1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

60
1 Noti-Fire-Net TM Doc. 50257

Transcript of 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

Page 1: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

1

Noti-Fire-NetTM

Doc. 50257

Page 2: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

2

INA

AFP 200

AFP 200

1 SLC loopof 198 points

INA

PRN-4

PRN-4

PRN-4

CRT-2

ACS

ACSAFP-1010

AFP 200

AFP-10102 SLCloops

396points

10 SLCloops1980

points

AM2020

AM2020

S500 with NIB

S5000 with NIB

DigitallyGenerated

VoiceEvacuation

Signals

VAM2020

XP XP

NRT

NRT

Code:

NFN Twisted Pair Wire

NFN Dual Fiber Optic Link

Other Interfaces

RPT-WF24V

24V

24V 24V

INA

VTCC-1

3000 ft

6000 ftTwisted Pair

speakersphones

speakersphones

3000 ftRPT-F

RPT-W

NOTI•FIRE•NETPossib le Node C onfigura tions

Bloc k Diagram

{ {RPT-W

netconfg.c dr

Page 3: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

3

Network Components

Page 4: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

4

Noti-Fire-NetTM

A series of modules and products which allow a group of Fire Alarm Control Panels and other control equipment to connect forming a true peer-to-peer network.

Page 4

Page 5: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

5

Noti-Fire-NetTM

Equipment that connects to NOTI-FIRE-NET and communicates with other equipment using the network may be referred to as a network node. NOTI-FIRE-NET supports up to 103 nodes with a total capacity of 201,960 points. A node may be:AM2020 Fire Alarm Control PanelAFP1010 Fire Alarm Control PanelNRT Network Reporting TerminalAFP-200 with NAM-232 ModuleINA Intelligent Network Annunciator

Page 4

Page 6: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

6

Media Interface Board

The Media Interface Board (MIB) provides the physical interface to the following medium which connects node together forming a network:MIB-W - Two twisted pair wire portsMIB-F - Two fiber optic cable portsMIB-WF - One twisted pair port and one fiber

optic cable portPage 4

Page 7: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

7

Network Adapter Module

NAM-232 Provides a physical interface from the AFP-200 or AM2020/AFP1010 Analog Fire Panel through the EIA-232 data port to the NetworkNAM-232W - Two twisted pair wire portsNAM-232F - Two fiber optic cable ports

Page 5

Page 8: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

8

The Serial Interface Board

The Serial Interface Board (SIB-NET) connects an AM2020 or AFP1010 to the network through an MIB.

Each AM2020/AFP1010 requires a network node address and the SIB-NET permits communication between the AM2020/AFP1010 and other nodes on the network.

The SIB-NET also provides an EIA-232 and EIA-485 output circuits for other external devices.

Page 5

Page 9: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

9

The NRT-NET Board

The NRT-NET interface card and a MIB allow the Network Reporting Terminal (NRT) to communicate with the network.

The NRT-NET interface card plugs directly into a computer expansion slot located on the NRT mother board.

The MIB plugs onto the NRT-NET card to complete the network interface.

Each NRT requires a network node address.Page 5

Page 10: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

10

The Repeaters (RPTs)

The Repeaters (RPT) boost data signals between network nodes extending communication distances.RPT-W supports twisted pair wireRPT-F supports fiber optic cableRPT-WF supports twisted pair wire and fiber

optic cable.Page 5

Page 11: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

11

Related Documents

AM2020/AFP1010 Fire Alarm Control Panel 50119/15088 Liquid Crystal Display (LCD-80) 15037 Network Reporting Terminal (NRT) 15090 Intelligent Network Annunciator (INA) 15092 Universal Zone Coder Installation (UZC-256) 15216 Product Installation Document (CCM-1) 15328 Product Installation Document (MPS-TR) 15331 AM2020/AFP1010 Operator Instructions 15337 Notifier Device Compatibility Document 15378 Analog Fire Panel (AFP-200) 15511 Canadian Requirements for the AM2020/AFP1010 15631 Network Interface Board (NIB-96) 15666 Smoke Control Manual 15712 NR45-24 Charger 15760

