10AA
-
Upload
carameloo2012 -
Category
Documents
-
view
216 -
download
0
Transcript of 10AA
-
7/30/2019 10AA
1/12
10A
HUBBELL
Power SystemsCHANCE CENTRALIA, MISSOURI
JULY 2010
Se
10HUBBELL
Type C-POLYMER
Cutouts (Standard, Linkbreak & Loadbreak)
and
Cutout-Arrester Combinations
CAUTION: The equipment covered in this catalog section should be installed, used, and serviced only by competent per-sonnel amiliar with and ollowing good work and saety practices. This equipment is or use by such personnel and is notintended as a substitute or adequate training and experience in sae procedures or this type o equipment.
This catalog inormation and any related instruction sheets do not cover all details or situations in equipment use nor dothey provide or every possible contingency to be encountered in relation to installation, operation or maintenance. Shouldadditional inormation and details be desired, or i specic situations arise that are not covered adequately or the user'spurpose the specics should be reerred to Hubbell Power Systems, Inc.
Warranty - MaterialHubbell Power Systems, Inc. warrants all products sold by it to be merchantable (as such term is defned in the Uniorm Commercial Code) and to be ree rom deects in material and workmanship.
Buyer must notiy the Company promptly o any c laim under this warranty. The Buyer's exclusive remedy or breach o this warranty shall be the repair or replacement, F.O.B. actory, at the Company'soption, o any product deective under the warranty which is returned to the Company within one year rom the date o shipment. NO OTHER WARRANTY, WHETHER EXPRESS OR ARISING BY
OPERATION OF LAW, COURSE OF DEALING, USAGE OF TRADE OR OTHERWISE IMPLIED, SHALL EXIST IN CONNECTION WITH THE COMPANY'S PRODUCTS OR ANY SALE OR USE
THEREOF. The Company shall in no event be l iable or any loss o profts or any consequential or special damages incurred by Buyer. The Company's warranty shall run only to the frst Buyer o aproduct rom the Company, rom the Company's distributor, or rom an original equipment manuacturer reselling the Company's product, and is non-assignable and non-transerable and shall be o
no orce and eect i asserted by any person other than such frst Buyer. This warranty applies only to the use o the product as intended by Seller and does not cover any misapplication or misuse o
said product.
Warranty - ApplicationHubbell Power Systems, Inc. does not warrant the accuracy o and results rom product or system perormance recommendations resulting rom any engineering analysis or study. This applies
regardless o whether a charge is made or the recommendation, or i it is provided ree o charge.
Responsibility or selection o the proper product or application rests solely with the purchaser. In the event o errors or inaccuracies determined to be caused by Hubbell Power Systems, Inc., its
liability will be l imited to the re-perormance o any such analysis or study.
Photos show 15 kVproducts.
27 kV products alsoare available.
Copyright 2010 Hubbell Incorporated 210 North Allen Street Centralia, MO 65240 USAwww.hubbellpowersystems.com
E-mail: [email protected]
NOTE: Because Hubbell has a policy o continuous product improvement, we reserve the right to change design and specifcations without notice.
Printed in USA
NOTICE: For latest revision o our Catalog and Literature, please visit our web site: www.hubbellpowersystems.com
-
7/30/2019 10AA
2/12
0AA-2
CHANCE CENTRALIA, MISSOURIJULY 2010 HUBBELL
Power Systems
HUBBELL Type C-POLYMER Cutouts
the ground, rom a bucket truckor rom the pole.
The toggle type trunnion is aselective silver-plated bronzecasting or eicient currenttranser to the lower hinge con-tacts. A cam shaped projectionon each side o the trunnioncasting provides high pressureparallel current paths to thelower contacts. These projections,or pivot pins, are cast ull roundor smooth rotational operationin the hinge. The link ejector as-sists in arc interruption duringlow ault current or excessiveoverload conditions. A groove inthe center o the link ejector al-lows the use links pigtail to godirectly rom the use tube to theattachment nut. A curved ejectorminimizes bending stresses in thepigtail to prevent broken strands.
A stainless steel torsion spring onthe link ejector helps to rapidlyeject the link rom the bore o theuseholder during interruption.The 200 amp link ejector has a
wider groove area and increasedspring orce to accommodate thelarger links.
The link ejector is pinned to thetrunnion casting with a stainlesssteel pin to provide resistance to
corrosive elements and provide smooth pivotal action. Aninterlocking eature between the link ejector and tube castingprevents excessive tension on the use link during closure,thereby preventing link breakage.
The link ejector employs a hammer eect to enhance toggleaction o the trunnion during low ault and overload inter-ruptions, hence dropout action is enhanced. The link ejectorprovides sucient surace area to acilitate re-using by
linemen wearing gloves.
