1073380000 BT PB_EN_1.3_08.09

97
SAI Active Universal for Bluetooth Manual

Transcript of 1073380000 BT PB_EN_1.3_08.09

SAI Active Universal for Bluetooth

Manual

Weidmüller t

Bluetooth SAI Manual

2 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

Contents 1. The SAIs 4 1.1. SAI 5 1.2. PROFIBUS-DP 6 1.3. Bluetooth 7 2. Project Planning and SAIs 8 2.1. Project planning 9 2.2. Power supply 10 3. Mounting the SAIs 11 3.1. Mounting dimensions and position 12 3.2. Mounting SAI distributors 13 3.3. Marking and labelling 14 3.4. Setting the PROFIBUS address 15 3.5. Setting the Bluetooth address 17 3.6. Dismounting the SAI 18 4. Connecting the SAI Distributor 19 4.1. PROFIBUS / RS-485 20 4.2. SAI-AU M12 GW PB/BT 12I 22 4.3. SAI-AU M12 BT 16DI 28 4.4. SAI-AU M12 BT 16DI/8DO 34 4.5. SAI-AU M12 BT 4AI2AO2DIO 42 5. Initial Commissioning 50 5.1. Device Data Base Files (GSD) and bitmap files 51 5.2. Copy the GSD files to the local directory 52 5.3. Install the GSD files in Step7 53 5.4. Adding a BT-GW in the hardware configurator 55 5.5. Assigning the input and output addresses 57 5.6. Configuration and setting parameters 58 5.7. SAI parameter data 59 6. Diagnosis 63 6.1. LED displays 64 6.2. Diagnostic telegrams 67 6.3. Evaluating diagnostic data in Step7 76 Appendix A: Product Overview 78 Appendix B: Drilling Templates 81 Appendix C: Converting from Hexadecimal to Decimal 82 Appendix D: Configuration of the DESINA inputs 83 Appendix E: Configuration of the digital connection points 84 Appendix G: Configuration of analogue outputs 85 Sources 86 Index 87 Glossary 90

1073380000/1.3/08.09 Weidmüller t 3

Bluetooth SAI Manual

1. The SAIs

The SAIs

1.1 SAI

4

1.2 PROFIBUS-DP

6

1.3. Bluetooth

7

This chapters explains • the characteristics and operating

principle of SAIs • PROFIBUS-DP and its master/

slave structure • the Bluetooth subsystem

4 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

1073380000/1.3/08.09 Weidmüller t 5

1.1. SAI

The SAI consists of the following components: The acronym SAI stands for Sensor Actuator Interface. It is a compact-designed distributor and collector of signal lines.

• An I/O section: to connect the signal lines. • A settings section:

to set the network addresses and insert the jump-ers for the different electric potentials.

Signals to and from the process in field installations are often controlled from a central point, for example, by a PLC or industrial PC. Typically, the distance between the installation and the central controls is significant. The resulting costs for installation and materials for the cabling are high. This in turn increases the susceptibility of the system to interference and errors.

• A bus / power section: for the connection and loop through for the supply voltage as well as the bus connection.

Weidmüller offers the following I/O versions: • M12 16DI with 16 digital inputs.

• M12 16DI / 8DO with 8 fixed digital inputs and 8 individually configurable inputs or outputs. The use of SAIs has proven successful under numer-

ous conditions: • The signal lines of the peripheral devices are bun-

dled together at the process in the installation and connected to a bus.

In addition, Weidmüller also offers: • Network components for the Fieldbus systems

mentioned above • Signal lines are connected simply and conveniently by means of Plug and Play. • Sensor / valve connector cables

• The controls are at a central point • Plug-in connectors and twin-plugs • The reliability of the data transfer is guaranteed by

a bus system. • Tools

I/O section

Settings section

Bus / power section

Figure 1: Basic design of an SAI distributor

Bluetooth SAI Manual

1.2. PROFIBUS-DP

PROFIBUS PROFIBUS (PROcess Field BUS) is a part of the in-ternational IEC 61158 and IEC 61784 standards. Physically, PROFIBUS is either an electrical network based on a shielded, two-conductor cable or an optical network based on a fibre optics cable. PROFIBUS-DP (DP = Decentralised Periphery) is a special application for automating factory production. System A typical PROFIBUS-DP system is made up of: • At least one PLC or industrial PC (master) operat-

ing as a control system. • Various field devices, such as digital or analogue

I/O devices, AC or DC drives, magnetic or pneu-matic valves, frequency converters, starters, oper-ating and indicating devices (slaves).

Data transfer Data exchange within the system is carried out by means of cyclic polling. The master establishes com-munications with one slave at a time and makes data available and/or requests data. The slave being ad-dressed responds immediately to the request for data. Once completed, this procedure is repeated with the other slave devices. This is a continuous cyclic process.

GSD files (device database files) The GSD file is the obligatory ‘ID card’ of each and every PROFIBUS device. It contains the characteristic data of the device, details about its communication capabilities as well as other information, such as diag-nostic values. Weidmüller has made available for downloading all GSD files of the SAI distributors from the SAI Active Universal series – at: http://www.weidmueller.com. For more information, please refer to Chapter 5 (Com-missioning).

Figure 2: Basic PROFIBUS system configuration

6 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

1.3. Bluetooth

Bluetooth Bluetooth defines a universal wireless interface in the 2.4 GHz ISM band. No license is required for the 2.4 GHz ISM band. Users are not required to register or pay usage fees. The acronym ISM stands for Industrial Scientific Medi-cal and describes the potential scope of its use. A range between 10 metres to 100 metres is defined because of Bluetooth's minimal transmitting power of a few milliwatts. System A Bluetooth system consists of a maximum of 255 nodes. From these however, only 8 can be simultane-ously connected to each other.

The Weidmüller Bluetooth SAIs are formed from Picon-ets consisting of one master and six slaves. Thirty-two of these Piconets can be operated in parallel. The Bluetooth master, which functions as the PROFIBUS gateways, is simultaneously a slave in the PROFIBUS system. The PROFIBUS master views it as a standard PROFIBUS slave with a modular I/O con-figuration. The Bluetooth gateway can be configured with a GSD file. Protocol The standard Bluetooth profile is used. The communi-cation protocol then uses this. The implementation is based on the CANopen / WIRELESSopen standards.

Figure 3: Basic PROFIBUS system configuration with subordinate Bluetooth

Slave (1) Slave (6)

Bluetooth SAIs

Gateway

PLC

PROFIBUS

1073380000/1.3/08.09 Weidmüller t 7

Bluetooth SAI Manual

2. Project Planning and SAIs

Project Planning and SAIs

2.1 Project planning

9

2.2 Power supply

10

8 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

2.1. Project planning

Planning the bus system The following steps must be taken into consideration when designing an installation: • Location of the machine or facility • Assignment of the signals to the installation to a logical group • Selection of the field devices • Assignment of the signals to the field devices • Determination of where the field devices are to be installed Criteria for determining the correct SAI distributor: Size of the connec-tors

Determine the size of the connectors to suit your application, the design of the sen-sors or according to your personal preferences. Weidmüller offers both M12 and M8 variants for purely digital signals

Number of poles of the I/O connections

Please consider the sensor/actuator cable to be connected; possible options are 3 or 5 poles

Y-piece (twin) Specifically for 5-pole M12 sensor connections, you can feed two cables to a dis-tributor input by means of a Y-piece.

Inputs / outputs Weidmüller has a variety of SAI distributors on offer such as a variant with 16 digital inputs, with mixed digital inputs/outputs as well as an analogue/digital version (for more information please refer to Chapter 4 (Connecting SAIs).

Shielding Shielding by means of metal connectors is necessary for bus connections. We rec-ommend the same approach for analogue signals to restrict the susceptibility to interference.

Signals Please consider if you wish to transmit analogue or digital signals.

Table 1: Determining the SAI distributor

For more information, please refer to Appendix A: Overview of articles to determine correct selection of products.

1073380000/1.3/08.09 Weidmüller t 9

Bluetooth SAI Manual

10 Weidmüller t 1073380000/1.3/08.09

2.2. Power supply

Example calculation to determine voltage drop in the lines:

Star or line topology wiring can be used to feed the power supply. Only modules without digital outputs are suitable for line topology wiring.

Power is supplied via the plug in connection AUX IN; power is fed to the next module via the module connec-tion AUX OUT.

Caution

The maximum current supplied to the first module must not exceed 2.5 A per power supply pin. The supply voltage at the last module must not fall below 18 V DC.

When determining the maximum number of modules in series you should take into con-sideration the total current of all modules and the voltage drop in the line.

Figure 4: Voltage drop

Voltage drop to module 1 (line resistance x length of line L1 x 2) x current con-sumption (Module 1 + Module 2+ Module 3) Voltage drop from module 1 to module 2 (line resistance x length of line L2 x 2) x current con-sumption

Voltage drop in the lines: (Line resistance) x (total length of line) x (2)

(Module 2 + Module 3) Voltage drop from module 2 to module 3 Total current of the modules: (line resistance x length of line L3 x 2) x current con-sumption

Power consumption modules + total current of the con-sumers

(Module 3) Supply voltage to module 3 Input voltage – voltage drop 1 – voltage drop 2 – voltage drop 3 Important: The power supply to module 3 must be equal to or greater than 18 V DC. Calculation: Max. current load per pin –> max. number of input modules L1 L2 L3

Bluetooth SAI Manual

3. Mounting the SAIs

Mounting the SAIs

3.1 Mounting dimensions and position

12

3.2 Mounting SAI distributors

13

3.3 Labelling

14

3.4 Setting the PROFIBUS address

15

3.5 Setting the Bluetooth address

17

3.6 SAI disassembly

18

1073380000/1.3/08.09 Weidmüller t 11

Bluetooth SAI Manual

12 Weidmüller t 1073380000/1.3/08.09

3.1. Mounting dimensions and position

Note

Please observe that a given distance to the adjacent module may be required when using custom assembly and angled connec-tors.

An SAI distributor can be mounted in any position. There are no restrictions placed with regard to their position when being mounted: vertical, horizontal, on their side, or overhead. However, to ensure that the LEDs can be seen, we recommend that – where possi-ble – the modules are not mounted on their side or overhead. Our SAIs can be mounted side by side. The mounting dimensions of our SAI distributors are 210 x 54 mm.

You can find details about the mounting di-mensions in Appendix B: Drilling Templates.

Figure 5: Mounting dimensions for the SAI Active Uni-

versal

Bluetooth SAI Manual

3.2. Mounting SAI distributors

Mounting To mount the SAI distributor, select a firm and level surface. Pre-drill the bore holes (for more information, please refer to Appendix B: Drilling Template). Hold the distributor above the bore holes and fix it in positions with screws. Please use a spring washer if the SAI distributor is to be used in an environment where the loads are subject to increased shock and vibration. Please refer to Figure 5: Mounting dimensions for the SAI Active Universal. PROFIBUS guidelines Please observe the PROFIBUS guidelines: Installation Guideline for PROFIBUS-DP/FMS.

Figure 6: Mounting an SAI distributor

DANGER

Isolate (de-energize) the system before con-necting the power-supply connector or insert-ing or removing jumpers.

Torque We recommend the following torques: M8 connector: 0.6 Nm M8 protective cap: 0.4 Nm M12 connector: 0.8 Nm M12 protective cap: 0.8 Nm Screw for window: 0.5 Nm

Functional earth (FE) The functional earth is the earthing (ground) of equip-ment to its surroundings. Contrary to the protective earth (PE) the FE does not primarily serve to protect equipment or persons, but instead serves to discharge electrostatic charges and shield connections.

Caution

Electromagnetic pulses affect cabling and the distributor during operations. Flawed signals and false data can result. Do not use a PE conductor for the FE con-nection.

SAI distributors from the SAI Active Universal series are equipped with an FE connection integrated at the mounting hole in the bus/power section. Use this con-nection and fix the distributor directly to a conductive surface or attach a short, low impedance FE cable to the fixing screw by means of a cable lug. Please refer to Figure 6: Mounting an SAI distributor.

Figure 7: Functional earth ‘FE’ connection

Required accessories / DIN components 2 socket-head cap screws, M4 x 30 We recommend cylinder head studs with hexagon-socket or Torx type. Tools Allen key or Torx screwdriver appropriate to the screw you choose. For more information, please refer to Ap-pendix A: Overview of items - Recommended tools.

1073380000/1.3/08.09 Weidmüller t 13

Bluetooth SAI Manual

3.3. Marking and labelling

Twenty transparent markers in a MultiCard frame are included in the range of supply of the SAI distributors. These allow you to individually mark the I/O connections as well as the distributor. Either two normal or one longer marker can be used to specifically mark the distributor. Please refer to the following graphic Figure 8: Attaching the markers. Weidmüller has various printers and plotters available to achieve professional printing results. For advice and a demon-stration, please contact your Weidmüller partner.

To achieve rapid, manual on-site marking results, we recommend our STI-S fibre pen (please refer to Appendix A: Overview of items).

Figure 8: Attaching markers and tags

Note

Please note that you should not stick marker tags on top of one another. Nor should you use coloured markers since they can cover up the LEDs below them.

14 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

3.4. Setting the PROFIBUS address

PROFIBUS address The PROFIBUS address is used to determine at which address your SAI distributor will be identified on PROFIBUS-DP. Setting Set the PROFIBUS-DP address for the SAI distributor in the settings section of the distributor. Use a flat-bladed screwdriver to adjust the rotary switch. Tools Use a 2.5-mm flat-bladed screwdriver (please refer to Appendix A: Overview of items). Address / hexadecimal code Please note that PROFIBUS-DP allows a maximum of 126 possible addresses. The addresses 1 to 125 are defined. Please note that the address 126 is used for configuration purposes and the addresses 01 and 02 are retained for the PROFIBUS master. The distributor address is set in hexadecimal code by means of two rotary coding switches. To do so, you will have to con-vert the decimal address to hexadecimal or, for the sake of simplicity, you could make use of the table below.

Example: To set the PROFIBUS-DP address 93, turn the left-hand rotary coding switch to position 5 and the right-hand rotary coding switch to position D.

Note

Each address must be allocated only once on PROFIBUS-DP. The PROFIBUS address that you set must match the PROFIBUS address for this distributor set in the project configuration software. If you alter a PROFIBUS address during operations you will have to disconnect the power supply and then restart the system to enable the master to recognise the change.

Table 2: Code conversion decimal < - > hexadecimal

1073380000/1.3/08.09 Weidmüller t 15

Bluetooth SAI Manual

- Master:

The rotary switches are used for setting the Profibus address network. The switches are used for setting the Bluetooth network. Set the rotary switch to position 1. The sliding switch is used to define which networks are to be set. Slide the switch to position 1 in order to set the first 16 networks. Slide the switch to position ON in order to set the next 16 networks (17 – 31). - Slave:

The first rotary switch is used to set the slave's node address. The second rotary switch is used for setting the Bluetooth network. Set the rotary switch to position 1. The connection will be established within about 40 seconds. Tools Use a 2.5-mm flat-bladed screwdriver (please refer to Appendix A: Overview of items). Address / hexadecimal code

The distributor address is set in hexadecimal code by means of two (or three) rotary coding switches. To do so, you will have to convert the decimal address to hexadecimal or, for the sake of simplicity, you could make use of Table 2.

16 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

3.5. Setting the Bluetooth address

Note

Each Bluetooth address can occur only once with a Piconet. The defined network address must be identical with a network. If you alter a Bluetooth address during op-erations you will have to disconnect the power supply and then restart the system to enable the master to recognise the change.

Bluetooth address The Bluetooth address is used to determine at which address your SAI distributor will be identified from the Bluetooth master. The Bluetooth address consists of a node address and a network address. Slave address The slave address defines the location (address) of the participant within the Piconet. Each slave address can occur only once within a Piconet. The Bluetooth gate-way always uses the node address 0; this cannot be adjusted. Network address The network address defines the Piconet which the SAI should be connected to. The settings on the SAI and the Piconet gateway must be identical.

Setting Set the address for the SAI distributor in the settings section of the distributor. Use a flat-bladed screwdriver to adjust the rotary switch.

1073380000/1.3/08.09 Weidmüller t 17

Bluetooth SAI Manual

3.6. Dismounting the SAI

DANGER

Never plug in or pull out a power connector or jumpers when the system is live (ener-gized). Turn off the power supply to the sys-tem first.