Page 6

Page 12: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

12

Related Documents

Annunciator Control System 15842 Lamp Driver Modules (LDM) 15886 The XP Transponder Series 15888 Voice Alarm Multiplex 15889 Network Adapter Module (NAM-232) 50038 The UDACT Universal. Dig. Alarm Comm/Transmitter 50050 FCPS-24/FCPS-24E Field Charger Power Supply 50059 Video Graphics Annunciator System (VGAS) Inst. Manual 50251 Media Interface Board (MIB) 50255 Repeater (RPT) 50256 Telephone/Panel Interface (TPI-232) 50372 Media Evaluation Tool (MET-1) 50480 MMX-2 Installation Instructions M500-03-00

Page 6

Page 13: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

13

NOTI-FIRE-NET Specifications

When designing the wiring layout of a NOTI-FIRE-NET system, the following distance limitations must be considered:1.The length of each individual twisted pair or

fiber optic segment is limited. A segment is either point-to-point of two nodes/repeaters or bus connection (wire only) containing three or mode nodes.

Page 7

Page 14: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

14 NOTI-FIRE-NET Specifications Wire

Example 1 - POINT-TO-POINT Segments

NetworkNode

A B

NetworkNode

A B

NetworkNode

A B

Example 2 - BUS Segments. One BUS Segment may include from three to seven nodes.

NetworkNode

A B

NetworkNode

A B

NetworkNode

A BNetwork

Node

A B

Page 15: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

15

NOTI-FIRE-NET Specifications

NOTI-FIRE-NET distance limitations :Twisted Pair circuitsThe length of cable for each segment in the system must be

within the range specified in Table 1.5-1. If the distance required is greater than permitted, a RPT must be inserted into the circuit.Cable type should be selected to satisfy the code requirement

specific to a particular application.Note: This table has been expanded to include more wire sizes

and styles since original preparation. See the table in the manual for more information.

Page 7

Page 16: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

16 Twisted Pair LengthsTable 1.5-1

ManufacturerPart No.

Spec. DataThreshold

Pointto

Point

Bus

Belden 958014 awg 1pr unshld

FPLR HighLow

1-14001300-3000

1-100n/a

Belden 957216 awg 1pr unshld

FPLR HighLow

1-13001200-3000

1-100n/a

Guardian E2572S18 awg 1pr unshld

Mid-CapFPL, PVC

HighLow

1-12001000-3000

1-100n/a

Atlas 228-18-1TP-218 awg 1pr unshld

Low CapFPL, PVC

HighLow

1-12001000-3000

1-100n/a

Signal 82802-06-1418 awg 1pr unshld

Mid-CapFPLP, PVC

HighLow

1-12001000-2800

1-100n/a

Signal 98181-06-0418 awg 1pr unshld

Mid-CapFPL, PVC

HighLow

1-12001000-2800

1-100n/a

Page 17: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

17 Twisted Pair LengthsTable 1.5-1

ManufacturerPart No.

Spec. DataThreshold

Pointto

Point

Bus

West Penn D98018 awg 1pr unshld

FPL PVC HighLow

1-12001000-3000

1-100n/a

Brand-Rex 93782-0116 awg 1pr shld

Contactmfgr

HighLow

1-14001200-2000

1-100n/a

West Penn AQ22516 awg 1pr unshld

FPL orPLTC

HighLow

1-14001200-2800

1-100n/a

West Penn AQ29416 awg 1pr shld

FPL orPLTC

HighLow

1-10001000-1600

1-100n/a

Atlas 228-18-1STP-218 awg 1pr shld

Low-CapFPL, PVC

HighLow

1-800800-1600

1-100n/a

West Penn D97518 awg 1pr shld

FPL, PVC HighLow

1-800800-1400

1-100n/a

Page 18: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

18 Twisted Pair LengthsTable 1.5-1

ManufacturerPart No.

