASE

METER

2" MIN

2" MIN

N N

& CABLE

NEMA TYPE 3R MIN.

2" MIN.

METER

SOCKET

ASSEMBLY

(TPY.)

(TYP.)

12"

MIN.12"

MIN.

WALLWALL

ALTERNATE LOCATION OF LINE SIDE TROUGH

NEMA TYPE 3R MIN.

4" MIN

12. IDENTIFICATION OF PHASE CONDUCTORS SHALL BE WITH COLORED TAPE FOR A MINIMUM OF TWO INCHES.

PHASE CONDUCTOR IDENTIFICATION

MIN. 2" COLORED TAPE

TROUGH SUPPLY

SINGLE AND POLY-PHASE SELF CONTAINED METERS

200 AMPERE MULTI-METER SOCKET INSTALLATION

240/120 208Y/120

5. CONDUIT SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF THE NEC.

DWG. BASED ON

LIPA CS 8211

Section 11 - Drawings

D25

3. GAS SERVICE PIPES SHALL NOT BE USED AS A GROUNDING ELECTRODE.

AND SHALL BE COVERED WIRE.

Page 27: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

2. FOR SELF-CONTAINED METER ENCLOSURES, 2" RIGID GALVANIZED STEEL PIPE WITH APPROPRIATELY SIZED CHANNEL AND CONCRETE BASE MAY BE USED IN PLACE OF 4" PIPE DESIGN ; 4" X 4" TREATED LUMBER MAY

NOTES:

METER H FRAME CONSTRUCTION

OUTDOOR MOUNTING FOR TRANSFORMER AND/OR METER CABINET

1. CONCRETE FILLED PROTECTION BOLLARDS SHALL BE INSTALLED WHEN INSTALLATION IS IN

THE VICINITY OF VEHICULAR TRAFFIC. BOLLARDS SHALL BE PLACED A MINIMUM OF 4' FROM

THE CABINET AND SHALL BE PAINTED FLUORESCENT YELLOW. BOLLARDS SHALL BE CONSTRUCTED

FROM A MINIMUM OF 3.5" OUTSIDE DIAMETER SCHEDULE 40 GALVANIZED PIPE, SHALL BE SPACED 24" ON CENTERS AND SHALL BE A MINIMUM OF 3' HIGH.

4'- 0" MIN*

6'- 0" MAX

CONDUIT

SUPPORT

TOP OF METER

AS NEEDED

LOCKNUT

ENTRANCE CONDUCTORS

UNDERGROUND SERVICE

RGS CONDUIT

SHC. 80 PVC OR

12" DIA. CONC.

FILLED SONOTUBE

TRANSFORMER

METER CABINET

GALV. U-BOLT

FINISHED GRADE

6" MIN.

W/ CHAMFER

6" MIN.

(TYP.)

3/8" DIA.

(TYP.)

1-1/2" x 1-7/8"GALV. CHANNEL

4" SCH. 40 GALV.

(SEE NOTE #2)

GALV. CAP

STEEL PIPE

(TYP.)

(TYP.)

H - FRAME INSTALLATIONS ARE RESTRICTED/NOT PERMITTED BY SOME MUNICIPALITIES. CHECK LOCAL CODES PRIOR TO INSTALLATION.

(SEE NOTE 3)

3. RIGID METALLIC CONDUIT (RMC) AND RIGID NON-METALLIC CONDUIT (RNC) (SCHD. 40 OR 80 RESPECTIVELY, AS REQUIRED), ARE APPROVED FOR BELOW GRADE USE. ELECTRIC METALLIC TUBING (EMT) AND INTERMEDIATE METALLIC CONDUIT (IMC) ARE NOT APPROVED FOR BELOW GRADE INSTALLATION.

BE USED IN PLACE OF 4" X 6" POST DESIGN. USE OF PLYWOOD FOR EQUIPMENT INSTALLATION IS NOT PERMITTED.

4. FOR ADDITIONAL TRANS S CABINET REQUIREMENTS SEE DRAWINGS D28 & D29. FOR ADDITIONAL

(TYP.)

OR STRAP

AND/OR

(TYP.)

