B.A.B. Location 72 565 HOLMES AVE. NW SPARKMAN DR. HOLMES AVE. NW Sheet # Sheet Name Issued Rev # Rev Date Rev Description 1. GENERAL TS.1 TITLE SHEET 02/25/2020 TS.2 GENERAL INFORMAITON 02/25/2020 2. CODE COMPLIANCE CC1.0 CODE COMPLIANCE PLANS 02/25/2020 3. ARCHITECTURE A0.1 DEMOLITION PLAN - FIRST FLOOR 02/25/2020 A0.2 DEMOLITION PLAN - SECOND FLOOR 02/25/2020 A1.0 GENERAL INFORMATION FIRST AND SECOND FLOOR PLANS 02/25/2020 A1.1 FIRST FLOOR - OVERALL RENOVATION PLAN 02/25/2020 A1.2 SECOND FLOOR - OVERALL RENOVATION PLAN 02/25/2020 A1.2a CYBERSECURITY LAB - ENLARGED SECOND FLOOR PLAN 02/25/2020 A6.0 INTERIOR ELEVATIONS & DETAILS 02/25/2020 A7.0 PARTIAL SECOND FLOOR FINISH PLAN, INTERIOR FINISH LEGEND AND SCHEDULE 02/25/2020 A7.1 CYBERSECURITY LAB - SECOND FLOOR FURNITURE PLAN 02/25/2020 A8.0 DOOR SCHEDULE, DOOR AND FRAME DETAILS, AND INTERIOR DETAILS 02/25/2020 A9.1 FIRST FLOOR - REFLECTED CEILING PLAN 02/25/2020 A9.2 SECOND FLOOR - REFLECTED CEILING PLAN 02/25/2020 4. MECHANICAL, PLUMBING, FIRE PROTECTION FP1.0 FIRE PROTECTION FLOOR PLAN 02/25/2020 M1.0 MECHANICAL FLOOR PLAN 02/25/2020 M2.0 MECHANICAL FLOOR PLAN 02/25/2020 M3.0 MECHANICAL SCHEDULES 02/25/2020 P1.0 PLUMBING FLOOR PLAN - DEMOLITION 02/25/2020 P2.0 PLUMBING FLOOR PLAN - NEW CONSTRUCTION 02/25/2020 5. ELECTRICAL E0.1 ELECTRICAL LEGEND, SYMBOLS, & NOTES 02/25/2020 E0.2 ELECTRICAL SCHEDULES & LIGHTING RISER DIAGRAM 02/25/2020 E1.1 OVERALL SECOND FLOOR DEMOLITION PLAN - ELECTRICAL 02/25/2020 E2.1 OVERALL SECOND FLOOR PLAN - LIGHTING 02/25/2020 E2.2 PARTIAL SECOND FLOOR PLAN - LIGHTING 02/25/2020 E3.2 PARTIAL SECOND FLOOR PLAN - POWER 02/25/2020 E4.2 PARTIAL SECOND FLOOR PLAN - TECHNOLOGY 02/25/2020 INDEX OF DRAWINGS MECHANICAL, PLUMBING & FIRE PROTECTION ELECTRICAL Mechanical Design Solutions, Inc. 100 Church St. Suite 650 Huntsville, Alabama 35801 Phone: 256 - 534 - 5150 www.mdseng.com SSOE Group 303 Williams Avenue SW Suite 1211 Huntsville, AL 35801 Phone: (256) 534 - 2353 www.ssoe.com DESIGN TEAM LOCATION MAP ARCHITECT FUQUA & PARTNERS ARCHITECTS 100 Church Street, Suite 700 Huntsville, AL 35801 (256) 534 3516 Contact: Rodney Steger email: [email protected] 301 SPARKMAN DRIVE, HUNTSVILLE, AL 35899 UAH - BAB Cyber Lab / Interior Renovations A M A B A L A F O E T A T S R E G I S T E R E D A R C H I T E C T 3196 REGISTRATION NUMBER RODNEY STEGER MEMBER OF THE AMERICAN INSTITUTE OF ARCHITECTS This document is a copyright protected instrument of service and licnesed for use in the titled project only. This drawing may not be reproduced in whole or in part without written permission of FUQUA & PARTNERS ARCHITECTS, P.C. A Professional Corporation DATE: ISSUE: DRAWN: PROJECT NO: SHEET OF Architecture Interior Design Media Visualization Master Planning 100 Church Street, Suite 700 Huntsville, Alabama 35801 PH: (256) 534.3516 FX: (256) 533.4605 www.fuquaarchitects.com CHECKED: 2/26/2020 10:17:45 AM TS.1 TITLE SHEET 301 SPARKMAN DRIVE, HUNTSVILLE, AL 35899 LWF 02-25-2020 FPA #07519 RKS 100 % CDs 2 1 UAH BAB CYBER LAB / INTERIOR RENOVATIONS REVISIONS

Transcript of 100 Church Street, Suite 700 Huntsville, Alabama 35801 PH ...

Page 1: 100 Church Street, Suite 700 Huntsville, Alabama 35801 PH ...

B.A.B. Location

72

565

HOLMES AVE. NW

SPAR

KMAN

DR.

HOLMES AVE. NW

Sheet # Sheet Name Issued Rev # Rev Date Rev Description

1. GENERALTS.1 TITLE SHEET 02/25/2020TS.2 GENERAL INFORMAITON 02/25/20202. CODE COMPLIANCECC1.0 CODE COMPLIANCE PLANS 02/25/20203. ARCHITECTUREA0.1 DEMOLITION PLAN - FIRST FLOOR 02/25/2020A0.2 DEMOLITION PLAN - SECOND FLOOR 02/25/2020A1.0 GENERAL INFORMATION FIRST AND SECOND FLOOR PLANS 02/25/2020A1.1 FIRST FLOOR - OVERALL RENOVATION PLAN 02/25/2020A1.2 SECOND FLOOR - OVERALL RENOVATION PLAN 02/25/2020A1.2a CYBERSECURITY LAB - ENLARGED SECOND FLOOR PLAN 02/25/2020A6.0 INTERIOR ELEVATIONS & DETAILS 02/25/2020A7.0 PARTIAL SECOND FLOOR FINISH PLAN, INTERIOR FINISH LEGEND AND SCHEDULE 02/25/2020A7.1 CYBERSECURITY LAB - SECOND FLOOR FURNITURE PLAN 02/25/2020A8.0 DOOR SCHEDULE, DOOR AND FRAME DETAILS, AND INTERIOR DETAILS 02/25/2020A9.1 FIRST FLOOR - REFLECTED CEILING PLAN 02/25/2020A9.2 SECOND FLOOR - REFLECTED CEILING PLAN 02/25/20204. MECHANICAL, PLUMBING, FIRE PROTECTIONFP1.0 FIRE PROTECTION FLOOR PLAN 02/25/2020M1.0 MECHANICAL FLOOR PLAN 02/25/2020M2.0 MECHANICAL FLOOR PLAN 02/25/2020M3.0 MECHANICAL SCHEDULES 02/25/2020P1.0 PLUMBING FLOOR PLAN - DEMOLITION 02/25/2020P2.0 PLUMBING FLOOR PLAN - NEW CONSTRUCTION 02/25/20205. ELECTRICALE0.1 ELECTRICAL LEGEND, SYMBOLS, & NOTES 02/25/2020E0.2 ELECTRICAL SCHEDULES & LIGHTING RISER DIAGRAM 02/25/2020E1.1 OVERALL SECOND FLOOR DEMOLITION PLAN - ELECTRICAL 02/25/2020E2.1 OVERALL SECOND FLOOR PLAN - LIGHTING 02/25/2020E2.2 PARTIAL SECOND FLOOR PLAN - LIGHTING 02/25/2020E3.2 PARTIAL SECOND FLOOR PLAN - POWER 02/25/2020E4.2 PARTIAL SECOND FLOOR PLAN - TECHNOLOGY 02/25/2020

INDEX OF DRAWINGS

MECHANICAL, PLUMBING & FIRE PROTECTION

ELECTRICAL

Mechanical Design Solutions, Inc.

100 Church St. Suite 650Huntsville, Alabama 35801

Phone: 256-534-5150www.mdseng.com

SSOE Group

303 Williams Avenue SWSuite 1211

Huntsville, AL 35801Phone: (256) 534-2353

www.ssoe.com

DESIGN TEAMLOCATION MAP

ARCHITECTFUQUA & PARTNERS

ARCHITECTS

100 Church Street, Suite 700Huntsville, AL 35801

(256) 534 3516Contact: Rodney Steger

email: [email protected]

301 SPARKMAN DRIVE, HUNTSVILLE, AL 35899

UAH - BAB Cyber Lab / Interior Renovations

AMA

BALAFOETATSRE

GISTERED ARCHIT

EC

T

3196

REGISTRATIONNUMBER

RODNEY STEGER

MEMBER OF THE AMERICAN INSTITUTE OF ARCHITECTS

This document is a copyright protected instrument of service and licnesed for use in the titled project only. This drawing may not be

reproduced in whole or in part without written permission of FUQUA & PARTNERS ARCHITECTS, P.C.

A Professional Corporation

DATE:

ISSUE:

DRAWN:

PROJECT NO:

SHEET

OF

Architecture

Interior Design

Media Visualization

Master Planning

100 Church Street, Suite 700Huntsville, Alabama 35801

PH: (256) 534.3516FX: (256) 533.4605

www.fuquaarchitects.com

CHECKED:

2/26

/202

0 10

:17:

45 A

M

TS.1

TITL

E SH

EET

301

SPAR

KMAN

DRI

VE, H

UN

TSVI

LLE,

AL

3589

9

LWF

02-25-2020

FPA #07519

RKS

100 % CDs

21

UAH

BAB

CYB

ER L

AB /

INTE

RIO

R RE

NO

VATI

ON

S

REVISIONS

Page 2: 100 Church Street, Suite 700 Huntsville, Alabama 35801 PH ...

FIRE EXTINGUISHER

3'-0"MIN

16"-18"

WATER

FIRE EXTINGUISHER CABINET

TELEPHONE HOUSING WHEELCHAIR ACCESSIBLE

(N.I.C.)

48" M

AX

TO

HIG

HES

TO

PERA

BLE

WALL PHONE (N.I.C.)33

" - 3

6"

WATER

AFF

SEAT

17" -

19"

42" MIN

54" MIN

MAX1'-0"

39" -

41"

MIN

1'-6"

39" - 41" 2'-0"

URINAL

URINAL SCREEN (WHERE OCCURS)

1'-1 1/2"MIN

1'-0"MINMIN2'-0"

59" MIN

5'-0"MIN

MIN1'-3"

LAVATORY OR VANITY SINK

OFFSET WASTE

ACCESSIBLE SINK BOWL 6 1/2" DEEP

COUNTER WHERE OCCURS

INSULATE EXPOSED PIPING

ADA SHOWER

CONTROL WALL(CONTROLS)

CONTROLAREA

ENTRANCE SIDE

THERMOSTAT

48" M

AX

48" M

AX

SWITCH/ CARD READER

ROOM SIGN

4'-0"

MIN

5'-0"

MAX

F.F.L.

3'-6"

RECESSED PAPER TOWELDISPENSER &

4'-6"

MAX

1'-5" M

AX2'-

10"

2'-3"

TO H

IGH

EST

OPE

RABL

E D

EVIC

E

48" M

AX

TO

HIG

HES

TO

PERA

BLE

48" M

AX

TO

HIG

HES

TO

PERA

BLE

TO

HIG

HES

TO

PERA

BLE

TO H

IGH

EST

OPE

RABL

ED

EVIC

E

48" M

AX T

O

HIG

HES

TO

PERA

BLE

DEV

ICE

FRO

M F

FL O

R G

ROU

ND

SUR

FAC

E TO

BAS

ELIN

E O

F H

IGH

EST

TAC

TILE

C

HAR

ACTE

R

FRO

M F

FL O

R G

ROUN

D S

URF

ACE

TO B

ASEL

INE

OF

LOW

EST

TAC

TILE

C

HAR

ACTE

R

SEAT WALL

17"-1

9"

CONTROL WALL (GRAB BARS)

FOLDINGADA

ENTRANCE SIDE

GRAB BARS

TOP

OF

GRA

S PIN

G S

URFA

CE2'-

10"M

IN T

O 3

6" M

AX T

O

TWO-WALL TUB/SHOWER GRAB BAR

TOILET SEATCOVER

DISPENSER

TO

HIG

HES

TO

PERA

BLE

9" M

IN

PARTITIO

33" -

36"

18" M

IN

CO

NTR

OL

44" M

AXFL

USH

4'-0"

SEMI RECESSED PAPER TOWEL RECEPTACLE

TO

HIG

HES

TO

PERA

BLE

48" M

AX

48" M

AX

6"MAX TOE9"M

IN.

KNEE8" MINM

IN2'-

5"

1'-5" MIN DEPTH

MAX

2'-3" MAX

2'-10

"

LAVATORY - WALL (TYPICAL H.C.)

INSULATE BOOT ON EXPOSED DRAIN PIPE

INTERIOR SIGNAGE: LATCH

SIDE OR NEAREST

FIRE ALARM WITH STROBE

TO B

/ DEV

ICE

6'-8"

MIN

1'-6"MIN

9" MIN

EQ EQCENTERED ON TACTILE CHARACTERS

T.O

. PUL

L DO

WN

42 -

48" T

O

MIN

1'-6"

30" C

NTR

TP.

3'-2"

34" C

NTR

TP.

3'-6"U.N.

O.

4'-6"

MAX

ELECTRICAL DEVICES: ROTATEELECTRICAL COVER PLATES

HORIZONTAL IF COUNTERTOP IS ABOVE 42" HIGH

2'-6"

2'-10

"

SANITARYNAPKIN

DISPOSAL

RECESSED

SANITARYNAPKIN

SANITARYNAPKIN

DISPENSE

WALL MOUNTED SOAP DISPENSER

TO

HIG

HES

TO

PERA

BLE

TO

HIG

HES

TO

PERA

BLE

PAPER TOWEL DISPENSER

TO

HIG

HES

TO

PERA

BLE

18" M

IN

TOILET PAPER DISPENSER

RECESSED TOILET PAPER DISPENSER/HOLDER

ZONE

18" M

IN

TOILET PAPER HOLDER

MIN

1'-6" 4'-

0" M

AX

3'-6" MAX

3'-0" MAX

12" M

IN (I

F M

OU

NTE

D AB

OVE

GRA

B BA

R)

12" M

IN (I

F M

OU

NTE

D AB

OVE

GRA

B BA

R)

BEL

OW

GRA

B BA

R)

1-1/

2" M

IN B

ELO

W B

AR(IF

MO

UNTE

D

BELO

W G

RAB

BAR)

1-1/

2" M

IN B

ELO

W B

AR(IF

MO

UNTE

D

BAR

BAR

ABO

VE G

RAB

BAR)

48" M

AX (I

F M

OUN

TED

ABO

VE G

RAB

BAR)

48" M

AX (I

F M

OUN

TED

48" M

AX

48" M

AX

48" M

AX

E.W.C. (WC ACCESSIBLE)

TO S

POUT

3'-0"

MAX

E.W.C. (STANDING PERSON)

TO S

POUT

38" -

43"

4" MAX

3"-6

"

33"-3

6"

1'-3"

ENTRANCE SIDE

BACK WALL

1'-6"

17"-1

9"

HEAD END WALL

33" -

3'-0"

CONTROL END WALL

33" -

3'-0"

ADA TUB

8"-1

0"

BACK WALL(BARS)

33" -

36"

BACK WALL(SEAT)

REMOVABLE TUB SEAT, 15-16" WIDE

17-1

'-7"

24" MIN

18" M

IN

3" -

6"

1'-0"MIN

3'-6"

FLIP DOWNBABY CHANGE UNIT

TOWEL BAR

SHOWERCURTAIN ROD

6'-8"

TO H

IGH

EST

OPE

RABL

ED

EVIC

E

ROBE/ COATHOOK

4'-0"

MAX

MIRRO

3'-4"

MAX

TO B

OTT

OM

OF

REFL

ECTI

VE S

URFA

CE

40" M

IN -

48"

MAX

COAT RACK

5'-6"

BROOM/MOPHOLDER

48" M

AX

F.F.L.

F.F.L.

F.F.L.

F.F.L.

1. TYPICAL HEIGHTS: MOUNTING HEIGHTS INDICATED HEREIN ARE TYPICAL MOUNTING HEIGHTS FOR DEVICE INDICATED. HOWEVER, MOUNTING HEIGHTS FOR PRODUCTS MAY VARY BY MANUFACTURER, AND THEREFORE THE GENERAL CONTRACTOR SHALL NOTIFY THE ARCHITECT WHERE A DISCREPANCY EXISTS BETWEEN THE INDICATED MOUNTING HEIGHT AND THE MANUFACTURER RECOMMENDED MOUNTING HEIGHT, PRIOR TO INSTALLATION OF THE DEVICE.

2. THE GENERAL CONTRACTOR SHALL REFER TO FLOOR PLANS FOR LOCATIONS OF DEVICES SHOWN HEREIN. 3. ADA DEVICES: ALL DEVICES AND FIXTURES NOTED AS “ADA” OR “ACCESSIBLE” SHALL BE INSTALLED IN

STRICT ACCORDANCE WITH THE AMERICANS WITH DISABILITIES ACT AND APPLICABLE BUILDING CODES.

4. ELECTRICAL DEVICES: SEE ELECTRICAL DRAWINGS AND SPECIFICATIONS FOR REQUIRED MOUNTING HEIGHT OF ELECTRICAL DEVICES AND FIXTURES. WHERE CONFLICTS EXIST BETWEEN MOUNTING HEIGHTS INDICATED HEREIN AND THE REQUIREMENTS OF THE ELECTRICAL ENGINEER, THE GENERAL CONTRACTOR SHALL NOTIFY THE ARCHITECT PRIOR TO ROUGH-IN.

5. MECHANICAL/PLUMBING DEVICES: SEE MECHANICAL AND PLUMBING DRAWINGS AND SPECIFICATIONS FOR REQUIRED MOUNTING HEIGHT OF MECHANICAL AND PLUMBING DEVICES AND FIXTURES. WHERE CONFLICTS EXIST BETWEEN MOUNTING HEIGHTS INDICATED HEREIN AND THE REQUIREMENTS OF THE MECHANICAL ENGINEER, THE GENERAL CONTRACTOR SHALL NOTIFY THE ARCHITECT PRIOR TO ROUGH-IN.

6. INSTALL ADA / ANSI COMPLIANT UNDER LAVATORY GUARDS ON ALL EXPOSED SINK PIPING.

UNOBSTRUCTED SIDE REACH

WALL MTD.

OBSTRUCTED HIGH SIDE REACH

WALL MTD. DEVICE

FIXED OBJECT

WALL MTD. DEVICE

FIXED OBJECT

TO H

IGH

EST

OPE

RABL

E DE

VIC

E

TO H

IGH

EST

OPE

RABL

E D

EVIC

E

TO H

IGH

EST

OPE

RABL

E

10" MAX

34" M

AX

34" M

AX

3'-10

"MAX

4'-0"

MAX

48" M

AX

MIN

1'-3"

10"MAX MAX>10" - 24"

UNOBSTRUCTED FORWARD REACH OBSTRUCTED HIGH FORWARD REACH

TO H

IGH

EST

OPE

RABL

E DE

VIC

EWALL MTD. DEVICE WALL MTD. DEVICE

COUNTER TOP

WALL MTD. DEVICE

F.F.L.

TO H

IGH

EST

OPE

RABL

E

COUNTER TOP

MIN

1'-3"

4'-0"

MAX

SEE

ELEV

.

4'-0"

MAX

SEE

ELEV

. HIG

HES

T O

PERA

BLE

DEVI

CE3'-

8"M

AX T

O

MAX>20" - 25"

MAX1'-8"

F.F.L.

AC acre ACC accessibleACI American Concrete Institute ACT acoustical ceiling tile ADD addendum AFF above finished floor ALT alternate ALUM aluminum APPROX approximate ARCH architect (ural)ADJ adjacent

B&B balled and burlapped B/B back to back BC base of curb BD board BLDG buildingBLKG blocking BM benchmark BOT bottom BRG bearingBSMT basementBUR built-up roof BOW bottom of wallB/W between

C channelCAB cabinet CAL caliper CB catch basin C/C center to center CD core deck CF cubic footCI cast iron CIP cast iron pipe CJ construction or control joint CLG ceiling CLO closet CLR clear (ance) CMP corrugated metal pipe CMU concrete masonry unit CO clean out COL column CONC concrete CONN connection CONST construction CONT continuous or continue COORD coordinateCPT carpet (ed)CS countersink CSMU calcium silicate masonry unit

CT ceramic tile CW curtain wallCY cubic yard

D dryer DBL double DEM demolish or demolition DET detail DH double hung DIA diameter DIAG diagonal DIM dimension DIP ductile iron pipe DL dead loadDS downspout DWG drawing DF drinking fountain

EA each EF each face EIFS exterior insulation finish system EJ expansion joint ELEV elevation/elevator ELEC electric (al)ENGR engineer EOP edge of pavement

FRT fire retardant treatedFT foot/feet FTG footing

GA gauge GALV galvanizedGHM galvanized hollow metalGI galvanized iron GWB gypsum wall board GYP gypsum

H heightHC handicapHM hollow metal HORIZ horizontal HP high point/horse powerHSS hollow structural steelHVAC heating/ventilating/air conditioning HW hardware

ID inside diameter IE invert elevation IJ isolation joint IN inch/inches INSUL insulation

JAN janitor's closet JG joist girder JT joint

K thousand KIP 1000 # KJ key joint KSI 1000 # per sq in

LAM laminate (d) LF linear foot L length, angleLAB laboratory LAV lavatory LH left hand LL live load LLH long leg horizontalLLV long leg vertical LP low point LT GA light gauge LT light

EOS edge of slab EQ equal EW each way EWC electric water cooler EXH exhaust EXIST existing EXP exposedEXPN expansion EXT exterior

FBO furnished by others FD floor drain FEC fire extinguisher and cabinet FFE finish floor elevationFFL finish floor levelFHC fire hose and cabinetF/F face to faceFL floor FLG flange FND foundation FO face of FOB face of brick FOC face of concrete FOF face of finish FOM face of masonry FOS face of studFR frame (ed), (ing)

MATL material MAX maximum MC miscellaneous channelMECH mechanical MEZZ mezzanine MANUF manufacture (er) MH manhole MIN minimumMO masonry openingMULL mullion

NIC not in contract NO number NOM nominalNTS not to scale

O/H overheadOC on center (s) OCC occupant (s)OD outside diameterOH opposite hand OPG opening OPP opposite

PJ precast jointPL property line, plate

REQ'D required RET retaining REV revision (s), revisedRH right hand RJ recessed jointRM roomRO rough opening ROW right of way RTU roof top unit

SC sealed concrete SCHED scheduledSD storm drain SECT sectionSF storefrontSIM similar SPEC specification (s) SQ square SS solid surface SST stainless steel STD standardSTL steelSTOR storage STRUCT structuralSY square yard

PLAM plastic laminatePNT paint (ed)PREFAB prefabricatedPREFIN prefinishedPREMANUF premanufacturedPSF pounds per square foot PSI pounds per square inch PT point / pressure treated/

point of tangencyPVC polyvinyl chloride PVMT pavement PWD plywood

QT quarry tile

RA return air RAD radius RB rubber base RCP reflected ceiling plan RD roof drain REBAR reinforcement bar REF refrigerator/ reference REINF reinforce (d), (ing)

VB vinyl base VCT vinyl composition tile VERT vertical VWC vinyl wall covering

W washer/width/wide flange WB wood base WC water closet WD wood WH water heater WIN window WP work point,

waterproofingWT weight W/W wall to wall WWF welded wire fabric W/ with W/O without

TELE telephoneTERM terminationT&G tongue and groove TH thick (ness)THK thick (ness)TO top ofTOC top of curbTOF top of footingTOJ top of joistTOS top of slab/top of steelTOW top of wallTYP typical TZ terrazzo

UNO unless noted otherwise

A0.0

11 1

1

000

3

0 REFLECTED CEILING PLANA101 1/8" = 1'-0"View Description

S1

1A101

SIM

ROOM REFERENCE SYMBOL:

COLUMN LINES: 2 - CONSECUTIVE NUMBERS (123) ARE USING FOR COLUMN LINES RUNNING NORTH & SOUTH A - CONSECUTIVE LETTERS (ABC) ARE USED FOR COLUMN LINES RUNNING EAST & WEST

NOTE: IF A COLUMN LINE IS ADDED, "SUB" NUMBERS/LETTERS ARE USED

00.00

DATUM SYMBOL (ELEVATION MARK)00.00 - ELEVATION (FT)

REVISION SYMBOLUSED TO INDICATE SCOPE OF CURRENT REVISION

DOOR SYMBOL:-DOOR NUMBER 000-DOOR TYPE ASEE DOOR SCHEDULE & FLOOR PLANS

WINDOW SYMBOL:-WINDOW TYPE 00SEE EXTERIOR ELEVATIONS & WINDOW SCHEDULE

WALL SYMBOL:-WALL TYPE 3 SEE PARTITION LEGEND

BUILDING SECTION SYMBOL:SECTION 0 ON SHEET A0.0

WALL SECTION SYMBOL:SECTION 0 ON SHEET A0.0

ENLARGED PLAN / DETAIL SYMBOL:DETAIL 0 ON SHEET A0.0

ELEVATION SYMBOL:ELEVATION 1 ON SHEET A0.0

SPECIALTY EQUIPMENT TAG:-SPECIALTY EQUIPMENT TYPE S1SEE SPECIALTY EQUIPMENT SCHEDULE

PLAN KEYNOTE TAG- NOTE NUMBER 3SEE PLAN KEYNOTE SCHEDULE

CASEWORK TAGCASEWORK HAS BEEN DEVELOPED USING THE ARCHITECTURAL WOODWORK STANDARDS CASEWORK DESIGN SERIES DESIGNATIONS

-- ROOM NAME 1--: FLOOR NUMBER -- 01: SPACE NUMBER150 SF: NET SQUARE FOOTAGE

Room name101

150 SF

0

0

LEVEL

1

0A0.0

SIM

NORTH ARROW

0A0.0

SIM

500M30 24

36modification

3

FFENOT IN CONTRACT

00

MOUNTING HEIGHT LEGEND

ACRONYMS & ABBREVIATIONS

DRAWING SYMBOLS

TYPICAL ADA REACH RANGE

MOUNTING HEIGHT NOTES

AMA

BALAFOETATSRE

GISTERED ARCHIT

EC

T

3196

REGISTRATIONNUMBER

RODNEY STEGER

MEMBER OF THE AMERICAN INSTITUTE OF ARCHITECTS

This document is a copyright protected instrument of service and licnesed for use in the titled project only. This drawing may not be

reproduced in whole or in part without written permission of FUQUA & PARTNERS ARCHITECTS, P.C.

A Professional Corporation

DATE:

ISSUE:

DRAWN:

PROJECT NO:

SHEET

OF

Architecture

Interior Design

Media Visualization

Master Planning

100 Church Street, Suite 700Huntsville, Alabama 35801

PH: (256) 534.3516FX: (256) 533.4605

www.fuquaarchitects.com

CHECKED:

2/26

/202

0 10

:17:

51 A

M

TS.2

GEN

ERAL

INFO

RMAI

TON

301

SPAR

KMAN

DRI

VE, H

UN

TSVI

LLE,

AL

3589

9

AWF/ LF

02-25-2020

FPA #07519

RKS

100 % CDs

22

UAH

BAB

CYB

ER L

AB /

INTE

RIO

R RE

NO

VATI

ON

S

REVISIONS

Page 3: 100 Church Street, Suite 700 Huntsville, Alabama 35801 PH ...

UP

UP

UP

- D et ail

UP

145'

65'

2 HR RATED PARTITION

FIRE EXTINGUISHER CABINET

MAXIMUM TRAVEL DISTANCE TO EXIT

COMMON PATH OF TRAVEL

CLEAR EXIT WIDTH IN INCHES

EXIT SIGN

FEC

1 HR RATED PARTITION

34170 DOOR CLEAR WIDTH & EXIT CAPACITY

NOT IN SCOPE

ADJACENT EXISTING BUILDING(UAH I2C: BC#2016472)

EXIT

EXIT

EXIT

EXIT

EXIT

EXIT

FEC

EXIT

EXIT

EXIT

EXISTINGSTUDY

RESOURCE

EXISTINGTRADE LAB

CONFERENCEPBX

MAIL RM

ELECT.

EXISTINGMECHANICAL

EXISTINGTEAM

EXISTINGTEAM

EXISTINGTEAM

EXISTINGTEAM

EXISTINGTEAM

EXISTINGCASE

ROOM #2

EXISTINGCASE

ROOM #1EXISTINGSTAIR

ADMIN.

EXISTINGRECORD

EXISTINGRECEPTION

B.S.CONTROL

EXIST.CORRIDOR

BEHAV.SCIENCE

STUDYALCOVE

EXIST.CORRIDOR

EXISTINGATRIUMLOBBY

EXISTINGCASE

ROOM #3

EXISTINGCASE

ROOM #4

EXISTINGCASE

ROOM #5

EXISTINGMECHANICAL

MEN

EXIST. JAN.

EXISTINGAUDITORIUM

EXISTINGCORRIDOR

FEC

FEC

EXISTING RATED STAIR SHAFT EXTENDS TO GRADE LEVEL EXIT

EXISTING RATED STAIR SHAFT EXTENDS TO GRADE LEVEL EXIT

EXISTING BUILDING:28,000 S.F. PER FLOORTYPE 2A, SPRINKLERED

EXISTING ELEVATOR

EXISTING ELEVATOR

5'-7 1/4"

EXISTINGOFFICE

EXISTINGOFFICE

EXISTINGOFFICE

EXISTINGOFFICE

EXISTINGCORRIDOR

EXISTINGCORRIDOR

EXISTINGSTAIRS

EXISTINGOFFICEEXISTING

OFFICEEXISTINGOFFICE

EXISTINGOFFICE

EXISTINGOFFICE

EXISTINGOFFICE

EXISTINGOFFICE

EXISTINGOFFICE

EXIST.WORKROOM

EXIST.CONF.

EXIST.CONF.

EXISTINGCORRIDOR

EXIST.ELEV.

AIRLOCK

EXIST. CORRIDOR

EXIT

EXIT

EXIT

OPEN TO BELOW

DOWN

DOWN

UP

ELEVATOR

DOWN

UP

DOWN

DOWN

FEC

WOMEN

PBX

MEN

EXIST.CLASSROOM

EXIST.CORRIDOR

COMPUTERCLASSROOM

EXIST.CORRIDOR

EXISTING RATED STAIR SHAFT EXTENDS TO GRADE LEVEL EXIT

EXISTING RATED STAIR SHAFT EXTENDS TO GRADE LEVEL EXIT

EXISTING UAH I2C BUILDING

EXISTING BUILDING:28,000 S.F. PER FLOORTYPE 2A, SPRINKLERED

EXISTING ELEVATOR

EXISTING ELEVATOR

SHADED AREA IS SCOPE OF WORK AREA

EXIT

EXIST.CLASSROOM

EXIST.CLASSROOM

CLASSROOM

EX.SERVERROOM

EXISTINGPORCH

EXISTING MONUMENTAL STAIR

TRAVEL DISTANCE = 49'

EXIST.CLASSROOM

EXIST.CLASSROOM

EXIST.CLASSROOM

EXISTINGMECHANICAL

RECEPTION

CONFERENCEROOM

SECRETARY

TOIL.

OFFICE

OFFICE

OFFICE

OFFICE

CORRIDOR

EXISTINGMECHANICAL

OFFICE

EXIST.BALCONY

EXIST.BALCONY

EXIT

CYBERSECURITYLAB

LABSUPPORT

CYBERLOUNGE

JAN CLOSET

CLOSET

EXIST. CORRIDOR

UTILIY

EXIST. LAB

EXIST. LAB

FEC

EXISTING RATED STAIR SHAFT EXTENDS TO GRADE LEVEL EXIT

EXISTING RATED STAIR SHAFT EXTENDS TO GRADE LEVEL EXIT

EXISTING BUILDING:28,000 S.F. PER FLOORTYPE 2A, SPRINKLERED

EXISTING ELEVATOR

EXISTING ELEVATOR

EXISTING MONUMENTAL STAIR

FACULTY /STAFF

CORR.

MEN

OFFICE(TYP.)

2015 International Building Code

2015 International Plumbing Code

2015 International Mechanical Code

2015 International Fuel Gas Code

2015 International Fire Code

2014 National Electric Code

ANSI/ASHRAE/IESNA Standard 90.1-2013 Energy Standard for

Buildings Except Low-Rise Residential

2010 Americans with Disability Act Accessibility Standards

2003 National Fire Code (NFPA)

APPLICABLE CODES & REGULATIONS

2013 National Fire Alarm and Signaling Code (NFPA 72)

2015 International Existing Building Code

GENERAL INFORMATION

EXISTING BUILDINGS - CHAPTER 3 - COMPLIANCE METHODS

EXISTING BUILDINGS - CHAPTER 5 - CLASSIFICATION OF WORK

CONSTRUCTION TYPE AND SPRINKLER INFORMATION

PRIMARY OCCUPANCY CLASSIFICATION(S)

OCCUPANCY LOAD

MEANS OF EGRESS

PROJECT SCOPE CONSISTS OF INTERIOR RENOVATIONS

WORK AREA COMPLIANCE METHOD

FIRST FLOOR : LEVEL 1 ALTERATIONS - REMOVAL AND REPLACEMENT OF EXISTING FINISHES ONLYSECOND FLOOR : LEVEL 2 ALTERATIONS - RECONFIGURE AN EXISTING CLASSROOM AREA. REMOVAL AND REPLACEMENT OF EXISTING FINISHES

EXISTING TYPE 2A CONSTRUCTION, FULLY SPRINKLERED, IS BEING MAINTAINED.

EXISTING BUILDING OCCUPANCY WILL NOT CHANGE. CURRENT OCCUPANCIES INCLUDE:BUSINESS GROUP BASSEMBLY GROUP A-3

EXISTING OCCUPANCY LOAD IS BEING MAINTAINED.

NUMBER OF EXITS IS BEING MAINTAINED.EGRESS WIDTH AND PATH OF TRAVEL IS BEING MAINTAINED.ACCESSIBILITY MEANS OF EGRESS IS BEING MAINTAINED.

PLUMBING SYSTEMS NUMBER OF EXISTING FIXTURES COMPLIES WITH LEVEL 1 AND LEVEL 2 ALTERATIONS REQUIREMENTS.

LIFE SAFETY PLAN LEGEND

CC1.0 1/16" = 1'-0"

1 LIFE SAFETY PLAN - FIRST FLOOR

AMA

BALAFOETATSRE

GISTERED ARCHIT

EC

T

3196

REGISTRATIONNUMBER

RODNEY STEGER

MEMBER OF THE AMERICAN INSTITUTE OF ARCHITECTS

This document is a copyright protected instrument of service and licnesed for use in the titled project only. This drawing may not be

reproduced in whole or in part without written permission of FUQUA & PARTNERS ARCHITECTS, P.C.