Ratings/Specifcations
STANDARD Type C-Polymer cutouts are maximum designvoltage rated to eliminate application and selection conusion.There are no restrictions on application to grounded wye,ungrounded wye, or delta systems having maximum operat-ing voltages (line-to-line) equal to or less than the cutoutmaximum design voltage rating. (See the LINKBREAK andLOADBREAK cutouts or their specications.) Interruptiontests have been perormed at ull system line-to-line voltage.100-amp and 200-amp use tubes and 300-amp disconnectblades are available or each voltage class. They all t into acommon mounting assembly rated at 300 amps continuous.
QualityConstructionEfcient Current Transer
The Type C-Polymer cutout hasan all copper current path. Allcontacts are silver-plated. Ter-minals are tin-plated bronze oruse with copper or aluminumconductors.
Loadbreak Hooks
Galvanized steel hooks arestandard on all Type C cutouts,except the arc chute version, oruse with a portable loadbreaktool. These sturdy hooks aremounted on the top support andserve to guide the useholderinto the latch socket.
Top Contact
The top contact is attached tothe galvanized-steel hood bya stainless rivet to provide asmooth sel-aligning action
during closing even in severelycorrosive environments. Thetop contact provides a socket-type cavity or latching theuseholder and prevents anypossible over-travel o theuseholder. The top contact ismade o a highly conductive copper strip with silver-platedembossments or ecient current transer. The contacts areheld under constant pressure designed to maintain rmcontact with the useholder contact surace until ault inter-ruption is accomplished.
Hinge
The hinge on the Type C-Polymer cutout employs large pivot
areas or the useholders trunnion and is cast o a copper alloychosen or its strength and corrosion resistance. The hingecontacts are highly conductive copper alloy stampings andare plated to assure low resistance current transer rom thetrunnion casting. The parallel current paths are backed up byhigh strength cantilever springs and are riveted to the hingecastings. Fuseholder can be dropped into place and easilylited up and out. No tricky maneuvering is required.
Fuseholders
The solid cap on the single vent useholder is a copper alloy,silver-plated to provide ecient current transer. An integralring is provided in the top tube casting or opening and clos-ing the useholder with an appropriate disconnect tool rom
ApplicationThe primary purpose o any cutout is to provide protec-tion to the lines o your system and the various apparatuson those lines such as transormers and capacitor banks.Hubbell Type C-Polymer cutouts provide reliable protectionrom low-level overloads that just melt the use link, inter-
mediate aults, and very high aults, through maximum
interrupt rating.
In addition, Type C-Polymer cutouts can also be used as asectionalizing device. With the use o a portable loadbreaktool, Type C-Polymer cutouts can unction much like anoverhead disconnect switch. A 300 amp disconnect blade
is also available or this purpose.
Polymer InsulatorsType C-Polymer cutout insulators are manuacturedwith ESP silicone alloy rubber, the same material usedin Ohio Brass PDV arresters and Hi*Lite insulators.ESP is a polymer compound made by alloying siliconeand EPDM rubber. This alloy oers the desirable tough-ness and resistance to tracking o our original EPR,with the hydrophobic characteristics derived rom lowmolecular weight silicone oils.
Hubbell Power Systems uses several tests to evaluate
materials. Tracking, QUV, corona cutting, salt og,oxidative stability and variations o dierential ther-mal analysis tests conrm the quality o the material.For urther inormation on our polymers, ask yourHubbell Power Systems representative or the publica-tion "Polymer Materials or Insulator Weathersheds"EU1264-H.
Upgrades to Cutout Perormance
The increased metal-to-metal leakage distance o TypeC-Polymer Cutouts compares to their porcelain coun-terparts at 12.6" (319 mm) vs 8.7" (220 mm) or 15kVand 17.1" (434 mm) vs 12.6" (319 mm) or 27kV.
Signicantly lighter, Type C-Polymer Cutouts typicallyweigh only approximately hal their porcelain counter-
parts. This ergonomic advantage makes them simpleto install and, o course, ar less ragile than porcelain.That means reduced or eliminated losses rom routineshipping, storage and handling.