Caution

No immediate damage will occur to the de-vice if you dismount an SAI distributor when the system is operating. However, the disruption to PROFIBUS will place the rest of the plant in an uncontrolled state. This can lead to indirect damage. Disconnect the power to the system before you mount or take off the distributor.

Dismounting • Turn off the power supply to the system. • Disconnect the connections to the power supply on

the SAI distributor. • Disconnect the PROFIBUS connections on the SAI

distributor. • Disconnect the I/O connections. • Dismount the distributor by undoing the mounting

screws. Tools Use an Allen key or Torx screwdriver appropriate to the screw you choose. For more information, please refer to Appendix A: Overview of items - Recommended tools.

18 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

4. Connecting the SAI Distributor

Connecting the SAI Distributor

4.1 PROFIBUS / RS-485

20

4.2 SAI SAI-AU M12 GW PB/BT 12I

22

4.3 SAI SAI-AU M12 BT 16DI

28

4.4 SAI SAI-AU M12 BT 16 DI/8DO

34

4.4 SAI SAI-AU M12 BT 4AI2AO2DIO

42

1071640000/1.3/08.09 Weidmüller t 19

Bluetooth SAI Manual

4.1. PROFIBUS / RS-485

PROFIBUS is a universal, open, digital communication system providing solutions for a wide spectrum of appli-cations – first and foremost in production and process automation. PROFIBUS is a suitable solution for fast, time-critical applications, as well as for complex com-munications tasks. PROFIBUS communication is an-chored in the international standards IEC 61158 and IEC 61784.61158. The criteria for its use and planning are defined in the openly accessible guidelines available from the PROFIBUS User’s Organisation (PUO). These guide-lines fulfil the demands on the part of the users for multi-vendor and open solutions. That guarantees the communication between devices of differing manufac-tures – without having to make prior adjustments. Additional information is available under www.profibus.com. Connection The following section pertains only to the SAI-AU M12 GW PB/BT 12I Bluetooth gateway. Module connection from BUS IN Contact system M12 male connector, 5-pole Coding B Pin assignment Pin 1: +5 V DC

Pin 2: Data A (green wire) connected with BUS-OUT Pin 2

Pin 3: GND Pin 4: Data B (red wire)

connected with BUS-OUT Pin 4

Pin 5: Shield

Table 3: Contact assignment (pin out) of the PROFIBUS connector

Select the bus cable as cable type A in accordance with IEC 61158. The PROFIBUS connection is made via a 5-pole M12 male connector (Bus IN) and a 5-pole M12 female connector (Bus OUT). Both connections are B-coded. Use the "Bus In" connection to feed in signals and "Bus Out" to route these forward. In the SAI, male and female connectors are conduc-tively connected. That enables the PROFIBUS to be routed from SAI to SAI without the need for spur lines.

Note

It is possible to connect the SAI distributors by means of a spur line for low transmission rates up to 1500 Kbit/s. The total length of the spur line must not exceed 6.6 meters. The spur lines should be kept as short as possible. Avoid the use of spur lines for baud rates greater than 1500 Kbit/s.

Module connection from Bus OUT Contact system M12 female connector, 5-pole Coding B Pin assignment Pin 1: +5 V DC

Pin 2: Data A (green wire) connected with BUS-OUT Pin 2

Pin 3: GND Pin 4: Data B (red wire)

connected with BUS-OUT Pin 4

Pin 5: Shield

Table 4: Contact assignment (pin out) of the PROFIBUS female contact socket

20 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

Bus termination A reference voltage of 5 V DC is applied to both bus connections. This voltage is isolated from the internal system voltage and is applied exclusively to supply an external bus connection with power. Install the termina-tions at the physical beginning and end according to the PROFIBUS standard EN 50170 using the following values:

Figure 9: Bus termination wiring

Accessories: Terminating resistor connector, PROFIBUS-DP in M12 connector Type: SAIEND PM M12 5P B-COD QTY.: 1 Order No.: 1784770000 Setting the transmission rate The SAI recognises and adopts the transmission speed which is being used on the bus. Any change to the transmission speed on the bus will also be recognised and adopted. SAI distributors support all conventional baud rates.

Technical specifications

Fieldbus interface PROFIBUS-DP V0 according to DIN EN 61158 certified by the PUO

Protocol PROFIBUS IEC 61158

GSD file (Device Data Base File)

Device-specific for each mod-ule

Transmission RS485

Transmission me-dium

Twisted pair

Separation of poten-tials

Yes, to module electronics

Dielectric strength 500 V DC

Baud rates 9.6, 19.2, 45.45, 93.75, 187.5, 500, 1500, 3000, 6000, 12000 Kbit/s set automatically

Number of nodes Max. 32 in one segment; max. 127 with repeater

Range of bus ad-dresses

0 to 126; recommended 2 to 125

Setting the bus ad-dress

By means of two rotary coding switches; Coding hexadecimal

Table 5: Technical data, PROFIBUS

1073380000/1.3/08.09 Weidmüller t 21

Bluetooth SAI Manual

4.2. SAI-AU M12 GW PB/BT 12I

The SAI distributor Active Universal has the functions of a decentralized I/O system. Each distributor is equipped with module-specific actuator/sensor functions and a Fieldbus interface. The module combines the complete electronics in a water- and dust-proof protected housing. This enables it to be used in harsh environments. The module SAI-AU M12 GW PB/BT 12I is designed to connect 12 digital sensors with 6 M12 connectors.

Figure 10: SAI-AU M12 GW PB/BT 12I

LEDs:

BF PROFIBUS status indicator

BT Bluetooth communication

LQ Link quality (displays field strength)

UI1 Supply voltage UI1

Supplies the module and the DI1, DI3 and DI5 slots

UI2 Supply voltage UI2

Supplies the D12, DI4 and DI6 slots

UL Power supply to module Address area illumination

DI1 to DI12 Digital inputs

Connections:

AUX IN Supply voltage UI1 and UI2

AUX OUT Feed through supply voltage UI1 and UI2

BUS IN PROFIBUS input

BUS OUT PROFIBUS output

1 to 6 Two digital inputs each

Rotary switch:

X1 PROFIBUS address low byte

X10 PROFIBUS address high byte

NA Bluetooth network address

Jumper field:

J1 Switch/jumper for network ad-dresses

Table 6: SAI-AU M12 GW PB/BT 12I

BF BT LQ UI1 UI2 - -

LED BF LED BT LED LQ LED UI1 LED UI2 Unoccupied Unoccupied

LED UL (Illuminated address area)

LED DI13 (PIN 2) LED DI5 (PIN 4) LED DI11 (PIN 2) LED DI3 (PIN 4) LED DI9 (PIN 2) LED DI1 (PIN 4)

LED DI13 (PIN 2) LED DI5 (PIN 4) LED DI11 (PIN 2) LED DI3 (PIN 4) LED DI9 (PIN 2) LED DI1 (PIN 4)

22 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

PROFIBUS addressing Two rotary switches in the address section of the SAI are used to make the necessary bus address settings. The setting is made in hexadecimal code from 00H to 7EH which corresponds to the decimal values from 0 to 126 (see also Appendix C: Converting decimal to hexa-decimal, page 82). Note It is only possible to set the bus address in the address section of the SAI. Any alterations made to the bus address during operations will be recognised and adopted following the next reset (turning off the power supply). The factory-set default bus address on the SAI is 03.

A table is available in the Appendix C to aid conversion of decimal to hexadecimal ad-dresses.

Figure 11: PROFIBUS address switch

1073380000/1.3/08.09 Weidmüller t 23

Bluetooth SAI Manual

Setting the Bluetooth gateway address The Bluetooth side of the gateway only needs to have a network address specified. The node address at the gateway is always 0 and cannot be changed. The rotary switch NA and jumper J1 are used to establish the address and SAI address range. The table on the right lists the exact functioning of the net-selection switch (NA). Network addresses from 1 to 31 can be assigned.

Figure 12: Bluetooth address switch

Piconets Net-selection

switch (NA) Jumper (J1)

1 1 1 (OFF) 2 2 1 (OFF) 3 3 1 (OFF) 4 4 1 (OFF) 5 5 1 (OFF) 6 6 1 (OFF) 7 7 1 (OFF) 8 8 1 (OFF) 9 9 1 (OFF) 10 A 1 (OFF) 11 B 1 (OFF) 12 C 1 (OFF) 13 D 1 (OFF) 14 E 1 (OFF) 15 F 1 (OFF) 16 0 ON 17 1 ON 18 2 ON 19 3 ON 20 4 ON 21 5 ON 22 6 ON 23 7 ON 24 8 ON 25 9 ON 26 A ON 27 B ON 28 C ON 29 D ON 30 E ON 31 F ON

Table 7: Bluetooth gateway addresses

Any combination not listed here will lead to an address error and will be indicated by a continual red status LED. Position 0 on the net-selection switch is never allowed when you are working with the lower address range.

24 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

Connection of supply voltage The power supply is 24 V DC in accordance with EN 61131–2; the permissible range is 18 to 30 V DC. The distributor is designed to offer protection against polar-ity reversal.

Note

The power supply is connected via a 5-pole A-coded M12 male connector and a 5-pole, A-coded M12 female connector. Both power supplies share a common earth and are not electrically isolated. Use the ‘AUX In’ connection to feed in the power supply and ‘Bus Out’ to feed it for-ward.

Module connection from AUX-IN

Contact system M12 male connector, 5-pole Coding A Pin assignment Pin 1: +24 V DC UI1

connected with AUX-OUT Pin 1

Pin 2: +24 V DC UI2 connected with AUX-OUT Pin 2

Pin 3: GND Pin 4: GND

Pin 5: PE

Table 8: Contact assignment (pin out) of the power supply connector

Module connection from AUX OUT

Contact system M12 female connector, 5-pole Coding A Pin assignment Pin 1: +24 V DC UI1

connected with AUX-IN Pin 1

Pin 2: +24 V DC UI2 connected with AUX-IN Pin 2

Pin 3: GND Pin 4: GND

Pin 5: PE

Table 9: Contact assignment (pin out) of the female power supply connector

The power rating per pin is max. 2.5 A. Both circuits supply the plug-in stations DI1 to DI6 and the module electronics as follows: • UI1: supply voltage for one sensor at pin 1 from the plug-in slots 1, 3, 5 and 7 and the module electronics • UI2: supply voltage for one sensor at pin 1 from the plug-in slots 2, 4 and 6

1073380000/1.3/08.09 Weidmüller t 25

Bluetooth SAI Manual

Connection of the digital inputs Connection for two digital inputs

Contact system M12 female connector, 5-pole Coding A

Pin 1: +24 V DC sensor volta-ge Pin 2: Input 2 or diagnostics input Pin 3: GND Pin 4: Input 1

Pin assignment

Pin 5: PE

Table 10: Contact assignment of the digital inputs

Block diagram of the digital input Input configuration, pins 2 and 4 from each M12 female connector:

Figure 13: Block diagram of the digital input

Optical displays The status of a digital input is shown with a yellow/red LED. LED IN: 0.0, 0.1, 0.2, 0.3, 0.4, 0.5, 1.1, 1.2, 1.3, 1.4, 1.5: • yellow: status of digital input from pin 4 • red: short-circuit at 24 V DC sensor voltage pin 1 LED UI1: • green: Voltage 1 > 18 V DC • red: Voltage 1 < 18 V DC LED UI2: • green: Voltage 2 > 18 V DC • red: Voltage 2 < 18 V DC LED BT: Bluetooth communication • Flashing green: Search for SAIs • green: All configured SAIs found, communication

established • red: No SAIs found, no communication established LED LQ: Link quality (displays field strength) • green: good reception • red: poor reception • Off: no connection

26 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

Technical specifications Power supply 24 V DC

Limit values 18 V DC to 30 V DC

Contact load 2.5 A per pin

Reverse polarity protection Yes

Current consumption Module: approx. 70 mA

Digital inputs 16 channels

Plug-in slots DI1, DI2, DI3, DI4, DI5 and DI6

Grouping Two groups per six channels, with common earth

Permissible input voltage –30 V DC to +30 V DC (protected against polarity reversal)

Input level Low < 5 V DC, acc. to EN 61131-2 Type 1

Input level High > 15 V DC acc. to EN 61131-2 Type 1

Input current Low < 15 mA acc. to EN 61131-2 Type 1

Input current High 2 mA to 15 mA acc. to EN 61131-2 Type 1

Input filter 3 ms

Separation of potentials (electrical isola-tion) to the module electronics

None

Display elements One yellow/red error/status LED per channel

General technical data:

Ambient temperature during operation 0 to +60 °C, acc. to EN 61131-2

Ambient temperature during storage –25 to +85 °C, acc. to EN 61131-2

Protection class IP65 / IP67

GSD file (Device Data Base File) WIAU0A75.GSD

Dimensions L x W x H, 210 x 54 x 52 mm

Weight 340 g

Article order number 1006980000

Article designation SAI-AU M12 GW PB/BT 12I

Table 11: Technical data for the SAI-AU M12 GW PB/BT 12I

1073380000/1.3/08.09 Weidmüller t 27

Bluetooth SAI Manual

28 Weidmüller t 1073380000/1.3/08.09

4.3. SAI-AU M12 BT 16DI

The SAI distributor Active Universal has the functions of a decentralized I/O system. Each distributor is equipped with module-specific actuator/sensor functions and a wireless interface.

LEDs:

BT Bluetooth communication

LQ Link quality (displays field strength)

UI1 Supply voltage UI1

Supplies the module and the plug-in stations DI1, DI3, DI5 and DI7

UI2 Supply voltage UI2

Supplies the D12, DI4, DI6 and DI8 slots

UL Power supply to module Address area illumination

DI1 to DI16 Digital inputs

Connections:

AUX IN Supply voltage UI1 and UI2

AUX OUT Feed through supply voltage UI1 and UI2

1 to 8 Two digital inputs each

Rotary switch:

KA Bluetooth node address

NA Bluetooth network address

Jumper field:

J1 Jumper for the voltages UI1 and UI2

The module combines the complete electronics in a water- and dust-proof protected housing. This enables it to be used in harsh environments. The SAI-AU M12 BT 16DI module is designed to con-nect 16 digital sensors with 8 M12 male connectors.

- BT LQ UI1 UI2 - -

Unoccupied LED BT LED LQ LED UI1 LED UI2 Unoccupied Unoccupied

LED DI15 (PIN 2) LED DI7 (PIN 4) LED DI13 (PIN 2) LED DI5 (PIN 4) LED DI11 (PIN 2) LED DI3 (PIN 4) LED DI9 (PIN 2) LED DI1 (PIN 4)

LED DI15 (PIN 2) LED DI7 (PIN 4) LED DI13 (PIN 2) LED DI5 (PIN 4) LED DI11 (PIN 2) LED DI3 (PIN 4) LED DI9 (PIN 2) LED DI1 (PIN 4)

LED UL (Illuminated address area)

Table 12: SAI-AU M12 BT 16DI

Figure 14: SAI-AU M12 BT 16DI

Bluetooth SAI Manual

Setting the Bluetooth address Two rotary switches in the address section of the SAI are used to make appropriate network address settings. The table on the right lists the exact functioning of the slave-selection switch (SA) and the net-selection switch (NA). Node addresses ranging from 1 to 6 and network addresses ranging from 1 to 31 can be specified.

Figure 15: Address switch

Network Slave-

selection switch (SA)

Net-selection switch (NA)

1 1..6 1 2 1..6 2 3 1..6 3 4 1..6 4 5 1..6 5 6 1..6 6 7 1..6 7 8 1..6 8 9 1..6 9 10 1..6 A (10) 11 1..6 B (11) 12 1..6 C (12) 13 1..6 D (13) 14 1..6 E (14) 15 1..6 F (15) 16 A..F (10..15) 0 +16 17 A..F (10..15) 1 +16 18 A..F (10..15) 2 +16 19 A..F (10..15) 3 +16 20 A..F (10..15) 4 +16 21 A..F (10..15) 5 +16 22 A..F (10..15) 6 +16 23 A..F (10..15) 7 +16 24 A..F (10..15) 8 +16 25 A..F (10..15) 9 +16 26 A..F (10..15) A (10) +16 27 A..F (10..15) B (11) +16 28 A..F (10..15) C( 12) +16 29 A..F (10..15) D (13) +16 30 A..F (10..15) E (14) +16 31 A..F (10..15) F (15) +16

BT LQ UI1 UI2

SA NA UL J 1

Table 13: Setting the Bluetooth address, SAI

Any combination not listed here will lead to an address error and will be indicated by a continual red status LED. Forbidden settings are: node numbers 0, 7, 8, 9 and the position 0 on the net-selection switch when you are working with the lower address range.

