101627739 ABB Electrical Installation Handbook 6th Edition2010

download 101627739 ABB Electrical Installation Handbook 6th Edition2010

of 548

Transcript of 101627739 ABB Electrical Installation Handbook 6th Edition2010

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    1/547

    Technical guide - 6th edition 2010

    Electrical installation handbook

    Protection, control and electrical devices

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    2/547

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    3/547

    First edition 2003Second edition 2004Third edition 2005Fourth edition 2006Fith edition 2007Sixth edition 2010

    Published by ABB SACE

    via Baioni, 35 - 24123 Bergamo (Italy)

    All rights reserved

    Electrical installation handbookProtection, control and electrical devices

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    4/547

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    5/547

    Electrical installation handbookProtection, control and electrical devices

    General aspects

    Part 1Protection and control devices

    Part 2Electrical devices

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    6/547

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    7/547

    Index

    Introduction ...............................................................................................................6

    1 Standards1.1 General aspects..............................................................................................71.2 IEC Standards or electrical installation ..........................................................19

    General aspects

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    8/547

    6 Protection, control and electrical devices | ABB

    Introduction

    Scope and objectives

    The scope o this electrical installation handbook is to provide the designer anduser o electrical plants with a quick reerence, immediate-use working tool. This

    is not intended to be a theoretical document, nor a technical catalogue, but, inaddition to the latter, aims to be o help in the correct defnition o equipment,in numerous practical installation situations.

    The dimensioning o an electrical plant requires knowledge o dierent actorsrelating to, or example, installation utilities, the electrical conductors and othercomponents; this knowledge leads the design engineer to consult numerousdocuments and technical catalogues. This electrical installation handbook, ho-wever, aims to supply, in a single document, tables or the quick defnition o themain parameters o the components o an electrical plant and or the selectiono the protection devices or a wide range o installations. Some application

    examples are included to aid comprehension o the selection tables.

    Electrical installation handbook users

    The electrical installation handbook is a tool which is suitable or all those who areinterested in electrical plants: useul or installers and maintenance techniciansthrough brie yet important electrotechnical reerences, and or sales engineersthrough quick reerence selection tables.

    Validity o the electrical installation handbook

    Some tables show approximate values due to the generalization o the selec-

    tion process, or example those regarding the constructional characteristics oelectrical machinery. In every case, where possible, correction actors are givenor actual conditions which may dier rom the assumed ones. The tables arealways drawn up conservatively, in avour o saety; or more accurate calcu-lations, the use o DOCWin sotware is recommended or the dimensioning oelectrical installations.

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    9/547

    ABB | Protection, control and electrical devices 7

    1 Standards

    1.1 General aspects

    In each technical feld, and in particular in the electrical sector, a conditionsufcient (even i not necessary) or the realization o plants according to the

    status o the art and a requirement essential to properly meet the demandso customers and o the community, is the respect o all the relevant laws andtechnical standards.Thereore, a precise knowledge o the standards is the undamental premiseor a correct approach to the problems o the electrical plants which shall bedesigned in order to guarantee that acceptable saety level which is neverabsolute.

    Juridical Standards

    These are all the standards rom which derive rules o behavior or the juridical

    persons who are under the sovereignty o that State.

    Technical Standards

    These standards are the whole o the prescriptions on the basis o whichmachines, apparatus, materials and the installations should be designed, ma-nuactured and tested so that efciency and unction saety are ensured.The technical standards, published by national and international bodies, arecircumstantially drawn up and can have legal orce when this is attributed bya legislative measure.

    Application elds Electrotechnics and Mechanics, Ergonomics

    ElectronicsTelecommunications

    and Saety

    International Body IEC ITU ISO

    European Body CENELEC ETSI CEN

    This technical collection takes into consideration only the bodies dealing with electrical and electronictechnologies.

    IEC International Electrotechnical Commission

    The International Electrotechnical Commission (IEC) was ofcially ounded in1906, with the aim o securing the international co-operation as regardsstandardization and certifcation in electrical and electronic technologies. Thisassociation is ormed by the International Committees o over 40 countries allover the world.The IEC publishes international standards, technical guides and reports whichare the bases or, in any case, a reerence o utmost importance or any nationaland European standardization activity.IEC Standards are generally issued in two languages: English and French.In 1991 the IEC has ratifed co-operation agreements with CENELEC (Europeanstandardization body), or a common planning o new standardization activitiesand or parallel voting on standard drats.

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    10/547

    8 Protection, control and electrical devices | ABB

    1 Standards

    CENELEC European Committee or Electrotechnical Standardization

    The European Committee or Electrotechnical Standardization (CENELEC) wasset up in 1973. Presently it comprises 31 countries (Austria, Belgium, Bulgaria,

    Cyprus, Croatia, Czech Republic, Denmark, Estonia, Finland, France, Germany,Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta,Netherlands, Norway, Portugal, Poland, Romania, Slovakia, Slovenia, Spain,Sweden, Switzerland, United Kingdom) and cooperates with 12 afliates (Albania,Belarus, Georgia, Bosnia and Herzegovina, Tunisia, Former Yugoslav Republico Macedonia, Serbia, Libia, Montenegro, Turkey, Ukraine and Israel) which havefrst maintained the national documents side by side with the CENELEC onesand then replaced them with the Harmonized Documents (HD).There is a dierence between EN Standards and Harmonization Documents(HD): while the frst ones have to be accepted at any level and without additionsor modifcations in the dierent countries, the second ones can be amendedto meet particular national requirements.EN Standards are generally issued in three languages: English, French andGerman.From 1991 CENELEC cooperates with the IEC to accelerate the standardspreparation process o International Standards.CENELEC deals with specifc subjects, or which standardization is urgentlyrequired.When the study o a specifc subject has already been started by the IEC, theEuropean standardization body (CENELEC) can decide to accept or, when-ever necessary, to amend the works already approved by the Internationalstandardization body.

    EC DIRECTIVES FOR ELECTRICAL EQUIPMENT

    Among its institutional roles, the European Community has the task o promul-gating directives which must be adopted by the dierent member states andthen transposed into national law.Once adopted, these directives come into juridical orce and become a re-erence or manuacturers, installers, and dealers who must ulfll the dutiesprescribed by law.Directives are based on the ollowing principles:harmonizationislimitedtoessentialrequirements;

    onlytheproductswhichcomplywiththeessentialrequirementsspeciedbythe directives can be marketed and put into service;

    theharmonizedstandards,whosereferencenumbersarepublishedintheOfcial Journal o the European Communities and which are transposedinto the national standards, are considered in compliance with the essentialrequirements;

    theapplicabilityoftheharmonizedstandardsorofothertechnicalspecications

    is acultative and manuacturers are ree to choose other technical solutionswhich ensure compliance with the essential requirements;

    amanufacturercanchooseamongthedifferentconformityevaluationproce-dure provided by the applicable directive.

    The scope o each directive is to make manuacturers take all the necessarysteps and measures so that the product does not aect the saety and healtho persons, animals and property.

    1.1 General aspects

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    11/547

    ABB | Protection, control and electrical devices 9

    1 Standards

    Low Voltage Directive 2006/95/CE

    The Low Voltage Directive reers to any electrical equipment designed or useat a rated voltage rom 50 to 1000 V or alternating current and rom 75 to1500 V or direct current.In particular, it is applicable to any apparatus used or production, conversion,transmission, distribution and use o electrical power, such as machines,transormers, devices, measuring instruments, protection devices and wiringmaterials.The ollowing categories are outside the scope o this Directive:electricalequipmentforuseinanexplosiveatmosphere;

    electricalequipmentforradiologyandmedicalpurposes;

    electricalpartsforgoodsandpassengerlifts;

    electricalenergymeters;

    plugsandsocketoutletsfordomesticuse;

    electricfencecontrollers;radio-electricalinterference;

    specializedelectricalequipment,foruseonships,aircraftorrailways,which

    complies with the saety provisions drawn up by international bodies in whichthe Member States participate.

    Directive EMC 2004/108/CE (Electromagnetic Compatibility)

    The Directive on electromagnetic compatibility regards all the electrical and elec-tronic apparatus as well as systems and installations containing electrical and/or electronic components. In particular, the apparatus covered by this Directive

    are divided into the ollowing categories according to their characteristics:domesticradioandTVreceivers;

    industrialmanufacturingequipment;

    mobileradioequipment;

    mobileradioandcommercialradiotelephoneequipment;

    medicalandscienticapparatus;

    informationtechnologyequipment(ITE);

    domesticappliancesandhouseholdelectronicequipment;

    aeronauticalandmarineradioapparatus;

    educationalelectronicequipment;

    telecommunicationsnetworksandapparatus;

    radioandtelevisionbroadcasttransmitters;

    lightsanduorescentlamps.

    The apparatus shall be so constructed that:a) the electromagnetic disturbance it generates does not exceed a level allowing

    radio and telecommunications equipment and other apparatus to operateas intended;

    b) the apparatus has an adequate level o intrinsic immunity to electromagneticdisturbance to enable it to operate as intended.

    An apparatus is declared in conormity to the provisions at points a) and b) whenthe apparatus complies with the harmonized standards relevant to its productamily or, in case there arent any, with the general standards.

    1.1 General aspects

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    12/547

    10 Protection, control and electrical devices | ABB

    1 Standards

    When the CE marking is afxed on a product, it represents a declaration o themanuacturer or o his authorized representative that the product in questionconorms to all the applicable provisions including the conormity assessmentprocedures. This prevents the Member States rom limiting the marketing andputting into service o products bearing the CE marking, unless this measureis justifed by the proved non-conormity o the product.

    Flow diagram or the conormity assessment procedures established by the Directive

    2006/95/CE on electrical equipment designed or use within particular voltage range:

    Manuacturer

    Technical ile

    The manuacturerdraw up the technicaldocumentationcovering the design,manuacture andoperation o theproduct

    EC declaration oconormity

    The manuacturerguarantees and declaresthat his products are inconormity to the technicaldocumentation and to thedirective requirements

    ASDC008045F0201

    Naval type approval

    The environmental conditions which characterize the use o circuit breakers oron-board installations can be dierent rom the service conditions in standardindustrial environments; as a matter o act, marine applications can requireinstallation under particular conditions, such as:- environments characterized by high temperature and humidity, including salt-mist atmosphere (damp-heat, salt-mist environment);- on board environments (engine room) where the apparatus operate in thepresence o vibrations characterized by considerable amplitude and duration.