-
7/30/2019 10AA
3/12
10A
HUBBELL
Power SystemsCHANCE CENTRALIA, MISSOURI
JULY 2010
HUBBELL Type C-POLYMER Cutouts
STAINLESS-STEELSPRING PROVIDESPROPER TOGGLE ACTIONOF FUSELINK EJECTOR(CAST-BRONZE ON ALL 200AND LINKBREAK FUSEHOLDERS;STAINLESS-STEEL ON ALL 100A)
Compare Hubbellquality and technical expertise
SILVER-TO-SILVERCONTACTS
CAST BRONZE HINGEFOR CORROSION RESISTANCE
COPPERCURRENTPATH
FUSEHOLDER TOGGLE LATCHLIMITS TENSION OF FUSELINK
CAST BRONZELOWER TUBE
CASTING
CAST BRONZE TOP TUBE CASTINGAND PULL RING
HIGH-STRENGTH FIBERGLASS FUSETUBECOATED WITH ULTRA-VIOLET INHIBITOR
GALVANIZED STEEL HOOKSFOR LOADBREAK TOOL
STAINLESS STEELBACKUP SPRINGTO MAINTAINCONTACT PRESSURE
POLYMERINSULATOR
TIN-PLATED BRONZE TERMINALSFOR USE WITH COPPEROR ALUMINUM CONDUCTOR
GALVANIZED-STEEL CHANNEL
COPPERARC-SHORTENING ROD(ON SOME RATINGS)
TWO-PLACE LOCKINGTO PREVENT SIDEMOVEMENT OF HOOD,CONTACTS OR HOOKS
COPPER CURRENT PATH
All Type C Cutouts meet or exceed ANSI/NEMA specifcations.
SYNTHETICFUSE TUBELINER
LARGE NUT TOFASTEN FUSELINKWITHOUT BREAK-ING STRANDS
MECHANICAL ASSIST:
FUSEHOLDER IS AVAIL-ABLE WITH A TORSIONALSPRING ON TRUNNION TOAID DROP OUT OPERATIONIN CORROSIVE ENVIRON-MENTS.
15 kV product shown. 27 kV cutout varies slightly in appearance.
-
7/30/2019 10AA
4/12
0AA-4
CHANCE CENTRALIA, MISSOURIJULY 2010 HUBBELL
Power Systems
Type C-Polymer
STANDARD Cutout
kVLIW (BIL)
110
125
STANDARD Type C-Polymer Cutoutwith NEMA Type B Bracket
A
155/8"
395 mm
161/16"
408 mm
B
47/8"
125 mm
65/8"
167 mm
C
115/8"
295 mm
131/16"
332 mm
D
31/4"
82 mm
27/8"
72 mm
E
221/16"
561 mm
27"
686 mm
InterchangeabilityChance was the rst to design a cutout that could interchangeuseholders and mounting assemblies with those o anothermanuacture. Standard Type C useholders and mounting as-semblies are mutually interchangeable with the S&C ElectricCompanys Type XS cutout (within the same voltage class).
The Type C-Polymer Standard cutout is mutually interchange-able with Chance Type C Porcelain Standard cutout.
Synthetic Arc-Quenching FusetubeThe1/2-inch inside diameter o the Type C-Polymer cutouts 100ampere usetube increases internal pressure giving superiorand reliable expulsion action. During requently encounteredintermediate ault ranges this diameter also permits higherTRV (transient recovery voltage) values to be tolerated. Thissmall bore design eliminates any concern related to highimpedance phase-to-phase aults on ungrounded wye anddelta systems.
The inside liner is a synthetic arc-quenching ormulation inpart consisting o polyester ber, epoxy and Aluminum TriHydrate. The liner is chemically bonded to the tube's glass-reinorced shell. This combination provides a moisture sourceto extinquish the arc during interrupt operations without
absorption o atmospheric moisture leading to potentialswelling and delamination, and provides a high burstingstrength. It is protected rom the weather and environmentby a special ultra-violet resistant coating. For more inor-mation on the synthetic arc-quenching material, reer toBulletin 10-0201.
The Hubbell use tube operates with uselinks rom all majorsuppliers.
100 amp or smaller uselinks shall not be used in 200-ampuseholders.
BracketsType C-Polymer cutouts come packed one per carton includ-ing a NEMA Heavy Duty B bracket with captive 11/2" boltor crossarm mounting.
Type X brackets, also or crossarm mounting, provides 2 5/8"additional clearance between the crossarm and the cutout.
D brackets are used to mount cutouts and/or arrestersdirectly to the pole. Three brackets may be used or three-phase application. Type D brackets provide a clean, quickmounting without crossarm or special pole bands.
All the above brackets are galvanized steel or long lastingservice. Cutouts can be ordered without any brackets.
Higher Interrupt CapacitiesBy using a copper arc shortening rod inside the top o theusetube, higher interrupt ratings are obtainable. An arcshortening rod is attached to the cap o some usetubes andlowers the use link within the usetube. This permits amuch shorter arc, resulting in less arc energy, and higher
interrupting capacities. For 200 A tubes, it allows or ullvoltage ratings.
It is necessary to use use links with removable buttonheadswhen arc shortening rods are employed.
TerminalsTin-plated bronze parallel groove type terminals are standardon Type C cutouts. They can accommodate aluminum orcopper conductor sizes ranging rom No. 6 (13.3 mm2) solidcopper through 4/0 (160.6 mm2) ACSR or 250 (167.5 mm2)kcmil stranded copper. The parallel groove design is perector handling two dierent sizes o conductor as is the casewhen arresters are being used. Eyebolts are also available.See ordering data, page 10AA-11.
