MV90 IP Data Transport ERCOT Recommendation John Fisher Jeff Maddox.
09hv-mv90-cw.pdf
-
Upload
abeltoledofuentes -
Category
Documents
-
view
214 -
download
0
Transcript of 09hv-mv90-cw.pdf
MEDIUM-EXTRA HIGH VOLTAGE POWER CABLES
Phelps Dodge International (Thailand) Limited.
Maneeya Center Building, 16th Floor, 518/5 Ploenchit Rd., Lumpinee, Pathumwan, Bangkok 10330 Telephone : (66 2) 680 5800 Fax : (66 2) 680 5896, 680 5898 Website : http://www.pdic.co.th/
© 2012 Phelps Dodge International (Thailand) Limited. All rights reserved.
Revision : November 2012 Page 1 of 5
Note : When desired for manufacturing reasons, the semi-conducting tape may be applied over stranded bare copper conductor.
APPLICATION :
For use in aerial, conduit and underground duct installation.
CLASSIFICATION :
5 to 35 kV rating sunlight resistance, AC and DC, 100% IL and 133% IL, maximum conductor temperature 90°C for normal operation, 130°C for emergency overload condition and 250°C for short circuit condition.
REFERENCE STANDARD :
UL 1072
PHELPS DODGE CONDUCTOR TYPE MV 90
CONSTRUCTION :
Stranded bare copper : Compact-stranded annealed uncoated copper. per ASTM B-496 and UL 1072 Extruded semi-conducting strand shield : Extruded semi-conducting cross-linked polyethylene compound. Insulation : Cross-linked polyethylene (XLPE). Extruded semi-conducting insulation shield : Extruded semi-conducting cross-linked polyethylene compound. Bare copper wire shield : Uncoated helically applied copper wires.
Tape separator : Polyester non-woven tape Sunlight resistant PVC sheath : Extruded PVC sheath " Sunlight resistant".
MEDIUM-EXTRA HIGH VOLTAGE POWER CABLES
Phelps Dodge International (Thailand) Limited.
Maneeya Center Building, 16th Floor, 518/5 Ploenchit Rd., Lumpinee, Pathumwan, Bangkok 10330 Telephone : (66 2) 680 5800 Fax : (66 2) 680 5896, 680 5898 Website : http://www.pdic.co.th/
© 2012 Phelps Dodge International (Thailand) Limited. All rights reserved.
Revision : November 2012 Page 2 of 5
PHELPS DODGE CONDUCTOR TYPE MV 90
SizeConductor
Diameter
Insulation
Thickness
No./Wire Size of
Copper Shield
Sheath
Thickness
Approx.
Outside
Diameter
Approx. Cable
Weight
(AWG or kcmil) (mm) (mm) (mm) (mm) (mm) (kg / km)
2 6.8 2.29 20 / 0.8 1.52 21 635 190
1 7.6 2.29 20 / 0.8 1.52 21 725 225
1/0 8.6 2.29 20 / 0.8 1.52 22 840 260
2/0 9.6 2.29 20 / 0.8 2.03 24 1,035 300
4/0 12.1 2.29 20 / 0.8 2.03 27 1,440 400
250 13.2 2.29 20 / 0.8 2.03 28 1,650 445
350 15.7 2.29 20 / 0.8 2.03 31 2,145 550
500 18.7 2.29 20 / 0.8 2.03 34 2,885 695
750 23.0 2.29 20 / 0.8 2.03 39 4,175 900
1000 26.9 2.29 20 / 0.8 2.03 43 5,395 1,075
Ampacities**
** Ampacities for one insulated conductor isolated in air based on conductor temperature of 90°C and ambient air temperature of
40°C per Table 310-69 of the 1990 National Electrical Code (NFPA 70-1990)
SizeConductor
Diameter
Insulation
Thickness
No./Wire Size of
Copper Shield
Sheath
Thickness
Approx.
Outside
Diameter
Approx. Cable
Weight
(AWG or kcmil) (mm) (mm) (mm) (mm) (mm) (kg / km)
2 6.8 2.29 20 / 0.8 1.52 21 635 190
1 7.6 2.29 20 / 0.8 1.52 21 725 225
1/0 8.6 2.29 20 / 0.8 1.52 22 840 260
2/0 9.6 2.29 20 / 0.8 2.03 24 1,035 300
4/0 12.1 2.29 20 / 0.8 2.03 27 1,440 400
250 13.2 2.29 20 / 0.8 2.03 28 1,650 445
350 15.7 2.29 20 / 0.8 2.03 31 2,145 550
500 18.7 2.29 20 / 0.8 2.03 34 2,885 695
750 23.0 2.29 20 / 0.8 2.03 39 4,175 900
1000 26.9 2.29 20 / 0.8 2.03 43 5,395 1,075
Ampacities**
** Ampacities for one insulated conductor isolated in air based on conductor temperature of 90°C and ambient air temperature of
40°C per Table 310-69 of the 1990 National Electrical Code (NFPA 70-1990)
MEDIUM-EXTRA HIGH VOLTAGE POWER CABLES
Phelps Dodge International (Thailand) Limited.