3'-6"

CONDUIT

STRAP

STEEL OR GALVANIZED LAG

FASTENED WITH STAINLESS

METER ENCLOSURE TO BE

ANGLE CUTS (TYP).

4" X 6" TREATED LUMBER

POSTS, AND 5/4" CROSS

METAL CAP OR

TRANSFORMER

METER CABINET

AND/OR

(TYP.)

LOCKNUT

(TYP.)

MIN.

OR THROUGH BOLTS

ALTERNATE DESIGN

FINISHED GRADE

STANDARD DESIGN

DWG. BASED ON

LIPA CS 8602

2012 Edition Redbook

D26

CT CABINET WITH REMOTE METER SOCKET REQUIREMENTS SEE DRAWINGS D30 & D31.

SHC. 80 PVC OR

RGS CONDUIT(SEE NOTE 3)

UNDERGROUND SERVICE

ENTRANCE CONDUCTORS

BRACES SEE NOTE #2

5/4 X 6" TREATED LUMBER

CROSS BRACE (TYP)

may be 3'-0"

meters, min. height

* Note: For self-contained

5. CHECK WITH LOCAL MUNICIPALITY FOR ANY SPECIAL REQUIREMENTS BEFORE INSTALLING METERING

EQUIPMENT ON H-FRAME.

Page 28: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

12"TRANS "S" TRANS "S"

MULTI - METER STACK

2. WHEN METERS ARE ON WALLS FACING EACH OTHER, THERE MUST BE 4' OF CLEAR SPACE FROM FLOOR TO CEILING BETWEEN METERS.

SWITCHGEAR

OR TRANS "S"

3. SWITCHGEAR DOORS MUST BE ABLE TO OPEN FULLY WITHOUT BEING OBSTRUCTED BY ANY

METER ENCLOSURES OR WALLS.

4' MIN

4' MIN

TRANS "S"

OR TRANS "S"

SWITCHGEAR

SELF-CONTAINED

METER ENCLOSURES

SELF-CONTAINED

METER ENCLOSURES

4. ROOMS CLASSIFIED AS CONFINED SPACE AND THOSE THAT REQUIRE LADDER ACCESS SHALL

SHALL NOT BE USED AS METER ROOMS.

5. PITS AND VAULTS BELOW GRADE ARE NOT ACCEPTABLE AS METER ROOMS.

6. MINIMUM METER ROOM CEILING HEIGHT SHALL BE 6'-6". ADEQUATE LIGHTING SHALL BE

7. GAS METERS ARE NOT PERMITTED IN ELECTRIC METER ROOMS.

ELECTRIC METER ROOM

EQUIPMENT CLEARANCES

2" 2"

12"TRANS "S"

2"

PROVIDED IN METER ROOM.

DWG. BASED ON

LIPA CS 8604

Section 11 - Drawings

D27

NOTES:

1. METER ROOM CONSTRUCTION SHALL COMPLY WILL ALL CODE REQUIREMENTS ( eg. NEC110.26) PERTAINING TO ACCESS, EGRESS, AND SAFETY.

8. FOR EXISTING METER ROOMS WITH GAS METERS, A MINIMUM OR 3' CLEARANCE IS REQUIRED BETWEEN THE GAS SERVICE PIPING AND METER AND ANY ELECTRICAL

SERVICE EQUIPMENT.

12"

12"

12"

12"

4' MIN

4' MIN

5'MIN

12"

5'MIN

12"

NOT TO SCALE

NOT TO SCALE

Page 29: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

TIN PLATED

COPPER BUS

STANDOFF

INSULATOR

NEUTRAL

BUS

LIPA APPROVED

WITH METER SOCKET

AND

4", 3.5" CONCENTRIC

KNOCKOUTS (4 TYP.)

TOP VIEW

TEST SWITCH

SILVER OR

HEX SCREW ( 3 typ.)

K.O TO ACCOMODATE

LIPA's LOCKING DEVICE

METER ENCLOSURE

RECESSED IN DOOR

CURRENT TRANSFORMERS

FURNISHED AND INSTALLED

BOTTOM VIEW

METER FURNISHED

AND INSTALLED

BY LIPA

GROUND STRAP

CONTINUOUS STAINLESS

STEEL PIANO HINGED DOOR.