100 Amp Single Vent
15 kV/110 kV LIW (BIL)
110 kV LIW (BIL) product isdepicted.125 kV LIW (BIL) product variesslightly in appearance.
-
7/30/2019 10AA
5/12
10A
HUBBELL
Power SystemsCHANCE CENTRALIA, MISSOURI
JULY 2010
No option (may not beused with Z in Option 2)Mechanical Assist Fuse-holder (may not be usedwith Blank in Option 2)Fargo cutout cover(available or 15 kVonly) (may not be usedwith Blank in Option 2)
NEMA Heavy Duty B bracketor crossarm (11/2" bolt)Extended type bracket or cros-sarm (Horizontal sectionis 25/8" longer than Type Bbracket)D-shape bracket (pole)No bracket (must be used withM in Option 3)No bracket (cannot use with Min Option 3)
27 kV - 17.1" leakage
TP7102MMPB
Type C-Polymer STANDARD Cutout
Maximum
DesignVoltage15 kV15 kV15 kV15 kV
NominalSystem VoltageThru 14.4 kVThru 14.4 kVThru 14.4 kVThru 14.4 kV
319 mm319 mm319 mm319 mm
Arc
ShorteningRodNo
Yes
Yes
N/A
Continuous
Current(Amps)
100100200300
12.6"12.6"12.6"12.6"
Leakage to GroundMetal to Metal
Interrupt
Capacity(Asym Amps)
10,00016,00012,00012,000**
Specifcations and Ordering InormationAll Type C Cutouts meet or exceed ANSI/NEMA specifcations.
15 kV - 110 kV LIW (BIL) RUS LISTED
See page 10AA-11 or Accessories.
*Weight(lb./kg.)
9.6/4.49.8/4.510.4/4.79.9/4.5
Replacement
FusetubeCap
P7001535PE7001767PE7002146PP7001535P
434 mm434 mm434 mm434 mm
P7001535PE7001768PE7002479PP7001535P
27 kV - 125 kV LIW (BIL)27 kV27 kV27 kV27 kV
NoYes
Yes
N/A
100100200300
8,00012,00010,000
12,000**
Thru 24.9 kVThru 24.9 kVThru 24.9 kVThru 24.9 kV
CP710211CP710213CP710242CP710233
17.1"17.1"17.1"17.1"
11.0/5.011.0/5.011.6/5.311.2/5.1
1.8 lb.2.0 lb.2.6 lb.2.1 lb.
CutoutBase Catalog
NumberCP710112CP710114CP710143CP710133
Fuseholders and Mounting Assemblies
0.76 kg.0.79 kg.1.18 kg.0.95 kg.
15 kV - 110 kV LIW (BIL)Mounting Assembly
only*Base Catalog No.
TP7101MM
Fuseholder orBlade onlyCatalog No.
T710112TT710114TT710143TT710133T
3.6 kg.8.0 lb.
Weight *Weight
**Momentary rating -Solid blade. Must use removable buttonhead use links. *Adjust total weight when selecting Options below.
CP710211CP710213CP710242CP710233
T710211TT710213TT710242TT710233T
1.9 lb.2.0 lb.2.5 lb.2.1 lb.
0.86 kg.0.91 kg.1.13 kg.0.97 kg.
4.1 kg.9.16 lb.TP7102MM
27 kV - 125 kV LIW (BIL)
300A
Blade
100A 200AFuseholders
*Option Sufx 1
Terminal Variations
*Option Sufx 2
Bracket Variations
*Option Sufx 3
Mechanical AssistFuseholder
*Option
sufxesbelow
1 2 31 2 31 2 31 2 3
1 2 31 2 31 2 31 2 3
*Adjust total weight when se-lecting Option suxes above.
*Weight(lb./kg.)
0.33/0.150.16 /0.070.31/0.14
Sufx1
PEL
Description
Parallel-groove clampsSmall eyeboltsLarge eyebolts
Sufx3
Blank
M
F
Description
*Weight(lb./kg.)
2.84/1.29
3.75/1.70
7.67/3.48
Sufx2
B
X
DZ
Blank
Description
Must specify one selection for Option 1.
300ABlade
200AFuseholders
100A
15 kV
12.6" leakage
*Catalog No.
TP7101MMPB
MountingAssembly only
*Base
CatalogNo.
CP710112CP710114CP710143CP710133
Universal Cutout ToolIdeal or Standard and Linkbreak 100 amp useholders (ABB, Chance S&C) to easily lit out, place,*open and close. Inverted, secure method also tsChance Electronic Sectionalizers.Cat. No. PSC4033484 (Wt. 4 oz.) See Tools Catalog Section 2100.*When opening a cutout, follow all work rules and OSHA regula-tions. Not for use with Loadbreak cutouts.