Spec. DataThreshold

Pointto

Point

Bus

Guardian E2582S18 awg 1pr shld

Mid-CapFPL PVC

HighLow

1-800800-1400

1-100n/a

Signal 84743-06-1418 awg 1pr shld

Mid-CapFPLP, PVC

HighLow

1-600600-1200

1-100n/a

Signal 98281-06-0418 awg 1pr shld

Mid CapFPL, PVC

HighLow

1-600600-1200

1-100n/a

Belden 958114 awg 1pr shld

FPLR HighLow

1-600600-1200

1-100n/a

Belden 957516 awg 1pr shld

FPLR HighLow

1-600600-1200

1-100n/a

Belden 958312 awg 1pr shld

FPLR HighLow

1-600600-1200

1-100n/a

Page 19: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

19 Twisted Pair LengthsTable 1.5-1

ManufacturerPart No.

Spec. DataThreshol

d

Pointto

Point

Bus

Ace Wire 61401SLL14 awg 1pr shld

FPLP HighLow

1-1000800-1400

1-100n/a

RemeeNY5145HHIRHPHB14 awg 1pr shld

FPLP HighLow

1-1000800-1400

1-100n/a

Note: In the event of a power failure at a wire node, the data is not regeneratedlocally, it is merely fed through to the next node. Therefore, the total length ofwire is the sum of both lengths of wire between operating nodes. If the total lengthexceeds the maximum allowable length for a given threshold, the network maylose communication. Separately powered repeaters may be employed at each nodein a point-to-point series connection to ensure data regeneration.

Page 20: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

20

NOTI-FIRE-NET Specifications

NOTI-FIRE-NET distance limitations :Fiber Optic circuitsCable attenuation between two nodes must not exceed a

10 dB limit. Distances greater than permitted require a repeater module inserted at intervals less than or equal to 10 dB.To determine loss, find the rated dB loss per foot and

multiply by the distance required, and add the dB loss for each connector and spliceLoss = ((loss/ft) X (length in feet)) + conn. loss.

Page 10

Page 21: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

21

NOTI-FIRE-NET Specifications

NOTI-FIRE-NET distance limitations :2. System path length is limited and determined

by using Table 1.5-2. The path is defined as the distance of travel from one end of the network to the other, and is influenced by the number of MIB, NAM and RPT devices, and medium of the circuit path.

Page 10

Page 22: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

22

System Path Length

System Path Length = Sum of the length of Segments 1, 2, 3, 4, and 5.

NetworkNode

A B

12

3

4

5Network

Nodeor

Repeater

A B

NetworkNode

orRepeater

A BNetwork

Nodeor

Repeater

A B

NetworkNode

orRepeater

A B

NetworkNode

A B

Page 23: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

23 Node versus Medium Distance Table 1.5-2

900,000

800,000

700,000

600,000

500,000

400,000

300,000

200,000

100,000

00 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750

Page 24: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

24

Minimum Requirements

An NRT or INA and a fire panel with initiating devices and notification appliances define the minimum system requirements for a NOTI-FIRE-NET.For each AM2020/AFP1010 panel configured

for NFPA 72-1993 Local Fire Alarm System a CMX module set at Loop 1, address 96 with Type ID EVGA is also required.

Page 11

Page 25: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

25

NFPA Style 4 Configuration

Noti-Fire-Net is capable of communicating using NFPA Style 4 SLC.Under this style of operation, a single open, wire-to-wire

short, wire-to-wire short and open, wire-to-wire short and ground, or open and ground results in fragmentation of the network.

A single ground does not affect communication, but is detected.

Each fragment of the network reconfigures to permit communications among nodes within the fragment.

Page 12

Page 26: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

26

NFPA Style 4 Configuration

NOTEA wire-to-wire short hereresults in loss of commu-nication between all fournodes/repeaters on thisbus connection as well asfragmentation of the net-work. Bus connectionsshould be no longer than100’ within conduit or thesame enclosure.

NFPA Style 4 SLCWithout Regeneration

(Bus Connection)

KEY=Network Nodewith Two Ports

(A & B)

A B

A B

A B

A B

AB

AB

AB

A B

NFPA Style 4 SLCWith Regeneration

(Point-to-Point Connections

A BA B

Point-to-PointConnection

A B

A B

A B

Point-to-PointConnection

Point-to-PointConnection

Page 27: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

27

NFPA Style 4 Configuration

In an NFPA Style 4 fiber-optic system, a single break will result in loss of communication between network nodes within the fragment of the network that can only receive signals from the other fragment.