    In order to ensure the proper unction in such environments, the shipping re-gisters require that the apparatus has to be tested according to specifc typeapproval tests, the most signifcant o which are vibration, dynamic inclination,humidity and dry-heat tests.

    CE conormity marking

    The CE conormity marking shall indicate conormity to all the obligations im-posed on the manuacturer, as regards his products, by virtue o the EuropeanCommunity directives providing or the afxing o the CE marking.

    1.1 General aspects

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    13/547

    ABB | Protection, control and electrical devices 11

    1 Standards

    ABB SACE circuit-breakers (Tmax-Emax) are approved by the ollowing ship-ping registers:

    RINA Registro Italiano Navale Italian shipping register

    DNV Det Norske Veritas Norwegian shipping register BV Bureau Veritas French shipping register

    GL Germanischer Lloyd German shipping register

    LRs Lloyds Register o Shipping British shipping register

    ABS American Bureau o Shipping American shipping register

    It is always advisable to ask ABB SACE as regards the typologies and the per-ormances o the certifed circuit-breakers or to consult the section certifcatesin the website http://bol.it.abb.com.

    Marks o conormity to the relevant national and

    international Standards

    The international and national marks o conormity are reported in the ollowingtable, or inormation only:

    OVE

    COUNTRY Symbol Mark designation Applicability/Organization

    EUROPE Mark o compliance with theharmonized European standardslisted in the ENEC Agreement.

    AUSTRALIA AS Mark Electrical and non-electricalproducts.It guarantees compliance withSAA (Standard Association o

    Australia).

    AUSTRALIA S.A.A. Mark Standards Association o Australia(S.A.A.).

    The Electricity Authority o NewSouth Wales Sydney Australia

    AUSTRIA Austrian Test Mark Installation equipment andmaterials

    1.1 General aspects

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    14/547

    12 Protection, control and electrical devices | ABB

    1 Standards

    COUNTRY Symbol Mark designation Applicability/Organization

    AUSTRIA VE IdentifcationThread

    Cables

    BELGIUM CEBEC Mark Installation materials and electricalappliances

    BELGIUM CEBEC Mark Conduits and ducts, conductors

    andexiblecords

    BELGIUM Certifcation oConormity

    Installation material and electricalappliances (in case there are noequivalent national standards orcriteria)

    CANADA CSA Mark Electrical and non-electricalproducts.

    This mark guarantees compliancewith CSA (Canadian Standard

    Association)

    CHINA CCC Mark This mark is required or a widerange o manuactured productsbeore being exported to or soldin the Peoples Republic o Chinamarket.

    Czech Republic EZU Mark Electrotechnical Testing Institute

    SlovakiaRepublic

    EVPU Mark Electrotechnical Research andDesign Institute

    1.1 General aspects

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    15/547

    ABB | Protection, control and electrical devices 13

    1 Standards

    COUNTRY Symbol Mark designation Applicability/Organization

    CROATIA KONKAR Electrical Engineering Institute

    DENMARK DEMKOApproval Mark

    Low voltage materials.This mark guarantees thecompliance o the product withthe requirements (saety) o theHeavy Current Regulations

    FINLAND Saety Mark

    o the ElektriskaInspektoratet

    Low voltage material.

    This mark guarantees thecompliance o the product withthe requirements (saety) o theHeavy Current Regulations

    FRANCE ESC Mark Household appliances

    FRANCE NF Mark Conductors and cables Con-duits and ducting Installationmaterials

    FRANCE NF IdentifcationThread

    Cables

    FRANCE NF Mark Portable motor-operated tools

    FRANCE NF Mark Household appliances

    1.1 General aspects

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    16/547

    14 Protection, control and electrical devices | ABB

    1 Standards

    geprfteSicherheit

    MARK

    OFCONFO

    RM

    ITY

    I.I.R .S.

    COUNTRY Symbol Mark designation Applicability/Organization

    GERMANY VDE Mark For appliances and technicalequipment, installation accessori-es such as plugs, sockets, uses,wires and cables, as well as othercomponents (capacitors, earthingsystems, lamp holders and elec-tronic devices)

    GERMANY VDEIdentifcation Thread

    Cables and cords

    GERMANY VDE Cable Mark For cables, insulated cords, instal-

    lation conduits and ducts

    GERMANY VDE-GS Markor technicalequipment

    Saety mark or technicalequipment to be afxed ater theproduct has been tested and cer-tifed by the VDE Test Laboratoryin Oenbach; the conormity markis the mark VDE, which is grantedboth to be used alone as well asin combination with the mark GS

    HUNGARY MEEI Hungarian Institute or Testingand Certifcation o ElectricalEquipment

    JAPAN JIS Mark Mark which guarantees complian-ce with the relevant JapaneseIndustrial Standard(s).

    IRELAND IIRS Mark Electrical equipment

    IRELAND IIRS Mark Electrical equipment

    1.1 General aspects

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    17/547

    ABB | Protection, control and electrical devices 15

    1 Standards

    KEUR

    B

    AP

    PROV

    ED

    TO

    SINGAPORES

    TAND

    AR

    D

    MARCA

    DECON

    FORMIDADAN

    ORMAS

    UNE

    COUNTRY Symbol Mark designation Applicability/Organization

    ITALY IMQ Mark Mark to be afxed on electricalmaterial or non-skilled users;it certifes compliance with theEuropean Standard(s).

    NORWAY Norwegian ApprovalMark

    Mandatory saety approval or lowvoltage material and equipment

    NETHERLANDS KEMA-KEUR General or all equipment

    POLAND KWE Electrical products

    RUSSIA Certifcation o Con-ormity

    Electrical and non-electrical pro-ducts. It guarantees compliancewith national standard (Gosstan-dard o Russia)

    SINGAPORE SISIR Electrical and non-electricalproducts

    SLOVENIA SIQ Slovenian Institute o Quality andMetrology

    SPAIN AEE Electrical products.The mark is under the control othe Asociacin ElectrotcnicaEspaola (Spanish Electrotechni-

    cal Association)

    1.1 General aspects

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    18/547

    16 Protection, control and electrical devices | ABB

    1 Standards

    CER

    TIFICATION TRADEM

    ARK

    COUNTRY Symbol Mark designation Applicability/Organization

    SPAIN AENOR Asociacin Espaola de Normali-zacin y Certifcacin.

    (Spanish Standarization andCertifcation Association)

    SWEDEN SEMKOMark

    Mandatory saety approval or lowvoltage material and equipment.

    SWITZERLAND Saety Mark Swiss low voltage material subject

    to mandatory approval (saety).

    SWITZERLAND Cables subject to mandatoryapproval

    SWITZERLAND SEV Saety Mark Low voltage material subject tomandatory approval

    UNITEDKINGDOM

    ASTA Mark Mark which guarantees com-pliance with the relevant BritishStandards

    UNITEDKINGDOM

    BASEC Mark Mark which guarantees complian-ce with the British Standards orconductors, cables and ancillaryproducts.

    UNITEDKINGDOM

    BASECIdentifcation Thread

    Cables

    1.1 General aspects

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    19/547

    ABB | Protection, control and electrical devices 17

    1 Standards

    APP

    ROVEDT

    OBRITISHS

    TAND

    ARD

    AN

    INDEP

    ENDENTLABO

    RATOR

    Y

    TESTIN

    GFORPUBLI

    C SAFET

    Y

    L I S T E D

    (Product Name)

    (Control Number)

    COUNTRY Symbol Mark designation Applicability/Organization

    UNITEDKINGDOM

    BEABSaety Mark

    Compliance with the British Stan-dards or household appliances

    UNITEDKINGDOM

    BSISaety Mark

    Compliance with the BritishStandards

    UNITED

    KINGDOM

    BEAB

    Kitemark

    Compliance with the relevant

    British Standards regardingsaety and perormances

    U.S.A. UNDERWRITERSLABORATORIESMark

    Electrical and non-electricalproducts

    U.S.A. UNDERWRITERSLABORATORIESMark

    Electrical and non-electricalproducts

    U.S.A. UL Recognition Electrical and non-electricalproducts

    CEN CEN Mark Mark issued by the EuropeanCommittee or Standardization(CEN): it guarantees compliancewith the European Standards.

    CENELEC Mark Cables

    1.1 General aspects

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    20/547

    18 Protection, control and electrical devices | ABB

    1 Standards

    COUNTRY Symbol Mark designation Applicability/Organization

    CENELEC Harmonization Mark Certifcation mark providingassurance that the harmonizedcable complies with the relevantharmonized CENELEC Standards identifcation thread

    EC Ex EUROPEA Mark Mark assuring the compliancewith the relevant European Stan-dards o the products to be usedin environments with explosionhazards

    CEEel CEEel Mark Mark which is applicable to some

    household appliances (shavers,electric clocks, etc).

    EC - Declaration o Conormity

    The EC Declaration o Conormity is the statement o the manuacturer, whodeclares under his own responsibility that all the equipment, procedures orservices reer and comply with specifc standards (directives) or other normative

    documents.The EC Declaration o Conormity should contain the ollowing inormation:nameandaddressofthemanufacturerorbyitsEuropeanrepresentative;

    descriptionoftheproduct;

    referencetotheharmonizedstandardsanddirectivesinvolved;

    anyreferencetothetechnicalspecicationsofconformity;

    thetwolastdigitsoftheyearofafxingoftheCEmarking;

    identicationofthesigner.

    A copy o the EC Declaration o Conormity shall be kept by the manuactureror by his representative together with the technical documentation.