LEFT HAND SWING ONLY

SIDE VIEW

(2 TYP.)

7"6"6"5"

6" 6"6" 6" 3"3"

HUB OPENING FOR

3", 3.5" OR 4" HUB

CL CL CL

GROUND LUG

NEMA TWO

HOLE LUG

PATTERN

RACEWAY

FOR

BOTTOM

ENTRY

OR EXIT

400 TO 800 AMPERE SERVICE

TRANS "S" CABINET INSTALLATION

FOR NOTES SEE DRAWING D29DWG. BASED ON

LIPA CS 8804

2012Edition Redbook

D28

TRANS-S CABINET

Page 30: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

NOTES:

1. BUS BARS SHALL BE SILVER OR TIN PLATED COPPER AND SHALL BE SIZED PER THE NEC.

2. ONLY THE RIGHT HAND SIDE OF THE CABINET SHALL ALLOW FOR LINE AND LOAD CABLES

TO ENTER AND EXIT THROUGH THE BOTTOM OF THE CABINET. THIS SPACE SHALL

ALLOW FOR THE CABLES TO MEET THE MINIMUM BENDING RADIUS TO THE NEAREST

PHASE OR NEUTRAL BUS. AS PER THE NEC.

3. CABINET DESIGN SHALL HAVE PROVISIONS FOR A SOLID DOOR TO ALLOW FOR THE

METER ENCLOSURE TO BE MOUNTED REMOTELY FROM THE CABINET.

4. MANUFACTURER SHALL FURNISH AND INSTALL 1/2-13 STUDS WITH SPLIT LOCK WASHERS AND HEX NUTS FOR C.T MOUNTING.

5. USE ONLY MANUFACTURED APPROVED LUG KITS.

7. THIS STANDARD SHALL NOT BE USED AS A DESIGN CRITERIA. DIMENSIONS SHOWN ARE

RECOMMENDED MINIMUMS ONLY. LARGER DIMENSIONS SHALL BE USED WHERE REQUIRED

BY CODE.

400 TO 800 AMPERE SERVICE

TRANS "S" CABINET INSTALLATION - NOTES & BONDING DIAGRAM

8. MAINTAIN CLEARANCES BETWEEN TRANS S CABINET AND TROUGHS OF 2" ON TOP AND 4"

ON BOTTOM OF CABINET.

Section 11 - Drawings

D29

NN

NON-METALLIC

CONDUIT/

LINE

BOND STRAP

NEUTRAL-TO-

ENCLOSURE

BONDING

BUSHING

BOND TO

ENCLOSURE

RACEWAY

RACEWAY

CONDUIT/METALLIC

TRANS S

CABINET

TRANS S

CABINET

BOND STRAP

NEUTRAL-TO-

ENCLOSURE

LINE

TRANS S CABINET BONDING DIAGRAM

NON - GFI MAIN DISCONNECT INSTALLATION

GFI MAIN DISCONNECT INSTALLATION

TRANS S CABINET BONDING DIAGRAM

LINE

RACEWAY

CONDUIT/

NON-METALLIC

N

BOND*

ENCLOSURE

TRANS S

CABINET

METALLIC

CONDUIT/RACEWAY

BONDING

BUSHING

N

CABINET

TRANS S

NO BOND

GFI

BETWEEN

NEUTRAL &

CABINET CABINET

NEUTRAL &

BETWEEN

NO BOND

BOND*

ENCLOSURE

TO GFI

BOND

POINT

GFI

LINE

TO BONDING

BUSHING

9. PERMANENTLY IDENTIFY LINE AND LOAD CONDUCTORS INSIDE CABINET.

(APPLIES TO 120/208V & 277/480V SERVICES)

6. METERING ENCLOSURES SHALL NOT BE ADDED. ONLY FACTORY SUPPLIED KNOCKOUTS

AND PERMITTED. FIELD MADE KNOCKOUTS OR ANY OTHER FIELD ALTERATIONS

WILL NOT BE ACCEPTED.

* USE MANUFACTURER'S BOND ATTACHMENT POINT

Page 31: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

CURRENT

AND TEST SWITCH

METER SOCKET

TRANSFORMER RATED

NEUTRAL BUS

NOTES:

SIDE

LOAD (LINE)

1-1/4" CONDUIT MIN.