Page 13

NetworkNode

A B

NetworkNode

A B

NetworkNode

A B

NetworkNode

A B

BreakThese nodes continueto communicate

These nodes continueto communicate

Communication is partiallylost between these nodes

Page 28: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

28

NFPA Style 7 Configuration

Noti-Fire-Net is capable of communicating using NFPA Style 7 SLC.Under this style of operation, a single open, wire-to-wire

short, wire-to-wire short and open, wire-to-wire short and ground, or open and ground will not result in fragmentation of the network.

A single ground does not affect communication, but is detected.

Style 7 operation may be achieved using fiber optic cable or mixed media (wire and fiber)

Page 12

Page 29: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

29

NFPA Style 7 Configuration

A B

AB

A B

A BA BA B

KEY=Network Nodewith Two Ports

(A & B)

A B

NFPA Style 7 With Regeneration(Twisted Pair Wire,

Point-to-Point Connections,or Transmit and ReceiveFiber Optic Cable Pairs)

NOTEBuss connections are not permitted

in a Style 7 system

Page 30: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

30

Configuration Definitions

Point-to-Point wiring configuration is defined as a twisted-pair segment with only two nodes/ repeaters attached to it. Terminating resistors are required at each end of every segment, and are built into each MIB, NAM-232, and RPT.

Page 14

NetworkNode

or RPT

A B

NetworkNode

or RPT

A B

NetworkNode

or RPT

A B

NetworkNode

or RPT

A B

Page 31: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

31

Configuration Definitions

Characteristic Impedance in a Point-to-Point ConfigurationWire segment of each connection is a transmission

line.Physical construction of the cable used determines the

characteristic impedance of that segment.To minimize unwanted data reflections, never mix

more than one brand name, gauge or type of wire within a segment.

Page 14

Page 32: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

32

Configuration Definitions

NetworkNode

orRepeater

A BNetwork

Nodeor

Repeater

A B

NetworkNode

orRepeater

A B

NetworkNode

orRepeater

A B

NetworkNode

A B

NetworkNode

A B

Add this segmentfor a Style 7 System

NFPA Style 4 or Style 7 SystemPoint-to-Point Configuration

Page 33: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

33

Bus ConfigurationA bus wiring configuration is defined as a twisted pair

network with more than two nodes. Terminating resistors are only needed on the first and last node of the bus pair, all other resistor must be removed.

Page 16

NetworkNode

or RPT

NetworkNode

or RPT

NetworkNode

or RPT

NetworkNode

or RPT

A B A B A BA B

Page 34: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

34

Bus Configuration

In a bus configuration, more than one node /repeater shares the same circuit.

A fault anywhere along the bus will affect the rest of the nodes/ repeaters on the bus.

Because of their inherent weakness, bus configurations are best employed for wiring between nodes/repeaters local to each other (within the same cabinet or room).

Page 16

Page 35: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

35

Bus Configuration

Wiring Distances Between Nodes on a BusIn a bus configuration, data is shared between

all ports on the twisted pair, thereby reducing the allowable transmission distance to a maximum of 100 ft.

Page 16

Page 36: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

36

Bus Configuration

Characteristic Impedance in a Bus ConfigurationThe wire segment for each bus connection is a transmission line.The physical construction of the twisted-pair cable used for a

segment determines the characteristic impedance of that segment.

To minimize unwanted data reflections, never mix more than one brand name, gauge, or type of wire within a bus segment.

Always make bus connections at the module terminals provided.Do not make branch connections at other points.

Page 16

Page 37: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

37

Combination Configuration

RemoteBuilding

RemoteBuilding

RemoteBuilding

RemoteBuilding

CentralFacility

NetworkNode

A B

NetworkNode

A B

NetworkNode

A B

NetworkNode

A B

Repeater

A B

NetworkNode

A B

Repeater

A B

NetworkNode

A B

A Combination configuration can be used to distribute the network circuit from a central facility, saving on wiring run lengths.

A repeater is bus-wired to two existing nodes in each central facility (located in the same room) to support point-to-point connections in the remaining buildings in the system.

Page 17

Page 38: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

38 Terminating Point-to-Point and Bus Configurations

Both point-to-point and bus twisted wire pair configurations require end-of-line termination at each end of the respective circuit.

