    RECOMMENDED RESIDENTIAL CONSTRUCTION FOR COASTAL AREAS D-

    D.FoundationAnalysis andDesignExamplesChapter 3 described the types o loads considered in this manual. This

    appendix demonstrates how these loads are calculated using a samplebuilding and oundation. The reactions rom the loads imposed on the

    example building are calculated, the loads on the oundation elements

    are determined, and the total loads are summed and applied to the

    oundation.

    There is a noteworthy dierence between the approach taken or designing the oundationsincluded in this manual and the analyses that a designer may undertake or an individualbuilding. The analyses used or the designs in this manual were based on the worst case load-ing scenario or a range o building sizes and weights. This approach was used to provide

  • 7/29/2019 11 Fema p550 Apndxd

    2/32

    D- Building on strong and safe foundations

    D foundation analysis and design examples

    designers and contractors with some exibility in selecting the home ootprint and character-istics or which these pre-engineered oundations would apply. This also simplifes applicationo the pre-engineered oundations, reducing the number o pre-engineered oundations, andresults in conservative designs.

    For example, the designs presented were developed to resist uplit and overturning or a rela-tively light structure with a at roo (worst case uplit and overturning) while gravity loads werebased on a relatively heavy structure to simulate worst case gravity loads. Sliding orces were de-termined or a relatively deep home with a steep roo to simulate the largest lateral loads. Therange o building weights and dimensions applicable to the designs are listed in Appendix C.

    Since the designs are inherently conservative or some building dimensions and weights, a localdesign proessional may be consulted to determine i reanalyzing to achieve a more efcient de-sign is warranted. I a reanalysis is determined to be cost-eective, the sample calculations willaid the designer in completing that analysis.

    D.1 SampleCalculations

    The sample calculations have been included to show one method o determining and calculat-ing individual loads, and calculating load combinations.

    TypeofBuilding

    The sample calculation is based on a two-story home with a 8-oot by 4-oot ootprint and amean roo height o 6 eet above grade. The home is located on Little Bay in Harrison County,Mississippi, approximately .5 miles southwest o DeLisle (see Figure D-). The site is locatedon the Harrison County Flood Recovery Map in an area with an Advisory Base Flood Eleva-tion (ABFE) o 8 eet, located between the .5-oot wave contour and the 3-oot wave contour(Coastal A zone). The local grade elevation is 5 eet North American Vertical Datum (NAVD).The calculations assume short- and long-term erosion will occur and the ground elevation willdrop oot during the lie o the structure. This places the home in a Coastal A zone with theood elevation approximately 4 eet above the eroded exterior grade. Based on ASCE 7-05, the3-second gust design wind speed at the site is 8 miles per hour (mph) Exposure Category C.To reduce possible damage and or greater resistance to high winds, the home is being designedor a 40-mph design wind speed.

    The home has a gabled roo with a 3: roo pitch. The home is wood-ramed, contains no brickor stone veneer, and has an asphalt shingled roo. It has a center wood beam supporting the frstoor and a center load bearing wall supporting the second oor. Clear span trusses rame theroo and are designed to provide a -oot overhang. No vertical load path continuity is assumedto exist in the center supports, but vertical and lateral load path continuity is assumed to existelsewhere in the structure.

  • 7/29/2019 11 Fema p550 Apndxd

    3/32

    D-3RECOMMENDED RESIDENTIAL CONSTRUCTION FOR COASTAL AREAS

    foundation analysis and design examples D

    The proposed oundation or the home is a system o steel pipe piles, a reinorced concretegrade beam, and concrete columns extending rom the grade beam to the elevated structure.

    Methodology

    . Determine the loads based on the buildings parameters (Section D..)

    . Calculate wind and ood loads using ASCE 7-05 (Section D..)

    3. Consider the structure as a rigid body, and use orce and moment equilibrium equations todetermine reactions at the perimeter oundation elements (Section D.)

    FigureD-1.

    StarindicatesthelocationofthesamplecalculationhomeonLittleBayinHarrisonCounty,Mississippi,

    approximately1.5milessouthwestofDeLisle.Insetontheleft(fromthemap)isenlarged.

  • 7/29/2019 11 Fema p550 Apndxd

    4/32

    D-4 Building on strong and safe foundations

    D foundation analysis and design examples

    D.1.1 DeterminingIndividualLoadsonaStructure

    Building Dimensions and Weights(pulled rom the text o the example problem)

    B = 4 Building width (t)

    L = 8 Building depth (t)

    F = 0 First oor height (t)

    F = 0 Second oor height (t)

    r = 3 3: roo pitch

    Wovhg = Width o roo overhang (t)

    Dead Loads

    WrDL = Roo dead load including upper level ceiling fnish (inpounds per square oot [ps])

    WstDL = 8 First oor dead load (ps)

    WndDL = 0 Second oor dead load, including frst oor ceiling fnish (ps)

    WwlDL = 9 Exterior wall weight (ps o wall area)

    Live Loads

    WstLL = 40 First oor live load (ps)

    WndLL = 30 Second oor live load (ps)

    WrLL = 0 Roo live load (ps)

    Wind Loads

    Building Geometry

    h/L =

    L/B = 0.7

  • 7/29/2019 11 Fema p550 Apndxd

    5/32

    D-5RECOMMENDED RESIDENTIAL CONSTRUCTION FOR COASTAL AREAS

    foundation analysis and design examples D

    Site Parameters (ASCE 7-05, Chapter 6)

    Kzt = Topographic actor (no isolated hills, ridges, or escarpments)

    Kd = 0.85 Directionality actor (or use with ASCE 7-05, Chapter ,

    Load Combinations)

    Kh = 0.94 For simplicity, Velocity Pressure Coefcient used at the 6 ootmean roo height was applied at all building suraces.See ASCE 7-05, Table 6-3, Cases and .

    I = Importance actor (residential occupancy)

    V = 40 3-second gust design wind speed (mph)

    G = 0.85 Gust eect actor (rigid structure, ASCE 7-05, Section 6.5.8.)

    External Pressure Coefcients (Cp) (ASCE 7-05, Figure 6-6)

    Cpwwr = -.0 Windward roo (side acing the wind)

    Cplwr = -0.6 Leeward roo

    Cpwwl = 0.8 Windward wall

    Cplwwl = -0.5 Leeward wall (side away, or sheltered, rom the wind)

    Cpeave

    = -0.8 Windward eave

    Positive coefcients indicate pressures acting on the surace. Negative coefcients indicate pres-sures acting away rom the surace.

    Velocity Pressure (qh) (ASCE 7-05, Section 6.5.10)

    Velocity pressure at mean roo height:

    qh = 0.0056 KhKztKd V I

    = 0.0056 (0.94)()(0.85)(40)()

    qh = 40 ps

    Wind Pressures (P)

    Determine external pressure coefcients or the various building suraces. Internal pressures,which act on all internal suraces, do not contribute to the oundation reactions. For sign conven-tion, positive pressures act inward on a building surace and negative pressures act outward.