Maneeya Center Building, 16th Floor, 518/5 Ploenchit Rd., Lumpinee, Pathumwan, Bangkok 10330 Telephone : (66 2) 680 5800 Fax : (66 2) 680 5896, 680 5898 Website : http://www.pdic.co.th/
© 2012 Phelps Dodge International (Thailand) Limited. All rights reserved.
Revision : November 2012 Page 3 of 5
PHELPS DODGE CONDUCTOR TYPE MV 90
SizeConductor
Diameter
Insulation
Thickness
No./Wire Size of
Copper Shield
Sheath
Thickness
Approx.
Outside
Diameter
Approx. Cable
Weight
(AWG or kcmil) (mm) (mm) (mm) (mm) (mm) (kg / km)
2 6.8 4.45 20 / 0.8 2.03 26 820 195
1 7.6 4.45 20 / 0.8 2.03 27 920 225
1/0 8.6 4.45 20 / 0.8 2.03 28 1,045 260
2/0 9.6 4.45 20 / 0.8 2.03 29 1,195 300
4/0 12.1 4.45 20 / 0.8 2.03 31 1,615 400
250 13.2 4.45 20 / 0.8 2.03 33 1,835 445
350 15.7 4.45 20 / 0.8 2.03 36 2,375 550
500 18.7 4.45 20 / 0.8 2.03 39 3,135 685
750 23.0 4.45 20 / 0.8 2.03 44 4,430 885
1000 26.9 4.45 20 / 0.8 2.79 49 5,830 1,060
Ampacities**
** Ampacities for one insulated conductor isolated in air based on conductor temperature of 90°C and ambient air temperature of
40°C per Table 310-69 of the 1990 National Electrical Code (NFPA 70-1990)
SizeConductor
Diameter
Insulation
Thickness
No./Wire Size of
Copper Shield
Sheath
Thickness
Approx.
Outside
Diameter
Approx. Cable
Weight
(AWG or kcmil) (mm) (mm) (mm) (mm) (mm) (kg / km)
2 6.8 5.46 20 / 0.8 2.03 26 895 195
1 7.6 5.46 20 / 0.8 2.03 29 995 225
1/0 8.6 5.46 20 / 0.8 2.03 30 1,125 260
2/0 9.6 5.46 20 / 0.8 2.03 31 1,280 300
4/0 12.1 5.46 20 / 0.8 2.03 33 1,705 400
250 13.2 5.46 20 / 0.8 2.03 35 1,930 445
350 15.7 5.46 20 / 0.8 2.03 38 2,480 550
500 18.7 5.46 20 / 0.8 2.03 41 3,250 685
750 23.0 5.46 20 / 0.8 2.79 47 4,710 885
1000 26.9 5.46 20 / 0.8 2.79 52 6,020 1,060
Ampacities**
** Ampacities for one insulated conductor isolated in air based on conductor temperature of 90°C and ambient air temperature of
40°C per Table 310-69 of the 1990 National Electrical Code (NFPA 70-1990)
MEDIUM-EXTRA HIGH VOLTAGE POWER CABLES
Phelps Dodge International (Thailand) Limited.
Maneeya Center Building, 16th Floor, 518/5 Ploenchit Rd., Lumpinee, Pathumwan, Bangkok 10330 Telephone : (66 2) 680 5800 Fax : (66 2) 680 5896, 680 5898 Website : http://www.pdic.co.th/
© 2012 Phelps Dodge International (Thailand) Limited. All rights reserved.
Revision : November 2012 Page 4 of 5
PHELPS DODGE CONDUCTOR TYPE MV 90
SizeConductor
Diameter
Insulation
Thickness
No./Wire Size of
Copper Shield
Sheath
Thickness
Approx.