1073380000/1.3/08.09 Weidmüller t 29

Bluetooth SAI Manual

Connection of supply voltage The power supply is 24 V DC in accordance with EN 61131–2; the permissible range is 18 to 30 V DC. The distributor is designed to offer protection against polar-ity reversal. Module connection from AUX-IN

Contact system M12 male connector, 5-pole Coding A Pin assignment Pin 1: +24 V DC UI1

connected with AUX-OUT Pin 1

Pin 2: +24 V DC UI2 connected with AUX-OUT Pin 2

Pin 3: GND Pin 4: GND

Pin 5: PE

Table 14: Contact assignment (pin out) of the power supply connector

Note

The power supply is connected via a 5-pole A-coded M12 male connector and a 5-pole, A-coded M12 female connector. Both power supplies share a common earth and are not electrically isolated. Use the ‘AUX In’ connection to feed in the power supply and ‘Bus Out’ to feed it for-ward.

Module connection from AUX OUT

Contact system M12 female connector, 5-pole Coding A Pin assignment Pin 1: +24 V DC UI1

connected with AUX-IN Pin 1

Pin 2: +24 V DC UI2 connected with AUX-IN Pin 2

Pin 3: GND Pin 4: GND

Pin 5: PE

Table 15: Contact assignment (pin out) of the female power supply connector

The power rating per pin is max. 2.5 A. Both circuits supply the plug-in stations DI1 to DI8 and the module electronics as follows:

• UI1: supply voltage for one sensor at pin 1 from the plug-in slots 1, 3, 5 and 7 and the module electronics • UI2: supply voltage for one sensor at pin 1 from the plug-in slots 2, 4 6 and 8 Both voltages can be bridged at the plug-in jumper position using a jumper. The module will then be supplied from only one voltage source. Jumper field J1, jumper options

2 – 1* bridge voltage UI2 and UI1

* Factory default setting

1 – 1 parked jumper position All other combinations are not possible as pin 3 of this mod-ule has no function.

Table 16: Plug-in jumper positions for the SAI-AU M12 BT 16DI

30 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

Connection of the digital inputs Connection for two digital inputs

Contact system M12 female connector, 5-pole Coding A

Pin 1: +24 V DC sensor volta-ge Pin 2: Input 2 or diagnostics input Pin 3: GND Pin 4: Input 1

Pin assignment

Pin 5: PE

Table 17: Contact assignment (pin out) of the digital input

Block diagram of the digital input Input wiring of pins 4 and 2 for each M12 female con-nector:

Figure 16: Block diagram of the digital input

DESINA DESINA is an abbreviation for DistributEd and Stan-dardised INstAllation technology for machine tools and manufacturing systems. DESINA describes the stan-dardised process for electrical, hydraulic and pneumatic installations for automatic machine tools and production systems. For further information, please visit www.desina.de.

Note

It is possible to monitor the sensor cable for breakage by bridging the 24 V DC power supply and the DESINA diagnostics input with an adapter.

Optical displays The status of a digital input is shown with a yellow/red LED.

Figure 17: View of M12 16DI

LED IN1: 0.0, 0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7: • yellow: status of digital input from pin 4 • red: Short-circuit at 24 V DC sensor voltage pin 1 LED IN2: 1.0, 1.1, 1.2, 1.3, 1.4, 1.5, 1.6, 1.7: • yellow: status of digital input or DESINA input from

Pin 2 • red: short-circuit at 24 V DC of the sensor voltage

Pin 1 or error message at DESINA input LED UI1: • green: Voltage 1 > 18 V DC • red: Voltage 1 < 18 V DC LED UI2: • green: Voltage 2 > 18 V DC • red: Voltage 2 < 18 V DC LED BT: Bluetooth communication • Flashing blue: detectable for all masters • blue: not detectable, connection already estab-

lished • Flashing green: Comm. stopped, no answer to

polling • green: Operation, BT connection established LED LQ: Link quality (displays field strength) • green: good reception • red: poor reception • Off: no connection

1073380000/1.3/08.09 Weidmüller t 31

Bluetooth SAI Manual

Connection of sensors with diagnostics outputs in accordance with DESINA specifications Figure 18: Sensors with DESINA Depending on the type of sensor, the DESINA diagnostics functionality senses and reports wire breaks, connector inter-face damage and defects in the electronics. Connection of sensors with monitoring for wire breakage

Figure 19: Sensor without DESINA

32 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

Technical specifications Power supply 24 V DC

Limit values 18 V DC to 30 V DC

Contact load 2.5 A per pin

Reverse polarity protection Yes

Current consumption Module: approx. 70 mA

Digital inputs 16 channels

Plug-in slots DI1, DI2, DI3, DI4, DI5, DI6, DI7 and DI8

Grouping Two groups for each eight channels, with common earth

Permissible input voltage –30 V DC to +30 V DC (protected against polarity reversal)

Input level Low < 5 V DC, acc. to EN 61131-2 Type 1

Input level High > 15 V DC acc. to EN 61131-2 Type 1

Input current Low < 15 mA acc. to EN 61131-2 Type 1

Input current High 2 mA to 15 mA acc. to EN 61131-2 Type 1

Input filter 3 ms

Separation of potentials (electrical isola-tion) to the module electronics

None

Display elements One yellow/red error/status LED per channel

General technical data:

Ambient temperature during operation 0 to +60 °C, acc. to EN 61131-2

Ambient temperature during storage –25 to +85 °C, acc. to EN 61131-2

Protection class IP65 / IP67

Dimensions L x W x H, 210 x 54 x 52 mm

Weight 340 g

Article order number 1006940000

Article designation SAI-AU M12 BT 16DI

Table 18: Technical data for the SAI-AU M12 BT 16DI

1073380000/1.3/08.09 Weidmüller t 33

Bluetooth SAI Manual

34 Weidmüller t 1073380000/1.3/08.09

4.4. SAI-AU M12 BT 16DI/8DO

The SAI distributor Active Universal has the functions of a decentralized I/O system. Each distributor is equipped with module-specific actuator/sensor functions and a wireless interface. The module combines the complete electronics in a water- and dust-proof protected housing. This enables it to be used in harsh environments.

LEDs:

BT Bluetooth communication

LQ

Link quality (displays field strength)

UI Supply voltage UI

Supplies the module and the in-puts

UQ1 Supply voltage UQ1

Power supply to the outputs 0.0 and 0.1

UQ2 Supply voltage UQ2

Power supply to the outputs 0.2 and 0.3

UQ3 Supply voltage UQ3

Power supply to the outputs 0.4 to 0.7

UL Power supply to module Address area illumination

IO1 to IO16 Digital inputs

Connections:

AUX IN1 Supply voltage UI and UQ1

AUX IN2 Supply voltage UQ2 and UQ3

1 to 8 Two digital inputs each, or one digital input and one DESINA diagnostic input, or one digital output and one digital input

Rotary switch:

KA Bluetooth node address

NA Bluetooth network address

Jumper field:

J1 Jumper for the voltages UQ1, UQ2 and UQ3

The SAI-AU M12 BT 16DI/8DO module is designed to connect 16 digital sensors. Alternatively, up to eight channels can be used as outputs. Of these, six outputs are designed for a load current of 0.5A and two outputs for a load current of 2A. The signals are connected via eight M12 plug-in connectors.

Figure 20: SAI-AU M12 BT 16DI/8DO

Table 19: SAI-AU M12 BT 16DI/8DO

Unoccupied LED BT LED LQ LED UI LED UQ1 LED UQ2 LED UQ3

LED DI15 (PIN 2) LED DI7 (PIN 4) LED DI13 (PIN 2) LED DI5 (PIN 4) LED DI11 (PIN 2) LED DI3 (PIN 4) LED DI9 (PIN 2)

LED DI15 (PIN 2) LED DI7 (PIN 4) LED DI13 (PIN 2) LED DI5 (PIN 4) LED DI11 (PIN 2) LED DI3 (PIN 4) LED DI9 (PIN 2) LED DI1 (PIN 4)

LED DI1 (PIN 4)

- BT LQ UI UQ1 UQ2 UQ3

LED UL (Illuminated address area)

Bluetooth SAI Manual

Setting the Bluetooth slave address Two rotary switches in the address section of the SAI are used to make appropriate network address settings. The table on the right lists the exact functioning of the slave-selection switch (SA) and the net-selection switch (NA). Node addresses ranging from 1 to 6 and network addresses ranging from 1 to 31 can be specified.

Figure 21: Address switch

Note

The specified nodes correspond to the as-signed plug-in slot on the slave.

Example: Assigned slot 2 Address to be set: 27 Gateway setting: J1 = ON NA = B Slave setting: SA = B NA = B

Caution

Any combination not listed here will lead to an address error and will be indicated by a continual red status LED.

Forbidden settings are: node numbers 0, 7, 8, 9 and the position 0 on the slave-selection switch when you are working with the lower address range.

Piconets Slave-

selection switch (SA)

Net-selection switch (NA)

1 1..6 1 2 1..6 2 3 1..6 3 4 1..6 4 5 1..6 5 6 1..6 6 7 1..6 7 8 1..6 8 9 1..6 9 10 1..6 A 11 1..6 B 12 1..6 C 13 1..6 D 14 1..6 E 15 1..6 F 16 A..F 0 17 A..F 1 18 A..F 2 19 A..F 3 20 A..F 4 21 A..F 5 22 A..F 6 23 A..F 7 24 A..F 8 25 A..F 9 26 A..F A 27 A..F B 28 A..F C 29 A..F D 30 A..F E 31 A..F F

BT LQ UI UQ1 UQ2 UQ3

SA NA UL J 1

Table 20: Setting the Bluetooth address, SAI

1073380000/1.3/08.09 Weidmüller t 35

Bluetooth SAI Manual

Connection of supply voltage The power supply is 24 V DC in accordance with EN 61131–2; the permissible range is 18 to 30 V DC. The distributor is designed to offer protection against polar-ity reversal. Module connection from AUX IN1

Contact system M12 male connector, 5-pole Coding A Pin assignment Pin 1: +24 V DC UI

Pin 2: +24 V DC UQ1 Pin 3: GND Pin 4: GND

Pin 5: PE

Table 21: Contact assignment (pin out) of the power supply connector

Note

The power supply is connected via a 5-pole A-coded M12 male connector and a 5-pole, A-coded M12 female connector. Use the ‘AUX In’ connection to feed in the power supply and ‘Bus Out’ to feed it for-ward. Both power supplies share a common earth and are not electrically isolated.

Module connection from AUX IN2

Contact system M12 male connector, 5-pole Coding A Pin assignment Pin 1: +24 V DC UQ2

Pin 2: +24 V DC UQ3 Pin 3: GND Pin 4: GND

Pin 5: PE

Table 22: Contact assignment (pin out) of the power supply connector

The current load per pin is a maximum of 2.5 A. – The total current per module is 8A. The four circuits supply the three output circuits, the sensor supplies and the module electronics as described below: • Voltage UI: 16 sensors at pin 1 from plug-in stations 1 to 8 and module supply • Voltage UQ1: one output driver with 0.5 A to 0.0 and one output driver with 2.0 A to 0.1 • Voltage UQ2: one output driver with 0.5 A to 0.2 and one output driver with 2.0 A to 0.3 • Voltage UQ3: four output drivers with 0.5 to 0.4, 0.5, 0.6 and 0.7 The three voltages for the output drivers can be connected together using jumpers at a plug-in jumper position. Jumper field J1, jumper options

2 – 1 Bridge voltage UQ1 and UQ2

3 – 1 Bridge voltage UQ1 and UQ3

2 – 1 and 3 – 1*

Bridge voltage UQ1, UQ2 and UQ3

2 – 3 Bridge voltage UQ2 and UQ3

* Factory default setting

Table 23: Plug-in jumper positions for the SAI-AU M12 BT 16DI/8DO

36 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

Connection of the digital input Connection for a digital input

Contact system M12 female connector, 5-pole Coding A

Pin 1: +24 V DC sensor volta-ge Pin 2: Input 2 or diagnostics input Pin 3: GND Pin 4: Input 1

Pin assignment

Pin 5: PE

Table 24: Contact assignment (pin out) of the digital input

Block diagram of the digital input Input wiring of pins 4 and 2 for each M12 female con-nector:

Figure 22: Block diagram of the digital input

DESINA DESINA is an abbreviation for DistributEd and Stan-dardised INstAllation technology for machine tools and manufacturing systems. DESINA describes the stan-dardised process for electrical, hydraulic and pneumatic installations for automatic machine tools and production systems. For further information, please visit www.desina.de.

Note

It is possible to monitor the sensor cable for breakage by bridging the 24 V DC power supply and the DESINA diagnostics input with an adapter.

Optical displays The status of a digital input is shown with a yellow/red LED.

Figure 23: /A view of M12 16DI

LED IN1: 0.0, 0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7: • yellow: status of digital input from pin 4 • red: Short-circuit at 24 V DC sensor voltage pin 1 LED IN2: 1.0, 1.1, 1.2, 1.3, 1.4, 1.5, 1.6, 1.7: • yellow: status of digital input or DESINA input from

Pin 2 • red: short-circuit at 24 V DC of the sensor voltage

Pin 1 or error message at DESINA input LED UI1: • green: Voltage 1 > 18 V DC • red: Voltage 1 < 18 V DC LED UI2: • green: Voltage 2 > 18 V DC • red: Voltage 2 < 18 V DC LED BT: Bluetooth communication • Flashing blue: detectable for all masters • blue: not detectable, connection already estab-

lished • Flashing green: Comm. stopped, no answer to

polling • green: Operation, BT connection established LED LQ: Link quality (displays field strength) • green: good reception • red: poor reception • Off: no connection

1073380000/1.3/08.09 Weidmüller t 37

Bluetooth SAI Manual

Connection of sensors with diagnostics outputs in accordance with DESINA specifications Figure 24: Sensor with DESINA Depending on the type of sensor, the DESINA diagnostics functionality senses and reports wire breaks, connector inter-face damage and defects in the electronics. Connection of sensors with monitoring for wire breakage

Figure 25: Sensor without DESINA

38 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

Block diagram of digital output Figure 26: Block diagram of the digital outputs

Figure 27: Assignment of the 0.5 A and 2 A outputs

Optical displays The status of each connection group with two digital inputs or with a digital input and a diagnostics input to DESINA specifications is indicated by means of two dual-coloured yellow/red LEDs. LED I/O1: 0.0, 0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7: • yellow: status of digital input or digital output

from pin 4 • red: short-circuit of 24 V DC sensor voltage pin 1

or short-circuit at the output on pin 4 LED DI2: 1.0, 1.1, 1.2, 1.3, 1.4, 1.5, 1.6, 1.7: • yellow: status of digital input or DESINA input

from pin 2 • red: short-circuit of 24 V DC sensor voltage pin 1

or error message at DESINA input

LED UI: • green: Voltage 1 > 18 V DC • red: Voltage 1 < 18 V DC LEDs UQ1, UQ2, UQ3: • green: Voltage > 18 V DC or • red: Voltage < 18 V DC Figure 28: I/O housing M12 16DI/8DO

1073380000/1.3/08.09 Weidmüller t 39

Bluetooth SAI Manual

Technical specifications Power supply 24 V DC

Limit values 18 V DC to 30 V DC

Contact load 2.5 A per pin

Reverse polarity protection Yes

Current consumption Module: approx. 70 mA

Digital inputs 16 channels

Plug-in slots DI1, DI2, DI3, DI4, DI5, DI6, DI7 and DI8

Grouping Two groups for each eight channels, with common earth

Permissible input voltage –30 V DC to +30 V DC (protected against polarity reversal)

Input level Low < 5 V DC, acc. to EN 61131-2 Type 1

Input level High > 15 V DC acc. to EN 61131-2 Type 1

Input current Low < 15 mA acc. to EN 61131-2 Type 1

Input current High 2 mA to 15 mA acc. to EN 61131-2 Type 1

Input filter 3 ms

Separation of potentials (electrical isolation) to the module electronics

None

Display elements One yellow/red error/status LED per channel

Digital outputs 8 channels, 2 channels 2 A, 6 channels 0.5

Plug-in stations with 0.5 A I/O1, I/O3, I/O5, I/O6, I/O7, I/O8

Plug-in stations with 2 A I/O2, I/O4

Grouping One group for 8 channels with common earth

Driver type Highside

Total current UQ1, I/O1 and I/O2 2,5 A

Total current UQ2, I/O3 and I/O4 2,5 A

Total current UQ3, I/O5, I/O6, I/O7 and I/O8 2,5 A

Total current, module 8 A

Output voltage Low 0 V

Output voltage: UQ minus the on-state voltage of the damping diode

Switching capacity, resistive load Max. 100 Hz

Switching capacity, inductive load Max. 1 Hz

Switching capacity, lamp load: Max. 8 Hz

Short-circuit proof Yes, switch-off in case of short-circuit and error message

Short-circuit current at 25 °C 1.4 A at 0.5 A outputs

Short-circuit current at 25 °C 5.6 A at 2.0 A outputs

Separation of potentials (electrical isolation) to None

40 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

1073380000/1.3/08.09 Weidmüller t 41

the module electronics

Display elements One yellow/red error/status LED per channel

General technical specifications

Ambient temperature during operation 0 to +60 °C, acc. to EN 61131-2

Ambient temperature during storage –25 to +85 °C, acc. to EN 61131-2

Protection class IP65 / IP67

Dimensions L x W x H, 210 x 54 x 52 mm

Weight 340 g

Article order number 1006930000

Article designation SAI-AU M12 BT 16DI/8DO

Table 25: Technical data for the SAI-AU M12 BT 16DI/8DO

Bluetooth SAI Manual

4.5. SAI-AU M12 BT 4AI2AO2DIO

The SAI distributor Active Universal has the functions of a decentralized I/O system. Each distributor is equipped with module-specific actuator/sensor functions and a wireless interface. The module combines the complete electronics in a water- and dust-proof protected housing. This enables it to be used in harsh environments.