A Professional Corporation

DATE:

ISSUE:

DRAWN:

PROJECT NO:

SHEET

OF

Architecture

Interior Design

Media Visualization

Master Planning

100 Church Street, Suite 700Huntsville, Alabama 35801

PH: (256) 534.3516FX: (256) 533.4605

www.fuquaarchitects.com

CHECKED:

2/26

/202

0 10

:17:

37 A

M

CC1.0

CO

DE

CO

MPL

IAN

CE

PLAN

S

301

SPAR

KMAN

DRI

VE, H

UN

TSVI

LLE,

AL

3589

9

LF

02-25-2020

FPA #07519

RKS

100 % CDs

11

UAH

BAB

CYB

ER L

AB /

INTE

RIO

R RE

NO

VATI

ON

S

CC1.0 1/16" = 1'-0"

2 LIFE SAFETY PLAN - SECOND FLOOR

CC1.0 1/16" = 1'-0"

3 LIFE SAFETY PLAN - THIRD FLOOR

REVISIONS

Page 4: 100 Church Street, Suite 700 Huntsville, Alabama 35801 PH ...

- De ta il

EXISTING CASEROOM #1

161

EXISTING TEAM117

EXISTING TEAM116

EXISTING TEAM118

EXISTING TEAM119

EXISTING CASEROOM #3

120

EXISTINGMECHANICAL

158

EXISTING TEAM159

EXISTING CASEROOM #2

160EXISTING STAIR

101EXISTING RECORD102

EXISTINGRECEPTION

110

STUDY ALCOVE114

EXIST. CORRIDOR115

EXIST. CORRIDOR115

EXISTING CORRIDOR146

EXISTING STUDYRESOURCE

150

EXISTING TRADE LAB147

WOMEN151

MEN144

EXISTING ATRIUMLOBBY

121

EXISTING CORRIDOR125

EXISTING CORRIDOR125

EXISTINGAUDITORIUM

26

EXISTINGMECHANICAL

142EXIST. JAN.145

EXISTING CASEROOM #4

123

EXISTING CASEROOM #5

124

EXIST. ELEV.143

BEHAV. SCIENCE113

B.S. CONTROL112

EXISTING OFFICE207EXISTING OFFICE

218

EXISTING OFFICE221

EXISTING OFFICE226

EXISTING OFFICE233

EXIST. WORKROOM126

EXISTING OFFICE128

EXISTING OFFICE127

EXIST. CONF.136

EXIST. CONF.135

EXISTING CORRIDOR137

EXISTING OFFICE134

EXISTING OFFICE129

EXISTING OFFICE130

EXISTING OFFICE131

EXISTING OFFICE132

EXISTING OFFICE133

EXISTING STAIRS256

EXISTING CORRIDOR137

AIRLOCK146A

2222

22

22 22

25

25

24

24

*ONLY AS REQUIRED FOR WORKABOVE

*ONLY AS REQUIRED FOR WORKABOVE

A. PRE-DEMOLITION MEETING: PRIOR TO THE ACTUAL START OF DEMOLITION WORK, THE CONTRACTOR SHALL SCHEDULE A PRE-DEMOLITION MEETING. THIS MEETING SHALL BE ATTENDED BY THE ARCHITECT, CONTRACTOR, SUPERINTENDENT, DEMOLITION FORMAN, AND OWNER. THE MEETING SHALL BE HELD AT THE CONSTRUCTION SITE. THE PURPOSE OF THE MEETING IS TO REVIEW THE SCOPE OF DEMOLITIONAND ALL ITEMS TO BE SALVAGED DURING DEMOLITON. THE CONTRACTOR SHALL PROVIDE A SET OF PLANS FOR THE MEETING. THE PLANS SHALL BE USED TO REVIEW AND MARK SPECIFIC ITEMS OF QUESTION. ALL ITEMS SHALL BE RESOLVED AND PART OF THE RECORD MINUTES TO BE DISTRIBUTED TO ALL PARTIES FOR RECORD. NO DEMOLITION SHALL OCCUR UNTIL THIS MEETING HAS BEEN CONDUCTED.

B. DEMOLITION DRAWINGS: DEMOLITION DRAWINGS ILLUSTRATE THE GENERAL SCOPE OF DEMOLITION WORK TO BE PERFORMED AND ARE NOT INTENDED TO BE COMPREHENSIVE OR ALL-INCLUSIVE. THE CONTRACTOR SHALL PERFORM THE DEMOLTION WORK INCLUDED IN THE DEMOLITION PLANS AND ITS ASSOCIATED CONSTRUCTION, ALONG WITH ANY AND ALL DEMOLITION REQUIRED FOR THE SUCCESSFUL COMPLETION OF THE NEW CONSTRUCTION WORK TO BE PERFORMED, INCLUDING THAT REQUIRED OF ARCHITECTURAL, STRUCTURAL, MECHANICAL, ELECTRICAL, AND SIMILAR APPLICABLE SUB-CONTRACTOR WORK.

C. TEMPORARY BRACING: PRIOR TO REMOVAL OF EXISTING STRUCTURAL ELEMENTS, THE CONTRACTOR SHALL TEMPORARILY SHORE AND/OR BRACE EXISTING CONSTRUCTION TO REMAIN AS REQUIRED TO SUPPORT EXISTING LOADS AND/OR LOADS IMPOSED DURING CONSTRUCTION.

D. THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS, CONSTRUCTION, MATERIALS, METHODS OF CONSTRUCTION, ELEVATIONS, ETC. PRIOR TO BIDDING, CONSTRUSTION, AND INSTALLATION. NOTIFY ARCHITECT OF ANY CONDITIONS WHICH MAY IMPACT THE BID, INCLUDING BUT NOT LIMITED TO CONCEALED CONDITIONS AFFECTING THE WORK AND ANY DISCREPANCIES WITHIN DOCUMENTS OR ENCOUNTERED DURING CONSTRUCTION PRIOR TO PROCEEDING WITH WORK.

E. ALL WORK SHALL BE COORDINATED WITH THE WORK OF OTHER TRADES TO AVOID INTERFERENCES AND CONFLICTS. REFER TO THE DRAWINGS OF THE RESPECTIVE SYSTEMS PRIOR TO SUBMISSION OF BIDS FOR ADDITIONAL WORK WHICH MAY BE REQUIRED AS PART OF THEIR WORK. NO ALLOWANCES WILL BE MADE FOR THE LACK OF COORDINATION BETWEEN DISCIPLINES OR SYSTEMS AND EQUIPMENT.

F. THE CONTRACTOR SHALL TAKE EXTREME CAUTION TO FULLY INVESTIGATE EXISTING FINISHES, CONSTRUCTION, MECHANICAL, ELECTRICAL AND PLUMBING SYSTEMS PRIOR TO DEMOLITION TO ASSURE CRITICAL SERVICES ARE NOT INTERRUPTED.

G. IT IS THE CONTRACTORS RESPONSIBILTY TO BARRICADE OFF AREA OF WORK AND PROVIDE PROTECTED ENTRANCES AND EXITS TO AND FROM THE BUILDING. DO NOT BLOCK EXITS.

H. PROJECT PLANS HAVE BEEN DEVELOPED FROM DRAWINGS PREVIOUSLY PREPARDED BY OTHERS. ACTUAL CONDITIONS MAY VARY. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND DETAILS RELATED TO EXISTING CONSTRUCTION AND MAKE MINOR ADJUSTMENTS AS REQUIRED. CONTRACTOR SHALL REPORT ANY DIFFERENCES TO THE ARCHITECT PRIOR TO BIDDING.

I. IT IS THE CONTRACTORS SOLE RESPONSIBILITY DURING DEMOLITION TO PROVIDE PROTECTION FOR ALL EXISTING CONSTRUCTION TO REMAIN. CONTRACTOR TO PATCH, REPAIR, AND REPLACE ANY AND ALL EXISTING CONSTRUCTION DAMAGED BY THE DEMOLITION, INCLUDING BUT NOT LIMITED TO: EXISTING STRUCTURE, FINISHES, CEILINGS. THE CONTRACTOR SHALL ALSO PROVIDE PROTECTIVE BARRIERS FROM DUST AND WEATHER DURING DEMOLITION SO AS NOT TO DAMAGE EXISTING CONSTRUCTION INDICATED TO REMAIN.

J. THE CONTRACTOR IS RESPONSIBLE FOR ANY ADDITIONAL DEMOLITION REQUIRED FOR THE COMPLETION OF THE WORKS AS DESCRIBED IN THE CONTRACT DOCUMENTS. THESE ITEMS INCLUDE BUT ARE NOT LIMITED TO: PIPING, WIRING, ETC. ANY CLARIFICATION REQUIRED SHALL BE OBTAINED FROM THE ARCHITECT, IN WRITING.

K. IT IS THE INTENT THAT WHERE NEW WORK IS INDICATED, THAT SOME EXISTING FINISHES, MATERIALS, ETC. SHALL BE REMOVED AS NECESSARY AND PRACTICAL TO INSTALL THE NEW WORK. ALL ADJACENT WALLS, CEILINGS, FLOORS, FINISHES, ETC. SHALL BE PREPARED AS REQUIRED TO RECEIVE NEW WORK.

L. EXISTING VCT TO REMAIN, UNLESS NOTED OTHERWISE.M. WHEN FLOORING IS TO BE REMOVED THE CONTRACTOR SHALL PROVIDE IN THE BASE BID ANY AND ALL COSTS ASSOCIATED WITH THE

REMOVAL OF THE EXISTING FLOORING SYSTEMS, DAMAGED SUBSTRATES, AND ANY OTHER ASSOCIATED CONSTRUCTION. THE BASE BID SHALL ALSO INCLUDE THE PATCHING, REPAIR AND LEVELING OF ANY EXISTING SUBSTRATE TO RECIEVE NEW FLOORING SYSTEMS.

N. CODE COMPLIANCE: PERFORM ALL WORK IN STRICT ACCORDANCE WITH APPLICABLE LAWS, CODES, AND ORDINANCES.O. SECURE NECESSARY PERMITS AND APPROVALS FOR WORK IN AND ADJACENT TO CITY RIGHT-OF-WAYS. P. ALL DUCTWORK, PIPING AND CONDUIT SCHEDULED FOR SELECTIVE DEMOLITION SHOULD INCLUDE COMPLETE REMOVAL INCLUDING ALL

HANGERS, SUPPORTS, TECH.Q. REMOVE ALL EXISTING BASE TRIM, WAINSCOT TRIM, FLOORING, WALL COVERING, AND WALL ACCESSORIES WITHIN THE SCOPE OF WORK

AREA.

DEMOLITION/CONSTRUCTION NOTES

EXISTING WALLS TO REMAIN

EXISTING CONSTRUCTION TO BE DEMOLISHED

DEMOLITION KEY NOTES

WALLS TO BE MODIFIED

EXTENT OF CEILING RENOVATION

BEYOND EXTENT OF RENOVATION

EXISTING FIXTURES TO BE DEMOLISHED

DEMOLITION PLAN LEGEND

2

DEMOLITION KEY NOTES#

AIR RETURN (V.I.F.)

AIR SUPPLY (V.I.F.)

1. REMOVE AND REPLACE EXISTING CEILING. SEE RCP DEMOLITION PLAN FOR ADDITIONAL INFORMATION2. EXISTING EXIT LIGHTS, FIRE PULL, PUSH TO EXIT BOXES, AND THERMOSTAT TO BE REMOVED. RELOCATE ANY DEVICES AS INDICATED ON

ELECTRICAL ENGINEERING DRAWINGS3. EXISTING STEEL COLUMN AND RAIN WATER LEADER TO REMAIN4. EXISTING MARKER BOARD, WALL CLOCK, PROJECTION SCREEN, AND ACCESSORIES TO BE REMOVED AND TURNED OVER TO OWNER.5. EXISTING HVAC UNIT TO REMAIN6. EXISTING ELECTRICAL PANELS TO REMAIN7. EXISTING WATER COOLER TO BE REMOVED AND LINES CAPPED OR REROUTED TO NEW WATER COOLER LOCATION, PER ENGINEERING

DRAWINGS.8. REMOVE EXISTING CASEWORK AND TURN OVER TO OWNER9. DEMOLISH EXISTING WOOD SHELVING10. REMOVE EXISTING WALL-MOUNTED ELECTRICAL RACEWAY11. EXISTING THERMOSTAT. RELOCATE PER ENGINEERING DRAWINGS12. REMOVE EXISTING TELEVISION WALL MOUNT AND TURN OVER TO OWNER13. EXISTING CEILING GRID TO REMAIN. CEILING TILES TO BE REPLACED. 14. EXISTING LIGHTING TO BE RE-USED IF FIXTURES ARE LED, IF NOT REPLACE WITH LED FIXTURES AND INSTALL PER ELECTRICAL

ENGINEERING DRAWINGS.15. SALVAGE EXISTING DOORS FOR POSSIBLE RE-USE. (IF DOORS ARE TO BE RE-USED TOUCH UP TO LIKE NEW CONDITION)16. REMOVE EXISTING REVEAL, PATCH WALL TO BE FLUSH WITH REMAINDER OF CYBERSECURITY LAB WALL17. EXISTING LIGHTING AND HVAC SUPPLY AND RETURN GRILLES TO BE REMOVED AND REPLACED. VERIFY QUANTITIES AND CONFIGURATION 18. REMOVE WALL COVERING AND REPAIR GYPSUM WALL BOARD WHERE NECESSARY. PREPARE WALL FOR NEW FINISHES19. EXISTING REVEALS TO REMAIN AND BE REPAINTED20. REMOVE EXISTING PROJECTOR AND TURN OVER TO OWNER21. EXISTING FIRE EXTINGUISHER CABINET TO BE REMOVED AND RE-LOCATED PER NEW CONSTRUCTION DRAWINGS22. EXISTING COLUMN WRAP TO BE DEMOLISHED AND RE-WRAPPED PER NEW CONSTRUCTION DRAWINGS; IF COLUMN CONTAINS NO

STRUCTURE DO NOT REPLACE, COLUMN IS TO BE ELIMINATED COMPLETELY23. EXISTING FLOORING TO BE REMOVED AND FLOOR IS TO BE CLEANED AND PREPARED TO RECEIVE SCHEDULED FLOORING24. CEILING REMOVED AND REINSTALLED AS REQUIRED FOR MODIFICATIONS OF PLUMBING & ELECTRICAL IN SPACE ABOVE. 25. EXISTING COLUMN WRAP TO REMAIN, PREPARE SURFACES TO RECEIVE NEW PAINT FINISHES.26. EXISTING STRUCTURE AND ROOF LEADER TO REMAIN

AMA

BALAFOETATSRE

GISTERED ARCHIT

EC

T

3196

REGISTRATIONNUMBER

RODNEY STEGER

MEMBER OF THE AMERICAN INSTITUTE OF ARCHITECTS

This document is a copyright protected instrument of service and licnesed for use in the titled project only. This drawing may not be

reproduced in whole or in part without written permission of FUQUA & PARTNERS ARCHITECTS, P.C.

A Professional Corporation

DATE:

ISSUE:

DRAWN:

PROJECT NO:

SHEET

OF

Architecture

Interior Design

Media Visualization

Master Planning

100 Church Street, Suite 700Huntsville, Alabama 35801

PH: (256) 534.3516FX: (256) 533.4605

www.fuquaarchitects.com

CHECKED:

3/9/

2020

7:5

9:04

AM

A0.1

DEM

OLI

TIO

N P

LAN

-FI

RST

FLO

OR

301

SPAR

KMAN

DRI

VE, H

UN

TSVI

LLE,

AL

3589

9

LWF

02-25-2020

FPA #07519

RS

100 % CDs

121

UAH

BAB

CYB

ER L

AB /

INTE

RIO

R RE

NO

VATI

ON

S

NORTH

1/8" = 1'-0"

FIRST FLOOR DEMOLITION PLAN

KEY PLAN

0' 4' 8' 16' 32'

REVISIONS

1 Addendum #1 MARCH 9, 2020

1

Page 5: 100 Church Street, Suite 700 Huntsville, Alabama 35801 PH ...

DNDN

UP

A. PRE-DEMOLITION MEETING: PRIOR TO THE ACTUAL START OF DEMOLITION WORK, THE CONTRACTOR SHALL SCHEDULE A PRE-DEMOLITION MEETING. THIS MEETING SHALL BE ATTENDED BY THE ARCHITECT, CONTRACTOR, SUPERINTENDENT, DEMOLITION FORMAN, AND OWNER. THE MEETING SHALL BE HELD AT THE CONSTRUCTION SITE. THE PURPOSE OF THE MEETING IS TO REVIEW THE SCOPE OF DEMOLITIONAND ALL ITEMS TO BE SALVAGED DURING DEMOLITON. THE CONTRACTOR SHALL PROVIDE A SET OF PLANS FOR THE MEETING. THE PLANS SHALL BE USED TO REVIEW AND MARK SPECIFIC ITEMS OF QUESTION. ALL ITEMS SHALL BE RESOLVED AND PART OF THE RECORD MINUTES TO BE DISTRIBUTED TO ALL PARTIES FOR RECORD. NO DEMOLITION SHALL OCCUR UNTIL THIS MEETING HAS BEEN CONDUCTED.

B. DEMOLITION DRAWINGS: DEMOLITION DRAWINGS ILLUSTRATE THE GENERAL SCOPE OF DEMOLITION WORK TO BE PERFORMED AND ARE NOT INTENDED TO BE COMPREHENSIVE OR ALL-INCLUSIVE. THE CONTRACTOR SHALL PERFORM THE DEMOLTION WORK INCLUDED IN THE DEMOLITION PLANS AND ITS ASSOCIATED CONSTRUCTION, ALONG WITH ANY AND ALL DEMOLITION REQUIRED FOR THE SUCCESSFUL COMPLETION OF THE NEW CONSTRUCTION WORK TO BE PERFORMED, INCLUDING THAT REQUIRED OF ARCHITECTURAL, STRUCTURAL, MECHANICAL, ELECTRICAL, AND SIMILAR APPLICABLE SUB-CONTRACTOR WORK.

C. TEMPORARY BRACING: PRIOR TO REMOVAL OF EXISTING STRUCTURAL ELEMENTS, THE CONTRACTOR SHALL TEMPORARILY SHORE AND/OR BRACE EXISTING CONSTRUCTION TO REMAIN AS REQUIRED TO SUPPORT EXISTING LOADS AND/OR LOADS IMPOSED DURING CONSTRUCTION.

D. THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS, CONSTRUCTION, MATERIALS, METHODS OF CONSTRUCTION, ELEVATIONS, ETC. PRIOR TO BIDDING, CONSTRUSTION, AND INSTALLATION. NOTIFY ARCHITECT OF ANY CONDITIONS WHICH MAY IMPACT THE BID, INCLUDING BUT NOT LIMITED TO CONCEALED CONDITIONS AFFECTING THE WORK AND ANY DISCREPANCIES WITHIN DOCUMENTS OR ENCOUNTERED DURING CONSTRUCTION PRIOR TO PROCEEDING WITH WORK.

E. ALL WORK SHALL BE COORDINATED WITH THE WORK OF OTHER TRADES TO AVOID INTERFERENCES AND CONFLICTS. REFER TO THE DRAWINGS OF THE RESPECTIVE SYSTEMS PRIOR TO SUBMISSION OF BIDS FOR ADDITIONAL WORK WHICH MAY BE REQUIRED AS PART OF THEIR WORK. NO ALLOWANCES WILL BE MADE FOR THE LACK OF COORDINATION BETWEEN DISCIPLINES OR SYSTEMS AND EQUIPMENT.

F. THE CONTRACTOR SHALL TAKE EXTREME CAUTION TO FULLY INVESTIGATE EXISTING FINISHES, CONSTRUCTION, MECHANICAL, ELECTRICAL AND PLUMBING SYSTEMS PRIOR TO DEMOLITION TO ASSURE CRITICAL SERVICES ARE NOT INTERRUPTED.

G. IT IS THE CONTRACTORS RESPONSIBILTY TO BARRICADE OFF AREA OF WORK AND PROVIDE PROTECTED ENTRANCES AND EXITS TO AND FROM THE BUILDING. DO NOT BLOCK EXITS.

H. PROJECT PLANS HAVE BEEN DEVELOPED FROM DRAWINGS PREVIOUSLY PREPARDED BY OTHERS. ACTUAL CONDITIONS MAY VARY. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND DETAILS RELATED TO EXISTING CONSTRUCTION AND MAKE MINOR ADJUSTMENTS AS REQUIRED. CONTRACTOR SHALL REPORT ANY DIFFERENCES TO THE ARCHITECT PRIOR TO BIDDING.

I. IT IS THE CONTRACTORS SOLE RESPONSIBILITY DURING DEMOLITION TO PROVIDE PROTECTION FOR ALL EXISTING CONSTRUCTION TO REMAIN. CONTRACTOR TO PATCH, REPAIR, AND REPLACE ANY AND ALL EXISTING CONSTRUCTION DAMAGED BY THE DEMOLITION, INCLUDING BUT NOT LIMITED TO: EXISTING STRUCTURE, FINISHES, CEILINGS. THE CONTRACTOR SHALL ALSO PROVIDE PROTECTIVE BARRIERS FROM DUST AND WEATHER DURING DEMOLITION SO AS NOT TO DAMAGE EXISTING CONSTRUCTION INDICATED TO REMAIN.

J. THE CONTRACTOR IS RESPONSIBLE FOR ANY ADDITIONAL DEMOLITION REQUIRED FOR THE COMPLETION OF THE WORKS AS DESCRIBED IN THE CONTRACT DOCUMENTS. THESE ITEMS INCLUDE BUT ARE NOT LIMITED TO: PIPING, WIRING, ETC. ANY CLARIFICATION REQUIRED SHALL BE OBTAINED FROM THE ARCHITECT, IN WRITING.

K. IT IS THE INTENT THAT WHERE NEW WORK IS INDICATED, THAT SOME EXISTING FINISHES, MATERIALS, ETC. SHALL BE REMOVED AS NECESSARY AND PRACTICAL TO INSTALL THE NEW WORK. ALL ADJACENT WALLS, CEILINGS, FLOORS, FINISHES, ETC. SHALL BE PREPARED AS REQUIRED TO RECEIVE NEW WORK.

L. EXISTING VCT TO REMAIN, UNLESS NOTED OTHERWISE.M. WHEN FLOORING IS TO BE REMOVED THE CONTRACTOR SHALL PROVIDE IN THE BASE BID ANY AND ALL COSTS ASSOCIATED WITH THE

REMOVAL OF THE EXISTING FLOORING SYSTEMS, DAMAGED SUBSTRATES, AND ANY OTHER ASSOCIATED CONSTRUCTION. THE BASE BID SHALL ALSO INCLUDE THE PATCHING, REPAIR AND LEVELING OF ANY EXISTING SUBSTRATE TO RECEIVE NEW FLOORING SYSTEMS.

N. CODE COMPLIANCE: PERFORM ALL WORK IN STRICT ACCORDANCE WITH APPLICABLE LAWS, CODES, AND ORDINANCES.O. SECURE NECESSARY PERMITS AND APPROVALS FOR WORK IN AND ADJACENT TO CITY RIGHT-OF-WAYS. P. ALL DUCTWORK, PIPING AND CONDUIT SCHEDULED FOR SELECTIVE DEMOLITION SHOULD INCLUDE COMPLETE REMOVAL INCLUDING

ALL HANGERS, SUPPORTS, TECH.Q. REMOVE ALL EXISTING BASE TRIM, WAINSCOT TRIM, FLOORING, WALL COVERING, AND WALL ACCESSORIES WITHIN THE SCOPE OF

WORK AREA.

DEMOLITION/CONSTRUCTION NOTES

EXISTING WALLS TO REMAIN

EXISTING CONSTRUCTION TO BE DEMOLISHED

DEMOLITION KEY NOTES

WALLS TO BE MODIFIED

EXTENT OF CEILING RENOVATION

BEYOND EXTENT OF RENOVATION

EXISTING FIXTURES TO BE DEMOLISHED

DEMOLITION PLAN LEGEND

2

1. REMOVE AND REPLACE EXISTING CEILING. SEE RCP DEMOLITION PLAN FOR ADDITIONAL INFORMATION2. EXISTING EXIT LIGHTS, FIRE PULL, PUSH TO EXIT BOXES, AND THERMOSTAT TO BE REMOVED. RELOCATE ANY DEVICES AS INDICATED ON

ELECTRICAL ENGINEERING DRAWINGS3. EXISTING STEEL COLUMN AND RAIN WATER LEADER TO REMAIN4. EXISTING MARKER BOARD, WALL CLOCK, PROJECTION EQUIPMENT, VOICE AMPLIFICATION EQUIPMENT AND ACCESSORIES TO BE

REMOVED AND TURNED OVER TO OWNER.5. EXISTING HVAC UNIT TO REMAIN. REFER TO MECHANICAL DRAWINGS FOR DETAILS.6. EXISTING ELECTRICAL PANELS TO REMAIN7. EXISTING WATER COOLER TO BE REMOVED AND LINES CAPPED OR REROUTED TO NEW WATER COOLER LOCATION, PER ENGINEERING

DRAWINGS.8. REMOVE EXISTING CASEWORK AND TURN OVER TO OWNER9. DEMOLISH EXISTING WOOD SHELVING10. REMOVE EXISTING WALL-MOUNTED ELECTRICAL RACEWAY11. EXISTING THERMOSTAT. RELOCATE PER ENGINEERING DRAWINGS12. REMOVE EXISTING TELEVISION WALL MOUNT AND TURN OVER TO OWNER13. EXISTING CEILING GRID TO REMAIN. CEILING TILES TO BE REPLACED. 14. EXISTING LIGHTING TO BE RE-USED IF FIXTURES ARE LED, IF NOT REPLACE WITH LED FIXTURES AND INSTALL PER ELECTRICAL

ENGINEERING DRAWINGS.15. SALVAGE EXISTING DOORS FOR POSSIBLE RE-USE. (IF DOORS ARE TO BE RE-USED TOUCH UP TO LIKE NEW CONDITION)16. REMOVE EXISTING REVEAL, PATCH WALL TO BE FLUSH WITH REMAINDER OF CYBERSECURITY LAB WALL17. EXISTING LIGHTING AND HVAC SUPPLY AND RETURN GRILLES TO BE REMOVED AND REPLACED. VERIFY QUANTITIES AND CONFIGURATION 18. REMOVE WALL COVERING AND REPAIR GYPSUM WALL BOARD WHERE NECESSARY. PREPARE WALL FOR NEW FINISHES19. EXISTING REVEALS TO REMAIN AND BE REPAINTED20. REMOVE EXISTING PROJECTOR AND TURN OVER TO OWNER21. EXISTING FIRE EXTINGUISHER CABINET TO BE REMOVED AND RE-LOCATED PER NEW CONSTRUCTION DRAWINGS22. EXISTING COLUMN WRAP TO BE DEMOLISHED AND RE-WRAPPED PER NEW CONSTRUCTION DRAWINGS; IF COLUMN CONTAINS NO

STRUCTURE DO NOT REPLACE, COLUMN IS TO BE ELIMINATED COMPLETELY23. EXISTING FLOORING TO BE REMOVED AND FLOOR IS TO BE CLEANED AND PREPARED TO RECEIVE SCHEDULED FLOORING24. SALVAGE EXISTING METAL REVEALS TO BE REUSED IF POSSIBLE.25. EXISTING COLUMN WRAP TO REMAIN, PREPARE SURFACES TO RECEIVE NEW PAINT FINISHES.26. EXISTING STRUCTURE AND ROOF LEADER TO REMAIN

DEMOLITION KEY NOTES#

AIR RETURN (V.I.F.)

AIR SUPPLY (V.I.F.)

UP

WOMEN

PBX

EXIST.CORRIDOR

COMPUTERCLASSROOM

EXIST.BALCONY

MENEXISTING

ELEC.

EXIST.CLASSROOM

EXIST. CORRIDOR211

RECEPTION

EXISTINGPORCH

EX. SERVER ROOM238

EXISTING CORRIDOR231

EXISTINGCLOSET

EXIST.JANITOR EXIST.

COPY RM

EXIST.ELEV.

EXISTINGMECHANICAL

EXIST.ELEV.

EXISTINGMECHANICAL

EXIST.CLASSROOM

EXIST.CLASSROOM

CLASSROOM

EXIST.CLASSROOM

EXIST.CLASSROOM

EXIST.CLASSROOM

OFFICE

OFFICESECRETARY

CONFERENCEROOM

STOR.

TOIL.

OFFICE

STAIRS

EXIST. CORRIDOR207

18 19

18 19

EXIST. CLASSROOM

EXIST. LAB

4 18 20 410 18 2010

EXIST. GRAD STUDENTLOUNGE

22

22

21

7

LAB

LAB

2222

22

18 19

23

23 23

4 18 2010 23

18 20 23

18 19CARPET AND TILE FLOORING TO BE REMOVED UP TO THIS LINE

EXIST. SITTING AREA

17

17

1

171

171

1

1 114

14

14

4 101 14

EXIST. CLASSROOM

1

15

AIRLOCK233

18 19171

15

15 15

15

24

24

25

WALLCOVERING TO REMAIN13'-3" EXISTING

26

DOWN

DOWN

DN

AMA

BALAFOETATSRE

GISTERED ARCHIT

EC

T

3196

REGISTRATIONNUMBER

RODNEY STEGER

MEMBER OF THE AMERICAN INSTITUTE OF ARCHITECTS

This document is a copyright protected instrument of service and licnesed for use in the titled project only. This drawing may not be

reproduced in whole or in part without written permission of FUQUA & PARTNERS ARCHITECTS, P.C.

A Professional Corporation

DATE:

ISSUE:

DRAWN:

PROJECT NO:

SHEET

OF

Architecture

Interior Design

Media Visualization

Master Planning

100 Church Street, Suite 700Huntsville, Alabama 35801

PH: (256) 534.3516FX: (256) 533.4605

www.fuquaarchitects.com

CHECKED:

2/26

/202

0 10

:14:

46 A

M

A0.2

DEM

OLI

TIO

N P

LAN

-SE

CO

ND

FLO

OR

301

SPAR

KMAN

DRI

VE, H

UN

TSVI

LLE,

AL

3589

9

LF

02-25-2020

FPA #07519

RKS

100 % CDs

122

UAH

BAB

CYB

ER L

AB /

INTE

RIO

R RE

NO

VATI

ON

S

NORTH

1/8" = 1'-0"

SECOND FLOOR DEMOLITION PLAN

KEY PLAN

0' 4' 8' 16' 32'

REVISIONS

Page 6: 100 Church Street, Suite 700 Huntsville, Alabama 35801 PH ...

UP

DN

SHADED AREAS ARE EXISTING TO REMAIN (NO WORK)

REMOVE EXISTING WALLCOVERING, AND REFINISH WALLS IN EXISTING CORRIDORS. EXISTING GYP. REVEALS ARE TO REMAIN. REPLACE EXISTING CEILING AND LIGHTING

REMOVE EXISTING WALLCOVERING, AND REFINISH WALLS IN EXISTING CORRIDORS. EXISTING GYP. REVEALS ARE TO REMAIN. REPLACE EXISTING SUSPENDED CEIILING AND LIGHTING

COMPUTERCLASSROOM

EXIST.CLASSROOM

EXIST. LAB

EXIST. LAB

EXISTINGPORCH

EXIST.CLASSROOM

EXIST.CLASSROOM

EXIST.CLASSROOM

EXIST.CLASSROOM

EXIST.CLASSROOM

CLASSROOM

STAIR

CORRIDOROFFICE

OFFICE

OFFICE SECRETARYCONFERENCE

ROOM

RECEPTION EXIST.CORRIDOR

EXIST.BALCONY

EXIST.CORRIDOR

EXISTINGMECHANICAL

CYBERSECURITYLAB

CYBERLOUNGE

LABSUPPORT

STAIRS

EXIST.CORRIDOR

SHADED AREAS ARE EXISTING TO REMAIN (NO WORK)

REPAIR AND PATCH CEILING AND FLOOR WHERE COLUMNS ARE REMOVED OR MODIFIED - SEE FINISH FLOOR PLAN FOR TILE DETAILS

WORK IN THIS AREA LIMITED TO REMOVAL OF CEILING AS REQUIRED FOR ABOVE CEILING WORK. EXISTING CEILING TO BE STORED AND REINSTALLED ONCE WORK IS COMPLETE

EXISTINGAUDITORIUM

EXISTINGCASE

ROOM #5

EXISTINGCASE

ROOM #4

EXISTINGCASE

ROOM #1

EXISTINGCASE

ROOM #2

EXISTINGCASE

ROOM #3

EXISTINGATRIUMLOBBY

WOMEN

MEN

EXISTINGTRADE LAB

EXISTINGSTUDY

RESOURCE

EXISTINGMECHANICAL

EXIST.CONF.

EXIST.CONF.

EXISTINGCORRIDOR

EXISTINGOFFICE

EXISTINGOFFICE

EXISTINGOFFICE

EXISTINGOFFICE

EXISTINGOFFICE

EXISTINGOFFICE

EXISTINGOFFICE

EXISTINGOFFICE

EXIST.WORKROOM

ADMIN.

EXISTINGRECORD

EXISTINGSTAIR

EXISTINGOFFICE

EXISTINGOFFICE

EXISTINGOFFICE

EXISTINGOFFICE

EXISTINGCORRIDOR

B.S.CONTROL

BEHAV.SCIENCE

STUDYALCOVE

EXISTINGTEAM

EXISTINGTEAM

EXISTINGTEAMEXISTING

TEAM

AMA

BALAFOETATSRE

GISTERED ARCHIT

EC

T

3196

REGISTRATIONNUMBER

RODNEY STEGER

MEMBER OF THE AMERICAN INSTITUTE OF ARCHITECTS

This document is a copyright protected instrument of service and licnesed for use in the titled project only. This drawing may not be

reproduced in whole or in part without written permission of FUQUA & PARTNERS ARCHITECTS, P.C.

A Professional Corporation

DATE:

ISSUE:

DRAWN:

PROJECT NO:

SHEET

OF

Architecture

Interior Design

Media Visualization

Master Planning

100 Church Street, Suite 700Huntsville, Alabama 35801

PH: (256) 534.3516FX: (256) 533.4605

www.fuquaarchitects.com

CHECKED:

2/26

/202

0 10

:15:

09 A

M

A1.0

GEN

ERAL

INFO

RMAT

ION

FIR

ST A

ND

SEC

ON

D F

LOO

R PL

ANS

301

SPAR

KMAN

DRI

VE, H

UN

TSVI

LLE,

AL

3589

9

LF

02-25-2020

FPA #07519

RKS

100 % CDs

123

UAH

BAB

CYB

ER L

AB /

INTE

RIO

R RE

NO

VATI

ON

S

0' 2' 4 8' 16'

KEY PLAN

REVISIONS

NORTH

1/16" = 1'-0"

SECOND FLOOR PLAN - GENERAL INFORMATIONNORTH

1/16" = 1'-0"

FIRST FLOOR PLAN - GENERAL INFORMATION

Page 7: 100 Church Street, Suite 700 Huntsville, Alabama 35801 PH ...

EXISTINGCASE

ROOM #1

EXISTING TEAM117

EXISTING TEAM116

EXISTING TEAM118

EXISTING TEAM119

EXISTINGCASE

ROOM #3

EXISTINGMECHANICAL

EXISTINGTEAM

EXISTINGCASE

ROOM #2EXISTING STAIR101

EXISTINGRECORD

EXISTINGRECEPTION

STUDYALCOVE

EXIST. CORRIDOR115

EXIST. CORRIDOR115

EXISTING CORRIDOR146

EXISTING STUDYRESOURCE

150

EXISTING TRADE LAB147

WOMEN

MEN

EXISTINGATRIUMLOBBY

EXISTING CORRIDOR125

EXISTING CORRIDOR125

EXISTINGAUDITORIUM

EXISTINGMECHANICAL

EXIST. JAN.