Outside
Diameter
Approx. Cable
Weight
(AWG or kcmil) (mm) (mm) (mm) (mm) (mm) (kg / km)
1 7.6 6.60 20 / 0.8 2.03 31 1,095 225
1/0 8.6 6.60 20 / 0.8 2.03 32 1,225 260
2/0 9.6 6.60 20 / 0.8 2.03 33 1,380 300
4/0 12.1 6.60 20 / 0.8 2.03 36 1,845 395
250 13.2 6.60 20 / 0.8 2.03 37 2,075 440
350 15.7 6.60 20 / 0.8 2.03 40 2,605 545
500 18.7 6.60 20 / 0.8 2.03 43 3,385 680
750 23.0 6.60 20 / 0.8 2.79 50 4,865 870
1000 26.9 6.60 20 / 0.8 2.79 54 6,195 1,040
Ampacities**
** Ampacities for one insulated conductor isolated in air based on conductor temperature of 90°C and ambient air temperature of
40°C per Table 310-69 of the 1990 National Electrical Code (NFPA 70-1990)
SizeConductor
Diameter
Insulation
Thickness
No./Wire Size of
Copper Shield
Sheath
Thickness
Approx.
Outside
Diameter
Approx. Cable
Weight
(AWG or kcmil) (mm) (mm) (mm) (mm) (mm) (kg / km)
1 7.6 8.76 20 / 0.8 2.03 36 1,320 225
1/0 8.6 8.76 20 / 0.8 2.03 37 1,460 260
2/0 9.6 8.76 20 / 0.8 2.03 38 1,625 300
4/0 12.1 8.76 20 / 0.8 2.03 40 2,080 395
250 13.2 8.76 20 / 0.8 2.03 42 2,315 440
350 15.7 8.76 20 / 0.8 2.79 46 3,005 545
500 18.7 8.76 20 / 0.8 2.79 49 3,815 680
750 23.0 8.76 20 / 0.8 2.79 54 5,235 870
1000 26.9 8.76 20 / 0.8 2.79 58 6,545 1,040
Ampacities**
** Ampacities for one insulated conductor isolated in air based on conductor temperature of 90°C and ambient air temperature of
40°C per Table 310-69 of the 1990 National Electrical Code (NFPA 70-1990)
MEDIUM-EXTRA HIGH VOLTAGE POWER CABLES
Phelps Dodge International (Thailand) Limited.
Maneeya Center Building, 16th Floor, 518/5 Ploenchit Rd., Lumpinee, Pathumwan, Bangkok 10330 Telephone : (66 2) 680 5800 Fax : (66 2) 680 5896, 680 5898 Website : http://www.pdic.co.th/
© 2012 Phelps Dodge International (Thailand) Limited. All rights reserved.
Revision : November 2012 Page 5 of 5
PHELPS DODGE CONDUCTOR TYPE MV 90
SizeConductor
Diameter
Insulation
Thickness
No./Wire Size of
Copper Shield
Sheath
Thickness
Approx.
Outside
Diameter
Approx. Cable
Weight
(AWG or kcmil) (mm) (mm) (mm) (mm) (mm) (kg / km)
1/0 8.6 8.76 20 / 0.8 2.03 37 1,406 260
2/0 9.6 8.76 20 / 0.8 2.03 38 1,625 300
4/0 12.1 8.76 20 / 0.8 2.03 40 2,080 395
250 13.2 8.76 20 / 0.8 2.03 42 2,315 440
350 15.7 8.76 20 / 0.8 2.79 46 3,005 545
500 18.7 8.76 20 / 0.8 2.79 49 3,815 680
750 23.0 8.76 20 / 0.8 2.79 54 5,235 870
1000 26.9 8.76 20 / 0.8 2.79 58 6,545 1,040
Ampacities**
** Ampacities for one insulated conductor isolated in air based on conductor temperature of 90°C and ambient air temperature of
40°C per Table 310-69 of the 1990 National Electrical Code (NFPA 70-1990)
SizeConductor
Diameter
Insulation
Thickness
No./Wire Size of
Copper Shield
Sheath
Thickness
Approx.
Outside
Diameter
Approx. Cable
Weight
(AWG or kcmil) (mm) (mm) (mm) (mm) (mm) (kg / km)
1/0 8.6 10.67 20 / 0.8 2.03 41 1,670 260
2/0 9.6 10.67 20 / 0.8 2.03 42 1,840 300
4/0 12.1 10.67 20 / 0.8 2.79 46 2,450 395
250 13.2 10.67 20 / 0.8 2.79 47 2,700 440
350 15.7 10.67 20 / 0.8 2.79 50 3,270 545
500 18.7 10.67 20 / 0.8 2.79 53 4,140 680
750 23.0 10.67 20 / 0.8 2.79 58 5,550 870
1000 26.9 10.67 20 / 0.8 2.79 62 6,880 1,040
Ampacities**
** Ampacities for one insulated conductor isolated in air based on conductor temperature of 90°C and ambient air temperature of
40°C per Table 310-69 of the 1990 National Electrical Code (NFPA 70-1990)