The SAI-AU M12 BT 4AI2AO2DIO module is used for connecting four inputs with four M12 connectors; where two each can be used as outputs.

Figure 29: SAI-AU M12 BT 4AI2AO2DIO

LEDs:

BT Bluetooth communication

LQ Link quality (displays field strength)

UI1 Supply voltage UI1

Supplies the module and the plug-in stations DI1, DI3, DI5 and DI7

UI2 Supply voltage UI2

Supplies the D12, DI4, DI6 and DI8 slots

UL Power supply to module

Address area illumination

DIO0 to DIO1 Digital inputs / outputs

DI2 to DI3 Digital inputs

AI0 to AI3 Fault-LED for analogue inputs

AO0 to AO1 Fault-LED for analogue outputs

Connections:

AUX IN Supply voltage UI1 and UI2

AUX OUT Feed through supply voltage UI1 and UI2

1 to 8 Two digital inputs each

Rotary switch:

KA Bluetooth node address

NA Bluetooth network address

Jumper field:

J1 Jumper for the voltages

UI1 and UI2

Table 26: SAI-AU M12 BT 4AI2AO2DIO

42 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

Setting the Bluetooth address Two rotary switches in the address section of the SAI are used to make appropriate network address settings. The table on the right lists the exact functioning of the slave-selection switch (SA) and the net-selection switch (NA). Node addresses ranging from 1 to 6 and network addresses ranging from 1 to 31 can be specified.

Figure 30: Address switch

Caution

Any combination not listed here will lead to an address error and will be indicated by a continual red status LED. Forbidden settings are: node numbers 0, 7, 8, 9 and the position 0 on the net-selection switch when you are working with the lower address range.

Networks Slave-

selection switch

Net-selection switch

1 1..6 1 2 1..6 2 3 1..6 3 4 1..6 4 5 1..6 5 6 1..6 6 7 1..6 7 8 1..6 8 9 1..6 9 10 1..6 A (10) 11 1..6 B (11) 12 1..6 C (12) 13 1..6 D (13) 14 1..6 E (14) 15 1..6 F (15) 16 A..F (10..15) 0 +16 17 A..F (10..15) 1 +16 18 A..F (10..15) 2 +16 19 A..F (10..15) 3 +16 20 A..F (10..15) 4 +16 21 A..F (10..15) 5 +16 22 A..F (10..15) 6 +16 23 A..F (10..15) 7 +16 24 A..F (10..15) 8 +16 25 A..F (10..15) 9 +16 26 A..F (10..15) A (10) +16 27 A..F (10..15) B (11) +16 28 A..F (10..15) C( 12) +16 29 A..F (10..15) D (13) +16 30 A..F (10..15) E (14) +16 31 A..F (10..15) F (15) +16

BT LQ UI1 UI2

SA NA UL J 1

Table 27: Setting the Bluetooth address, SAI

1073380000/1.3/08.09 Weidmüller t 43

Bluetooth SAI Manual

Connection of supply voltage The power supply is 24 V DC in accordance with EN 61131–2; the permissible range is 18 to 30 V DC. The distributor is designed to offer protection against polarity reversal.

Note

The power supply is connected via a 5-pole, A-coded M12 male connector and a 5-pole, A-coded M12 female connector. Use the ‘AUX In’ connection to feed in the power supply and ‘Bus Out’ to feed it for-ward. Both power supplies share a common earth and are not electrically isolated.

Module connection from AUX IN1

Contact system M12 male connector, 5-pole Coding A Pin assignment Pin 1: +24 V DC UI1 con-

nected to AUX OUT, pin 1

Pin 2: +24 V DC UI2 con-nected to AUX OUT, pin 2

Pin 3: GND Pin 4: GND

Pin 5: PE

Table 28: Contact assignment (pin out) of the power supply connector

Module connection from AUX OUT

Contact system M12 female connector, 5-pole Coding A Pin assignment Pin 1: +24 V DC UI

Pin 2: +24 V DC UQ1 Pin 3: GND Pin 4: GND

Pin 5: PE

Table 29: Contact assignment (pin out) of the female power supply connector

Power supply: The power rating per pin is max. 2.5 A. Both circuits supply the plug-in stations DI1 to DI6 and the module electronics as follows: • UI1: supply voltage for two sensors each, at pin 1 from the plug-in stations: 1, 3, 5, 7, 9, 11, 13, 15, and the module

electronics. • UI2: supply voltage for one sensor at pin 1 from the plug-in stations 2, 4, 6, 8, 10, 12, 14 and 16 Both voltages can be bridged at the plug-in jumper position using a jumper. The module will then be supplied from only one voltage source.

Jumper field J1, jumper options

2 – 1* bridge voltage UI2 and UI1

* Factory default setting

1 – 1 parked jumper position All other combinations are not possible as pin 3 of this mod-ule has no function.

Table 30: Plug-in jumper positions for the SAI-AU M12 BT 4AI2AO2DIO

44 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

Connection for an analogue input Contact system M12 male connector, 5-

pole Coding A

Pin 1: + 24 V DC Sensor voltage Pin 2: Analogue input + Pin 3: GND Pin 4: Analogue output current

Pin assignment

Pin 5: PE

Housing Shield

Table 31: Contact assignment (pin out) of the ana-logue input

Connection for an analogue output Contact system M12 female connector, 5-

pole Coding A

Pin 1: + 24 V DC, actuator voltage Pin 2: Analogue output voltage Pin 3: GND Pin 4: Analogue output current

Pin assignment

Pin 5: PE

Housing Shield

Table 32: Contact assignment (pin out) of an ana-logue output

Block diagram of the analogue input

Figure 31: Block diagram of the analogue input

Block diagram of the analogue output

Figure 32: Block diagram of the analogue output

Connection for two digital inputs or for a digital input with diagnostics input to DESINA specifica-tions.

Contact system M12 female connector, 5-pole

Coding A

Pin assignment

PIN 1: +24 V DC sensor voltage

PIN 2: Input 2 or diagnostics input

PIN 3: GND

PIN 4: Input 1 / output

PIN 5: ÜE Table 33: Contact assignment of the digital inputs DESINA (www.desina.de) DESINA is an abbreviation for DistributEd and Stan-dardised INstAllation technology for machine tools and manufacturing systems. DESINA describes the stan-dardised process for electrical, hydraulic and pneumatic installations for automatic machine tools and production systems.

Block diagram of the digital input Input wiring of pins 4 and 2 for each M12 female con-nector:

Figure 33: Block diagram of the digital input

Note

It is possible to monitor the sensor cable for breakage by bridging the 24 V DC power supply and the DESINA diagnostics input with an adapter.

1073380000/1.3/08.09 Weidmüller t 45

Bluetooth SAI Manual

Optical displays The status of a digital input is shown with a yellow/red LED.

Figure 34: /A view of M12 4AI

LED IN: DIO0 / DIO1 • yellow: status of digital input from Pin 4 • red: Short-circuit at 24 V DC sensor voltage pin 1 LED IN: DI2 / DI3 • yellow: status of digital input or DESINA input from

Pin 2 • red: short-circuit at 24 V DC of the sensor voltage

Pin 1 or error message at DESINA input LED AI0, AI1, AI2, AI3: • red: Range Fault LED AO0, AO1: • red: Range Fault LED UI1: • green: Voltage 1 > 18 V DC • red: Voltage 1 < 18 V DC LED UI2: • green: Voltage 2 > 18 V DC • red: Voltage 2 < 18 V DC LED BT: Bluetooth communication • Flashing blue: detectable for all masters • blue: not detectable, connection already estab-

lished • Flashing green: Comm. stopped, no answer to

polling • green: Operation, BT connection established LED LQ: Link quality (displays field strength) • green: good reception • red: poor reception • Off: no connection

46 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

Connection of sensors with diagnostics outputs in accordance with DESINA specifications Figure 35: Sensors with DESINA Depending on the type of sensor, the DESINA diagnos-tics functionality senses and reports wire breaks, con-nector interface damage and defects in the electronics. Connection of sensors with monitoring for wire breakage

Figure 36: Sensors without DESINA

1073380000/1.3/08.09 Weidmüller t 47

Bluetooth SAI Manual

48 Weidmüller t 1073380000/1.3/08.09

Technical specifications Power supply 24 V DC

Limit values 18 V DC to 30 V DC

Contact load 2.5 A per pin

Reverse polarity protection Yes

Current consumption Module: approx. 70 mA

Digital inputs

Plug-in slots DI1, DI1, DI2, DI3,

Grouping One groups for each two channels, with common earth

Permissible input voltage –30 V DC to +30 V DC (protected against polarity reversal)

Input level Low < 5 V DC, acc. to EN 61131-2 Type 1

Input level High > 15 V DC acc. to EN 61131-2 Type 1

Input current Low < 15 mA acc. to EN 61131-2 Type 1

Input current High 2 mA to 15 mA acc. to EN 61131-2 Type 1

Input filter 3 ms

Separation of potentials (electrical isola-tion) to the module electronics

None

Display elements One yellow/red error/status LED per channel

Digital outputs

Plug-in slots DO0, DO1

Grouping 1 Gruppe für 2 Kanäle mit gemeinsamer Masse

Driver type Highside

Total current UI1 2,5 A

Total current module 2,5 A

Output voltage Low 0 V

Output voltage High UQ minus the on-state voltage of the damping diode

Switching capacity, resistive load max. 100 Hz

Switching capacity, inductive load max. 1 Hz

Switching capacity, lamp load max. 8 Hz

Short-circuit proof Yes, switch-off in case of short-circuit and error message

Short-circuit current at 25 °C 1,4 A bei 0,5 A Ausgängen

Short-circuit current at 25 °C 5,6 A bei 2,0 A Ausgängen

Separation of potentials to the module electronics

none

Indication elements One yellow/red error/status LED per channel

Analogue inputs

Bluetooth SAI Manual

Plug-in slots AI0, AI1, AI2, AI3

Limit values -10 V …+10 V

Input type Differential measurement between pins 2 and 4

Sampling period 10 – 250 ms adjustable per analogue input

Accuracy < 0.2 % of the upper limit of effective range

Offset error < 0.1 % of the upper limit of effective range

Linearity < 0,05 % of upper limit of effective range

Temperature coefficient < 300 ppm/K of upper limit of effective range

Analogue outputs

Steckplätze AO0, AO1

Limit values - 10 V …+10 V (PIN 2/3)

0 V …+10 V (PIN 2/3)

4 … 20 mA (PIN 4/3)

0… 20 mA (PIN 4/3)

Sampling period 5 – 250 ms adjustable per analogue input

Accuracy < 0.2 % of the upper limit of effective range

Offset error < 0.1 % of the upper limit of effective range

Linearity < 0,05 % of upper limit of effective range

Temperature coefficient < 300 ppm/K of upper limit of effective range

General technical specifications

Ambient temperature during operation 0 to +60 °C, acc. to EN 61131-2

Ambient temperature during storage –25 to +85 °C, acc. to EN 61131-2

Protection class IP65 / IP67

Dimensions L x W x H 210 x 54 x 52 mm

Weight 340 g

Article order number 1006920000

Article designation SAI-AU M12 BT 4AI2AO2DIO

Table 34: Technical data for the SAI-AU M12 BT 4AI2AO2DIO

1073380000/1.3/08.09 Weidmüller t 49

Bluetooth SAI Manual

5. Initial Commissioning

Initial commissioning

5.1 Device Data Base Files (GSD) and bitmap files

51

5.2 Copy the GSD files to the local directory

52

5.3 Install the GSD files in Step7

53

5.4 Adding an SAI module in the hardware configurator

55

5.5 Assigning the input and output addresses

57

5.6 Configuring and setting parameters

58

5.7 SAI parameter data

59

50 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

5.1. Device Data Base Files (GSD) and bitmap files

GSD files (device database files) GSD files are the electronic data sheets of a device that provide a PROFIBUS master with straightforward in-formation about the characteristics of the PROFIBUS DP field device. The information in these files includes: • The supported transmission rates • The length of the input and output data to be ex-

changed • The meaning of the diagnostics parameters and

the application parameters • The field device type • The supported services

The files are provided with the file extension gsd. The following data is valid for the SAI-AU BT GW 12DI PROFIBUS gateway: ID number: 0A75 GSD file (device database file): WIAU0A75.GSD Version: 14

Bitmap files Symbols are made available for display in the hardware configurator. The name of the bitmap file for normal operations is WIAU_BTN.DIB. The name of the bitmap file for diagnostics is WIAU_BTS.DIB.

WIAU_BTN.DIB WIAU_BTS.DIB

Figure 37: Bitmaps for hardware configurator

How the GSD and bitmap files are used and their memory location depends on the con-figuration tool being used. Hardware configuration is explained below, based on an ex-ample using the programming software Simatic® Step7. ® Registered trademark of Siemens AG

1073380000/1.3/08.09 Weidmüller t 51

Bluetooth SAI Manual

5.2. Copy the GSD files to the local directory

The GSD files are available for downloading free of charge from Weidmüller’s homepage, http://www.weidmueller.com/54266/Downloads/Software/SAI-Active-Data/cw_index.aspx?newsid= The memory location of the GSD files is determined by the installation routine of the Step7 programme. Usually, this is below the installation directory \Step7\S7DATA\GSD. The necessary bitmap files are copied into the \Step7\S7DATA\NSBMP directory.

52 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

5.3. Install the GSD files in Step7

Open the proper project in the programme Step7 and select the hardware configuration.

Figure 38: Installing the GSD file: step 1

Note

Close all Step7 applications before continu-ing with the following commands.

Select the command Extras > Update Catalogue to update the contents of the catalogue in the hardware configurator.

Figure 39: Installing the GSD file: step 2

1073380000/1.3/08.09 Weidmüller t 53

Bluetooth SAI Manual

When selecting the PROFIBUS-DB device, look under PROFIBUS-DP => Additional field devices => Gateway => Bluetooth-Gateway for the Weidmüller Bluetooth SAI modules.

Figure 40: GSD file catalogue

54 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

1073380000/1.3/08.09 Weidmüller t 55

5.4. Adding a BT-GW in the hardware configurator

The hardware configuration with a PROFIBUS DP-enabled central processing unit (CPU 315-2 DP) has been launched and a PROFIBUS DP master system has been defined for this CPU.