  • 7/29/2019 11 Fema p550 Apndxd

    6/32

    D-6 Building on strong and safe foundations

    D foundation analysis and design examples

    PwwrV = qh GCpwwr Windward roo

    = (40)(0.85)(-)

    PwwrV = -34 ps

    Likewise

    PlwrV = qh GCplwr Leeward roo

    PlwrV = -0 ps

    Pwwwl = qh GCpwwwl Windward wall

    Pwwwl = 7 ps

    Plwwl = qh GCplwwl Leeward wall

    Plwwl = -7 ps

    Pwweave = qh GCpeave Windward roo overhang

    Pwweave = -7 ps - eave

    = -34 ps - upper surace

    = -6 ps - total

    Wind Forces (F) (on a 1-oot wide section o the home)

    FwwrV = PwwrV L/ Windward roo vertical orce

    = (-34 ps)(4 s/l)

    = -476 lb/l

    FlwrV = PlwrVL/ Leeward roo vertical orce

    = (-0 ps)(4 s/l)

    = -80 lb/l

    FwwrH

    = PwwrH

    L/ (r/) Windward roo horizontal orce

    = (-34 ps)(4 s/l)(3/)

    = -9 lb/l

    FlwrH = PlwrH L/ (r/) Leeward roo horizontal orce

    = (-0 ps)(4 s/l)(3/)

    = -70 lb/l

  • 7/29/2019 11 Fema p550 Apndxd

    7/32

    D-7RECOMMENDED RESIDENTIAL CONSTRUCTION FOR COASTAL AREAS

    foundation analysis and design examples D

    Fwwwlst = Pwwwl (F) Windward wall on frst oor

    = (7 ps)(0 s/l)

    = 70 lb/l

    Fwwwlnd = Pwwwl (F) Windward wall on second oor

    = (7 ps)(0 s/l)

    = 70 lb/l

    Flwwlst = Plwwl (F) Leeward wall on frst oor

    = (-7 ps)(0 s/l)

    = -70 lb/l

    Flwwlnd = Plwwl (F) Leeward wall on second oor

    = (-7 ps)(0 s/l)

    = -70 lb/l

    Fwweave = Pwweavewowhg Eave vertical orce (lb)

    = -(6 ps)( s/l) horizontal projected areas is negligible so horizontal orce is neglected

    = - lb/l

    D.1.2 CalculatingReactionsfromWind,andLiveandDeadLoads

    Sum overturning moments (Mwind) about the leeward corner o the home. For sign convention,consider overturning moments as negative. Since vertical load path continuity is assumed not tobe present above the center support, the center support provides no resistance to overturning(see Figure D-).

    Mwind = (-476 lb/l)( t) + (-80 lb/l)(7 t) + (9 lb/l)(.75 t) +(-70 lb/l)(.75 t) + (-70 lb/l)(5 t) + (-70 lb/l)(5 t) +(-70 lb/l)(5 t) + (-70 lb/l)(5 t) + (- lb/l)(9 t)

    = -3,88 t-lb/l

    Solving or the windward reaction, thereore:

    Wwind = Mwind L

    Wwind = -3,8 t (lb/l 8 t)

    Wwind = -830 lb/l

  • 7/29/2019 11 Fema p550 Apndxd

    8/32

    D-8 Building on strong and safe foundations

    D foundation analysis and design examples

    The leeward reaction is calculated by either summing vertical loads or by summing momentsabout the windward oundation wall. Leeward reaction equals -48 lb/l.

    Lateral Wind Loads

    Sum horizontal loads (Flat) on the elevated structure. (Forces to the let are positive. See Fig-ure D-.)

    Flat = (-9 lb/l) + (70 lb/l) + (70 lb/l) + (70 lb/l) + (70 lb/l) + (70 lb/l)

    = 83 lb/l

    Dead Loads

    In this example, dead load reactions (Wdead) are determined by summing loads over the tribu-tary areas. Since the roo is ramed with clear-span trusses and there is a center support in thehome, each exterior oundation wall supports o the roo load, all o the exterior wall load,

    FigureD-2.Pathsfor

    wind,live,anddead

    loads.

  • 7/29/2019 11 Fema p550 Apndxd

    9/32

    D-9RECOMMENDED RESIDENTIAL CONSTRUCTION FOR COASTAL AREAS

    foundation analysis and design examples D

    and o the frst and second oor loads. This approach to analysis is somewhat conservativesince it does not consider the entire dead load o the structure to resist overturning. Standardengineering practice oten considers the entire weight o the structure (i.e., not just the portionsupported by the perimeter oundation walls) available to resist overturning. The closed oun-dations in this guidance were developed considering only the tributary dead load to resist uplit.

    The open oundations were developed considering all dead loads to resist uplit.

    Wdead = L/ (wrDL)+ L/4 (wstDL + wndDL) + (F + F) wwlDL

    = [4 s/l ( ps)] + [7 s/l (8 ps + 0 ps)] + [(0 s/l + 0 s/l) 9 ps]

    = 474 lb/l

    Live Loads

    Floor

    Live loads (Wlive) are calculated in a similar ashion

    Wlive = L/4(WstLL + WndLL)

    = (7 sq t/l)(40 + 30) ps

    = 490 lb/l

    Roof

    Wliveroo = L/(WrLL)

    = (4 sq t/l)(0 ps)

    = 80 lb/l

    D.2 DeterminingLoadCombinations

    Combine loads as specifed in Chapter o ASCE 7-05. For this example, an allowable stress de-sign approach was used. A strength-based design is equally valid.

    Other loads (such as snow, ice, and seismic) are listed in the ASCE 7-05 Load Combinations,but were considered to be too rare in the Gul Coast o the United States to be consideredin the design. ASCE 7-05 also lists rain loads that are appropriate or the Gul Coast region.Since a minimum roo slope ratio o 3: was assumed or the homes, rain loading was notconsidered. Table D- lists oundation wall reactions or each load case. Critical reactions thatcontain the oundation design are highlighted.

  • 7/29/2019 11 Fema p550 Apndxd

    10/32

    D-0 Building on strong and safe foundations

    D foundation analysis and design examples

    TableD-1.DesignReactionsonBaseofElevatedHome

    ASCE7-05LoadCombination Vertical(lb/lf) Horizontal (lb/lf)

    #1 D 474 --

    #2 D + L 964 --#3 D + L 754 --

    #4 D + 0.75(L) + 0.75(L) {1,052} --

    #5 D + W -356 831

    #6 D + 0.75(W) + 0.75(L) + 0.75(L ) 1,016 623

    #7 0.6D + W {-546} {831}

    #8 0.6D 284 --

    Where

    D = dead load

    L = live load

    Lr = roo live load

    W = wind load

    Note: Critical loads are in bold with brackets ({ }).

    Flood Load Eects on a Foundation

    In this example, since the oundation selected is a system o steel pipe piles, the equations used

    to calculate ood loads are based on open oundations. Some o the equations used to calculateood loads will be dierent i the building has a closed oundation system.