(SEE NOTE #6 AND #7)WITH CONTROL CABLE

CT

ENCLOSURE

400-1200 C.T CABINET

MOUNTED TO WALL

COPPER BUS

WALL

OR APPROVED STRUCTURE.(Note4)

METER SOCKET ENCLOSURE AND TO THE CT. CABINET.

1. LIPA APPROVED CURRENT TRANSFORMER CABINET AND METER SOCKET SHALL NOT BE LOCATED IN ANY

AREA CLASSIFIED AS A HALLWAY, CONFINED SPACE, OR WHERE A LADDER ACCESS IS REQUIRED. (Ref Sect-8.2.3)

2. PITS AND VAULTS BELOW GRADE ARE NOT ACCEPTABLE AS METER ROOMS. METER

ENCLOSURES OR CURRENT TRANSFORMER CABINETS SHALL NOT BE LOCATED IN THESE

3. REFER TO NEC ARTICLE 250 FOR GROUNDING AND BONDING REQUIREMENT.

4. CENTERLINE OF C.T CABINET SHALL BE A MAXIMUM OF 5'-0" OR A MINIMUM OF 3'-6"

5. CONTROL CABLE SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR, SEE SECT. 8.9. FINAL TERMINATION IN THE METER AND TRANSFORMER CABINET SHALL BE DONE BY LIPA

6. MAXIMUM DISTANCE OF METER SOCKET FROM C.T CABINET SHALL BE DETERMINED BY LIPA

7. WHEN PVC CONDUIT IS USED A # 8 AWG 600 VOLT FACTORY INSULATED COPPER BOND WIRE SHALL BE INSTALLED BETWEEN THE METER SOCKET ENCLOSURE AND THE C.T CABINET

THE BOND WIRE SHALL BE GREEN OR MARKED AS SUCH AND SHALL BE BONDED TO THE

TYPES OF AREAS.

FROM FINISHED FLOOR.

TRANSFORMER RATED METER SOCKET

AND

CURRENT TRANSFORMER CABINET INSTALLATION

CT CT

LINE (LOAD)SIDE

TRANSFORMER (TYP)

DWG. BASED ON

LIPA CS 8606

2012 Edition Redbook

D30

6'-0" MAXIMUM

4'-0" MINIMUM

FINISHED GRADE

EXIT THROUGH MFG.

KNOCKOUT ONLY

LIPA APPROVED

LIPA APPROVED

CT/TRANS CABINET

LIPA APPROVED

8. REFER TO DRAWINGS D26, D27, D28, AND D29 FOR OTHER REQUIREMENTS.

9. LINE AND LOAD SIDES OF THE COMPARTMENT SHALL BE CLEARLY AND PERMANENTLY

MARKED.

Page 32: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

11. LINE AND LOAD SIDES OF THE COMPARTMENT SHALL BE CLEARLY AND PERMANENTLY

MOUNTING OF CURRENT TRANSFORMERS. BOLTS SHALL BE PERMANENTLY AFFIXED

10. GALVANIZED BOLTS, BELLEVILLE WASHERS AND NUTS SHALL BE PROVIDED FOR

9. BUS BAR SUPPORT SHALL BE CONSTRUCTED FROM INSULATING MATERIALS CONFORMING

SHALL BE LOCATED WITHIN AN ENCLOSURE EQUIPPED WITH TAMPER PROOF SCREWS.

8. ALL BUS BARS LOCATED ON THE LINE SIDE OF THE CURRENT TRANSFORMER COMPARTMENT

PROVISIONS FOR HOLDING THE DOORS IN THE OPEN POSITION.

7. DOOR SWING SHALL BE GREATER THAN 90 DEGREES AND SHALL BE EQUIPPED WITH

WHICH SHALL BE EQUIPPED WITH A THREE POINT LATCHING MECHANISM AND HAVE

6. THE FRONT OF THE CUBICLE SHALL BE FURNISHED WITH A DOUBLE SWING DOOR

5. THE NEUTRAL BUS SHALL BE DRILLED WITH A 1/4 - 20 TAP FOR CURRENT

3. BUS BARS WITHIN THE CURRENT TRANSFORMER CUBICLE SHALL BE COPPER AND SHALL

FROM THE REMAINDER OF THE SWITCHGEAR CUBICLE BY MEANS OF INSULATING BARRIERS

2. THE CURRENT TRANSFORMER COMPARTMENT SHALL BE COMPLETELY ISOLATED

SWITCHGEAR CUBICLE WHICH SHALL BE CONSTRUCTED IN CONFORMANCE WITH UL 891.