    1.1 General aspects

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    21/547

    ABB | Protection, control and electrical devices 19

    1 Standards

    1.2 IEC Standards or electrical

    installation

    STANDARD YEAR TITLE

    IEC 60027-1 1992 Letter symbols to be used in ectricaltechnology - Part 1: General

    IEC 60034-1 2010 Rotating electrical machines - Part 1: Rating

    and perormance

    IEC 60617-DB-Snapshot 2010 Graphical symbols or diagrams

    IEC 61082-1 2006 Preparation o documents used in

    electrotechnology - Part 1: Rules

    IEC 60038 2009 IEC standard voltages

    IEC 60664-1 2007 Insulation coordination or equipment within

    low-voltage systems - Part 1: Principles, requi-

    rements and tests

    IEC 60909-0 2001 Short-circuit currents in three-phase a.c. sy-

    stems - Part 0: Calculation o currents

    IEC 60865-1 1993 Short-circuit currents - Calculation o eects -

    Part 1: Denitions and calculation methods

    IEC 60076-1 2000 Power transormers - Part 1: General

    IEC 60076-2 1993 Power transormers - Part 2: Temperature rise

    IEC 60076-3 2000 Power transormers - Part 3: Insulation levels,

    dielectric tests and external clearances in air

    IEC 60076-5 2006 Power transormers - Part 5: Ability to with-

    stand short circuit

    IEC/TR 60616 1978 Terminal and tapping markings or power

    transormers

    IEC 60076-11 2004 Power transormers - Part 11: Dry-type tran-

    sormers

    IEC 60445 2010 Basic and saety principles or man-machine

    interace, marking and identication - Identi-

    cation o equipment terminals and conductorterminations

    IEC 60073 2002 Basic and saety principles or man-machine

    interace, marking and identication Coding

    or indicators and actuators

    IEC 60447 2004 Basic and saety principles or man-machine

    interace, marking and identication - Actuating

    principles

    IEC 60947-1 2007 Low-voltage switchgear and controlgear - Part

    1: General rules

    IEC 60947-2 2009 Low-voltage switchgear and controlgear - Part

    2: Circuit-breakers

    The ollowing pages list the main Standards which reer to the most common

    low voltage electrical applications and report their publication years.The Standards might have been amended, but the relevant amendaments arenot mentioned here.

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    22/547

    20 Protection, control and electrical devices | ABB

    1 Standards

    STANDARD YEAR TITLE

    IEC 60947-3 2008 Low-voltage switchgear and controlgear - Part

    3: Switches, disconnectors, switch-disconnec-

    tors and use-combination units

    IEC 60947-4-1 2009 Low-voltage switchgear and controlgear - Part

    4-1: Contactors and motor-starters Electro-

    mechanical contactors and motor-starters

    IEC 60947-4-2 2007 Low-voltage switchgear and controlgear - Part

    4-2: Contactors and motor-starters AC semi-

    conductor motor controllers and starters

    IEC 60947-4-3 2007 Low-voltage switchgear and controlgear -

    Part 4-3: Contactors and motor-starters AC

    semiconductor controllers and contactors or

    non-motor loads

    IEC 60947-5-1 2009 Low-voltage switchgear and controlgear - Part

    5-1: Control circuit devices and switchingelements - Electromechanical control circuit

    devices

    IEC 60947-5-2 2007 Low-voltage switchgear and controlgear - Part

    5-2: Control circuit devices and switching

    elements Proximity switches

    IEC 60947-5-3 2005 Low-voltage switchgear and controlgear - Part

    5-3: Control circuit devices and switching

    elements Requirements or proximity devices

    with dened behaviour under ault conditions

    IEC 60947-5-4 2002 Low-voltage switchgear and controlgear -

    Part 5: Control circuit devices and switching

    elements Section 4: Method o assessing theperormance o low energy contacts. Special

    tests

    IEC 60947-5-5 2005 Low-voltage switchgear and controlgear - Part

    5-5: Control circuit devices and switching

    elements - Electrical emergency stop device

    with mechanical latching unction

    IEC 60947-5-6 1999 Low-voltage switchgear and controlgear - Part5-6: Control circuit devices and switchingelements DC interace or proximity sensorsand switching ampliers (NAMUR)

    IEC 60947-6-1 2005 Low-voltage switchgear and controlgear - Part

    6-1: Multiple unction equipment Transerswitching equipment

    IEC 60947-6-2 2007 Low-voltage switchgear and controlgear - Part6-2: Multiple unction equipment - Control andprotective switching devices (or equipment)(CPS)

    IEC 60947-7-1 2009 Low-voltage switchgear and controlgear - Part7: Ancillary equipment - Section 1: Terminalblocks or copper conductors

    1.2 IEC standards or electrical installation

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    23/547

    ABB | Protection, control and electrical devices 21

    1 Standards

    STANDARD YEAR TITLE

    IEC 60947-7-2 2009 Low-voltage switchgear and controlgear - Part7: Ancillary equipment - Section 2: Protec-tive conductor terminal blocks or copper

    conductorsIEC 61439-1 2009 Low-voltage switchgear and controlgear

    assemblies - Part 1: General rules

    IEC 60439-2 2005 Low-voltage switchgear and controlgearassemblies - Part 2: Particular requirements orbusbar trunking systems (busways)

    IEC 60439-3 2001 Low-voltage switchgear and controlgearassemblies - Part 3: Particular requirementsor low-voltage switchgear and controlgearassemblies intended to be installed in placeswhere unskilled persons have access or theiruse - Distribution boards

    IEC 60439-4 2004 Low-voltage switchgear and controlgearassemblies - Part 4: Particular requirements orassemblies or construction sites (ACS)

    IEC 60439-5 2006 Low-voltage switchgear and controlgearassemblies - Part 5: Particular requirementsor assemblies or power distribution in publicnetworks

    IEC 61095 2009 Electromechanical contactors or householdand similar purposes

    IEC/TR 60890 1987 A method o temperature-rise assessmentby extrapolation or partially type-testedassemblies (PTTA) o low-voltage switchgearand controlgear

    IEC/TR 61117 1992 A method or assessing the short-circuitwithstand strength o partially type-testedassemblies (PTTA)

    IEC 60092-303 1980 Electrical installations in ships. Part 303:Equipment - Transormers or power andlighting

    IEC 60092-301 1980 Electrical installations in ships. Part 301:Equipment - Generators and motors

    IEC 60092-101 2002 Electrical installations in ships - Part 101:

    Denitions and general requirements

    IEC 60092-401 1980 Electrical installations in ships. Part 401:Installation and test o completed installation

    IEC 60092-201 1994 Electrical installations in ships - Part 201:System design - General

    IEC 60092-202 1994 Electrical installations in ships - Part 202:System design - Protection

    1.2 IEC standards or electrical installation

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    24/547

    22 Protection, control and electrical devices | ABB

    1 Standards

    STANDARD YEAR TITLE

    IEC 60092-302 1997 Electrical installations in ships - Part 302: Low-voltage switchgear and controlgear assemblies

    IEC 60092-350 2008 Electrical installations in ships - Part 350:

    General construction and test methods opower, control and instrumentation cables orshipboard and oshore applications

    IEC 60092-352 2005 Electrical installations in ships - Part 352:Choice and installation o electrical cables

    IEC 60364-5-52 2009 Electrical installations o buildings - Part 5-52:Selection and erection o electrical equipment Wiring systems

    IEC 60227 Polyvinyl chloride insulated cables o ratedvoltages up to and including 450/750 V

    2007 Part 1: General requirements

    2003 Part 2: Test methods1997 Part 3: Non-sheathed cables or xed wiring

    1997 Part 4: Sheathed cables or xed wiring

    2003 Part 5: Flexible cables (cords)

    2001 Part 6: Lit cables and cables or fexibleconnections

    2003 Part 7: Flexible cables screened andunscreened with two or more conductors

    IEC 60228 2004 Conductors o insulated cables

    IEC 60245 Rubber insulated cables - Rated voltages up toand including 450/750 V

    2008 Part 1: General requirements

    1998 Part 2: Test methods

    1994 Part 3: Heat resistant silicone insulated cables

    2004 Part 4: Cord and fexible cables

    1994 Part 5: Lit cables

    1994 Part 6: Arc welding electrode cables

    1994 Part 7: Heat resistant ethylene-vinyl acetaterubber insulated cables

    2004 Part 8: Cords or applications requiring highfexibility

    IEC 60309-2 2005 Plugs, socket-outlets and couplers or indu-strial purposes - Part 2: Dimensional interchan-geability requirements or pin and contact-tubeaccessories

    IEC 61008-1 2010 Residual current operated circuit-breakerswithout integral overcurrent protection orhousehold and similar uses (RCCBs) - Part 1:General rules

    IEC 61008-2-1 1990 Residual current operated circuit-breakerswithout integral overcurrent protection orhousehold and similar uses (RCCBs). Part 2-1:

    Applicability o the general rules to RCCBsunctionally independent o line voltage

    1.2 IEC standards or electrical installation

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    25/547

    ABB | Protection, control and electrical devices 23

    1 Standards

    STANDARD YEAR TITLE

    IEC 61008-2-2 1990 Residual current operated circuit-breakerswithout integral overcurrent protection orhousehold and similar uses (RCCBs). Part 2-2:

    Applicability o the general rules to RCCBsunctionally dependent on line voltage

    IEC 61009-1 2010 Residual current operated circuit-breakers withintegral overcurrent protection or householdand similar uses (RCBOs) - Part 1: Generalrules

    IEC 61009-2-1 1991 Residual current operated circuit-breakers withintegral overcurrent protection or householdand similar uses (RCBOs) Part 2-1: Applicabil-ity o the general rules to RCBOs unctionallyindependent o line voltage

    IEC 61009-2-2 1991 Residual current operated circuit-breakers withintegral overcurrent protection or household

    and similar uses (RCBOs) - Part 2-2: Applica-bility o the general rules to RCBOs unctional-ly dependent on line voltage

    IEC 60670-1 2002 Boxes and enclosures or electrical accesso-ries or household and similar xed electricalinstallations - Part 1: General requirements

    IEC 60669-2-1 2009 Switches or household and similar xedelectrical installations - Part 2-1: Particularrequirements Electronic switches