    Many ood calculations depend on the stillwater ooding depth (ds). While not listed on FIRMs,ds can be calculated rom the BFE by knowing that the breaking wave height (Hb) equals 78percent o the stillwater depth and that 70 percent o the breaking wave exists above the stillwa-ter depth (see Figure -3 o FEMA 55). Stated algebraically:

    BFE = GS + ds + 0.70 Hb

    = GS + ds + 0.70(0.78 ds)

    = GS + .55 ds

    GS = 5 t NAVD (initial elevation) t (short- and long- term erosion)

    = 4 t NAVD

    ds = (BFE GS) .55

    = (8 eet NAVD 4 eet NAVD) .55

  • 7/29/2019 11 Fema p550 Apndxd

    11/32

    D-RECOMMENDED RESIDENTIAL CONSTRUCTION FOR COASTAL AREAS

    foundation analysis and design examples D

    = 4 t .55

    = .6 t

    Hydrostatic Loads

    Hydrostatic loads act laterally and vertically on all submerged oundation elements. On openoundations, lateral hydrostatic loads cancel and do not need to be considered but vertical hy-drodynamic orces (buoyancy) remain. The buoyancy orces reduce the eective weight o theoundation by the weight o the displaced water and must be considered in uplit calculations.For example, normal weight concrete which typically weighs 50 lb/t3 only weighs 86 lb/t3when submerged in saltwater (slightly more in reshwater).

    In this example, calculations are based on an 8-inch square normal weight concrete columnthat extends 4 eet above eroded ground elevation. The column weighs ,350 pounds dry ((.5t)(.5 t)(4 t)(50 lb/t3). Under ood conditions, the column displaces 9 t3 o saltwater that,

    at 64 lb/t3

    , weighs 576 pounds so the column weighs only 774 pounds when submerged.

    Hydrodynamic Loads

    Flood Velocity

    Since a Coastal A zone is close to the ood source, ood velocity is calculated using the ASCE7-05 Equation C5-:

    V = (g ds)/ Upper bound ood velocity

    Where

    g = Gravitational acceleration (3. t/sec)

    ds = Design stillwater depth (t)

    Hence

    V = [(3.)(.6)]/

    = 9.5 eet per second (ps)

    Hydrodynamic Forces

    A modifed version o ASCE 7-05 Equation C5-4 can be used to calculate the hydrodynamicorce on a oundation element as

    Fdyn = CdV A

    Where

    Fdyn = Hydrodynamic orce (lb) acting on the submerged element

  • 7/29/2019 11 Fema p550 Apndxd

    12/32

    D- Building on strong and safe foundations

    D foundation analysis and design examples

    Cd = .0 Drag coefcient (equals .0 or a square or rectangular column)

    = Mass density o salt water (slugs/cubic oot)

    A = .5 ds Surace area o obstruction normal to ow (t)

    For open oundation, A is the area o pier or column perpendicular to food direction (calculated or an18-inch square column).

    Hence

    Fdyn = () ()()(9.5)(.5)(.6)

    = 653 lb/column

    The orce is assumed to act at a point ds/ above the eroded ground surace.

    The ormula can also be used or loads on oundation walls. The drag coefcient, however, is

    dierent. For oundation walls, Cd is a unction o the ratio between oundation width and oun-dation height or the ratio between oundation width and stillwater depth. For a building withdimensions equal to those used in this example, Cd or a closed oundation would equal .5 orull submersion (4 eet by 4 eet) or .3 i submersed only up to the .6-oot stillwater depth.

    Dynamic loads or submersion to the stillwater depth or a closed oundation are as ollows:

    Fdyn = Cd V A

    Fdyn = () (.3)()(9.5)()(.6)

    = 83 lb/l o wall

    Floodborne Debris Impacts

    In this example, the loads imposed by oodborne debris were approximated using ormula -9 contained in FEMA 55.

    The Commentaryo ASCE 7-05 contains a more sophisticated approach or determining debrisimpact loading, which takes into account the natural period o the impacted structure, local de-bris sources, upstream obstructions that can reduce the velocity o the oodborne debris, etc.

    It is suggested that designers o coastal oundations review the later standards to determine ithey are more appropriate to use in their particular design.

    The FEMA 55 Formula .9 estimates debris impact loads as ollows:

    Fi = wV (g t)

  • 7/29/2019 11 Fema p550 Apndxd

    13/32

    D-3RECOMMENDED RESIDENTIAL CONSTRUCTION FOR COASTAL AREAS

    foundation analysis and design examples D

    Where

    Fi = impact orce (lb)

    w = weight o the oodborne debris (lb)

    V = velocity o oodborne debris (t/sec)g = gravitational constant = 3. t/sec

    t = impact duration (sec)

    Floodborne debris velocity is assumed to equal the velocity o the moving oodwaters and act-ing at the stillwater level. For debris weight, FEMA 55 recommends using ,000 pounds whenno other data are available. The impact duration depends on the relative stiness o the ounda-tion and FEMA 55 contains suggested impact durations or wood oundations, steel oundations,and reinorced concrete oundations. For this example, the suggested impact duration o 0.second was used or the reinorced concrete column oundation.

    Fi = wV gt

    Fi = [,000 lb (9.5 t/sec)] [(3. t/sec)(0. sec)]

    Fi = ,84 lb

    Breaking Wave Loads

    When water is exposed to even moderate winds, waves can build quickly. When adequate windspeed and upstream etch exist, oodwaters can sustain wave heights equal to 78 percent otheir stillwater depths. Depending on wind speeds, maximum wave height or the stillwater

    depth at the site can be reached with as little as to miles o upwind etch.

    Breaking wave orces were calculated in this example using ASCE 7-05 ormulae or wave orceson continuous oundation walls (ASCE 7-05 Equations 5-5 and 5-6) and on vertical piles andcolumns (ASCE 7-05 Equation 5-4).

    The equation or vertical piles and columns rom ASCE 7-05 is

    Fbrkp = Cdb DHb

    Where

    Fbrkp = Breaking wave orce (acting at the stillwater level) (lb)

    Cdb = Drag coefcient (equals .5 or square or rectangular piles/columns)

    = Specifc weight o water (64 lb/t3 or saltwater)

    D = Pile or column diameter in t or circular sections, or or a square pile orcolumn, .4 times the width o the pile or column (t). For this example,since the column is 8 inches square, D = (.4)(.5 t) = . t.

  • 7/29/2019 11 Fema p550 Apndxd

    14/32

    D-4 Building on strong and safe foundations

    D foundation analysis and design examples

    Hb = Breaking wave height (0.78 ds)(t) = (0.78)(.6) = .03 t

    Note: The critical angle o a breaking wave occurs when the wave travels in a direction perpen-dicular to the surace o the column. Waves traveling at an oblique angle () to the surace othe waves are attenuated by the actor sin.

    Fbrkp = Cdb DHb

    = (.5)(64 lb/t3)(. t)(.03 t)

    = 63 lb

    For closed oundations, use equations in Section 5.4.4. o ASCE 7-05 to calculate F brkp. FEMA55 contains the ollowing two equations or calculating loads on closed oundations:

    Fbrkw = . Cp ds + .4 ds

    Case

    and

    Fbrkw = . Cp ds + .9 ds

    Case

    Where and ds are the specifc weights o water and design stillwater depths as beore. Cpis the dynamic pressure coefcient that depends on the type o structure. Cp equals .8 orresidential structures, 3. or critical and essential acilities, and .6 or accessory structureswhere there is a low probability o injury to human lie. The term Fbrkw is a distributed lineload and equals the breaking wave load per oot o wall length whereFbrkwis assumed to actat the stillwater elevation.