You can now add individual devices to the PROFIBUS DP master system. A pop-up window opens in which the PROFIBUS address can be assigned. You can set parameters on the Parameter tabbed page.

Note

Assign each PROFIBUS address only once.

Figure 41: Hardware configurator

Bluetooth SAI Manual

The gateway which has been inserted now has slots available for modules. Up to seven modules can be added to these slots. A maximum of six devices can be connected with Bluetooth. The seventh device or the first device depicts 12 digital gateway inputs (digital input: DI). On PROFIBUS, these 12 DIs are connected via a 16-DI identifier, since only a byte-by-byte assignment is pos-sible. An excerpt from a gateway is shown in the figure below. In this example, all available module types are listed once.

Note

According to the definition, the Gateway IOs must occupy the first slot. No "holes" are allowed in the slot list. The SAIs must be listed in the proper order according to their identifiers (node numbers).

Figure 42: The gateway slot list

These modules are stored in the GSD file. They are assigned the application parameters in this file. There are a total of four modules in the selection list: the Gateway-IOs 12DI, a SAI 16DI, a SAI 16DI/8DO and a SAI 4AI/2AO/4DI.

Note

The Universal Module is a Step7 attachment and cannot be deleted.

Figure 43: Module types

56 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

5.5. Assigning the input and output addresses

Each PROFIBUS DP device is already automatically assigned an address, with which data is exchanged with the PLC programme.

You can accept or alter these addresses. The quickest method is to double-click the address bar of the se-lected device. Then it is possible to select the starting address.

Figure 44: Assigning input / output addresses

1073380000/1.3/08.09 Weidmüller t 57

Bluetooth SAI Manual

5.6. Configuration and setting parameters

The functionality for all modules is defined via one or several configuration bytes in the configuration menu. To access this menu click Edit => Object properties => Configure properties.

Figure 45: Parameter

Refer to the following sub-section for details about module parameterization methods.

An overview of the diagnostics of the SAIs the meaning of the diagnostics bytes is available in Chapter 6.

58 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

5.7. SAI parameter data

Each SAI module is associated with specific parameters in the GSD file. The operator may alter these parameters. SAI-AU M12 GW PB/BT 12I With these module types, the user can activate the DESINA configuration for each digital input. More on the DESINA configuration can be found under [2].

SAI: SAI-AU M12 GW PB/BT 12I

Number of parameter bytes:

5

First byte: 0xAA (frame separator) Second byte: 0x0D (the number of pa-

rameter bytes which follow) Third byte: 0x00 Activates the DESINA

function Fourth byte: 0x14 Configuration of the

maximum transmit power Fifth byte: 0x00 Activation of the

channel-specific diagnos-tics, configuration of the behaviour of the input data in event of module loss

6 – 15 bytes: 0xFF Configuration of the use for the Bluetooth chan-nels

Table 35: Overview of the SAI parameters GW 12I

SAI-AU M12 BT 16DI DESINA configuration is also available for this module.

SAI: SAI-AU M12 BT 16DI Number of parameter bytes:

5

First byte: 0xAA (frame separator) Second byte: 0x03 (the number of pa-

rameter bytes which follow) Third byte: Activates the DESINA

function Fourth byte: 0x14 Configuration of the

maximum transmit power Fifth byte: 0x00 reserved

Table 36: Overview of SAI parameters, 16DI

SAI-AU M12 BT 16DI/8DO With this module type, the user also has the possibility for DESINA configuration. In addition, the user can specify the type (output or input) and specify a safe status for each output.

SAI: SAI-AU M12 BT 16DI/8DO Number of parameter bytes:

8

First byte: 0xAA (frame separator) Second byte: 0x06 (the number of pa-

rameter bytes which follow) Third byte: 0x00 Activates the DESINA

function Fourth byte: 0x00 Defines the function

of the connection points as input or output

Fifth byte: 0x00 Defines how the out-puts react when there is a bus malfunction.

Sixth byte: 0x00 Defines the safe status of outputs

Seventh byte: 0x14 Configuration of the maximum transmit power

Eighth byte: reserved

Table 37: Overview of SAI parameters, 16DI/8DO

1073380000/1.3/08.09 Weidmüller t 59

Bluetooth SAI Manual

SAI-AU M12 BT 4AI2AO2DIO With this module type, the user also has the possibility for DESINA configuration. In addition, the user can specify the type (output or input) for each digital input and specify a safe status for each output.

SAI: SAI-AU M12 BT 4AI2AO2DIO

Number of parameter bytes:

10

First byte: 0xAA (frame separator) Second byte: 0x13 (the number of pa-

rameter bytes which follow) Third byte: 0x00 Defines the meas-

urement range for the ana-logue inputs

Fourth byte: 0x00 Defines the output range for the analogue inputs

Fifth byte: 0xFA Defines the conver-sion time for the analogue input channel 1

Sixth byte: 0xFA Defines the conver-sion time for the analogue input channel 2

Seventh byte: 0xFA Defines the conver-sion time for the analogue input channel 3

Eighth byte: 0xFA Defines the conver-sion time for the analogue input channel 4

Ninth byte: 0x00 reserved Tenth byte: 0x00 reserved Eleventh byte: 0x00 Defines how the ana-

logue outputs react when there is a bus malfunction.

12th and 13th bytes: 0x00 Defines the safe status of the analogue output 1

14th and 15th bytes: 0x00 Defines the safe status of the analogue output 2

Sixteenth byte: 0x00 Activates the DESINA function

Seventeenth byte: 0x00 Defines the function of the connection point as input or output

Eighteenth byte: 0x00 Defines how the digi-tal outputs react when there is a bus malfunction.

Nineteenth byte: 0x00 Defines the safe status of the digital outputs

Twentieth byte: 0x14 Configuration of the maximum transmit power

Twenty-first byte: 0x00 reserved

Table 38: Overview of SAI parameters, 4AI2AO2DIO

60 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

Activates the DESINA function Bits 0 to 7 set the DESINA diagnostics of the connec-tions 1 to 8. The DESINA diagnostics functionality is activated if the corresponding bit is set to 1. If the DESINA diagnostic functionality is activated, the con-nection at pin 4 acts as a DESINA diagnostics input. The connection at pin 2 is then the switch input to be monitored.

Bits 0 to 7 1 = DESINA functionality ON Bits 0 to 7 0 = DESINA functionality OFF

Table 39: DESINA parameters

Defines the function of the connection point as input or output The input of bit 0 to bit 7 sets the functionality of pin 2 of the connections 1 to 8 as well as 1 to 16 of the M8 connection. Setting this bit to 1 activates the output. Set to this status, short-circuits to earth and +24 V DC will be recognised and reported in the diagnostics. Bits 0 to 7 1= connection pin 2 is INPUT Bits 0 to 7 0= connection pin 2 is OUTPUT

Table 40: Reversal of input and output

Defines how the outputs react when there is a bus malfunction. The entries for Bit 0 to Bit 7 determine for each output if it enters a safe status or if it retains the last status. If this bit is set to 1, the output retains the last status that prevailed before the bus error occurred. The safe status is defined in byte 5 Bits 0 to 7 1 = OUTPUT goes into safe

status Bits 0 to 7 0 = OUTPUT retains most recent

status

Table 41: Behaviour when bus malfunction occurs

Defines the safe status of outputs The entries for Bit 0 to Bit 7 determine for each output if it is ON or OFF when in the safe status. Bits 0 to 7 1 = OUTPUT switches ON Bits 0 to 7 0 = OUTPUT switches OFF

Table 42: Behaviour when bus malfunction occurs

1073380000/1.3/08.09 Weidmüller t 61

Bluetooth SAI Manual

Configuration of the analogue inputs The four analogue inputs are set with two bits respec-tively. The first bit defines the type of measurement as voltage or current measurement; the second bit sets the meas-urement range in accordance with the selected meas-urement.

Bit 0 0 = analogue input 0 VOLTAGE measurement 1 = analogue input 0 CURRENT measurement

Bit 1 0 = analogue input 0 measurement range 0 to 10 V or 0 to 20 mA 1 = analogue input 0 measurement range –10 V to +10 V or 4 to 20 mA

Bit 2 0 = analogue input 1 VOLTAGE measurement 1 = analogue input 1 CURRENT measurement

Bit 3 0 = analogue input 1 measurement range 0 to 10 V or 0 to 20 mA 1 = analogue input 1 measurement range –10 V to +10 V or 4 to 20 mA

Bit 4 0 = analogue input 2 VOLTAGE measurement 1 = analogue input 2 CURRENT measurement

Bit 5 0 = analogue input 2 measurement range 0 to 10 V or 0 to 20 mA 1 = analogue input 2 measurement range –10 V to +10 V or 4 to 20 mA

Bit 6 0 = analogue input 3 VOLTAGE measurement 1 = analogue input 3 CURRENT measurement

Bit 7 0 = analogue input 3 measurement range 0 to 10 V or 0 to 20 mA 1 = analogue input 3 measurement range –10 V to +10 V or 4 to 20 mA

Table 43: Configuration of the analogue inputs

Configuration of the analogue outputs The type of signals of the two analogue outputs (as current or voltage output) is determined by the selection of the connection pin and the configuration. The meas-urement range is configured in accordance with the selected output type.

Bit 0 0 = analogue output 0 VOLTAGE measure-ment 1 = analogue output 0 CURRENT measure-ment

Bit 1 0 = analogue output 0 measurement range 0 to 10 V or 0 to 20 mA 1 = analogue output 0 measurement range –10 V to +10 V or 4 to 20 mA

Bit 2 0 = analogue output 1 VOLTAGE measure-ment 1 = analogue output 1 CURRENT measure-ment

Bit 3 0 = analogue output 1 measurement range 0 to 10 V or 0 to 20 mA 1 = analogue output 1 measurement range –10 V to +10 V or 4 to 20 mA

Bit 4 Not used Bit 5 Not used Bit 6 Not used Bit 7 Not used

Table 44: Configuration of the analogue outputs

62 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

6. Diagnosis

Diagnosis

6.1 LED displays

64

6.2 Diagnostic telegrams

67

6.3 Evaluating diagnostic data in Step7

76

1073380000/1.3/08.09 Weidmüller t 63

Bluetooth SAI Manual

6.1. LED displays

Assignment of the PROFIBUS, Bluetooth and supply voltage LEDs SAI-AU M12 GW PB/BT 12I SAI-AU M12 BT 16DI SAI-AU M12 BT AI/AO/DI SAI-AU M12 BT 16DI/8DO

BF BT LQ UI1 UI2 - -

- BT LQ UI1 UI2 - -

- BT LQ UI UQ1 UQ2 UQ3

Figure 46: Status LEDs

LED displays of PROFIBUS, Bluetooth and supply voltages

ON = slave exchanging data LED BF

PROFIBUS

green

flashing = transition after SAI is turned on

red ON = error, no data is being exchanged

LED BT blue Flashing: - detectable for all masters

Illuminated: - not detectable, connection already exists

green Flashing: - communication stopped, no answer to polling

Illuminated: - operation, BT connection established

LED LQ green - good reception

red - poor reception

Off - no connection

green ON = UI1 > 18 V DC OFF = UI1 < 18 V DC LED UI1

Power supply red ON = UI1 < 18 V DC OFF = UI1 > 18 V DC

green ON = UI2 > 18 V DC OFF = UI2 < 18 V DC LED UI2

Power supply red ON = UI2 < 18 V DC OFF = UI2 > 18 V DC

green ON = UI > 18 V DC OFF = UI < 18 V DC LED UI

Power supply red ON = UI < 18 V DC OFF = UI > 18 V DC

LED UQ1 green ON = UQ1 > 18 V DC OFF = UQ1 < 18 V DC

64 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

Power supply red ON = UQ1 < 18 V DC OFF = UQ1 > 18 V DC

green ON = UQ2 > 18 V DC OFF = UQ2 < 18 V DC LED UQ2

Power supply red ON = UQ2 < 18 V DC OFF = UQ2 > 18 V DC

green ON = UQ3 > 18 V DC OFF = UQ3 < 18 V DC LED UQ3

Power supply red ON = UQ3 < 18 V DC OFF = UQ3 > 18 V DC

Table 45: LED displays for PROFIBUS and supply voltages

1073380000/1.3/08.09 Weidmüller t 65

Bluetooth SAI Manual

66 Weidmüller t 1073380000/1.3/08.09

The assigned LEDs can be used to detect the status/diagnostics of the digital inputs and digital outputs and the DESINA information. Example of LED assignments based on the SAI-AU M12 BT 16DI

- BT LQ UI1 UI2 - -

Unoccupied LED BT LED LQ LED UI1 LED UI2 Unoccupied Unoccupied

Figure 47: LED assignments for SAI-AU M12 BT 16DI

LED display of the digital input

yellow Status of the digital input ON OFF

Short-circuit at pin 1, sensor voltage

Pin 4 Digital Input

red

Pin 2 Digital input 2 yellow Status of digital input or DESINA diagnostics input ON OFF

DESINA diagnostics red Short-circuit at pin 2, sensor voltage (together with LED pin 4)

Table 46: LED display of the digital inputs

Bluetooth SAI Manual

6.2. Diagnostic telegrams

The diagnostic telegram consists of six bytes of standard diagnostic information and manufacturer diagnostic information. The number of bytes required for the manufacturer’s diagnostics varies from module to module. Standard diagnostics information

Byte 0, station status 1

Bit 0 station_non_exist 1 = station cannot be reached; always "0"

Bit 1 station_not_ready 1 = station is not ready for data exchange

Bit 2 cfg_fault 1 = configuration error with the master

Bit 3 ext_diag 1 = extended diagnostics data is available

Bit 4 not_supported 1 = a requested function is not supported

Bit 5 invalid_slave_response 1 = the slave response was not valid

Bit 6 prm_fault 1 = false or incomplete parameter data

Bit 7 master_lock 1 = parameters are from another master set - access is locked

Byte 1, station status 2

Bit 0 Prm_req 1 = parameter must be transmitted again

Bit 1 Stat_diag 1 = diagnostic data is present

Bit 2 „1“ Slave always sets "1"

Bit 3 WD_ON 1 = The slave has activated the watchdog

Bit 4 freeze_mode 1 = The slave has received the "freeze" control command

Bit 5 sync_mode 1 = The slave has received the "sync" control command

Bit 6 reserved Slave always sets "0"

Bit 7 deactivated 1 = set from master, slave is inactive, slave always sets "0"

Byte 2, station status 3

Bit 0 reserved Slave always sets "0"

Bit 1 reserved Slave always sets "0"

Bit 2 reserved Slave always sets "0"

Bit 3 reserved Slave always sets "0"

Bit 4 reserved Slave always sets "0"

Bit 5 reserved Slave always sets "0"

Bit 6 reserved Slave always sets "0"

Bit 7 ext_overflow 1 = Diagnostic data overflow

1073380000/1.3/08.09 Weidmüller t 67

Bluetooth SAI Manual

Byte 3, Diag. master address

FFH PB address of master FF = Parameter has still not been received from master

02H or the address of the master, which the parameter has set

Byte 4, Ident Number (high byte)

08H High byte of the ident number The ID number of the PROFIBUS device high byte

Byte 5, ident number (low byte)

15H Low byte of the ident number The ID number of the PROFIBUS device low byte

Table 47: Standard diagnostics information

68 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

1073380000/1.3/08.09 Weidmüller t 69

Manufacturer diagnostics information The manufacturer’s diagnostics information can be composed of one or more bytes. The manufacturer determines the amount and their content. For SAI modules, these include various diagnostic information depending on the type of module; a part of this information has to be activated by parameterisation.

An overview of the diagnostic bytes is given below; these bytes are counted after the standard diagnostics information byte 6.

The gateway is structured modularly with up to seven modules. Seven universal modules are established in the diagnostics data so that each module can be added to each gateway position.

Byte 6 Extended diagnostic data: Header

The number of bytes of the manufacturer’s diagnostics, including this byte.