    IEC 60669-2-2 2006 Switches or household and similar xedelectrical installations - Part 2: Particular requi-rements - Section 2: Remote-control switches

    (RCS)IEC 60669-2-3 2006 Switches or household and similar xed

    electrical installations - Part 2-3: Particularrequirements Time-delay switches (TDS)

    IEC 60079-10-1 2009 Explosive atmospheres Part 10 -1: Cassifcation

    o area - explosive gas atmospheres

    IEC 60079-14 2007 Explosive atmospheres Part 14: Electrical

    installation design, selection and erection

    IEC 60079-17 2007 Electrical apparatus or explosive gas

    atmospheres - Part 17: Inspection and

    maintenance o electrical installations in

    hazardous areas (other than mines)

    IEC 60269-1 2009 Low-voltage uses - Part 1: General

    requirements

    IEC 60269-2 2010 Low-voltage uses. Part 2: Supplementary

    requirements or uses or use by authorized

    persons (uses mainly or industrial application)

    examples o standardized system o uses A to J

    1.2 IEC standards or electrical installation

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    26/547

    24 Protection, control and electrical devices | ABB

    1 Standards

    STANDARD YEAR TITLE

    IEC 60269-3 2010 Low-voltage uses - Part 3-1: Supplementary

    requirements or uses or use by unskilled

    persons (uses mainly or household and similar

    applications) - Sections I to IV: examples ostandardized system o uses A to F

    IEC 60127-1/10 Miniature uses -

    2006 Part 1: Denitions or miniature uses and

    general requirements or miniature use-links

    2010 Part 2: Cartridge use-links

    1988 Part 3: Sub-miniature use-links

    2005 Part 4: Universal Modular Fuse-Links (UMF)

    Through-hole and surace mount types

    1988 Part 5: Guidelines or quality assessment o

    miniature use-links

    1994 Part 6: Fuse-holders or miniature cartridge

    use-links

    2001 Part 10: User guide or miniature uses

    EC 60364-1 2005 Low-voltage electrical installations

    Part 1: Fundamental principles, assessment o

    general characteristics, denitions

    IEC 60364-4-41 2005 Low-voltage electrical installations

    Part 4-41: Protection or saety - Protection

    against electric shock

    IEC 60364-4-42 2010 Electrical installations o buildings

    Part 4-42: Protection or saety - Protection

    against thermal eects

    IEC 60364-4-43 2008 Electrical installations o buildings

    Part 4-43: Protection or saety - Protection

    against overcurrent

    IEC 60364-4-44 2007 Electrical installations o buildings

    Part 4-44: Protection or saety - Protection

    against voltage disturbances and

    electromagnetic disturbances

    IEC 60364-5-51 2005 Electrical installations o buildings

    Part 5-51: Selection and erection o electrical

    equipment Common rules

    IEC 60364-5-52 2009 Electrical installations o buildingsPart 5-52: Selection and erection o electrical

    equipment Wiring systems

    IEC 60364-5-53 2002 Electrical installations o buildings

    Part 5-53: Selection and erection o electrical

    equipment Isolation, switching and control

    IEC 60364-5-54 2002 Electrical installations o buildings

    Part 5-54: Selection and erection o electrical

    equipment Earthing arrangements, protective

    conductors and protective bonding conductors

    1.2 IEC standards or electrical installation

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    27/547

    ABB | Protection, control and electrical devices 25

    1 Standards

    STANDARD YEAR TITLE

    IEC 60364-5-55 2008 Electrical installations o buildings

    Part 5-55: Selection and erection o electrical

    equipment Other equipment

    IEC 60364-6 2006 Electrical installations o buildings

    Part 6: Verication

    IEC 60364-7 20042010 Electrical installations o buildings

    Part 7: Requirements or special installations

    or locations

    IEC 60529 2001 Degrees o protection provided by enclosures

    (IP Code)

    IEC 61032 1997 Protection o persons and equipment by

    enclosures - Probes or verication

    IEC/TR 61000-1-1 1992 Electromagnetic compatibility (EMC)

    Part 1: General - Section 1: application and

    interpretation o undamental denitions andterms

    IEC/TR 61000-1-3 2002 Electromagnetic compatibility (EMC)

    Part 1-3: General - The eects o high-altitude

    EMP (HEMP) on civil equipment and systems

    1.2 IEC standards or electrical installation

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    28/547

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    29/547

    Index

    1 Protection and control devices

    1.1 Circuit-breaker nameplates................................281.2 Main defnitions .................................................311.3 Types o releases ...............................................35

    1.3.1 Thermomagnetic releases andonly magnetic releases ...........................35

    1.3.2 Electronic releases ..................................381.3.3 Residual current devices .........................44

    2 General characteristics

    2.1 Electrical characteristics o circuit breakers ........502.2 Trip curves.........................................................58

    2.2.1 Sotware Curves 1.0 ............................592.2.2 Trip curves o thermomagnetic

    releases ..................................................602.2.3 Functions o electronic releases ..............65

    2.3 Limitation curves ...............................................902.4 Specifc let-through energy curves.....................932.5 Temperature derating ........................................942.6 Altitude derating ..............................................106

    2.7 Electrical characteristics o switchdisconnectors .................................................1073 Protection coordination

    3.1 Protection coordination ..................................1143.2 Discrimination tables .......................................1233.3 Back-up tables ................................................1563.4 Coordination tables between

    circuit breakers and switch disconnectors .......162

    Part 1Protection and control devices

    4 Special applications

    4.1 Direct current networks ...................................1664.2 Networks at particular requencies; 400 Hz

    and 16 2/3 Hz .................................................1834.2.1 400 Hz networks ..................................1834.2.2 16 2/3 Hz networks ..............................196

    4.3 1000 Vdc and 1000 Vac networks ..................2004.4 Automatic Transer Switches ...........................212

    5 Switchboards

    5.1 Electrical switchboards ....................................2145.2 MNS switchboards ..........................................2295.3 ArTu distribution switchboards .........................230

    Annex A: Protection against short-circuit eects

    inside low-voltage switchboards .........................233Annex B: Temperature rise evaluation

    according to IEC 60890 ..........................................243Annex C: Application examples:

    Advanced protection unctions with PR123/P and

    PR333/P releases ..................................................257

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    30/547

    28 Protection and control devices | ABB

    1 Protection and control devices

    Moulded-case circuit-breaker: SACE Tmax XT

    1.1 Circuit-breaker nameplates

    IEC 60947-2

    ABB SACEItaly

    on

    off

    160XT1B

    I

    In = 160ATEST

    SACE Tmax

    Rated operationalvoltage Ue

    Tmax XT1B 160

    Ue (V)

    Icu (kA)

    Ics

    Cat A

    (% Icu)

    Ue=690V AC/500V DC Ui=800V Uimp=8kV S/N:

    230

    25

    100 100

    18

    415 525

    100

    6 3

    100

    690

    2P in series50-60Hz

    250

    18

    100

    Tmax

    Cat A

    Rated impulsewithstand voltageUimp; i.e. the peakvalue o impulsevoltage which thecircuit-breaker canwithstand underspeciied testconditions.

    Rated insulationvoltage Ui; i.e. themaximum r.m.s. valueo voltage which thecircuit-breaker iscapable owithstanding at thesupply requencyunder speciied testconditions.

    Rated ultimate short-circuit breaking capacity(Icu) and rated serviceshort-circuit breakingcapacity (Ics) atdierent voltage values.

    According to theinternational StandardIEC 60947-2, the circuitbreakers can be dividedinto CategoryA, i.e.without a speciiedshort-time withstandcurrent rating, orCategory B, i.e. with aspeciied short-timewithstand current rating.

    CE marking aixed onABB circuit-breakers toindicate compliancewith the ollowing CEdirectives:Low Voltage Directive(LVD) no. 2006/95/CEElectromagneticCompatibility Directive(EMC) no. 89/336 EEC.

    Compliance with theinternationalStandardIEC 60947-2:Low-Voltage

    switchgear andcontrolgear-Circuit-breakers.

    Size1

    2

    3

    4

    5

    6

    7

    CIRCUIT-BREAKER TYPE

    Size160 A250 A

    Rated ultimate short-circuitbreaking capacity at 415 Vac

    B = 18 kA (XT1)C = 25 kA (XT1)N = 36 kAS = 50 kAH = 70 kAL = 120 kA (XT2-XT4)

    V= 150 kA (XT2-XT4)

    Size1

    2

    3

    4

    SeriesXT

    Seriel number

    In rated current

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    31/547

    ABB | Protection and control devices 29

    1 Protection and control devices

    Moulded-case circuit-breaker: Tmax T

    ASDC0

    08046F0201

    Tmax T2L160

    Ue (V)

    Icu (kA)

    Ics

    Cat A

    (% Icu)

    Iu=160A Ue=690V Ui=800V Uimp=8kV IEC 60947-2

    230

    150

    75 75

    85

    400/415 440

    75

    75 50

    75

    500 690

    10

    75

    250

    85

    75

    500

    85

    75

    Made in Italyby ABB SACE

    2 P 3 Pin series50-60Hz

    Rated impulsewithstand voltageUimp; i.e. the peakvalue of impulsevoltage which thecircuit-breaker canwithstand underspecified testconditions.

    Rated uninterruptedcurrent Iu

    Rated operationalvoltage Ue

    Rated insulationvoltage Ui; i.e. themaximum r.m.s. valueof voltage which thecircuit-breaker iscapable ofwithstanding at thesupply frequencyunder specified testconditions.

    Rated ultimate short-circuit breaking capacity(Icu) and rated serviceshort-circuit breakingcapacity (Ics) atdifferent voltage values.

    According to theinternational StandardIEC 60947-2, the circuitbreakers can be dividedinto CategoryA, i.e.without a specifiedshort-time withstandcurrent rating, orCategory B, i.e. with aspecified short-time

    withstand current rating.

    CE marking affixed onABB circuit-breakers toindicate compliancewith the following CEdirectives:Low Voltage Directive(LVD) no. 2006/95/CEElectromagneticCompatibility Directive(EMC) no. 89/336 EEC.