    Case o Formula .6 represents a condition where oodwaters are not present on the interioro the wall being designed or analyzed. Case is appropriate or oundation walls that lack oodvents (see Figure D-3). The less stringent Case is appropriate or walls where NFIP requiredood vents are in place to equalize hydrostatic loads and reduce orces (see Figure D-4).

    In non-Coastal A Zones, the maximum wave height is .5 eet. This corresponds to a stillwa-ter depth (ds) o approximately eet (i.e., .5 oot/0.78 or a depth limited wave). For closedoundations in coastal areas with ood vents, a .5-oot breaking wave creates ,80 lbs per lin-ear oot o wall and ,400 lbs per linear oot o wall on oundations that lack ood vents.

    Wind Load on Columns

    Wind loads have been calculated per ASCE 7-05, Section 6.5.3 (Wind Loads on Open Buildingsand with Monoslope, Pitched, or Troughed Roos). The velocity pressure (qh) calculated previ-ously was used, although this is a conservative fgure based on the 6-oot mean roo height. Theorce coefcient (C) was determined rom ASCE 7-05, Figure 6- (chimneys, tanks, rootopequipment, and similar structures); ASCE 7-05, Figure 6-0 (walls and solid signs) could havebeen used as well.

  • 7/29/2019 11 Fema p550 Apndxd

    15/32

    D-5RECOMMENDED RESIDENTIAL CONSTRUCTION FOR COASTAL AREAS

    foundation analysis and design examples D

    From ASCE 7-05 Equation 6-8:

    Fwind = qz G CA

    = 40 ps (0.85)(.33*)(.5 t)(4 t)

    = 70 lb*Interpolated C

    Wind loads on the oundation elements are not considered in combination with ood loadssince the elements are submerged during those events.

    Flood Load Combinations

    Section .6. o FEMA 55 provides guidance on combining ood loads. In Coastal A zones,FEMA 55 suggests two scenarios or combining ood loads. Case involves analyzing breakingwave loads on all vertical supports and impact loading on one corner or critical support and

    Case involves analyzing breaking wave loads applied to the ront row o supports (row closestto the ood source), and hydrodynamic loads applied to all other supports and impact loads onone corner or critical support.

    Depending on the relative values or dynamic and breaking waves, Case oten controls or de-signing individual piers or columns within a home. Case typically controls or the design o theassemblage o piers or columns working together to support a home. Because o the magnitudeo the load, it is not always practical to design or impact loads. As an alternative, structural re-dundancy can be provided in the elevated home to allow one pier or column to be damaged byoodborne debris impact without causing collapse or excessive deection.

    FigureD-3.Case1.Normallyincident

    breakingwave

    pressuresagainsta

    verticalwall(space

    behindverticalwallis

    dry).

    Source: ASce 7-05

  • 7/29/2019 11 Fema p550 Apndxd

    16/32

    D-6 Building on strong and safe foundations

    D foundation analysis and design examples

    For the sample calculations, Case was used (see Figure D-5) with a breaking wave load o 63pounds applied to a non-critical column. The loads were then determined and summarized.Since the calculations must combine distributed loads on the elevated structure and discreteloads on the columns themselves, a column spacing o 7 eet is assumed in the calculations.For lateral loads on the structure, calculations are based on three rows o columns sharinglateral loads (Table D-).

    FigureD-4.Case2.

    Normallyincident

    breakingwave

    pressuresagainsta

    verticalwall(stillwater

    levelequalonboth

    sidesofwall).

    Source: ASce 7-05

    FigureD-5.

    Floodloads.

  • 7/29/2019 11 Fema p550 Apndxd

    17/32

    D-7RECOMMENDED RESIDENTIAL CONSTRUCTION FOR COASTAL AREAS

    foundation analysis and design examples D

    TableD-2.LoadsonColumnsSpaced7FeetOnCenter(forthreerowsofcolumns)

    ASCE7-05LoadCombination Vertical(lb) Horizontal(lb)

    #1 D + F 1,350 + [7(474)] = 4,668 --

    #2 D + F + L 1,350 + [7(964)] = 8,098 --

    #3 D + F + L 1,350 + [7(754)] = 6,628 --

    #4 D + F + 0.75(L) + 0.75(L) 774 + 7(1,052) = {8,138} --

    #5 D + F + W + 1.5(Fa) 774 + [7(474 - 48)] = 3,756[(1/3)7(831)] + [1.5(623)]

    = {2,874}

    #6 D + F + 0.75(W) + 0.75(L) +

    0.75(L) + 1.5(Fa)

    774 + 7[474 + 0.75(-48+490+280)]

    = 7,883

    [(1/3)7(0.75)(831)] + [1.5(623)]

    = 2,388

    #7 0.6D + W + 1.5(Fa)0.6[774 + 7(474)] + [7(-830)]

    = {-3,555}[(1/3)7(831)] + [1.5(623)]

    = {2,874}

    #8 0.6D [0.6(1,350)] + [7(306)] = 3,000 --

    Where

    D = dead load

    F = load due to uids with well-defned pressures and maximum heights(see Section D. or additional inormation)

    Fa = ood load

    L = live load

    Lr = roo live load

    W = wind load

    Note: Critical loads are in bold with brackets ({ }).

    Results

    Each perimeter column needs to support the ollowing loads:

    Vertical Load = 8,38 lb

    Uplit = 3,555 lb

    Lateral Load = ,874 lb

    With the critical loads determined, the oundation elements and their connections to the homecan be designed.

    The ollowing two examples are to demonstrate designs using inormation provided in thismanual. The frst example is based on a closed oundation; the second example is based on anopen oundation.

  • 7/29/2019 11 Fema p550 Apndxd

    18/32

    D-8 Building on strong and safe foundations

    D foundation analysis and design examples

    D.3 ClosedFoundationExample

    A structure to be supported by the closed oundation is identical to the structure analyzed inthe example rom Section D.. The site, however, is dierent. For the closed oundation de-

    sign, the structure is to be placed in a non-Coastal A zone where breaking waves are limited to.5 eet. The design stillwater depth is eet, and the BFE is 3 eet above exterior grade. Whilethe structure could be placed on a 3-oot oundation, the property owner requested additionalprotection rom ooding and a 4-oot tall oundation is to be built. Since the home elevation isidentical to that in the example, the loads and load combinations listed in Table D- are identi-cal. However, since the oundation is closed, ood orces must frst be analyzed.

    Like the previous analysis example, ood orces consist o hydrodynamic loads, debris loads,and breaking wave loads. Since the home is located in a non-Coastal A zone, it is appropriate touse lower bound ood velocities. This will signifcantly reduce hydrodynamic and debris loads.From FEMA 55, the ollowing equation is used:

    Vlower = ds

    = t/sec

    Hydrodynamic Loads

    Fdyn = Cd V A

    = Cd V () ds

    Fdyn = () (.4)()()()()

    = lb/l o wall

    Where Cd o .4 is or a (width o wall/ds) ratio o (4 t/ t)

    (From FEMA 55, Table .)

    The hydrodynamic load can be considered to act at the mid-depth o the stillwater elevation.The hydrodynamic load is less than the 7 ps wind load on the windward wall.