Whereas a point-to-point circuit has a terminating resistor at each node/repeater port, a bus circuit spans multiple nodes/repeaters, with termination only at the outer edges of the circuit.

Page 18

Page 39: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

39 Terminating Point-to-Point and Bus Configurations

Terminating resistors are present on all MIBs, NAMs, and repeaters. The terminating resistor on the first and last nodes/repeaters of a wire segment must remain intact. The terminating resistors on all the other nodes/repeaters connected to the same bus segment must be cut and removed from each board.

Page 18

Page 40: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

40 On-Board Terminating ResistorsTable 1.10-1

Module \ Port Port A Port B

RPT-W R40 R41

RPT-WF R40 N/A

MIB-W R20 R21

MIB-WF R20 N/A

NAM-232W R69 R70

Page 41: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

41

On-Board Terminating Resistors

NetworkNode

A B

NetworkNode

A B

NetworkNode

A B

These point-to-point segments are terminated at each node/repeater.

Point-to-Point Termination

Page 42: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

42

On-Board Terminating Resistors

NetworkNode

A B

NetworkNode

A B

NetworkNode

A B

NetworkNode

orRepeater

A B

NetworkNode

orRepeater

A B

NetworkNode

orRepeater

A B

A point-to-pointcircuit link, termi-nated at each end

with a resistor

A point-to-pointcircuit link, termi-nated at each end

with a resistor

A point-to-pointcircuit link, termi-nated at each end

with a resistor

A bus circuit spans multiple nodes/repeaters with a terminating resistor at each end of the circuit link.

Bus Termination

Page 43: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

On-Board Terminating Resistors

On boardterminatingresistor

Bus Configuration

Point-to-PointConfiguration

Page 44: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

44 Network Wiring Ground Fault Detection

Twisted pair communications links between nodes can be isolated through the MIB/ NAM transformer coupling, so a single ground fault has no effect on circuit operation.Ground fault of the isolated link is not necessary

unless required by LAHJ.Ground fault detection from a node power supply

may be fed-through or disabled at the MIB/NAM.Page 20

Page 45: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

45 Network Wiring Ground Fault Detection

Media Interface Board (MIB)SW1 corresponds to Channel

ASW2 corresponds to Channel

B

Network Adapter Module (NAM-232)JP1 corresponds to Channel AJP2 corresponds to Channel B

Page 20

Switch set ON to enableground fault feed-through.

Switch set OFF to disableground fault feed through

321

321

Jumper set ON to enableground fault feed-through.

Jumper set OFF to disableground fault feed through

Page 46: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

46 Network Wiring Ground Fault Detection

Ground fault circuit operation:Ground fault detection may be provided by a

FACP node which is powered by a MPS-24A or by an AFP-200 connected with a NAM-232.INA and NRT cannot provide ground fault

detection. Switches SW1 and SW2 on the INA or NRT must always be off.

Page 20

Page 47: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

47 Network Wiring Ground Fault Detection

Point-to-Point Configuration In point-to-point without repeaters, enable ground fault

in only one of two nodes.Page 20

Network Node

PowerSupply

GF DetectionEnabled

A

SW2

OFF

MIB-W

Ports B

PowerSupply

GF DetectionEnabled

B

SW2

ON

MIB-W

Network Node

PortsA

Page 48: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

48 Network Wiring Ground Fault Detection

Point-to-Point ConfigurationIf an RPT-W is used, two ground fault

detection schemes are possible. One or both nodes may provide detection depending on the RPT pass through switch (SW3) Setting.

Page 21

Page 49: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

49 Network Wiring Ground Fault Detection

Point-to-point Left side node provides detection. Port B SW2 is ON. RPT passes through detection. SW3 is ON. Right node blocks detection. Port A SW1 is OFF.

Page 21

Network Node

PowerSupply

GF DetectionEnabled

A B

MIB-W

SW2

OFF

Network Node

SW2

ON

RPT-W

PortsA B

PowerSupply

GF DetectionEnabled

A

SW2

ON

MIB-W

Ports B Ports

Page 50: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

50 Network Wiring Ground Fault Detection

Point-to-Point Left side node provides detection. Port B SW2 is ON. RPT blocks detection. SW3 is OFF. Right node provides detection. Port A SW1 is ON.