-
7/30/2019 10AA
6/12
0AA-6
CHANCE CENTRALIA, MISSOURIJULY 2010 HUBBELL
Power Systems
15 kV - 110 kV LIW (BIL)
15/27 kV - 125 kV LIW (BIL)
A sharp downward pull on the lever with a hookstickbreaks the fuselink. (15/27 kV product shown here)
Application
The Type C-Polymer 100 amp Linkbreak cutout provides shortcircuit protection to utility lines with the added eature omechanical linkbreak capability in a loadbreaking unction.Linkbreak cutouts provide reliable protection rom overloadsthat just melt the uselink through the maximum interruptcapacity o the useholder and also provide inductive andcapacitive loadbreak capability. For loadbreak ratings seechart, next page.
The unit will also accept the Type C-Polymer 200 amp non-loadbreak useholder or a 300 amp disconnect blade. EachLinkbreak cutout includes standard loadbreak hooks to usewith portable loadbreak tools. This method is particularlyuseul or switching o the 200 amp useholder and 300 ampdisconnect blade.
Design / Product FeaturesConstruction and product details shown on page 10AA-3 ap-ply to the Linkbreak cutout except that the link-ejector onthe linkbreak useholder is a copper-alloy casting instead oa stainless-steel stamping.
The unit utilizes a stainless-steel linkbreak lever to me-chanically break uselink elements thereby obtaining loadinterruption within the useholder. The Type C-PolymerLinkbreak useholder is not designed to be interchangeablewith any other manuacturers cutout.
All standard non-loadbreak useholders and the linkbreakuseholders are interchangeable and t into both the non-
loadbreak and Type C-Polymer or Porcelain Linkbreak cutoutmounting assemblies. Mounting assemblies are the same asthose or Type C-Polymer or Porcelain STANDARD cutouts,shown on page 10AA-5.
Ratings / Specifcations
The 15 kV Type C-Polymer Linkbreak cutout has a maximumdesign voltage rating o 15 kV. There are no voltage restric-tions on application to grounded wye, ungrounded wye, ordelta systems having maximum operating voltages (line toline) equal to or less than the cutout maximum design volt-age rating.
The 15/27kV Type C-Polymer LINKBREAK cutout hasmaximum design slant voltage ratings. These cutouts are tobe used on systems which have phase-to-ground voltages nogreater than the value listed to the let o the slant (/) and
which have phase-to-phase voltages no greater than the valuelisted to the right o the slant.
The Type C-Polymer Linkbreak cutout is to be used withuselinks requiring 1 inch or less elongation beore break-ing. Fuselinks requiring more than 1 inch elongation beorebreaking must not be used with the Type C-Polymer Link-break cutout.
Type C-Polymer
LINKBREAK Cutout
(15 kV product shown here)
-
7/30/2019 10AA
7/12
10A
HUBBELL
Power SystemsCHANCE CENTRALIA, MISSOURI
JULY 2010
125 kV LIW (BIL)
Type C-Polymer100-Amp LINKBREAK Cutout
LINKBREAK Cutout with NEMA Type B Bracket
LIW (BIL)kV
110
125
CapacitiveAmperes
100100100100
*See specications and ordering inormation below.Limited to grounded-wye systems with grounded-wye loads.
InductiveAmperes
100100100100
kV,Nominal
System Voltage
14.414.424.924.9
*Base CutoutCatalogNumber
CP720112CP720114CP720211
CP720213
Loadbreak Ratings
Dimensions
lb.2.52.72.72.9
kg.1.131.221.221.32
WeightFuseholderCatalog No.T720112TT720114TT720211TT720213T
Cutout BaseCatalog Number
CP720112CP720114CP720211CP720213
kV& LIW (BIL)
15 kV110 kV BIL
15/27 kV125 kV BIL
*Mounting assemblies are same as STANDARD cutouts, on 10AA-5.
*Fuseholders (100 Amp only)
110 kV LIW (BIL)product is depicted.125 kV LIW (BIL) product varies
slightly in appearance.
For application on single-phase to neutral circuits with phase-to-ground voltages not exceeding the value to the let o the slant; and or application on three-phase solidly-grounded-wye systems with solidly-grounded loads with line-to-line voltages not exceeding the value to the right o the slant.
Must use removable buttonhead use links. *Adjust total weight when selecting Options below.
Specifcations and Ordering InormationAll Type C Cutouts meet or exceed ANSI/NEMA specifcations.15 kV - 110 kV LIW (BIL) RUS LISTED
15/27 kV - 125 kV LIW (BIL)
Sufx1
PEL
Description
Parallel-groove clampsSmall eyeboltsLarge eyebolts
Must specify one selection for Option 1.