    Debris Loads

    Fi = wV gt

    Fi = [,000 lb ( t/sec)] [(3. t/sec)(0. sec)]

    Fi = 60 lb

    Due to load distribution, the impact load will be resisted by a section o the wall. Horizontalshear reinorcement will increase the width o the section o wall available to resist impact. Forthis example, a 3-oot section o wall is considered to be available to resist impact. The debrisimpact load becomes:

  • 7/29/2019 11 Fema p550 Apndxd

    19/32

    D-9RECOMMENDED RESIDENTIAL CONSTRUCTION FOR COASTAL AREAS

    foundation analysis and design examples D

    Fiwall = (/3) 60 lb

    Fiwall = 0 lb/t

    Breaking Wave Loads

    The home is to be constructed in an SFHA; hence, the NFIP required ood vents will be in-stalled. The breaking wave load can be calculated using ormulae or equalized ood depths(Case ).

    Fbrkw = . Cp ds + .9 ds

    Fbrkw = ds (. Cp + .9)

    Fbrkw = (64)(){(.)(.8) + .9}

    Fbrkw = ,80 lb/l

    The breaking wave load can be considered to act at the -oot stillwater depth (ds) above thebase o the oundation wall.

    The oundation must resist the loads applied to the elevated structure plus those on the oun-dation itsel. Chapter o ASCE 7-05 directs designers to include 75 percent o the ood loadin load combinations 5, 6, and 7 or non-Coastal A zones. Table D- lists the actored loads onthe elevated structure.

    Critical loads rom Table D- include 546 lb/l uplit, ,05 lb/l gravity, and 83 lb/l lateralrom wind loading. The uplit load needs to be considered when designing oundation wallsto resist wind and ood loads and when sizing ootings to resist uplit; the gravity load must be

    considered when sizing ootings and the lateral wind and ood loads must be considered in de-signing shear walls.

    Extending reinorcing steel rom the ootings to the walls allows the designer to consider thewall as a propped cantilever fxed at its base and pinned at the top where it connects to thewood ramed oor raming system. The oundation wall can also be considered simply supported(pinned at top and bottom). The analysis is somewhat simpler and provides conservative results.

    The ,80 lb/l breaking wave load is the controlling ood load on the oundation. The prob-ability that oodborne debris will impact the oundation simultaneously with a design breakingwave is low so concurrent wave and impact loading is not considered. Likewise, the dynamic

    load does not need to be considered concurrently with the breaking wave load and the 7 lb/swind load can not occur concurrently on a wall submerged by oodwaters.

    The breaking wave load is analyzed as a point load applied at the stillwater level. When sub-jected to a point load (P), a propped cantilevered beam o length (L) will produce a maximummoment o 0.97 (say 0.) PL. The maximum moments occur when P is applied at a distance0.43L rom the base. For the 4-oot tall wall, maximum moment results when the load is appliednear the stillwater level (ds). In this example, the ASCE 7-05 required ood load o 75 percento the breaking wave load will create a bending moment o:

  • 7/29/2019 11 Fema p550 Apndxd

    20/32

    D-0 Building on strong and safe foundations

    D foundation analysis and design examples

    M = (0.) brkw (L)

    = (0.)(0.75)(,80 lb/t) (4 t)

    = 768 t-lb/l or

    = 9,00 in-lb/l

    The reinorced masonry wall is analyzed as a tension-compression couple with moment armjd, where d is the distance rom the extreme compression fber to the centroid o the rein-orcing steel, and j is a actor that depends on the reinorcement ratio o the masonry wall.While placing reinorcing steel o center in the wall can increase the distance (d) (and reducethe amount o steel required), the complexity o o-center placement and the inspections re-quired to veriy proper placement make it disadvantageous to do so. For this design example,steel is considered to be placed in the center o the wall and d is taken as one hal o the wallthickness. For initial approximation, j is taken as 0.85 and a nominal 8-inch wall with a thick-ness o 7-5/8 inches is assumed.

    Solving the moment equation is as ollows:

    M = T (jd)

    T = M/(jd) = Tension orce

    = M/(j)(t/) (t = thickness o wall)

    T = (9,00 in-lb/l) {(0.85)(7.63 in)(0.5)}

    = ,837 lb/l

    For each linear oot o wall, steel must be provided to resist ,837 pounds o bending stress and546 pounds o uplit.

    Fsteel = ,837 lb/l (bending) + 546 lb/l (uplit)

    = 3,383 lb/l

    The American Concrete Institute (ACI) 530 allows 60 kips per square inch (ksi) steel to be stressedto 4 ksi so the reinorcement needed to resist breaking wave loads and uplit is as ollows:

    Asteel = 3,383 lb/l 4,000 lb/in

    = 0.4 in /l

    Placing #5 bars (at 0.3 in/bar) at 4 inches on centers will provide the required reinorce-ment. To complete the analysis, the reinorcement ratio must be calculated to determine theactual j actor and the stresses in the reinorcing steel need to be checked to ensure the limitsdictated in ACI 530 are not exceeded. The wall design also needs to be checked or its ability toresist the lateral orces rom ood and wind.

  • 7/29/2019 11 Fema p550 Apndxd

    21/32

    D-RECOMMENDED RESIDENTIAL CONSTRUCTION FOR COASTAL AREAS

    foundation analysis and design examples D

    Footing Sizing

    The oundation walls and ootings must be sized to prevent overturning and resist the 546 lb/l uplit. ASCE 7-05 load combination 6 allows 60 percent o the dead load to be considered inresisting uplit. Medium weight 8-inch masonry cores grouted at 4 inches on center weigh 50

    lb/s or, or a 4-oot tall wall, 00 lb/l. Sixty percent o the wall weight (0 lb/l) reduces theamount o uplit the ooting must resist to 46 lb/l. At 90 lb/t3 (60 percent o 50 lb/t3 ornormal weight concrete), the ooting would need to have a cross-sectional area o 4.7 squareeet. Grouting all cores increases the dead load to 68 lb/s and reduces the required ootingarea to 4.5 square eet. The bearing capacity o the soils will control ooting dimensions. Stron-ger soils can allow narrower ooting dimensions to be constructed; weaker soils will requirewider ooting dimensions.

    The design also needs to be checked to confrm that the ootings are adequate to prevent slid-ing under the simultaneous action o wind and ood orces. I marginal riction resistanceexists, ootings can be placed deeper to beneft rom passive soil pressures.

    D.4 OpenFoundationExample

    For this example, the calculations are based on a two-story home raised 8 eet above grade withan integral slab-grade beam, mat-type oundation and a 8-oot by 4-oot ootprint. The homeis sited approximately 800 eet rom the shore in a Coastal A zone. Subtracting the elevationo the site (determined rom a topographic map or preerably rom a survey) rom the ABFEand adding estimated erosion (in eet) determines that the oodwaters during a design event(including wave eects and runup) will extend 6 eet above the eroded exterior grade. It is im-

    portant to note, however, that submittal o an elevation certifcate and construction plans tolocal building code and oodplain ofcials in many jurisdictions will require that the elevationbe confrmed by a licensed surveyor reerencing an established benchmark elevation.

    The wood ramed home has a 3: roo pitch with a mean roo height o 30 eet, a center woodbeam supporting the frst oor, and a center load bearing wall supporting the second oor.Clear span trusses rame the asphalt-shingled roo and are designed to provide a -oot over-hang. This home is a relatively light structure that contains no brick or stone veneers.