    Compliance with theinternationalStandardIEC 60947-2:Low-Voltageswitchgear andcontrolgear-Circuit-breakers.

    Size123

    4567

    CIRCUIT-BREAKER TYPE

    Rateduninterrupted

    current160 A250 A320 A400 A630 A800 A1000 A

    1250 A1600 A

    Rated ultimate short-circuitbreaking capacity at 415 Vac

    B = 16 kAC = 25 kAN = 36 kAS = 50 kAH = 70 kAL = 85 kA (for T2)L = 120 kA (for T4-T5-T7)L = 100 kA (for T6)

    V= 150 kA (for T7)V= 200 kA

    Size1234567

    SeriesT

    1.1 Circuit breaker nameplates

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    32/547

    30 Protection and control devices | ABB

    1 Protection and control devices

    Air circuit-breaker: Emax

    ASDC0

    08048F0201

    SeriesE

    SizeX1

    1

    2

    3

    4

    6

    Rated ultimate short-circuitbreaking capacity at 415 Vac

    B = 42 kAN = 65 kA (50 kA E1)S = 75 kA (85 kA E2)H = 100 kAL = 130 kA (150 kA X1)

    V= 150 kA (130 kA E3)

    CIRCUIT-BREAKER TYPE

    Rateduninterrupted

    current

    SACE E3V 32Iu=3200A Ue=690VIcw=85kA x 1s

    Cat B ~ 50-60 Hz IEC 60947-2made in Italy byABB-SACEUe

    Icu

    Ics

    (V)

    (kA)

    (kA)

    230

    130

    100

    415

    130

    100

    440

    130

    100

    525

    100

    85

    690

    100

    85

    Rated uninterruptedcurrent Iu

    Rated operationalvoltage Ue

    According to theinternational StandardIEC 60947-2, the circuit-breakers can be dividedinto CategoryA, i.e.without a speciied short-time withstand currentrating, or Category B, i.e.with a speciied short-time

    withstand current rating.

    CE marking aixed onABB circuit-breakers toindicate compliancewith the ollowing CEdirectives:Low Voltage Directive(LVD) no. 2006/95/CEElectromagneticCompatibility Directive

    (EMC) no. 89/336 EEC.

    Rated short-timewithstand current Icw;i.e. the maximumcurrent thatthe circuit-breaker cancarry during aspeciied time.

    Compliance with theinternational StandardIEC 60947-2:Low-Voltageswitchgear andcontrolgear-Circuit-breakers.

    Rated ultimateshort-circuitbreaking capacity(Icu) and ratedservice short-circuit breakingcapacity (Ics) atdierent voltagevalues.

    630 A800 A

    1000 A1250 A1600 A2000 A2500 A3200 A

    4000 A5000 A6300 A

    1.1 Circuit breaker nameplates

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    33/547

    ABB | Protection and control devices 31

    1 Protection and control devices

    The main defnitions regarding LV switchgear and controlgear are included in the

    international Standards IEC 60947-1, IEC 60947-2 and IEC 60947-3.

    Main characteristics

    Circuit-breaker

    A mechanical switching device, capable o making, carrying and breaking cur-rents under normal circuit conditions and also making, carrying or a specifedtime and breaking currents under specifed abnormal circuit conditions suchas those o short-circuit.

    Current-limiting circuit-breaker

    A circuit-breaker with a break-time short enough to prevent the short-circuit

    current reaching its otherwise attainable peak value.Plug-in circuit-breaker

    A circuit-breaker which, in addition to its interrupting contacts, has a set ocontacts which enable the circuit-breaker to be removed.

    Withdrawable circuit-breaker

    A circuit-breaker which, in addition to its interrupting contacts, has a set oisolating contacts which enable the circuit-breaker to be disconnected romthe main circuit, in the withdrawn position, to achieve an isolating distance inaccordance with specifed requirements.

    Moulded-case circuit-breaker

    A circuit-breaker having a supporting housing o moulded insulating materialorming an integral part o the circuit-breaker.

    Disconnector

    A mechanical switching device which, in the open position, complies with therequirements specifed or the isolating unction.

    Release

    A device, mechanically connected to a mechanical switching device, whichreleases the holding means and permits the opening or the closing o theswitching device.

    1.2 Main denitions

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    34/547

    32 Protection and control devices | ABB

    1 Protection and control devices

    Fault types and currents

    Overload

    Operating conditions in an electrically undamaged circuit which cause an

    over-current.Short-circuit

    The accidental or intentional connection, by a relatively low resistance orimpedance, o two or more points in a circuit which are normally at dierentvoltages.

    Residual current (I)

    Itisthevectorialsumofthecurrentsowinginthemaincircuitofthecircuit-

    breaker.

    Rated perormances

    Voltages and requencies

    Rated operational voltage (Ue)

    A rated operational voltage o an equipment is a value o voltage which, combi-ned with a rated operational current, determines the application o the equipmentand to which the relevant tests and the utilization categories are reerred to.

    Rated insulation voltage (Ui)

    The rated insulation voltage o an equipment is the value o voltage to whichdielectric tests voltage and creepage distances are reerred. In no case themaximum value o the rated operational voltage shall exceed that o the rated

    insulation voltage.Rated impulse withstand voltage (U

    imp)

    The peak value o an impulse voltage o prescribed orm and polarity which theequipment is capable o withstanding without ailure under specifed conditionso test and to which the values o the clearances are reerred.

    Rated frequency

    The supply requency or which an equipment is designed and to which theother characteristic values correspond.

    Currents

    Rated uninterrupted current (In)

    The rated uninterrupted current or a circuit-breaker is a value o current, thatthe circuit-breaker can carry during uninterrupted service.

    Rated residual operating current (In)

    It is the r.m.s. value o a sinusoidal residual operating current assigned to theCBR by the manuacturer, at which the CBR shall operate under specifedconditions.

    Perormances under short-circuit conditions

    1.2 Main defnitions

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    35/547

    ABB | Protection and control devices 33

    1 Protection and control devices

    Rated making capacity

    The rated making capacity o an equipment is a value o current, stated by themanuacturer, which the equipment can satisactorily make under specifedmaking conditions.

    Rated breaking capacityThe rated breaking o an equipment is a value o current, stated by the manu-acturer, which the equipment can satisactorily break, under specifed breakingconditions.

    Rated ultimate short-circuit breaking capacity (Icu)

    The rated ultimate short-circuit breaking capacity o a circuit-breaker is themaximum short-circuit current value which the circuit-breaker can break twice(in accordance with the sequence O t CO), at the corresponding ratedoperational voltage. Ater the opening and closing sequence the circuit-breakeris not required to carry its rated current.

    Rated service short-circuit breaking capacity (Ics)The rated service short-circuit breaking capacity o a circuit-breaker is themaximum short-circuit current value which the circuit-breaker can break th-ree times in accordance with a sequence o opening and closing operations(O - t - CO - t CO) at a defned rated operational voltage (U

    e) and at a defned

    power actor. Ater this sequence the circuit-breaker is required to carry itsrated current.

    Rated short-time withstand current (Icw

    )

    The rated short-time withstand current is the current that the circuit-breaker inthe closed position can carry during a specifed short time under prescribed

    conditions o use and behaviour; the circuit-breaker shall be able to carry thiscurrent during the associated short-time delay in order to ensure discriminationbetween the circuit-breakers in series.

    Rated short-circuit making capacity (Icm

    )

    The rated short-circuit making capacity o an equipment is the value o short-circuit making capacity assigned to that equipment by the manuacturer or therated operational voltage, at rated requency, and at a specifed power-actoror ac.

    1.2 Main defnitions

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    36/547

    34 Protection and control devices | ABB

    1 Protection and control devices

    Utilization categories

    The utilization category o a circuit-breaker shall be stated with reerence towhether or not it is specifcally intended or selectivity by means o an intentional

    time delay with respect to other circuit-breakers in series on the load side, undershort-circuit conditions (Table 4 IEC 60947-2).

    Category A - Circuit-breakers not specifcally intended or selectivity undershort-circuit conditions with respect to other short-circuit protective devices inseries on the load side, i.e. without a short-time withstand current rating.

    Category B - Circuit-breakers specifcally intended or selectivity under short-circuit conditions with respect to other short-circuit protective devices in serieson the load side, i.e. with and intentional short-time delay provided or selec-tivity under short-circuit conditions. Such circuit-breakers have a short-time

    withstand current rating.A circuit-breaker is classifed in category B i its Icw

    is higher than (Table 3 IEC60947-2):

    12In or 5 kA, whichever is the greater or In 2500A30 kA or In > 2500A

    Electrical and mechanical durability

    Mechanical durability

    The mechanical durability o an apparatus is expressed by the number o

    no-load operating cycles (each operating cycle consists o one closing andopening operation) which can be eected beore it becomes necessary toservice or replace any o its mechanical parts (however, normal maintenancemay be permitted).

    Electrical durability

    The electrical durability o an apparatus is expressed by the number o on-loadoperating cycles and gives the contact resistance to electrical wear under theservice conditions stated in the relevant product Standard.

    1.2 Main defnitions

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    37/547

    ABB | Protection and control devices 35

    1 Protection and control devices

    1.3 Types o releases

    1.3.1 THERMOMAGNETIC RELEASES AND MAGNETIC ONLY RELEASES

    The thermomagnetic releases use a bimetal and an electromagnet to detectoverloads and short-circuits; they are suitable to protect both alternating and

    direct current networks.

    A circuit-breaker must control and protect, in case o aults or malunctioning,the connected elements o a plant. In order to perorm this unction, aterdetection o an anomalous condition, the release intervenes in a defnite time

    by opening the interrupting part.The protection releases ftted with ABB SACE moulded-case and air circuit-breakers can control and protect any plant, rom the simplest ones to thosewith particular requirements, thanks to their wide setting possibilities o boththresholds and tripping times.Among the devices sensitive to overcurrents, the ollowing can be conside-red:

    thermomagneticreleasesandmagneticonlyreleases;

    microprocessor-basedreleases;

    residualcurrentdevices.