Bits 6+7 0= Device-specific diagnostic

Byte 7 Software version, high byte

High byte, SW version SW version of the PB device, high byte

Byte 8 Software version, low byte

Low byte, SW version SW version of the PB device, low byte

Byte 9 Doubled address on sub-bus module

Bit 0 1= Doubled address, module 1

Bit 1 1= Doubled address, module 2

Bit 2 1= Doubled address, module 3

Bit 3 1= Doubled address, module 4

Bit 4 1= Doubled address, module 5

Bit 5 1= Doubled address, module 6

Bit 6 1= The sub-bus module is detected too much

Bit 7 reserved

Byte 10 Missing sub-bus module

Bit 0 1= Missing module 1

Bit 1 1= Missing module 2

Bit 2 1= Missing module 3

Bit 3 1= Missing module 4

Bit 4 1= Missing module 5

Bit 5 1= Missing module 6

Bit 6 reserved

Bit 7 reserved

Byte 11 Configuration error, QoS

Bluetooth SAI Manual

Bit 0 1= Configuration error, module 1

Bit 1 1= Configuration error, module 2

Bit 2 1= Configuration error, module 3

Bit 3 1= Configuration error, module 4

Bit 4 1= Configuration error, module 5

Bit 5 1= Configuration error, module 6

Bit 6 reserved

Bit 7 reserved

Table 48: Manufacturer's diagnostic information, bytes 6 – 11

Byte 12 Wrong sub-bus module detected

Bit 0 1= Wrong module 1 detected

Bit 1 1= Wrong module 2 detected

Bit 2 1= Wrong module 3 detected

Bit 3 1= Wrong module 4 detected

Bit 4 1= Wrong module 5 detected

Bit 5 1= Wrong module 6 detected

Bit 6 1= Wrong GW module detected

Bit 7 reserved

Byte 13 Poor wireless connection to sub-bus system

Bit 0 1= Poor connection, module 1

Bit 1 1= Poor connection, module 2

Bit 2 1= Poor connection, module 3

Bit 3 1= Poor connection, module 4

Bit 4 1= Poor connection, module 5

Bit 5 1= Poor connection, module 6

Bit 6 1= Communication error, gateway

Bit 7 reserved

Byte 14 LQI sub-bus module 1

LQI Byte Quality of wireless connection, module 1

Byte 15 LQI sub-bus module 2

LQI Byte Quality of wireless connection, module 2

Byte 16 LQI sub-bus module 3

LQI Byte Quality of wireless connection, module 3

Byte 17 LQI sub-bus module 4

70 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

LQI Byte Quality of wireless connection, module 4

Byte 18 LQI sub-bus module 5

LQI Byte Quality of wireless connection, module 5

Byte 19 LQI sub-bus module 6

LQI Byte Quality of wireless connection, module 6

Byte 20 Voltage monitoring, part 1

Bit 0 1= No voltage UI module 1

Bit 1 1= No voltage UQ1 module 1

Bit 2 1= No voltage UQ2 module 1

Bit 3 1= No voltage UQ3 module 1

Bit 4 1= No voltage, UI module 2

Bit 5 1= No voltage UQ1 module 2

Bit 6 1= No voltage UQ2 module 2

Bit 7 1= No voltage UQ3 module 2

Byte 21 Voltage monitoring, part 2

Bit 0 1= No voltage, UI module 3

Bit 1 1= No voltage UQ1 module 3

Bit 2 1= No voltage UQ2 module 3

Bit 3 1= No voltage UQ3 module 3

Bit 4 1= No voltage UI module 4

Bit 5 1= No voltage UQ1 module 4

Bit 6 1= No voltage UQ2 module 4

Bit 7 1= No voltage UQ3 module 4

Table 49: Manufacturer's diagnostic information, bytes 12 – 21

Byte 22 Voltage monitoring, part 3

Bit 0 1= No voltage UI module 5

Bit 1 1= No voltage UQ1 module 5

Bit 2 1= No voltage UQ2 module 5

Bit 3 1= No voltage UQ3 module 5

Bit 4 1= No voltage UI module 6

Bit 5 1= No voltage UQ1 module 6

Bit 6 1= No voltage UQ2 module 6

Bit 7 1= No voltage UQ3 module 6

Byte 23 Voltage monitoring, part 4

1073380000/1.3/08.09 Weidmüller t 71

Bluetooth SAI Manual

Bit 0 1= No voltage, UI gateway

Bit 1 1= No voltage, UQ1 gateway

Bit 2 1= No voltage, UQ2 gateway

Bit 3 1= No voltage, UQ3 gateway

Bit 4 reserved

Bit 5 reserved

Bit 6 reserved

Bit 7 reserved

Table 50: Manufacturer's diagnostic information, bytes 22 – 23

Byte 24 Short circuit on sensor voltage

Bit 0 1= Short circuit on sensor slot 1

Bit 1 1= Short circuit on sensor slot 2

Bit 2 1= Short circuit on sensor slot 3

Bit 3 1= Short circuit on sensor slot 4

Bit 4 1= Short circuit on sensor slot 5

Bit 5 1= Short circuit on sensor slot 6

Bit 6 1= Short circuit on sensor slot 7

Bit 7 1= Short circuit on sensor slot 8

Byte 25 Error message for DESINA characteristic

Bit 0 1= Desina diagnostic on slot 1

Bit 1 1= Desina diagnostic on slot 2

Bit 2 1= Desina diagnostic on slot 3

Bit 3 1= Desina diagnostic on slot 4

Bit 4 1= Desina diagnostic on slot 5

Bit 5 1= Desina diagnostic on slot 6

Bit 6 1= Desina diagnostic on slot 7

Bit 7 1= Desina diagnostic on slot 8

Byte 26 Short circuit on digital output to earth GND

Bit 0 1= Short circuit to earth on slot 1

Bit 1 1= Short circuit to earth on slot 2

Bit 2 1= Short circuit to earth on slot 3

Bit 3 1= Short circuit to earth on slot 4

Bit 4 1= Short circuit to earth on slot 5

Bit 5 1= Short circuit to earth on slot 6

72 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

Bit 6 1= Short circuit to earth on slot 7

Bit 7 1= Short circuit to earth on slot 8

Byte 27 Short circuit on digital output to +24 V DC

Bit 0 1= Short circuit to +24V DC on slot 1

Bit 1 1= Short circuit to +24V DC on slot 2

Bit 2 1= Short circuit to +24V DC on slot 3

Bit 3 1= Short circuit to +24V DC on slot 4

Bit 4 1= Short circuit to +24V DC on slot 5

Bit 5 1= Short circuit to +24V DC on slot 6

Bit 6 1= Short circuit to +24V DC on slot 7

Bit 7 1= Short circuit to +24V DC on slot 8

Byte 28 reserved

Byte 29 reserved

Table 51: Manufacturer's diagnostic information, bytes 24 – 29

1073380000/1.3/08.09 Weidmüller t 73

Bluetooth SAI Manual

After the gateway's device-specific diagnostic bytes, the module-specific diagnostic bytes are then added. In order to save space, one module is detailed as an example. This module would be executed up to seven times for a diagnostic telegram.

Byte x Short-circuit on sensor voltage

Bit 0 1= Short circuit on sensor slot 1

Bit 1 1= Short circuit on sensor slot 2

Bit 2 1= Short circuit on sensor slot 3

Bit 3 1= Short circuit on sensor slot 4

Bit 4 1= Short circuit on sensor slot 5

Bit 5 1= Short circuit on sensor slot 6

Bit 6 1= Short circuit on sensor slot 7

Bit 7 1= Short circuit on sensor slot 8

Byte x+1 Error message for DESINA characteristic

Bit 0 1= Desina diagnostic on slot 1

Bit 1 1= Desina diagnostic on slot 2

Bit 2 1= Desina diagnostic on slot 3

Bit 3 1= Desina diagnostic on slot 4

Bit 4 1= Desina diagnostic on slot 5

Bit 5 1= Desina diagnostic on slot 6

Bit 6 1= Desina diagnostic on slot 7

Bit 7 1= Desina diagnostic on slot 8

Byte x+2 Short circuit on digital output to earth GND

Bit 0 1= Short circuit to earth on slot 1

Bit 1 1= Short circuit to earth on slot 2

Bit 2 1= Short circuit to earth on slot 3

Bit 3 1= Short circuit to earth on slot 4

Bit 4 1= Short circuit to earth on slot 5

Bit 5 1= Short circuit to earth on slot 6

Bit 6 1= Short circuit to earth on slot 7

Bit 7 1= Short circuit to earth on slot 8

Byte x+3 Short circuit on digital output to +24 V DC

Bit 0 1= Short circuit to +24V DC on slot 1

Bit 1 1= Short circuit to +24V DC on slot 2

Bit 2 1= Short circuit to +24V DC on slot 3

Bit 3 1= Short circuit to +24V DC on slot 4

74 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

Bit 4 1= Short circuit to +24V DC on slot 5

Bit 5 1= Short circuit to +24V DC on slot 6

Bit 6 1= Short circuit to +24V DC on slot 7

Bit 7 1= Short circuit to +24V DC on slot 8

Byte x+4 Analogue input range 4–20 mA, 4 mA below

Bit 0 1= 4 mA too low out of range at analogue input 0

Bit 1 1= 4 mA too low out of range at analogue input 1

Bit 2 1= 4 mA too low out of range at analogue input 2

Bit 3 1= 4 mA too low out of range at analogue input 3

Bit 4 … 7 reserved

Byte x+5 Reserved for expansions

reserved

Table 52: Module-specific diagnostic bytes

1073380000/1.3/08.09 Weidmüller t 75

Bluetooth SAI Manual

76 Weidmüller t 1073380000/1.3/08.09

6.3. Evaluating diagnostic data in Step7

Whereas the data for inputs and outputs can be ex-changed and processed directly in Step7 with PROFIBUS via the input and output image, diagnostic data must be read into the application programme with an SFC.

Diagnostics data (slave diagnostics) of a DP slave is read with the SFC 13 "DPNRM_DG".

Figure 48: Diagnostics function block

Input variables:

REQ = 1: Request to read

LADDR: Planned diagnostics address of the DP slave; this can be read in the hardware con-figurator.

Note: The address must be entered in hexadecimal, for example, the diagnostic address 1022 (3FEH) means: LADDR: = W#16#3FE

Output variables:

RET_VAL RET_VAL contains the length of the actual transmitted data.

If an error occurs when the function is being processed, the return value contains an error code.

RECORD Target range for the read diagnostic data.

The minimum length of the data record to be read or the target range is 6.

BUSY = 1 The read operation has not been completed

Table 53: Diagnostics function block

In the example above, 10 bytes following the flag byte M 120.0 are reserved as target range of the diagnostics data for an SAI-AU M12 PB 16DI. These are divided up as follows:

Standard diagnostics information

MB 120 Byte 0 Station status 1

MB 121 Byte 1 Station status 2

MB 122 Byte 2 Station status 3

MB 123 Byte 3 Diag. master address

MB 124 Byte 4 Ident number (high byte)

MB 125 Byte 5 Ident number (low byte)

Bluetooth SAI Manual

Manufacturer diagnostics information

MB 126 Byte 6 The number of bytes of the manufacturer’s diagnostics, in-cluding this byte.

MB 127 Byte 7 MSB software version (high byte)

MB 128 Byte 8 LSB software version (low byte)

MB 129 Byte 9 Short-circuit at +24 V DC sensor voltage

MB 130 Byte 10 Error message for DESINA diagnostics

Table 54: Diagnostics information

Please refer to the Siemens Step7 programming manual as well as the Online Help file for further information.

1073380000/1.3/08.09 Weidmüller t 77

Bluetooth SAI Manual

78 Weidmüller t 1073380000/1.3/08.09

Appendix A: Product Overview

Modules

Modules

SAI-AU M12 GW PB/BT 12I in M12 with 12 digital inputs 1006980000

SAI-AU M12 BT 16DI in M12 with 16 digital inputs 1006940000

SAI-AU M12 BT 16DI/8DO in M12 with 16 digital inputs / 8 digital outputs 1006930000

SAI-AU M12 BT 4AI2AO2DIO in M12 with analogue I/Os and digital I/Os 1006920000 Connector

I/O and AUX connectors

SAIS-4/7 M12 male connector, 4-pole, straight 9457550000

SAISW-4/7 M12 male connector, 4-pole, angled 9457290000

SAIB-4/7 M12 female connector, 4-pole, straight 9457240000

SAIBW-4/7 M12 female connector, 4-pole, angled 9457700000

PROFIBUS connectors

SAISM 5/8S M12 5P B-COD PROFIBUS male connector, straight, B-coded 1784790000

SAIBM 5/8S M12 5P B-COD PROFIBUS female connector, straight, B-coded 1784780000

PROFIBUS terminating resistor

SAIEND PB M12 5P B-COD M12, 5-pole, B-coded 1784770000 Twin plug

Twin plug

SAI-Y-5S- M12/M12 M12 on 2 x M12, with connection for two sensors 1826880000

SAI-Y-4-4/2-4 M12/8 M12 on 2 x M8, with connection for two sensors 1783420000

Table 55: Connectors – product overview

Bluetooth SAI Manual

Cables

General cables Example: Cable length: 3 m

SAIL-M12G-4-3.0U M12 male connector, 4-pole, straight, PUR, 3 m cable 9456100300

SAIL-M12BG-4-3.0U M12 female connector, 4-pole, straight, PUR, 3 m ca-ble

9457730300

SAIL-M12GM12G-4-1.5U M12 male connector, 4-pole, straight on female, M12 straight, PUR, 1.5 m cable

9457190000

SAIL-M12W-4-3.0U M12 male connector, 4-pole, angled, PUR, 3 m cable 1906260300

SAIL-M12BW-4-3.0U M12 female connector, 4-pole, angled, PUR, 3 m cable 9457740300

SAIL-M12GM12G-4-3.0U M12 male connector, 4-pole, straight on female, M12 straight, PUR, 3 m cable

1906300300

SAIL-M8GS-3-3.0U M8 male connector, 3-pole, straight, shielded, PUR, 3 m cable

1824590300

SAIL-M8WS-3-3.0U M8 male connector, 3-pole, angled, shielded, PUR, 3 m cable

1857550300

SAIL-M8GBS-3-3.0U M8 female connector, 3-pole, straight, shielded, PUR, 3 m cable

9457450300

SAIL-M8WBS-3-3.0U M8 female connector, 3-pole, angled, shielded, PUR, 3 m cable

9457380300

SAIL-M8GSM8GS-3-3.0U M8 male connector, straight, on female, M8, straight, 3-pole, shielded, PUR, 3m cable

1824570300

PROFIBUS cables Example: Cable length: 3 m

SAIL-M12G-PB-3.0U M12 male connector, straight, PUR, 3 m cable 1873300300

SAIL-M12GM12G-PB-3.0U M12 male connector, straight on female, M12, straight, PUR, 3 m cable

1873310300

SAIL-M12BG-PB-3.0U M12 female connector, straight, PUR, 3 m cable 1873320300

Table 56: Cables – product overview

Please observe that we are only able to print a small selection of all of our cables

We have a wide variety on offer: • Various lengths: 1.5 m; 3.0 m; 5.0 m; 10,0 m; with more custom lengths on request • Shielded or unshielded • With/without LEDs • Straight/angled • A variety of pole counts

1073380000/1.3/08.09 Weidmüller t 79

Bluetooth SAI Manual

80 Weidmüller t 1073380000/1.3/08.09

• Different cable materials • With/without valve connectors For more detailed information, please refer to our SAI section catalogue. Tools

Cutting

KT 8 Cable Cutter 9002650000

Unsheathing/stripping

CST VARIO Stripping tool 9005700000

STRIPAX for cable stripping 9005000000

MULTI-STRIPAX 6-16 for cable stripping and wire-end ferrule crimping 9202210000

Crimping

PZ 6 Roto for crimping in all positions 9014350000

H-BOX 0.14-0.75QMM Box with wire-end ferrules 0.14 – 0.75 mm2 9025410000

Screwdriver, flat-blade

SD 0.6 x 3.5 x 100 for setting the address range 9008330000

Fastening and screwing

Screwty set For tightening and loosening knurled nuts on con-nectors

1910000000

Screwty set - DM see above, but with torque 1920000000 Accessories

Protective caps

SAI-SK-M12-UNI M12, in black plastic 2330260000

SAI-SK M8 M12, in black plastic 1802760000

Marking tags

ESG 8/13,5/43,3 SAI AU MultiCard labelling sets 1912130000 Testing

Simulation plug

SAIS-T-2/1-K Bridge between pin 1 and pin 2 8569100000

SAIS-T-4/1-K Bridge between pin 1 and pin 4 8726310000

Table 57: Tools and accessories – product overview

Bluetooth SAI Manual

Appendix B: Drilling Templates

Figure 49: Drilling Templates

1073380000/1.3/08.09 Weidmüller t 81

Bluetooth SAI Manual

Appendix C: Converting from Hexadecimal to Decimal

Dec. Hex. Dec. Hex. Dec. Hex. Dec. Hex.