    The surrounding site is at, gently sloping approximately oot in 50 eet. The site and sur-rounding property have substantial vegetation, hardwood trees, concrete sidewalks, and streets.

    A our-lane highway and a massive concrete seawall run parallel to the beach and the estab-lished residential area where the site is located. The beach has been replenished several times inthe last 50 years. Areas to the west o the site that have not been replenished have experiencedbeach erosion to the ace o the seawall. The ASCE 7-05, 3-second gust design wind speed is 40mph and the site is in an Exposure Category C.

    The proposed oundation or the home incorporates a monolithic carport slab placed integrallywith a system o grade beams along all column lines (see Figure D-6). The dimensions o the

  • 7/29/2019 11 Fema p550 Apndxd

    22/32

    D- Building on strong and safe foundations

    D foundation analysis and design examples

    grade beam were selected to provide adequate bearing support or gravity loads, resistance tooverturning and sliding, and mitigate the potential o undermining o the grade beams and slabdue to scour action. The home is supported by concrete columns, extending rom the top othe slab to the lowest member o the elevated structure, spaced at 4 eet on center (see FigureD-7).

    FigureD-6.

    LayoutofOpenFoundationExample.

    14'-0"

    Maximum

    3'-0"

    3'-0"5'-6"

    Critical Areaof Grade Beam

    6" Concrete Slab

    Grade Beam36" Wde x 48" Deep

    16"x16"Column

    FigureD-7.

    LoadingDiagramforOpen

    FoundationExample.

  • 7/29/2019 11 Fema p550 Apndxd

    23/32

    D-3RECOMMENDED RESIDENTIAL CONSTRUCTION FOR COASTAL AREAS

    foundation analysis and design examples D

    Lateral Wind Loads

    Sum horizontal loads (Flat) on the elevated structure (orces to the let are positive)

    Flat = (-6 lb/l) + (74 lb/l) + (80 lb/l) + (80 lb/l) + (80 lb/l) + (80 lb/l)

    = 868 lb/lDead Loads

    Dead load reactions (Wdead) are determined by summing loads over the tributary areas. Forthe anterior columns:

    Wdead = L/ (wrDL)+ L/4 (wstDL + wndDL) + (F + F) wwlDL

    = [4 s/l ( ps)] + [7 s/l (8 ps + 0 ps)] + [(0 s/l + 0 s/l) 9 ps]

    = 474 lb/l

    Live Loads

    Floor

    Live loads (Wlive) are calculated in a similar ashion

    Wlive = L/4(WstLL + WndLL)

    = (7 sq t/l)(40 + 30) ps

    = 490 lb/l

    Roof

    Wliveroo = L/(WrLL)

    = (4 sq t/l)(0 ps)= 80 lb/l

    A minimum roo slope o 3: was assumed or the homes; rain loading was not considered.

    Flood Eects

    Since the oundation selected is a system o concrete columns, the equations used to calculateood loads are based on open oundation. The stillwater ooding depth (ds) is as ollows:

    ds = DFE .55

    = 6 t .55

    = 3.9 t

    Hydrostatic Loads

    Calculations are based on a 6-inch square normal weight concrete column that extends 8 eetabove the concrete slab.

  • 7/29/2019 11 Fema p550 Apndxd

    24/32

    D-4 Building on strong and safe foundations

    D foundation analysis and design examples

    The column weighs ,3 pounds dry ((.33 t)(.33 t)(8 t)(50 lb/t3).

    Under ood conditions, the column displaces 0.6 t3 o saltwater which, at 64 lb/t3, weighs 679pounds so the column weighs ,444 pounds when submerged.

    Hydrodynamic Loads

    Flood Velocity

    Since a Coastal A zone is close to the ood source, ood velocity is calculated using the ASCE7-05 Equation C5- as ollows:

    V = [(3. t/sec)(3.9 t)]/

    = . eet per second (ps)

    Flood Force

    ASCE 7-05 Equation C5-4 is as ollows:

    Fdyn = Cd V A

    = () ()()(. ps)(.33 t)(3.9 t)

    = ,303 lb/column

    Floodborne Debris Impact

    The ood debris impact can be estimated, per FEMA 55 Formula .9, as ollows:

    Fi

    = wV gt

    = [,000 lb (. t/sec)] [(3. t/sec)(0. sec)]

    = 3,478 lb

    Breaking Wave Load

    The equation or vertical piles and columns rom ASCE 7-05 is as ollows:

    Fbrkp = Cdb DHb

    = (.5)(64 lb/t3)(.8 t)(3.04 t*)

    = , lb

    Wind Load on Columns

    For a load case combining both wind and ood orces, the column would be almost completelysubmerged; thereore, the wind load on the column shall not be included.

    * A wave height o 3.04 t suggests a V zone but, in this example, the depth o water is increased by erosion, which is not considered in

    mapping A zones. The deeper water supports a bigger wave, which in this case exceeds the V-zone wave height minimum.

  • 7/29/2019 11 Fema p550 Apndxd

    25/32

    D-5RECOMMENDED RESIDENTIAL CONSTRUCTION FOR COASTAL AREAS

    foundation analysis and design examples D

    Calculating Reactions rom Wind, Live, and Dead Loads

    Sum overturning moments (Mwind) and (Mood) about the leeward corner o the mat ounda-tion. For sign convention, consider overturning moments as negative. Note in this example thehome is slightly higher above grade and hence the wind loads are slightly higher.

    Mwind = (-504 lb/l)( t) + (-94 lb/l)(7 t) + (6 lb/l)(.75 t) + (-74 lb/l)(.75t) + (-80 lb/l)(3 t) + (-80 lb/l)(3 t) + (-80 lb/l)(3 t) + (-80 lb/l)(3 t) + (-30 lb/l)(9 t)

    = -3,84 t-lb/l

    The vertical components o the reaction caused by the wind overturning moment is:

    Rx = 3,84 lb 8 t = +/- ,37 lb/t

    Mood = .5[((-, lb)(3.9 t)) + ((-,303 lb)(3.9 t/)) + ((-3,478 lb)(3.9 t))] =35,053 t-lb/t

    The vertical component o the reaction caused by the ood overturning moment is:

    Rx = 35,053 lb 8 t = +/- ,5 lb outboard columns

    Load Combinations

    Table D-3 summarizes loads on the open oundation example. Loads are listed or the eightload combinations and critical loads are highlighted.