    The choice and adjusting o protection releases are based both on the requi-rements o the part o plant to be protected, as well as on the coordinationwith other devices; in general, discriminating actors or the selection are therequired threshold, time and curve characteristic.

    The ollowing table shows the types o thermo-magnetic and magnetic only tripunits available or SACE Tmax XT and Tmax T circuit-breakers.

    CBsthermomagnetic releases

    MF MA TMD TMA TMGXT1 - - - -XT2

    XT3 - -XT4 - -

    Legenda

    MF Fixed magnetic only releases

    MA Adjustable magnetic only releases

    TMG Thermomagnetic release or generator protection

    TMD Thermomagnetic release with adjustable thermal and fxed magnetic threshold

    TMA Thermomagnetic release with adjustable thermal and magnetic threshold

    SACE Tmax XT

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    38/547

    36 Protection and control devices | ABB

    1 Protection and control devices

    MCCBs XT1 XT2 XT3 XT4

    160 160 250 250

    1,6

    TMD

    2

    2,5

    3,2

    4

    5

    6,3

    8

    10

    12.5

    16

    TMD

    TMD

    TMGTMD

    20

    25

    32

    40

    TMA

    TMG

    TMA

    50

    63

    TMD

    TMG

    80

    100

    125

    160200

    225 -

    250 TMD/TMG

    In Iu

    Legenda

    MF Fixed magnetic only releases

    MA Adjustable magnetic only releases

    TMG Thermomagnetic release or generator protection

    TMD Thermomagnetic release with adjustable thermal and fxed magnetic threshold

    TMA Thermomagnetic release with adjustable thermal and magnetic threshold

    MCCBs XT2 XT3 XT4

    160 250 250

    1

    MF2

    4

    8,5

    10

    MA

    12,5 MF

    20

    MA

    32

    52

    80

    100

    MA125

    160

    200

    In Iu

    Power distribution Motor protection

    1.3 Types o releases

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    39/547

    ABB | Protection and control devices 37

    1 Protection and control devices

    MCCBs T1 T2 T3 T4 T5 T6

    160 160 250 250 400 630 630 800

    1,6

    TMD

    2

    2,53,2

    4

    5

    6,3

    8

    10

    12.5

    16

    TMF

    TMD

    TMD

    TMG

    20 TMD TMD25

    TMD

    TMG

    32 TMD TMD

    40TMD

    TMGTMG

    50 TMD TMD

    63

    TMD

    TMG TMD

    TMG

    80

    TMA

    100

    125

    160200

    250

    320 TMATMG TMA

    TMG400

    500

    630 TMA

    800 TMA

    In Iu

    MCCBs T2 T3 T4

    160 250 250

    1

    MF

    1,62

    2,5

    3,2

    4

    5

    6,5

    8,510 MA

    11

    12,5

    20 MA

    25 MA

    32

    MA52

    MA

    80

    100

    MA125

    160

    200

    In Iu

    Power distribution

    CBsthermomagnetic releases

    MF MA TMF TMD TMA TMGT1 - - - -T2 - -T3 - - -T4 - - -T5 - - - -T6 - - - - -

    Legenda

    MF Fixed magnetic only releases

    MA Adjustable magnetic only releasesTMG Thermomagnetic release or generator protectionTMF Thermomagnetic release with thermal and fxed

    magnetic threshold

    Tmax T

    TMD Thermomagnetic release with adjustable thermal

    and fxed magnetic thresholdTMA Thermomagnetic release with adjustable thermal

    and magnetic threshold

    1.3 Types o releases

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    40/547

    38 Protection and control devices | ABB

    1 Protection and control devices

    1.3.2 ELECTRONIC RELEASES

    These releases are connected with current transormers (three or our accordingto the number o conductors to be protected), which are positioned inside thecircuit-breaker and have the double unctions o supplying the power necessaryto the proper unctioning o the release (sel-supply) and o detecting the valueofthecurrentowinginsidetheliveconductors;thereforetheyarecompatible

    with alternating current networks only.The signal coming rom the transormers and rom the Rogowsky coils isprocessed by the electronic component (microprocessor) which compares itwith the set thresholds. When the signal exceeds the thresholds, the trip o thecircuit-breaker is operated through an opening solenoid which directly acts onthe circuit-breaker operating mechanism.In case o auxiliary power supply in addition to sel-supply rom the currenttransormers, the voltage shall be 24 Vdc 20%.

    Besides the standard protection unctions, releases provide:

    - measuraments o currents (Ekip LSI/LSIG + Ekip COM, Ekip M LRIU + Ekip COM,PR222, PR232, PR331, PR121);

    - measurament o currents,voltage,requency,power,energy,power actor(PR223,PR332,PR122) and moreover or PR333 and PR123, the measure-ment o harmonic distortions is available;

    - serial comunication with remote control or a complete management othe plant (Ekip LSI/LSIG + Ekip COM, Ekip M LRIU + Ekip COM, PR222,PR223, PR232, PR331, PR332, PR333, PR121, PR122, PR123).

    The ollowing table shows the types o electronic trip units available orSACE Tmax XT, Tmax T and Emax circuit-breakers.

    CBs

    electronic releases with ABB circuit breakers

    Ekip Ekip G Ekip N PR221 PR222 PR223 PR231 PR232 PR331 PR332 PR333 PR121 PR122 PR123

    I

    LS/I

    LSI

    LSIG LS/I LS/I

    I

    LS/I

    LSI

    LSIG LSIG

    I

    LS/I LSI LSIG

    LI

    LSI

    LSIG

    LSRc

    LI

    LSI

    LSIG

    LI

    LSI

    LSIG

    LI

    LSI

    LSIG

    LSRc

    LI

    LSI

    LSIG

    XT2 - - - - - - - - - - -

    XT4 - - - - - - - - - - -

    T2 - - - - - - - - - - - - -T4 - - - - - - - - - - -

    T5 - - - - - - - - - - -

    T6 - - - - - - - - - - -

    T7 - - - - - - - - - -

    X1 - - - - - - - - - - -

    E1 - - - - - - - - - - -

    E2 - - - - - - - - - - -

    E3 - - - - - - - - - - -

    E4 - - - - - - - - - - -

    E5 - - - - - - - - - - -E6 - - - - - - - - - - -

    1.3 Types o releases

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    41/547

    ABB | Protection and control devices 39

    1 Protection and control devices

    The ollowing table shows the available rated currents with the SACE Tmax XT,Tmax T and Emax circuit- breakers.

    The ollowing table shows the available rated currents or motor protection withthe SACE Tmax XT and Tmax T circuit- breakers.

    MCCBs XT2 XT4 T2 T4 T5 T6 T7

    160 160 250 160 250 320 400 630 630 800 1000 800 1000 1250 1600

    10 (1) - - - - - - - - - - - - -

    25 (1) - - - - - - - - - - - - -

    40 - - - - - - - - - - - - -

    63 - - - - - - - - - - -

    100 - - - - - - - - -

    160 (1) - - - - - - - - -

    250 - - (1) - - - - - - - - - -

    320 - - - - - - - - - - - -

    400 - - - - - - - - -

    630 - - - - - - - - -800 - - - - - - - - - -

    1000 - - - - - - - - - - -

    1250 - - - - - - - - - - - - -

    1600 - - - - - - - - - - - - - -

    In Iu

    (1) Not available or Ekip N and Ekip I; only or XT2 In=10 A not available with Ekip G

    Tmax T

    MCCBs T2 160 T4 250 T5 400 T6 800

    PR221MP

    LI

    PR222MP

    LRIU

    40 n - - -

    63 n - - -

    100 n n - -

    160 - n - -

    200 - n - -

    320 - - n -

    400 - - n -

    630 - - - n

    In

    Trip units

    SACE Tmax XT

    MCCBs XT2 160 XT4 160 XT4 250

    Ekip M

    I

    Ekip M

    LIU or LRIU

    20 n - - -

    25 - n - -

    32 n - - -

    40 - - n n

    52 n - - -

    63 - n n n

    100 n n n n

    160 - - - n

    In

    Trip units

    1.3 Types o releases

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    42/547

    40 Protection and control devices | ABB

    1 Protection and control devices

    ACBs

    E3H-V E3 N-S-H-V E3 S-H-V-L

    E3 N-S-

    H-VE4S-H-V E6V E6H-V

    E2S E2N-

    S-L

    E2B-N-

    S-L E2B-

    N-SE1B-N

    X1B-N-L X1B-N630 800 1250 (2) 1600 2000 2500 3200 4000 3200 4000 5000 6300

    400 - - - - - -

    630 - - - - - -

    800 - - - - - - -

    1000 - - - - - - - -

    1250 - - - - - -

    1600 - - - - - - -

    2000 - - - - - - - -

    2500 - - - - - - - - -

    3200 - - - - - -4000 - - - - - - - - -

    5000 - - - - - - - - - - -

    6300 - - - - - - - - - - - -

    In Iu

    (2) Also or Iu = 1000 A (not available or E3V and E2L).

    Example o reading rom the table

    The circuit-breaker type E3L is available with Iu=2000A and Iu=2500A, but it is notavailable with Iu=3200A.

