1 © ABB AB, 2008 2008-02-05 Multi-terminal Line Differential Protection Installed on Series...
-
Upload
shona-chapman -
Category
Documents
-
view
214 -
download
1
Transcript of 1 © ABB AB, 2008 2008-02-05 Multi-terminal Line Differential Protection Installed on Series...
1
©A
BB
AB
, 20
08
2008-02-05
Multi-terminal Line Differential Protection Installed on Series Compensated, 400kV Line with Five-Ends
Zoran Gajić
ABB AB
Vasteras, Sweden
Authors:Z. Gajić, ABB SwedenI. Brnčić, ABB Sweden F. Rios, Svenska Kraftnät
2
©A
BB
AB
, 20
08
2008-02-05
Application Description
The following data are valid for this application:
Positive sequence line impedance
Zero sequence line impedance
Total series capacitor reactance
this corresponds to the impedance of 400kV line with length of 265km
~211km
~92km
~74km~0.1km
400kV Station #1
400kV Station #2
400kV Station #3
-jXc
(0.018 0.275)j km
(0.26 0.982)j km
73j
3
©A
BB
AB
, 20
08
2008-02-05
Application Description
The following data are valid for this application:
Line three-phase reactive power generation 657.5 kVAr/km at 400kV (circa 350A per phase of charging current at 400kV over the whole length of the protected line). This corresponds to phase to ground fault with resistance of 650 Ohms primary.
Main CT involved in this scheme have ratio:
2000/2 in Station #1, 3000/1 in Station #2 2400/2 in Station #3.
~211km
~92km
~74km~0.1km
400kV Station #1
400kV Station #2
400kV Station #3
-jXc
4
©A
BB
AB
, 20
08
2008-02-05
For this installation master-master differential protection principle is used (i.e. every differential relay had all five currents available and is able to perform the differential protection algorithm).
Distance protection is included in each differential relay in order to provide reserve protection for the line.
The line differential protection scheme uses a telecommunication SDH/PDH network with unspecified route switching. Therefore differential relays utilize the GPS for the time synchronization. In the substations there are 16 x G.703 64 kbit/s channels. The following SDH/PDH configuration is used:
SDH multiplexing (STM-1 or STM-4)à 8 x 2 Mbit/s (E1) à PDH multiplexing à 16 x 64 kbit/s (E0).
Communication Setup
5
©A
BB
AB
, 20
08
2008-02-05
Overall System Setup
SDH/PDH network
~211km
~92km
~74km~0.1km
400kV Station #1
400kV Station #2
400kV Station #3
-jXc
6
©A
BB
AB
, 20
08
2008-02-05
Differential Operating Characteristic
Differential current (Operate current) is the vectorial sum of measured currents at all line ends and it is calculated separately for each phase
Bias current (Restrain current) is considered as the greatest phase current in any line end and it is common for all three phases
Dual slope characteristic is used
Unrestraint differential level is available
IdMinHigh used during initial line energizing
Section 1
UnrestrainedLimit
Section 2 Section 3
Restrain
Operate
unconditionally 5
4
3
2
1
0
0 1 2 3 4 5
IdMin
EndSection1
EndSection2
Restrain current[ in pu of IBase]
Operate current[ in pu of IBase]
SlopeSection2
SlopeSection3
Operate
conditionallyIdMinHigh
AC
B
7
©A
BB
AB
, 20
08
2008-02-05
External/Internal Fault Discriminator
Based on theory of symmetrical components
It utilize the negative sequence current component from all ends of the protected line
Directional comparison principle is applied
Negative sequence current component from the local end is compared with the sum of the negative sequence current components from all remote ends
When these two phasors are in phase fault is internal
When these two phasors are in contra-phase fault is external
NegSeqROA (Relay
Operate Angle)
0 deg180 deg
90 deg
270 deg
120 deg
IMinNegSeq
If one or the other of currents is too low, then no measurement is done, and 120 degrees is mapped
External fault region
Internal fault region
Internal/external fault boundary
8
©A
BB
AB
, 20
08
2008-02-05
Problem of Charging Current for Long Lines
R
UB
I
C2
C2
ICBICAUA
CT CTL
Capacitance of the protected line causes false differential current to be measured by IED
Π – equivalent circuit can be used to estimate the charging current if voltage measurement on both end of the line is available
Charging currents are symmetrical (i.e. they exist mostly as positive sequence current component)
9
©A
BB
AB
, 20
08
2008-02-05
Problem of Charging Current for Long Lines
By using voltage derivative charging current can be estimated It is only APROXIMATE method because the Π – equivalent circuit
is too simplified and do not represent properly the line especially during transient conditions
Problem for more complex line configurations: Series compensation Multi-terminal lines HV cables
+
-
S Fourierfilter
Communicationunit
Differentialprotectionalgorithm
Trip
dUdt
CIcc
U
I
10
©A
BB
AB
, 20
08
2008-02-05
Why Charging Current is Required?
