0870203597 NC0100-0300B WCV Ex -0001 IM en

60
Instruction Manual COBRA ATEX Dry Screw Vacuum Pumps NC 0100-0300 B (water-cooled version) 0870203597/-0001_en / Original instructions / Modifications reserved 11/12/2019 Ateliers Busch S.A. Zone industrielle, 2906 Chevenez Switzerland

Transcript of 0870203597 NC0100-0300B WCV Ex -0001 IM en

Page 1: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Instruction ManualCOBRA ATEXDry Screw Vacuum PumpsNC 0100-0300 B (water-cooled version)

0870203597/-0001_en / Original instructions / Modifications reserved 11/12/2019

Ateliers Busch S.A.Zone industrielle, 2906 ChevenezSwitzerland

Page 2: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Table of Contents

2 / 60 0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en

Table of Contents1 Safety........................................................................................................................... 4

2 Product Description ..................................................................................................... 5

2.1 Operating Principle...............................................................................................8

2.2 Application ...........................................................................................................8

2.3 Start Controls .......................................................................................................9

2.4 Standard Features.................................................................................................92.4.1 Thermometer.............................................................................................92.4.2 Sealing Systems .........................................................................................92.4.3 Barrier Gas System.....................................................................................92.4.4 Nitrogen Panel...........................................................................................9

2.5 Accessories ...........................................................................................................102.5.1 Gas Ballast Valve........................................................................................102.5.2 Silencer ......................................................................................................102.5.3 Resistance Thermometer............................................................................102.5.4 Pressure Transmitter ..................................................................................102.5.5 Pressure Switch..........................................................................................102.5.6 Mechanical Seals........................................................................................102.5.7 PTFE Shaft Seals.........................................................................................112.5.8 Terminal box..............................................................................................112.5.9 Flame Arresters ..........................................................................................11

2.6 Explanation of ATEX Classification........................................................................112.6.1 ATEX Nameplate........................................................................................11

2.7 Safety concept......................................................................................................122.7.1 ATEX Classifications and Associated Accessories ........................................122.7.2 P&ID "Piping and Instrumentation Diagram" ............................................13

3 Transport ..................................................................................................................... 16

4 Storage......................................................................................................................... 16

5 Installation................................................................................................................... 17

5.1 Installation Conditions ..........................................................................................17

5.2 Connecting Lines / Pipes ......................................................................................185.2.1 Suction Connection....................................................................................185.2.2 Discharge Connection................................................................................195.2.3 Cooling Water Connection ........................................................................195.2.4 Barrier Gas System Connection ..................................................................215.2.5 Dilution Gas System Connection (Optional) ...............................................225.2.6 Purge Gas System Connection ...................................................................245.2.7 Flame Arrester Bypass Connection (Optional) ............................................25

5.3 Earth Connection..................................................................................................26

5.4 Filling Oil ..............................................................................................................26

5.5 Filling Cooling Liquid ............................................................................................28

5.6 Liquid Flushing Device Installation (Optional) .......................................................29

5.7 Fitting the Coupling..............................................................................................29

5.8 Electrical Connection ............................................................................................305.8.1 Wiring Diagram Three-Phase Motor (Pump Drive).....................................315.8.2 Wiring Diagram Solenoid Valve .................................................................32

5.9 Electrical Connection of the Monitoring Devices ...................................................335.9.1 Wiring Diagram Resistance Thermometer ..................................................335.9.2 Wiring Diagram Pressure Switch ................................................................345.9.3 Wiring Diagram Pressure Transmitter.........................................................345.9.4 Wiring Diagram Vibration Sensor...............................................................355.9.5 Wiring Diagram Flow Switch......................................................................35

Page 3: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Table of Contents

0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en 3

5.9.6 Wiring Diagram Level Switch .....................................................................365.9.7 Wiring Diagram Pressure Switch (With Gas Lubricated Double

Mechanical Seals Only)..............................................................................36

5.10 Electrical Connection of the Flame Arrester Bypass (Optional) ..............................365.10.1 Wiring Diagram Limit Switch .....................................................................365.10.2 Wiring Diagram Solenoid Valve .................................................................37

5.11 Flowchart .............................................................................................................38

6 Commissioning............................................................................................................ 39

6.1 Adjustment of the Thermostatic Valve (Direct Cooling Only)................................40

6.2 Conveying Condensable Vapours .........................................................................41

6.3 Liquid Flushing Procedure.....................................................................................41

6.4 Gas Purging Procedure .........................................................................................41

6.5 Trip Procedure......................................................................................................42

7 Maintenance ................................................................................................................ 42

7.1 Maintenance Schedule..........................................................................................43

7.2 Oil Level Inspection ..............................................................................................43

7.3 Cooling Liquid Level Inspection ............................................................................44

7.4 Oil Change...........................................................................................................45

7.5 Cooling Liquid Change .........................................................................................48

7.6 Calibration Procedure of the Electrical Devices .....................................................497.6.1 Procedure A...............................................................................................497.6.2 Procedure B ...............................................................................................497.6.3 Procedure C...............................................................................................497.6.4 Procedure D...............................................................................................497.6.5 Procedure E ...............................................................................................497.6.6 Procedure F ...............................................................................................497.6.7 Procedure G...............................................................................................507.6.8 Procedure H...............................................................................................50

7.7 Flame Arrester Maintenance.................................................................................50

8 Overhaul...................................................................................................................... 51

9 Decommissioning ........................................................................................................ 51

9.1 Dismantling and Disposal......................................................................................52

10 Spare Parts ................................................................................................................... 52

11 Troubleshooting........................................................................................................... 53

12 Technical Data ............................................................................................................. 55

13 Cooling Liquid ............................................................................................................. 55

14 Oil ............................................................................................................................... 55

15 EU Declaration of Conformity - ATEX 1G(i)/2G(o)....................................................... 56

16 EU Declaration of Conformity - ATEX 2G(i/o) and 3G(i/o) .......................................... 57

Page 4: 0870203597 NC0100-0300B WCV Ex -0001 IM en

1 | Safety

4 / 60 0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en

1 SafetyPrior to handling the machine, this instruction manual should be read and understood. Ifanything needs to be clarified, please contact your Busch representative.

Read this manual carefully before use and keep for future reference.

This instruction manual remains valid as long as the customer does not change anythingon the product.

The machine is intended for industrial use. It must be handled only by technically trainedpersonnel.

Always wear appropriate personal protective equipment in accordance with the localregulations.

The machine has been designed and manufactured according to state-of-the-art methods. Nevertheless, residual risks may remain. This instruction manual highlights po-tential hazards where appropriate. Safety notes and warning messages are tagged withone of the keywords DANGER, WARNING, CAUTION, NOTICE and NOTE as follows:

DANGER... indicates an imminent dangerous situation that will result in death or serious injuries ifnot prevented.

WARNING... indicates a potentially dangerous situation that could result in death or serious injuries.

CAUTION... indicates a potentially dangerous situation that could result in minor injuries.

NOTICE... indicates a potentially dangerous situation that could result in damage to property.

NOTE... indicates helpful tips and recommendations, as well as information for efficient andtrouble-free operation.

Page 5: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Product Description | 2

0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en 5 / 60

2 Product DescriptionNC 0100-0300 C ATEX 1G(i)/2G(o) (only the obligatory accessories are illustrated)

FME,FS-/0501 TMTV

CWP

NP2 OFP

ODP, MP

OSG

PMR

CWD

EB

PRV

CWD

CWI

CWO

MANMV2GC, NIF

TSA+/0101IN, FA PSA or PS+

/0301

EB

OUT, FA TSA+/0102 TSA+/0103

OFP

OSG ODP, MP MTB

NC

020

0 B

wit

h di

rect

coo

ling

NC

020

0 B

wit

h di

rect

coo

ling

NP1 CWD

CLDCWI CWO

CLFEV CLP

CLD

PHESVN

C 0

100

B w

ith

plat

e he

at e

xcha

nger

CLD Cooling liquid drain valve CLF Cooling liquid fill plug

CLP Cooling liquid pump CWD Cooling water drain plug

CWI Cooling water inlet CWO Cooling water outlet

CWP Cooling water pump EB Eye bolt

EV Expansion vessel FA Flame arrester

FME Flow meter FS Flow switch

GC Gas connection IN Suction connection

MAN Manometer MP Magnetic plug

MTB Motor terminal box MV Solenoid valve

NIF Nitrogen inlet filter NP Nameplate

ODP Oil drain plug OFP Oil fill plug

OSG Oil sight glass OUT Discharge connection

PHE Plate heat exchange PMR Plug for manual rotation of rotors

PRV Pressure regulating valve PS/PSA Pressure switch/transmitter

SV Safety valve TM Thermometer

TSA Temperature transmitter TV Thermostatic valve

Page 6: 0870203597 NC0100-0300B WCV Ex -0001 IM en

2 | Product Description

6 / 60 0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en

NC 0100-0300 C ATEX 2G(i/o) (only the obligatory accessories are illustrated)FME,

FS-/0501* TMTV

CWP

NP2 OFP

ODP, MP

OSG

PMR

CWDPRV

CWD

CWI

CWO

MANMV2GC, NIF

PSA or PS+/0301

EB

OUT

TSA+/0102

TSA+/0103OFP OSG ODP, MP MTB DA CLDCWI CWO

CLFEV CLP

CLD

PHESV

NC

020

0 B

wit

h di

rect

coo

ling

NC

010

0 B

wit

h pl

ate

heat

exc

hang

er

NC

020

0 B

wit

h di

rect

coo

ling

FME INMV4

MAN

SA+/0701

* recommended

NP1

CLD Cooling liquid drain valve CLF Cooling liquid fill plug

CLP Cooling liquid pump CWD Cooling water drain plug

CWI Cooling water inlet CWO Cooling water outlet

CWP Cooling water pump EB Eye bolt

EV Expansion vessel FME Flow meter

FS Flow switch GC Gas connection

IN Suction connection MAN Manometer

MP Magnetic plug MTB Motor terminal box

MV Solenoid valve NIF Nitrogen inlet filter

NP Nameplate ODP Oil drain plug

OFP Oil fill plug OSG Oil sight glass

OUT Discharge connection PGC Purge gas connection

PHE Plate heat exchange PMR Plug for manual rotation of rotors

PRV Pressure regulating valve PS/PSA Pressure switch/transmitter

SA Vibration transmitter SV Safety valve

TM Thermometer TSA Temperature transmitter

TV Thermostatic valve

Page 7: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Product Description | 2