    1.3 Types o releases

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    43/547

    ABB | Protection and control devices 41

    1 Protection and control devices

    1.3.2.1 PROTECTION FUNCTIONS OF ELECTRONIC RELEASES

    The protection unctions available or the electronic releases are:

    L - Overload protection with inverse long time delay

    Function o protection against overloads with inverse long time delay andconstant specifc let-through energy; it cannot be excluded.L - Overload protection in compliance with Std. IEC 60255-3Function o protection against overloads with inverse long time delay and tripcurves complying with IEC 60255-3; applicable in the coordination with usesand with medium voltage protections.S - Short-circuit protection with adjustable delayFunction o protection against short-circuit currents with adjustable delay; thanksto the adjustable delay, this protection is particularly useul when it is necessaryto obtain selective coordination between dierent devices.S

    2- Double S

    This unction allows two thresholds o protection unction S to be set indepen-dently and activated simultaneously, selectivity can also be achieved underhighly critical conditions.D - Directional short-circuit protection with adjustable delayThe directional protection, which is similar to unction S, can intervene in adierent way according to the direction o the short-circuit current; particularlysuitable in meshed networks or with multiple supply lines in parallel.I - Short-circuit protection with instantaneous tripFunction or the instantaneous protection against short-circuit.EFDP - Early Fault Detection and PreventionThanks to this unction, the release is able to isolate a ault in shorter times than

    the zone selectivities currently available on the market.Rc - Residual current protectionThis unction is particularly suitable where low-sensitivity residual currentprotection is required and or high-sensitivity applications to protect peopleagainst indirect contact.G - Earth ault protection with adjustable delayFunction protecting the plant against earth aults.U - Phase unbalance protectionProtection unction which intervenes when an excessive unbalance between thecurrents o the single phases protected by the circuit-breaker is detected.OT - Sel-protection against overtemperature

    Protection unction controlling the opening o the circuit-breaker when thetemperature inside the release can jeopardize its unctioning.UV - Undervoltage protectionProtection unction which intervenes when the phase voltage drops below thepreset threshold.OV - Overvoltage protectionProtection unction which intervenes when the phase voltage exceeds thepreset threshold.RV - Residual voltage protectionProtection which identifes anomalous voltages on the neutral conductor.RP - Reverse power protection

    Protection which intervenes when the direction o the active power is oppo-

    1.3 Types o releases

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    44/547

    42 Protection and control devices | ABB

    1 Protection and control devices

    to normal operation.UF - Under requency protectionThis requency protection detects the reduction o network requency above theadjustable threshold, generating an alarm or opening the circuit.

    OF - Overrequency protectionThis requency protection detects the increase o network requency above theadjustable threshold, generating an alarm or opening the circuit.M - Thermal memoryThanks to this unction, it is possible to take into account the heating o acomponent so that the tripping is the quicker the less time has elapsed sincethe last one.R - Protection against rotor blockageFunction intervening as soon as conditions are detected, which could lead tothe block o the rotor o the protected motor during operation.Iinst - Very ast instantaneous protection against short-circuit

    This particular protection unction has the aim o maintaining the integrity o thecircuit-breaker and o the plant in case o high currents requiring delays lowerthan those guaranteed by the protection against instantaneous short-circuit. Thisprotection must be set exclusively by ABB SACE and cannot be excluded.Dual settingWith this unction it is possible to program two dierent sets o parameters (LSIG)and, through an external command, to switch rom one set to the other.K - Load controlThanks to this unction, it is possible to engage/disengage individual loads onthe load side beore the overload protection L trips.

    1.3 Types o releases

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    45/547

    ABB | Protection and control devices 43

    1 Protection and control devices

    Only with PR120/V or Emax and PR330/V or X1

    PR221

    PR222

    PR223

    PR231

    PR232

    PR331

    PR332

    PR333

    PR121

    PR122PR123

    Protection against overload

    Standard trip curve according to IEC 60255-3

    Protection against short-circuit with time delay

    Protection against short-circuit with time delay

    Protection against short-circuit with time delay

    Protection against directional short-circuit

    Protection against instantaneous short-circuit

    Protection against earth ault with adjustable delay

    Protection against earth ault with adjustable delay

    Protection against earth ault with adjustable delay

    Protection against earth ault with adjustable delay

    Protection against earth ault with adjustable delay

    Residual current protection

    Protection against phase unbalance

    Protection against temperature out o range

    Protection against undervoltage

    Protection against overvoltage

    Protection against residual voltageProtection against reverse active power

    Protection against underrequency

    Protection against overrequency

    Instantantaneous sel-protection

    Early Fault Detection and Prevention

    Protection unctions

    Tmax XT

    L (t=k/I2)

    L

    S1 (t=k)

    S1 (t=k/I2)

    S2 (t=k)

    D (t=k)

    I (t=k)

    G (t=k)

    G (t=k/I2)

    Gext (t=k)

    Gext (t=k/I2)

    Gext (Idn)

    Rc (t=k)

    U (t=k)

    OT

    UV(t=k)

    OV(t=k)

    RV(t=k)RP (t=k)

    UF

    OF

    Iinst

    EF

    Tmax T

    T7/X1

    X1

    Emax

    Ekip

    Ekip-G

    Ekip-N

    The ollowing table summarizes the types o electronic release and the unctionsthey implement:

    1.3 Types o releases

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    46/547

    44 Protection and control devices | ABB

    1 Protection and control devices

    When the release detects a residual current dierent rom zero, it opens thecircuit-breaker through an opening solenoid.

    As we can see in the picture the protection conductor or the equipotentialconductor have to be installed outside the eventual external toroid.

    Opening

    solenoid

    Load

    Circuit-breaker

    Protective conductor

    L1

    L2L3

    N

    PE

    Generic distribution system (IT, TT, TN)

    ASDC008002F0201

    1.3.3 RESIDUAL CURRENT DEVICES

    The residual current releases are associated with the circuit-breaker in order toobtain two main unctions in a single device:- protection against overloads and short-circuits;

    - protection against indirect contacts (presence o voltage on exposed con-ductive parts due to loss o insulation).Besides, they can guarantee an additional protection against the risk o frederiving rom the evolution o small ault or leakage currents which are notdetected by the standard protections against overload.Residual current devices having a rated residual current not exceeding 30 mAare also used as a means or additional protection against direct contact incase o ailure o the relevant protective means.Their logic is based on the detection o the vectorial sum o the line currentsthrough an internal or external toroid.This sum is zero under service conditions or equal to the earth ault current (I

    )

    in case o earth ault.

    The operating principle o the residual current release makes it suitable or thedistribution systems TT, IT (even i paying particular attention to the latter) andTN-S, but not in the systems TN-C. In act, in these systems, the neutral isused also as protective conductor and thereore the detection o the residualcurrent would not be possible i the neutral passes through the toroid, since thevectorial sum o the currents would always be equal to zero.

    1.3 Types o releases

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    47/547

    ABB | Protection and control devices 45

    1 Protection and control devices

    In presence o electrical apparatuses with electronic components (computers,photocopiers, ax etc.) the earth ault current might assume a non sinusoidalshape but a type o a pulsating unidirectional dc shape. In these cases it isnecessary to use a residual current release classifed as type A.In presence o rectiying circuits (i.e. single phase connection with capacitiveload causing smooth direct current, three pulse star connection or six pulsebridge connection, two pulse connection line-to-line) the earth ault currentmight assume a unidirectional dc shape. In this case it is necessary to use aresidual current release classifed as type B.

    Correct unctioning o residualcurrent devices

    Form o residualcurrent

    Type

    AC A B

    with or without 0,006A

    suddenly applied

    slowly rising

    suddenly applied

    slowly rising

    +

    +

    +

    +

    ++

    Sinusoidal ac

    Pulsating dc

    Smooth dc

    ASDC008003F02

    01

    One o the main characteristics o a residual current release is its minimum ratedresidual current I

    n. This represents the sensitivity o the release.

    According to their sensitivity to the ault current, the residual current circuit-breakers are classifed as:

    - type AC: a residual current device or which tripping is ensured in case oresidual sinusoidal alternating current, in the absence o a dc componentwhether suddenly applied or slowly rising;

    - type A: a residual current device or which tripping is ensured or residualsinusoidal alternating currents in the presence o specifed residual pulsatingdirect currents, whether suddenly applied or slowly rising.

    - type B residual current device or which tripping is ensured or residual sinu-soidal alternating currents in presence o specifed residual pulsanting directcurrents whether suddenly applied or slowy rising, or residual directs mayresult rom rectiying circuits.

    1.3 Types o releases

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    48/547

    46 Protection and control devices | ABB

    1 Protection and control devices

    In order to ulfll the requirements or an adequate protection against earth aults

    ABB SACE has designed the ollowing product categories:

    - Miniature circuit-breakers:

    RCBOs(residualcurrentoperatedcircuit-breakerswithintegralovercurrentprotection) DS201, DS202C series with rated current from 1 A up to 40 A;

    RCBOs(residualcurrentoperatedcircuit-breakerswithintegralovercurrent

    protection)DS200withratedcur-rentfrom6Aupto63A;

    RCBOs(residualcurrentoperatedcircuit-breakerswithintegralovercurrent

    protection) DS800 with 125A rated current;

    RCDblocks(residualcurrentblocks)DDA200typetobecoupledwiththe

    thermalmagneticcircuit-breakerstypeS200withratedcurrentfrom0.5

    Ato63A;

    RCDblocks(residualcurrentblocks)DDA60,DDA70,DD90typetobe

    coupledwiththethermalmagneticcircuit-breakerstypeS290withratedcurrent rom 80 A to 100 A with C characteristic curve;

    RCDblocks(residualcurrentblocks)DDA800 typetobecoupledwith

    thethermalmagneticcircuit-breakerstypeS800NandS800Swithrated

    currentupto100A.Theseblocksareavailableintwosizes:63Aand

    100 A;

    RCCBs(residualcurrentcircuit-breakers)F200type,withratedcurrent

    from16Ato125A.

    RD2-RD3:residualcurrentmonitorforxingonDINrail.

    - Tmax XT moulded case circuit breakers: RCSel200mmXT1(withadjustabletimeofnontrip):residualcurrent

    releasescanbeinstalledin200mmmodules;itcanbecoupledwithX1

    circuitbreakerswitharatedcurrentupto160A.