EXISTINGCASE

ROOM #4

EXISTINGCASE

ROOM #5

EXIST.ELEV.

BEHAV.SCIENCE

B.S.CONTROL

EXISTINGOFFICEEXISTING

OFFICE

EXISTINGOFFICE

EXISTINGOFFICE

EXISTINGOFFICE

EXIST.WORKROOM

EXISTINGOFFICE

EXISTINGOFFICE

EXIST.CONF.

EXIST.CONF.

EXISTINGCORRIDOR

EXISTINGOFFICE

EXISTINGOFFICE

EXISTINGOFFICE

EXISTINGOFFICE

EXISTINGOFFICE

EXISTINGOFFICE

EXISTING STAIRS256

EXISTING CORRIDOR137

REPAIR AND PATCH CEILING AND FLOOR AT NEW COLUMN DETAIL - SEE FINISH FLOOR PLAN FOR TILE DETAILS

REPAIR AND PATCH CEILING AND FLOOR WHERE COLUMN WAS REMOVED - SEE FINISH FLOOR PLAN FOR TILE DETAILS

REPAIR AND PATCH CEILING AND FLOOR WHERE COLUMN WAS REMOVED - SEE FINISH FLOOR PLAN FOR TILE DETAILS

AIRLOCK146A

1

REPAIR AND PATCH CEILING AND FLOOR WHERE COLUMN WAS REMOVED - SEE FINISH FLOOR PLAN FOR TILE DETAILS

WORK IN THIS AREA LIMITED TO REMOVAL OF CEILING ONLY AS REQUIRED FOR ABOVE CEILING WORK. EXISTING CEILING TO BE STORED AND REINSTALLED ONCE WORK IS COMPLETE

CONFERENCE149

A6.0

9

EXIST.ELECT.

PBX

MAIL RM

EXIST.ELEV.

EXISTINGOFFICE

ADMIN.

EXIST.CORRIDOR

1

1

EXIST. AVBOOTH

EXIST.CLOSET

EXIST.STORAGE

EXIST.ELECT.

1

1

1

1

GENERAL RENOVATION NOTESA. EXISTING ROUND COLUMN WRAPS AND BASE TO BE REMOVEDB. EXISTING CEILING AND LIGHTING TO REMAINC. EXISTING CEILING TO BE REPAIRED AND PATCHED AFTER COLUMN WRAP REMOVALD. EXISTING FLOOR TILE TO BE SAW CUT AT EXISTING ROUND COLUMNS AFTER REMOVAL TO CREATE NEW PATTERN - SEE COLUMN COVER REMOVAL

DETAIL BELOW FOR GENERAL LAYOUT

RENOVATION PLAN LEGEND

EXISTING CONSTRUCTION TO REMAIN

AMA

BALAFOETATSRE

GISTERED ARCHIT

EC

T

3196

REGISTRATIONNUMBER

RODNEY STEGER

MEMBER OF THE AMERICAN INSTITUTE OF ARCHITECTS

This document is a copyright protected instrument of service and licnesed for use in the titled project only. This drawing may not be

reproduced in whole or in part without written permission of FUQUA & PARTNERS ARCHITECTS, P.C.

A Professional Corporation

DATE:

ISSUE:

DRAWN:

PROJECT NO:

SHEET

OF

Architecture

Interior Design

Media Visualization

Master Planning

100 Church Street, Suite 700Huntsville, Alabama 35801

PH: (256) 534.3516FX: (256) 533.4605

www.fuquaarchitects.com

CHECKED:

3/9/

2020

7:5

9:23

AM

A1.1

FIRS

T FL

OO

R -O

VERA

LL R

ENO

VATI

ON

PLA

N301

SPAR

KMAN

DRI

VE, H

UN

TSVI

LLE,

AL

3589

9

LWF

02-25-2020

FPA #07519

RS

100 % CDs

124

UAH

BAB

CYB

ER L

AB /

INTE

RIO

R RE

NO

VATI

ON

S

NORTH

1/8" = 1'-0"

FIRST FLOOR - OVERALL RENOVATION PLAN

0' 4' 8' 16' 32'

KEY PLAN

1

1

REVISIONS

1 Addendum #1 MARCH 9, 2020

Page 8: 100 Church Street, Suite 700 Huntsville, Alabama 35801 PH ...

UP

OPEN TO BELOW

EXIST.BALCONY

COMPUTERCLASSROOM

206

PBX

MEN

EXISTINGELEC.

EXIST. CLASSROOM209

WOMEN

UP

DN

EX

EXISTINGCLOSET

EX

EX

EX

EXISTINGCORRIDOR

231

EXISTINGPORCH

UTILITY

EXIST. CORRIDOR211

RECEPTION

STAIR201

EXIST.JANITOR EXIST.

COPY RM

EXIST.ELEV.

EXISTINGMECHANICAL

EXIST.ELEV.

EXISTINGMECHANICAL

EXIST. CLASSROOM232C

EXIST. CLASSROOM205

CLASSROOM243

102 SF

LABSUPPORT

217

EXIST. CLASSROOM220

EXIST. CLASSROOM224

EXIST. CLASSROOM222

RECORDSOFFICE

OFFICE

OFFICESECRETARY

CONFERENCEROOM

STOR.

TOIL.

OFFICE

STAIRS219

CORRIDOR

EX EX

EX

EXEX

EX

EX

EX

EX

EX

EX EX

EX

EX

EX

EX EX

EXEXEX

EX

EX

EX

EX

EX

EX

CYBER LOUNGE218

CYBERSECURITY LAB219

219A

219B 217

EX

EX

EX

EX

EX

EX

1 1NEW COLUMN WRAPSSEE DETAILS ON A

A1.2a

1

1

8'-5 1/4" 26'-8 1/2" 10'-5"

7'-10

1/4

"

9'-11

"

23'-6

1/4

"34

'-1"

222 2

A6.0

5

A6.0

12

3

NEW WATER FOUNTAIN / BOTTLE FILLER

RELOCATEDFIRE EXTIGUISHER CABINET

EXIST.CORRIDOR

207

EX

A6.07

A6.0

8

PNT-4

PNT-4

PNT-4

PNT-4

PNT-4

PNT-4

AIRLOCK233

TECH COUNTER

RACK5'-0"

EX

3

6

DN

EXIST. LAB244

EXIST. LAB258

15A6.0

15A6.0

1

OFFICE

EXISTING SERVER RM.

RENOVATION PLAN LEGEND

EXISTING TO REMAIN

GENERAL RENOVATION NOTESA. WHERE SCHEDULE, DOOR FRAMES (ON RENOVATION SIDE) TO BE PAINTED PNT-2. ONLY FRAMES TO BE PAINTED. DOORS SHOULD REMAIN

UNPAINTEDB. WITHIN RENOVATED AREAS OR AS INDICATED ON SCHEDULE, ALL EXISTING ROOM SIGNS, PLAQUES, AND PORTRAITS TO BE CAREFULLY REMOVED,

THEN REPLACED ONCE WALLS HAVE BEEN PAINTED. (IF SIGNAGE ALTERNATE IS NOT ACCEPTED)C. WITHIN RENOVATED AREAS, ALL EXISTING ARTWORK TO BE CAREFULLY REMOVED AND TURNED OVER TO THE UNIVERSITY.D. WITHIN RENOVATED AREAS, REMOVE EXISTING WALL COVERING AND REPAIR GYPSUM WALL BOARD WHERE NECESSARY. PREPARE WALL FOR NEW

FINISHESE. WITHIN RENOVATED AREAS, EXISTING METAL REVEALS TO REMAIN AND BE PAINTED PNT-2F. WITHIN RENOVATED AREAS, ALL HARD TILE BASE IS TO REMAIN UNLESS OTHERWISE NOTED.G. WITHIN RENOVATED AREAS, OR AS INDICATED ON SCHEDULE, INTERIOR SIDE OF WINDOW TRIM TO BE PAINTED PNT-2.H. WITHIN RENOVATED AREAS, EXISTING INTERIOR UNPAINTED BRICK ARE TO BE CLEANED AND PAINTED PNT-1.

THIS DRAWING IS INTENDED TO SHOW GENERAL LOCATIONS OF INTERIOR WALL TYPES. REFER TO OTHER DRAWINGS FOR SPECIFIC WALL CONSTRUCTION, INCLUDING LOCATION OF APPLIED FINISHES. REFER TO WALL SECTIONS AND DETAILS FOR INFORMATION REGARDING CONSTRUCTION OF EXTERIOR WALLS.

3 5/8" METAL STUDS WITH 3/4" PLYWOOD ON ALL SIDES, EXTEND 6" ABOVE CEILING. SEE DETAIL 9/A6.0 FOR WALL CONSTRUCTION.

3 5/8" METAL STUDS AT 16" O.C. WITH ONE LAYER 5/8" GYP.BD. ON TWO SIDES, EXTEND TO DECK AND SEAL

3 5/8" METAL STUDS AT 16" O.C. WITH ONE LAYER 5/8" GYP.BD. ON ONE SIDE, WALL TO EXTEND 6" ABOVE CEILING

INTERIOR PARTITION NOTES

AMA

BALAFOETATSRE

GISTERED ARCHIT

EC

T

3196

REGISTRATIONNUMBER

RODNEY STEGER

MEMBER OF THE AMERICAN INSTITUTE OF ARCHITECTS

This document is a copyright protected instrument of service and licnesed for use in the titled project only. This drawing may not be

reproduced in whole or in part without written permission of FUQUA & PARTNERS ARCHITECTS, P.C.

A Professional Corporation

DATE:

ISSUE:

DRAWN:

PROJECT NO:

SHEET

OF

Architecture

Interior Design

Media Visualization

Master Planning

100 Church Street, Suite 700Huntsville, Alabama 35801

PH: (256) 534.3516FX: (256) 533.4605

www.fuquaarchitects.com

CHECKED:

3/9/

2020

7:5

9:38

AM

A1.2

SEC

ON

D F

LOO

R -O

VERA

LL R

ENO

VATI

ON

PLA

N

301

SPAR

KMAN

DRI

VE, H

UN

TSVI

LLE,

AL

3589

9

LF

02-25-2020

FPA #07519

RKS

100 % CDs

125

UAH

BAB

CYB

ER L

AB /

INTE

RIO

R RE

NO

VATI

ON

S

NORTH

1/8" = 1'-0"

SECOND FLOOR - OVERALL RENOVATION PLAN

0' 4' 8' 16' 32'

KEY PLAN

1

2

3

REVISIONS

1 Addendum #1 MARCH 9, 2020

1

1

Page 9: 100 Church Street, Suite 700 Huntsville, Alabama 35801 PH ...

EXIST.CLASSROOM

232C

EXIST. CLASSROOM220

STAIRS219

CEILING MOUNTED MONITORS

217

1906 SF

CYBERSECURITYLAB219

102 SF

LABSUPPORT

217219B

219A

CEILING MOUNTED MONITOR

657 SF

CYBER LOUNGE218

WALL MOUNTED MONITORS

WALL MOUNTED MONITOR

WALL MOUNTED MONITOR

ALIGN WALL WITH EXISTING VERTICAL MULLION

8'-0"

26'-6 1/2" 10'-5" 13'-3"

21'-6" 16'-3"

12'-9

1/2

"

POWER AND DATA FLOOR BOXES(ES)

POWER AND DATAFLOOR BOX

POWER AND DATA FLOOR BOX

DEMOUNTABLE WALL WITH FULL HEIGHT GLASS (TO BE INCLUDED IN FURNITURE PACKAGE)

15'-9

"

POWER AND DATA FLOOR BOX

GLASS WALLHOLD OPENING TO 26'-4 1/4"

A6.0

5

A6.0

1

ROLLER SHADES AT ALL WINDOWS IN LAB - SEE 1/A7.0 FOR EXTENTS

ROLLER SHADES AT ALL WINDOWS IN LAB - SEE 1/A7.0 FOR EXTENTS

7'-7

1/2"

CEILING MOUNTED MONITOR

CEILING MOUNTED MONITOR

CEILING MOUNTED MONITOR

CEILING MOUNTED MONITORS

ROLLER SHADES AT ALL WINDOWS IN LAB - SEE 1/A7.0 FOR EXTENTS

23

NEW WATER FOUNTAIN / BOTTLE FILLER

RELOCATEDFIRE EXTIGUISHER CABINET

A6.0

16

ACCESS CONTROLLED DOOR (BADGE IN ONLY)

ACCESS CONTROLLED DOOR (BADGE IN ONLY)

ACCESS CONTROLLED DOOR (BADGE IN ONLY)

15'-6 1/2" 12'-10"

A6.07

A6.0

8

(ver

if y)

9'-11

"

ROLLER SHADES AT ALL WINDOWS IN LAB - SEE 1/A7.0 FOR EXTENTS

MANUAL ROLLER SHADES AT ALL WINDOWS IN LOUNGE - SEE 1/A7.0 FOR EXTENTS

EXISTING STRUCTURAL COLUMN AND ROOF LEADER

RACK5'-0"

12A6.0

10A6.0

15A6.0

12A6.0

15A6.0

A6.0

9

15'-2"

A1.2a

A

6

A6.0

4

3"

15A6.0

12A6.0

15A6.0

sim.

GENERAL RENOVATION NOTESA. WHERE SCHEDULE, DOOR FRAMES (ON RENOVATION SIDE) TO BE PAINTED PNT-2. ONLY FRAMES TO BE PAINTED. DOORS SHOULD REMAIN

UNPAINTEDB. WITHIN RENOVATED AREAS OR AS INDICATED ON SCHEDULE, ALL EXISTING ROOM SIGNS, PLAQUES, AND PORTRAITS TO BE CAREFULLY REMOVED,

THEN REPLACED ONCE WALLS HAVE BEEN PAINTED. (IF SIGNAGE ALTERNATE IS NOT ACCEPTED)C. WITHIN RENOVATED AREAS, ALL EXISTING ARTWORK TO BE CAREFULLY REMOVED AND TURNED OVER TO THE UNIVERSITY.D. WITHIN RENOVATED AREAS, REMOVE EXISTING WALL COVERING AND REPAIR GYPSUM WALL BOARD WHERE NECESSARY. PREPARE WALL FOR NEW

FINISHESE. WITHIN RENOVATED AREAS, EXISTING METAL REVEALS TO REMAIN AND BE PAINTED PNT-2F. WITHIN RENOVATED AREAS, ALL HARD TILE BASE IS TO REMAIN UNLESS OTHERWISE NOTED.G. WITHIN RENOVATED AREAS, OR AS INDICATED ON SCHEDULE, INTERIOR SIDE OF WINDOW TRIM TO BE PAINTED PNT-2.H. WITHIN RENOVATED AREAS, EXISTING INTERIOR UNPAINTED BRICK ARE TO BE CLEANED AND PAINTED PNT-1.

RENOVATION PLAN LEGEND

EXISTING TO REMAIN

THIS DRAWING IS INTENDED TO SHOW GENERAL LOCATIONS OF INTERIOR WALL TYPES. REFER TO OTHER DRAWINGS FOR SPECIFIC WALL CONSTRUCTION, INCLUDING LOCATION OF APPLIED FINISHES. REFER TO WALL SECTIONS AND DETAILS FOR INFORMATION REGARDING CONSTRUCTION OF EXTERIOR WALLS.

3 5/8" METAL STUDS WITH 3/4" PLYWOOD ON ALL SIDES, EXTEND 6" ABOVE CEILING. SEE DETAIL 9/A6.0 FOR WALL CONSTRUCTION.

3 5/8" METAL STUDS AT 16" O.C. WITH ONE LAYER 5/8" GYP.BD. ON TWO SIDES, EXTEND TO DECK AND SEAL

3 5/8" METAL STUDS AT 16" O.C. WITH ONE LAYER 5/8" GYP.BD. ON ONE SIDE, WALL TO EXTEND 6" ABOVE CEILING

INTERIOR PARTITION NOTES

5/8" GYPSUM WALL BOARD ON METAL STUD FRAMING AS SCHEDULED. CENTER WALL ON STOREFRONT MULLION

COMPRESSED CLOSED CELL FOAM W/ ADHESIVE TO MATCH FRAMING IN WIDTH TO SEAL ALL CAPS

BREAK METAL TRIM TO MATCH STOREFRONT HEM EDGES - BREAK PAST 90 DEGREES FOR TENSION FIT

1 1/2"

INSIDE FACE OF CURTAIN WALL FRAME BELOW

EXISTING CURTAIN WALL MULLION

AMA

BALAFOETATSRE

GISTERED ARCHIT

EC

T

3196

REGISTRATIONNUMBER

RODNEY STEGER

MEMBER OF THE AMERICAN INSTITUTE OF ARCHITECTS

This document is a copyright protected instrument of service and licnesed for use in the titled project only. This drawing may not be

reproduced in whole or in part without written permission of FUQUA & PARTNERS ARCHITECTS, P.C.

A Professional Corporation

DATE:

ISSUE:

DRAWN:

PROJECT NO:

SHEET

OF

Architecture

Interior Design

Media Visualization

Master Planning

100 Church Street, Suite 700Huntsville, Alabama 35801

PH: (256) 534.3516FX: (256) 533.4605

www.fuquaarchitects.com

CHECKED:

3/9/

2020

8:0

0:04

AM

A1.2a

CYB

ERSE

CU

RITY

LAB

-EN

LARG

ED S

ECO

ND

FLO

OR

PLAN

301

SPAR

KMAN

DRI

VE, H

UN

TSVI

LLE,

AL

3589

9

LWF

02-25-2020

FPA #07519

RKS

100 % CDs

126

UAH

BAB

CYB

ER L

AB /

INTE

RIO

R RE

NO

VATI

ON

S

NORTH

1/4" = 1'-0"

SECOND FLOOR - CYBERSECURITY LAB - ENLARGED PLAN

0' 2' 4 8' 16'

KEY PLAN

REVISIONS

1 Addendum #1 MARCH 9, 2020

A1.2a 3" = 1'-0"

A PARTITION INTERSECTING MULLION

1

2

3

1

1

1

1

1

Page 10: 100 Church Street, Suite 700 Huntsville, Alabama 35801 PH ...

65" MONITORS

5'-8

1/2"

4'-11" 4'-2 1/4"

PL-1, PLASTIC LAMINATE COUNTERTOP W/ 4" BACKSPLASH

WALL MOUNTED POWER AND DATA MODULE

INSIDE WALL MOUNT SUPPORT BRACKETS AS NEEDED

FRL-1 WITH PROTECTIVE OUTSIDE CORNER BEADS TO MATCH

RB-1

30"

11A6.0

PNT-4

1-1/2" LAMINATED DOUBLE EASED EDGE

4A6.0

5'-10

"

85" MONITOR

7'-2"

RB-1

PNT-1

EXISTING REVEALS TO BE PAINTED PNT-2

EXISTING WINDOW FRAME / SILL TO BE SANDED AND PAINTED PNT-1

33 7

/8"

3/4"

40"

3/4"

41 5

/8"

PNT-1

SPECIFIED ROLLER SHADE WITH METAL FASCIA PAINTED PNT-2

5'-10

"

85" MONITOR

EXISTING BRICK TO BE PAINTED PNT-1

PNT-4

EXISTING DOOR / TRIM TO BE PAINTED PNT-2

RB-1

6"

GLASS WALLHOLD OPENING TO 26'-4 1/4" 8'-4 1/2"

DONORSIGNAGE

GYP BULKHEAD TO BE EXTENDED TO DECKSEE DETAIL 10/A6.0

RB-1

PNT-1

10A6.0

7'-6"

2'-0"

WALL BY OTHERS

HO

LD O

PENI

NG T

O 9

'-9"

2'-6"

REFER TO ELEVATION FOR COUNTERTOP MATERIAL - SEE PLAN VIEW FOR SHAPE

INSIDE WALL MOUNT SUPPORT BRACKETS AS NEEDED(CENTERLINE BRACKETS -COUNTER SUPPORT - FRONT MOUNTING PLUS)

GROMMET LOCATIONS PER OWNERS REQUEST / QUANTITY OF 4 MIN.

SCHEDULED WALL BASE

5/8" GYP

4"

FRL ON 3/4" PLYWOOD SUBSTRATE

1 1/

2"

1-1/2" LAMINATED DOUBLE EASED EDGE

ACOUSTICAL PANEL CEILING

*SEE REFLECTED CEILING PLAN FOR CEILING HEIGHTS AND DIMENSIONS

EXISTING WOOD SILL AND TRIM TO REMAIN - SAND AND PAINT PER ELEVATION

SPECIFIED ROLLER SHADE WITH METAL FASCIA PAINTED PER ELEVATIONS

ACOUSTICAL PANEL CEILING

CORNER BEAD EA. SIDE, TYP

BULKHEAD - 3-5/8" METAL STUD FRAMING #16" O.C. WITH 5/8" GWB. EXTEND METAL STUDS TO ROOF DECK. PROVIDE DIAGONAL BRACES AT 48" .C. FROM STUDS TO EXISTING STRUCTURE. WHERE ADJACENT CEILING IS APC, EXTEND GWB 6" ABOVE FINISHED CEILING. WHERE THE ADJACENT SPACE IS EXPOSED TO STRUCTURE, EXTEND GWB TO STRUCTURE.

SEE REFLECTED CEILING PLAN FOR CEILING HEIGHTS AND DIMENSIONS

WALL TO EXTEND TO DECK, TYP.

5"

DEMOUNTABLE WALL WITH FULL HEIGHT GLASS (TO BE INCLUDED IN FURNITURE PACKAGE)

BRACING TO DECK REQUIRED

CONTINUOS BLOCKING ABOVE DEMOUNTABLE WALL

METAL CORNER BEAD (TIGHT TO BRICK)

EXISTING BRICK VENEER AFTER DEMO

V.I.F

1-1/2" STUD WITH 5/8" GYP ON ONE SIDE

EXISTING STAIRWELL

6'-9"7'-

11"

SEE DETAILS 9,13,14/A6.0 FOR COLUMN FINISH

CEILING MOUNTED TV

9A6.0

FRL-1 ON 1/2" SUBSTRATE

FRY REGLET MILLWORK CHANNEL WITH RETURN KEYS, INSTALLED HORIZONTALLY ONLY, HORIZONTAL REVEALS TO ALIGN WITH EXISTING REVEALS ON ADJACENT WALLS

4" MILLWORK REVEAL BASE WITH RETURN KEY

HALLWAYS: BLACK FLOOR TILE. SEE FINISH FLOOR PLAN FOR EXTENTS

RB-1

PNT-1

EXISTING WINDOW FRAME / SILLS TO BE PAINTED PNT-2

PNT-1

WC-1 AND FASCIA TO BE CEILING MOUNTED TO UNDERSIDE OF BULKHEAD

V.I.F

.33

7/8

"2

1/2"

V.I.F

.35

3/4

"2

1/2"

V.I.F

.42

3/8

"

PNT-1

CEILING MOUNTED MONITOR

CEILING MOUNTED MONITOR

EXISTING WINDOW FRAME / SILL TO BE SANDED AND PAINTED PNT-1

12A6.0

15A6.0

PNT-1

TYPI

CAL

7'-5"

ACOUSTICAL PANEL CEILING

*SEE REFLECTED CEILING PLAN FOR CEILING HEIGHTS AND DIMENSIONS

SPECIFIED TV MOUNT CEILING PLATE

STEEL PLATE OR BLOCKING TO BE SECURED TO DECK OR STRUCTURE ABOVE FOR ATTACHEMENT OF TV MOUNT

DECORATIVE TILE RING, WHITE

SPECIFIED CEILING TV MOUNT

SPECIFIED ROLLER SHADE WITH METAL FASCIA PAINTED PER ELEVATIONS

EXISTING THIRD FLOOR SLAB

EXISTING EXTERIOR WALL

EXISTING EXTERIOR CURTAIN WALL

(FINAL SIZE TBD IN FIELD)1'-6 1/4"

EXISTING STEEL COLUMN

3 5/8" METAL STUDS

3/4" PLYWOOD

FRL-1 APPLIED TO 1/2" AC PLYWOOD FRY REGLET

MILLWORK CORNER KEY

1/2"

1/4"

3/4"

3 3/4"

*ALSO SEE DETAILS 13 & 14/A6.0 FOR ADDITIONAL INFORMATION

SOME COLUMN WRAPS ARE TO INCLUDE ROOF DRAIN PIPE IN ADDITION TO STRUCTURAL COLUMN

PL-1, PLASTIC LAMINATE COUNTERTOP W/ 4" BACKSPLASH

INSIDE WALL MOUNT SUPPORT BRACKETS AS NEEDED FRL-1 FRL-1 WITH

PROTECTIVE OUTSIDE CORNER BEADS TO MATCH

RB-1

11A6.0

4A6.0

WINDOW BEYOND

PNT-1

93.07°

2'-6"

2'-10

1/4

"

2'-4"

R 0'-8 3

/8"

R 0'-9 1/32"

12'-10 3/4"

7'-1

1/4"

10'-4 3/4"

TECH COUNTER

1'-9"

KNEE WALL TO BE WRAPPED IN SPECIFIED LAMINATE - SEE ELEVATIONS

KNEE WALL TO BE WRAPPED IN SPECIFIED LAMINATE - SEE ELEVATION

INSIDE WALL MOUNT SUPPORT BRACKETS AS NEEDED

6"

FRL-1 ON 1/2" AC PLYWOOD ALL SIDES OF COLUMN

FRY REGLET MILLWORK CHANNEL WITH RETURN KEYS, INSTALLED HORIZONTALLY ONLY, HORIZONTAL REVEALS ON ALL SIDES OF COLUMN ARE TO ALIGN WITH EXISTING REVEALS ON ADJACENT WALLS

4" MILLWORK REVEAL BASE WITH RETURN KEY

PANELS TO BE MOUNTED USING Z-CLIP SYSTEM

MILLWORK CHANNEL "L" ANGLE WITH RETURN KEY - TO BE INSTALLED TIGHT TO THE CEILING

EXISTING STRUCTURAL COLUMN

3-5/8" METAL STUDS ALL SIDES

FRL-1 ON 1/2" AC PLYWOOD ALL SIDES OF COLUMN

3/4" PLYWOOD ALL SIDES

STUDS TO EXTEND 6" ABOVE CEILING

SEE RCP FOR CEILING INFORMATION

AMA

BALAFOETATSRE

GISTERED ARCHIT

EC

T

3196

REGISTRATIONNUMBER

RODNEY STEGER

MEMBER OF THE AMERICAN INSTITUTE OF ARCHITECTS

This document is a copyright protected instrument of service and licnesed for use in the titled project only. This drawing may not be

reproduced in whole or in part without written permission of FUQUA & PARTNERS ARCHITECTS, P.C.

A Professional Corporation

DATE:

ISSUE:

DRAWN:

PROJECT NO:

SHEET

OF

Architecture

Interior Design

Media Visualization

Master Planning

100 Church Street, Suite 700Huntsville, Alabama 35801

PH: (256) 534.3516FX: (256) 533.4605

www.fuquaarchitects.com

CHECKED:

2/26

/202

0 11

:26:

22 A

M

A6.0

INTE

RIO

R EL

EVAT

ION

S &

DETA

ILS

301

SPAR

KMAN

DRI

VE, H

UN

TSVI

LLE,

AL

3589

9

LF

02-25-2020

FPA #07519

RKS

100 % CDs

127

UAH

BAB

CYB

ER L

AB /

INTE

RIO

R RE

NO

VATI

ON

S

A6.0 3/8" = 1'-0"

5 INTERIOR ELEVATIONCOUNTERTOP ELEVATION

A6.0 3/8" = 1'-0"

1 INTERIOR ELEVATIONMONITOR ELEVATION A A6.0 3/8" = 1'-0"

2 INTERIOR ELEVATIONMONITOR ELEVATION B A6.0 3/8" = 1'-0"

3 INTERIOR ELEVATIONDEMOUNTABLE WALL ELEVATION

A6.0 1 1/2" = 1'-0"

11 DETAILCOUNTERTOP DETAIL

A6.0 1 1/2" = 1'-0"

15 DETAILROLLER SHADE - CYBER LAB

A6.0 1 1/2" = 1'-0"

10 CEILING DETAILBULKHEAD AT DEMOUNTABLE WALL

A6.0 1 1/2" = 1'-0"

16 DETAIL

A6.0 3/8" = 1'-0"

8 INTERIOR ELEVATION50" MONITOR @ COLUMN - CYBER LAB

A6.0 3/4" = 1'-0"

13 DETAILCOLUMNS - 3D VIEW

A6.0 3/8" = 1'-0"

7 INTERIOR ELEVATIONEXTERIOR WALL

A6.0 1 1/2" = 1'-0"

12 DETAILCEILING TV MOUNT - CYBER LAB

A6.0 1 1/2" = 1'-0"

9 DETAILCOLUMN WRAP DETAIL A

REVISIONS

A6.0 3/8" = 1'-0"

6 INTERIOR ELEVATIONA6.0 3/8" = 1'-0"

4 TECH COUNTER

A6.0 1" = 1'-0"

14 DETAILCOLUMN WRAP DETAIL B

Page 11: 100 Church Street, Suite 700 Huntsville, Alabama 35801 PH ...

FINISH LEGENDFLOORKEY

CPT-1

TYPE

CARPET TILE

DETAIL DESCRIPTION

PNT-1 PAINT

PNT-4 PAINT

MANUFACTURER: Sherwin WilliamsCOLOR: SW 7015 Repose GrayLOCATIONS: Field Paint

PNT-3 PAINT

MANUFACTURER: Sherwin WilliamsCOLOR: SW 6797 Jay BlueLOCATION: Accent Wall

MANUFACTURER: Sherwin WilliamsCOLOR: SW 7007 Ceiling Bright WhiteFINISH: FlatLOCATION: Gyp. Bulkheads unless specified otherwise

BASE

CPT-2

MANUFACTURER: InterfaceSTYLE NAME: BitrateCOLOR: 106305 Dark BlueSIZE: 25cm x 1mINSTALLATION: See Finish floor Plan, 1/A7.0

CARPET TILE

KEY TYPE DETAIL DESCRIPTION

MANUFACTURER: InterfaceSTYLE NAME: UploadCOLOR: 106297 Light BlueSIZE: 25cm x 1mINSTALLATION: See Finish floor Plan, 1/A7.0

CPT-3

HTB-1 HARD TILE MANUFACTURER: CrossvilleSTYLE NAME: Cross ColorsCOLOR: Onyx A880 Cove base standard + Cove base corner - rightSIZE: 6" x 8"

HTF-1 HARD TILE PRODUCT EQUAL TO:MANUFACTURER: Crossville STYLE NAME: Cross ColorsCOLOR: Onyx A880 - Cross-Slate (CS)SIZE: 12x12INSTALLATION: At all Columns noted to recieve demo and at transition to carpet in Cyber Lounge

RB-1 RUBBER BASE PRODUCT EQUAL TO:MANUFACTURER: Johnsonite PRODUCT: Millwork - Reveal MW-XX-F6COLOR: 20 CharcoalSIZE: 6"

MILLWORKKEY TYPE DETAIL DESCRIPTION

PL-1 PLASTIC LAMINATE MANUFACTURER: FormicaCOLOR: Storm HexLOCATION: Tech counter - See Interion Elevations

TRIM & TRANSITIONSNUMBER TYPE DETAIL DESCRIPTION

TR-1 TRANSITION SCHLUTER SYSTEMS, RENO-TK PROFILE IN BRUSHED STAINLESS (TYP. BETWEEN CARPET & HARD TILE)

TR-2 TRANSITION JOHNSONITE SLT-XX-L, IN COLOR: SUBMIT FULL RANGE (TYP WHERE CARPET MEETS FINISH CONCRETE)

THESE TRANSITIONS ARE TYPICAL & TO BE INSTALLED AT ALL LOCATIONS WHERE THESE CONDITIONS OCCUR. SOME ARE SPECIFICALLY INDICATED FOR CLARITY.

WALK-OFF CARPET TILE

PRODUCT EQUAL TO:MANUFACTURER: Tandus CentivaSTYLE NAME: Assertive Stria 04839COLOR: ChromiumSIZE: 24" x 24"INSTALLATION: AshlarLOCATION: Entry and Stairs

SC-1 SEALED CONCRETE PRODUCT EQUAL TO:MANUFACTURER: H&CSTYLE NAME: Colortop SealerCOLOR: SW 7066 Gray MattersFINISH: 5% Grit Extra FineINSTALLATION: Per manufactures instructions

PNT-2 PAINT MANUFACTURER: Sherwin WilliamsCOLOR: SW 7068 Grizzle GrayLOCATION: Corridor Trim, Door & Window Frames

CPT-4 ALTERNATE BROADLOOMCARPET

MANUFACTURER: ManningtonSTYLE NAME: Glitch Art - Cross TalkCOLOR: Plasma Effect (custom) CUSTOM NUMBER: M41796-002A-10LOCATION: Case rooms with auditorium style seatingRep Contact: Nels Howalt / 1-615-618-3303

WALLKEY TYPE DETAIL DESCRIPTION

MISC.NUMBER TYPE DETAIL DESCRIPTION

PL-2 PLASTIC LAMINATE MANUFACTURER: WilsonartCOLOR: Fawn Cypress 8208K-16LOCATION: Tech counter - See Interion Elevations

FRL-1 FIBER REINFORCED LAMINATE

MANUFACTURER: PanolamPRODUCT: FRL Wall Protection PanelsCOLOR: HP565SD Storm Gray - True FRL INSTALLATION: To be applied to AC plywood with recommended adhesive- See Detail 9/A6.0 LOCATION: At Columns to remain - See Detail 9/A6.0CONTACT REP FOR SPECIFIC COLORATION: Beth Heins - C:404-548-7720 [email protected]

WC-1 WINDOW COVERING

(MANUAL - BASE BID)

MANUFACTURER: LutronSTYLE: Manual - Single Shade - with FaciaMOUNTING: Outside Ceiling mountedFABRIC: T-Screen w/ Kool Black(White side to face Exterior)COLOR: White / CharcoalMODEL: TS0235K-3SAMPLE: WSF-TS0235K-3

WDF & WD2L

STAINED WOODDOORS

MANUFACTURER: ASSA ABLOYSTYLE: Graham Flush Wood DoorsSPECIES: Plain Sliced White Birch STAIN: 550-1014

FO FLOOR OUTLET SEE ELECTRICAL DRAWINGS FOR SPECIFICATION. LOCATIONS PER ARCHITECTURAL DRAWINGS.