0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en 7 / 60

NC 0100-0300 C ATEX 3G(i/o) (only the obligatory accessories are illustrated)

TMTV

CWP

NP2 OFP

ODP,MP

OSG

PMR

CWD CWI

CWO

EB

OUT

TSA+/0102

OFP OSG ODP, MP MTB CLDCWI CWO

CLFEV CLP

CLD

PHE SV

NC

020

0 B

wit

h di

rect

coo

ling

NC

010

0 B

wit

h pl

ate

heat

exc

hang

er

NC

020

0 B

wit

h di

rect

coo

ling

IN

CWD

OUTCDSIGB

NC 0200 B with silencerand gas ballast valve (Options)

NP1

CD Condensate drain CLD Cooling liquid drain valve

CLF Cooling liquid fill plug CLP Cooling liquid pump

CWD Cooling water drain plug CWI Cooling water inlet

CWO Cooling water outlet CWP Cooling water pump

EB Eye bolt EV Expansion vessel

IN Suction connection MP Magnetic plug

MTB Motor terminal box NP Nameplate

ODP Oil drain plug OFP Oil fill plug

OSG Oil sight glass OUT Discharge connection

PHE Plate heat exchange PMR Plug for manual rotation of rotors

SI Silencer SV Safety valve

TM Thermometer TSA Temperature transmitter

TV Thermostatic valve

Page 8: 0870203597 NC0100-0300B WCV Ex -0001 IM en

2 | Product Description

8 / 60 0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en

NOTETechnical term.

In this instruction manual, we consider that the term ‘machine’ refers to the ‘vacuumpump’.

2.1 Operating PrincipleWater-cooled version with direct cooling:

Water-cooled version with plate heat exchanger (optional):

The machine works on the one-stage, twin-screw pump principle.

Two screw rotors are rotating inside the cylinder. The pumped medium is trappedbetween the cylinder and screw chambers, compressed, and transported to the gas out-let. During the compression process, the two screw rotors do not come into contact witheach other nor with the cylinder. There is no need for a lubrication or an operating fluidin the compression chamber.

2.2 ApplicationThe machine is intended for the suction of air and other dry, non-aggressive and non-toxic gases.

Explosive gases and vapour mixtures can be drawn according to the scope of the Direct-ive ATEX 2014/34/EU.

It is necessary to check and ensure that the process media is compatible with the pumpmaterials and that the explosion protection will not be compromised e.g. by corrosion. Ifnecessary, contact your local Busch representative.

Depending on the equipment, the machine is intended for suction of explosive gases ac-cording to the data given on the nameplate of the machine (NP), see Explanation ofATEX Classification [► 11].Conveying of other media leads to an increased thermal and/or mechanical load on themachine and is permissible only after a consultation with Busch.

Page 9: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Product Description | 2

0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en 9 / 60

The machine is intended for the placement in a potentially explosive environment ac-cording to the data given on the nameplate of the motor and the nameplate of the ma-chine (NP), see Explanation of ATEX Classification [► 11].In case Busch delivered the machine without motor and coupling, the following must beobserved:

• In regards to its explosive atmosphere protection class, the motor and the coup-ling must have at least the same ATEX classification as the machine for the outsidearea “Outside (o)”.

• The motor and the coupling do not require an ATEX certification when the ma-chine ATEX classification corresponds to “Outside (o) No ATEX zone”.

The machine is capable of maintaining ultimate pressure, see Technical Data [► 55].The machine is suitable for continuous operation.

Permitted environmental conditions, see Technical Data [► 55].

2.3 Start ControlsThe machine comes without start controls. The control of the machine is to be providedin the course of installation.

The machine can be optionally equipped with a starter unit or a variable-frequency drive.

2.4 Standard Features

2.4.1 ThermometerThe thermometer allows a visual display of the cooling water temperature in the coolingwater chamber.

2.4.2 Sealing SystemsThe machine is equipped with labyrinth seals on the motor side and suction side.

Other sealing systems are optionally available, see Mechanical Seals [► 10] or PTFEShaft Seals [► 11].Sealing systems prevent the process gas going to the bearings chambers.

2.4.3 Barrier Gas SystemThe barrier gas system allows the supply of compressed air or nitrogen into the motorside shaft seals in order to improve the sealing efficiency.

2.4.4 Nitrogen PanelThe nitrogen panel fitted to the base frame allows the supply of nitrogen to a number ofdifferent points on the machine.

Each device consists of a pressure regulator and a flow meter to adjust pressure andvolume flow separately.

The following devices are available:

– The barrier gas system for sealing systems on motor side. This device is equippedwith a flow switch integrated to the flow meter to switch off the machine if the ni-trogen volume flow drops below the minimum set flow value.

With gas lubricated double mechanical seals, the machine must be switched off if thenitrogen volume flow goes over the maximum set flow value.

Page 10: 0870203597 NC0100-0300B WCV Ex -0001 IM en

2 | Product Description

10 / 60 0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en

– The dilution gas ballast prevents the formation of condensates or dilutes them, de-pending on the application. The nitrogen is fed into the cylinder.

– The purge gas system fitted at the inlet flange allows to flush the machine after useor during operation. The nitrogen is fed into the inlet flange.

2.5 Accessories

NOTEDepending on the ATEX classification of the machine, some of the following accessoriesmay be mandatory, see ATEX Classifications and Associated Accessories [► 12].

2.5.1 Gas Ballast ValveThe gas ballast valve mixes the process gas with a limited quantity of ambient air tocounteract the condensation of vapour inside the machine.

The gas ballast valve has an influence on the ultimate pressure of the machine, see Tech-nical Data [► 55].

2.5.2 SilencerA silencer at the discharge connection (OUT) can be provided to reduce the exhaust gasnoise.

A non-return flap can be optionally added to the silencer.

2.5.3 Resistance ThermometerThe resistance thermometer monitors gas temperature. It can be installed at three differ-ent places depending on the ATEX classification.

Warning and trip signals must be set, see Wiring Diagram Resistance Thermometer[► 33].

2.5.4 Pressure TransmitterThe pressure transmitter monitors the gas pressure at the discharge connection (OUT).

Warning and trip signals must be set, see Wiring Diagram Pressure Transmitter [► 34].

2.5.5 Pressure SwitchThe pressure switch monitors the gas pressure at the discharge connection (OUT). It canbe installed instead of the pressure transmitter.

The machine must be stopped when the gas reaches a certain pressure, see Wiring Dia-gram Pressure Switch [► 34].

2.5.6 Mechanical SealsThe sealing systems can be equipped with mechanical seals. The following variants arepossible:

– Oil lubricated single mechanical seals on the motor side and labyrinth seals on thesuction side.

– Oil lubricated single mechanical seals on the motor side and suction side.

Page 11: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Product Description | 2

0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en 11 / 60

– Gas lubricated double mechanical seals on the motor side and oil lubricated singlemechanical seals on suction side.

The gas lubricated double mechanical seals require a pressure switch in order to monit-ors if the gas pressure drops below the minimum allowable pressure. See Wiring Dia-gram Pressure Switch (With Gas Lubricated Double Mechanical Seals Only) [► 36].

2.5.7 PTFE Shaft SealsThe sealing systems on the motor side can also be equipped with PTFE shaft seals.

2.5.8 Terminal boxThe machine can be optionally equipped with one or two terminal boxes. All electricaldevices, except the motor, are already wired to the terminal box.

2.5.9 Flame ArrestersThe flame arresters are safety devices. They do not prevent explosion but avoid thepropagation of a deflagration within the machine compression chamber to the up anddownstream lines of the system.

To avoid a loss of suction capacity through the flame arrester at the machine inlet, a by-pass connection with a ball valve can be optionally delivered, see Flame Arrester BypassConnection (Optional) [► 25].

2.6 Explanation of ATEX ClassificationThe ATEX classification is written on the nameplate of the machine (NP), see below amarking example:

Inside (i)

Outside (o)

II 2G Ex h IIB T3 Gb X

II 2G Ex h IIB T3 Gb X

Explosion group inside the machine

Equipment category for explosive gases inside the machine

Equipment category for gas and dust outside the machine

Equipment group II (not for mining application)

Explosion protection inside the machine

Explosion protection outside the machine

Design approved according to ATEX Directive

Equipment group II (not for mining application)

Temperature class inside the machine

Equipment protection level

(T2=300°C) ; (T3=200°C) ; (T4=135°C)

Type of protection

Special conditions for operation*

Type of protectionExplosion group outside the machine

Temperature class outside the machine

Equipment protection level

Special conditions for operation*

* The specific operating conditions are determined in this instruction manual.

2.6.1 ATEX NameplateThe machine has two different nameplates:

– A nameplate (NP1) is fixed on the base frame of the machine with the ATEX markinginscription.

– A second nameplate (NP2) is fixed on the machine stage (module) identifying thatthe stage is suitable for ATEX certified machine.

This allows the preservation of the machine ATEX certification if the machine stageshould be replaced.

Page 12: 0870203597 NC0100-0300B WCV Ex -0001 IM en

2 | Product Description

12 / 60 0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en

2.7 Safety concept

WARNINGMisinterpretation of the ATEX instructions.

Risk of severe injury!

Risk of explosion!

• Make sure that the recommendations described in this manual correspond to theATEX marking written on the nameplate (NP).

• If anything needs to be clarified, please contact your Busch representative.

The safety concept is based on the prevention of sparks and excessive temperatures bymeans of various accessories.

The monitoring devices must be integrated into the system control such that operationof the machine will be inhibited if the safety limit values are exceeded.

2.7.1 ATEX Classifications and Associated AccessoriesThe following table defines the obligatory accessories depending on the ATEX classifica-tion.