    TableD-3.LoadsatBaseofColumnsSpaced14FeetOnCenter(forthreerowsofcolumnsperbay)

    ASCE7-05LoadCombination Vertical(lb) Horizontal( lb)#1 D + F 1,444 + 14(474) = 8,080

    #2 D + F + L 1,444 + 14(964) = 14,940

    #3 D + F + L 1,444 + 14(754) = 12,000

    #4 D + F + 0.75(L) + 0.75(L) 8,080 + (0.75)[(14)(490+280)] =16,165

    #5 D + F + W + 1.5(Fa) 8,080 +/- 14(1,137) +/- 1,252 =25,876; -9,716 windwad; lwad

    wind + (1.5)[Fdyn + Fi]

    [(14(868)(1/3)] + (1.5)[(1,303+3,478)] = 11,222

    #6 D + F + 0.75(W) + 0.75(L) +

    0.75(L) + 1.5(Fa)

    8,080 +/- (0.75)(14)(1,137)

    +(0.75)(14)([(490+280)] +/-1,252 = 2,348; 29,982 windwad;

    lwad

    (0.75) wind + (1.5)[Fdyn + Fi]

    [(0.75)(14)(868)(1/3)] +(1.5)[(1,303+3,478)] = 10,210

    #7 0.6D + W + 1.5(Fa) 0.6 [2,123+14(474)] +/- 14(1,137)

    +/- (1.5)1,252 = -12,541; 23,051windwad; lwad

    wind + (1.5)[Fdyn + Fi][(14(868)(1/3)] + (1.5)[(1,303+3,478)] = 11,222

    #8 0.6D [0.6((2,123) + 14(474))] = 5,255

    citial lads a in bld.

  • 7/29/2019 11 Fema p550 Apndxd

    26/32

    D-6 Building on strong and safe foundations

    D foundation analysis and design examples

    Where

    D = dead load

    F = uid (buoyancy) load

    L = live loadLr = roo live load

    W = wind load

    ww = windward

    lw = leeward

    Results

    Each perimeter column needs to support the ollowing loads:

    Vertical Load = 9,98 lb

    Uplit = ,54 lb

    Lateral Load = , lb

    Moment wind + dyn = [(/3)(4)(,34)(8) + (,303)(3.9/)] ,000 lb/kip

    = 5.6 t-kip

    Moment wind + brkp = [(/3)(4)(,34)(8) + (,3)(3.9)] ,000 lb/kip

    = 96.9 t-kip

    Moment debris = (3,478)(3.9) ,000 lb/kip= 3.6 t-kip

    Moment wind + dyn+ debris = 5.6 t-kip + 3.6 t-kip

    = 65. t-kip

    The orce is assumed to act at a point d s/ above the eroded ground surace. For concrete de-sign, we use load actors per ASCE 7-05.

    Ultimate Moment wind + dyn = (48.6)(.)+(.5)(.0)

    = 63.4 t-kip

    Ultimate Moment wind + brkp = (48.6)(.)+(4.3)(.0)

    = 66.9 t-kip

    Ultimate Moment wind + dyn + debris = (63.4)+3.6()

    = 90.6 t-kip

  • 7/29/2019 11 Fema p550 Apndxd

    27/32

    D-7RECOMMENDED RESIDENTIAL CONSTRUCTION FOR COASTAL AREAS

    foundation analysis and design examples D

    Foundation Design

    Overturning

    The overturning moment due to wind with a typical bay o 4 eet wide is as ollows:

    Mwind = (-3,84 t-lb/l)(4 t)= -445,774 t-lb

    MFa (.5) = (.5)[(, lb)(3.9 t) + ()(,303 lb)(3.9 t/)]

    = -4,707 t-lb

    Mo = -445,774 t-lb - 4,707 t-lb

    = -460,48 t-lb

    In this example, it is assumed that the home and the oundation slab are reasonably symmetri-cal and uniorm; thereore, it is assumed the center o gravity or the dead loads is at the center

    o the bay.

    Dead load at perimeter columns

    Dext = (474 lb/t)(4 t)( columns)

    = 3,7 lb

    Dead load at an interior column:

    Dint = (4 t)(4 t)(8 ps)

    = ,568 lb

    Dead load o 3 columns: (3)(8 t)(.33 t x .33 t)(50)lb cubic t

    = 6,368 lb

    Assume that only the grade beams are sufciently reinorced to resist overturning (neglectweight o slab)

    Dead load o the grade beams (area)(depth) (density o concrete)[(8 t x 3 t) + (3)(( t)(3 t)](4 t)(50 lb cubic t) = 09,800 lb

    Summing the dead loads = 3,7 + ,568 + 6,368 + 09,800 = 3,008 lb

    Allowable dead load moment o 60 percent

    Md = (0.6)( 3,008 lb)(4 t)

    = ,00,476 t-lb

    Since Mot= 460,48 t-lb is very much less than 0.6 Md = ,00,476 t-lb, the oundation can beassumed to resist overturning.

  • 7/29/2019 11 Fema p550 Apndxd

    28/32

    D-8 Building on strong and safe foundations

    D foundation analysis and design examples

    Sliding

    The maximum total lateral load o wind and ood acting on the entire typical bay is as ollows:

    Lwa = W + .5 Fa

    = [(4 t (868 lb/ t) + .5(7,03 lb)]

    = 3,375 lb

    Sliding Resistance = (tan)N + Passive Resistance at Vertical Foundation Suraces

    = internal angle o soil riction, assume = 5 degrees

    N = net normal orce (building weight - uplit orces)

    N = (3,008) + (4 t)[((6 t)(- ps )+(4 t)(-36 ps)+( t)(-65 ps)]

    = 7,48 lb

    Ignore passive soil pressure

    Dead Load Sliding Resistance = (tan 5)(7,48 lb)

    = 54,758 lb

    Since Lwa = 3,37 lb is less than 60 percent o Dead Load Sliding Resistance = 54,758, the oun-dation can be assumed to resist sliding.

    Soil Bearing Pressure

    The simplifed approach or this mat oundation assumes that only the grade beams carry loadsto the soil; the slab between grade beams is not considered to contribute support. It is urther as-sumed that the bearing pressure is uniorm in the absence o wind and ood loading. The areaso the grade beams along the outboard column lines, in the direction o the ow o wind andood, are considered the critical areas o the grade beam. The load combination table belowindicates the bearing pressures or the ASCE 7- 05 load combinations or the critical grade beamarea. These load combinations are calculated to ensure that downward orces o the wind andood moment couple do not overstress the soil. The actored dead load moment that resistsoverturning is o a magnitude such that there is no net uplit along critical grade beams. TableD-4 presents oundation bearing pressures or typical bays.

    Sel Weight o square o oot Grade Beam = (4 t)(50 lb/cubic t) = 650 ps

    Area o Critical Grade Beam = [(3t)(4 t)] + [(3 t)(5.5 t)]

    = 58.5 t

    Weight o Critical Grade Beam = (58.5 t)(4 t)(50 lb/cubic t)

    = 35,00 lb

    Critical Column Uplit = ,54 lb (load combination 7)

  • 7/29/2019 11 Fema p550 Apndxd

    29/32

    D-9RECOMMENDED RESIDENTIAL CONSTRUCTION FOR COASTAL AREAS

    foundation analysis and design examples D

    Verifcation o Uplit Resistance = [35,00 lb(0.6)] ,54 lb

    = 8,59 lb (positive load, no uplit)

    Presumptive Allowable Bearing Pressure = ,500 ps

    TableD-4.FoundationBearingPressuresforTypicalBays(forthreerowsofcolumnsperbay)

    ASCE7-05LoadCombination Combined Loads( lb) BearingPressures(psf)

    #1 D + F 8,080 8,090 58.5 + 650 = 788

    #2 D + F + L 14,940 14,950 58.5 + 650 = 905

    #3 D + F + L 12,000 12,000 58.5 + 650 = 855

    #4 D + F + 0.75(L) + 0.75(L) 16,165 16,165 58.5 + 650 = 926

    #5 D + F + W + 1.5(Fa) 28,104 28,104 58.5 + 650 = 1,130

    #6 D + F + 0.75(W) + 0.75(L) +

    0.75(L) + 1.5(Fa)29,982 29,982 58.5 + 650 = 1,163

    #7 0.6D + W + 1.5(Fa) 23,051 23,051 58.5 + 650 = 1,044

    #8 0.6D 5,255 5,255 58.5 + 650 = 740

    Where

    D = dead load

    F = load due to uids with well-defned pressures and maximum heights(See Section D. or additional inormation)

    Fa = ood load

    L = live load

    Lr = roo live load

    W = wind load

    Note: The maximum bearing pressure is in bold (,63 ps) and is less than the assumed ,500ps bearing pressure.