WC-2 WINDOW COVERING

(POWEREDALTERNATE)

MANUFACTURER: LutronSTYLE: Roller 64 - Single Shade - with FaciaMOUNTING: Outside Ceiling mountedFABRIC: T-Screen w/ Kool Black(White side to face Exterior)COLOR: White / CharcoalMODEL: TS0235K-3SAMPLE: WSF-TS0235K-3

(Alternate in Cybersecurity Lab 219 ONLY) CYBERSECURITY LAB

219

CYBER LOUNGE218

LAB SUPPORT217

EXIST. CORRIDOR211

EXIST. CLASSROOM220

EXIST. CLASSROOM232C

STAIRS219

FO

FO FO

FOFO

EXISTING FLOOR / BASE TILE TO REMAIN

ALIGN TRANSITION WITH CORNERLINE OF EXISTING TILE

FLOORING TO BE REMOVED

FO FO FO

PNT-1,2,4RB-1

CPT-1,CPT-2

CPT-1

CPT-1

CPT-1

CPT-2

CPT-2

PNT-1,4RB-1

CPT-1,CPT-2

PNT-1RB-1SC-1

PNT-4

PNT-

4

PNT-

4

PNT-4

PNT-2WINDOW FRAME & SILLS

PNT-2WINDOW FRAME & SILLS

PNT-2WINDOW FRAME & SILLS

HTF-1

PNT-4A6.0

4

PNT-

4

PNT-4

WC-

1

WC-

1: B

ASE

BID

WC-

2: A

LTER

NATE

WC-1: BASE BIDWC-2: ALTERNATE

WC-1: BASE BID

WC-2: ALTERNATE

WC-

1: BA

SE B

IDW

C-2:

ALTE

RNAT

E

A) FLOORING NOTES:1. ARRANGE A PRE-CONSTRUCTION MEETING TO CONFIRM CARPET BORDERS AND TILE PATTERNS.2. ALL PORCELAIN TILE GROUT JOINTS SHOULD BE 1/8", UNLESS OTHERWISE NOTED.3. FINISHED GROUT WILL NOT BE ACCEPTED UNTIL A SAMPLE MOCKUP IS SUBMITTED FOR APPROVAL.4. FLOORING TRANSITIONS AT DOORWAYS SHOULD ALWAYS BE ALIGNED SO THAT THEY ARE NOT VISIBLE WHEN DOORS ARE SHUT.5. TILE AND CARPET HATCHING ARE SHOWN IN LEGEND TO THE EXTENT USED IN PATTERNS AND BORDERS. UNHATCHED ROOMS OR SPACES ARE EITHER

SINGLE MATERIALS OR ARE IN THE REMAINING FIELD MATERIAL NOT EXPLICITLY HATCHED FOR CLARITY.6. ALL EXPOSED CONCRETE FLOORS SHALL BE PROPERLY REPAIRED AND SEALED W/ H&C HIGH PERFORMANCE INDUSTRIAL CLEAR COAT, W/ SHARK GRIP

ADDITIVE (OR APP. EQ.), & INSTALLED PER MANUFACTURER'S INSTRUCTIONS.7. REFER TO ALL A7.0 SERIES SHEETS FOR EXACT FLOORING TRANSITION LOCATIONS & PATTERN INFO.8. WHERE PORCELAIN WALL BASE IS USED, GROUT SHOULD BE OMITTED ALONG THE TOP EDGE, IN LIEU OF CAULK, TO ENSURE NEAT INSTALLATION OF

WALL FINISHES.9. ALL CARPET TILE SHOULD BE CENTERED IN ROOM, NO LESS THAN 1/2 OF TILE SHOULD ALIGN ALL EDGES OF THE ROOM.

B) TRIM/MILLWORK/CASEWORK/RUBBER TRIM NOTES:1. ALL DOORS SCHEDULED TO BE PAINTED, WOOD & METAL TRIM ARE TO BE SEMI-GLOSS FINISH, UNLESS OTHERWISE NOTED.2. REFER TO INTERIOR ELEVATIONS & DOOR SCHEDULE FOR INTERIOR DOOR FINISH INFO.3. SEE FINISH LEGEND AND INTERIOR ELEVATIONS FOR CABINETRY FINISHES.4. CABINET & CASEWORK DOORS/DRAWERS ARE FULL-OVERLAY STYLE, UNLESS OTHERWISE NOTED.5. ANY OPEN/EXPOSED SHELVING IN CABINETRY IS TO BE FINISHED TO MATCH ADJACENT DOOR/DRAWER FINISHES, INSTEAD OF WHITE MELAMINE. WHITE

MELAMINE SHOULD NOT BE VISIBLE WHEN DOORS AND DRAWERS ARE CLOSED.6. ALL UPPER CABINETS TO HAVE TWO ADJUSTABLE SHELVES PER UNIT, ALL LOWER CABINETS TO HAVE ONE ADJUSTABLE SHELF PER UNIT, UNLESS

OTHERWISE NOTED.7. ALL EDGES OF DOORS AND DRAWERS OF CASEWORK ARE TO HAVE MINIMUM 3MM PVC EDGEBANDING APPLIED. SUBMIT FULL RANGE OF CANPLAST (OR

APPROVED EQUAL) COLORS FOR APPROVAL. (DOES NOT APPLY TO MILLWORK.)8. ALL HINGES, UNLESS OTHERWISE NOTED, ARE TO BE CONCEALED.9. COUNTERTOPS ARE TO HAVE MINIMUM 3/4" OVERHANG, ON ALL SIDES, TYP.10. RAKKS BRACKETS: SPACING, QUANTITY, AND INSTALLATION METHODS TO BE COORDINATED BY GENERAL CONTRACTOR, BASED ON MANUFACTURER'S

INSTRUCTIONS.

C) WALL FINISH NOTES:1. ALL PAINTED GYP WALLS ARE TO BE EGGSHELL FINISH, UNLESS OTHERWISE NOTED.2. ALL TILED WALLS AND WET-WALLS ARE TO BE MOISTURE-RESISTANT GYP. BOARD UNLESS OTHERWISE NOTED.3. PROVIDE 8.5"X11" RETAINER FOR ALL PAINTS SPECIFIED BEFORE APPLYING PAINT SAMPLES ON JOB SITE. BENCHMARK SAMPLES WILL BE REVIEWED ON

SITE IN CONDITIONS ACCORDING TO SPECIFICATIONS PRIOR TO FINISH PAINTING.4. WHERE CEILING IS EXPOSED & PAINTED, CONTRACTOR IS TO STRIKE LINE AT POINT OF LOWEST STRUCTURAL, ELECTRICAL, HVAC, OR SPRINKLER

COMPONENT TO TRANSITION FROM WALL TO CEILING PAINT.5. ALL VINYL WALLCOVERING IS TO BE MICRO-PERFORATED.

D) MISC./GENERAL NOTES:1. ALL PAINTED GYP CEILINGS & EXPOSED CEILINGS ARE TO BE PNT-XXX FLAT FINISH, UNLESS OTHERWISE NOTED.2. PROVIDE DELIVERY SCHEDULE OF ALL FINISH MATERIALS 10 DAYS FOLLOWING BID DATE.3. PROVIDE MEMO SAMPLES OF ALL SPECIFIED INTERIOR FINISHES ACCORDING TO SPECS. 4. ALL EXTERIOR FINISHES ARE SPECIFIED ELSEWHERE. VERIFY ALL EXTERIOR FINISHES WITH ARCHITECT BEFORE PROCEEDING.5. GWB LOCATED ADJACENT TO WALLS AT COFFER DETAILS SHALL BE PAINTED TO MATCH WALL COLORS UNLESS OTHERWISE NOTED.6. CONTRACTOR TO VERIFY AND COORDINATE WITH ARCHITECT ALL FINISHES INCLUDING WALLS, FLOORS, AND CEILINGS.

SCHEDULED CARPET

TR-1, EQUAL TO SCHLUTER SYSTEMS, RENO-TK PROFILE IN BRUSHED STAINLESS STEEL

CONCRETE SLAB

SCHEDULED HARD TILE FLOOR

SCHEDULED CARPET

TR-2, EQUAL TO TARKETT1/8" MATERIAL TO SUBFLOOR TRANSITION STRIP OR EQUAL; FINISH: SUBMITFULL RANGE TO BE SELECTEDBY DESIGNER.

CONCRETE SLAB WITH SCHEDULED FINISH

FINISH SCHEDULE

Room No Room Name Floor Finish Wall Finish Base Finish Comments

115 EXIST. CORRIDOR HTF-1 PNT-1,2 EXISTING TO REMAIN Flooring to be replaced around column only125 EXISTING CORRIDOR HTF-1 PNT-1,2 EXISTING TO REMAIN Flooring to be replaced around column only146 EXISTING CORRIDOR HTF-1 PNT-1,2 EXISTING TO REMAIN Flooring to be replaced around column only146A AIRLOCK CPT-3 PNT-2 RB-1207 EXISTING OFFICE HTF-1 PNT-1,2 EXISTING TO REMAIN Flooring to be replaced around column only211 EXIST. CORRIDOR HTF-1 PNT-1,2 EXISTING TO REMAIN Flooring to be replaced around column only217 LAB SUPPORT SC-1 PNT-1 RB-1218 CYBER LOUNGE CPT-1,CPT-2 PNT-1,2,4 RB-1219 CYBERSECURITY LAB CPT-1,CPT-2 PNT-1,4 RB-1231 EXISTING CORRIDOR HTF-1 PNT-1,2 EXISTING TO REMAIN Flooring to be replaced around column only233 AIRLOCK CPT-3 PNT-1243 CLASSROOM NONE PNT-2 WINDOW SILLS NONE INTERIOR SIDE OF DOOR FRAME AND

WINDOW FRAMES/ SILLS TO RECEIVE PNT-2

AMA

BALAFOETATSRE

GISTERED ARCHIT

EC

T

3196

REGISTRATIONNUMBER

RODNEY STEGER

MEMBER OF THE AMERICAN INSTITUTE OF ARCHITECTS

This document is a copyright protected instrument of service and licnesed for use in the titled project only. This drawing may not be

reproduced in whole or in part without written permission of FUQUA & PARTNERS ARCHITECTS, P.C.

A Professional Corporation

DATE:

ISSUE:

DRAWN:

PROJECT NO:

SHEET

OF

Architecture

Interior Design

Media Visualization

Master Planning

100 Church Street, Suite 700Huntsville, Alabama 35801

PH: (256) 534.3516FX: (256) 533.4605

www.fuquaarchitects.com

CHECKED:

3/9/

2020

8:0

0:11

AM

A7.0

PART

IAL

SEC

ON

D F

LOO

R FI

NIS

H P

LAN

, IN

TERI

OR

FIN

ISH

LEG

END

AN

D S

CH

EDU

LE

301

SPAR

KMAN

DRI

VE, H

UN

TSVI

LLE,

AL

3589

9

LF

02-25-2020

FPA #07519

RKS

100 % CDs

128

UAH

BAB

CYB

ER L

AB /

INTE

RIO

R RE

NO

VATI

ON

S

A7.0 1/4" = 1'-0"

1 PARTIAL FINISH PLAN - SECOND FLOOR

GENERAL FINISH NOTES

0' 2' 4 8' 16'

KEY PLAN

A7.0 3" = 1'-0"

2 DETAILCARPET TO HARD TILE

FINISH SCHEDULE - ALTERNATE

Room No Room NameFloorFinish Wall Finish Base Finish Comments

116 EXISTING TEAM CPT-1 PNT-1 OVER EXISTING VINYL WALLCOVERING PNT-2 INTERIOR SIDE OF DOOR FRAME AND WINDOW FRAMES/ SILLS TO RECEIVE PNT-2117 EXISTING TEAM CPT-1 PNT-1 OVER EXISTING VINYL WALLCOVERING PNT-2 INTERIOR SIDE OF DOOR FRAME AND WINDOW FRAMES/ SILLS TO RECEIVE PNT-2119 EXISTING TEAM CPT-1 PNT-1 OVER EXISTING VINYL WALLCOVERING PNT-2 INTERIOR SIDE OF DOOR FRAME AND WINDOW FRAMES/ SILLS TO RECEIVE PNT-2149 CONFERENCE CPT-1 PNT-1 OVER EXISTING VINYL WALLCOVERING PNT-2 INTERIOR SIDE OF DOOR FRAME AND WINDOW FRAMES/ SILLS TO RECEIVE PNT-2150 EXISTING STUDY RESOURCE CPT-1 PNT-1 OVER EXISTING VINYL WALLCOVERING PNT-2 INTERIOR SIDE OF DOOR FRAME AND WINDOW FRAMES/ SILLS TO RECEIVE PNT-2205 EXIST. CLASSROOM CPT-1 MATCH EXSTING; TOUCH UP AS NEEDED MATCH EXISTING; TOUCH UP AS NEEDED206 COMPUTER CLASSROOM CPT-1 MATCH EXSTING; TOUCH UP AS NEEDED MATCH EXISTING; TOUCH UP AS NEEDED209 EXIST. CLASSROOM CPT-1 PNT-1 OVER EXISTING VINYL WALLCOVERING PNT-2 INTERIOR SIDE OF DOOR FRAME AND WINDOW FRAMES/ SILLS TO RECEIVE PNT-2220 EXIST. CLASSROOM CPT-1 PNT-1 OVER EXISTING VINYL WALLCOVERING PNT-2 INTERIOR SIDE OF DOOR FRAME AND WINDOW FRAMES/ SILLS TO RECEIVE PNT-2222 EXIST. CLASSROOM CPT-1 PNT-1 OVER EXISTING VINYL WALLCOVERING PNT-2 INTERIOR SIDE OF DOOR FRAME AND WINDOW FRAMES/ SILLS TO RECEIVE PNT-2224 EXIST. CLASSROOM CPT-1 PNT-1 OVER EXISTING VINYL WALLCOVERING PNT-2 INTERIOR SIDE OF DOOR FRAME AND WINDOW FRAMES/ SILLS TO RECEIVE PNT-2232C EXIST. CLASSROOM CPT-1 PNT-1 OVER EXISTING VINYL WALLCOVERING PNT-2 INTERIOR SIDE OF DOOR FRAME AND WINDOW FRAMES/ SILLS TO RECEIVE PNT-2243 CLASSROOM NONE PNT-2 WINDOW SILLS NONE INTERIOR SIDE OF DOOR FRAME AND WINDOW FRAMES/ SILLS TO RECEIVE PNT-2

REVISIONS

1 Addendum #1 MARCH 9, 2020

A7.0 3" = 1'-0"

3 DETAILCARPET TO SEALED CONCRETE

1

1

1

1

1

1

Page 12: 100 Church Street, Suite 700 Huntsville, Alabama 35801 PH ...

C C

B B

A A

8

8

9

9

7

7

EXIST.CLASSROOM

232CEXIST. CLASSROOM

220

STAIRS219

CEILING MOUNTED MONITORS

217

1906 SF

CYBERSECURITYLAB219

LABSUPPORT

102 SF

LABSUPPORT

217

219B

219A

MONITOR

60 SEATS

OPEN SHELF STORAGE

657 SF

CYBER LOUNGE218

MONITORS

8'-0"

10'-5" 13'-3"

DEMOUNTABLE WALL WITH FULL HEIGHT GLASS AND DIGITAL WINDOW FILM (TO BE INCLUDED IN FURNITURE PACKAGE)

A6.0

5

CEILING MOUNTED MONITOR

CEILING MOUNTED MONITOR

CEILING MOUNTED MONITOR

CEILING MOUNTED MONITOR

CEILING MOUNTED MONITOR

FLOOR BOX(ES)

FLOOR BOX FLOOR BOX

FLOOR BOX(ES)

FLOOR BOX

WALL MOUNTED MONITOR

WALL MOUNTED MONITOR

FLOOR BOX

OPEN SHELF STORAGE

A6.07

A6.0

8

MONITORSMONITORS

MONITORSMONITORS

MONITOR

MONITOR

FURNITURE SHOWN TO BE INCLUDED IN FURNITURE PACKAGE

6

A6.0

4

R R

Not For

s

n

t ur

Co

P

tc

in

Y

o

IE

IL M AN

MEMBER OF THE AMERICAN INSTITUTE OF ARCHITECTS

This document is a copyright protected instrument of service and licnesed for use in the titled project only. This drawing may not be

reproduced in whole or in part without written permission of FUQUA & PARTNERS ARCHITECTS, P.C.

A Professional Corporation

DATE:

ISSUE:

DRAWN:

PROJECT NO:

SHEET

OF

Architecture

Interior Design

Media Visualization

Master Planning

100 Church Street, Suite 700Huntsville, Alabama 35801

PH: (256) 534.3516FX: (256) 533.4605

www.fuquaarchitects.com

CHECKED:

2/26

/202

0 10

:16:

55 A

M

A7.1

CYB

ERSE

CU

RITY

LAB

-SE

CO

ND

FLO

OR

FURN

ITU

RE P

LAN

UAH

BAB

CYB

ER L

AB /

INTE

RIO

R RE

NO

VATI

ON

S30

1 SP

ARKM

AN D

RIVE

, HU

NTS

VILL

E, A

L 35

899

LWF

02-25-2020

FPA #07519

RS

100 % CDs

129

NORTH

1/4" = 1'-0"

CYBERSECURITY LAB - FURNITURE PLAN

0' 2' 4 8' 16'

KEY PLAN

REVISIONS

Page 13: 100 Church Street, Suite 700 Huntsville, Alabama 35801 PH ...

DOOR & FRAME GENERAL NOTES

1. AT DOORS AND OPENINGS IDENTIFIED ON THE FLOOR PLAN WITH AN "EX", THE EXISTING DOOR, FRAME, AND HARDWARE ARE TO REMAIN. EXISTING FRAME IS TO BE PAINTED. ANY EXISTING LITE FRAMES ARE TO BE PAINTED.

2. ALL STEEL DOORS AND ALL FRAMES SHALL COMPLY WITH STEEL DOOR INSTITUTE SDI 100/ANSI A250.8 "RECOMMENDED SPECIFICATIONS FOR STANDARD STEEL DOORS AND FRAMES" LEVEL 2 HEAVY DUTY FOR INTERIOR APPLICATIONS AND LEVEL 3 EXTRA HEAVY DUTY FOR EXTERIOR APPLICATIONS.

3. DOOR LOUVERS SHALL COMPLY WITH STEEL DOOR INSTITUTE SDI 111C "RECOMMENDED LOUVER DETAILED FOR STANDARD STEEL DOORS".

4. DOOR LOUVERS SHALL BE INSERT LOUVERS UNLESS NOTED OTHERWISE AND SHALL BE INVERTED "V" BLADES. LOUVER FRAMES SHALL BE MINIMUM 20 GAUGE STEEL AND LOUVER BLADES SHALL BE MINIMUM 24 GAUGE. LOUVERS SHALL PROVIDE A MINIMUM 50% FREE AREA IN A GIVEN SIZE LOUVER.

5. ALL DOORS SHALL BE 1-3/4" THICK WITH A STANDARD 3/4" UNDERCUT.6. VISION GLASS IN ALL DOORS, VIEW WINDOWS AND SIDE LITES SHALL BE MIN 1/4"

THICK TEMPERED GLASS UNLESS NOTED OTHERWISE.7. ALL STEEL DOORS SHALL HAVE NON-BEVELED HINGE EDGE REINFORCED WITH A

CONTINUOUS OR SEGMENTED 16 GAUGE STEEL CHANNEL PROJECTION WELDED AT A MAXIMUM 5" ON CENTER.

8. ALL STEEL DOORS SHALL HAVE OVERLAPPING EDGE SEAMS, FLUSH 16 GAUGE TOP CHANNEL AND INVERTED 16 GAUGE BOTTOM CHANNEL.

9. STEEL DOOR CORES FOR NON-RATED APPLICATIONS SHALL BE MANUFACTURERS STANDARD POLYSTYRENE REINFORCED BY LAMINATING FACE SKINS TO A FOAM CORE SLAB WITH MINIMUM DENSITY OF 1 POUND PER CUBIC FOOT.

10. STEEL DOOR FACE SKINS SHALL BE MINIMUM 18 GAUGE FOR DOOR WIDTHS UP TO 36-INCHES. 6 AND 4 PANEL (ELEVATIONS E4 AND E6) DOORS AND DOOR WIDTHS GREATER THAN 36-INCHES SHALL BE MINIMUM 16 GAUGE.

11. ALL FIRE RATED DOORS AND FRAMES SHALL COMPLY WITH NFPA 80 AND/OR THE AUTHORITY HAVING JURISDICTION.

12. ALL INTERIOR DOOR FRAME PROFILES SHALL BE MINIMUM 16 GAUGE, STANDARD DOUBLE RABBET PROFILE, MULTI-USE WITH DIE-MITERED CORNER CONSTRUCTION, ADJUSTABLE BASE ANCHORS AND FACTORY APPLIED BAKED-ON RUST INHIBITING PRIMER (ANSI A250.10-1998).

DOOR, FRAME and CONFIGURATION LEGENDAL ALUMINUM STOREFRONT

DOOR ALUM ALUMINUMCS CASED OPENINGF FLUSH DOORFG FULL GLASS DOORGP GLASS PARTITIONHM HOLLOW METALHO HOLD OPENINSUL INSULATEDMTL METAL/STEEL

DOOR & FRAME KEY NOTES

A. EXISTING DOOR AND FRAME: PAINT EXISTING HM FRAME ON RENOVATION SIDE(S) OF OPENING. EXISTING DOOR, HARDWARE AND FINISH TO REMAIN. ENSURE HARDWARE IS IN GOOD OPERATIONAL CONDITION, AND REPAIR IF NECESSARY.

B. IF CLASSROOM ALTERNATE APPROVED AND IS TO PROCEED; EXISTING DOOR AND FRAME: PAINT EXISTING HM FRAME ON BOTH SIDE(S) OF OPENING. EXISTING DOOR, HARDWARE AND FINISH TO REMAIN. ENSURE HARDWARE IS IN GOOD OPERATIONAL CONDITION, AND REPAIR IF NECESSARY.

DOOR SIGNAGE NOTES

GENERAL SIGNAGE NOTES:• GC TO COORDINATE ALL SIGNAGE REQUIRED BY APPLICABLE BUILDING CODES

PRIOR TO FINAL INSPECTIONS.• PROVIDE SIGNS BY INPRO OR PRE- APPROVED EQUAL.• TACTILE CHARACTERS SHALL BE RAISED THE REQUIRED 1/32" FROM THE SIGN

FACE. SEE DOOR SCHEDULES FOR OTHER SPECIFIC LOCATIONS TO RECEIVE TEXT.• LETTERING AND BRAILLE SHALL CONFORM TO ADA/ANSI REQUIREMENTS WITH

RESPECT TO, BUT NOT LIMITED TO TYPE FACES, PROPORTION, HEIGHT, SPACING, ANY OTHER CONFLICTS (SUCH AS FIT OF REQUESTED LETTERING WITHIN SIGN LIMITS OR ANY OTHER PROVISION.)

• ALL SIGNS ARE TO BE SECURED TO WALL ON LATCH SIDE OF DOOR WITH SCREWS OR TAMPER-PROOF FASTENERS. MOUNT CENTER OF SIGN PER ADA GUIDELINES.

• SUBMIT SIGNAGE MESSAGE, FINISHES AND GRAPHICS TO ARCHITECT FOR APPROVAL, CLIENT TO APPROVE PRIOR TO FABRICATION

PREFIN PREFINISHEDSF STOREFRONTSS STAINLESS STEELWDF WOOD FLUSHWD2L WOOD TWO LITESG SINGLEAA PAIR, BOTH ACTIVEAI PAIR, ACTIVE, INACTIVEDE DOUBLE EGRESSSD SINGLE, DOUBLE ACTING

WDF

SCHE

DULE

D HE

IGHT

WIDTHSCHEDULED

BOTT

OF

GLA S

S12

" M

IN T

O

TO GLASS6" MIN

TO G

LASS

6" M

IN

WIDTHSCHEDULED

SCHE

DULE

D HE

IGHT

WD2L

3'-4"

6" M

IN 1/4" CLEAR TEMP. GLASS

METAL LITE FRAMEPAINTED PNT-2

STAIN FINISH: ASSA ABLOY, GRAHAM: PLAIN SLICED WHITE BIRCH - FINISH: 550-1014

1/4" CLEAR TEMP. GLASS F1

SCHE

DULE

D HE

IGHT

2"

2"WIDTH

SCHEDULED 2"

FRAMEPAINTED PNT-2

1'

2'

3'

4'

5'

6'

7'

48" MIN.(LOWEST TACTILE CHARACTERBASELINE NOT PERMITTEDBELOW BASELINE ZONE)

(HIGHEST TACTILE CHARACTER BASELINE NOTPERMITTED ABOVE BASELINEZONE) 60" MAX

TACTILE CHARACTERBASELINE ZONE

1'-6"

18"x18" CLEARFLOOR AREACENTERED ONTACTILE SIGN

TACTILE SIGNS ATSINGLE DOORS

0'-9"

POSITION SIGN ON LATCHSIDE OF DOOR ORNEAREST ADJACENT WALL,AT 9 INCH MINIMUMDISTANCE FROM THE CENTER OF THE RAISEDCHARACTERS ON THE SIGN

LATCH SIDE OF THE DOOR

TACTILE SIGNS ATDOUBLE DOORS

0'-9"

INACTIVE DOOR LEAF ACTIVE DOOR LEAF

0'-9"

1'-6"

18"x18" CLEARFLOOR AREACENTERED ONTACTILE SIGN

POSITION SIGN ON THEINACTIVE DOOR LEAF. IFTWO ACTIVE DOOR LEAFS, SIGN TO BE INSTALLED TORIGHT OF RIGHT HAND DOOR. IF SPACE IS NOT AVAILABLE, THEN INSTALLON NEAREST ADJACENTWALL.

45°

MINIMUM 18"x18" CLEARFLOOR AREA, CENTERED ON TACTILE CHARACTERS OF SIGN

MINIMUM 18"x18" CLEARFLOOR AREA, CENTERED ON TACTILE CHARACTERS OF SIGN

SIGNS CONTAINING TACTILE CHARACTERSSHALL BE LOCATED SO THAT A CLEAR FLOOR SPACE OF 18"x18" MINIMUM, CENTERED ON THE TACTILE CHARACTERS, IS PROVIDED BEYOND THE ARC OF THE DOOR SWING BETWEEN CLOSE AND 45DEGREES OPEN

45°

6" X 9"TYPE 1

6" X 9"TYPE 2

6" X 8"TYPE 3

5" IN

CH

1 1/

2" IN

CH

8" X 8"TYPE 5

CLASSROOM

12" X 18"TYPE 6

(PROVIDE 1 AT EACH LANDINGWITHIN STAIR)

INTERIOR SIGNAGE:

*BASIS OF DESIGN IS: INPRO SIGNAGE - ZURICH COLLECTION 8-1/2"X11" LANDSCAPE INSERT. COORDINATE FINISHES, FINAL DIMENSIONS, GRAPHICS AND WORDING WITH DESIGNER.

1. SIGN MATERIAL SHALL BE APPROX. 1/8" THICK W/ CONTRASTING CORE COLOR2. TACTILE CHARACTERS SHALLS BE RAISED THE REQUIRED 1/32" FROM THE SIGN FACE. SEE DOOR SCHEDULES FOR OTHER SPECIFIC LOCATIONS TO RECEIVE TEXT3. SECURE SIGNS TO WALL ON LATCH SIDE OF DOOR W/ SCREWS OR TAMPER-PROOF FASTENERS. MOUNT CENTER OF SIGN TO 60" A.F.F.5. COLOR:• INSET BOARDER: SUBMIT FULL RANGE OF COLORS/FINISHES

FOR DESIGNERS REVIEW AND SELECTION• BACKPLATE: SUBMIT FULL RANGE OF COLORS/FINISHES FOR

DESIGNERS REVIEW AND SELECTION• TEXT: SUBMIT FULL RANGE OF COLORS/FINISHES FOR

DESIGNERS REVIEW AND SELECTION6. STANDARD OF DESIGN IS CURRENTLY INSTALLED IN THE UAH I2C AND SSB. CONTACT DESIGNER FOR MORE INFORMATION.

SIGNAGE LEGEND

8" X 8"TYPE 4OFFICE

8" X 5"TYPE 7

JANITOR106

GRADE 2 BRAILLE

INTERIOR SIGNAGE:

*BASIS OF DESIGN IS: INPRO SIGNAGE - ZURICH COLLECTION 8-1/2"X11" LANDSCAPE INSERT. COORDINATE FINISHES, FINAL DIMENSIONS, GRAPHICS AND WORDING WITH DESIGNER.

1. SIGN MATERIAL SHALL BE APPROX. 1/8" THICK W/ CONTRASTING CORE COLOR2. TACTILE CHARACTERS SHALLS BE RAISED THE REQUIRED 1/32" FROM THE SIGN FACE. SEE DOOR SCHEDULES FOR OTHER SPECIFIC LOCATIONS TO RECEIVE TEXT3. SECURE SIGNS TO WALL ON LATCH SIDE OF DOOR W/ SCREWS OR TAMPER-PROOF FASTENERS. MOUNT CENTER OF SIGN TO 60" A.F.F.5. COLOR:• INSET BOARDER: SUBMIT FULL RANGE OF COLORS/FINISHES

FOR DESIGNERS REVIEW AND SELECTION• BACKPLATE: SUBMIT FULL RANGE OF COLORS/FINISHES FOR

DESIGNERS REVIEW AND SELECTION• TEXT: SUBMIT FULL RANGE OF COLORS/FINISHES FOR

DESIGNERS REVIEW AND SELECTION6. STANDARD OF DESIGN IS CURRENTLY INSTALLED IN THE UAH I2C AND SSB. CONTACT DESIGNER FOR MORE INFORMATION.

6" X 9"

BASE BID SIGNAGE SCHEDULEQTY TYPE MESSAGE

ALTERNATE SIGNAGE SCHEDULE

TYPE 1

TYPE 2

TYPE 3

TYPE 4

TYPE 5

TYPE 6

(SECOND FLOOR ONLY) (FIRST FLOOR ONLY)

MESSAGE

WOMENWOMEN'S RESTROOM

MENMEN'S RESTROOM

-

OFFICES/ CONFERENCE ROOMS/ WORKROOMS

NOT USED

TBD IN SUBMITTAL

CLASSROOMS/ CASE ROOMS/TEAM ROOMS/ LABS/ RESOURCE/ STAIRS

TBD IN SUBMITTAL

QTY TYPE MESSAGE

TYPE 1

TYPE 2

TYPE 3

TYPE 4

TYPE 5

TYPE 6

MESSAGE

WOMENWOMEN'S RESTROOM

MENMEN'S RESTROOM

-NOT USED

TBD IN SUBMITTAL

TBD IN SUBMITTAL

TYPE 7 JANITOR/ MECHANICAL/COPY ROOMS/ STORAGE/UTILITY/ PBX/ ELEVATORS/ SUPPORT

TYPE 7 JANITOR/ MECHANICAL/COPY ROOMS/ STORAGE/UTILITY/ MAIL ROOM/ PBX/ ELEVATORS/ AV

(1)

(1)

(8)

(13)

(14)

(2)

TBD IN SUBMITTAL TBD IN SUBMITTAL

(1)

(1)

(22)

(14)

(12)

(2)STAIRWELLS TBD IN SUBMITTAL TBD IN SUBMITTALSTAIRWELLS

OFFICES/ CONFERENCE ROOMS/ WORKROOMS

- -

CLASSROOMS/ CASE ROOMS/TEAM ROOMS/ LABS/ RESOURCE/ STAIRS

** NOTES: - ALL SIGNAGE QUATITIES ARE TO BE VERIFIED IN FIELD PRIOR TO SUBMITTAL.- MESSAGE SCHEDULE TO BE INCLUDED IN SUBMITTAL - REFER TO EXISTING ROOM NAMES FOR SUBMITTAL - FINAL TEXT AND ROOM NUMBERS TO BE APPROVED BY OWNER.

** NOTES: - ALL SIGNAGE QUATITIES ARE TO BE VERIFIED IN FIELD PRIOR TO SUBMITTAL.- MESSAGE SCHEDULE TO BE INCLUDED IN SUBMITTAL - REFER TO EXISTING ROOM NAMES FOR SUBMITTAL - FINAL TEXT AND ROOM NUMBERS TO BE APPROVED BY OWNER.

AMA

BALAFOETATSRE

GISTERED ARCHIT

EC

T

3196

REGISTRATIONNUMBER

RODNEY STEGER

MEMBER OF THE AMERICAN INSTITUTE OF ARCHITECTS

This document is a copyright protected instrument of service and licnesed for use in the titled project only. This drawing may not be

reproduced in whole or in part without written permission of FUQUA & PARTNERS ARCHITECTS, P.C.

A Professional Corporation

DATE:

ISSUE:

DRAWN:

PROJECT NO:

SHEET

OF

Architecture

Interior Design

Media Visualization

Master Planning

100 Church Street, Suite 700Huntsville, Alabama 35801

PH: (256) 534.3516FX: (256) 533.4605

www.fuquaarchitects.com

CHECKED:

3/9/

2020

8:0

0:21

AM

A8.0

DO

OR

SCH

EDU

LE, D

OO

R AN

D F

RAM

E DE

TAIL

S, A

ND

INTE

RIO

R DE

TAIL

S

301

SPAR

KMAN

DRI

VE, H

UN

TSVI

LLE,

AL

3589

9

LF

02-25-2020

FPA #07519

RKS

100 % CDs

1210

UAH

BAB

CYB

ER L

AB /

INTE

RIO

R RE

NO

VATI

ON

S

DOOR SCHEDULE

Room Name Door #DOOR FRAME DOOR & FRAME

W H T Elev Glazing Finish Type Finish Fire Rating

LAB SUPPORT 217 3'-0" 7'-0" 0'-1 3/4" WDF - STAINED A PAINTEDCYBERSECURITY LAB 219A 3'-0" 7'-0" 0'-1 3/4" WD2L TEMP STAINED A PAINTEDCYBERSECURITY LAB 219B 3'-0" 7'-0" 0'-1 3/4" WD2L TEMP STAINED A PAINTEDEXISTING RECEPTION 219F 3'-0" 7'-0" 0'-1 3/4" WD2LSTAIRS EX 5'-11 7/8" 6'-8" 0'-1 3/4" EX EX PNT-2 EX PAINTED

A8.0 1/4" = 1'-0"

1 DOOR TYPE ELEVATIONSONLY DOORS NOTED IN SCHEDULE ARE USED A8.0 1/4" = 1'-0"

2 DOOR FRAME TYPE ELEVATIONS

A8.0 1/2" = 1'-0"

3 TACTILE SIGN REQUIREMENTS

A8.0 3/32" = 1'-0"

4 SIGNAGE

A8.0 1/2" = 1'-0"

5 ELEVATIONCYBER LAB SIGNAGE

REVISIONS

1 Addendum #1 MARCH 9, 2020

1

1

1

Page 14: 100 Church Street, Suite 700 Huntsville, Alabama 35801 PH ...

APC-1 : 24X24 LAY-IN ACOUSTICAL CEILING & GRID SYSTEM

CEILING FINISHES:

APC-1 MANUFACTURER: ARMSTRONG STYLE: DUNE 1774COLOR: WHITEEDGE: ANGLED TEGULARSIZE: 24" X 24" X 5/8"GRID: Prelude XL 15/16" Exposed Tee. Color: WHITE

PRODUCT EQUAL TO:

EXISTING CEILING TO REMAIN

RECESSED 2X4 LED FIXTURE

LIGHTING:

RECESSED 2X2 LED FIXTURE

CEILING KEYNOTES:1. CEILING HEIGHTS ARE 9' - 9" A.F.F. UNLESS NOTED OTHERWISE.GENERAL NOTES:1. COORDINATE THE WORK OF ALL TRADES INVOLVED IN THE CEILING WORK TO INSURE CLEARANCES FOR FIXTURES, DUCTS, PIPING, CEILING

SUSPENSION SYSTEM, ETC., NECESSARY TO MAINTAIN THE FINISHED CEILING HEIGHTS. VERIFY IN FIELD.2. SEE ENGINEERING DRAWINGS FOR THE LOCATION OF CEILING FIXTURES, LIGHT TYPES, LIGHT FIXTURES, SWITCH LOCATIONS, AND ASSOCIATED

ITEMS. REFER TO ENGINEERING DRAWINGS FOR CIRCUITING, WIRING LAYOUT, AND ADDITIONAL INFORMATION.3. ALL SPECIFIC INFORMATION CONCERNING INSTALLATION OF VARIOUS ABOVE-CEILING ELEMENTS ARE TO BE FOUND IN THE HVAC, PLUMBING,

FIRE PROTECTION, ELECTRICAL, AND LIGHTING DRAWINGS.4. LIGHT FIXTURES, EXIT SIGNS, SPRINKLERS, AND OTHER CEILING ELEMENTS SHALL BE LOCATED IN CENTER OF INDIVIDUAL CEILING TILE, U.N.O.5. NOTIFY ARCHITECT OF ANY CONFLICTS OF LIGHT FIXTURE LOCATIONS WITH MAIN RUNNERS, DUCTS, STRUCTURES, HVAC, AND/OR CONDUIT,

PRIOR TO FRAMING FOR LIGHTS. ANY DISCREPANCIES BETWEEN ARCHITECTS’ CEILING GRID LOCATION AND ACTUAL FIELD CONDITIONS ARE TO BE CLARIFIED WITH THE ARCHITECT PRIOR TO FRAMING.