1. THE LIPA APPROVED CURRENT TRANSFORMER COMPARTMENT SHALL BE LOCATED WITHIN THE INCOMING

NOTES:

TO THE COPPER LANDING PADS.

PROVISIONS FOR LIPA PADLOCKING.

TRANSFORMER CONNECTION.

AS A MINIMUM BE TIN PLATED AT TERMINATION POINTS.

AS PER UL 891.

TO UL 746.

MARKED.

LC LC

7"MIN7"MIN

LC

7.5" MIN

SEE DETAIL A

25.0" MIN.

DETAIL A

6.875"

1.375"

.625"

HOLES(TYP.)9/16" DIA.

36.0" MIN.

15.0" MIN.

INSULATING

BARRIER

400 TO 1200 AMPERE SERVICE

CURRENT TRANSFORMER COMPARTMENT INSTALLATION

4. BUS BARS SHALL HAVE A MINIMUM THICKNESS OF 0.25 INCHES AND SHALL BE RATED AS PER NEC

FOR 1000 AMPERES PER SQUARE INCH.

DWG. BASED ON

LIPA CS 8801

WHITE OR GRAY

BLACK

120/208 277/480

PHASE CONDUCTOR IDENTIFICATION

MIN. 2" COLORED TAPE ON EACH END.

PHASE C

NEUTRAL

PHASE B

PHASE A

ORANGE

BLACK

BLUE

DELTA

RED

BLUE

WYE

YELLOW

BROWN

ORANGE

WYE120/240

Section 11 - Drawings

D31

7"MIN7"MIN 7"MIN

LC

Page 33: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

REPLACEMENT OF THE INSTRUMENT TRANSFORMERS.

2. THE BUS BAR INSTALLATION SHALL BE SO DESIGNED AS TO PERMIT A PRACTICAL AND EASY

8. THERE SHALL BE A MINIMUM OF FOUR FEET FROM FLOOR TO CEILING OF CLEAR WORKING SPACE

MINIMUM, THE OVERALL WIDTH AND HEIGHT OF THE TRANSFORMER COMPARTMENT.

SHALL BE ACCESSIBLE THROUGH A LOCKABLE DOUBLE HINGED DOOR WHICH SHALL SPAN, AS A

ENCLOSURE WITH AN INSULATING MATERIAL CONFORMING TO UL 746 AND UL 94. THE TRANSFORMERS

7. THE TRANSFORMER COMPARTMENT SHALL BE COMPLETELY ISOLATED FROM THE REST OF THE

6. THE TRANSFORMER SHELF AND SUPPORTING BRACKETS SHALL BE CONSTRUCTED FROM NON-FERROUS

5. ALL PHASE BUS AND THE NEUTRAL BUS SHALL BE DRILLED AND TAPPED FOR 1/4" - 20 SCREWS

LOCATED ON THE LINE SIDE WHEREBY THE SECONDARY CONNECTIONS WILL BE READILY ACCESSIBLE.

4. THE TRANSFORMERS SHALL BE INSTALLED SO THAT THE PRIMARY POLARITY MARKS (H1) IS

REQUIRED. THE MINIMUM DISTANCES BETWEEN CENTERLINES OF TRANSFORMERS SHALL BE 10 INCHES.

3. MOUNTING OF THE TRANSFORMERS MAY BE STAGGERED VERTICALLY WHERE CLOSER CENTERS ARE

CONDUCTOR SHALL BE COPPER BUS AND SHALL BE TIN PLATED AT TERMINATION POINTS AS A MINIMUM. BUS

1. CURRENT TRANSFORMER COMPARTMENT SHALL BE LIPA APPROVED, AND SHALL BE INSTALLED AS SHOWN.

IN FRONT OF THE TRANSFORMER CABINET.