*Option Sufx 1Terminal Variations
MaximumDesignVoltage15 kV15 kV
NominalSystem Voltage
Thru 14.4 kVThru 14.4 kV
319 mm319 mm
ArcShortening
Rod
NoYes
ContinuousCurrent(Amps)
100100
12.6"12.6"
Leakage to GroundMetal to Metal
InterruptCapacity
(Asym Amps)10,00016,000
See page 10AA-11 or Accessories.
*Weight(lb./kg.)
10.2/4.610.3/4.7
ReplacementFusetube
Cap
P7001469PE7001784P
434 mm434 mm P7001469PE7001785P15/27 kV15/27 kV NoYes100100 8,00012,000
No Restrictions
thru 14.9 kV; 20.8thru 24.9 kV
17.1"17.1" 11.4/5.211.5/5.2
*Option Sufx 2Bracket Variations
*Optionsufxesbelow
1 2 31 2 3
1 2 31 2 3
*Weight(lb./kg.)
0.33/0.150.16 /0.070.31/0.14
*Weight(lb./kg.)
2.84/1.29
3.75/1.70
7.67/3.48
Sufx2
B
X
DZ
Blank
Description
110 kV LIW (BIL)
F167/16"417
mm157/8"403mm
A1515/16"
405
mm167/8"418mm
B415/16"125
mm69/16"167mm
C115/8"295
mm131/4"337mm
D31/4"82
mm27/8"72
mm
E221/8"561
mm271/4"692mm
*BaseCatalog
No.CP720112CP720114
CP720211CP720213
NEMA Heavy Duty B bracketor crossarm (11/2" bolt)Extended type bracket or cros-sarm (Horizontal sectionis 25/8" longer than Type Bbracket)
D-shape bracket (pole)No bracket (must be used withM in Option 3)No bracket (cannot use with Min Option 3)
No option (may not beused with Z in Option 2)Mechanical Assist Fuse-holder (may not be usedwith Blank in Option 2)
Fargo cutout cover(available or 15 kVonly) (may not be usedwith Blank in Option 2)
*Option Sufx 3Mechanical Assist
Fuseholder
Sufx3
Blank
M
F
Description
-
7/30/2019 10AA
8/12
0AA-8
CHANCE CENTRALIA, MISSOURIJULY 2010 HUBBELL
Power Systems
B
63/8"162 mm
713/16"199 mm
C
115/8"295 mm
131/4"337 mm
A
2413/16"630 mm
273/4"704 mm
D
31/4"82 mm
27/8"72 mm
E
265/16"668 mm
317/16"798 mm
kV LIW(BIL)
110
125
Dimensions
Application
The Type C-Polymer Loadbreak Cutout is available orapplication on 15 and 27 kV distribution systems. The ad-dition o the arc chute expands the fexibility o the Chanceprotective devices amily by providing loadbreak capabilityor cutouts and disconnect solid blade units. The loadbreakcutout provides short circuit protection to utility lines withthe added eature o a loadbreaking unction.
The loadbreak cutout is applicable or transormer andcapacitor bank switching or line sectionalizing. Loadbreakcutouts provide protection rom overloads that just melt theuselink through the maximum interrupt capacity o theuseholder. They also provide loadbreak capability through300 amperes.
Design
All design eatures and most components o the loadbreakunit are identical to those incorporated in the Type C-Poly-mer standard cutout. The loadbreak portion o the TypeC-Polymer Loadbreak cutout is a heavy duty, reliable loadinterrupter that provides a positive visible loadbreak. A com-mon loadbreak mounting assembly will accept the ChanceType C-Polymer 100 amp and 200 amp loadbreak useholdersor a 300 amp loadbreak disconnect blade.
Ratings/Specifcations
The 15kV Type C-Polymer loadbreak cutout has a maximumdesign voltage rating o 15kV. There are no voltage restric-tions on applicaton to grounded wye, ungrounded wye, ordelta systems having maximum operating voltages (line toline) equal to or less than the cutout maximum design volt-age rating.
The 15/27 and 20/34.5 kV Type C loadbreak cutouts havemaximum design slant voltage ratings. These cutouts areto be used on systems which have phase-to-ground voltages
Type C-Polymer
LOADBREAK Cutout with Arc Chute Interrupter
110 kV LIW (BIL) product isdepicted.125 kV LIW (BIL) product variesslightly in appearance.
no greater than the value listed to the let o the slant (/)and which have phase-to-phase voltages no greater than the
value listed to the right o the slant.
Fuseholders and mounting assemblies rom other manu-acturers' loadbreak cutouts are not interchangeable withChance loadbreak cutouts. Likewise, Chance useholdersand mountings are not interchangeable with other manu-acturers' loadbreak cutouts.