(i) II 1G c IIB3 T4, T3 (o) II 2G c IIB T4, T3

TSA+/0102

PSA+/0301 ATEXMOT IIC

ATEXCPL ECP

X X

X

X

X

X

X X

X

X

X X

X X

A

B

C

D

TSA+/0103

ATEXMOT IIB

(i) II 1G c IIB3 T4, T3 (o) II 2G c IIC T4, T3

X

X

X

SA+/0701

X

XX X

X

MV

MV2MV3

MV2MV3

MV2

MV2

FS-/0501FS+/0501

X

X

PS+/0301

X

X X

E

F

(i) II 2G Ex h IIB T4, T3 Gb(o) No ATEX zone

(i) II 3G Ex h IIC T4, T3 Gc(o) II 3G Ex h IIB T4, T3 Gc

X

X X

(i) II 2G Ex h IIB T4, T3 Gb(o) II 2G Ex h IIB T4, T3 Gb

(i) II 2G Ex h IIB T4, T3 Gb(o) II 2G Ex h IIC T4, T3 Gb

X XG (i) II 3G Ex h IIC T4, T3 Gc(o) II 3G Ex h IIC T4, T3 Gc X X

X XH (i) II 3G Ex h IIB T4, T3 Gc(o) No ATEX zone

FA

X

X

MV2MV3

TSA+/0101

X

X

X

X

X

X

X

X

X

(X)

(X)

(X)

PS-/0302* *

X

X

X

X

X

X

X

X

(X)

(X)

(X)

ATEX classification

(PS-/0302) and (FS+/0501) is only required if the machineis equipped with gas lubricated double mechanical seals

*

(x) recommended

CPL Coupling ECP Pump earth connection

FA Flame arrester FS Flow switch

MOT Motor (IIB or IIC) MV Solenoid valve

PSA Pressure transmitter PS Pressure switch

SA Vibration transmitter TSA Resistance thermometer

For direct cooling version:The temperature class of the machine can be influenced by the thermostatic valve ad-justment, see Adjustment of the Thermostatic Valve (Direct Cooling Only) [► 40].

Page 13: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Product Description | 2

0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en 13 / 60

2.7.2 P&ID "Piping and Instrumentation Diagram"

TSA+0102

MV4

0201LS-

0202LS-

SA+0701

TSA+0103

PSA+0301

MV3MV2

MV5

FS-0501

FME

FME

FME

FS-0503

FS-0504

FLV

NRV

NRV

NRV

GC

NIF

MAN

PS+0301

IN

OUT

TSA+0101

FA

FA

D C

FS+0501

FMENRVD C

E

E PS-0302

MCPL

MOT

DN50 PN16

CWO

CWIMV7

CWP

TV

WIF

NRV

A

B

FL

CWO

CWI

MV7

PHE

CLP

TTV

55°C

A

BG1/2

G1/2

G1/4GS

0601GS

0602MV6

PMC

PRV

MANPRV

MANPRV

MANPRV

G1/4

Barrier gas system

Purge gas system

Dilution gas system

With gas lubricated double mechanical seals

Flame arresterbypass

= optional

= variant

Flushing liquid device

With plate heat exchanger

With direct cooling

or

DN15PN10

DN40 PN16 (NC0100B)

DN50 PN16 (NC0200-0300B)

DN15PN10

DN50 PN16

DN40 PN16 (NC0100B)

DN50 PN16 (NC0200-0300B)

MV5

GCG1/4

For dilution gas system only

or

= optional

Barrier gas system

Purge gas system

Dilution gas system

Flushing liquid device

= variantWith gas lubricated double mechanical seals

P&ID for classification A and B Flame arresterbypass

(see ATEX classification, chapter 2.7.1)

For dilution gas system only

CPL Coupling CWI Cooling water inlet

CWO Cooling water outlet CLP, CWP Cooling liquid/water pump

FA Flame arrester FL Flow limiter

FLV Flushing liquid vessel FME Flow meter

FS Flow switch GC Gas connection

GS Limit switch IN Suction connection

LS Level switch MAN Manometer

MOT Motor MV Solenoid valve

NIF Nitrogen inlet filter NRV Non-return valve

OUT Discharge connection PHE Plate heat exchanger

PMC Pneumatic connection PRV Pressure regulating valve

PSA Pressure transmitter PS Pressure switch

SA Vibration transmitter TSA Resistance thermometer

TTV Three-way thermostatic valve TV Thermostatic valve

WIF Water inlet filter

Page 14: 0870203597 NC0100-0300B WCV Ex -0001 IM en

2 | Product Description

14 / 60 0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en

MV4

0201LS-

0202LS-

SA+0701

MV3MV2

FS-0501

FME

FME

FME

FS-0503

FS-0504

FLV

NRV

NRV

GC

NIFIN

OUT

CWO

CWIMV7

CWP

TV

WIF

NRV

A

B

FL

D C

FS+0501

FMENRVD C

E

E PS-0302

IS

MCPL

MOT

NRV

SITSA+0103

PSA+0301PS+

0301

CWO

CWI

MV7

PHE

CLP

TTV

55°C

A

B

Ø85mm

DN40 PN16 (NC0100B)

DN50 PN16 (NC0200-0300B)

G1/4

G1/2

DN15PN10

G1/2

DN40 PN16 (NC0100B)

DN50 PN16 (NC0200-0300B)

GB

MANPRV

MANPRV

MANPRV

MANPRV

Barrier gas system

Purge gas system

Dilution gas system

With gas lubricated double mechanical seals

= optional

= variant

Flushing liquid device

With plate heat exchanger

With direct cooling

or

Air

DN15PN10

MV5

MV5

GCG1/4

For dilution gas system onlyTSA+0102

or

P&ID for classification C , D and E

= optional

Barrier gas system

Purge gas system

Dilution gas system

Flushing liquid device

= variant

With plate heat exchanger

With direct cooling

Air

(see ATEX classification, chapter 2.7.1)

With gas lubricated double mechanical seals

For dilution gas system only

With gas lubricated double mechanical seals

CLP Cooling liquid pump CPL Coupling

CWI Cooling water inlet CWO Cooling water outlet

CWP Cooling water pump FL Flow limiter

FLV Flushing liquid vessel FME Flow meter

FS Flow switch GB Gas ballast valve

GC Gas connection IN Suction connection

IS Inlet screen LS Level switch

MAN Manometer MOT Motor

MV Solenoid valve NIF Nitrogen inlet filter

NRV Non-return valve OUT Discharge connection

PHE Plate heat exchanger PRV Pressure regulating valve

PSA Pressure transmitter PS Pressure switch

SA Vibration transmitter SI Silencer

TSA Resistance thermometer TTV Three-way thermostatic valve

TV Thermostatic valve WIF Water inlet filter

Page 15: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Product Description | 2

0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en 15 / 60

TSA+0102

MV4

0201LS-

0202LS-

SA+0701

MV3MV2

FS-0501

FME

FME

FME

FS-0503

FS-0504

FLV

NRV

NRV

NRV

GC

NIFIN

OUT

D C

FS+0501

FMENRVD C

E

E PS-0302

SI

IS

MCPL

MOT

TSA+0103

PSA+0301PS+

0301

GB

CWO

CWI

MV7

PHE

CLP

TTV

55°C

A

B

G1/4

G1/2

G1/2

Ø85mm

MANPRV

MANPRV

MANPRV

MANPRV

Barrier gas system

Purge gas system

Dilution gas system

With gas lubricated double mechanical seals

= optional

= variant

Flushing liquid device

With plate heat exchanger

With direct cooling

Air

or

DN40 PN16 (NC0100B)

DN50 PN16 (NC0200-0300B)

DN15PN10

DN40 PN16 (NC0100B)

DN50 PN16 (NC0200-0300B)

DN15PN10

MV5

MV5

GCG1/4

For dilution gas system onlyCWO

CWIMV7

CWP

TV

WIF

NRV

A

B

FL

or

P&ID for classification F , G and H

= optional

Barrier gas system

Purge gas system

Dilution gas system

Flushing liquid device

= variant

With plate heat exchanger

With direct cooling

With gas lubricated double mechanical seals

Air

(see ATEX classification, chapter 2.7.1)

For dilution gas system only

CLP Cooling liquid pump CPL Coupling

CWI Cooling water inlet CWO Cooling water outlet

CWP Cooling water pump FL Flow limiter

FLV Flushing liquid vessel FME Flow meter

FS Flow switch GB Gas ballast valve

GC Gas connection IN Suction connection

IS Inlet screen LS Level switch

MAN Manometer MOT Motor

MV Solenoid valve NIF Nitrogen inlet filter

NRV Non-return valve OUT Discharge connection

PHE Plate heat exchanger PRV Pressure regulating valve

PSA Pressure transmitter PS Pressure switch

SA Vibration transmitter SI Silencer

TSA Resistance thermometer TTV Three-way thermostatic valve

TV Thermostatic valve WIF Water inlet filter

Page 16: 0870203597 NC0100-0300B WCV Ex -0001 IM en

3 | Transport

16 / 60 0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en

3 Transport

WARNINGSuspended load.

Risk of severe injury!

• Do not walk, stand or work under suspended loads.

WARNINGLifting the machine using the motor eye bolt.

Risk of severe injury!

• Do not lift the machine using the eye bolt fitted to the motor. Only lift the machine asshown.

NOTICEIn case the machine is already filled with oil.

Tilting a machine that is already filled with oil can cause large quantities of oil to in-gress into the cylinder.

• Drain the oil prior to every transport or always horizontally transport the machine.

• Make sure that the eyebolt (EB) is in faultless condition, fully screwed in and tightenedby hand.

Machine weight:see the technical data or the nameplate (NP)

• Check the machine for transport damage.

If the machine is secured to a base plate:

• Remove the machine from the base plate.

4 Storage• Seal all apertures with adhesive tape or reuse provided caps.

If the machine is to be stored for more than 3 months:

• Wrap the machine in a corrosion inhibiting film.

• Store the machine indoors, dry, dust free and if possible in original packagingpreferably at temperatures between 5 ... 55 °C.

Page 17: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Installation | 5

0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en 17 / 60

5 Installation

5.1 Installation Conditions

WARNINGThe installation conditions are not respected in an ATEX environment.

Risk of severe injury!

Risk of explosion!

• Take care that the installation conditions are met.

NOTICEUse of the machine outside of the permitted installation conditions.

Risk of premature failure!

Loss of efficiency!

• Take care that the installation conditions are fully complied with.

• Make sure that the environment of the machine complies with the ATEX classificationof the machine according to the data given on the nameplate of the motor and thenameplate of the machine (NP).

• Make sure that the ambient conditions comply with the Technical Data [► 55].• Make sure that the environmental conditions comply with the protection class of the

motor and the electrical instruments.