ON THE LINE SIDE OF THE TRANSFORMERS.

NOTES:

MIN.

7"

ELEVATION

MIN.

13"MIN

13"

MIN.

7"

5.375"

SECTION A-A

11" MIN 7" MIN

8.5"

8.5"

9. WHEN NEUTRAL BUS IS RECESSED, PROVISIONS SHALL BE MADE TO EXTEND THE NEUTRAL CONNECTION TO THE FRONT OF THE CUBICLE TO ACCOMODATE THE CONNECTION OF THE

INSTRUMENT TRANSFORMERS.

NON-CONDUCTING, TYPE MATERIAL. MATERIAL SHALL CONFORM TO UL 746 AND UL 94.

A

A

MUST BE CENTERED IN THE WINDOW OF THE TRANSFORMER.

10. BUS BARS SHALL HAVE A MINIMUM THICKNESS OF 0.25 INCHES AND SHALL BE RATED PER

THE NEC FOR 1000 AMPERES PER SQUARE INCH. MAXIMUM BUS WIDTH SHALL BE 5 INCHES.

11. THE INSTRUMENT TRANSFORMER COMPARTMENT SHALL BE FURNISHED WITH A DOUBLE SWING

DOOR EQUIPPED WITH A THREE POINT LATCHING MECHANISM WITH PROVISIONS FOR LIPA

PADLOCKING.

CURRENT TRANSFORMER

PLAN VIEW

B

B

CT SECONDARY

TERMINAL

1600 AMPERE SERVICE AND ABOVE

CURRENT TRANSFORMER COMPARTMENT INSTALLATION

WHITE OR GRAY

BLACK

120/208 277/480

PHASE CONDUCTOR IDENTIFICATION

MIN. 2" COLORED TAPE ON EACH END.

PHASE C

NEUTRAL

PHASE B

PHASE A

ORANGE

BLACK

BLUE

DELTA

RED

BLUE

WYE

YELLOW

BROWN

ORANGE

WYE

12. LINE AND LOAD SIDES OF THE COMPARTMENT MUST BE CLEARLY AND

CT SHELF MIN.

1" THK. NON-CONDUCTIVE

MATERIAL

DWG. BASED ON

LIPA CS 8802PERMANENTLY MARKED.

2012 Edition Redbook

D32

NEUTRAL

BUS

11" MIN. BUS EDGE TO ACCESS DOOR

42" MIN

7" MIN. BUSEDGE

TO REAR INSULATING

BARRIER

METAL ENCL.

SIDEWALL

LC LC LC

Page 34: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

BOND WIRE SHALL BE A MINIMUM OF #8 AWG GREEN INSULATED COPPER.

BUSHING. BUSHINGS SHALL BE BONDED TO THEIR RESPECTIVE ENCLOSURES.

3. WHERE GALVANIZED OR ELECTRICAL METAL TUBING IS USED WITH BONDING

ELECTRICAL CODE.

2. GROUNDING SHALL BE IN ACCORDANCE WITH ARTICLE 250 OF THE NATIONAL

IS APPLICABLE WHERE TEN FEET OF CONTINUOUS METAL WATER PIPE IN

SIX FEET FROM THE FIRST. THE REQUIREMENT FOR A SECOND GROUND ROD

GROUND ROD IS REQUIRED TO BE INSTALLED AT A MINIMUM DISTANCE OF

1. WHERE WATER PIPING SYSTEM IS CONSTRUCTED FROM PLASTIC, A SECOND

INSULATED NEUTRAL CONDUCTOR

GROUND CONDUCTOR

CUSTOMER'S MAIN DISCONNECT

NEUTRAL BLOCK

ELECTRIC METER ENCLOSURE

EARTH IS NOT AVAILABLE.

NOTES:

(SEE NOTE #1)

WATER PIPING SYSTEM

UNDERGROUND METAL

PER NEC.