To make line differential protection sensitive for high resistance faults
Is there any more general method which will work for independently from the primary system set-up?
11
©A
BB
AB
, 20
08
2008-02-05
Assumption for New Charging Current Algorithm
During high resistance faults voltage drop will be quite small therefore the charging current just before and after the fault inception will be approximately the same
For heavy external or internal faults influence of charging current will be practically negligible
12
©A
BB
AB
, 20
08
2008-02-05
New Charging Current Algorithm
Differential function learns the false symmetrical differential current over a period of time (i.e. it consider all three phases simultaneously)
Once this value is learned it is simply subtracted from the presently measured RMS currents in every phase
Any change in measured currents freezes charging current estimation Algorithm is adaptive and does not need to know anything about primary
system setup, however it needs some short time before it becomes effective
Voltage measurement is not required Only end user setting is to enable or disable it (i.e. On/Off)
13
©A
BB
AB
, 20
08
2008-02-05
Charging Current Compensation Principle
0 20 40 60 80 100 120 140 160 180-100
-50
0
50
100
time since start in ms
Inst
anta
neou
s di
ff.
curr
.
Instantaneous differential currents, and fundamental frequency diff. currents
instDifCurr L1
instDifCurr L2
instDifCurr L3
0 20 40 60 80 100 120 140 160 1800
20
40
60
time since start in ms
Fun
d. f
req.
diff
. cu
rr.
difCurr L1
difCurr L2
difCurr L3
L1 L2 L3function ON
differentialfunctionswitchedON
Currents low,symmetricaland not changing
DFFtransients
Charging currentscompensated in approx. 100 ms
Compensationstarts step bystep
Note that only RMS differential current are compensated, not the instantaneous differential current values
Both of them are available from IED as service value and to the built-in disturbance recorder
14
©A
BB
AB
, 20
08
2008-02-05
Recorded Internal Faults
Two captured recordings in this installation are presented in the paper.
Both recordings were captured by line differential protection IED installed in Station #3.
The first recording is an internal L2-L3-Gnd fault which was caused by lightning. The fault location was estimated to be 99km from Station #1 and estimated fault resistance was around 24 Ohms primary.
The second recording is an internal L2-Gnd fault. The fault location was estimated to be 7km from Station #1 and the fault resistance was estimated to be around 8 Ohms primary. The cause of this fault is unknown.
Differential protection has operated properly for both internal faults.
15
©A
BB
AB
, 20
08
2008-02-05
Internal Fault No 1; Recorded Diff Currents
L1-DIFF L2-DIFF L3-DIFF t/s-0,075 -0,050 -0,025 0,000 0,025 0,050 0,075 0,100 0,125one-10000-500005000
Instantaneous Diff Currents
BIAS IDIFF L1 RMS IDIFF L2 RMS IDIFF L3 RMS NEG SEQ DIFF t/s-0,075 -0,050 -0,025 0,000 0,025 0,050 0,075 0,100 0,125I/kA0246
Diff RMS Quantities
Present before the fault
Zero before the fault
16
©A
BB
AB
, 20
08
2008-02-05
Internal Fault No 2; Recorded Diff Currents
BIAS IDIFF L1 RMS IDIFF L2 RMS IDIFF L3 RMS NEG SEQ DIFF t/s-0,075 -0,050 -0,025 0,000 0,025 0,050 0,075I/kA0,02,55,0
L1-DIFF L2-DIFF L3-DIFF t/s-0,075 -0,050 -0,025 0,000 0,025 0,050 0,075one-10000-500005000
Diff RMS Quantities
Instantaneous Diff Currents
Present before the fault
Zero before the fault
17
©A
BB
AB
, 20
08
2008-02-05
L1-DIFF L2-DIFF L3-DIFF t/s-0,08 -0,06 -0,04 -0,02 0,00 0,02 0,04 0,06 0,08one-500005000
BIAS IDIFF L1 RMS IDIFF L2 RMS IDIFF L3 RMS t/s-0,08 -0,06 -0,04 -0,02 0,00 0,02 0,04 0,06 0,08I/kA024
Internal Fault No 3 Summer 09; Recorded Diff Currents
Diff RMS Quantities
Instantaneous Diff Currents
Present before the fault
Zero before the fault
18
©A
BB
AB
, 20
08
2008-02-05
The proposed charging current compensation method, independent from voltage measurements, seems to work very well for such long, series-compensated overhead line configurations.
It has been shown that the multi-terminal line differential protection is a good solution for protection of long, series-compensated, high-voltage lines with more than two ends.
Combination of multi-terminal line differential protection and distance protection provides good protection solution for such lines.
Differential protection is in service for almost two years with correct behavior
Conclusion
19
©A
BB
AB
, 20
08
2008-02-05
СПАСИБО
ЗА ВНИМАНИЕ!
THANK YOU!