OperationThe sel-contained loadbreak device enables the lineman tointerrupt load current by means o a simple hookstick opera-tion. To break the current, the lineman inserts a hookstickinto the operating ring and rapidly opens the device. Uponopening, a spring-loaded stainless steel blade mechanismsnaps out through a gray arc chute and elongates, cools andextinguishes the conned arc. The loadbreaking operationis independent o the operating speed o the lineman. Theuse remains undamaged. No special or portable tools arerequired to operate the unit. In the open position, the use-holder or blade hangs in an approximate vertical positionor the visible-break.
-
7/30/2019 10AA
9/12
10A
HUBBELL
Power SystemsCHANCE CENTRALIA, MISSOURI
JULY 2010
300A
Blade
*Adjust total weight when selecting Option suxes above.
Extra corrosion resistance:Not Available*Adjust total weight when selecting Options below. **Momentary rating Solid blade Must use removable buttonhead use links.For application on single-phase to neutral circuits with phase-to-ground voltages not exceeding the value to the let o the slant; and or application on three-phase solidly-grounded-wye systems with solidly-grounded loads with line-to-line voltages not exceeding the value to the right o the slant.
Specifcations and Ordering InormationAll Type C Cutouts meet or exceed ANSI/NEMA specifcations.
Type C-Polymer LOADBREAK Cutout
3.3 lb.3.5 lb.4.1 lb.3.6 lb.
Base CutoutCatalogNumber
CP730112CP730114CP730143CP730133
1.5 kg.1.6 kg.1.9 kg.1.6 kg.
15 kV - 110 kV LIW (BIL) MountingAssembly only
*Base Catalog No.
TP7301MM
Fuseholder orBlade onlyCatalog No.T730112TT730114TT730143TT730133T
4.5 kg.10.0 lb.
Weight Weight
Fuseholders and Mounting Assemblies
3.6 lb.3.8 lb.4.4 lb.4.0 lb.
5.0 kg.11.1 lb.TP7302MM
1.6 kg.1.7 kg.2.0 kg.1.8 kg.
T730211TT730213TT730242TT730233T
15/27 kV - 125 kV LIW (BIL)CP730211CP730213CP730242CP730233
15 kV - 110 kV LIW (BIL) RUS LISTED
15/27 kV - 125 kV LIW (BIL)CP730211CP730213CP730242CP730233
100AFuseholders
*Option Sufx 1Terminal Variations
Sufx1
PEL
Parallel-groove clampsSmall eyeboltsLarge eyebolts
Must specify one selection for Option 1.
See page 10AA-11 or Accessories.
MaximumDesignVoltage
15 kV15 kV15 kV15 kV
NominalSystem VoltageThru 14.4 kVThru 14.4 kVThru 14.4 kVThru 14.4 kV
319 mm319 mm319 mm319 mm
ArcShortening
Rod
NoYes
Yes
N/A
ContinuousCurrent(Amps)
100100200300
12.6"12.6"12.6"12.6"
Leakage to GroundMetal to Metal
InterruptCapacity
(Asym Amps)10,00016,00012,00012,000**
*Weight(lb./kg.)
15.1/6.815.2/6.915.8/7.215.4/7.0
ReplacementFusetube
CapP7001535PE7001767PE7002146PP7001535P
434 mm434 mm434 mm434 mm
P7001535PE7001768PE7002479PP7001535P
15/27 kV15/27 kV15/27 kV15/27 kV
NoYes
Yes
N/A
100100200300
8,00012,00010,00012,000**
17.1"17.1"17.1"17.1"
15.5/7.015.6/7.116.2/7.415.8/7.2
*Optionsufxesbelow
1 2 31 2 31 2 31 2 3
1 2 31 2 31 2 31 2 3
No Restrictions
thru 14.4 kV;20.8 thru 24.9 kV
15/27 kV
TP7302MMPB
300A
Blade200A
Fuseholders100A
200A
*Option Sufx 2Bracket Variations
*Option Sufx 3Mechanical Assist
Fuseholder*Weight(lb./kg.)
0.33/0.150.16/0.070.31/0.14
DescriptionSufx
3
Blank
M
Description
No option (may not beused with Z in Option2)Mechanical AssistFuseholder (may notbe used with Blank inOption 2)
*Weight(lb./kg.)
2.84/1.29
3.75/1.70
7.67/3.48
Sufx2
B
X
DZ
Blank
Description
NEMA Heavy Duty B bracketor crossarm (11/2" bolt)Extended type bracket or cros-sarm (Horizontal sectionis 25/8" longer than Type Bbracket)D-shape bracket (pole)No bracket (must be used withM in Option 3)No bracket (cannot use with Min Option 3)
Replacement Arc
Chute InterrupterCat. No. T7300080
(1.2 lb. / 0.54 kg.)
*BaseCatalog
No.