6. ALL SPRINKLER HEADS TO BE CONCEALED AND FLUSH WITH THE FINISH CEILING.7. SUBMIT GRILLE, SPRINKLER, THERMOSTAT, AND OTHER FIXTURE AND ELEMENT LAYOUTS TO THE ARCHITECT FOR REVIEW AT LEAST 2 WEEKS

PRIOR TO INSTALLATION8. PROVIDE CEILING ACCESS AS REQUIRED FOR EQUIPMENT AND SYSTEM MAINTENANCE, AND MATCH ADJACENT CEILING FINISH, U.N.O.

ARCHITECT TO APPROVE LOCATION PRIOR TO INSTALLATION.9. INSTALL LIGHT FIXTURES WITH PROTECTIVE FILM OR SIMILAR COVER OVER LOUVER, LENS, BAFFLE, AND THE LIKE, TO AVOID FIXTURE SOILING OR

DAMAGE; FIXTURES SHALL BE MAINTAINED CLEAN AND AS NEW; LAMPS SHALL BE NEW AT PROJECT COMPLETION.10. PERIMETER CEILING ANGLE, WHERE OCCURS, SHALL BE INSTALLED TIGHT TO VERTICAL SURFACES, FREE FROM CURVES, BREAKS, OR OTHER

IRREGULARITIES, AND PAINTED TO MATCH CEILING FINISH. 11. WALL SWITCH LOCATIONS SHALL BE COORDINATED WITH FURNITURE AND WALL MOUNTED EQUIPMENT LOCATIONS PRIOR TO BOX ROUGH-INS.

NOTIFY ARCHITECT OF ANY CONFLICTS PRIOR TO INSTALLATION OF ROUGH-INS.12. VERIFY FIELD CONDITIONS AND LOCATIONS OF ALL PLUMBING, MECHANICAL DUCTS, STRUCTURAL ELEMENTS, AND ANY AND ALL OTHER

APPLICABLE ITEMS; INSTALL APPLICABLE NEW PLUMBING, MECHANICAL FANS, DUCTS, CONDUITS, AND OTHER RELATED AND APPURTENANT ITEMS SO AS TO NOT CONFLICT WITH LUMINARIES AND ANY AND ALL FIELD CONDITIONS.

13. REFER TO ENGINEERING DRAWINGS FOR ALL LIFE SAFETY DEVICES REQUIRED BY CODE AND ALL EMERGENCY LIGHT FIXTURES. COORDINATE LOCATION OF DEVICES WITH ALL ARCHITECTURAL DOCUMENTS PRIOR TO INSTALLATION OF BACK BOXES. REVIEW ALL ARCHITECTURAL AND ENGINEERING DOCUMENTS AND NOTIFY ARCHITECT OF ANY CONFLICTS. GENERAL CONTRACTOR TO COORDINATE AND VERIFY LOCATIONS OF EXISTING DEVICES TO REMAIN WITH ARCHITECTURAL PLANS AND NOTIFY ARCHITECT OF ANY CONFLICTS DURING THE ROUGH-IN PHASE OF PROJECT.

EXISTINGMECHANICAL

EXISTINGAUDITORIUM

EXISTINGCASE

ROOM #5

EXISTINGCASE

ROOM #4

EXISTINGATRIUMLOBBY

EXISTING CORRIDOR146

EXISTINGTRADE LAB

AIRLOCK146A

EXISTING STUDYRESOURCE

150

CONFERENCE149

WOMEN

MEN

MAIL RM

PBX

ELECT.

EXISTINGMECHANICAL

EXISTING TEAM117

EXISTING TEAM116

EXISTING TEAM118

EXISTING TEAM119

STUDYALCOVEBEHAV.

SCIENCEB.S.

CONTROLEXISTING

CORRIDOREXISTINGOFFICE

EXISTINGRECEPTION

EXISTINGOFFICE

EXISTINGOFFICE

EXISTINGOFFICE

EXISTINGRECORD

EXISTINGSTAIR

EXISTINGCASE

ROOM #1

EXISTINGCASE

ROOM #2

EXISTINGTEAM

EXIST. CORRIDOR115

EXIST. CORRIDOR115

EXIST.ELEV.

EXISTING CORRIDOR125

EXISTING CORRIDOR125 EXISTING STAIRS

256

EXISTING CORRIDOR137

EXISTING CORRIDOR137

EXIST. CONF.136

EXIST. CONF.135

EXISTING OFFICE133

EXISTING OFFICE134

EXISTING OFFICE132

EXIST. WORKROOM126

EXISTING OFFICE128

EXISTING OFFICE127

EXISTING OFFICE129

EXISTING OFFICE130

EXISTING OFFICE131

EXISTING CASEROOM #3

120

EXIST. JAN.

EXIT. ELEV.

REPAIR AND PATCH CEILING AT NEW COLUMN DETAIL

REPAIR AND PATCH CEILING WHERE COLUMN WAS REMOVED

EXISTING CEILING TO REMAIN REPAIR AND PATCH CEILING WHERE COLUMN WAS REMOVED

REPAIR AND PATCH CEILING WHERE COLUMN WAS REMOVED

repair ceilings disturbed by installation of floor boxes above

patch and repair ceiling disturbed by installation of conduit above

EXISTINGATRIUMLOBBY

AMA

BALAFOETATSRE

GISTERED ARCHIT

EC

T

3196

REGISTRATIONNUMBER

RODNEY STEGER

MEMBER OF THE AMERICAN INSTITUTE OF ARCHITECTS

This document is a copyright protected instrument of service and licnesed for use in the titled project only. This drawing may not be

reproduced in whole or in part without written permission of FUQUA & PARTNERS ARCHITECTS, P.C.

A Professional Corporation

DATE:

ISSUE:

DRAWN:

PROJECT NO:

SHEET

OF

Architecture

Interior Design

Media Visualization

Master Planning

100 Church Street, Suite 700Huntsville, Alabama 35801

PH: (256) 534.3516FX: (256) 533.4605

www.fuquaarchitects.com

CHECKED:

2/26

/202

0 10

:17:

13 A

M

A9.1

FIRS

T FL

OO

R -R

EFLE

CTE

D C

EILI

NG

PLA

N

301

SPAR

KMAN

DRI

VE, H

UN

TSVI

LLE,

AL

3589

9

LWF

02-25-2020

FPA #07519

FS

100 % CDs

1211

UAH

BAB

CYB

ER L

AB /

INTE

RIO

R RE

NO

VATI

ON

SREFLECTED CEILING PLAN NOTES

RCP LEGEND

NORTH

1/8" = 1'-0"

PARTIAL FIRST FLOOR - REFLECTED CEILING

KEY PLAN

0' 4' 8' 16' 32'

REVISIONS

Page 15: 100 Church Street, Suite 700 Huntsville, Alabama 35801 PH ...

COMPUTERCLASSROOM

EXIST.BALCONY

EXIST.CLASSROOM

EXIST.CORRIDOR

211

MEN

EXISTINGELEC.

WOMEN

PBX

A.F.F.APC-1

11'-4"

EX.SERVERROOM

EXISTING CORRIDOR231

EXISTINGCLOSET

EXISTINGPORCH

UTILITY

RECEPTION

STAIR

EXIST.JANITOR EXIST.

COPY RM

EXIST.ELEV.

EXISTINGMECHANICAL

EXIST.ELEV.

EXISTINGMECHANICAL

EXIST.CLASSROOM

EXIST.CLASSROOM

CLASSROOM

LABSUPPORT

EXIST.CLASSROOM

EXIST.CLASSROOM

EXIST.CLASSROOM

RECORDS

OFFICEOFFICE

OFFICE

OFFICESECRETARY

CONFERENCEROOM

STOR.

TOIL.

OFFICE

STAIRS

CORRIDOR

EXIST.CORRIDOR

207

CYBERSECURITYLAB219

CYBERLOUNGE

218

A.F.F.APC-1

9'-9"

A.F.F.APC-1

9'-9"

A.F.F.APC-1

9'-6"

CEILING MOUNTED MONITORS

DEMOUNTABLE WALL WITH FULL HEGHT GLASS (TO BE INCLUDED IN FURNITURE PACKAGE)

CEILING MOUNTED MONITOR CEILING MOUNTED

MONITOR

CEILING MOUNTED MONITORS

WALL MOUNTED MONITORS26'-4 1/4"

CEILING MOUNTED MONITOR

A.F.F.APC-1

9'-9"

10A6.0

12A6.0

15A6.0

CEILING MOUNTED ELECTRIC ROLLER SHADES AT EACH WINDOW, TYPICAL. LENGTH AS CENTERED ON EACH VERTICAL MULLION (V.I.F.)

CEILING MOUNTED ELECTRIC ROLLER SHADES AT EACH WINDOW, TYPICAL. LENGTH AS CENTERED ON EACH VERTICAL MULLION (V.I.F.)

EXIST.BALCONY

EXIST. LAB

EXIST. LAB

AIRLOCK233

CEILING MOUNTED MANUALROLLER SHADES AT EACH WINDOW, TYPICAL. LENGTH AS CENTERED ON EACH VERTICAL MULLION (V.I.F.)

A6.0

9A6.0

9

A6.0

9 sim.

APC-1 : 24X24 LAY-IN ACOUSTICAL CEILING & GRID SYSTEM

CEILING FINISHES:

APC-1 MANUFACTURER: ARMSTRONG STYLE: DUNE 1774COLOR: WHITEEDGE: ANGLED TEGULARSIZE: 24" X 24" X 5/8"GRID: Prelude XL 15/16" Exposed Tee. Color: WHITE

PRODUCT EQUAL TO:

EXISTING CEILING TO REMAIN

RECESSED 2X4 LED FIXTURE

LIGHTING:

RECESSED 2X2 LED FIXTURE

CEILING KEYNOTES:1. CEILING HEIGHTS ARE 9' - 9" A.F.F. UNLESS NOTED OTHERWISE.GENERAL NOTES:1. COORDINATE THE WORK OF ALL TRADES INVOLVED IN THE CEILING WORK TO INSURE CLEARANCES FOR FIXTURES, DUCTS, PIPING, CEILING

SUSPENSION SYSTEM, ETC., NECESSARY TO MAINTAIN THE FINISHED CEILING HEIGHTS. VERIFY IN FIELD.2. SEE ENGINEERING DRAWINGS FOR THE LOCATION OF CEILING FIXTURES, LIGHT TYPES, LIGHT FIXTURES, SWITCH LOCATIONS, AND ASSOCIATED

ITEMS. REFER TO ENGINEERING DRAWINGS FOR CIRCUITING, WIRING LAYOUT, AND ADDITIONAL INFORMATION.3. ALL SPECIFIC INFORMATION CONCERNING INSTALLATION OF VARIOUS ABOVE-CEILING ELEMENTS ARE TO BE FOUND IN THE HVAC, PLUMBING,

FIRE PROTECTION, ELECTRICAL, AND LIGHTING DRAWINGS.4. LIGHT FIXTURES, EXIT SIGNS, SPRINKLERS, AND OTHER CEILING ELEMENTS SHALL BE LOCATED IN CENTER OF INDIVIDUAL CEILING TILE, U.N.O.5. NOTIFY ARCHITECT OF ANY CONFLICTS OF LIGHT FIXTURE LOCATIONS WITH MAIN RUNNERS, DUCTS, STRUCTURES, HVAC, AND/OR CONDUIT,

PRIOR TO FRAMING FOR LIGHTS. ANY DISCREPANCIES BETWEEN ARCHITECTS’ CEILING GRID LOCATION AND ACTUAL FIELD CONDITIONS ARE TO BE CLARIFIED WITH THE ARCHITECT PRIOR TO FRAMING.

6. ALL SPRINKLER HEADS TO BE CONCEALED AND FLUSH WITH THE FINISH CEILING.7. SUBMIT GRILLE, SPRINKLER, THERMOSTAT, AND OTHER FIXTURE AND ELEMENT LAYOUTS TO THE ARCHITECT FOR REVIEW AT LEAST 2 WEEKS

PRIOR TO INSTALLATION8. PROVIDE CEILING ACCESS AS REQUIRED FOR EQUIPMENT AND SYSTEM MAINTENANCE, AND MATCH ADJACENT CEILING FINISH, U.N.O.

ARCHITECT TO APPROVE LOCATION PRIOR TO INSTALLATION.9. INSTALL LIGHT FIXTURES WITH PROTECTIVE FILM OR SIMILAR COVER OVER LOUVER, LENS, BAFFLE, AND THE LIKE, TO AVOID FIXTURE SOILING OR

DAMAGE; FIXTURES SHALL BE MAINTAINED CLEAN AND AS NEW; LAMPS SHALL BE NEW AT PROJECT COMPLETION.10. PERIMETER CEILING ANGLE, WHERE OCCURS, SHALL BE INSTALLED TIGHT TO VERTICAL SURFACES, FREE FROM CURVES, BREAKS, OR OTHER

IRREGULARITIES, AND PAINTED TO MATCH CEILING FINISH. 11. WALL SWITCH LOCATIONS SHALL BE COORDINATED WITH FURNITURE AND WALL MOUNTED EQUIPMENT LOCATIONS PRIOR TO BOX ROUGH-INS.

NOTIFY ARCHITECT OF ANY CONFLICTS PRIOR TO INSTALLATION OF ROUGH-INS.12. VERIFY FIELD CONDITIONS AND LOCATIONS OF ALL PLUMBING, MECHANICAL DUCTS, STRUCTURAL ELEMENTS, AND ANY AND ALL OTHER

APPLICABLE ITEMS; INSTALL APPLICABLE NEW PLUMBING, MECHANICAL FANS, DUCTS, CONDUITS, AND OTHER RELATED AND APPURTENANT ITEMS SO AS TO NOT CONFLICT WITH LUMINARIES AND ANY AND ALL FIELD CONDITIONS.

13. REFER TO ENGINEERING DRAWINGS FOR ALL LIFE SAFETY DEVICES REQUIRED BY CODE AND ALL EMERGENCY LIGHT FIXTURES. COORDINATE LOCATION OF DEVICES WITH ALL ARCHITECTURAL DOCUMENTS PRIOR TO INSTALLATION OF BACK BOXES. REVIEW ALL ARCHITECTURAL AND ENGINEERING DOCUMENTS AND NOTIFY ARCHITECT OF ANY CONFLICTS. GENERAL CONTRACTOR TO COORDINATE AND VERIFY LOCATIONS OF EXISTING DEVICES TO REMAIN WITH ARCHITECTURAL PLANS AND NOTIFY ARCHITECT OF ANY CONFLICTS DURING THE ROUGH-IN PHASE OF PROJECT.

AMA

BALAFOETATSRE

GISTERED ARCHIT

EC

T

3196

REGISTRATIONNUMBER

RODNEY STEGER

MEMBER OF THE AMERICAN INSTITUTE OF ARCHITECTS

This document is a copyright protected instrument of service and licnesed for use in the titled project only. This drawing may not be

reproduced in whole or in part without written permission of FUQUA & PARTNERS ARCHITECTS, P.C.

A Professional Corporation

DATE:

ISSUE:

DRAWN:

PROJECT NO:

SHEET

OF

Architecture

Interior Design

Media Visualization

Master Planning

100 Church Street, Suite 700Huntsville, Alabama 35801

PH: (256) 534.3516FX: (256) 533.4605

www.fuquaarchitects.com

CHECKED:

2/26

/202

0 10

:17:

23 A

M

A9.2

SEC

ON

D F

LOO

R -R

EFLE

CTE

D C

EILI

NG

PLA

N301

SPAR

KMAN

DRI

VE, H

UN

TSVI

LLE,

AL

3589

9

AWF/ LF

02-25-2020

FPA #07519

RKS

100 % CDs

1212

UAH

BAB

CYB

ER L

AB /

INTE

RIO

R RE

NO

VATI

ON

S

NORTH

1/8" = 1'-0"

SECOND FLOOR - REFLECTED CEILING PLAN

REFLECTED CEILING PLAN NOTES

RCP LEGEND

0' 2' 4 8' 16'

KEY PLAN

REVISIONS

Page 16: 100 Church Street, Suite 700 Huntsville, Alabama 35801 PH ...

J J

H H

G G

F F

E E

D D

C C

B B

A A

1

1

2

2

3

3

4

4

5

5

6

6

8

8

9

9

7

7

SPRINKLER HEADS TO BE REWORKED TO NEW CEILING IN THESE AREAS. NEW HEADS SHALL BE INSTALLED. CEILINGS TO BE INSTALLED AT THE SAME ELEVATION AS EXISTING. COORDINATE WITH ARCHITECTURAL.

CYBERSECURITY

LAB

219

CYBER LOUNGE

218

EXIST.

CLASSROOM

220

EXIST.

CLASSROOM

232C

EXIST.

CLASSROOM

222

EXIST.

CLASSROOM

224

BALCONY

230

EXISTING PORCH

208

EXIST. CORRIDOR

207

EXISTING

CORRIDOR

231

EXIST. CORRIDOR

211

LAB SUPPORT

217

GRAPHIC SCALE: 1/16" = 1'-0"

0 8' 16' 32' 48' 64'24' 40'

mdsMechanical Design Services, Inc.

100 Church St. SW, Suite 650, Huntsville, AL 35801

(256) 534-5150 [email protected]

GENERAL FIRE PROTECTION NOTES

1. THIS CONTRACTOR IS RESPONSIBLE FOR REVIEWING ALL DRAWINGS AND SPECIFICATIONS OF ALL DISCIPLINES FOR ANY AND ALL WORK THAT WILL IMPACT THIS CONTRACTOR AND WILL BE THE RESPONSIBILITY OF THIS CONTRACTOR TO PROVIDE SAID WORK.

2. CONTRACTOR(S) SHALL COORDINATE PRIOR/DURING CONSTRUCTION TO ELIMINATE ANY CONFLICTS.

3. ALL WET SYSTEMS SHALL BE INSTALLED WITHIN THE WARM SIDE OF THE BUILDING INSULATION ENVELOPE OR HEATED AREA.

4. ALL SPRINKLER HEADS SHALL BE COORDINATED WITH LIGHTS, CEILING SOFFITS, SOUND BAFFLES, ARCHITECTURAL FEATURES, CEILING DEVICES, ETC. "OVER COVERAGE" SHALL BE PROVIDED TO ENSURE CEILING SYMMETRY.

5. HEADS SHALL BE PROVIDED UNDER ANY OBSTRUCTION 48" IN WIDTH OR GREATER.

6. ALL PIPING, HANGERS, ETC. SHALL NOT INTERFERE WITH MECHANICAL, PLUMBING, AND ELECTRICAL EQUIPMENT, DEVICES, DAMPERS, ETC.

7. WIRE GUARDS ARE TO BE PROVIDED ON ALL HEADS IN ALL EXPOSED AREAS INCLUDING MECHANICAL AND ELECTRICAL ROOMS.

8. COORDINATE WITH BOTH LOCAL AND STATE AHJ AND ELECTRICAL FOR REQUIREMENTS OF ELECTRICAL EQUIPMENT SHIELDING.

THREADED ROD COUPLING AND JAMB NUT

HEAVY DUTY EXPANSION ANCHOR EQUAL TO HILTI HSLG SERIES.

CONCRETE FLOOR

WASHER & NUT

HEAVY DUTY SIDE BEAM ANGLE BRACKET FOR USE WITH WOOD, STEEL OR CONCRETE BEAMS.

NUT ON TOP AND BOTTOM.

NUT ON TOP AND BOTTOM.

CLEVIS HANGER.

BEAM CLAMP EQUAL TO PHD MFG. FIGURE 350 FOR USE WITH BEAM TOP FLANGE OR BAR JOIST.

THREADED ROD (TYPICAL).

PIPE

PIPE HANGER DETAILNOT TO SCALE

A

LA B A M

A

JO

H

NN

YN . E C

H

OL

S

JO

H

NN

YN . E C

H

OL

S

ENG I NE ER

L ICENSED

No. 30043

PROFESSIONAL

MEMBER OF THE AMERICAN

INSTITUTE OF ARCHITECTS

This document is a copyright protected instrument of service and

licnesed for use in the titled project only. This drawing may not be reproduced in whole or in part without written permission of

FUQUA & PARTNERS ARCHITECTS, P.C.A Professional Corporation

DATE:

ISSUE:

DRAWN:

PROJECT NO:

SHEET

OF

Architecture

Interior Design

Media Visualization

Master Planning

100 Church Street, Suite 700Huntsville, Alabama 35801

PH: (256) 534.3516FX: (256) 533.4605

www.fuquaarchitects.com

CHECKED:

2/2

5/2

020 4

:46:1

6 P

M

FP1.0

FIR

E P

RO

TE

CT

ION

FLO

OR

PLA

N

301

SP

AR

KM

AN

DR

IVE

, HU

NT

SV

ILLE

AL.

358

99

JJP

02-25-2020

FPA #07519

JNE

COORDINATION

UA

H B

AB

CY

BE

R L

AB

/ IN

TE

RIO

R R

EN

OV

AT

ION

1/16" = 1'-0"

FIRE PROTECTION - 2ND FLOOR

REVISIONS

Page 17: 100 Church Street, Suite 700 Huntsville, Alabama 35801 PH ...

TT

T

T

T

T

GRAPHIC SCALE: 1/8" = 1'-0"

0 4' 8' 16' 24' 32'2' 6' 12'

mdsMechanical Design Services, Inc.

100 Church St. SW, Suite 650, Huntsville, AL 35801

(256) 534-5150 [email protected]

E E

D D

C C

B B

A A

8

8

9

9

7

7

54"x

14"

FD

FD

FD

FD52"x12"

44"x

14"

14"x8"

6"x10"

8"x10"

8"x

10"

12"x

12"

14"x

12"

10"x

12"

12"x

12"

6"x12"12"x12"

26"x14"

8"x

12"

14"x

12"

FD FD FD

FD

TO AC 2-1

230 CFM240 CFM

240 CFM

230 CFM

250 CFM140 CFM 190 CFM 190 CFM

240 C

FM

180 CFM

140 CFM

280 CFM

280 CFM 280 CFMDEMO SECTION OF DUCT FOR NEW FIRE DAMPER. TYPICAL FOR 3.

A

B B

A

C

C

C

AA A

AAA

AA

B

A

A A

A

EXISTING FD NOT REQUIRED, BUILDING IS NOW SPRINKLED. FIRE DAMPER TO REMAIN IN EXISTING WALL, TYPICAL FOR FIRE DAMPERS IN UNCHANGED WALLS.

D

DD

ZO

NE

D

ZO

NE

F

ZO

NE

H

ZO

NE

J

E E

D D

C C

B B

A A

8

8

9

9

7

7

EXIST. CORRIDOR

211

EXISTING

CLOSET

236

EXIST. COPY RM

225EXIST. ELEV.

239B

EXISTING

MECHANICAL

223

EXIST.

CLASSROOM

232C

LAB SUPPORT

217

EXIST.

CLASSROOM

220

EXIST.

CLASSROOM

224

EXIST.

CLASSROOM

222

STAIRS

219

CYBERSECURITY

LAB

219

CYBER LOUNGE

218

PATCH EXISTING

24X24 CD-1

125 CFM

24X24 CD-1

125 CFM

24X24 CD-1

125 CFM

24X24 CD-1

125 CFM

10"x

12"

14"x

12"

12"x

12"

24X24 CD-1

500 CFM

24X24 CD-1

500 CFM

24X24 CD-1

420 CFM

24X24 CD-1

250 CFM

24X24 CD-1

420 CFM

24X24 CD-1

420 CFM

12"x12"

14"x

12"

54"x

14"

24X24 CD-1

140 CFM

8"ø

ZONE "D"

ZONE F, J & H

8"ø8"ø

8"ø8"ø

12"ø

10"ø

EXISTING AC 2-1

22X22 CG-1

755 CFM

TYP. FOR 214X14 CG-1

400 CFM

REBALANCE AC 2-1 ZONES D,F,H, & J TO NEW FLOW RATES.

10"ø

10"ø

12"x

12"

12"x

12"

10"ø

CONNECT TO EXISTING 3" CHILLED WATER PIPING.

3/4"ø CHWS3/4"ø CHWR

1 1/4"ø HWS1 1/4"ø HWR

3"ø CHWR3"ø CHWS

52"x12"

SV

SV

IU-217

NOTE:ROUTE 3/4" CONDENSATE LINE FROM IU-217 TO FLOOR/HUB DRAIN IN EXISTING MECHANICAL ROOM 223. ROUTE IN MANNER TO NOT CAUSE A TRIP HAZARD.

24X24 CD-1

140 CFM

22X22 CG-1

INSULATED END CAP.

DUCT DAMPERS & ACTUATORSFD = FIRE DAMPER WITH ACCESS DOORM = MOTORIZED DAMPERSV = SERVICE VALVEVD = VOLUME DAMPER

PIPING SYSTEMSCHWS = CHILLED WATER SUPPLYCHWR = CHILLED WATER RETURN

SENSORS (INSIDE SENSOR ICON)T = THERMOSTAT

MECHANICAL NOTATION LEGEND MECHANICAL SYMBOL LEGEND

= NEW WORK (DUCT, EQUIPMENT, PIPE, ETC.)

= EXISTING WORK TO REMAIN

= EXISTING WORK TO BE REMOVED

= MANUAL VOLUME DAMPER

= MOTORIZED DAMPERM

T

A

= SENSOR ICON

= DEMOLITION KEY NOTE

= SUPPLY DROP / RISE

= RETURN DROP / RISE

= EXHAUST DROP / RISE

= PIPE DROP / RISE

GENERAL MECHANICAL NOTES

1. THIS CONTRACTOR IS RESPONSIBLE FOR REVIEWING ALL DRAWINGS AND SPECIFICATIONS OF ALL DISCIPLINES FOR ANY AND ALL WORK THAT WILL IMPACT THIS CONTRACTOR AND WILL BE THE RESPONSIBILITY OF THIS CONTRACTOR TO PROVIDE SAID WORK.

2. CERTAIN AREAS WILL REQUIRE EXTENSIVE COORDINATION BETWEEN ALL TRADES. CONTRACTOR(S) SHALL COORDINATE PRIOR/DURING CONSTRUCTION TO ELIMINATE ANY CONFLICTS.

3. THE LOCATION OF ALL CEILING MOUNTED AIR DISTRIBUTION DEVICES SHALL BE COORDINATED WITH THE ARCHITECTURAL REFLECTED CEILING PLAN AND SHALL AVOID CONFLICT WITH ALL CEILING DEVICES, MOUNTED LIGHTS, PROJECTORS, ETC.

4. ALL DUCT SIZES INDICATED ON THE DRAWINGS ARE FOR THE CLEAR INSIDE DIMENSION. CONTRACTOR SHALL INCREASE DUCT SIZE IF INTERIOR DUCT INSULATION IS CALL FOR ON THE DRAWINGS. THE SAME APPLIES FOR DOUBLE WALL SPIRAL DUCT.

5. THE BOTTOM OF ALL DUCTWORK AND PIPING TO BE COORDINATED WITH ROOM FINISH SCHEDULE FOR CEILING HEIGHTS AND SHALL BE A MINIMUM OF 6" ABOVE THE CEILING GRID. ALL SERVICEABLE ITEMS SUCH AS EQUIPMENT, ACTUATORS, DAMPERS, VALVES, CONTROL DEVICES, ETC. SHALL BE LOCATED NO MORE THAN 24" ABOVE THE CEILING GRID.

6. ALL DUCTS AND PIPING INDICATED ON THE DRAWINGS ARE DIAGRAMMATIC ONLY. THEY MAY BE REQUIRED TO BE SHIFTED, OFFSET OR INSTALLED HIGH IN BETWEEN THE JOISTS AS DETERMINED BY FIELD CONDITIONS. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE ALL MATERIALS AND LABOR NECESSARY TO INSTALL THE PIPING AND DUCTS TO MEET THE INTENT OF THE DRAWINGS.

7. ROUND BRANCH RUN-OUTS TO AIR DISTRIBUTION DEVICES ARE TO BE ENTIRELY SHEET METAL WITH THE EXCEPTION THAT UP TO FIVE FEET OF FLEX DUCT MAY BE USED ON EACH BRANCH UNLESS OTHERWISE INDICATED. ALL FLEX DUCT SHALL BE SUPPORTED INDEPENDENT OF THE CEILING, PIPING, CONDUITS, OTHER DUCTS, ETC. AND SHALL BE SUPPORTED IN SUCH A WAY AS TO AVOID KINKING OR OBSTRUCTION OF AIR FLOW.

8. THE MECHANICAL CONTRACTOR SHALL INSTALL FIRE DAMPERS, SMOKE DAMPERS OR COMBINATION DAMPERS AT ALL FIRE RATED WALLS AND/OR SMOKE BARRIERS. REFER TO THE EXISTING ARCHITECTURAL LIFE SAFETY PLANS, IN THE OWNER'S POSSESSION, FOR THE WALL / CEILING RATINGS AND LOCATIONS.

9. CONTRACTOR SHALL NOT FABRICATE OR CONSTRUCT DUCTWORK, PIPING, ETC. FROM THE DRAWINGS PRIOR TO VERIFYING DUCT, PIPING, ETC. CAN BE INSTALLED IN THE FIELD WITH RESPECT TO FIELD CONDITIONS.

10. COORDINATE WITH ARCHITECTURAL PLANS FOR CEILING REPLACEMENT AREAS. REPLACE ANY AIR TERMINALS WITH LIKE KIND.

MECHANICAL DEMOLITION NOTES

A. REMOVE EXISTING DUCT BRANCH AND CEILING MOUNTED DIFFUSER / GRILLE BACK TO THE MAIN TRUNK INCLUDING ALL DUCT HANGERS ETC. PATCH, INSULATE & SEAL DUCTWORK AIR TIGHT. EXTEND DUCT WHERE REQUIRED AS SHOWN ON NEW DRAWING TO ATTACH TO NEW GRILLE / DIFFUSER.

B. REMOVE EXISTING FIRE DAMPER. PATCH, INSULATE & SEAL DUCTWORK AIR TIGHT.

C. REMOVE EXISTING TRANSFER DUCT INCLUDING ALL DUCT HANGERS ETC.

D. REMOVE EXISTING WALL MOUNTED PNEUMATIC THERMOSTAT. SEE SEQUENCE OF CONTROL.

A

LA B A M

A

JO

H

NN

YN . E C

H

OL

S

JO

H

NN

YN . E C

H

OL

S

ENG I NE ER

L ICENSED

No. 30043

PROFESSIONAL

MEMBER OF THE AMERICAN

INSTITUTE OF ARCHITECTS

This document is a copyright protected instrument of service and

licnesed for use in the titled project only. This drawing may not be reproduced in whole or in part without written permission of

FUQUA & PARTNERS ARCHITECTS, P.C.A Professional Corporation

DATE:

ISSUE:

DRAWN:

PROJECT NO:

SHEET

OF

Architecture

Interior Design

Media Visualization

Master Planning

100 Church Street, Suite 700Huntsville, Alabama 35801

PH: (256) 534.3516FX: (256) 533.4605

www.fuquaarchitects.com

CHECKED:

2/2

5/2

020 4

:46:1

7 P

M

M1.0

ME

CH

AN

ICA

L F

LOO

R P

LAN

301

SP

AR

KM

AN

DR

IVE

, HU

NT

SV

ILLE

AL.

358

99

JJP

02-25-2020

FPA #07519

JNE

COORDINATION

UA

H B

AB

CY

BE

R L

AB

/ IN

TE

RIO

R R

EN

OV

AT

ION

1/8" = 1'-0"

DEMOLTION - 2ND FLOOR DUCT SYSTEMS1/8" = 1'-0"

SECOND FLOOR DUCT SYSTEMS

REVISIONS

Page 18: 100 Church Street, Suite 700 Huntsville, Alabama 35801 PH ...

24X24 CD-1

170 CFM

SEE MECHANICAL FLOOR PLAN FOR GRILLE CHANGES IN THIS AREA.

CEILINGS TO BE REPLACED IN THESE AREAS. REMOVE EXISTING AIR TERMINALS AND REPLACE WITH NEW. COORDINATE WITH ARCHITECTURAL.

CEILINGS TO BE REPLACED IN THESE AREAS. REMOVE EXISTING AIR TERMINALS AND REPLACE WITH NEW.COORDINATE WITH ARCHITECTURAL.

3'-0" SD-1

250 CFM

3'-0" SD-1

250 CFM

3'-0" SD-1

250 CFM

3'-0" SD-1

250 CFM

22X22 CG-1

24X24 CD-1

190 CFM

24X24 CD-1

190 CFM

24X24 CD-1

170 CFM

24X24 CD-1

170 CFM

24X24 CD-1

160 CFM

22X22 CG-1

22X22 CG-1

24X24 CD-1

140 CFM24X24 CD-1

140 CFM

mdsMechanical Design Services, Inc.

100 Church St. SW, Suite 650, Huntsville, AL 35801

(256) 534-5150 [email protected]

GRAPHIC SCALE: 1/16" = 1'-0"

0 8' 16' 32' 48' 64'24' 40'

A

LA B A M

A

JO

H

NN

YN . E C

H

OL

S

JO

H

NN

YN . E C

H

OL

S

ENG I NE ER

L ICENSED

No. 30043

PROFESSIONAL

MEMBER OF THE AMERICAN

INSTITUTE OF ARCHITECTS

This document is a copyright protected instrument of service and

licnesed for use in the titled project only. This drawing may not be reproduced in whole or in part without written permission of

FUQUA & PARTNERS ARCHITECTS, P.C.A Professional Corporation

DATE:

ISSUE:

DRAWN:

PROJECT NO:

SHEET

OF

Architecture

Interior Design

Media Visualization

Master Planning

100 Church Street, Suite 700Huntsville, Alabama 35801

PH: (256) 534.3516FX: (256) 533.4605

www.fuquaarchitects.com

CHECKED:

2/2

5/2

020 4

:46:1

8 P

M

M2.0

ME

CH

AN

ICA

L F

LOO

R P

LAN

301

SP

AR

KM

AN

DR

IVE

, HU

NT

SV

ILLE

AL.

358

99

Author

02-25-2020

FPA #07519

Checker

COORDINATION

UA

H B

AB

CY

BE

R L

AB

/ IN

TE

RIO

R R

EN

OV

AT

ION

1/16" = 1'-0"

MECHANICAL CEILING PLAN

REVISIONS

Page 19: 100 Church Street, Suite 700 Huntsville, Alabama 35801 PH ...

CHILLED WATER FAN COIL UNIT WITH ELECTRIC HEAT SCHEDULE

MARK

UNIT SIZE

TOTAL AMPS

MIN. VOLT.