• Make sure that the installation space or location is vented such that sufficient coolingof the machine is provided.

• Make sure that cooling air inlets and outlets of the motor fan are not covered or ob-structed and that the cooling air flow is not affected adversely in any other way.

• Make sure that the oil sight glass (OSG) remains easily visible.

• Make sure that enough space remains for maintenance work.

• Make sure that the machine is placed or mounted horizontally, a maximum of 1° inany direction is acceptable.

• Check the oil level, see Oil Level Inspection [► 43].If the machine is equipped with a plate heat exchanger (PHE):

• Check the cooling liquid level, see Cooling Liquid Level Inspection [► 44].

• Make sure that the cooling water complies with the requirements, see Cooling WaterConnection [► 19].

If the machine is installed at an altitude greater than 1000 meters above sea level:

• Contact your Busch representative, the motor should be derated or the ambienttemperature limited.

If additional electrical components not included in scope of delivery should be added:

• Make sure that they have a better or equal ATEX classification than that of themachine, see the ATEX marking on the nameplate (NP).

For classification type “E” and “H” (see ATEX Classifications and Associated Accessor-ies [► 12]):

• Make sure that the installation space or location is ventilated enough in order toprevent the formation of an explosive area.

Page 18: 0870203597 NC0100-0300B WCV Ex -0001 IM en

5 | Installation

18 / 60 0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en

5.2 Connecting Lines / Pipes• Remove all protective covers before installation.

• Make sure that the connections are gas tight.

• Make sure that the connection lines cause no stress on the machine‘s connection; ifnecessary use flexible joints.

• Make sure that the line size of the connection lines over the entire length is at least aslarge as the connections of the machine.

In case of very long connection lines it is advisable to use larger line sizes in order toavoid a loss of efficiency. Seek advice from your Busch representative.

WARNINGThe connection lines can build up an electrostatic charge.

Risk of severe injury!

Risk of explosion!

• The connection lines must be made out of conductive material or provisions must bemade against creating an electrostatic charge.

5.2.1 Suction Connection

WARNINGUnprotected suction connection.

Risk of severe injury!

• Do not put hand or fingers in the suction connection.

NOTICEIngress of foreign objects or liquids.

Risk of damage to the machine!

If the inlet gas contains dust or other foreign solid particles:

• Install a suitable filter (5 micron or less) upstream from the machine.

If the machine corresponds to ATEX Classification “A” or “B” (see ATEX Classificationsand Associated Accessories [► 12])

• The machine must be equipped with flame arresters at the suction and dischargeconnections.

Connection size(s):

With flame arresters (FA):

– DN50 PN16, EN 1092-1

– DN80 PN16, EN 1092-1 (Optional)

Without flame arresters:

– DN40 PN16, EN 1092-1 for NC 0100 B

– DN50 PN16, EN 1092-1 for NC 0200 B and NC 0300 B

If the machine is used as part of a vacuum system:

• Busch recommends the installation of an isolation valve in order to prevent themachine from turning backwards.

Page 19: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Installation | 5

0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en 19 / 60

5.2.2 Discharge ConnectionIf the machine corresponds to ATEX Classification “A” or “B” (see ATEX Classificationsand Associated Accessories [► 12])

• The machine must be equipped with flame arresters at the suction and dischargeconnections.

Connection size(s):

At the machine discharge connection:

– Ø85 / 8 x M8

With flame arrester (FA):

– DN50 PN16, EN 1092-1

With extra flange (straight or elbow):

– DN40 PN16, EN 1092-1 for NC 0100 B

– DN50 PN16, EN 1092-1 for NC 0200 B and NC 0300 B

At the silencer (SI) discharge connection (Optional):

– DN40 PN16, EN 1092-1 for NC 0100 B

– DN50 PN16, EN 1092-1 for NC 0200 B and NC 0300 B

• Make sure that the discharged gas will flow without obstruction. Do not shut off orthrottle the discharge line or use it as a pressurised air source.

• Make sure that the counter pressure (also termed back pressure) at the discharge con-nection (OUT) does not exceed the maximum allowable discharge pressure, see Tech-nical Data [► 55].

5.2.3 Cooling Water ConnectionWater-cooled version with direct cooling:

12345

CWOCWITV

Thermostatic valveadjustment

CWI Cooling water inlet CWO Cooling water outlet

TV Thermostatic valve

Page 20: 0870203597 NC0100-0300B WCV Ex -0001 IM en

5 | Installation

20 / 60 0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en

Water-cooled version with plate heat exchanger (optional):

CWOCWI PHE

CWI Cooling water inlet CWO Cooling water outlet

PHE Plate heat exchanger

• Connect the cooling water connections (CWI / CWO) to the water supply.

Connection size:

– DN15 PN10, DIN 2566 (CWI / CWO) with direct cooling

– G1/2, ISO 228-1 (CWI / CWO) with plate heat exchanger

NOTICEAmbient temperature below 0°C.

Risk of freezing in the cooling system!

• Make sure that the water supply complies with the cooling water requirements.

• Foresee antifreeze in the supply cooling water system.

• Make sure that the cooling water complies with the following requirements:Supply capacity l/min 2 ... 4

Water pressure bar 3 ... 6 (direct cooling)1 ... 6 (plate heat exchanger)

Supply temperature °C +10 ... +25

Required pressure differential across supplyand return

bar ≥ 3 (direct cooling)> 0.5 (plate heat exchanger)

• To reduce the maintenance effort and ensure a long product lifetime we recommendthe following cooling water quality:

Hardness mg/l (ppm) < 90

Properties Clean & clear

PH value 7 … 8

Particle size µm < 200

Chloride mg/l < 100

Electrical conductivity µS/cm ≤ 100

Free chloride mg/l < 0.3

Materials in contact with the cooling water Stainless steel, copper and cast iron

NOTEWater hardness unit conversion.

1 mg/l (ppm) = 0.056 °dh (german degree) = 0.07 °e (english degree) = 0.1 °fH (french degree)

Page 21: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Installation | 5

0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en 21 / 60

5.2.4 Barrier Gas System Connection

PRVBGC MANFME, NIPMV2

FS-/0501FS+/0501

(with oil lubricated single mechanical seals)

(with gas lubricated double mechanical seals)

NIF(optional) (optional)

BGC Barrier gas connection FME Flow meter

FS Flow switch MAN Manometer

MV Solenoid valve NIF Nitrogen inlet filter

NIP Nitrogen panel PRV Pressure regulating valve

• Connect the barrier gas connection (BGC) to the gas supply.Connection size:

– G1/4, ISO 228-1If one or several solenoid valves (MV) are installed:

• Electrically connect the solenoid valve(s) (MV), see Wiring Diagram Solenoid Valve[► 32].

• Electrically connect the flow switch (FS) of the flow meter, see Wiring Diagram Flow Switch[► 35].

• Make sure that the gas complies with the following requirements:Gas type Dry nitrogen or air

Gas temperature °C 0 ... 60

Maximum gas pressure bar 13

Recommended pressure setting at thepressure regulating valve (PRV)

bar 3

Filtration µm 5

Recommended flow ratefor labyrinth seals, oil lubricated singlemechanical seals and PTFE shaft seals

SLM* 2.5 ... 3

Recommended flow ratefor gas lubricated double mechanical seals

SLM* ≤1

Air quality (only for air) Acc. to ISO 8573-1 Class 5.4.4.

* standard litre per minute

NOTICEOperate the machine equipped with gas lubricated double mechanical seals without supplyingbarrier gas.

Risk of damage to the sealing system!

• Make sure that the barrier gas supply is open.

Page 22: 0870203597 NC0100-0300B WCV Ex -0001 IM en

5 | Installation

22 / 60 0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en

5.2.5 Dilution Gas System Connection (Optional)

PRVDGC MANFME, FRNIP

DGC Dilution gas connection FME Flow meter

FR Flow regulator MAN Manometer

NIP Nitrogen panel PRV Pressure regulating valve

PRVDGC MANFME, FR

NIP FS-/0504(optional)

MV2(optional)

MV5 MV5 DGC

Variante

NIF(optional)

DGC Dilution gas connection FME Flow meter

FR Flow regulator FS Flow switch

MAN Manometer MV Solenoid valve

NIF Nitrogen inlet filter NIP Nitrogen panel

PRV Pressure regulating valve

• Connect the dilution gas connection (DGC) to the gas supply.

Connection size:

– G1/4, ISO 228-1

Page 23: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Installation | 5

0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en 23 / 60

If a flow switch is installed:

• Electrically connect the flow switch (FS) of the flow meter, see Wiring DiagramFlow Switch [► 35].

• Make sure that the gas complies with the following requirements:Gas type Dry nitrogen

Gas temperature °C 0 ... 60

Maximum gas pressure bar 13

Recommended pressure setting at thepressure regulating valve (PRV)

bar 0.5

Filtration µm 5

Recommended flow rate SLM* 20

* standard litre per minute

Page 24: 0870203597 NC0100-0300B WCV Ex -0001 IM en

5 | Installation

24 / 60 0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en

5.2.6 Purge Gas System Connection

PRVPGC MANFME, FR

NIP MV3 INFFS-/0503(optional)

MV2NIF(optional)(optional)

PGC Purge gas connection FME Flow meter

FR Flow regulator FS Flow switch

INF Inlet flange MAN Manometer

MV Solenoid valve NIF Nitrogen inlet filter

NIP Nitrogen panel PRV Pressure regulating valve

• Connect the purge gas connection to the gas supply.

Connection size:

– G1/4, ISO 228-1

If a flow switch is installed:

• Electrically connect the flow switch (FS) of the flow meter, see Wiring DiagramFlow Switch [► 35].

• Make sure that the gas complies with the following requirements:Gas type Dry nitrogen

Gas temperature °C 0 ... 60

Maximum gas pressure bar 13

Recommended pressure setting at thepressure regulating valve (PRV)

bar 0.5

Filtration µm 5

Recommended flow rate SLM* ≥ 40 for NC 0100-0200 B

* standard litre per minute

Page 25: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Installation | 5

0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en 25 / 60

5.2.7 Flame Arrester Bypass Connection (Optional)

WARNINGInlet pressure >100 hPa with open bypass.

Risk of severe injury!

Risk of explosion propagation!

• The bypass must only be open when the inlet pressure (P1 and P2) is <100 hPa.