0 00 32 20 64 40 96 60

1 01 33 21 65 41 97 61

2 02 34 22 66 42 98 62

3 03 35 23 67 43 99 63

4 04 36 24 68 44 100 64

5 05 37 25 69 45 101 65

6 06 38 26 70 46 102 66

7 07 39 27 71 47 103 67

8 08 40 28 72 48 104 68

9 09 41 29 73 49 105 69

10 0A 42 2A 74 4A 106 6A

11 0B 43 2B 75 4B 107 6B

12 0C 44 2C 76 4C 108 6C

13 0D 45 2D 77 4D 109 6D

14 0E 46 2E 78 4E 110 6E

15 0F 47 2F 79 4F 111 6F

16 10 48 30 80 50 112 70

17 11 49 31 81 51 113 71

18 12 50 32 82 52 114 72

19 13 51 33 83 53 115 73

20 14 52 34 84 54 116 74

21 15 53 35 85 55 117 75

22 16 54 36 86 56 118 76

23 17 55 37 87 57 119 77

24 18 56 38 88 58 120 78

25 19 57 39 89 59 121 79

26 1A 58 3A 90 5A 122 7A

27 1B 59 3B 91 5B 123 7B

28 1C 60 3C 92 5C 124 7C

29 1D 61 3D 93 5D 125 7D

30 1E 62 3E 94 5E 126 7E

31 1F 63 3F 95 5F 127 7F

Table 58: Converting from Hexadecimal to Decimal

82 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

Appendix D: Configuration of the DESINA inputs

Modules SAI-AU M12 GW PB/BT 12I, SAI-AU M12 BT 16 DI, SAI-AU M12 BT 16DI/8DO First byte in the configuration: Activates the DESINA function Bit 0 with bit 7 OFF = DESINA function deactivated

ON = DESINA function activated

OFF OFF OFF OFF .. .. .. .. 0.. OFF OFF OFF ON .. .. .. .. 1.. OFF OFF ON OFF .. .. .. .. 2.. OFF OFF ON ON .. .. .. .. 3.. OFF ON OFF OFF .. .. .. .. 4.. OFF ON OFF ON .. .. .. .. 5.. OFF ON ON OFF .. .. .. .. 6.. OFF ON ON ON .. .. .. .. 7.. ON OFF OFF OFF .. .. .. .. 8.. ON OFF OFF ON .. .. .. .. 9.. ON OFF ON OFF .. .. .. .. A.. ON OFF ON ON .. .. .. .. B.. ON ON OFF OFF .. .. .. .. C.. ON ON OFF ON .. .. .. .. D.. ON ON ON OFF .. .. .. .. E.. ON ON ON ON .. .. .. .. F..

.. .. .. .. OFF OFF OFF OFF ..0

.. .. .. .. OFF OFF OFF ON ..1

.. .. .. .. OFF OFF ON OFF ..2

.. .. .. .. OFF OFF ON ON ..3

.. .. .. .. OFF ON OFF OFF ..4

.. .. .. .. OFF ON OFF ON ..5

.. .. .. .. OFF ON ON OFF ..6

.. .. .. .. OFF ON ON ON ..7

.. .. .. .. ON OFF OFF OFF ..8

.. .. .. .. ON OFF OFF ON ..9

.. .. .. .. ON OFF ON OFF ..A

.. .. .. .. ON OFF ON ON ..B

.. .. .. .. ON ON OFF OFF ..C

.. .. .. .. ON ON OFF ON ..D

.. .. .. .. ON ON ON OFF ..E

.. .. .. .. ON ON ON ON ..F

0.7 0.6 0.5 0.4 0.3 0.2 0.1 0.0 1.7 1.6 1.5 1.4 1.3 1.2 1.1 1.0

input 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0.0 DESINA 1.7 1.6 1.5 1.4 1.3 1.2 1.1 1.0

Example:

ON OFF OFF OFF .. .. .. .. 8.. .. .. .. .. ON ON OFF OFF ..C Table 59: Configuration of a DESINA function: 0x8C

1073380000/1.3/08.09 Weidmüller t 83

Bluetooth SAI Manual

Appendix E: Configuration of the digital connection points

Modules SAI-AU M12 PB 16DI/8DO Second byte in the configuration: Defines the function of the connection points as input or output Bit 0 with bit 7 OUT = connection to pin 2 is output

IN = connection to pin 2 is input

OUT OUT OUT OUT .. .. .. .. 0.. OUT OUT OUT IN .. .. .. .. 1.. OUT OUT IN OUT .. .. .. .. 2.. OUT OUT IN IN .. .. .. .. 3.. OUT IN OUT OUT .. .. .. .. 4.. OUT IN OUT IN .. .. .. .. 5.. OUT IN IN OUT .. .. .. .. 6.. OUT IN IN IN .. .. .. .. 7.. IN OUT OUT OUT .. .. .. .. 8.. IN OUT OUT IN .. .. .. .. 9.. IN OUT IN OUT .. .. .. .. A.. IN OUT IN IN .. .. .. .. B.. IN IN OUT OUT .. .. .. .. C.. IN IN OUT IN .. .. .. .. D.. IN IN IN OUT .. .. .. .. E.. IN IN IN IN .. .. .. .. F..

.. .. .. .. OUT OUT OUT OUT ..0

.. .. .. .. OUT OUT OUT IN ..1

.. .. .. .. OUT OUT IN OUT ..2

.. .. .. .. OUT OUT IN IN ..3

.. .. .. .. OUT IN OUT OUT ..4

.. .. .. .. OUT IN OUT IN ..5

.. .. .. .. OUT IN IN OUT ..6

.. .. .. .. OUT IN IN IN ..7

.. .. .. .. IN OUT OUT OUT ..8

.. .. .. .. IN OUT OUT IN ..9

.. .. .. .. IN OUT IN OUT ..A

.. .. .. .. IN OUT IN IN ..B

.. .. .. .. IN IN OUT OUT ..C

.. .. .. .. IN IN OUT IN ..D

.. .. .. .. IN IN IN OUT ..E

.. .. .. .. IN IN IN IN ..F

Connection 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0.0 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0.0 Example:

IN IN IN OUT .. .. .. .. E.. .. .. .. .. OUT OUT OUT OUT ..0 Table 60: Establishing the configuration for the digital connection points: 0xE0

84 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

Appendix G: Configuration of analogue outputs

7 6 5 4 3 2 1 0 Measurement range Value range .. .. .. .. .. .. 0 0 Analogue output 0: 0 to 10 V 0 to 2047 .. .. .. .. .. .. 0 1 Analogue output 0: 0 to 20 mA 0 to 4095 .. .. .. .. .. .. 1 0 Analogue output 0: -10 V to +10 V 0 to 4095 .. .. .. .. .. .. 1 1 Analogue output 0: 4 to 20 mA 819 to 4095 .. .. .. .. 0 0 .. .. Analogue output1: 0 to 10 V 0 to 2047 .. .. .. .. 0 1 .. .. Analogue output 1: 0 to 20 mA 0 to 4095 .. .. .. .. 1 0 .. .. Analogue output 1: -10 V to +10 V 0 to 4095 .. .. .. .. 1 1 .. .. Analogue output 1: 4 vbis 20 mA 819 to 4095

Table 61: Configuration of the analogue output

1073380000/1.3/08.09 Weidmüller t 85

Bluetooth SAI Manual

Sources

Web addresses www.weidmueller.com www.profibus.com

Standards IEC 61158-x: Digital data communications for measurement and control – Fieldbus for use in industrial control sys-

tems. IEC 61784-1: Digital Data Communications for Measurement and Control – Part1: Profile Sets for continuous and discrete Manufacturing relative to Fieldbus Use in Industrial Control Systems EN 50170: Universal Field Communication System, Revision A2

86 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

Index

Figure 1: Basic design of an SAI distributor 5 Figure 2: Basic PROFIBUS system configuration 6 Figure 3: Basic PROFIBUS system configuration with subordinate Bluetooth 7 Figure 4: Voltage drop 10 Figure 5: Mounting dimensions for the SAI Active Universal 12 Figure 6: Mounting an SAI distributor 13 Figure 7: Functional earth ‘FE’ connection 13 Figure 8: Attaching markers and tags 14 Figure 9: Bus termination wiring 21 Figure 10: SAI-AU M12 GW PB/BT 12I 22 Figure 11: PROFIBUS address switch 23 Figure 12: Bluetooth address switch 24 Figure 13: Block diagram of the digital input 26 Figure 14: SAI-AU M12 BT 16DI 28 Figure 15: Address switch 29 Figure 16: Block diagram of the digital input 31 Figure 17: View of M12 16DI 31 Figure 18: Sensors with DESINA 32 Figure 19: Sensor without DESINA 32 Figure 20: SAI-AU M12 BT 16DI/8DO 34 Figure 21: Address switch 35 Figure 22: Block diagram of the digital input 37 Figure 23: /A view of M12 16DI 37 Figure 24: Sensor with DESINA 38 Figure 25: Sensor without DESINA 38 Figure 26: Block diagram of the digital outputs 39 Figure 27: Assignment of the 0.5 A and 2 A outputs 39 Figure 28: I/O housing M12 16DI/8DO 39 Figure 29: SAI-AU M12 BT 4AI2AO2DIO 42 Figure 30: Address switch 43 Figure 31: Block diagram of the analogue input 45 Figure 32: Block diagram of the analogue output 45 Figure 31: Block diagram of the digital input 45 Figure 34: /A view of M12 4AI 46 Figure 35: Sensors with DESINA 47 Figure 36: Sensors without DESINA 47 Figure 37: Bitmaps for hardware configurator 51 Figure 38: Installing the GSD file: step 1 53 Figure 39: Installing the GSD file: step 2 53 Figure 40: GSD file catalogue 54 Figure 41: Hardware configurator 55 Figure 42: The gateway slot list 56 Figure 43: Module types 56 Figure 44: Assigning input / output addresses 57 Figure 45: Parameter 58 Figure 46: Status LEDs 64 Figure 47: LED assignments for SAI-AU M12 BT 16DI 66 Figure 48: Diagnostics function block 76 Figure 49: Drilling Templates 81

1073380000/1.3/08.09 Weidmüller t 87

Index

Table 1: Determining the SAI distributor 9 Table 2: Code conversion decimal < - > hexadecimal 15 Table 3: Contact assignment (pin out) of the PROFIBUS connector 20 Table 4: Contact assignment (pin out) of the PROFIBUS female contact socket 20 Table 5: Technical data, PROFIBUS 21 Table 6: SAI-AU M12 GW PB/BT 12I 22 Table 7: Bluetooth gateway addresses 24 Table 8: Contact assignment (pin out) of the power supply connector 25 Table 9: Contact assignment (pin out) of the female power supply connector 25 Table 10: Contact assignment of the digital inputs 26 Table 11: Technical data for the SAI-AU M12 GW PB/BT 12I 27 Table 12: SAI-AU M12 BT 16DI 28 Table 13: Setting the Bluetooth address, SAI 29 Table 14: Contact assignment (pin out) of the power supply connector 30 Table 15: Contact assignment (pin out) of the female power supply connector 30 Table 16: Plug-in jumper positions for the SAI-AU M12 BT 16DI 30 Table 17: Contact assignment (pin out) of the digital input 31 Table 18: Technical data for the SAI-AU M12 BT 16DI 33 Table 19: SAI-AU M12 BT 16DI/8DO 34 Table 20: Setting the Bluetooth address, SAI 35 Table 21: Contact assignment (pin out) of the power supply connector 36 Table 22: Contact assignment (pin out) of the power supply connector 36 Table 23: Plug-in jumper positions for the SAI-AU M12 BT 16DI/8DO 36 Table 24: Contact assignment (pin out) of the digital input 37 Table 25: Technical data for the SAI-AU M12 BT 16DI/8DO 41 Table 26: SAI-AU M12 BT 4AI2AO2DIO 42 Table 27: Setting the Bluetooth address, SAI 43 Table 28: Contact assignment (pin out) of the power supply connector 44 Table 29: Contact assignment (pin out) of the female power supply connector 44 Table 30: Plug-in jumper positions for the SAI-AU M12 BT 4AI2AO2DIO 44 Table 31: Contact assignment (pin out) of the analogue input 45 Table 32: Contact assignment (pin out) of an analogue output 45 Table 33: Contact assignment of the digital inputs 45 Table 34: Technical data for the SAI-AU M12 BT 4AI2AO2DIO 49 Table 35: Overview of the SAI parameters GW 12I 59 Table 36: Overview of SAI parameters, 16DI 59 Table 37: Overview of SAI parameters, 16DI/8DO 59 Table 38: Overview of SAI parameters, 4AI2AO2DIO 60 Table 39: DESINA parameters 61 Table 40: Reversal of input and output 61 Table 41: Behaviour when bus malfunction occurs 61 Table 42: Behaviour when bus malfunction occurs 61 Table 43: Configuration of the analogue inputs 62 Table 44: Configuration of the analogue outputs 62 Table 45: LED displays for PROFIBUS and supply voltages 65 Table 45: LED display of the digital inputs 66 Table 47: Standard diagnostics information 68 Table 48: Manufacturer's diagnostic information, bytes 6 – 11 70 Table 49: Manufacturer's diagnostic information, bytes 12 – 21 71 Table 50: Manufacturer's diagnostic information, bytes 22 – 23 72 Table 51: Manufacturer's diagnostic information, bytes 24 – 29 73 Table 52: Module-specific diagnostic bytes 75 Table 53: Diagnostics function block 76 Table 54: Diagnostics information 77 Table 54: Connectors – product overview 78 Table 55: Cables – product overview 79 Table 56: Tools and accessories – product overview 80 Table 58: Converting from Hexadecimal to Decimal 82 Table 59: Configuration of a DESINA function: 0x8C 83 Table 60: Establishing the configuration for the digital connection points: 0xE0 84

88 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

1073380000/1.3/08.09 Weidmüller t 89

Table 61: Configuration of the analogue output 85

Glossary

Glossary

AC or DC drives

AC or DC motors

Accuracy

Bit accuracy is a measure of the exactness of digital measurement and calculation operations. With an accu-racy of 8 bit, for example, 1 byte corresponds to an accu-racy of 1/(2^8) = 1/256 or 0.390625% steps. This is par-ticularly important when converting from an analogue signal to a digital value if the measurement value of a sensor (temperature, pressure or similar) is to undergo further digital processing.

AI

Please see Analogue input

Analogue input

Analogue input detects analogue signals as voltage sig-nals from 0 to 10 V or as current signals from 0 to 20 mA or 4 to 20 mA; resolution is generally 10 or 12 bit, 16 bit representation.

Analogue output

Analogue input control variable as analogue signal; volt-age signals from 0 to 10 V or -10 V to +10 V or as current signals from 0 to 20 mA or 4 to 20 mA; resolution is gen-erally 10 or 12 bit, representation 16 bit representation.

AO

Please see Analogue output

AUX IN

Power supply, 24 VDC feed in

AUX OUT

Power supply, 24 VDC feed out

Baud rate

The baud rate describes the number of signal codes (symbol) that can be transmitted per second.

Bitmap file

This is an image file or graphic consisting of pixels; with black and white information. Each bit corresponds to an information unit and can consequently code a pixel. For display purposes in the hardware configurator, bitmap files in DIB format with 70 x 40 pixels are recommended.

Bus / power section

This is the section on the SAI to which the Fieldbus and the supply voltage are connected.

BUS IN

PROFIBUS connection module, feed in. It is fully con-nected to Bus OUT.

BUS OUT

PROFIBUS connection, bus feed out. It is fully connected to Bus IN.

Bus termination

Install the bus terminations at the physical beginning and physical end, according to the PROFIBUS standard, with one bus termination each.