ACCESSORIES:

1. PROVIDE 24VAC WIRED WALL MOUNTED THERMOSTAT WITH AUTOMATIC CHANGEOVER.

2. PROVIDE 2-WAY NC VALVE AND 24V MOTORIZED ACTUATOR. PROVIDE HOSE KITS CONSISTING OF; RETURN SIDE (FULL PORT BALL VALVE, 24" STAINLESS STEEL HOSE, AUTOMATIC BALANCING VALVE WITH P/T PORTS) SUPPLY SIDE (FULL PORT BALL VALVE WITH P/T PORTS, 24" STAINLESS STEEL HOSE, Y STRAINER WITH BLOWDOWN VALVE).

3. PROVIDE CONDENSATE PUMP KIT, 115 V

NOTES:

A.

B.

SUPPLY FAN

CFM

FAN QTY

COOLING COIL

TOTAL CAPACITY, MBH

SENSIBLE CAPACITY, MBH

E.A.T. DB / WB , °F

E.W.T. DB / L.W.T., °F

ELEC. HEAT kW

BASIS OF DESIGN

MANUFACTURER

MODEL

WEIGHT, LBS.

ACCESSORIES

IU-217

GPM

WATER ΔP, PSI

FULLY INSULATE THE HOSE KITS, CONTROL VALVES AND ACCESSORIES. INSULATION SHALL BE GLUED TO THE UNIT CASING. INSULATION COVERING SERVICEABLE ITEMS SHALL BE OVER CUT AND AN ARMAFLEX UNGLUED INSERT PLACED INSIDE THE OVER CUT GLUED ARMAFLEX INSULATION.

CLOSELY COORDINATE THE UNIT LOCATION WITH OTHER TRADES.

18

600

1

17.7

80 / 67

44 / 60

2.5

4.3

197

17

20

EMI

WCP18

120

1, 2, 3

A, B

14.1

L.A.T. DB / WB , °F 59.2 / 58.6

ELECTRICAL

FAN HP

ELEC. HEAT AMPS

FAN AMPS

MCA

MOCP

VOLT / PHASE 208 / 1

13.6

3.0

13.1

0.07

0.56

NOTES

GRILLE, REGISTER AND DIFFUSER SCHEDULE

MARK

DESCRIPTION

MOUNTING

MATERIAL

FINISH

BORDER TYPE

CD-1

SQUARE PLAQUE FACE CEILING DIFFUSER

ROUND NECK

LAY-IN

ALUMINUM

ACCESSORIES:

1. TITUS HAS BEEN SPECIFIED TO ESTABLISH THE TYPE AND QUALITY OF AIR DEVICE TO BE INSTALLED. PRIOR APPROVED EQUALS WILL BE CONSIDERED. PRIOR APPROVAL REQUEST MUST BE SUBMITTED 10 DAYS PRIOR TO BID.

2.

3.

4.

5.

6.

7.

TITUS MODEL

MATCH CEILING COLOR

TYPE 3

OMNI-AA

SD-1

LAY-IN

ALUMINUM

MATCH CEILING COLOR

TYPE 2A

ML-39

CG-1

SQUARE LOUVERED FACE CEILING GRILLE, SQUARE

NECK, 35° DEFLECTION

SURFACE

ALUMINUM

MATCH CEILING COLOR

TYPE 1

350FL

MAXIMUM NC RATING SHALL NOT EXCEED 30.

AIR DEVICES THAT ARE CEILING CUT-IN TYPE SHALL BE CENTERED IN THE TILE.

CEILING MOUNTED LOUVERED RETURN / EXHAUST GRILLES SHALL BE INSTALLED WITH THE BLADES POINTED TOWARD THE CLOSEST WALL SO THAT THE BLADES FORM A VIEW BLOCK.

WALL MOUNTED RETURN / EXHAUST GRILLES SHALL BE INSTALLED WITH THE BLADES POINTING TOWARD THE FLOOR OR CEILING, WHICHEVER IS NEAREST, SO THAT THE BLADES FORM A VIEW BLOCK.

INTERNAL PORTION OF DUCT, INCLUDING INLET PLENUM BOX, ATTACHED TO SUPPLY, RETURN, EXHAUST AND TRANSFER GRILLES SHALL BE BLACKED OUT WITH A DULL FINISH, NON-TOXIC, DTM PAINT.

GRILLE TERMINATION SHALL BE FLEXMASTER FISB OR PRIOR APPROVED EQUAL UNLESS OTHERWISE SPECIFIED IN SCHEDULE ABOVE OR NOTED ON DRAWINGS. SEE DETAIL FOR DUCT TO GRILLE, REGISTER, DIFFUSER CONNECTION.

SLOT DIFFUSER, (3) 1" SLOTS, ADJUSTABLE

PATTERN CONTROLLERS

RETURN / EXHAUST AIRFLOWSUPPLY AIRFLOW

RECTANGULAR TO ROUND 45°

DUCT TAKE-OFF DETAILNOT TO SCALE

RECTANGULAR DUCT

ROUND BRANCH DUCT. SEE FLOOR PLANS FOR SIZE AND ROUTING.

45° RECTANGULAR TO ROUND DUCT TAKE-OFF EQUAL TO CROWN PRODUCTS COMPANY MODEL 3300-DS2. TAKE-OFF SHALL HAVE A CONTINUOUS ROD DAMPER WITH A 2" STAND-OFF FOR INSULATION.

NOTE:A MINIMUM 12" OF SHEET METAL DUCT SHALL BE INSTALLED ON TAKE-OFF WHERE SHORT RUNS (5' OR LESS) OF FLEX DUCT IS USED TO MAKE GRILLE / DIFFUSER CONNECTION.

BRANCH DUCT OPENING SHALL BE CUT FULL SIZE OF RECTANGULAR OPENING OF TAKE-OFF.

INSULATED FLEX DUCT

2" FG BLANKET TO COVER ENTIRE 2' X 2' TILE.

RIGID ADJUSTABLE ELBOW FORMED AT 45° AND DUCT SEALED.

STICK-ON TAP WITHOUT A DAMPER.

GRILLE, REGISTER,OR DIFFUSER

2" X 2" 24 GAUGE METAL ANGLE TO SPAN ENTIRE 2' X 2' TILE. ANGLE TO BE SECURED TO SQUARE TO ROUND ADAPTER WITH 1/4" SELF TAPPING SHEET METAL SCREWS.

ACOUSTICAL CEILING TILE

NOTE:FOIL TAPE ALL INSULATION SEAMS TO PROVIDE A VAPOR BARRIER. AIR TERMINAL SHALL BE FASTENED TO STRUCTURE ABOVE WITH METAL CABLING AND FASTENERS VIA EARTHQUAKE TABS ON AIR TERMINAL.

26 GAUGE SHEET METAL PLENUM. PLENUM SHALL BE EQUAL TO FLEXMASTER SISB. PLENUM SHALL BE SEALED WITH SPECIFIED SEALANT. PLENUM SHALL BE FULL SIZE OF GRILLE OPENING. PLENUM SHALL BE FULLY INSULATED WITH FOIL FACED WRAP. LINER WILL NOT BE ALLOWED.

2X2 A.C.T. SURFACE MOUNTED

GRILLE / REGISTER / DIFFUSER DETAILNOT TO SCALE

PROVIDE 5' OF INSULATED FLEX DUCT FOR NOISE CONTROL

RIGID ADJUSTABLE ELBOW FORMED AT 45° AND DUCT SEALED.

STICK-ON TAP WITH LOCKABLE QUADRANT DAMPER.

RETURN GRILLE

2" X 2" 24 GAUGE METAL ANGLE TO SPAN ENTIRE 2' X 2' TILE. ANGLE TO BE SECURED TO SQUARE TO ROUND ADAPTER WITH 1/4" SELF TAPPING SHEET METAL SCREWS.

ACOUSTICAL CEILING TILE

26 GAUGE SHEET METAL PLENUM. PLENUM SHALL BE EQUAL TO FLEXMASTER SISB. PLENUM SHALL BE SEALED WITH SPECIFIED SEALANT. PLENUM SHALL BE FULL SIZE OF GRILLE OPENING. PLENUM SHALL BE INTERNALLY INSULATED WITH ARMAFLEX DUCT LINER.

2X2 A.C.T. SURFACE MOUNTED

PLENUM RETURN GRILLE DETAILNOT TO SCALE

NOTE:FOIL TAPE ALL INSULATION SEAMS TO PROVIDE A VAPOR BARRIER. AIR TERMINAL SHALL BE FASTENED TO STRUCTURE ABOVE WITH METAL CABLING AND FASTENERS VIA EARTHQUAKE TABS ON AIR TERMINAL.

mdsMechanical Design Services, Inc.

100 Church St. SW, Suite 650, Huntsville, AL 35801

(256) 534-5150 [email protected]

INSULATED FLEX DUCT

2" FG BLANKET TO COVER ENTIRE 2' X 2' TILE.

RIGID ADJUSTABLE ELBOW FORMED AT 45° AND DUCT SEALED.

STICK-ON TAP WITHOUT A DAMPER.

GRILLE, REGISTER, OR DIFFUSER

NOTE:FOIL TAPE ALL INSULATION SEAMS TO PROVIDE A VAPOR BARRIER. AIR TERMINAL SHALL BE FASTENED TO STRUCTURE ABOVE WITH METAL CABLING AND FASTENERS VIA EARTHQUAKE TABS ON AIR TERMINAL.

26 GAUGE SHEET METAL PLENUM. PLENUM SHALL BE EQUAL TO FLEXMASTER SISB. PLENUM SHALL BE SEALED WITH SPECIFIED SEALANT. PLENUM SHALL BE FULL SIZE OF GRILLE OPENING. PLENUM SHALL BE FULLY INSULATED WITH FOIL FACED WRAP. LINER WILL NOT BE ALLOWED.

ACOUSTICAL CEILING LAY-IN

GRILLE / REGISTER / DIFFUSER DETAILNOT TO SCALE

SEQUENCE OF CONTOL

EXISTING AC 2-1:CYBER SECURITY LAB:THE EXISTING PNEUMATIC CONTROLS SYSTEM AND TUBING TO BE REWORKED TO SATISFY THE INTENT OF THIS SEQUENCE OF CONTROL. THE PNEUMATIC THERMOSTATS SHALL BE DEMOED WITH CARE AND REINSTALLED WHERE SHOWN ON THE DRAWINGS. THERMOSTATS NOT REQUIRED FOR REUSE SHALL BE TURNED OVER TO THE OWNER. AC 2-1 FOR ZONE DAMPERS FOR ZONES F, H & J ARE TO BE CONTROLLED BY A SINGLE PNEUMATIC THERMOSTAT (REUSED THERMOSTAT FROM DEMO). THE DAMPERS ARE TO CONTROL (OPEN / CLOSE) TOGETHER WITH THE SINGLE AIR PRESSURE CONTROL FROM THE SINGLE THERMOSTAT. CONTRACTOR TO REWORK THE PNEUMATIC TUBING AT THE AC 2-1 AND ADD NECESSARY PNEUMATIC CONTROLLERS AND PNEUMATIC RELAYS TO CONTROL THE AIR DAMPERS FROM A SINGLE PNEUMATIC THERMOSTAT FOR CYBER SECURITY LAB.

THE EXISTING AIR HANDLER OUTSIDE AIR AND SUPPLY AIR FLOW RATES ARE TO BE TESTED PRIOR TO DEMOLITION WORK BEGINS TO ESTABLISH A BASELINE. THE OUTSIDE VENTILATION AND SUPPLY AIR RATES SHALL BE RECORDED. ORIGINAL DESIGN OF AC 2-1 OUTSIDE AIR IS 1,600 CFM WITH A SUPPLY AIR RATE OF 11,800 CFM. THE RENOVATED AREA COMPRISED OF CLASSROOM SPACES WITH MORE OF AN OCCUPANCY LOAD THAN THE RENOVATED AREA.

LAB SUPPORT (SERVER ROOM):IU-217 IS TO BE CONTROLLED VIA A LOCAL THERMOSTAT. PROVIDE ANY NECESSARY RELAYS, TRANSFORMERS, CHILLED WATER ACTUATED CONTROL VALVES (2 POSITION ON/OFF CONTROL), ETC. THE WALL HARD WIRED THERMOSTAT SHALL ENABLE THE FAN AND CONTROL THE CHILLED WATER VALVE TO MAINTAIN THE SPACE COOLING SETPOINT. THE WALL HARD WIRED THERMOSTAT SHALL ENABLE THE FAN AND STAGE THE ELECTRIC HEAT TO MAINTAIN THE SPACE HEATING SET POINT.

THE CYBER SECURITY LAB AND LAB SUPPORT CONSIST OF A COMPUTER LAB AND SERVER ROOM ONLY AND DOES NOT REQUIRE GENERAL EXHAUST PER 2015 IMC TABLE 403.3.1.1.

CYBER LOUNGE SHALL BE CONTROLLED BY A REUSED PNEUMATIC THERMOSTAT. REWORK AND PROVIDE PNEUMATIC TUBING AS NEEDED FOR THE RELOCATION OF THE THERMOSTAT SHOWN ON THE NEW WORK DRAWINGS.

A

LA B A M

A

JO

H

NN

YN . E C

H

OL

S

JO

H

NN

YN . E C

H

OL

S

ENG I NE ER

L ICENSED

No. 30043

PROFESSIONAL

MEMBER OF THE AMERICAN

INSTITUTE OF ARCHITECTS

This document is a copyright protected instrument of service and

licnesed for use in the titled project only. This drawing may not be reproduced in whole or in part without written permission of

FUQUA & PARTNERS ARCHITECTS, P.C.A Professional Corporation

DATE:

ISSUE:

DRAWN:

PROJECT NO:

SHEET

OF

Architecture

Interior Design

Media Visualization

Master Planning

100 Church Street, Suite 700Huntsville, Alabama 35801

PH: (256) 534.3516FX: (256) 533.4605

www.fuquaarchitects.com

CHECKED:

2/2

5/2

020 4

:46:1

8 P

M

M3.0

ME

CH

AN

ICA

L S

CH

ED

ULE

S

301

SP

AR

KM

AN

DR

IVE

, HU

NT

SV

ILLE

AL.

358

99

JJP

02-25-2020

FPA #07519

JNE

COORDINATION

UA

H B

AB

CY

BE

R L

AB

/ IN

TE

RIO

R R

EN

OV

AT

ION

REVISIONS

Page 20: 100 Church Street, Suite 700 Huntsville, Alabama 35801 PH ...

mdsMechanical Design Services, Inc.

100 Church St. SW, Suite 650, Huntsville, AL 35801

(256) 534-5150 [email protected]

GRAPHIC SCALE: 1/8" = 1'-0"

0 4' 8' 16' 24' 32'2' 6' 12'

E E

D D

C C

B B

A A

8

8

9

9

7

7

UP TO 2ND FLOOR

VALVE WITH HOSE BIBB DRAIN PORT.

EXISTING EWC TO REMAIN.

1/2"ø

3"ø

CW

3"ø3/4"ø CW

1/2"ø CW

3"ø CW

3"ø W

BELOW GRADE WASTE TO REMAIN.

EXISTING

CORRIDOR

125

EXISTING

AUDITORIUM

26

EXISTING

CORRIDOR

125EXISTING CASE

ROOM #5

124

Room

136

Room

135

EXISTING OFFICE

134

EXISTING OFFICE

132

EXISTING OFFICE

133

EXISTING OFFICE

127

EXISTING OFFICE

129

EXISTING OFFICE

130

EXISTING OFFICE

131

EXISTING

MECHANICAL

142

REMOVE EXISTING WASTE AND WATER PIPING TO THE EXTENT SHOWN AND REWORK AS SHOWN ON NEW DRAWING(S).

E E

D D

C C

B B

A A

8

8

9

9

7

7

CW & WASTE ABOVE CEILING. PIPING UP TO 3RD FLOOR TO REMAIN AND BE RECONNECTED TO NEW AS SHOWN ON NEW DRAWING(S).

EXISTING EWC. TO BE REMOVED

UP FROM 1ST FLOOR

3"ø

1/2"ø CW

3"ø C

W

3"ø W

3"ø C

W

1/2

"ø3"ø

1/2"ø C

W

3"ø

3/4"ø CW

3"ø

1/2"ø

EXISTING EWC TO REMAIN

EXISTING EWC TO REMAIN

EXISTING EWC TO BE REMOVED

EXISTING 3" VTR

REMOVE EXISTING WASTE AND WATER PIPING TO THE EXTENT SHOWN AND REWORK AS SHOWN ON NEW DRAWINGS.

A

LA B A M

A

JO

H

NN

YN . E C

H

OL

S

JO

H

NN

YN . E C

H

OL

S

ENG I NE ER

L ICENSED

No. 30043

PROFESSIONAL

MEMBER OF THE AMERICAN

INSTITUTE OF ARCHITECTS

This document is a copyright protected instrument of service and

licnesed for use in the titled project only. This drawing may not be reproduced in whole or in part without written permission of

FUQUA & PARTNERS ARCHITECTS, P.C.A Professional Corporation

DATE:

ISSUE:

DRAWN:

PROJECT NO:

SHEET

OF

Architecture

Interior Design

Media Visualization

Master Planning

100 Church Street, Suite 700Huntsville, Alabama 35801

PH: (256) 534.3516FX: (256) 533.4605

www.fuquaarchitects.com

CHECKED:

2/2

5/2

020 4

:46:2

0 P

M

P1.0

PLU

MB

ING

FLO

OR

PLA

N -

DE

MO

LIT

ION

301

SP

AR

KM

AN

DR

IVE

, HU

NT

SV

ILLE

AL.

358

99

JJP

02-25-2020

FPA #07519

JNE

COORDINATION

UA

H B

AB

CY

BE

R L

AB

/ IN

TE

RIO

R R

EN

OV

AT

ION

1/8" = 1'-0"

DEMOLITION PLUMBING - 1ST FLOOR1/8" = 1'-0"

DEMOLITION PLUMBING - 2ND FLOORRISER DIAGRAM - DEMOLITION

REVISIONS

Page 21: 100 Church Street, Suite 700 Huntsville, Alabama 35801 PH ...

E E

D D

C C

B B

A A

8

8

9

9

7

7

EXISTING VALVE WITH HOSE BIBB DRAIN PORT.

EXISTING EWC TO REMAIN.

3"ø W

3"ø

CW

1/2"ø CW

UP TO 2ND FLOOR

3"ø W

ABOVE CEILING

BELOW GRADE

3"ø CW

CONNECT TO EXISTING CW & WASTE ABOVE CEILING.

E E

D D

C C

B B

A A

8

8

9

9

7

7

CYBERSECURITY

LAB

219

CYBER LOUNGE

218

EX

IST

. C

OR

RID

OR

211EXIST.

CLASSROOM

232CEXIST.

CLASSROOM

220

EXIST.

CLASSROOM

224

EXIST.

CLASSROOM

222

EXISTING

MECHANICAL

223

STAIRS

219

LAB SUPPORT

217

1/2" CW & 3" WASTE ABOVE CEILING.

CONNECT TO EXISTING CW & WASTE ABOVE 2ND FLOOR CEILING.

CW & WASTE UP FROM 1ST FLOOR. P-1

IU-217

GRAPHIC SCALE: 1/8" = 1'-0"

0 4' 8' 16' 24' 32'2' 6' 12'

mdsMechanical Design Services, Inc.

100 Church St. SW, Suite 650, Huntsville, AL 35801

(256) 534-5150 [email protected]

3"ø C

W

3"ø C

W

3"ø W

1/2"ø CW

3"ø W

3"ø W

3/4"ø CW

EXISTING EWC TO REMAIN

EXISTING EWC TO REMAIN

P-1

EXISTING VAVLE WITH HOSE BIBB DRAIN PORT.

EXISTING 3" VTR

CONNECT TO EXISTING.

CONNECT TO EXISTING.

1/2"ø CW

PLUMBING FIXTURE CONNECTION SCHEDULE

FIXTURE TAG

TYPE OF FIXTURECONNECTION SIZES

WASTE CW HW HWR

P-1 ELECTRIC WATER COOLER 1-1/2" 1/2"

NOTES:

1. COORDINATE MOUNTING HEIGHT OF ALL WALL MOUNTED FIXTURES WITH THE ARCHITECTURAL DRAWINGS.

A

LA B A M

A

JO

H

NN

YN . E C

H

OL

S

JO

H

NN

YN . E C

H

OL

S

ENG I NE ER

L ICENSED

No. 30043

PROFESSIONAL

MEMBER OF THE AMERICAN

INSTITUTE OF ARCHITECTS

This document is a copyright protected instrument of service and

licnesed for use in the titled project only. This drawing may not be reproduced in whole or in part without written permission of

FUQUA & PARTNERS ARCHITECTS, P.C.A Professional Corporation

DATE:

ISSUE:

DRAWN:

PROJECT NO:

SHEET

OF

Architecture

Interior Design

Media Visualization

Master Planning

100 Church Street, Suite 700Huntsville, Alabama 35801

PH: (256) 534.3516FX: (256) 533.4605

www.fuquaarchitects.com

CHECKED:

2/2

5/2

020 4

:46:2

3 P

M

P2.0

PLU

MB

ING

FLO

OR

PLA

N -

NE

W C

ON

ST

RU

CT

ION

301

SP

AR

KM

AN

DR

IVE

, HU

NT

SV

ILLE

AL.

358

99

Author

02-25-2020

FPA #07519

Checker

COORDINATION

UA

H B

AB

CY

BE

R L

AB

/ IN

TE

RIO

R R

EN

OV

AT

ION

1/8" = 1'-0"

PLUMBING - 1ST FLOOR1/8" = 1'-0"

PLUMBING - 2ND FLOORRISER DIAGRAM- NEW CONSTRUCTION

REVISIONS

Page 22: 100 Church Street, Suite 700 Huntsville, Alabama 35801 PH ...

ABBREVIATION SYMBOLS SCHEDULE

GROUNDING SYMBOLS SCHEDULE

POWER SYMBOLS SCHEDULE

MANUAL MOTOR STARTER/DISCONNECT SWITCH WITH THERMAL OVERLOAD PROTECTION

DUPLEX RECEPTACLE - NEMA 5-20R WITH ISOLATED GROUND, HORIZONTAL LINE INDICATES MOUNTED AFC UON, SHADING INDICATES CIRCUITED TO GENERATOR/UPS POWER

SIMPLEX RECEPTACLE - NEMA 5-20R, HORIZONTAL LINE INDICATES MOUNTED AFC UON, SHADING INDICATES CIRCUITED TO GENERATOR/UPS POWER

DISTRIBUTION PANEL

BRANCH CIRCUIT PANELBOARD

ENCLOSED DISCONNECT SWITCH, SHADING INDICATES SWITCH IS FUSIBLE

COMBINATION MAGNETIC MOTOR CONTROLLER/STARTER, SHADING INDICATES STARTER IS FUSIBLE

ENCLOSED CIRCUIT BREAKER

TRANSFORMER

CONTROL PANEL/CONTROL POWER PANEL (FURNISHED BY OTHERS)

JUNCTION BOX, LEG INDICATES WALL MOUNTING IS REQUIRED, SQUARE INDICATES FLOOR MOUNTED

MOTOR

PUSHBUTTON STATION

CONDUIT TURNING UP

CONDUIT TURNING DOWN

INDICATES CIRCUITS TO PANEL, 'RP1' INDICATES PANEL DESIGNATION AND '1,3,5' INDICATED POLE POSITION(S)

RP1-1,3,5

'X' INDICATES QUANTITY AND 'Y' INDICATES SIZE OF CONDUCTORS, Z INDICATES CONDUIT SIZEX#Y, X#YG.,Z"C.

ABOVE FINISHED FLOORAFF

ABOVE FINISHED GRADEAFG

ELECTRICAL CONTRACTOREC

ELECTRIC WATER COOLEREWC

GROUND FAULT INTERRUPTERGFI

NATIONAL ELECTRICAL CODENEC

NOT IN CONTRACTNIC

NIGHT LIGHT - FIXTURE CONTROLLED AT BRANCH CIRCUIT BREAKERNL

NOT TO SCALENTS

WEATHERPROOF WHILE IN USE COVER/ENCLOSURE, NEMA 3R UONWP

TRANSFORMERXFMR

CADWELD CONNECTION BETWEEN GROUND CABLE AND BUILDING COLUMN

CADWELD CABLE TO CABLE 'X' CONNECTION

CADWELD CABLE TO CABLE 'T' CONNECTION

COPPERWELD TYPE GROUND ELECTRODE WITH CADWELD CONNECTION

BARE COPPER GROUND CABLE. INSTALL MINIMUM 30" BELOW FINISHED FLOOR OR GRADE

LUG CONNECTION BETWEEN BUS BAR AND CABLE

CADWELD CONNECTION BETWEEN REBAR OR ROD AND CABLE

BARE COPPER GROUND CABLE

TECHNOLOGY SYSMBOLS SCHEDULE

CPT CONTROL POWER TRANSFORMER

EPO EMERGENCY POWER OFF

RELOCATED(R)

(NOT ALLSYMBOLS USED)

(NOT ALLSYMBOLS USED)

(NOT ALLSYMBOLS USED)

(NOT ALLSYMBOLS USED)

CP

J

T

GROUND ELECTRODE TEST WELLTW

SPLIT-WIRED DUPLEX RECEPTACLE - NEMA 5-20R, HORIZONTAL LINE INDICATES MOUNTED AFC UON, SHADING INDICATES CIRCUITED TO GENERATOR/UPS POWER

ABOVE FINISHED CABINET/COUNTERAFC

LIGHTING SYMBOLS SCHEDULE

BATTERY POWERED EMERGENCY LIGHTING UNIT, LIGHT HEADS ON SIDES OF UNIT INDICATES CEILING MOUNTED

SURFACE OR PENDANT LIGHT FIXTURE, CHEVRON INDICATED WALL WASH AIMING, SHADING INDICATES EMERGENCY EGRESS LIGHT FIXTURE

(NOT ALLSYMBOLS USED)

RECESSED LIGHT FIXTURE, CHEVRON INDICATED WALL WASH AIMING, HALF-SHADING INDICATES EMERGENCY EGRESS LIGHT FIXTURE

SURFACE OR PENDANT LIGHT FIXTURE, HALF-SHADING INDICATES EMERGENCY EGRESS LIGHT FIXTURE

RECESSED LIGHT FIXTURE, HALF-SHADING INDICATES EMERGENCY EGRESS LIGHT FIXTURE

XXX LIGHT FIXTURE TYPE, REFER TO LUMINAIRE SCHEDULE

SURFACE OR CHAIN HUNG STRIP LIGHT FIXTURE, HALF-SHADING INDICATES EMERGENCY EGRESS LIGHT FIXTURE

RECESSED ARCHITECTURAL LIGHT FIXTURE, HALF-SHADING INDICATES EMERGENCY EGRESS LIGHT FIXTURE

WALL MOUNTED LIGHT FIXTURE, HALF-SHADING INDICATES EMERGENCY EGRESS LIGHT FIXTURE

WALL MOUNTED LIGHT FIXTURE, HALF-SHADING INDICATES EMERGENCY EGRESS LIGHT FIXTURE

EXIT SIGN, PROVIDE ARROWS/CHEVRONS AS INDICATED ON PLANS, SHADED AREA INDICATES FACE, FOOT ON SYMBOL INDICATES WALL MOUNTED, LIGHT HEADS INDICATE COMBINATION EXIT/BATTERY POWERED EMERGENCY LIGHTING UNIT

TRACK MOUNTED LIGHT FIXTURE

XaSINGLE POLE SWITCH - 20A, 125/277V UON,

-'a' INDICATES WHICH FIXTURES/DEVICES ARE CONTROLLED VIA SWITCH-'X' DENOTES TYPE:

BLANK - SINGLE POLE2 - DOUBLE POLE3 - THREE WAY4 - FOUR WAYD - DIMMERK - KEY OPERATEDI - ILLUMINATED (ILLUMINATED IN 'OFF' POSITION)P - WITH PILOT LIGHT (LIGHT ON IN 'ON' POSITION)T - TIME SWITCHL - LOW VOLTAGEC - MOMENTARY CONTACTO - WALL BOX OCCUPANCY SENSOR - PASSIVE INFRAREDV - WALL BOX VACANCY SENSOR - PASSIVE INFRARED

OCCUPANCY/VACANCY SENSOR, FOOT ON SYMBOL INDICATES WALL MOUNTED, -'a' INDICATES WHICH FIXTURES ARE CONTROLLED VIA SENSOR-'X' DENOTES TYPE:

A - 180° DUAL TECHNOLOGY OCCUPANCY SENSORB - 360° DUAL TECHNOLOGY OCCUPANCY SENSORC - 180° PASSIVE INFRARED OCCUPANCY SENSORD - 360° ULTRASONIC OCCUPANCY SENSOR

VSXa

OSXa

VSXa

OSXa

DSa

DSa

DAYLIGHT SENSOR, FOOT ON SYMBOL INDICATES WALL MOUNTED, -'a' INDICATES WHICH FIXTURES ARE CONTROLLED VIA SENSOR

LIGHTING CONTACTOR, SIZE AS INDICATED ON DRAWINGS/DETAILC

M

DUPLEX RECEPTACLE - NEMA 5-20R, HORIZONTAL LINE INDICATES MOUNTED AFC UON, SHADING INDICATES CIRCUITED TO GENERATOR/UPS POWER

QUADPLEX RECEPTACLE - NEMA 5-20R, HORIZONTAL LINE INDICATES MOUNTED AFC UON, SHADING INDICATES CIRCUITED TO GENERATOR/UPS POWER (ALL OTHER NEMA 5-20R QUAD RECEPTACLE SYMBOLS FOLLOW SAME STACKED DUPLEX PATTERN)

SPECIAL RECEPTACLE-'X' DENOTES TYPE:

A - (NEMA L5-30R) 125V, 30A, SINGLE PHASE, TWIST-LOCK RECEPTACLE 2 POLE, 3 WIRE B - (NEMA 6-20R) 250V, 20A, SINGLE PHASE RECEPTACLE 2 POLE, 3 WIRE C - (NEMA 6-30R) 250V, 30A, SINGLE PHASE RECEPTACLE, 2 POLE, 3 WIRE D - (NEMA L6-20R) 250V, 20A, SINGLE PHASE, TWIST-LOCK RECEPTACLE 2 POLE, 3 WIRE E - (NEMA L15-30R) 250V, 30A, THREE PHASE, TWIST-LOCK RECEPTACLE, 3 POLE, 4 WIRE F - (NEMA L21-30R) 208Y/120V, 30A, THREE PHASE, TWIST-LOCK RECEPTACLE 4 POLE, 5 WIRE G - (NEMA 14-30R) 125/ 250V SINGLE PHASE RECEPTACLE 3 POLE, 4 WIRE H - (NEMA 6-50R) 250V SINGLE PHASE RECEPTACLE 2 POLE, 3 WIRE I - (NEMA 14-50R) 250V

SINGLE POINT ELECTRICAL CONNECTION

DUPLEX RECEPTACLE - NEMA 5-20R, GROUND FAULT INTERRUPTING, HORIZONTAL LINE INDICATES MOUNTED AFC UON, SHADING INDICATES CIRCUITED TO GENERATOR/UPS POWER

COMBINATION DUPLEX RECEPTACLE (NEMA 5-20R)/USB (TYPE A, 2.0 ), TWO CHARGING USB PORTS, HORIZONTAL LINE INDICATES MOUNTED AFC UON, SHADING INDICATES CIRCUITED TO GENERATOR/UPS POWER

X

X

CEILING MOUNTED SIMPLEX RECEPTACLE - NEMA 5-20R, SHADING INDICATES CIRCUITED TO GENERATOR/UPS POWER

CEILING MOUNTED DUPLEX RECEPTACLE - NEMA 5-20R, SHADING INDICATES CIRCUITED TO GENERATOR/UPS POWER

CEILING MOUNTED SPECIAL RECEPTACLE-'X' DENOTES TYPE:

REFER TO WALL MOUNTED SPECIAL RECEPTACLE TYPES ABOVE

CB

J

MAGNETIC MOTOR CONTROLLER

J

VARIABLE FREQUENCY DRIVE (FURNISHED BY OTHERS)VFD

AUTOMATIC TRANSFER SWITCHATS

MANUAL TRANSFER SWITCHMTS

M UTILITY METER

FLOOR BOX, 'X' INDICATES TYPE, REFER TO FLOOR BOX SCHEDULEFBX

PTX POKE THRU, 'X' INDICATES TYPE, REFER TO FLOOR BOX SCHEDULE

MOTOR CONTROL CENTER

MULTI-OUTLET SURFACE RACEWAY

UNLESS OTHERWISE NOTEDUON, UNO

(RR) REMOVE AND RELOCATE

EXISTING TO REMAIN(E)

POWER SUPPLYPS

GENERATOR ANNUNCIATORGA

BUILDING MANAGEMENT SYSTEM PANEL (FURNISHED BY OTHERS)BMS

FIRE ALARM CONTROL PANEL (FURNISHED BY OTHERS)FACP

FAA FIRE ALARM ANNUNCIATOR (FURNISHED BY OTHERS)

FIRE ALARM NOTIFICATION APPLIANCE CIRCUIT PANEL (FURNISHED BY OTHERS) FNAC

ELECTRICALLY OPERATEDEO

AMP FRAME - CIRCUIT BREAKER; AMP FUSE - FUSED SWITCHAF

AMPERESA, AMP

AMPERES TRIPAT

AMPERE INTERRUPTING CAPACITYAIC

AUTOMATIC TRANSFER SWITCHATS

CONDUITC

CURRENT TRANSFORMERCT

EMERGENCYEM

FULL LOAD AMPERESFLA

GROUNDG, GND

HAND-OFF-AUTOHOA

HORSEPOWERHP

KILOVOLTKV

KILOVOLT-AMPERESKVA

KILOWATTKW

KILOWATT-HOURSKWH

MAIN CIRCUIT BREAKERMCB

MECHANICAL CENTRAL POWERMCP

MAIN LUGS ONLYMLO

NEUTRALN

NORMALLY CLOSEDNC

NORMALLY OPENNO

ON CENTEROC

POLEP

PHASEPH

POTENTIAL TRANSFORMERPT

RECEPTACLERECEPT

LIGHTSLTS

DISHWASHERDW

MICROWAVEMW

REF REFRIGERATOR

GARBAGE DISPOSALGD

TR TAMPER-RESISTANT

TYP TYPICAL OF LIKE DEVICES IN SAME AREA

VOLTSV

WIREW

EXPLOSION PROOFXP, EP

ALUMINUMAL

COPPERCU

EXISTING, REMOVE AND REPLACE WITH NEW IN SAME LOCATION(XRP)

DRAWING CONVENTIONS

NEW WORK

EXISTING TO REMAIN(E)

EXISTING TO REMOVE (DEMOLISHED)

HATCHED EXISTING TO REMOVE (DEMOLISHED)

UNINTERUPTABLE POWER SUPPLYUPS

COFFEE MAKER/MACHINECM

HORIZONTAL/HORIZONTALLY MOUNTEDH

ARC FAULT INTERRUPTERAFI

CRITICAL / CRITICAL BRANCH EMERGENCYCR

ELTD , GTD EMERGENCY LOAD/GENERATOR TRANSFER DEVICE

EDIT ITEMS IN () TO SUIT PROJECT

RP1 PANEL TAG, i.e. CIRCUITS WITHIN AREA WHERE TAG IS LOCATED ON PLAN ARE CIRCUITED TO PANEL 'RP1' UON

EQUIPMENT GROUNDEG

TIME CLOCKTC

LS LIFE SAFETY BRANCH EMERGENCY

EQUIPMENT BRANCH EMERGENCYEQ

ICE MACHINEIM

LIGHTING CONTROL POINTCP

J

1'-6"

4'-0"

6'-6"

NOTES:

1.