WATER

METER

FINISHED

GRADE

TYPICAL GROUNDING REQUIREMENTS

SINGLE METER / MAIN INSTALLATION

1/2" X 8' CU WELD OR5/8" X 8' CU PLATED GROUND ROD

DWG. BASED ON

LIPA CS 8603

Section 11 - Drawings

D33

Page 35: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

WATER

METER

GROUND BUS

1/2" X 8' COPPER WELD OR

WIRE SIZED IN ACCORDANCE

W/ THE NEC REQUIREMENTS

WIRE SIZED FOR SERVICE ENTRANCE

CONDUCTOR SIZE IN ACCORDANCE W/

WITHIN 5' OF BUILDING

ENTRANCE AND 10' OF

CONTACT WITH EARTH

TROUGH

MAIN

OR

PANEL

TYPICAL GROUNDING DETAILS

MULTI METER / MULTI MAIN INSTALLATION

PANEL

MAIN

OR

GROUND BUS

PANEL

MAIN

OR

GROUND BUS

METER

SOCKET SOCKET

METER

SOCKET

METER

THE NEC REQUIREMENTS

1. WHERE THE WATER PIPING SYSTEM IS CONSTRUCTED FROM PLASTIC, A SECOND GROUND ROD

IS REQUIRED TO BE INSTALLED AT A MINIMUM DISTANCE OF SIX FEET FROM THE FIRST. THE

REQUIREMENT FOR A SECOND GROUND ROD IS APPLICABLE WHERE TEN FEET OF CONTINUOUS

METAL WATER PIPE IN EARTH IS NOT AVAILABLE.

2. GROUNDING SHALL BE IN ACCORDANCE WITH ARTICLE 250 OF THE NATIONAL ELECTRIC CODE.

3. WHERE GALV. OR ELECTRICAL METAL TUBING IS USED WITH BONDING BUSHING. BUSHINGS SHALL

BE BONDED TO THEIR RESPECTIVE ENCLOSURES. BOND WIRE SHALL BE A MINIMUM OF #8 AWG GREEN INSULATED COPPER.

NOTES:

UNDERGROUND METAL WATER

PIPING SYSTEM PER NEC

(SEE NOTE 1) 5/8" X 8' COPPER PLATED

2012 Edition Redbook

D34

Apt.1

Apt.1

Apt.2

Apt.2

Apt.3

Apt.3

GROUND ROD

Page 36: 11.0 GENERAL DRAWINGS AND  · PDF file11.0 general drawings and standards ... pole mounted service 100 ... open suply conductors over 750v to 22kv (primary bare or tree wire)

OPTIONAL STANDBY SYSTEMS

THE FOLLOWING 2 ONE-LINE SCHEMATICS OUTLINE THE CONNECTIONS

LIPA WILL ALLOW FOR THE INTERCONNECTION OF OPTIONAL STANDBY

SYSTEM EQUIPMENT. THE INTENT OF THE INTERCONNECTION

SCHEMES IS TO PREVENT BOTH BACKFEED INTO THE LIPA

ELECTRIC DISTRIBUTION SYSTEM, AND UNINTENTIONAL PARALLELOPERATION WITH AN ENERGIZED LIPA SYSTEM. IMPROPER

PARALLEL OPERATION CAN RESULT IN SERIOUS DAMAGE TO THE

GENERATOR, THE LIPA DISTRIBUTION SYSTEM, OR BOTH, AND BEA SAFETY HAZARD TO PERSONNEL.

TO ENTIRE

LOAD

GGENERATOR

GENERATOR

PROTECTIVE

CIRCUIT BREAKER

MAIN

DISCONNECT

LIPA

METERED

FIG. 1: STANDBY GENERATOR FOR ENTIRE LOAD.

DOUBLE THROW SWITCH

DOUBLE THROW SWITCH

CIRCUIT BREAKER

PROTECTIVE

GENERATOR

GENERATOR

G

STANDBY LOAD

LOADS NOT

BACKED UP

BY GENERATOR

FIG. 2: STANDBY GENERATOR FOR PARTIAL LOADS

SERVICE

METERED

SERVICE

LIPA

MAIN

DISCONNECT

Section 11 - Drawings

D35

NOTE: CUSTOMER'S METERING

EQUIPMENT MUST BE

PLACARDED THAT A GENERATOR IS PRESENT

NOTE: CUSTOMER'S METERING

EQUIPMENT MUST BE

PLACARDED THAT A GENERATOR IS PRESENT