    RCSelXT1-XT3(withadjustabletimeofnontrip):residualcurrentreleases

    tobecoupledwithcircuitbreakersXT1,XT3witharatedcurrentupto

    160AwithXT1and250AwithXT3

    1.3Typesofreleases

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    49/547

    ABB | Protection and control devices 47

    1 Protection and control devices

    RC Sel 200mm

    XT1

    RC Inst

    XT1-XT3

    RC Sel

    XT1-XT3

    RC Sel

    XT2-XT4

    RC B Type

    XT3

    Type L shaped L shaped L shaped Placed below Placed below

    Technology Microprocessor - based

    Primary power supply

    voltage[V] 85...500 85...500 85...500 85...500 85...500

    Operating requence [Hz] 45...66 45...66 45...66 45...66 45...66

    Sel-supply n n n n n

    Test operation range 85...500 85...500 85...500 85...500 85...500

    Rated service current [A] up to 160up to 160-XT1

    up to 250-XT3

    up to 160-XT1

    up to 250-XT3

    up to 160-XT2

    up to 250-XT4up to 225

    Rated residual current trip [A]

    0.03-0.05-0.1-

    0.2-0.3-0.5-1-

    3-5-10

    0.03-0.1-0.3-

    0.5-1-3

    0.03-0.05-0.1-

    0.3-0.5-1-3-

    5-10

    0.03-0.05-0.1-

    0.3-0.5-1-3-

    5-10

    0.03-0.05-0.1-

    0.3-0.5-1

    Adjustable NON-trip time

    settings et 2xIn[s]

    Instantaneous

    Instantaneous

    Instantaneous Instantaneous Instantaneous

    0.1-0.2-0.3-

    0.5-1-2-3

    0.1-0.2-0.3-

    0.5-1-2-3

    0.1-0.2-0.3-

    0.5-1-2-3

    0.1-0.2-0.3-

    0.5-1-2-3

    RC Sel 200mm RC Inst RC Sel RC Sel RC B Type Ekip LSIG

    A A A A B -

    XT1 16160 n n n - - -

    XT2 1.6160 - - - n - n

    XT3 63250 - n n - n(1) -

    XT4 16250 - - - n - n

    TypeIn

    (1) Up to 225 A

    RCInstXT1-XT3(instantaneous):residualcurrentreleasestobecoupled

    with circuit breakers XT1, XT3 with a rated current up to 160A.

    RCSelXT2-XT4(withadjustabletimeofnontrip):residualcurrentreleases

    to be coupled with circuit breakers XT2, XT4 with a rated current up to160A with XT2 and 250A with XT4

    RCBTypeXT3(withadjustabletimeofnontrip):residualcurrentreleases

    to be coupled with circuit breaker XT3 with a rated current up to 225A

    ElectronictripunitsEkipLSIGforcircuitbreakersXT2andXT4witha

    rated current rom 10 to 250A.

    1.3 Types o releases

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    50/547

    48 Protection and control devices | ABB

    1 Protection and control devices

    RC221 RC222 RC223

    Circuit-breaker size T1-T2-T3 T1-T2-T3 T4 and T5 4p T4 4p

    Type L shaped placed below

    Technology microprocessor-based

    Action With trip coil

    Primary service voltage (1) [V] 85500 85500 85500 110500

    Operating requence [Hz] 4566 4566 4566 0-400-700-1000

    Sel-supply

    Test operation range (1) 85500 85500 85500 110500

    Rated service current [A] up to 250 A up to 250 A up to 500 A up to 250 A

    Rated residual current trip [A]0.03-0.1-0.3

    0.5-1-3

    0.03-0.05-0.1-0.3

    0.5-1-3-5-10

    0.03-0.05-0.1

    0.3-0.5-1-3-5-10

    0.03-0.05-0.1

    0.3-0.5-1

    Time limit or non-trip [s] IstantaneousIstantaneous - 0.1

    -0.2-0.3-0.5-1-2-3

    Istantaneous - 0.1

    -0.2-0.3-0.5-1-2-3

    Istantaneous -0- 0.1

    -0.2-0.3-0.5-1-2-3

    Tolerance over trip times 20% 20% 20%

    (1) Operation up to 50 V phase-neutral (55 V or RC223).

    - Tmax T moulded case circuit breakers:

    RC221residualcurrentreleasestobecoupledwithcircuit-brakersTmax

    T1, T2, T3 with rated current rom 16 A to 250A;

    RC222residualcurrentreleasestobecoupledwithcircuit-breakersTmax

    T1,T2,T3,T4,T5 with rated currents rom 16A to 500A;

    RC223residualcurrentreleasestocoupledwithcircuit-breakerTmaxT4

    with rated currents up to 250A;

    electronicreleasesPR222DS/P,PR223DS/PLSIGforcircuitbreakers

    T4, T5, T6 with rated current rom 100A to 1000A;

    electronicreleasesPR331,PR332LSIGforthecircuitbreakerTmaxT7

    with rated currents rom 800A to 1600A;

    electronicreleaseR332withresidualcurrentintegratedprotectionforthe

    circuit-breaker type Tmax T7 with rated uninterrupted current rom 800A

    to 1600A.

    RC 221 RC 222 RC 223PR332

    LSIRc

    PR222

    LSIG

    PR223

    LSIG

    PR332

    LSIRc

    A-AC A-AC B A-AC - - -

    T1 16160 n n - - - - -

    T2 10160 n n - - - - -

    T3 63250 n n n(1) - - - -

    T4 100320 - n n(2) - n n -

    T5 320630 - n - - n n -

    T6 6301000 - - - - n n -

    T7 8001600 - - - n - - n

    TypeIn

    (1) Up to 225 A

    (2) Up to 250 A

    1.3 Types o releases

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    51/547

    ABB | Protection and control devices 49

    1 Protection and control devices

    Residual current relay with external transformer

    ABB SACE circuit breaker can be combined also with the residual current relaysRCQ 020/A with separate toroid in order to ulfll the requirements when theinstallation conditions are particulary restrictive, such as with circuit breakersalready installed, limited space in the circuit breaker compartment etc.Thanks to the settings characteristics o the residual current and o the triptimes, the residual current relays with external transormer can be easily installedalso in the fnal stages o the plant; in particolar, by selecting the rated residual

    current In=0.03A with instantaneous tripping, the circuit-breaker guaranteesprotection against indirect contact and represents an additional measure againstdirect contact also in the presence o particulary high earth resistance values.Such residual current relays are o the type with indirect action: the openingcommand given by the relay must cause the tripping o the circuit-breakerthrough a shunt opening release (to be provided by the user).

    Residual current relays SACE RCQ 020/A

    Power supply voltage AC [V] 115-230415

    Operating requency [Hz] 4566

    TripThreshold adjustement In [A] 0.03-0.05-0.1-0.3-0.5-1-3-5-10-30

    Trip time adjustement [s] Inst-0.1-0.2-0.3-0.5-0.7-1-2-3-5

    - Emax air circuit breaker:

    PR331,PR332,PR333LSIGelectronicreleasesforthecircuitbreaker

    Emax X1 with rated uninterrupted currents rom 630A to 1600A;

    AircircuitbreakerequippedwithelectronicreleasestypePR121,PR122,

    PR123 LSIG or the circuit breaker Emax E1 to E6 with rated uninterruptedcurrents rom 400A to 6300A.

    PR332,PR333electronicreleaseswithresidualcurrentintegratedpro-tection or circuit-breaker Emax X1 with rated uninterrupted currents rom630A to 1600A;

    PR122andPR123electronicreleaseswithresidualcurrent integrated

    protection or circuit-breakers Emax E1 to E6 with rated uninterruptedcurrents rom 400A to 6300A

    PR332

    PR333

    LIRc

    PR122LIRc

    PR331

    PR332PR333

    LSIG

    PR121

    PR122PR123

    LSIG

    A-AC A-AC - -

    X1 4001600 n - n -

    E1 4001600 - n - n

    E2 4002000 - n - n

    E3 4003200 - n - n

    E4 12504000 - - - n

    E6 32006300 - - - n

    TypeIn

    1.3 Types o releases

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    52/547

    50 Protection and control devices | ABB

    2 General characteristics

    2.1 Electrical characteristics o circuit-breakers

    Series S200 S200 M S200 P SN 201 L SN 201

    Characteristics B, C, D, K, Z B, C, D, K, Z B, C, D, K, Z B, C B, C, D

    Rated current [A] 0.5 In

    63

    0.5 In

    63

    0.2 In

    25

    32 In

    40

    50 In

    63

    2 In

    40

    2 In

    40

    Breaking capacity [kA]

    Reference standard Nr. poles Ue [V]

    IEC 23-3/EN 60898 Icn 230/400 6 10 25 15 15 4.5 6

    IEC/EN 60947-2 Icu 1, 1P+N 133 20 252 40 25 25 10 15

    230 10 152 25 15 15 6 10

    2, 3, 4 230 20 252 40 25 25

    400 10 15

    2

    25 15 152, 3, 4 500

    690

    Ics 1, 1P+N 133 15 18.72 20 18.7 18.7 6 10

    230 7.5 11.22 12.5 11.2 7.5 4.5 6

    2, 3, 4 230 151 18.72 20 18.7 18.7

    400 7.5 11.22 12.5 11.2 7.5

    2, 3, 4 500

    690

    IEC/EN 60947-2

    Direct cuttent

    T=I/R5ms or all

    series, except S280 UC

    and S800-UCwhwre T=I/R

  • 8/23/2019 101627739 ABB Electrical Installation Handbook 6th Edition2010

    53/547

    ABB | Protection and control devices 51

    2 General characteristics

    2.1 Electrical characteristics o circuit-breakers

    SN 201 M S 280 S 280 UC S 290 S800S S800N S800C

    B, C B, C B, K, Z K, Z C. D, K B, C, D K KM UCB UCK B, C, D B, C, D, K

    2 In

    40

    80 In

    100

    0.2 In

    40

    50 In

    63

    80 In

    125

    10 In

    125

    10 In

    125

    20 In

    80

    10 In

    125

    10 In

    125

    10 In

    125

    10 In

    125

    10 6 10 25 20 15

    20 15 10 6

    10 6 6 4.5 20 (15)3 50 50 50 36

    10 10 6 25 50 50 50 36 25

    6 6 4.5 20 (15)

    3

    50 50 50 36 25154 154 154 104 25

    64 64 64 4.5

    10 15 7.5 6

    7.5 6 6 4.5 10 (7.5)3 40 40 40 30 18

    10 7.5 6 12.5 40 40 40 30 18

    6 6 4.5 10 (7.5)3 40 40 40 30 18

    114 114 114 84

    44 44 44 3

    15 10 25

    6 4.5 30 30 30

    50 50 20 10

    1