CP730112CP730114CP730143CP730133
15 kVCat. No. TP7301MMPBMountingAssembly only
-
7/30/2019 10AA
10/12
0AA-10
CHANCE CENTRALIA, MISSOURIJULY 2010 HUBBELL
Power Systems
Direct
Direct
Direct
Small BlockNormal Duty
5 kA
Large BlockHeavy Duty
10 kA
RiserPole
OhioBrass
9
DL
EL
FL
10
DM
EM
FM
110
Polymer
Metal Oxide Varister
(MOV)
OperatingDesign
Housing
kV LIW (BIL)
or Cutout
kV RatingMCOVDuty
Cycle
kVRating
ArresterMa
nufacturer
Arrester
Connection
Method
Type C-PolymerCutout-Arrester Combinations
15 kV cutout with direct-connected Ohio Brass MOV,
polymer 9 kV lightning arrester
Advantages o combinationThe total installed cost o a Hubbell cutout-arrester com-bination is less than the total installed cost o separatelypurchased components. The combination units install aster,more economically and take up less space in storage, transitand service. Each combined unit takes up a minimum o spaceon the crossarm and has a avorable weight distribution orminimal o-center loading. The eld-proven quality o both
Over-the-Arm Type onlyCutout-Arrester
Dimensions
cutout and arrester assure consistent high perormance orthe combinations.
These units include Chance cutouts tted with only OhioBrassMOV arresters, superseding previous silicon-carbideunits. For easy conversion to the new arrester designationsystem, reer to the Cutout Cross-Reerence Guide, Bulletin10-0203.
For other dimensions see STANDARD Cutout, page 4.
18
DN
EN
FN
125
110 kV LIW (BIL) product is depicted.125 kV LIW (BIL) product varies slightly in appearance.
Ordering InormationTo speciy a Cutout-Arrester Combination:
1. Select a two-letter designation or the appropriate arresterrom the shaded section o the Table at let.
2. Substitute the two letters or the 0 in the Base CatalogNo. or the appropriate Cutout listed on page 5, 7 or 9.
G
245/16" (617 mm)
257/8" (657 mm)
E
207/8" (531 mm)
261/4" (667 mm)
kV LIW (BIL)110
125
-
7/30/2019 10AA
11/12
10A
HUBBELL
Power SystemsCHANCE CENTRALIA, MISSOURI
JULY 2010
Type C-Polymer CutoutsAccessories
Catalog No.T7001325T7001326T7001327
Terminal Connectors
Min. Order Qty.
101010
Description
Parallel-Groove Clamp, tin-plated bronze or No. 6 solid thru 4/0 ACSR or 250 kcmil strandedSmall Eyebolt or No. 8 solid thru 2/0 strandedLarge Eyebolt or No. 6 solid thru 4/0 ACSR or 250 kcmil stranded
C2060283C2060280C2060299C2060632
Mounting Brackets
NEMA Heavy Duty B Bracket with 11/2" captive bolt or crossarm mountingExtended Crossarm Bracket (Horizontal section is 25/8" longer than NEMA B bracket)D Pole Mounting BracketCutout/Arrester Bracket complete with carriage bolts and backstrap
Mounting Bracket Dimensions
Wt. (lb./kg.)0.33 / 0.150.16 / 0.070.40 / 0.14
2.84 / 1.293.75 / 1.707.67 / 3.484.00 / 1.81
Universal Cutout Tool
Ideal or Standard and Linkbreak 100 amp use holders (ABB,Chance, S&C) to easily lit out, place, *open and close. Inverted,
secure method also ts Chance Electronic Sectionalizers.
Cat. No. PSC4033484 (Wt. 4 oz.) See Tools Catalog Section 2100.*When opening a cutout, follow all work rules and OSHA regula-tions. Not for use with Loadbreak cutouts.
Fargo Cutout Cover
ONE PIECE WILDLIFE PROTECTOR
Available as an Option on Standard and Linkbreak Type C-Polymer Cutouts(see pages 10AA-5 and 10AA-7), Cover also may be ordered as a separate lineitem as Catalog No. CC101. Material: Proprietary low track vinyl that is UV
stabilized or long-term perormance. Gray color.
Designed to provide protection for cutouts from accidental contact by squir-rels, birds or other wildlie.
Universal one-piece design for easy installation or retrot. Fits Chance 15 kVStandard and Linkbreak Cutouts, both Polymer and Porcelain types.
Fastener installation locations(2 asteners per assembly)
-
7/30/2019 10AA
12/12
0AA-12
CHANCE CENTRALIA MISSOURI HUBBELL
Web: http://www.hubbellpowersystems.comE-mail: [email protected]
MEXICO
HUBBELL DE MEXICO, S.A. DE C.V.Av. Insurgentes Sur #1228, Piso 8Col. Tlacoquemacatl Del Valle
Mexico, D.F. 03200Phone: 52-55-9151-9999Fax: 52-55-9151-9988Website: hubbell.com.mx
UNITED STATES