Page 21

Network Node

Ports

PowerSupply

GF DetectionEnabled

A B

MIB-W

SW2

ON

Network Node

Ports

PowerSupply

GF DetectionEnabled

A B

SW2

ON

MIB-W

Ports

SW2

OFF

RPT-W

A B

Page 51: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

51 Network Wiring Ground Fault Detection

Ground fault detection feed-through is effective for a maximum of two point-to-point repeaters.

A maximum of 5 repeaters can be serially connected for proper ground fault operation.

Page 21

ON

NODE

ON

NODE

ON

RPT

ON

RPT

ON

RPT

ON

RPT

OFF

RPT

Page 52: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

52 Network Wiring Ground Fault Detection

Bus ConfigurationIn a bus configuration, as in point-to-point,

only one node can provide ground fault detection along the bus.The primary difference is that one node can

provide ground fault detection for multiple nodes along the bus.

Page 22

Page 53: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

53 Network Wiring Ground Fault Detection

Bus Configuration 2nd node from right provides ground fault detection. All other nodes have ground fault disabled. Note: Termination resistors removed from pass-through bus ports.

Page 22

Ports

PowerSupply

A B

SW2

OFF

MIB-W

PowerSupply

A

MIB-W

SW2OFF

Ports

PowerSupply

GF DetectionEnabled

A B

MIB-W

SW2

ON

Ports

PowerSupply

A B

MIB-W

SW2

OFF

Ports B

SW2

ON

RPT-W

A B

Page 54: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

54 Network Wiring Ground Fault Detection

Bus Configuration Node on the left and 2nd node from right provide ground fault detection,

and RPT SW3 is off to prevent pass through. This creates two separate ground fault circuits. All other nodes have ground fault disabled.

Page 22

PowerSupply

GF DetectionEnabled

A B

SW2

ON

MIB-W

PowerSupply

GF DetectionEnabled

A B

MIB-W

SW2

ON

PowerSupply

A B

MIB-W

SW2

OFF

PowerSupply

A

MIB-W

SW2

OFF

B

SW2

OFF

RPT-W

A B

Page 55: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

55

FCC Considerations

In order to comply with FCC regulations regarding radio frequency emissions, a ferrite cylinder (Notifier p/n 29087) must be installed on every twisted pair circuit connected to a MIB-W (two cylinders included) and MIB-WF (one cylinder included).

Page 20

Page 56: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

56

FCC Considerations

NRT Installation Thread the twisted pair(s) through the ferrite cylinder. Slide the cylinder along the pair(s) toward the MIB on the back of the NRT so that the closest

edge of the cylinder is no more than 3 inches away from the terminal connection block. Secure the ferrite cylinder to the wiring with the supplied toe wrap at each end of the cylinder.

Page 23

Page 57: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

57

FCC Considerations

INA & SIB-NET Installation Thread the twisted pair(s) through the ferrite cylinder. Slide the cylinder along the pairs toward the entrance point on the cabinet (not toward the MIB)

so that the edge of the cylinder and the cabinet are separated by no more than three inches. Secure the ferrite cylinder to the wiring with the supplied tie wrap at each end of the cylinder. Repeat for the second MIB-W port.

Page 23

Page 58: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

58

Tips and Techniques

Ground LoopWaveform

Surge Waveform

DigitalSignal

How to recognize and fix ground loops It’s important to realize that a ground loop is not the same as a surge.

A ground loop is a consistent electrical state, causing a steady high voltage with high current capability. A voltage surge, although it may be higher and more powerful, is typically an induced voltage with a very fast rise time.

Page 59: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

59

Noti-Fire-Net Data Pulse

L

TL

H

TH

The two thresholds available are HIGH (1.4 Volts) and LOW (800mV). If the pulse width = 2.1 at the HIGH(TH, 1.4V) and 2.4 at the LOW(TL, .8V), the threshold should be set to HIGH. The main criteria is to look for is a pulse width => 1.1 uSec at each threshold.

Page 60: 1 Noti-Fire-Net TM Doc. 50257. 2 3 Network Components.

60