• Provide two pressure controls (P1 and P2) enable to activate the solenoid valve(MV6).

• If ΔP between P1 and P2 is >10 hPa, the bypass must be closed.

• Install the bypass according to the scheme below:

IN

FA

FA

DN50DN80

DN50

GS0601GS

0602

DN40 (NC0100B)

DN50 (NC0200-0300B)

MV6

OUT

P1

IV

P2

COBRA

PMC

included in the delivery scope

not included in the delivery scope

P1 and P2 <100 hPa = bypass openP1 = P2 (pressure double check)

bypass closed

bypass open

FA Flame arrester GS Limit switch

IN Suction connection IV Isolation valve

MV Solenoid valve OUT Discharge connection

PMC Pneumatic connection

• Electrically connect the two limit switches (GS/0601 and GS/0602) and the solenoidvalve (MV6), see Electrical Connection of the Flame Arrester Bypass (Optional)[► 36].

• Connect the pneumatic actuator connection (PMC) to a pneumatic system supply.

Connection size:

– G1/4

• Make sure that the supply air pressure is between 3 ... 6 bar.

Page 26: 0870203597 NC0100-0300B WCV Ex -0001 IM en

5 | Installation

26 / 60 0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en

5.3 Earth ConnectionIn order to prevent the machine from creating an electrostatic charge:

• Connect the earth connection of the machine (ECP)

Earth connection ofthe machine (ECP)

5.4 Filling Oil

NOTICEUse of an inappropriate oil.

Risk of premature failure!

Loss of efficiency!

• Only use an oil type which has previously been approved and recommended byBusch.

Page 27: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Installation | 5

0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en 27 / 60

For oil type and oil capacity see Technical Data [► 55] and Oil [► 55].

1

2

Busch Oil

3

MAXMIN

4

Check oil level

Oil filling at the motor side

1

2

Busch Oil

3

MAXMIN

4

Check oil level

Oil filling at the suction side

Page 28: 0870203597 NC0100-0300B WCV Ex -0001 IM en

5 | Installation

28 / 60 0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en

When the oil filling is achieved:

• Write down the oil change date on the sticker.

Last oil change

__ / __ / ____

Oil type see nameplate

Change interval see

instruction manual

If there is no sticker (part no. 0565 568 959) on the machine:

• Order it from your Busch representative.

5.5 Filling Cooling LiquidThis step has to be carried out only if the machine is equipped with a plate heat ex-changer.

For cooling liquid type and cooling liquid capacity see Technical Data [► 55] andCooling Liquid [► 55].

1 2

Coo

ling

liqui

dZi

trec

M-2

5

3

MAX

MIN

4

Check cooling liquid level

NC 0100 BNC 0200 BNC 0300 B

NC 0200 BNC 0300 B NC 0100 B

Page 29: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Installation | 5

0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en 29 / 60

5.6 Liquid Flushing Device Installation (Optional)

LS-/0201 FRLIFLV INFMV4FLF LS-/0202

FLF Flushing liquid fill plug FLV Flushing liquid vessel

FR Flow regulator INF Inlet flange

LI Level indicator LS Level switch

MV Solenoid valve

• Electrically connect the two level switches (LS), see Wiring Diagram Level Switch[► 36].

• Fill the flushing liquid vessel (FLV) with a process compatible flushing liquid.

5.7 Fitting the Coupling

E

Coupling hub (machine side) Coupling hub (motor side)Coupling spider

Radial screw Max. admissibletorque: 10 Nm

Machine type Coupling size Value “E” (mm)

NC 0100 B ROTEX® 38 24

NC 0200 B

NC 0300 B

NC 0300 B ROTEX® 42 26

Page 30: 0870203597 NC0100-0300B WCV Ex -0001 IM en

5 | Installation

30 / 60 0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en

In case of a machine delivery without motor:

• Make sure that the ATEX marking of the coupling corresponds to the ATEX classi-fication of the machine.

• Fit the second coupling hub on the motor shaft (separately delivered).

• Axially adjust the hub in such a way until value "E" is reached.

• When the coupling adjustment is done, lock the coupling hub by tightening theradial screw.

• Mount the motor on the machine by including the coupling spider.

For further coupling information, go to www.ktr.com and download the instructionmanual of the ROTEX® coupling.

5.8 Electrical Connection

DANGERLive wires.

Risk of electrical shock.

• Electrical installation work must only be executed by qualified personnel.

• Make sure that the power supply for the motor is compatible with the data on thenameplate of the motor.

• The electrical installation must comply with applicable national and internationalstandards.

• Provide a lockable disconnect switch on the power line so that the machine is com-pletely secured during maintenance tasks.

• Provide an overload protection according to EN 60204-1 for the motor.

• Make sure that the motor of the machine will not be affected by electric or electro-magnetic disturbance from the mains; if necessary seek advice from Busch.

• Connect the protective earth conductor.

• Electrically connect the motor.

NOTICEThe admissible motor nominal speed exceeds the recommendation.

Risk of damage to the machine!

• Check the admissible motor nominal speed (nmax) on the nameplate of the machine(NP).

• Make sure to comply with it.

• Consult the Technical Data [► 55] to get more information.

NOTICEThe motor frequency is below 20 Hz. (even 25 Hz with gas lubricated double mechanicalseals)

Risk of damage to the machine!

• The motor nominal speed must always be higher than 1200 min-1 (20 Hz).

• The motor nominal speed must always be higher than 1500 min-1 (25 Hz), if the ma-chine is equipped with gas lubricated double mechanical seals.

Page 31: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Installation | 5

0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en 31 / 60

NOTICEIncorrect connection.

Risk of damage to the motor!

• The wiring diagrams given below are typical. Check the inside of the terminal box formotor connection instructions/diagrams.

5.8.1 Wiring Diagram Three-Phase Motor (Pump Drive)Delta connection (low voltage): Star connection (high voltage):

Double star connection, multi-voltagemotor with 9 pins (low voltage):

Star connection, multi-voltage motorwith 9 pins (high voltage):

Double star connection, multi-voltagemotor with 12 pins (low voltage):

4

4

4

Star connection, multi-voltage motorwith 12 pins (high voltage):

4

4

4

Delta connection, multi-voltage motorwith 12 pins (middle voltage):

4

4

4

Page 32: 0870203597 NC0100-0300B WCV Ex -0001 IM en

5 | Installation

32 / 60 0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en

NOTICEIncorrect direction of rotation.

Risk of damage to the machine!

• Operation in the wrong direction of rotation can destroy the machine in a short time!Prior to start-up, ensure that the machine is operated in the right direction.

The intended rotation direction of the motor is defined by the illustration below:

IN

• Jog the motor briefly.

• Watch the fan wheel of the motor and determine the direction of rotation just beforethe fan wheel stops.

If the rotation of the motor must be changed:

• Switch any two of the motor phase wires.

5.8.2 Wiring Diagram Solenoid Valve

2 (-)

1 (+)

PE

Part no. Supplier reference P&ID posi-tion

Specifications Maintenanceprocedure

0654 000 092 Parker Lucifer495905 C2

MV2 ;MV3 ;MV4 ; MV5

DN 3with seal in FFKM

Ex db mb IIC T4Ui = 24 VDC

Procedure G[► 50]

0654 538 544 Parker Lucifer495910 N7

MV2 ;MV3 ; MV5

DN 1.5with seal in PUR

Ex ia IIC T4Ui = 24 VDC

Procedure G[► 50]

0654 532 461 Bürkert Type 262 (pneumatic)Type 6014 C (electric)

MV2 ;MV3 ;MV5 ; MV7

DN 12with seal in PTFEpneumatic 3 ... 6 bar

Ex ia IIC T5Ui = 24 VDC

Procedure G[► 50] or Pro-cedure H[► 50]

0654 547 028 Parker Lucifer495905 F4

MV2 ;MV3 ; MV5

DN 3with seal in FFKM

Ex dm mb IIC T4Ui = 230 VAC

Procedure G[► 50]

0654 552 169 Parker Lucifer495910 N7

MV4 DN 1.5with seal in Rubis

Ex ia IIC T4Ui = 24 VDC

Procedure H[► 50]

0654 536 403 Bürkert Typ 6014

MV4 DN 0.9with seal in FKM

Ex ia IIC T6Ui = 24 VDC

Procedure H[► 50]

0654 518 062 Parker Lucifer495905 C2

MV7 DN 12with seal in FKM

Ex db mb IIC T4Ui = 24 VDC

Procedure H[► 50]

0654 545 633 Parker Lucifer483580.01

MV7 DN 15with seal in PTFEpneumatic 3.5 ... 10 bar

Ex ia IIC T6Ui = 24 VDC

Procedure H[► 50]

0654 518 061 Parker Lucifer495905 F4

MV7 DN 12with seal in FKM

Ex dm mb IIC T4Ui = 230 VAC

Procedure H[► 50]

Page 33: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Installation | 5

0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en 33 / 60

5.9 Electrical Connection of the Monitoring Devices

NOTEIn order to prevent potential nuisance alarms, Busch allows that the control system isconfigured with a time delay of 2 seconds.

NOTEThe accessories below are considered as standard.

If other specific components should be used, refer to the instruction manual of the ac-cessory in question.

WARNINGIf the monitoring sensors are not used.

Risk of explosion!

• Always use the mandatory monitoring sensors.

5.9.1 Wiring Diagram Resistance ThermometerPart no.:PT100 (Stainless steel): 0651 537 910PT100 (Hasteloy): 0651 538 233Transmitter: 0643 536 800 (optional)

Supplier reference:PT100: Albert Balzer AGref. (Stainless steel): TFE/ BDAEref. (Hasteloy): TFE/ BVAE

Transmitter: Endress+Hauserref. TMT 187-B41FJA

Maintenance procedure:Procedure A [► 49]P&ID position:TSA+/0101 “flame arrester temp.”TSA+/0102 “internal gas temp.”TSA+/0103 “exhaust gas temp.”