2.

3.

4.

MOUNTING HEIGHTS SHOWN ARE FROM FINISHED FLOOR TO CENTERLINE OF DEVICE/OUTLET/FIXTURE, UNLESS OTHERWISE NOTED.

MOUNTING HEIGHTS, WHERE INDICATED, ON FLOOR PLANS, SHALL TAKE PRECEDENCE OVER THESE MOUNTING HEIGHTS. LOCATIONS OF OUTLETS SHOWN ON ARCHITECTURAL ELEVATIONS SHALL TAKE PRECEDENCE OVER THESE MOUNTING HEIGHTS. FIELD LOCATE OUTLETS WITH ARCHITECT DURING ROUGH-IN.

INSTALL OUTLETS THAT ARE IN CLOSE PROXIMITY ON THE SAME CENTERLINE. OUTLETS THAT ARE WITHIN 2'-0" HORIZONTALLY AND WITHIN 1'-0" VERTICALLY SHALL BE INSTALLED ON THE SAME HORIZONTAL CENTERLINE LOCATED HALF WAY BETWEEN THE HEIGHTS SHOWN. OUTLETS THAT ARE MORE THAN 1'-0" APART VERTICALLY SHALL BE INSTALLED ON THE SAME VERTICAL CENTERLINE.

MAXIMUM MOUNTING HEIGHT FOR SWITCHES ABOVE A COUNTER TOP 20" DEEP OR LESS IS 48" AFF TO TOP OF BOX. SWITCHES MOUNTED ABOVE COUNTER TOPS DEEPER THAN 20" SHALL BE INSTALLED AT NO MORE THAN 44" AFF FLOOR TO TOP OF BOX. NOTIFY ARCHITECT WHERE COUNTERTOP PROHIBITS SWITCH INSTALLTION.

STANDARD MOUNTING HEIGHTS

S

6" ABOVECOUNTERWITHOUTBACKSPLASH

4" ABOVEBACKSPLASH

FINISHED FLOOR

W

F

4'-6"

6'-8"

THIS DIMENSION TO TOP OF BOX

FLOOR BOX S C H E D U L E

FB1

DEVICE DESCRIPTION

NOT USED

FB2RECESSED FLUSH-IN-FLOOR POKE-THRU 8 INCH BOX WITH (2) 20-A DUPLEX OUTLETS AND (8) RJ45 JACKS FOR DATA, 5 GANG CAPACITY (1 SPARE) WITH 2 HOUR FIRE RATING. LEGRAND #8CTC2BS.

PLENUM RATED STP CAT6 (475mHz 10G MIN.) TERMINATE T568B, CABLE QUANTITY IDENTIFIED

CAT-6 CABLE, QUANTITY IDENTIFIED

COMBINED DATA OUTLET, FLOOR BOX

2-PORT PLENUM RATED STP CAT6 (475mHz 10G MIN.) TERMINATE T568BTV

WIRELESS ACCESS POINT, CEILING MOUNTED (2) CAT-6AWAP

DATA OUTLET, FLOOR BOX

TELECOMMUNICATIONS BACKBOARD (FIRE RATED)

PRIMARY BONDING BUSBAR-PANDUIT GB2B0306TPI-1PBB

FIRE ALARM HORN WITH STROBE, CEILING MOUNTED

FIRE ALARM STROBE, MH=6'-8" AFF UNO

VIDEO SURVEILLANCE SYSTEM FIXED VIEW, CEILING MOUNTED

CARD READER, MH=4'-0" AFF UNOCR

F

AOM FIRE ALARM ADDRESSABLE OUTPUT MODULE

J JUNCTION BOX

PUBLIC ADDRESS SPEAKER, CEILING MOUNTEDS

303 Williams Ave. SW, Suite 1211Huntsville, AL 35801T. (256) 534-2353

SSOE, Inc.®

MEMBER OF THE AMERICAN

INSTITUTE OF ARCHITECTS

This document is a copyright protected instrument of service and

licnesed for use in the titled project only. This drawing may not be reproduced in whole or in part without written permission of

FUQUA & PARTNERS ARCHITECTS, P.C.A Professional Corporation

DATE:

ISSUE:

DRAWN:

PROJECT NO:

SHEET

OF

Architecture

Interior Design

Media Visualization

Master Planning

100 Church Street, Suite 700Huntsville, Alabama 35801

PH: (256) 534.3516FX: (256) 533.4605

www.fuquaarchitects.com

CHECKED:

2/2

1/2

020 5

:17:4

1 P

M

E0.1

ELE

CT

RIC

AL

LEG

EN

D, S

YM

BO

LS, &

NO

TE

S

301

SP

AR

KM

AN

DR

IVE

, HU

NT

SV

ILLE

, AL

3589

9

C.SHELTON

2020-02-25

FPA#07519

A.YORK

CONSTRUCTION SET

UA

H B

AB

CY

BE

R L

AB

/ IN

TE

RIO

R R

EN

OV

AT

ION

SSOE #020-00457-00

REVISIONS

Page 23: 100 Church Street, Suite 700 Huntsville, Alabama 35801 PH ...

NOTES ON WIRINGQS CONTROL LINKTHE QS CONTROL LINK HAS A FREE WIRING TOPOLOGY (DAISY CHAIN, T-TAP, ETC). THE SYSTEM WIRING

ILLUSTRATED BY THIS DRAWING HAS BEEN LAID OUT TO ENSURE APPROPRIATE POWER TO EACH DEVICE. IF FOR

ANY REASON THE SYSTEM IS TO BE WIRED DIFFERENTLY THAN WHAT IS SHOWN, PLEASE CONFIRM ALL DEVICE

POWER REQUIREMENTS ARE MET (PLEASE REFER TO “QS LINK POWER REQUIREMENTS” FOR INDIVIDUAL DEVICE

POWER REQUIREMENTS).

FOR QS CONTROL WIRE LENGTHS TOTALING LESS THAN 500 FT (153 M), USE LUTRON CABLE GRX-CBL-346S (4

CONDUCTOR NON-PLENUM), OR GRX-PCBL-346S (4 CONDUCTOR PLENUM). OTHERWISE USE 2 #18 AWG (1.0 SQ MM) +

2 #22 AWG (0.5 SQ MM) TWISTED AND SHIELDED OR EQUIVALENT (BELDEN #9461). FOR QS CONTROL WIRE LENGTHS

TOTALING UP TO 2,000 FT, USE GRX-CBL-46L (4 CONDUCTOR NON-PLENUM) OR GRX-PCBL-46L (4 CONDUCTOR

PLENUM). TOTAL QS CONTROL WIRE LENGTH MUST NOT EXCEED 2,000 FT (600 M).

QS LINK POWER REQUIREMENTS

DEVICE PDUS

QS DEVICES THAT SUPPLY PDU

DIN RAIL POWER SUPPLY +75

MYROOM DIN RAIL POWER SUPPLY +30

QS PLUG-IN POWER SUPPLY, QS J-BOX POWER SUPPLY +8

ENERGI SAVR NODE WITH ECOSYSTEM, ENERGI SAVR NODE WITHDALI, ENERGI SAVR NODE WITH T-SERIES TUNABLE-WHITE

+30

ENERGI SAVR NODE FOR 0–10 V, ENERGI SAVR NODE WITHSOFTSWITCH, ENERGI SAVR NODE FOR 0–10 V (DIN RAIL), ENERGISAVR NODE WITH SOFTSWITCH (DIN RAIL)

+14

ENERGI SAVR NODE PHASE ADAPTIVE (DIN RAIL), 1 A MYROOM DINRAIL POWER MODULE SWITCHING, 1 A MYROOM DIN RAIL POWERMODULE PHASE ADAPTIVE

+4

ENERGI SAVR NODE WITH DALI (DIN RAIL), ENERGI SAVR NODE WITHECOSYSTEM (DIN RAIL)

+3

QS MOTOR GROUP CONTROLLER (DIN RAIL), HOMEWORKS QS DINRAIL POWER MODULES

0

GRAFIK EYE QS (ALL MODELS EXCEPT GRAFIK EYE QS DALI WITHKNX), QS TIMECLOCK

+3

QP2 QUANTUM LIGHTING HUBLINK A : 0LINKS B,C,D : +33 EACH

QP3 QUANTUM LIGHTING HUB LINKS A,B : +33 EACH

QS DEVICES THAT CONSUME PDU

QS WALLSTATION (SEETOUCH, ARCHITRAVE, SIGNATURE SERIES, QSPICO, KEYSWITCH, SINGLE COLUMN PALLADIOM), QS SLIDER, GRAFIKT SLIDER, QS INFRARED (IR) EYE, WALLBOX INPUT CLOSUREINTERFACE

-1

QS NETWORK INTERFACE, QS DMX INTERFACE, ENERGI SAVR NODEPROGRAMMING INTERFACE, QS WALLSTATION (DOUBLE COLUMNPALLADIOM)

-2

QS SENSOR MODULE (QSM), NOT INCLUDING ATTACHED WIREDSENSORS (SEE SECTION BELOW FOR MORE INFORMATION), QSCONTACT CLOSURE INTERFACE, PALLADIOM ROOM THERMOSTAT

-3

GUESTROOM CONTROL UNIT -8

SENSORS & DEVICES THAT CONSUME PDUS WHEN WIRED TO A QSM

LUTRON DAYLIGHT SENSOR, LUTRON INFRARED (IR) RECEIVER, PICOWIRED CONTROLLER

-0.5

ECOSYSTEM WALLSTATION -1

LOS C SERIES OCCUPANCY SENSOR, HIGH BAY OCCUPANCY SENSOR -2

120V

#1QSPS-10PNLFloor 1\E1-2 - SECOND FLOOR PLAN -LIGHTING\Cyber Lab - Power Supply 002QS Smart Panel

120V

#2QSPS-10PNLFloor 1\E1-2 - SECOND FLOOR PLAN -LIGHTING\Cyber Lab - Power Supply 001QS Smart Panel

GRX-TVI120 V

GRX-TVI120 V

GRX-TVI120 V

GRX-TVI120 V

RF

120V

#3QSGRJ-4P-WHFloor 1\E1-2 - SECOND FLOOR PLAN -LIGHTING\Cyber Lab - Control Station 001GRAFIK Eye QS Wireless 4 zoneScenes 1-4 + Off4 gang backbox

0-1

0V

Cyber Labc506 W of LED 0-10LZ4 (11)

1

0-1

0V

Cyber Laba230 W of LED 0-10LZ4E (5)

2

0-1

0V

Cyber Labb46 W of LED 0-10LZ4E (1)

3

0-1

0V

Cyber Labd276 W of LED 0-10LZ4 (6)

4

RF

LUTRON

PJ2-4B-GWH-L31Floor 1\E1-2 - SECOND FLOOR PLAN - LIGHTING\CyberLab - Control Station 0044 Button Scene with Light Icon - Pico KeypadScenes 1-3 + Off

RF

LUTRON

PJ2-4B-GWH-L31Floor 1\E1-2 - SECOND FLOOR PLAN - LIGHTING\CyberLab - Control Station 0054 Button Scene with Light Icon - Pico KeypadScenes 1-3 + Off

LUT-ELI-3PHFloor 1\E1-2 - SECONDFLOOR PLAN -LIGHTING\Cyber Lab -Emergency LightingInterface 001Emergency Lighting Interface

Fire Alarm Control Panel(Contact Closure Input)

E

#4QSE-CI-NWK-EFloor 1\E1-2 - SECOND FLOOR PLAN -LIGHTING\Cyber Lab - Network Interface 001QS Ethernet & RS232 Control Interface

To Ethernet (Not Provided by Lutron)

QLink 1

To sheet 2 (2 Devices on T-Tap)

T1

#5QSWS2-3BDI-WHFloor 1\E1-2 - SECOND FLOOR PLAN- LIGHTING\Cyber Lab - ControlStation 002seeTouch QS Dual Insert 3 ButtonScenes 1-2 + Off, Scenes 1-31 gang backbox

#6QSWS2-3BDI-WHFloor 1\E1-2 - SECOND FLOOR PLAN- LIGHTING\Cyber Lab - ControlStation 003seeTouch QS Dual Insert 3 ButtonScenes 1-2 + Off, Scenes 1-31 gang backbox

120/277V

QSPS-J-1-35VFloor 1\E1-2 - SECOND FLOOR PLAN -LIGHTING\Cyber Lab - J-Box Power Supply002J-Box Power Supply can support one shadeor supply up to 8 PDU’s on a QS Link.

#7QSE-IOFloor 1\E1-2 - SECOND FLOOR PLAN -LIGHTING\Cyber Lab - IO 001QS Contact Closure Input/Output ControlInterfaceScenes 1-4 + Off

120/277V

QSPS-J-1-35VFloor 1\E1-2 - SECOND FLOOR PLAN -LIGHTING\Cyber Lab - J-Box Power Supply001J-Box Power Supply can support one shadeor supply up to 8 PDU’s on a QS Link.

QLink 1 QLink 1 QLink 1 QLink 1 QLink 1

QLink 1 QLink 1

QLink 1

T1

Link 1

Q

Q

D

E

F

P

3

P

S

P

T

T

Wire Legend

2 #12 AWG (4 sq mm) + ground

3 #12 AWG (4 sq mm) + ground

Panel Control Link (Connect wires 1, 2, 3, 4and 5)*

EcoSystem Bus/Loop*

DALI Loop

Lutron Sensor Cable C-CBL-522S or use3#22 AWG (1.0 sq mm)

DMX Cable. Use LutronGRX-CBL-DMX-250/GRX-CBL-DMX-500 orBeldon #9729 (Non-plenum) or Beldon#89729 (Plenum) or Dura Flex 22/4 WA Cable.

Lutron Sensor Cable C-CBL-522S or use4#22 AWG (1.0 sq mm)

QS Control Link (Connect wires 1, 3 and 4. Donot connect wire 2)*

RF Connection

Wired Connection

QS Control Link (Connect wires 1, 2, 3 and 4)*

Panel Control Link (Connect wires 1, 2, 3 and4. Do not connect wire #5)*

Normal Input Power 2 #12 AWG (4 sq mm) +ground

QS Sivoia Shade Control Link*

Normal-Emergency Input Power 2 #12 AWG(4 sq mm) + ground

3 Phase 4 wire Input Power, 4 #12 AWG (4sq mm) + ground

0-10 V Signal: 2#18AWG (1.0 sq mm)

2#18 AWG (1.0 sq mm)

3#18 AWG (1.0 sq mm)

Ethernet cable. CAT5E or better cable forLutron Network terminated with RJ45connectors (not provided by Lutron). 328 ft(100 m) maximum run.

Fiber optic cable for Lutron Networkterminated with appropriate fiber opticconnectors (not provided by Lutron). Requiresdedicated fiber optic link (single-mode ormulti-mode)

Panel Control Link (Connect wires 1, 3, 4 and5. Do not connect wire #2)*

T-Series Tunable-White Loop

Belden Cable 1387LA(Or Equivalent)

(28) (30) (1)

(36)

(36)

(38)

(38)

(32) (34)

LIGHTING RISER DIAGRAM* ALL CIRCUITS SHOWN (X) HOMERUN TO PANEL RP-2C.

7200 Suter RoadCoopersburg, PA 18036, USA+1.610.282.3800 | Fax: +1.610.282.1146

*Refer to Panel Schedule for feed and load information

VS

B

6 X VS

303 Williams Ave. SW, Suite 1211Huntsville, AL 35801T. (256) 534-2353

SSOE, Inc.®

MEMBER OF THE AMERICAN

INSTITUTE OF ARCHITECTS

This document is a copyright protected instrument of service and

licnesed for use in the titled project only. This drawing may not be reproduced in whole or in part without written permission of

FUQUA & PARTNERS ARCHITECTS, P.C.A Professional Corporation

DATE:

ISSUE:

DRAWN:

PROJECT NO:

SHEET

OF

Architecture

Interior Design

Media Visualization

Master Planning

100 Church Street, Suite 700Huntsville, Alabama 35801

PH: (256) 534.3516FX: (256) 533.4605

www.fuquaarchitects.com

CHECKED:

2/2

1/2

020 5

:17:4

2 P

M

E0.2

ELE

CT

RIC

AL

SC

HE

DU

LES

& L

IGH

TIN

G R

ISE

R D

IAG

RA

M

301

SP

AR

KM

AN

DR

IVE

, HU

NT

SV

ILLE

, AL

3589

9

C.SHELTON

2020-02-25

FPA#07519

A.YORK

CONSTRUCTION SET

UA

H B

AB

CY

BE

R L

AB

/ IN

TE

RIO

R R

EN

OV

AT

ION

SSOE #020-00457-00

LIGHTING FIXTURE SCHEDULETYPE LAMPS DESCRIPTION VOLTAGE MANUFACTURER APPARENT LOAD COUNT

LR6 LED, 4000K RECESSED DOWNLIGHT, 6-IN. DIA., SEMI-SPECULAR ALZAK REFLECTOR, 0-10V DIMMING, MINIMUM 4,000 LUMENS 277 V ACUITY:LDN6-40/40-LO6-AR-LSS-MVOLT-EZ10-HAO

44 VA 15

LR6E LED, 4000K SAME AS 'LR6', BUT ON LIFE SAFETY EMERGENCY CIRCUIT 277 V ACUITY:LDN6-40/40-LO6-AR-LSS-MVOLT-EZ10-HAO

44 VA 3

LZ4 LED, 3500K 2' x 2' RECESSED LUMINAIRE, ARCHITECTURAL BASKET LENS, ALUMINUM HOUSING , MINIMUM 5,000 LUMENS, 0-10V DIMMING 120 V CREE 39 VA 17

LZ4E LED, 3500K SAME AS FIXTURE LZ4 EXCEPT COMPLETE WITH EMERGENCY POWER 120 V CREE 39 VA 6

LZ5 LED, 4000K 2' x 4' RECESSED LUMINAIRE, ARCHITECTURAL BASKET LENS, ALUMINUM HOUSING, MINIMUM 4,800 LUMENS 277 V ACUITY:2ALL4-CTRF-48L-EZ1-LP840-N100

46 VA 13

LZ5E LED, 4000K SAME AS 'LZ5', BUT ON LIFE SAFETY EMERGENCY CIRCUIT 277 V ACUITY:2ALL4-CTRF-48L-EZ1-LP840-N100

46 VA 12

XAP LED UNIVERSAL MOUNTED L.E.D. EXIT SIGN, WITH DIE-CAST ALUMINUM HOUSING AND NATURAL BRUSHED ALUMINUM STENCILFACEPLATE AND TRIM WITH RED LETTERS. LUMINAIRE SHALL CONTAIN A MULTITUDE OF ULTRA LONG LIFE L.E.D.'SMOUNTED ON A PRINTED CIRCUIT BOARD. TOTAL WATTAGE NOT TO EXCEED 3 WATTS FOR A SINGLE FACE AND 6 WATTSFOR A DOUBLE FACE UNIT. L.E.D.'S SHALL BY PROTECTED BE A CLEAR PANEL AND OPTICAL DIFFUSER.

277 V LITHONIA:LE-S-1/2-R-120/277-ELN

3 VA 9

XBP LED UNIVERSAL MOUNTED L.E.D. EXIT SIGN, WITH PRECISION-MOLDED THERMO PLASTIC HOUSING AND STENCIL FACEPLATE ANDTRIM. FIXTURE SHALL CONTAIN A MULTITUDE OF ULTRA LONG LIFE L.E.D.'S MOUNTED ON A PRINTED CIRCUIT BOARD. TOTALWATTAGE NOT TO EXCEED 3 WATTS FOR A SINGLE FACE AND 6 WATTS FOR A DOUBLE FACE UNIT. L.E.D.'S SHALL BYPROTECTED BE A CLEAR PANEL AND OPTICAL DIFFUSER. HIGH OUTPUT LEAD CALCIUM BATTERY PACK

277 V LITHONIA CATALOGNUMBER-LQM-S-W-(1 OR 3 ASINDICATED ON THEDRAWINGS)-R-120/277,EL-H0-SD, OR EMERGI-LITE, ORSURE-LITE OR PRESCOLITE ORCHLORIDE CATALOG No.CXLA1RN

5 VA 4

XCP LED UNIVERSAL MOUNTED L.E.D. EXIT SIGN, WITH PRECISION-MOLDED THERMO PLASTIC HOUSING AND STENCIL FACEPLATE ANDTRIM. FIXTURE SHALL CONTAIN A MULTITUDE OF ULTRA LONG LIFE L.E.D.'S MOUNTED ON A PRINTED CIRCUIT BOARD. TOTALWATTAGE NOT TO EXCEED 3 WATTS FOR A SINGLE FACE AND 6 WATTS FOR A DOUBLE FACE UNIT. L.E.D.'S SHALL BYPROTECTED BE A CLEAR PANEL AND OPTICAL DIFFUSER. HIGH OUTPUT LEAD CALCIUM BATTERY PACK

120 V LITHONIA CATALOGNUMBER-LQM-S-W-(1 OR 3 ASINDICATED ON THEDRAWINGS)-R-120/277,EL-H0-SD, OR EMERGI-LITE, ORSURE-LITE OR PRESCOLITE ORCHLORIDE CATALOG No.CXLA1RN

20 VA 2

XRL LED, 4000K 2' x 4' RECESSED LUMINAIRE, ARCHITECTURAL BASKET LENS, ALUMINUM HOUSING, MINIMUM 4,800 LUMENS 120 V ACUITY:2ALL4-CTRF-48L-EZ1-LP840-N100

46 VA 2

A. REFER TO ARCHITECTURAL REFLECTED CEILINGPLANS FOR EXACT LOCATION OF ALL LIGHTINGFIXTURES UNLESS NOTED OTHERWISE.

B. REFER TO THE LUMINAIRE SCHEDULE LOCATED ONTHE ELECTRICAL GENERAL INFORMATION DRAWING.

C. ALL ELECTRICAL DEVICES INDICATED ON THIS PLANSHALL BE NEW UNLESS NOTED OTHERWISE.

D. LIGHT SWITCHES SHALL BE GROUPED UNDER ONECOMMON FACEPLATE WHERE MORE THAN ONE LIGHTSWITCH IS INDICATED TO BE INSTALLED AT THE SAMELOCATION.

E. ALL EXISTING LIGHTING INDICATED TO REMAIN SHALLBE RELAMPED AND CLEANED. REPAIR EXISTINGFIXTURES THAT ARE MALFUNCTIONING WHEREFEASIBLE. OTHERWISE REPLACE WITH NEW. REVISECIRCUITING AS INDICATED.

F. ALL LIGHTING BRANCH CIRCUIT WIRING ASSOCIATEDWITH NEW LIGHTING SHALL BE 2#12, 1#12GND IN 3/4"CUNLESS NOTED OTHERWISE.

G. ALL EXISTING EQUIPMENT/DEVICES NOTSPECIFICALLY INDICATED TO BE DEMOLISHED SHALLREMAIN OPERATIONAL. REVISE EXISTING CIRCUITINGTO MAINTAIN OPERATION TO SUCHEQUIPMENT/DEVICES AS REQUIRED.

H. REUSE THE EXISTING BRANCH CIRCUIT CONDUIT ANDWIRING ASSOCIATED WITH THE LIGHTING FIXTURESREMOVED DURING DEMOLITION TO REFEED NEWLIGHTING FIXTURES UNLESS NOTED OTHERWISE.REWORK THE EXISTING CIRCUIT TO PROVIDELIGHTING CONTROL AS INDICATED ON THIS DRAWING,UNLESS NOTED OTHERWISE.

I. ALL EXISTING LIGHTING INDICATED AS TO REMAINAND LOCATED IN AREAS WHERE THE CEILING ISBEING MODIFIED SHALL BE TEMPORARILYSUPPORTED AND REINSTALLED UPON COMPLETIONOF CEILING REVISIONS. COORDINATE WITHARCHITECTURAL REFLECTED CEILING PLANS ANDARCHITECTURAL TRADE.

J. ALL NIGHT LIGHT AND EXIT SIGNS SHALL BEUNCONTROLLED AND CONNECTED AHEAD OF THELOCAL LIGHTING CONTROLS.

K. ALL CONDUITS INSTALLED IN FINISHED AREAS SHALLBE ROUTED CONCEALED UNLESS NOTEDOTHERWISE.

L. ALL NOTES ADDED WILL APPEAR ON ALL DRAWINGSTHAT ARE OF THIS TYPE. NUMBERS WILL ALSO BETHE SAME TO PROMOTE CONSISTENCY.

GENERAL NOTES

Receptacle 21340 VA 73.43% 15670 VA Total Est. Demand: 67 A

Other 2261 VA 100.00% 2261 VA Total Conn.: 83 A

Lighting 1029 VA 100.00% 1029 VA Total Est. Demand: 24224 VA

HVAC 3264 VA 100.00% 3264 VA Total Conn. Load: 29894 VA

Equipment 2000 VA 100.00% 2000 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 75 A 116 A 62 A

Total Load: 8798 VA 13674 VA 7422 VA

41 0 0 1 20 A Spare 42

39IU-217 20 A 2

HACR STYLEBREAKER

3264 0 1 20 A Spare 40

37 Spare 20 A 1 0 0 1 20 A Spare 38

35 Spare 20 A 1 0 0 1 20 A Spare 36

33 Spare 20 A 1 0 400 1 20 A SHADE POWER SUPPLY 34

31 Spare 20 A 1 0 400 1 20 A SHADE POWER SUPPLY 32

29 Spare 20 A 1 0 730 30

27 EWC 20 A 1 600 7302 20 A LIGHTING QS PANEL

28

25 800 600 1 20 A Receptacle TV CYBER LOUNGE 26

23FL BOX CYBER LOUNGE 20 A 2

2-120V W/ HANDLETIE

800 800 24

21 800 800 2/120V W/ HANDLETIE

2 20 A FL BOX LAB EAST22

19FL BOX LAB SE 20 A 2

2-120V W/ HANDLETIE

800 800 20

17 800 800 2-120V W/ HANDLETIE

2 20 A FL BOX LAB NE18

15FL BOX LAB CENTER 20 A 2

2-120V W/ HANDLETIE

800 800 16

13 800 800 2-120V W/ HANDLETIE

2 20 A FL BOX LAB SW14

11FL BOX LAB NW 20 A 2

2-120V W/ HANDLETIE

800 800 12

9 Receptacle LAB DESK NE 20 A 1 1080 800 2-120V W/ HANDLETIE

2 20 A FL BOX LAB WEST10

7 Receptacle TV SOUTH LAB 20 A 1 720 540 1 20 A Receptacle TV WEST LAB 8

5 Recpt / LTS 217,219 20 A 1 932 960 1 20 A Receptacle TV EAST LAB 6

3 Receptacle DATA RACK 20 A 1 1600 2000 1 30 A SP PURPOSE DATA RACK 4

1 GRAPHIC EYE 20 A 1 938 1600 1 20 A Receptacle DATA RACK 2

CKT Circuit Description Trip P Comments A B C Comments P Trip Circuit Description CKT

Notes:

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains Rating: 100 A

Supply From: Phases: 3 Mains Type: MLO

Location: LAB SUPPORT 217 Volts: 208Y/120V Wye A.I.C. Rating: 14,000

RP-2C

REVISIONS

Page 24: 100 Church Street, Suite 700 Huntsville, Alabama 35801 PH ...

J

J

J

J

J

J

J

J

J

J

J

1 2 3 4 5 6

8 97

H

G

F

E

D

C

B

A

EXIST. CORRIDOR207

EXIST. CORRIDOR211

RECEPTION202A

BALCONY230

COMPUTERCLASSROOM

206

EXIST. CLASSROOM209

MEN228

EXISTING ELEC.229

PBX237

WOMEN235

EXISTING PORCH208

EX. SERVER ROOM238

EXISTING CORRIDOR231

EXISTING CLOSET236

EXIST. JANITOR227

EXIST. COPY RM225

EXIST. ELEV.239

EXISTINGMECHANICAL

240

EXIST. ELEV.239B

EXISTINGMECHANICAL

223

EXIST. CLASSROOM232C

EXIST. CLASSROOM205

EXIST. CLASSROOM220

EXIST. CLASSROOM224

EXIST. CLASSROOM222

OFFICE202F

OFFICE202G

SECRETARY202J

CONFERENCE ROOM242

STOR.202K

TOIL.202H

OFFICE241

STAIRS219

UTILITY238B

AIRLOCK233

XR

XR

XR

XR XR XR

XR

XR XR

XR XR

XR

XR

XR

XR

XR

XR

XR

XRXR

XR

XR

XR

XR

EX

EX EX

XR

XR XR

XR XR XR

XR

XR

XR

XR

XR

XR XR XR

XR

3

5 TYP

1

4

7

6

6 6

6

2

2

EX

EX

EX

EX

EX

EX

EX

EX

XR

XR

XR

XR

XRR

XR

XR

XR

XR

XR

8

8

9

9

9

F F

XR XR

F F

XR XR

F FXRR XRR

2

XR

F FXRR XRRF FXRR XRR

F

F

XRR

XRRXR

EX

F

XRR

XRRXRR

EX

EX

F FXRR XRR

EX

XR

F

EX

F XRR

F XRR

303 Williams Ave. SW, Suite 1211Huntsville, AL 35801T. (256) 534-2353

SSOE, Inc.®

MEMBER OF THE AMERICAN

INSTITUTE OF ARCHITECTS

This document is a copyright protected instrument of service and

licnesed for use in the titled project only. This drawing may not be reproduced in whole or in part without written permission of

FUQUA & PARTNERS ARCHITECTS, P.C.A Professional Corporation

DATE:

ISSUE:

DRAWN:

PROJECT NO:

SHEET

OF

Architecture

Interior Design

Media Visualization

Master Planning

100 Church Street, Suite 700Huntsville, Alabama 35801

PH: (256) 534.3516FX: (256) 533.4605

www.fuquaarchitects.com

CHECKED:

2/2

1/2

020 5

:17:4

5 P

M

E1.1

OV

ER

ALL

SE

CO

ND

FLO

OR

DE

MO

LIT

ION

PLA

N -

ELE

CT

RIC

AL

301

SP

AR

KM

AN

DR

IVE

, HU

NT

SV

ILLE

, AL

3589

9

C.SHLETON

2020-02-25

FPA#07519

A.YORK

CONSTRUCTION SET

UA

H B

AB

CY

BE

R L

AB

/ IN

TE

RIO

R R

EN

OV

AT

ION

SSOE #020-00457-00

SCALE: 1/8" = 1'-0"E1.1

1 OVERALL SECOND FLOOR DEMOLITION PLAN - ELECTRICAL

KEY PLAN

GENERAL NOTES

PLAN NOTES

A. SELECT DEMOLITION MAY BE REQUIRED FOR NEWCONSTRUCTION AND MAY NOT BE DELINEATED ONTHIS DRAWING. CAREFULLY COORDINATEDEMOLITION WITH NEW CONSTRUCTION PLANS OFALL DISCIPLINES TO VERIFY ACTUAL EXTENT OFDEMOLITION. VISIT THE SITE PRIOR TO SUBMISSIONOF BID TO EXAMINE THE EXISTING CONDITIONS ANDFULLY UNDERSTAND THE EXTENT OF DEMOLITIONWORK.

B. EXAMINE THE DRAWINGS OF OTHER TRADES AND BEFAMILIAR WITH THE DEMOLITION REQUIRED BYOTHER TRADES. PERFORM ALL INCIDENTALELECTRICAL DEMOLITION AND/OR RELOCATIONREQUIRED TO FACILITATE THE DEMOLITION WORK OFOTHER TRADES, WHETHER OR NOT SPECIFICALLYINDICATED.

C. QUANTITY AND LOCATION OF DEVICES SHOWN ONPLANS ARE APPROXIMATE. FIELD VERIFY DEVICESAND LOCATIONS.

D. ITEMS SHOWN HEAVY LINE WEIGHT DASHED LINES,HATCHED AND/OR NOTED SHALL BE DEMOLISHEDAND ALL ASSOCIATED DEVICES, CONDUIT, ANDWIRING SHALL BE REMOVED BACK TO THE NEARESTACTIVE JUNCTION BOX OR SOURCE UNLESS NOTEDOTHERWISE.

E. ALL EXISTING EQUIPMENT MAY NOT BE INDICATED.CONTRACTOR SHALL FIELD VERIFY EXISTINGCONDITIONS PRIOR TO BIDDING. EXISTING ITEMSNOT SHOWN HATCHED SHALL REMAIN IN OPERATION.REVISE THE EXISTING CIRCUITRY TO MAINTAINOPERATION OF ITEMS TO REMAIN.

F. PROVIDE PROPER SUPPORT FOR EXISTING TOREMAIN CONDUITS AND BOXES WHERE EXISTINGSUPPORT IS TO BE REMOVED. RE-ROUTE BRANCHCIRCUIT CONDUITS AND RELOCATE JUNCTION BOXESAS REQUIRED TO FACILITATE INSTALLATION OF NEWEQUIPMENT AND SYSTEMS IN CEILING SPACES.

G. COORDINATE WITH NEW WORK PLANS, ONE LINEDIAGRAMS AND RISER DIAGRAMS FOR EXTENT OFDEMOLITION WORK.

H. CIRCUITING SHOWN IS BASED ON CASUAL FIELDOBSERVATIONS AND/OR AS-BUILT DRAWINGS.CONTRACTOR SHALL FIELD VERIFY CIRCUITING.

I. MAINTAIN ELECTRICAL SERVICE TO ALL LIGHTINGFIXTURES, DEVICES AND EQUIPMENT THAT ARE TOREMAIN. EXTEND CONDUIT AND WIRE AS REQUIREDWHERE DEMOLITION WORK AFFECTS ELECTRICALSERVICE TO DOWNSTREAM LOADS THAT ARE TOREMAIN.

J. RECYCLE OR DISPOSE OF ALL MATERIALS OFF SITEAND INCLUDE ALL ASSOCIATED COSTS IN BID. ALLMATERIALS SHALL BE DISPOSED OF IN ACCORDANCEWITH ALL FEDERAL, STATE, AND LOCALREGULATIONS, INCLUDING LEED REQUIREMENTS,TCLP TESTING, PROPER DISPOSAL AND/ORRECYCLING OF FLUORESCENT LAMPS.

K. PROVIDE BLANK COVER PLATES WHERE DEVICESARE REMOVED BUT EXISTING WALLS/CEILINGSREMAIN INTACT.

L. RING OUT AND TAG ALL CIRCUITS AFFECTED BY THISALTERATION AT BOTH ENDS. MARK ALL UNUSEDCIRCUIT BREAKERS “SPARE” AND PLACE IN THE "OFF"POSITION.

M. VERIFY ALL UNDERGROUND AND IN SLAB UTILITYLOCATIONS PRIOR TO SAW-CUTTING ORPENETRATING ANY FLOOR SLAB.

N. OFFER OWNERS REPRESENTATIVE FIRST RIGHT OFREFUSAL OF ALL EQUIPMENT REMOVED FROMSPACE.

O. PROVIDE CODE-COMPLIANT SUPPORT TOEXISTING-TO-REMAIN UNSUPPORTED CONDUITS ANDBOXES WHERE CEILINGS ARE TO BE REMOVED.RE-ROUTE BRANCH CIRCUITS AND RELOCATEJUNCTION BOXES AS REQUIRED TO FACILITATEINSTALLATION OF NEW EQUIPMENT AND SYSTEMS INCEILING SPACES.