Bus termination

An active bus termination must be fitted at the beginning and end of each PROFIBUS segment. The termination consists of a combination of resistances. To function cor-rectly, it requires a 5-V supply voltage that is normally made available by each PROFIBUS device.

Coding A

Special coding for male or female M12 connectors for purposes of recognition and non-reversal. On SAI mod-ules, coding A is utilised for the power supply as well as inputs and outputs. B-coding is specified for the PROFIBUS Fieldbus.

Coding B

Special coding for male or female M12 connectors for purposes of recognition and non-reversal. Coding B is used for the PROFIBUS-DP Fieldbus.

90 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

Configuration

Please see Hardware configuration.

Configuration menu

This is used to enter and configure the hardware of a controller system. Please also see Hardware configuration.

Connector

A plug-in connector connects lines carrying electrical power or signals. The standards regulate the form and the contact assignment of the connector and the corre-sponding mating connector. They also define the electri-cal signals to be transmitted.

DATA A

Data from PROFIBUS is transmitted via a two-core, shielded twisted-pair cable with RS485 characteristics (differential signal transmission). The two wires are des-ignated as DATA A (green wire) and DATA B (red wire).

DATA B

Data from PROFIBUS is transmitted via a two-core, shielded twisted-pair cable with RS485 characteristics (differential signal transmission). The two wires are des-ignated as DATA A (green wire) and DATA B (red wire).

DESINA

Please see Diagnostics input DESINA

DI

Please see Digital input.

Diagnostic telegram

Diagnostic telegrams indicate the status of the PROFIBUS-DP slave. A diagnostic telegram is composed of six bytes of standard diagnostics information as well as the manufacturer’s diagnostics information. The number of bytes required for the manufacturer’s diagnostics var-ies from module to module.

Diagnostics data

Diagnostics data is transmitted in a diagnostics telegram. This information is differentiated between standard diag-nostics information (6 bytes) and vendor diagnostics in-formation, the length of which depends on the vendor.

Diagnostics input DESINA

DESINA is an abbreviation for DistributEd and Standard-ised INstAllation technology for machine tools and manu-facturing systems. DESINA describes the specification for

standardising the electric, hydraulic and pneumatic instal-lation of automated machine tools and manufacturing systems. DESINA diagnostics input supplies diagnostic information in addition to the digital input signal. See also http://www.desina.de.

DIN

German acronym: German Institute for Standardization

DO

Please see Digital output.

DP

Please see PROFIBUS-DP.

EMC

Electromagnetic compatibility describes the freedom from interference of electrical devices with regard to their envi-ronment.

FE

Please see Functional Earth.

Field devices

Field device is a term used to describe all of the devices operated on a Fieldbus. Field devices can be input and output modules (SAIs) as well as drives, controls and human-machine interfaces.

FMS Please see PROFIBUS FMS

Frequency converter

A frequency converter generates an alternating current of a certain frequency from an alternating current of a differ-ent frequency and may also alter the voltage; it makes it possible to adjust rotational speeds. In particular for three-phase motors, frequency converters are an eco-nomic form of control.

Functional earth

The functional earth serves to discharge compensating and interference currents in order to guarantee EMC characteristics. According to VDE 0100, the functional earth is not the same as the protective earth; it is forbid-den to use it as the protective earth.

GSD file (Device Data Base File)

A GSD file (Device Data Base File) contains a description of all of the DP slave-specific characteristics.

1073380000/1.3/08.09 Weidmüller t 91

The format of GSD files is defined in the standard IEC 61784-1:2002 Ed1 CP 3/1.

Hardware configuration

All devices and parameters of a control system are de-fined in a hardware configuration.

Hardware configurator

Special software that is normally manufacturer-specific and used for creating and downloading a hardware con-figuration.

Hexadecimal code

Numeric code that represents information from 1 digit, 4 bit, decimal numbers 0 to 15 using digits 0 to 9 together in conjunction with the letters A to F.

High byte

The high byte is the most-significant byte of a term con-sisting of two or more bytes, for example, a software ver-sion number. Please see Low byte.

I/O section

This is the section of the SAI where the digital or ana-logue sensors and actuators are connected.

Ident. number

Identification of a PROFIBUS-DP device. Assigned by the PROFIBUS User Organisation (PUO).

IEC

International Electro-technical Commission

IEC 61158

Digital Data Communications for Measurement and Con-trol – Field bus for use in industrial control systems. Part 1: Overview and guidance for the IEC 61158 series Part 2: Physical layer specification and service definition Part 3: Data link service definition Part 4: Data link protocol specification Part 5: Application layer service definition Part 6: Application layer protocol specification

Industry PC

A standard PC adapted to suit harsh production environ-ments.

Input addresses

External signals in a PLC are exchanged via digital or analogue inputs or outputs. These are controlled by the PLC programme via the addresses. The addresses can be a combination of station address, module address and connection address. It is possible that the addresses can only be accessed byte for byte or word for word.

ISO

International Standard Organization

J1

Designation for a special jumper field used to link supply voltages.

Jumpers

Jumpers are used to configure electronic sub-assemblies or set operating parameters that are carried out either rarely or only once during initial commissioning proce-dures. The jumper is usually made of a small metal plate and a plastic housing. It is plugged into two pins which results in an electrical contact being created via the metal plates. Generally, that results in the function of the hardware com-ponent being activated, deactivated or configured.

LED

Light Emitting Diode – used to indicate signal status of the digital inputs and outputs as well as the status of the voltage supply and Fieldbus.

LED BF

Red/green LED for indicating status on PROFIBUS Green ON = slave exchanging data Green flashing = transition after SAI is turned on Red = error, no data is being exchanged

LED UI

Red/green LED for indicating the status of supply voltage UQ1 Functions as LED U1

LED UI1

Red/green LED for indicating the status of supply voltage U1 Green ON = UI1 > 18 V DC Green OFF = UI1 < 18 V DC Red ON = UI1 < 18 V DC Red OFF = UI1 > 18 V DC

92 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

LED UI2

Red/green LED for indicating the status of supply voltage U2 Functions as LED U1

LED UL

Two green LEDs for indicating module power supply; also serve to illuminate the address section.

LED UQ1

Red/green LED for indicating the status of supply voltage UQ1 Functions as LED U1

LED UQ2

Red/green LED for indicating the status of supply voltage UQ2 Functions as LED U1

LED UQ3

Red/green LED for indicating the status of supply voltage UQ3 Functions as LED U1

Low byte

Least-significant byte of a term consisting of two or more bytes, for example, a software version number. Please see High byte.

M12

Metric thread with a thread diameter of 12 mm.

M12 socket (female connector)

A socket with cavities containing contacts for creating an electrical connection. Sockets are also referred to as fe-male connectors. The mating partner of a socket is re-ferred to as the plug or male connector. The socket outlet can be described as a special form of socket.

M8

Metric thread with a thread diameter of 8 mm.

Output addresses

External signals in a PLC are exchanged via digital or analogue inputs or outputs. These are controlled by the PLC programme via the addresses. The addresses can be a combination of station address, module address and connection address. It sometimes possible that the ad-dresses can only be accessed byte for byte or word for word.

Output interval

Please see sampling period.

Parameter

Parameters describe the technical characteristics of tech-nical devices. Weidmüller SAI parameters serve to acti-vate the DESINA diagnostic input, to define plug-in con-nectors as inputs or outputs, as well as define the ana-logue measurement ranges as a current or voltage input.

Parameterisation

Term used to describe assigning parameters with a parameterisation or programming tool.

PE

Please see Protective earth.

Peripheral devices

These are devices outside of a central processing unit; with Fieldbus systems, this also applies to all devices in the Fieldbus.

PLC

PLC is the acronym for Programmable Logic Controller

Plug and Play

Sometimes written as Plug 'n' Play or Plug & Play; it de-scribes the characteristics of modern, mostly peripheral devices that are immediately available for use without having to first install a programme.

Polling

The generally recognised term for "to poll" or query. The poll function is an operating mode of Fieldbus devices in a Fieldbus system.

Power supply

Electrical loads require a voltage supply to provide the power. In control systems, the supply voltage used is 24 VDC. Please see voltage range.

Power supply

Voltage with which the device is supplied. The power supply in automation engineering is usually 18 to 24 VDC.

PROFIBUS

(PROcess FIeld BUS) is a part of the international stan-dards IEC 61158 and IEC 61784. Physically, PROFIBUS is either an electrical network based on a shielded, two-

1073380000/1.3/08.09 Weidmüller t 93

conductor cable or an optical network based on a fibre optics cable.

PROFIBUS guidelines

Vendor-independent compatibility is guaranteed by tech-nical guidelines to ensure implementation of PROFIBUS technology. The technical guidelines are published and distributed centrally by the PROFIBUS User Organisation (PUO) to underline the fact that these are effectively a standard. Diverse PROFIBUS guidelines are available, for example: the "Optical transfer technology for PROFIBUS".

PROFIBUS slave

PROFIBUS slaves exchange data cyclically with a PROFIBUS master. In addition, parameterization, con-figuration and, in the case of a malfunction, diagnostic data is transmitted. Typical PROFIBUS slaves include connection terminals, repeaters, gateways, communica-tion terminals, valve blocks and others.

PROFIBUS User Organisation

More than 260 vendors and users of the standardised communication system PROFIBUS have come together in the registered association PROFIBUS User Organisa-tion (PUO) to jointly support further technical improve-ments and establish the use of the technology interna-tionally. The PROFIBUS User Organisation is a regis-tered association. Membership is open to any company or research facility anywhere in the world.

PROFIBUS-DP

This is a special application for automating factory pro-duction. DP = Decentralised Periphery

PROFIBUS-DP address

With the PROFIBUS address you determine at which address your SAI distributor will be identified on PROFIBUS-DP.

PROFIBUS-FMS

This is utilised for the universal, object-oriented, cyclic and acyclic exchange of data at a medium speed. FMS is particularly suitable for exchanging data between intelli-gent slaves such as PCs and PLCs. PROFIBUS-DP and PROFIBUS-PA are special variants. FMS = Fieldbus Message Specification

PROFIBUS-Master

PROFIBUS-DP differentiates between Class 1 and Class 2 masters. The Class 2 master is utilised for parameteri-

zation of PROFIBUS slaves by means of software; it is mainly used to set the PROFIBUS address. As well as exchanging data with the slave, the Class 1 master sup-plies the PROFIBUS slave with configuration and pa-rameter data.

PROFIBUS-PA

This is used to control field devices by means of a proc-ess control system in the processing industry. This variant of PROFIBUS is used in hazardous areas (Ex-Zone 0 & 1). Low currents only are used so that no sparks flash-over in the case of a malfunction; it uses a slower data transmission rate. PA= Process Automation

Protective earth

Protective earth conductors are often used in electrical equipment and cable lines. This is also known as the pro-tective lead, earth, earth connection or PE (protective earth). The task of the protective earth conductor in electrical systems is to protect human beings from dangerous touch voltages as well as to protect the system from damage. The PE conductor is fitted in such a manner that there is an electrical connection between the outer metal housing of the electrical equipment (for example lamps, fridges, motors). Should a fault occur and the electrical supply voltage comes into contact with the exterior of a piece of electrical equipment, the short-circuit to ground via the PE conduc-tor should ensure that the voltage between the housing of the respective electrical equipment and the ground (with which humans and animals are generally in contact) is reduced to a harmless level. At the same time, the high short-circuit currents trip the fuse. That ensures that the electrical equipment with the fault is disconnected extremely quickly from the supply voltage. German regulations stipulate that the PE conductor must be identifiable by the colour combination green/yellow.

Repeater

Repeaters are necessary in order to create a CAN net-work with more than 32 stations or establish a larger net-work extension. The repeater represents the beginning of a new segment in which the maximum number of stations can be used or the maximum extension is defined.

Rotary coding switch

94 Weidmüller t 1073380000/1.3/08.09

Bluetooth SAI Manual

Requiring a minimum of space, rotary coding switches are used to make settings. These settings are usually coded in decimal or hexadecimal formats.

RS-485

As a so-called differential voltage interface, the RS-485 interface operates with +5V (high) and 0V (low) by which the non-inverted signal is transmitted via one wire and the inverted (or negative) signal via the other wire. As distor-tions have the same effect on both signals, the difference between both signals remains (virtually) the same and can be used for evaluation purposes. An RS-485 connection constitutes a serial data transmis-sion, which means the bits are transmitted one after the other on a line.

SAI

The acronym SAI stands for Sensor – Actuator – Inter-face. It is a compact-designed distributor or collector of signal lines.

SAI distributor

Please see SAI.

Sampling period

The sampling period determines in which time interval an analogue input is converted. The sampling period for the SAI-AU AI/AO/DI can be set between 5 ms and 250 ms.

Segment

The PROFIBUS network consists of one or more seg-ments. The maximum extension of a segment depends on the baud rate being used. Up to 32 PROFIBUS sta-tions can be connected in each segment.

Settings section

Range on the SAI in which the configuration of the hard-ware is carried out; for example, the module address.

Shielding

Shielding is necessary to protect cables from radiated noise disturbances.

Simatic® Step7

STEP 7 is the current programming software used for the Simatic S7 PLC family of products from Siemens; this is a family of controls for PLC based automation systems. In accordance with IEC 61131-3, the basic version of STEP 7 includes the programming languages: • CFS - Continuous Function Chart

• LD – Ladder Diagram • STL – Statement List

Slave

Please see PROFIBUS slave.

Temperature coefficient

The temperature coefficient is a relative change to a physical variable resulting from a change in temperature of 1 K (Kelvin).

Torx screwdriver

Torx is an improvement to the cross-head screw and hexagon-socket (Allen) as a tool receiving socket, for example in counter-sunk screws. The profile is similar to a six-pointed star with rounded off points and corners – more or less a wave form. The com-pany Camcar belongs to the Textron Group and is the inventor and patent holder. In the meantime, the Torx patent has run out and the hexalobular internal drive fea-ture has been incorporated in international standards.

T-piece

A t-piece is used to provide uninterrupted feed of the supply voltage and the Fieldbus. T-pieces are connected straight onto the consumer load and interconnected with the supply voltage or Fieldbus by means of male and female connectors.

Transmission rate

Please see Baud rate.

Voltage range

The voltage range of the 24 VDC supply voltage is 18 VDC to 30 VDC.

X1

Rotary switch for setting the CAN address, in hexadeci-mal format, low byte from 01H to 0FH.

X10

Rotary switch for setting the CAN address, in hexadeci-mal format, high byte from 10H to F0H.

Y-Plugs

Y-plugs separate two digital signals, inputs or outputs applied to an M12 connector in two digital signals.

1073380000/1.3/08.09 Weidmüller t 95

96 Weidmüller t 1073380000/1.3/08.09

www.weidmueller.com

Ägypten Argentinien Aserbeidschan Australien

Kanada Kasachstan Katar Kolumbien Kroatien Kuwait Lettland Libanon Litauen Luxemburg Malaysia Mazedonien Mexiko Montenegro Neuseeland Niederlande Norwegen Österreich Oman Paraguay Peru Philippinen Polen Portugal Rumänien Russland Saudi-Arabien Schweden Schweiz Serbien Singapur

Slowakei Slowenien Spanien Südafrika Südkorea Syrien Taiwan Thailand Tschechien Türkei Ukraine Ungarn Uruguay USA VAE Venezuela Vietnam Weißrussland

Weidmüller is the leading manufacturer of electrical con-nection components for data and power transmissions.

We develop, produce and sell customer-oriented solutions which cover the full scope of the Weidmüller product line. As an OEM supplier, our company sets standards world-wide for electrical connection technology and systems.

The product portfolio includes terminal blocks, PCB and plug-in connectors, protected component assemblies, Industrial Ethernet components as well as relay couplers through to power supplies and surge protection modules that can be supplied with all types of connections. The programme is rounded off with materials for installation and marking of electrical equipment, basic I/O compo-nents as well as tools. Weidmüller products are used chiefly in the electrical cabinet and in field wiring. Our comprehensive service offering makes Weidmüller even more attractive for our customer.

Weidmüller Interface GmbH & Co. KG Postfach 3030 32720 Detmold Klingenbergstraße 16 32758 Detmold, Germany Telephone + 49 (0) 5231 14-0 Fax +49 (0) 5231 14-2083 E-mail [email protected] Order number: Internet www.weidmueller.com 1073380000