Wiring with transmitter:

2

1+

-1

23

4

5

6

+

-

1 = Brown ; 2 = Blue

Wiring without transmitter:

12

34

1 and 2 = Red ; 3 and 4 = White

Electrical data (PT100):Ui = 30 VDC ; Ii = 100 mA ; Pi = 0.1 (T4) … 0.75 (T3) W ;Li = 0.015 mH/m ; Ci = 280 pF/mElectrical data (transmitter):Ui = 30 V ; Ii = 100 mA ; Pi = 0.76 W ; Li = 4.5 mH ; Ci = 709 nF4 ... 20 mA ► 0 ... 300 °C

Warning signal: a warning signal can beset prior the trip signal.

Trip signal: see table below

Page 34: 0870203597 NC0100-0300B WCV Ex -0001 IM en

5 | Installation

34 / 60 0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en

COBRAtype

Temperatureclass

Trip signal

Ttrip (TSA+/0101) Ttrip (TSA+/0102) Ttrip (TSA+/0103)

NC 0100 B T4 (i/o) 80°C ► 8.26 mA 120°C ► 10.4 mA 125°C ► 10.67 mA

T3 (i/o)2G(i) or 3G(i)

only

N/A 140°C ► 11.47 mA 145°C ► 11.73 mA

NC 0200 B T4(i/o) 80°C ► 8.26 mA 115°C ► 10.13 mA 140°C ► 11.47 mA

T3(i) / T4(o) 165°C ► 12.8 mA 170°C ► 13.07 mA

T3(i/o) 165°C ► 12.8 mA 180°C ► 13.6 mA

NC 0300 B T4(i/o) 80°C ► 8.26 mA 130°C ► 10.93 mA 150°C ► 12 mA

T3(i/o) 174°C ► 13.28 mA 180°C ► 13.6 mA

NOTE: The values in “mA” are only valid for transmitter “4 ... 20 mA ► 0 ... 300 °C”

5.9.2 Wiring Diagram Pressure SwitchPart no.: 0653 539 030

Supplier reference: United Electric ControlsH100 (100 Series)

Maintenance procedure:Procedure B [► 49]P&ID position: PS+/0301

Electrical data:Ui = 49 VDC ; Ii = 3 A ; Li = 0 µH ; Ci = 0 pF

Contact: Normally closed

2

1

P

Switch point: P (PS+/0301) = 1300 hPa (mbar) abs. (factory default adjustment)

5.9.3 Wiring Diagram Pressure TransmitterPart no.:- 0653 537 031 or- 0653 541 862 (Hastelloy®) or- 0653 206 492 or- 0653 212 111 (Hastelloy®)

Supplier reference: ACS Precont Ex S10

Maintenance procedure:Procedure C [► 49]Connector: M12x1, 4-pin

P&ID position: PSA+/0301

1 2

4 3

3

1

+

-

1 = Brown ; 3 = Blue

Electrical data (0653 537 031 / 0653 541 862):Ui = 30 VDC ; Ii = 300 mA ; Pi = 0.9 W ; Li = 110 µH ; Ci = 19 nF4 ... 20 mA ► 0 ... 300 mbar (relative)

Electrical data (0653 206 492 / 0653 212 111):Ui = 30 VDC ; Ii = 300 mA ; Pi = 0.9 W ; Li = 110 µH ; Ci = 19 nF4 ... 20 mA ► -100 ... 400 mbar (relative)

Warning signal: a warning signal canbe set prior the trip signal.

Trip signal (0653 537 031 / 0653 541 862):Ptrip (PSA+/0301) = 0.3* bar ► 20 mA

Trip signal (0653 206 492 / 0653 212 111):Ptrip (PSA+/0301) = 0.3* bar ► 16.8 mA

*1300 hPa (mbar) abs.

Page 35: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Installation | 5

0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en 35 / 60

5.9.4 Wiring Diagram Vibration SensorPart no.: 0658 538 541

Supplier reference:Monitran MTN/2287ICM6-1

Maintenance procedure:Procedure D [► 49]P&ID position: SA+/0701

2 (-)

1 (+)

PEg

1 = White ; 2 = BlackPE = Screen

Electrical data:Ui = 28 VDC ; Ii = 93 mA ; Pi = 0.65 W ; Li = 6 µH ; Ci = 3 nF4 ... 20 mA ► 0 ... 1 g RMS

Warning signal:a warning signal can be set prior thetrip signal.

Trip signal:Ptrip (SA+/0701) = 0.4 g RMS ► 10.4 mA

5.9.5 Wiring Diagram Flow SwitchPart no.: No Busch ref. (integrated into theflow meter)

Supplier reference:Pepperl+Fuchs RC15-14-N3

Maintenance procedure:Procedure E [► 49]P&ID position:FS-/0501 “barrier gas flow”FS-/0503 “purge gas flow”FS-/0504 “dilution gas flow”

2 (-)

1 (+)

1 = Brown ; 2 = Blue

Electrical data: Ui = 16 VDC ; Ii = 1 … 3 mA

Switching element function: NAMUR, bistable

COBRAtype

Switch point

Barrier gas flow(FS-/0501)

Barrier gas flow(FS+/0501)*

Purge gas flow(FS-/0503)

Dilution gasflow(FS-/0504)

NC 0100 B 1.5 SLM

Contact:Normally open

1 SLM

Contact:Normally closed

25 SLM 20 SLM*

NC 0200 B 1.5 SLM

Contact:Normally open

1 SLM

Contact:Normally closed

40 SLM 20 SLM

NC 0300 B 1.5 SLM

Contact:Normally open

1 SLM

Contact:Normally closed

75 SLM 20 SLM

* with gas lubricated double mechanical seals only

Page 36: 0870203597 NC0100-0300B WCV Ex -0001 IM en

5 | Installation

36 / 60 0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en

5.9.6 Wiring Diagram Level SwitchPart no.: 0652 556 531

Supplier reference:Endress&Hauser FTL50/FEL58

Maintenance procedure:Procedure F [► 49]Connector: M12x1, 4-pin

P&ID position: LS-/0201 & LS-/0202

1 2

4 3

4

1

L

1 = Brown ; 4 = Black

Electrical data:Ui = 16 VDC ; Ii = 52 mA ; Pi = 0.17 W ; Ci = 0 nF ; Li = 0 mH

Switching element function: NAMUR

Contact: Normally closed

Switch point:Lwarning = LS-/0201 ► pin 1 + 4 ► low level “warning”Ltrip = LS-/0202 ► pin 1 + 4 ► low level “stop flushing”

5.9.7 Wiring Diagram Pressure Switch (With Gas LubricatedDouble Mechanical Seals Only)Part no.: 0653 518 304

Supplier reference: Trafag AGPST4B 9B4 (0…6 bar)

Maintenance procedure:Procedure B [► 49]P&ID position: PS-/0302

Electrical data:U = 30 V ; I = 0.1 A

Contact: Normally open

2 3

P PE

1

3

2

1

Switch point: Ptrip (PS-/0302) = 2.5 bar (relative) ► min. admissible pressure

5.10 Electrical Connection of the Flame ArresterBypass (Optional)

5.10.1 Wiring Diagram Limit SwitchPart no.: No Busch ref. (integrated into thepneumatic actuator)

Supplier reference:Pepperl+Fuchs NJ2-V3-N

P&ID position:GS/0601 “bypass closed”GS/0602 “bypass open”

Electrical data:U = 8 V ; I = 1 … 3 mA

Switching element function:NAMUR, bistable

2 (-)

1 (+)

1 = Brown ; 2 = Blue

Page 37: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Installation | 5

0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en 37 / 60

5.10.2 Wiring Diagram Solenoid ValvePart no. : No Busch ref. (integrated into thepneumatic actuator)

Supplier reference:Parker Lucifer 483580.01 N7 (electric)Parker Lucifer 341 N 3190 (pneumatic)

Electrical data:U = 28 VDC ; I = 110 mA

2 (-)

1 (+)

PE

Page 38: 0870203597 NC0100-0300B WCV Ex -0001 IM en

5 | Installation

38 / 60 0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en

5.11 FlowchartThe machine safety depends on the monitoring accessories sequencing according to thefollowing flowchart.

Gas

pre

ssur

e

Start

P < P warning?High gas pressure !

Warning:P < P trip?

P < P switch point?

OR YES

NO NO

YES

YES

NO

NO

YES

T < T warning? T < T trip?

PSA

+/0

301

PS+

/030

1TS

A+

/010

2

Machinein function? Start the machine

NO

YES

Stop button activated?

YES

NO

Stop the machine Stop the machineAlarm trip

YES

T < T warning?High gas temperature !

Warning:

YES

T < T trip?NO

TSA

+/0

103

Gas

tem

pera

ture

NO

YES

NO

YES

Vib

ratio

nBa

rrie

r ga

s flo

w

Vibration levelbelow the limit value?

Barrier gas flowsufficient?

(opt

iona

l if

3G(i)

)(o

ptio

nal i

f 3G

(i))

(opt

iona

l if

1G(i)

+ 3

G(i)

)(o

ptio

nal i

f 2G

(i) +

3G

(i))

Additional sequences may be added if optional monitoring accessories have been installed

SA+

/070

1FS

-/0

501

NO

YES

NO

TSA

+/0

101

Gas

tem

pera

ture

(opt

iona

l if

2G(i)

+ 3

G(i)

)

T < T warning?

YES

NOHigh gas temperature !

Warning:T < T trip?

YES

NO

FS+

/050

1O

R

YES

NOBarrier gas flowbelow limit

value?

High gas temperature !

Warning:

Gas

tem

pera

ture

with gas lubricated double mechanical seals only

with gas lubricated double mechanical seals only

Seal

ing

gas

pres

sure

PS-/

0302

YES

NOP > P switch point?

Page 39: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Commissioning | 6

0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en 39 / 60

6 Commissioning

DANGERSpecific conditions for machines certified ATEX 1G (i).

Risk of severe injury!

Risk of explosion!

If the machine has a classification type “A” and “B” (see ATEX Classifications and Asso-ciated Accessories [► 12]):

• Make sure to comply with all specific conditions mentioned in the EC-type examina-tion certificate attached to the ATEX Accessories Book provided separately.

WARNINGThe machine is still running after a monitoring device has tripped.

Risk of severe injury!

Risk of explosion!

• Follow the Trip Procedure [► 42].

NOTICEThe machine can be shipped without oil.

Operation without oil will ruin the machine in short time!

• Prior to commissioning, the machine must be filled with oil, see Filling Oil [► 26].

NOTICELubricating a dry running machine (compression chamber).

Risk of damage to the machine!