    Design of Concrete members per ACI-318-02 Code and ASCE 7-05; Sections 2.3.2 and 2.3.3-1

    Column Design

    Veriy that 6-inch x 6-inch column design is adequate.

    Concrete strength = 4,000 psi

  • 7/29/2019 11 Fema p550 Apndxd

    30/32

    D-30 Building on strong and safe foundations

    D foundation analysis and design examples

    Reinorced with (4) #8 bars, grade 60 reinorcing, with -inch clear cover

    Note: ,000 lb = .0 kip

    Assume that the total wind load distributed through the oor uniormly to 3 columns.

    Check combined axial and bending strength:

    Ultimate Moment wind + dyn = (.6)[(8 ft)((4 ft)(868 lb/ft)/(3))] + (.0)[(3.9 ft/)(,303)lb)]

    = 5,849 t-lb + 5,08 t-lb

    = 56,93 t-lb ,000 lb/kip = 56.9 t-kip

    Ultimate Moment wind + brkp = (5,849 t-lb) + (.0)[(, lb)(3.9 t)]

    = 6,95 t-lb ,000 lb/kip = 6.3 t-kip

    Ultimate Moment wind + brkp + debris = 6.3 t-kip + (.0)(3.5 kip)(3.9 t)

    = 88,6 t-kip

    Maximum Factored Moment = 88.6 t-kip = ,063 in kip

    Reer to Table D-3, conservatively assume ood load actor o .0 or all axial loads

    Maximum actored Axial Compression = (.0)(30.0 kip) = 60.0 kip

    Maximum actored Axial Tension = (.0)(.5 kip) = 5.0 kip

    Based on a chart published by the Concrete Reinorced Steel Institute (CRSI), the maximum al-lowable moment or the column = ,09 in kip or 0 axial load and ,407 in kip or 0 kip axialload; thereore, the column is adequate.

    Check shear strength:

    Critical Shear = wind + Fdyn + Fi

    Ultimate Shear = Vu = [(4 t)(0.868 kip)(/3)](.6) + [(.3 kip)+(3.5 kip](.0)

    = Vu = 6.0 kip

    As the maximum unit tension stress is only 5.0 kip/6 in x 6 in = 0.098 kip/in and themaximum axial compression stress is only 60.0 kip/6 in x 6 in = 0.34 kip/in, we can con-servatively treat the column as a exural member or beam. The allowable shear o the concretesection then, per ACI-38-0 .3.., .3..3, and .5.5. with minimum shear reinorcing(tie/stirrup), would be as ollows.

    Allowable Shear = Vc = (0.75)(6 in-.5 in)(6 in )()(4,000 psi)/ (/,000) = 0.5 kip

  • 7/29/2019 11 Fema p550 Apndxd

    31/32

    D-3RECOMMENDED RESIDENTIAL CONSTRUCTION FOR COASTAL AREAS

    foundation analysis and design examples D

    The shear strength o the column is adequate with minimum shear reinorcement.

    The minimum area o shear, Av, per ACI 38-0, .5.5.3 would be:

    Av = (50)(width o member)(spacing o reinorcing)/yield strength

    o reinorcing= (50)(6 in)(6 in)/(60,000 psi) = 0. in

    pieces o #4 bar As = ()(0.) = 0.40 in

    Use o #4 bar or column ties (shear reinorcement) is adequate.

    Check spacing per ACI -38-0, 7.0.4

    6 diameter o vertical reinorcing bar = (6)( in) = 6 in

    48 diameter o column tie bar = (48)(/ in) = 4 in

    Least horizontal dimension = 6 in

    Thereore, #4 ties at 6 inches on center are adequate.

    The column design is adequate.

    Grade Beam Design

    The size o the grade beam was confgured to provide adequate bearing area, resistance touplit, a reasonable measure o protection rom damaging scour, and to provide a actor o re-dundancy and reserve strength should the oundation be undermined. A grade beam 36 incheswide and 48 inches deep was selected.

    Maximum Bearing Pressure = ,63 ps = . ks (kip/square oot)

    Assume a combined load actor o .0 (or ood)

    Check Shear strength:

    Maximum Factored Uniorm Bearing Pressure = wu = (.0) (3.0 t )(. ks) = 7. kip/t

    Maximum Factored Shear = Vu = (7. kip/t)(4 t/) = 50.0 kip

    Allowable Shear without minimum shear reinorcing (stirrups) = Vc/

    Vc/= (0.75)(36 in)(48 - 3.5 in)(63 psi)(/,000) = 75.7 kip

    Use nominal #4 two leg stirrups at 4 inches on center

    Check exural strength: Assume simple span condition

    Maximum Factored Moment = Mu = (7. kip/t)(4 t) (/8) = 76 t-kip

  • 7/29/2019 11 Fema p550 Apndxd

    32/32

    D foundation analysis and design examples

    Concrete strength = 4,000 psi

    Reinorcement grade = 60,000 psi

    Try (4) #6 reinorcing bar continuous top and bottom

    As = (4)(0.44 in) = .76 in top or bottom

    total As = ()(.76) = 3.5 in

    Reinorcement ratio ()

    =As [(section width)(section depth- clear cover- bar diameter)]

    = As [(bw)(d)]

    = (.76 in) [(36)(48 - 3 - 0.375)]

    = 0.0096

    One method o calculating the moment strength o a rectangular beam, or a given sectionand reinorcement, is illustrated in the 00 edition o the CRSI Design Handbook. Reerencingpage 5-3 o the handbook, the ormula or calculating the moment strength can be written asollows:

    Mn = ()[((As)(y)(d)) (((As)(y)) ((0.85)( 'c)(width o member)()))]

    Mn = (0.9)[((.76)(60,000)(44.63)) (((.76)(60,000)) ((0.85)(4,000)(36)()))]

    = 4,4,634 in lb ,000 = 353 t-kip

    = 0.9

    Area o reinorcing steel (As) minimum exural

    = (0.0033)(4)(44.63)

    = 3.6 in

    or

    (.33) (As required by analysis) = Mn is much greater than Mu

    Area o steel or shrinkage and temperature required = (0.008)(48)(36) = 3. in

    Total area o steel provided = (8) #6 = (8)(0.44) = 3.5 in adequate

    Thereore, the grade beam design is adequate, use (4) #6 reinorcing bar continuous on the topand bottom with #4 stirrups at 4-inch spacing.