1. EXISTING WALL MOUNTED CLOCKS TO REMAINTYPICAL WITHIN CORRIDORS 207, 231, AND 211.

2. EXISTING WALL MOUNTED SWITCH ANDRECEPTACLE DEVICES TO REMAIN. COVER PLATESTO BE REPLACED WITH STAINLESS STEEL, TYPICALALL.

3. ALL AUXILIARY DEVICES STILL IN USE TO BEREMOVED FROM EXISTING CEILING, HUNG ANDSUPPORTED, AND RE-INSTALLED WITHIN NEWCEILING TILE. INCLUDES FIRE ALARM DETECTORS,VISUAL / AUDIO DEVICES, WIFI ANTENNAS, ETC.

4. EXISTING WALL MOUNTED JUCNTION BOXES NOLONGER IN USE OR ABANDONED SHALL HAVE WIREAND BOXES REMOVED AND OPENINGS PATCHED TOMATCH EXISTING FINISHES.

5. EXISTING LIGHTING AND EXIT SIGNAGE TO BEDEMOLISHED. CIRCUITS TO BE CAPPED IN BOXESAND RE-USED FOR NEW LIGHTING IN CORRIDORS207, 231, AND 211.

6. REMOVE AND RETURN EXISTING LUMINAIRES,CONTROLS, AND LIGHTING MODULES IN THIS ROOMTO OWNER DESIGNATED LOCATION ON CAMPUS.TWO OF THE 2X4 LUMINAIRES TO BE RELOCATED(XRL) IN THE LABE SUPPORT ROOM, SEE LIGHTINGDRAWINGS.

7. EXISTING FIRE ALARM CONTROL PANEL (FACP)LOCATED IN MEZZANINE ROOM BELOW.

8. EXISTING CIRCUITS MADE AVAILABLE FROMDEMOLITION (AND NOT THOSE CONTINUED) SHALLHAVE WIRING PULLED BACKTO PANEL AND CONDUIT/ CABLE REMOVED FROM THE CEILING. UPDATEPANEL DIRECTORY, TURN BREAKER OFF AND MARK"SPARE".

9. OWNER TO REMOVE EXISTING PROJECTIONEQUIPMENT PRIOR TO CONTRACTOR DEMOLITION.

N

DEMOLITION ABBREVIATIONS:

XR - EXISTING TO BE REMOVED

XRL - EXISTING RELOCATED

XRR - EXISTING REMOVE AND RELOCATE

EX - EXISTING TO REMAIN

REVISIONS

Page 25: 100 Church Street, Suite 700 Huntsville, Alabama 35801 PH ...

1 2 3 4 5 6

8 97

H

G

F

E

D

C

B

A

SEE SHEET E2.2 THIS AREA

CYBERSECURITY LAB219

CYBER LOUNGE218

EXIST. CORRIDOR211

EXISTING CORRIDOR231

AIRLOCK233

EXIST. CORRIDOR207

LR6E

LR6E

LZ5 LZ5E LZ5 LZ5E

LR6 LR6

LR6

LR6 LR6E

LZ5

LZ5E

LZ5

LZ5ELR6

LR6

LR6

XAP

LR6

LZ5E

LZ5E

LR6

LR6

LR6

LR6

LZ5E

LZ5E LZ5

LR6 LR6

LZ5E LZ5 LZ5E

LR6

LZ5

LZ5E

LZ5

LZ5 LZ5 LZ5E

LZ5LZ5LZ5

XBP

XAP

XAP

XBP

XBP XAP

2 TYP

2 TYP

2 TYP

2 TYP

XAP

XBP

XAP

XAP

XAP

NL

NL

NLNLNL

NL

NL

NL

NL

NL

NLNL

NL

NL

NL

303 Williams Ave. SW, Suite 1211Huntsville, AL 35801T. (256) 534-2353

SSOE, Inc.®

MEMBER OF THE AMERICAN

INSTITUTE OF ARCHITECTS

This document is a copyright protected instrument of service and

licnesed for use in the titled project only. This drawing may not be reproduced in whole or in part without written permission of

FUQUA & PARTNERS ARCHITECTS, P.C.A Professional Corporation

DATE:

ISSUE:

DRAWN:

PROJECT NO:

SHEET

OF

Architecture

Interior Design

Media Visualization

Master Planning

100 Church Street, Suite 700Huntsville, Alabama 35801

PH: (256) 534.3516FX: (256) 533.4605

www.fuquaarchitects.com

CHECKED:

2/2

1/2

020 5

:17:4

7 P

M

E2.1

OV

ER

ALL

SE

CO

ND

FLO

OR

PLA

N -

LIG

HT

ING

301

SP

AR

KM

AN

DR

IVE

, HU

NT

SV

ILLE

, AL

3589

9

C.SHELTON

2020-02-25

FPA#07519

A.YORK

CONSTRUCTION SET

UA

H B

AB

CY

BE

R L

AB

/ IN

TE

RIO

R R

EN

OV

AT

ION

SSOE #020-00457-00

SCALE: 1/8" = 1'-0"E2.1

1 OVERALL SECOND FLOOR PLAN - LIGHTING

KEY PLAN

GENERAL NOTES

PLAN NOTES

A. REFER TO ARCHITECTURAL REFLECTED CEILINGPLANS FOR EXACT LOCATION OF ALL LIGHTINGFIXTURES UNLESS NOTED OTHERWISE.

B. REFER TO THE LUMINAIRE SCHEDULE LOCATED ONTHE ELECTRICAL GENERAL INFORMATION DRAWING.

C. ALL ELECTRICAL DEVICES INDICATED ON THIS PLANSHALL BE NEW UNLESS NOTED OTHERWISE.

D. LIGHT SWITCHES SHALL BE GROUPED UNDER ONECOMMON FACEPLATE WHERE MORE THAN ONE LIGHTSWITCH IS INDICATED TO BE INSTALLED AT THE SAMELOCATION.

E. ALL EXISTING LIGHTING INDICATED TO REMAIN SHALLBE RELAMPED AND CLEANED. REPAIR EXISTINGFIXTURES THAT ARE MALFUNCTIONING WHEREFEASIBLE. OTHERWISE REPLACE WITH NEW. REVISECIRCUITING AS INDICATED.

F. ALL LIGHTING BRANCH CIRCUIT WIRING ASSOCIATEDWITH NEW LIGHTING SHALL BE 2#12, 1#12GND IN 3/4"CUNLESS NOTED OTHERWISE.

G. ALL EXISTING EQUIPMENT/DEVICES NOTSPECIFICALLY INDICATED TO BE DEMOLISHED SHALLREMAIN OPERATIONAL. REVISE EXISTING CIRCUITINGTO MAINTAIN OPERATION TO SUCHEQUIPMENT/DEVICES AS REQUIRED.

H. REUSE THE EXISTING BRANCH CIRCUIT CONDUIT ANDWIRING ASSOCIATED WITH THE LIGHTING FIXTURESREMOVED DURING DEMOLITION TO REFEED NEWLIGHTING FIXTURES UNLESS NOTED OTHERWISE.REWORK THE EXISTING CIRCUIT TO PROVIDELIGHTING CONTROL AS INDICATED ON THIS DRAWING,UNLESS NOTED OTHERWISE.

I. ALL EXISTING LIGHTING INDICATED AS TO REMAINAND LOCATED IN AREAS WHERE THE CEILING ISBEING MODIFIED SHALL BE TEMPORARILYSUPPORTED AND REINSTALLED UPON COMPLETIONOF CEILING REVISIONS. COORDINATE WITHARCHITECTURAL REFLECTED CEILING PLANS ANDARCHITECTURAL TRADE.

J. ALL NIGHT LIGHT AND EXIT SIGNS SHALL BEUNCONTROLLED AND CONNECTED AHEAD OF THELOCAL LIGHTING CONTROLS.

K. ALL CONDUITS INSTALLED IN FINISHED AREAS SHALLBE ROUTED CONCEALED UNLESS NOTEDOTHERWISE.

L. ALL NOTES ADDED WILL APPEAR ON ALL DRAWINGSTHAT ARE OF THIS TYPE. NUMBERS WILL ALSO BETHE SAME TO PROMOTE CONSISTENCY.

1. PROVIDE CONTINUOUS DIMMING CONTROL VIAREMOTE DAYLIGHTING SENSOR(S) PER ASHRAE 90.12010 FOR LIGHT FIXTURES LOCATED IN THE PRIMARYSIDELIGHTED AREA. DAYLIGHT CONTROLLEDFIXTURES LOCATED IN THE PRIMARY SIDELIGHTEDAREA SHALL BE SEPARATELY CONTROLLED FROMFIXTURES LOCATED IN THE SECONDARYSIDELIGHTED AREA, AS CONTROLS INDICATE ONPLAN. ALL LIGHT FIXTURES WITHIN SPACE SHALL BECONTROLLED VIA VACNANCY SENSOR(S) WITHIN THESAME SPACE. PROVIDE ADEQUATE COVERAGE OFSENSORS AS RECOMMENDED BY THEMANUFACTURER FOR THE SPACE, REGARDLESS OFQUANTITY INICATED ON DRAWINGS.

2. CIRCUIT NEW LIGHTING INTO EXISTING CIRCUIT MADEAVAILABLE FROM DEMOLITION. EMERGENCY EGRESSAND EXIT SIGNAGE SHALL MAINTAIN ALWAYS ONOPERATION ON LIFE SAFETY CIRCUIT, TYPICAL.EXISTING SWITCHING CONTROL LOCATION TOREMAIN, SEE DEMOLITION SHEET.

3. PROVIDE REMOTE IR LIGHTING CONTROL HAND-HELDDEVICES FOR DUPLICATION OF GRAPHIC EYEPRESETS.

4. SEE LIGHTING RISER DIAGRAM ON SHEET E0.2 FORCIRCUIT NUMBERS

5. VACANCY SENSORS TIED TO ROOM CONTROLLER(GRAPHIC EYE). IF NO MOTION AFTER SET TIMEFLOOR RECEPTACLES IN THIS ROOM SHUT OFF.

NREVISIONS

Page 26: 100 Church Street, Suite 700 Huntsville, Alabama 35801 PH ...

VS

VS

VS

VS

VS

VS

8

8

9

9

7

7

C C

B B

A A

LZ4 LZ4

LZ4 LZ4 LZ4 LZ4 LZ4 LZ4

LZ4 LZ4 LZ4

LZ4 LZ4 LZ4 LZ4

LZ4

LZ4E LZ4 LZ4E

LZ4E LZ4E

LZ4E

LZ4E

b b b b

b

b

cd

dd

adab

b d d

dadc

da

XCP

XCP

1

SEE SHEET E2.1 FOR WORK IN THIS AREA

CP

CP

XRL XRL

V

GRAPHIC EYECONTROL UNIT

GRAPHIC EYE"SEETOUCH"

3

CP

GRAPHIC EYE"SEETOUCH"(SHADE CONTROL)

(1)

RP-2C

(32,34)

(28,30)

(1) (1) (1) (1) (1)

(1) (1)

(1)

(1)(1)(1)(1)(1)(1)

(1) (1) (1) (1) (1)

(1)(1)(1)(1)

(5) (5)

(1)

(1)

B

B

B

B

B

B

5

5

5

5

5

5

NL NL

NL

303 Williams Ave. SW, Suite 1211Huntsville, AL 35801T. (256) 534-2353

SSOE, Inc.®

MEMBER OF THE AMERICAN

INSTITUTE OF ARCHITECTS

This document is a copyright protected instrument of service and

licnesed for use in the titled project only. This drawing may not be reproduced in whole or in part without written permission of

FUQUA & PARTNERS ARCHITECTS, P.C.A Professional Corporation

DATE:

ISSUE:

DRAWN:

PROJECT NO:

SHEET

OF

Architecture

Interior Design

Media Visualization

Master Planning

100 Church Street, Suite 700Huntsville, Alabama 35801

PH: (256) 534.3516FX: (256) 533.4605

www.fuquaarchitects.com

CHECKED:

2/2

1/2

020 5

:17:4

9 P

M

E2.2

PA

RT

IAL

SE

CO

ND

FLO

OR

PLA

N -

LIG

HT

ING

301

SP

AR

KM

AN

DR

IVE

, HU

NT

SV

ILLE

, AL

3589

9

C.SHELTON

2020-02-25

FPA#07519

A.YORK

CONSTRUCTION SET

UA

H B

AB

CY

BE

R L

AB

/ IN

TE

RIO

R R

EN

OV

AT

ION

SSOE #020-00457-00

PLAN NOTES

1. PROVIDE CONTINUOUS DIMMING CONTROL VIAREMOTE DAYLIGHTING SENSOR(S) PER ASHRAE 90.12010 FOR LIGHT FIXTURES LOCATED IN THE PRIMARYSIDELIGHTED AREA. DAYLIGHT CONTROLLEDFIXTURES LOCATED IN THE PRIMARY SIDELIGHTEDAREA SHALL BE SEPARATELY CONTROLLED FROMFIXTURES LOCATED IN THE SECONDARYSIDELIGHTED AREA, AS CONTROLS INDICATE ONPLAN. ALL LIGHT FIXTURES WITHIN SPACE SHALL BECONTROLLED VIA VACNANCY SENSOR(S) WITHIN THESAME SPACE. PROVIDE ADEQUATE COVERAGE OFSENSORS AS RECOMMENDED BY THEMANUFACTURER FOR THE SPACE, REGARDLESS OFQUANTITY INICATED ON DRAWINGS.

2. CIRCUIT NEW LIGHTING INTO EXISTING CIRCUIT MADEAVAILABLE FROM DEMOLITION. EMERGENCY EGRESSAND EXIT SIGNAGE SHALL MAINTAIN ALWAYS ONOPERATION ON LIFE SAFETY CIRCUIT, TYPICAL.EXISTING SWITCHING CONTROL LOCATION TOREMAIN, SEE DEMOLITION SHEET.

3. PROVIDE REMOTE IR LIGHTING CONTROL HAND-HELDDEVICES FOR DUPLICATION OF GRAPHIC EYEPRESETS.

4. SEE LIGHTING RISER DIAGRAM ON SHEET E0.2 FORCIRCUIT NUMBERS

5. VACANCY SENSORS TIED TO ROOM CONTROLLER(GRAPHIC EYE). IF NO MOTION AFTER SET TIMEFLOOR RECEPTACLES IN THIS ROOM SHUT OFF.

SCALE: 1/4" = 1'-0"E2.2

1 PARTIAL SECOND FLOOR PLAN - LIGHTING

A. REFER TO ARCHITECTURAL REFLECTED CEILINGPLANS FOR EXACT LOCATION OF ALL LIGHTINGFIXTURES UNLESS NOTED OTHERWISE.

B. REFER TO THE LUMINAIRE SCHEDULE LOCATED ONTHE ELECTRICAL GENERAL INFORMATION DRAWING.

C. ALL ELECTRICAL DEVICES INDICATED ON THIS PLANSHALL BE NEW UNLESS NOTED OTHERWISE.

D. LIGHT SWITCHES SHALL BE GROUPED UNDER ONECOMMON FACEPLATE WHERE MORE THAN ONE LIGHTSWITCH IS INDICATED TO BE INSTALLED AT THE SAMELOCATION.

E. ALL EXISTING LIGHTING INDICATED TO REMAIN SHALLBE RELAMPED AND CLEANED. REPAIR EXISTINGFIXTURES THAT ARE MALFUNCTIONING WHEREFEASIBLE. OTHERWISE REPLACE WITH NEW. REVISECIRCUITING AS INDICATED.

F. ALL LIGHTING BRANCH CIRCUIT WIRING ASSOCIATEDWITH NEW LIGHTING SHALL BE 2#12, 1#12GND IN 3/4"CUNLESS NOTED OTHERWISE.

G. ALL EXISTING EQUIPMENT/DEVICES NOTSPECIFICALLY INDICATED TO BE DEMOLISHED SHALLREMAIN OPERATIONAL. REVISE EXISTING CIRCUITINGTO MAINTAIN OPERATION TO SUCHEQUIPMENT/DEVICES AS REQUIRED.

H. REUSE THE EXISTING BRANCH CIRCUIT CONDUIT ANDWIRING ASSOCIATED WITH THE LIGHTING FIXTURESREMOVED DURING DEMOLITION TO REFEED NEWLIGHTING FIXTURES UNLESS NOTED OTHERWISE.REWORK THE EXISTING CIRCUIT TO PROVIDELIGHTING CONTROL AS INDICATED ON THIS DRAWING,UNLESS NOTED OTHERWISE.

I. ALL EXISTING LIGHTING INDICATED AS TO REMAINAND LOCATED IN AREAS WHERE THE CEILING ISBEING MODIFIED SHALL BE TEMPORARILYSUPPORTED AND REINSTALLED UPON COMPLETIONOF CEILING REVISIONS. COORDINATE WITHARCHITECTURAL REFLECTED CEILING PLANS ANDARCHITECTURAL TRADE.

J. ALL NIGHT LIGHT AND EXIT SIGNS SHALL BEUNCONTROLLED AND CONNECTED AHEAD OF THELOCAL LIGHTING CONTROLS.

K. ALL CONDUITS INSTALLED IN FINISHED AREAS SHALLBE ROUTED CONCEALED UNLESS NOTEDOTHERWISE.

L. ALL NOTES ADDED WILL APPEAR ON ALL DRAWINGSTHAT ARE OF THIS TYPE. NUMBERS WILL ALSO BETHE SAME TO PROMOTE CONSISTENCY.

GENERAL NOTES

KEY PLAN

N

REVISIONS

Page 27: 100 Church Street, Suite 700 Huntsville, Alabama 35801 PH ...

J

J

FB

2

FB

2F

B2

FB2

FB

2

FB

2

FB2

FB2

8

8

9

9

7

7

C C

B B

A A

LAB SUPPORT217

EXIST. CLASSROOM220

STAIRS219

CYBERSECURITY LAB219

CYBER LOUNGE218

1

1

TV 74"

TV 74" TV 74"

DATA RACK

5-30R

2

2

2

2

2

2

2

2

TV 74"

TV 74"

RP-2C

IU-217

(39,41)

RP-2C

UON

(2) (3)(4)(5)

(5)

(5)

(5)

(6) (6)

(6)

(6)

(7)

(7)

(7)(7)

(8)

(8)

(8)

(9) (9)

(9)

(10,12)

(11,13)

(14,16)

(15,17)

(18,20)

(19,21)

(22,24)

(23,25)

(26)

(26)

EXIST. CLASSROOM232C

APPROXIMATE LOCATION OF EXISTING WESTINGHOUSE POW-R-LINE PANEL "PP-B" ON FIRST FLOOR.

(27)

EWC

5 5

5

5

6

4

303 Williams Ave. SW, Suite 1211Huntsville, AL 35801T. (256) 534-2353

SSOE, Inc.®

MEMBER OF THE AMERICAN

INSTITUTE OF ARCHITECTS

This document is a copyright protected instrument of service and

licnesed for use in the titled project only. This drawing may not be reproduced in whole or in part without written permission of

FUQUA & PARTNERS ARCHITECTS, P.C.A Professional Corporation

DATE:

ISSUE:

DRAWN:

PROJECT NO:

SHEET

OF

Architecture

Interior Design

Media Visualization

Master Planning

100 Church Street, Suite 700Huntsville, Alabama 35801

PH: (256) 534.3516FX: (256) 533.4605

www.fuquaarchitects.com

CHECKED:

2/2

1/2

020 5

:17:5

1 P

M

E3.2

PA

RT

IAL

SE

CO

ND

FLO

OR

PLA

N -

PO

WE

R

301

SP

AR

KM

AN

DR

IVE

, HU

NT

SV

ILLE

, AL

3589

9

C.SHELTON

2020-02-25

FPA#07519

A.YORK

CONSTRUCTION SET

UA

H B

AB

CY

BE

R L

AB

/ IN

TE

RIO

R R

EN

OV

AT

ION

SSOE #020-00457-00

SCALE: 1/4" = 1'-0"E3.2

1 PARTIAL SECOND FLOOR PLAN - POWER

GENERAL NOTES

PLAN NOTES

A. REFER TO ARCHITECTURAL FLOOR PLAN ANDELEVATIONS FOR EXACT LOCATION OF DEVICESWHERE INDICATED.

B. ALL RECEPTACLE OUTLETS SHALL BE RATED 20A.

C. ALL DISCONNECT SWITCHES SHALL BE HEAVY DUTYTYPE.

D. PROVIDE GFCI PROTECTION WHERE REQUIRED BYTHE NEC WHETHER INDICATED OR NOT.

E. ALL BRANCH CIRCUIT JUNCTION BOXES SHALL BELABELED WITH THE CIRCUITS ENCLOSED.

F. ALL BRANCH CIRCUIT WIRING SHALL BE 2#12,1#12GND IN 3/4"C UNLESS NOTED OTHERWISE.

G. ALL EXISTING EQUIPMENT/DEVICES NOTSPECIFICALLY INDICATED TO BE DEMOLISHED SHALLREMAIN OPERATIONAL. REVISE EXISTING CIRCUITINGTO MAINTAIN OPERATION TO SUCHEQUIPMENT/DEVICES AS REQUIRED.

H. ALL CONDUITS SHALL BE ROUTED CONCEALEDUNLESS NOTED OTHERWISE.

I. ALL ELECTRICAL EQUIPMENT MOUNTED ON THEFLOOR SHALL BE MOUNTED ON A 4" CONCRETEHOUSEKEEPING PAD.

J. PROVIDE ARC FAULT CIRCUIT INTERRUPTER TYPECIRCUIT BREAKERS IN DWELLING AND DORMITORYUNITS AND FOR ALL BRANCH CIRCUITS INDICATED INSECTION 210.12 OF THE NEC.

K. PROVIDE HOSPITAL GRADE RECEPTACLE OUTLETS INALL PATIENT CARE VICINITY LOCATIONS.

L. PROVIDE A METAL RACEWAY SYSTEM, METALLICCABLE ARMOR, OR SHEATH ASSEMBLY THATQUALIFIES AS AN EQUIPMENT GROUND CONDUCTORIN ACCORDANCE WITH SECTION 250.118 OF THE NECIN PATIENT CARE AREAS AS REQUIRED BY SECTION517.13 OF THE NEC. AN INSULATED EQUIPMENTGROUND CONDUCTOR SHALL BE PROVIDED INADDITION AS INDICATED IN SECTION 517.13 OF THENEC.

M. ALL NOTES ADDED WILL APPEAR ON ALL DRAWINGSTHAT ARE OF THIS TYPE. NUMBERS WILL ALSO BETHE SAME TO PROMOTE CONSISTENCY.

1. PROVIDE 120V POWER ABOVE ACCESSIBLE CEILINGFOR LOW-VOLTAGE EQUIPMENT SUCH AS CARDREADERS AND CAMERAS. COORDINATE EXACTREQUIREMENTS WITH SECURITY EQUIPMENTINSTALLER PRIOR TO ROUGH-IN.

2. DIVIDED FLOOR BOX / POKE-THRU, COMPLETE WITH(2) DUPLEX RECEPTACLES AND (2) DEDICATED 20A,120V CIRCUITS. COORDINATE EXACT LOCATION WITHEQUIPMENT INSTALLER PRIOR TO ROUGH-IN. ALLFLOOR BOX OUTLETS TIED TO ON/OFF VACANCYRELAY CONTROLLED BY LIGHTING SYSTEM. SEEPANEL SCHEDULE FOR ADDITIONAL INFORMATION.

3. THERMAL MOTOR SWITCH WITH ADJUSTIABLESETTINGS TO MATCH EQUIPMENT LOAD.

4. NEW 200A 120/208V 3PH. 4W. MAIN LUGS PANEL FEDFROM NEW 150A/3 CIRCUIT BREAKER IN EXISTINGPANEL "PP-B". 22,000 AIC RATED BREAKER. FEEDUSING 4#1/0 & 1#6(G)-2" CONDUIT.

5. EXISTING RECEPTACLES TO REMAIN ON THIS WALL.REPLACE EXISTING WALL COVER PLATES WITHSTAINLESS STEEL.

6. MAINTAIN 36 INCHES CLEAR FOR MAINTENANCE OFPANEL. PROVIDE HAZARD YELLOW FLOOR HATCHINGRECTANGLE IDENTIFYING NEC. WORKINGCLEARANCE REQUIRED.

KEY PLAN

N

REVISIONS

Page 28: 100 Church Street, Suite 700 Huntsville, Alabama 35801 PH ...

CR

CR

WAP WAP

TV TV

TV

TV

TV

TV

TV

TV

TV TV

TV

PBB

F

F

F

CR

TV

AOM

S

S

S S

S

S S

S

S

S

S

J

J

J

J

J

J

J J J J JJ

J

J

J

J

J

J

J

8

8

9

9

7

7

C C

B B

A A

LAB SUPPORT217

STAIRS219

CYBERSECURITY LAB219

CYBER LOUNGE218

2D 2D

4D

4D

4D

4D

4D

4D

4D

4D

4D

4D

MH=80"

MH=80"

MH=80" MH=80"MAC MAC

MH=80"

2D

2D

4D

4D

LH

LH

LH

LH

LH

RH

LH LH LH LH RHLH

LH

LH

LH

LH

LH

LH

LH

KEYSTONE JACK AND PATCH CORD

10' OF CATEGORY 6ACABLE COILED

TILE BRIDGE

WAPPROVIDED AND INSTALLED BY OWNER

CEILING

5'MAX.

J HOOK

AF

F

ELECTRICALSERVICEGROUND

CONDUITS

RACK/CABINET

EQUIPMENT

BUILDINGENTRANCEPROTECTION

SPLICE TRAY GROUND

CABLE TRAY

#6 AWG (100 FEET MAX)

#6 AWG

#6 AWG

#6 AWG

#6 AWG

#6 AWG

#2/0 (30 FEET MAX)

#2/0 (30 FEET MAX)

#6 AWG (100 FEET MAX)

BUILDING STEEL

BUILDINGGROUND LOOP

PBB

18"

#2/O TBB

PROVIDE FIRE RATEDPLYWOOD PAINT TO MATCHROOM WITH FIRE RATED PAINT

TGB

(4) 2" CONDUITS TO FLOOR BELOW

PROVIDE CONDUIT BUSHINGS ON ALL OPEN CONDUIT ENDS

FIRESTOP ALL PENETRATIONSFIRE STOPPING SHALL MATCH WALL/FLOOR RATING

48"

UNSECURED SIDE DOOR ELEVATION

JUNCTION BOX AS REQUIRED

CEILING

SINGLE GANG BACK BOX

FOR RTM (CENTER

ABOVE DOOR)

EXTEND CONDUIT TO

FRAME FOR MAGNETIC

DOOR CONTACT

SECURED SIDE DOOR ELEVATION

SINGLE GANG BACK

BOX FOR CARD

READER

FINISHED FLOOR

OR GRADE

EXTEND CONDUIT DOWN

INSIDE DOOR FRAME FOR

ELECTRIC STRIKE

3/4" CONCEALED

CONDUIT (TYPICAL)

CEILING

CONTRACTORS TO ENSURE

THAT THE FIRE RATING FOR ALL

DOORS AND WALLS IS MAINTAINED.

INSTALL POWER

TRANSFER HINGE IF REX

CONTACTS ARE

PROVIDED IN EXIT DEVICE

OR IF ELECTRIC LOCK IS

PROVIDED IN THE

HANDSET

303 Williams Ave. SW, Suite 1211Huntsville, AL 35801T. (256) 534-2353

SSOE, Inc.®

MEMBER OF THE AMERICAN

INSTITUTE OF ARCHITECTS

This document is a copyright protected instrument of service and

licnesed for use in the titled project only. This drawing may not be reproduced in whole or in part without written permission of

FUQUA & PARTNERS ARCHITECTS, P.C.A Professional Corporation

DATE:

ISSUE:

DRAWN:

PROJECT NO:

SHEET

OF

Architecture

Interior Design

Media Visualization

Master Planning

100 Church Street, Suite 700Huntsville, Alabama 35801

PH: (256) 534.3516FX: (256) 533.4605

www.fuquaarchitects.com

CHECKED:

2/2

1/2

020 5

:17:5

3 P

M

E4.2

PA

RT

IAL

SE

CO

ND

FLO

OR

PLA

N -

TE

CH

NO

LOG

Y

301

SP

AR

KM

AN

DR

IVE

, HU

NT

SV

ILLE

, AL

3589

9

J. ROOSEN

2020-02-25

FPA#07519

E. BAKER

CONSTRUCTION SET

UA

H B

AB

CY

BE

R L

AB

/ IN

TE

RIO

R R

EN

OV

AT

ION

SSOE #020-00457-00

SCALE: 1/4" = 1'-0"

PARTIAL SECOND FLOOR PLAN - TECHNOLOGYN

A. THE CONTRACTOR SHALL INSTALL ALL CABLE IN APROFESSIONAL MANNER. CARE MUST BE GIVEN INTHE ROUTING OF THE CABLE SO AS TO PROVIDECLEARANCE TO ALLOW THE SERVICING OF OTHERELECTRICAL CONDUITS, EQUIPMENT, LIGHTS, ETC.

B. THE CONTRACTOR SHALL FURNISH ALL LABOR,SERVICES, AND MATERIALS NECESSARY TO INSTALLA COMPLETE, FUNCTIONAL CODE COMPLINAT, ANDOWNER APPROVED SYSTEM.

C. MINIMUM CONDUIT SIZE ALLOWABLE SHALL BE 1"UNLESS NOTED OTHERWISE. WIRE SIZE SHALL BEINCREASED AS REQUIRED TO PREVENT A VOLTAGEDROP EXCEEDING 18%. CONDUIT SIZE SHALL BEINCREASED AS REQUIRED TO MEET NECREQUIREMENTS.

D. CONTRACTOR SHALL COORDINATE AND VERIFYACTUAL EQUIPMENT SIZES WITH SIZES SHOWN ONPLANS. THE CONTRACTOR SHALL BE RESPONSIBLEFOR COORDINATING SPACE ALLOCATION WITHOTHER EQUIPMENT, EQUIPMENT ORIENTATION ANDFLOOR AND WALL.

E. VERTICALLY ALIGN DEVICES INSTALLED ON WALLWITH OTHER EQUIPMENT (THERMOSTATS, LIGHTSWITCHES, CARD READERS, MANUAL PULL STATIONS,ETC.) WHERE APPLICABLE. MAINTAIN PROPERMOUNTING HEIGHT AND LOCATION OF DEVICES TOMEET CODE.

F. COORDINATE THE EXACT LOCATION OF ALL FLOORBOXES WITH THE FINAL FURNITURE LAYOUTDRAWINGS AND ARCHITECTURAL TRADE.

G. CONTRACTOR SHALL BE RESPONSIBLE FOR ALLFEES, PERMITS, AND LICENSES FOR THE COMPLETEINSTALLATION OF HIS/HER WORK.

H. COORDINATE EXACT PHASING AND SEQUENCING OFALL WORK WITH PROJECT TECHNICAL LEADER ANDTHE OWNER.

I. ALL CABLES NOT CONCEALED IN A RACEWAYROUTED IN CEILING SPACE SHALL BE PLENUM RATEDPER NEC REQUIREMENTS.

J. ALL HORIZONTAL AND VERTICAL PENETRATIONSTHROUGH FIRE RATED STRUCTURE MUST BESLEEVED (RGS CONDUIT) AND SEALED WITH ANAPPROVED FIRE STOP.

K. ALL OUTLET BOXES INSTALLED BACK-TO-BACK INWALLS SHALL HAVE FIREPROOF SOUND INSULATINGMATERIALS INSTALLED BETWEEN THE BOXES TOPREVENT SOUND TRANSMISSION FROM ONE ROOMTO ANOTHER.

L. MISCELLANEOUS SUPPORT STEEL SHALL BE THERESPONSIBILITY OF THIS CONTRACTOR. PROVIDEFLOOR MOUNTING SUPPORT RACK FOR CONDUITSRUN BETWEEN THE EQUIPMENT AND VERTICALDROPS FROM OVERHEAD OR BUSWAY. DO NOT RUNCONDUITS ON THE FLOOR.

M. ELECTRICAL EQUIPMENT SHALL BE UL LISTED ANDLABELED.

N. CENTER ALL CEILING MOUNTED DEVICES IN THECENTER TITLE WHERE APPLICABLE.

O. CONTRACTOR TO PROVIDE AND INSTALL J-HOOKS TOSUPPORT ALL CABLING IN CEILING SPACES WHERECABLE TRAY IS NOT PRESENT. SPACING SHALL NOTEXCEED 5'-0" ON CENTER.

1. POWERED FURNITURE.

2. CONTRACTOR SHALL TIE ALL CAMERAS BACK INTOTHE EXISTING SITE AVIGILON VMS.

3. (4) FOUR 2" CONDUIT STUB UPS THROUGH SECONDFLOOR. BACKBOARD TO BE FIRE RATED PLYWOODWITH VERTICAL CABLE STRAPS. COORDINATE STUBUPS WITH ARCHITECT AND BEAM LOCATIONSBELOW.

4. MIDDLE ATLANTIC ERK CABINET. TERMINATE UAHNETWORK CABLING ON NEW PATCH PANELS ANDTEST. STP CABLING SHALL NOT BE TERMINATED ONPATCH PANEL AND SHALL HAVE 10' OF SPARE SLACKAT RACK. COORDINATE WITH AV CONSULTANT.

5. HORIZONTAL LADDER TRAY MH=7'-6".

6. CHIEF XCMIU. CEILING MOUNT DROP POLE BY AVCONSULTANT. COIL 10' OF NETWORK CABLINGABOVE CEILING.

7. STUB SPARE 1" CONDUIT WITH NYLON PULL STRINGBELOW CEILING FOR FUTURE DATA CABLING.

8. NEW FIRE ALARM DEVICES SHALL TIE TO EXISTINGSIMPLEXGRINNELL 4010 PANEL BUILDING FIREALARM SYSTEM. PANEL LOCATED IN MECHANICALROOM ON FIRST FLOOR.

9. LEGRAND 8ATC2PAA FLOOR BOX. COORDINATE WITHPOWER PLANS FOR RECEPTACLE LAYOUT.

10. RELAY MODULE SHUT DOWN AHU IN GENERALALARM CONDITION.

11. CHIEF PF2UB DUAL SCREEN FLOOR STAND BY AVCONSULTANT. FEED THROUGH FLOORBOX.

12. CEILING SPEAKERS SHOWN IN CEILING GRID FORREFERENCE ONLY. CABLING, AMPLIFIERS AND A/VSYSTEM BY OTHERS. AUDIO SYSTEM SPEAKERS ON10FT. x 12FT. GRID. MAINTAIN SPACING WITH LIGHTS,CEILING DIFFUSERS, AND OTHER DEVICES.

13. POWERED ROLLER SHADES BY LUTRON.LIGHTING/SHADING SYSTEM CONTROL VIA GRAFIKEYE. PROVIDE NECESSARY WIRING FOR COMPLETESYSTEM INSTALLATION. LH = LEFT HAND SIDE FEED.RH = RIGHT HAND SIDE FEED.

GENERAL NOTES PLAN NOTES

1 (TYPICAL)

2 (TYPICAL)

3

4

5

11

7

8 (TYPICAL)

6

6

KEY PLAN

6

6 6

6

6

11

11

11

11

10

2E4.2

2E4.2

2E4.2

1

E4.2

3

E4.2

SCALE: NOT TO SCALE

1 WIRELESS ACCESS POINT DETAIL

SCALE: NOT TO SCALE

3 DATA ROOM BACKBOARD DETAILSCALE: NOT TO SCALE

2 DOOR DETAILE4.2E4.2

E4.2

11

REVISIONS

12 (TYPICAL)