• Do not lubricate the compression chamber of the machine with oil or grease.

CAUTIONDuring operation the surface of the machine may reach temperatures of more than70°C.

Risk of burns!

• Avoid contact with the machine during and directly after operation.

CAUTIONNoise of running machine.

Risk of damage to hearing!

If persons are present in the vicinity of a non noise insulated machine over extendedperiods:

• Make sure that ear protection is being used.

• Make sure that the installation conditions (see Installation Conditions [► 17]) aremet.

Page 40: 0870203597 NC0100-0300B WCV Ex -0001 IM en

6 | Commissioning

40 / 60 0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en

If the machine corresponds to ATEX Classification “C” , “D” or “E” (see ATEX Classifica-tions and Associated Accessories [► 12]):

• Make sure that the machine has been purged by an inert gas, see Gas PurgingProcedure [► 41].

• Turn on the water supply.

• Adjust the thermostatic valve position according to the process requirements.

• See Adjustment of the Thermostatic Valve (Direct Cooling Only) [► 40].If the machine is equipped with a barrier gas system:

• Turn on the barrier gas supply.

• Adjust the barrier gas pressure and volume flow.

• Switch on the machine.

• Make sure that the maximum permissible number of starts does not exceed 6 startsper hour. Those starts should be spread within the hour.

• Make sure that the operating conditions comply with the Technical Data [► 55].If the machine is equipped with a plate heat exchanger (PHE):

• After a few minutes of operation, perform a Cooling Liquid Level Inspection[► 44].

• After a few minutes of operation, perform an Oil Level Inspection [► 43].As soon as the machine is operated under normal operating conditions:

• Measure the motor current and record it as reference for future maintenance andtroubleshooting work.

6.1 Adjustment of the Thermostatic Valve (DirectCooling Only)The adjustment of the thermostatic valve (TV) influences the temperature class of themachine.

Other factors have a direct influence on the monitored temperatures (i.e. gas inlet tem-perature, gas inlet pressure, cooling medium, water temperature, ambient temperature,etc…).

The table below shows the recommendations for thermostatic valve adjustments:Machine type Temp.

class(inside)

Temp.class(ouside)

Water inlettemp.

Water inlettemp.(with Water/Glycol)

Thermostaticvalve positionrange

NC 0100 B T4(i) T4(o) < 25°C < 20°C 0 … 4

T3(i) T3(o) < 30°C < 30°C 0 … 4

NC 0200 B T4(i) T4(o) < 40°C < 30°C 0 … 2

T3(i) T4(o) < 40°C < 30°C 0 … 4

T3(i) T3(o) < 40°C < 30°C 0 … 4

NC 0300 B T4(i) T4(o) < 25°C N/A 0 … 2

T4(i) T4(o) N/A < 20°C 0 … 1

T3(i) T3(o) < 40°C < 40°C 0 … 4

• If you need any further information, contact your Busch representative.

Page 41: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Commissioning | 6

0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en 41 / 60

6.2 Conveying Condensable VapoursThe machine, equipped either with a gas ballast valve or a dilution gas system, is suitablefor the conveyance of condensable vapours within the gas flow.

If condensable vapours are to be conveyed:

START

Open the gas ballastvalve* or the

dilution gas sytem*(solenoid valve)

Warm up themachine

30 minutes 30 minutes

• Open the inletvalve

• Perform the process• Close the inlet

valve

Close the gas ballastvalve*

orthe dilution gas

system*

END

* optional accessories

• Continuously drain condensate from the condensate drain plug (CD) of the silencer(SI) (Optional).

6.3 Liquid Flushing ProcedureIf after the application process a liquid flushing is required:

START

Reduce the motorspeed to 10 Hz* withthe inlet valve closed

Open the liquidflushing device(solenoid valve)

The flushing durationdepends on the application

Adapt the flushingliquid flow acc. to the

applicationrequirements

Close the liquidflushing device

END* minimum admissible frequency

NOTE: With gas lubricated double mechanical seals, the minimum admissible frequencyis 25 Hz.

6.4 Gas Purging ProcedureThe machine can optionally be equipped with a purge gas system.

If after the application process a gas purge is required, i.e. after a liquid flushing se-quence or to render the compression chamber inert:

START

Close the inlet valve Open the purge gas(solenoid valve)

The flushing durationdepends on the application

Close the purge gas

END

min. 200 seconds to renderthe machine inert

Page 42: 0870203597 NC0100-0300B WCV Ex -0001 IM en

7 | Maintenance

42 / 60 0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en

6.5 Trip ProcedureWhen one of the monitoring devices reach a limit value:

• Isolate the compression chamber by closing the inlet valve.

• Stop the machine.

If a purge gas system is installed:

• Perform a gas flushing of the compression chamber, see Gas Purging Procedure[► 41].

• Do not restart the machine before finding out the source of dysfunction. Once theproblem identified fix it, see Troubleshooting [► 53].

• In case of doubt, please contact your Busch representative.

7 Maintenance

WARNINGMachines contaminated with hazardous material.

Risk of poisoning!

Risk of infection!

If the machine is contaminated with hazardous material:

• Wear appropriate personal protective equipment.

CAUTIONHot surface.

Risk of burns!

• Prior to any action requiring touching the machine, let the machine cool down first.

NOTICEUsing inappropriate cleaners.

Risk of removing safety stickers and protective paint!

• Do not use incompatible solvents to clean the machine.

CAUTIONFailing to properly maintain the machine.

Risk of injuries!

Risk of premature failure and loss of efficiency!

• Respect the maintenance intervals or ask your Busch representative for service.

• Shut down the machine and lock against inadvertent start up.

• Turn off the water supply.

If the machine corresponds to ATEX Classification “C” , “D” or “E” (see ATEX Classifica-tions and Associated Accessories [► 12]):

• Make sure that the machine has been purged by an inert gas, see Gas PurgingProcedure [► 41].

Page 43: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Maintenance | 7

0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en 43 / 60

If the machine is equipped with a barrier gas system:

• Close the barrier gas supply.

• Vent the connected lines to atmospheric pressure.

If necessary:

• Disconnect all connections.

7.1 Maintenance ScheduleThe maintenance intervals depend very much on the individual operating conditions. Theintervals given below are desired to be considered as starting values which should beshortened or extended as appropriate. Particularly harsh applications or heavy duty oper-ation, such as high dust loads in the environment or in the process gas, other contamina-tion or ingress of process material, can make it necessary to shorten the maintenance in-tervals significantly.Interval Maintenance work

Monthly • Check the oil level, see Oil Level Inspection [► 43].If the machine is equipped with a plate heat exchanger(PHE):

• Check the cooling liquid level, see Cooling LiquidLevel Inspection [► 44].

• Check the machine for oil leaks - in case of leaks havethe machine repaired (contact Busch).

Yearly • Carry out a visual inspection and clean the machinefrom dust and dirt.

• Check the electrical connections and the monitoringdevices.

YearlyIn case of those accessoriesbeing installed.

• Check the filter of the gas ballast valve (GB), clean itif necessary.

• Check the silence (SI) and clean it if necessary.

Every 5000 hours, at the latestafter 1 year

• Change the oil of the gear and bearing housings(both sides), see Oil Change [► 45].

• Clean the magnetic plugs (MP).

Every 16000 hours, at thelatest after 4 years

• Have a major overhaul on the machine (contactBusch).

Depending on operating con-ditions and the contaminationlevel

• Check the flame arresters (ATEX category 1G(i) only)

• Clean them or replace them if necessary, see FlameArrester Maintenance [► 50].

7.2 Oil Level Inspection• Shut down the machine.

• When the machine is stopped, wait 1 minute before checking the oil level.

MAX

MIN

MAX

MIN

MAX

MIN

MAX

MIN

MAX

MIN

MAX

MINOil sight glass on motor side

Oil sight glass on suction side

• Fill up if necessary, see Oil Filling [► 26].

Page 44: 0870203597 NC0100-0300B WCV Ex -0001 IM en

7 | Maintenance

44 / 60 0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en

7.3 Cooling Liquid Level InspectionThis step has to be carried out only if the machine is equipped with a plate heat ex-changer.

• Shut down the machine.

For NC 0100 B:

• Let the machine cool down.

• Remove the cooling liquid fill plug (CLF).

• Check cooling liquid level.

MAX

MIN

MAX

MIN

MAX

MIN

For NC 0200 – 0300 B:

• Check cooling liquid level.

• Fill up if necessary, see Filling Cooling Liquid [► 28].

Page 45: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Maintenance | 7

0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en 45 / 60

7.4 Oil Change

NOTICEUse of an inappropriate oil.

Risk of premature failure!

Loss of efficiency!

• Only use an oil type which has previously been approved and recommended byBusch.

1

2

3Oil draining at the motor side

Cleaning cloth

Drain pan

Magnetic plug

Page 46: 0870203597 NC0100-0300B WCV Ex -0001 IM en

7 | Maintenance

46 / 60 0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en

1

2

3

Oil draining at the suction side

Cleaning cloth

Drain pan

Magnetic plug

For oil type and oil capacity see Technical Data [► 55] and Oil [► 55].

1

2

Busch Oil

3

MAXMIN

4

Check oil level

Oil filling at the motor side

Page 47: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Maintenance | 7

0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en 47 / 60

1

2

Busch Oil

3

MAXMIN

4

Check oil level

Oil filling at the suction side

When the oil filling is achieved:

• Write down the oil change date on the sticker.

Last oil change

__ / __ / ____

Oil type see nameplate

Change interval see

instruction manual

If there is no sticker (part no. 0565 568 959) on the machine:

• Order it from your Busch representative.

Page 48: 0870203597 NC0100-0300B WCV Ex -0001 IM en

7 | Maintenance

48 / 60 0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en

7.5 Cooling Liquid ChangeThis step has to be carried out only if the machine is equipped with a plate heat ex-changer.

1 2

3

4

NC 0100 BNC 0200 BNC 0300 B

For cooling liquid type and cooling liquid capacity see Technical Data [► 55] andCooling Liquid [► 55].

1 2

Coo

ling

liqui

dZi

trec

M-2

5

3

MAX

MIN

4

Check cooling liquid level

NC 0100 BNC 0200 BNC 0300 B

NC 0200 BNC 0300 B NC 0100 B

Page 49: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Maintenance | 7

0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en 49 / 60

7.6 Calibration Procedure of the Electrical Devices

7.6.1 Procedure A• Remove the resistance thermometer from the machine.

• Check it with a calibrated oven or send it to an approved laboratory for inspection.

• Reassemble the resistance thermometer on the machine.

7.6.2 Procedure B• Remove the pressure switch from the machine.

• Compare it with another calibrated pressure switch or send it to an approved laborat-ory for inspection.It must trip when the pressure reaches the prescribed trip value.

• Reassemble the pressure switch on the machine.

7.6.3 Procedure C• Remove the pressure transmitter from the machine.

• Compare it with another calibrated pressure transmitter or send it to an approvedlaboratory for inspection.

• Reassemble the pressure transmitter on the machine.

7.6.4 Procedure D• Remove the vibration sensor from the machine.

• Control it with a calibration system or send it to:

Monitran Ltd33 Hazlemere RoadPennHP10 [email protected]

Use an Analog Current Loop Simulator and Tester 4-20mA to test the remaining controlloop.

Compare and record the trip value.

• Reassemble the vibration sensor on the machine (8Nm).

7.6.5 Procedure E• Check that the flow switch changes state when the ball of the flowmeter is passing.

It is not necessary to disassemble the flowmeter or its switch.

7.6.6 Procedure F• Check that the level switch changes state by using the test magnet.

• Hold the test magnet against the “target” marking.

• Make sure that the switching status is changed.

• Read the instruction manual of the level switch for more information.

Page 50: 0870203597 NC0100-0300B WCV Ex -0001 IM en

7 | Maintenance

50 / 60 0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en

7.6.7 Procedure G• Check that the solenoid valve changes state by electrical supply.

• Perform a visual inspection of the solenoid valve sealing by means of the flow meter inorder to ensure that the device is still gas tight.

7.6.8 Procedure H• Check that the solenoid valve changes state by electrical supply.

• Perform a visual inspection of the solenoid valve sealing and ensure that there is no li-quid leak.

7.7 Flame Arrester Maintenance• Check and assess if a cleaning of the flame arresters is required (i.e. removing dust

and dirt).

• Check that the flame arresters do not show any signs of corrosion.

• Determine the flame arrester type according to the table below.

• Please refer to the flame arrester instruction manual (attached to the ATEX AccessoriesBook) for detailed information in order to carry out a correct maintenance.

Machine type Flame arresterSuction connection (IN)

Flame arresterDischarge connection (OUT)

Supplier / size Reference Supplier Reference

NC 0100 B Cashco / DN50 3 x 0.3 IIB3 Cashco / DN50 3 x 0.3 IIB3

Cashco / DN80 4 x 0.5 IIB3

BS&B / DN50 930-S50.1 / 3 x 0.3 / e-vp BS&B / DN50 930-S50.1 / 3 x 0.3 / e-vp

BS&B / DN80 930-S80.1 / 4 x 0.5 / e-vp

NC 0200 B Cashco / DN50 3 x 0.3 IIB3 Cashco / DN50 4 x 0.3 IIB3

Cashco / DN80 4 x 0.5 IIB3 Cashco / DN50 5 x 0,4 0530 IIB3

BS&B / DN50 930-S50.1 / 3 x 0.3 / e-vp BS&B / DN50 930-S50.1 / 4 x 0.3 / eC-vp

BS&B / DN80 930-S80.1 / 4 x 0.5 / e-vp BS&B / DN50 930-S50.1 / 5 x 0.4 /1 x 0530/ eC-vp

NC 0300 B Cashco / DN50 3 x 0.3 IIB3 Cashco / DN50 4 x 0.3 IIB3

Cashco / DN80 4 x 0.5 IIB3 Cashco / DN50 5 x 0,4 0530 IIB3

BS&B / DN50 930-S50.1 / 3 x 0.3 / e-vp BS&B / DN50 930-S50.1 / 4 x 0.3 / eC-vp

BS&B / DN80 930-S80.1 / 4 x 0.5 / e-vp BS&B / DN50 930-S50.1 / 5 x 0.4 /1 x 0530/ eC-vp

Page 51: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Overhaul | 8

0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en 51 / 60

8 OverhaulIn case of the machine having conveyed gas that was contaminated with foreign materi-als which are dangerous to health:

• Decontaminate the machine as much as possible and state the contaminationstatus in a ‘Declaration of Contamination’.

Busch will only accept machines that come with a completely filled in and legally bindingsigned ‘Declaration of Contamination’.(Form downloadable from www.buschvacuum.com)

NOTICEImproper assembly.

Risk of premature failure!

Loss of efficiency!

• It is highly recommended that any dismantling of the machine that goes beyond any-thing that is described in this manual should be done through Busch.

WARNINGMachines contaminated with hazardous material.

Risk of poisoning!

Risk of infection!

If the machine is contaminated with hazardous material:

• Wear appropriate personal protective equipment.

9 Decommissioning• Shut down the machine and lock against inadvertent start up.

• Turn off the water supply.

If the machine corresponds to ATEX Classification “C” , “D” or “E” (see ATEX Classifica-tions and Associated Accessories [► 12]):

• Make sure that the machine has been purged by an inert gas, see Gas PurgingProcedure [► 41].

If the machine is equipped with a barrier gas system:

• Close the barrier gas supply.

• Vent the connected lines to atmospheric pressure.

• Drain the cooling water from the two cooling water drain plugs (CWD).

• Disconnect all connections.

If the machine is going to be stored:

• See Storage [► 16].

Page 52: 0870203597 NC0100-0300B WCV Ex -0001 IM en

10 | Spare Parts

52 / 60 0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en

9.1 Dismantling and Disposal• Drain the oil.

If the machine is equipped with a plate heat exchanger (PHE):

• Drain the cooling liquid.

• Separate special waste from the machine.

• Dispose of special waste in compliance with applicable regulations.

• Dispose of the machine as scrap metal.

10 Spare Parts

NOTICEUse of non-Busch genuine spare parts.

Risk of premature failure!

Loss of efficiency and ATEX compliance!

• The exclusive use of Busch genuine spare parts and consumables is recommended forthe correct functioning of the machine and to validate the warranty.

There is no standard spare parts kits available for this product, if you require Busch gen-uine parts:

• Contact your Busch representative for the detailed spare parts list.

Page 53: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Troubleshooting | 11

0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en 53 / 60

11 Troubleshooting

DANGERLive wires.

Risk of electrical shock.

• Electrical installation work must only be executed by qualified personnel.

CAUTIONHot surface.

Risk of burns!

• Prior to any action requiring touching the machine, let the machine cool down first.

Problem Possible Cause Remedy

The machine does not start. The motor is not suppliedwith the correct voltage.

• Check the power supply.

The rotors are jammed orseized.

• Turn the screw rotorsmanually from the rotoraccess plug (PMR).

• Repair the machine (con-tact Busch).

Solid foreign matter hasentered the machine.

• Remove the solid foreignmatter or repair the ma-chine (contact Busch).

• Install an inlet filter if ne-cessary.

A temperature sensor hasreached the switch point.

• Let the machine cooldown.

• See problem “The ma-chine runs too hot”.

Corrosion in the machinefrom remaining condensate.

• Repair the machine.

• Check the process andfollow the recommenda-tion in case of ConveyingCondensable Vapours[► 41].

The motor is defective. • Replace the motor.

The machine does not reachthe usual pressure on thesuction connection.

Suction or discharge linestoo long or section diametertoo small.

• Use larger diameter orshorter lines.

• Seek advice from yourlocal Busch representa-tive.

Process deposits on thepumping components

• Flush the machine.

The machine runs in thewrong direction.

• Check the direction of ro-tation, see Wiring Dia-gram Three-Phase Motor.

Internal parts are worn ordamaged.

• Repair the machine (con-tact Busch).

Page 54: 0870203597 NC0100-0300B WCV Ex -0001 IM en

11 | Troubleshooting

54 / 60 0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en

The machine runs very nois-ily.

Wrong oil quantity or un-suitable oil type.

• Use one of the recom-mended oils in the correctquantity, see Oil [► 55].

Defective gears, bearings orcoupling element.

• Repair machine (contactBusch).

The machine runs too hot. Insufficient cooling. • Make sure to comply withthe cooling water require-ments, see Cooling WaterConnection [► 19].

Ambient temperature toohigh.

• Observe the permittedambient temperature, seeTechnical Data [► 55].

Temperature of the processgases at the inlet too high.

• Observe the permittedgas inlet temperature, seeTechnical Data [► 55].

The cooling water pump isdefective.

• Repair the machine.

Oil level too low. • Top up oil.

The oil is black. Oil change intervals are toolong.

• Drain the oil and fill innew oil, see Oil Change[► 45].

The machine runs too hot. • See problem "The ma-chine runs too hot".

For the solution of problems not mentioned in the troubleshooting chart contact yourBusch representative.

Page 55: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Technical Data | 12

0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en 55 / 60

12 Technical DataNC 0100 B NC 0200 B NC 0300 B

Pumping speed(50Hz / 60Hz)

m³/h 110 / 130 220 / 265 320 / 385

Ultimate pressurewith standard coating “NC xxxx xxx”(50Hz / 60Hz)

hPa (mbar)abs.

≤0.05 / ≤0.01

Ultimate pressurewith special coating NT xxxx xxx”(50Hz / 60Hz)

hPa (mbar)abs.

≤0.5 / ≤0.1

Nominal motor rating(50Hz / 60Hz)

kW 3.5 / 4.8 6 / 7.6 7.5 / 9.5

Nominal motor speed(50Hz / 60Hz)

min-1 3000 / 3600

Nominal motor torque Nm ≤12 ≤25 ≤50

Starting motor torque Nm ≤46 ≤90 ≤115

Noise level (EN ISO 2151)(50Hz / 60Hz)

dB(A) ≤70 / ≤74 ≤71 / ≤76 ≤72 / ≤77

Ambient temperature range °C -20 … 40

Max. allowable counter pressure at the dis-charge

hPa (mbar) 300

Max. allowable gas inlet temperature °C 60

Relative humidity at 30 °C 90%

Ambient pressure Atmospheric pressure

Cooling water requirements See Cooling Water Connection [► 19]Oil capacity - motor side l 1.1

Oil capacity - suction side l 0.45

Cooling liquid capacity approx.(with plate heat exchanger only)

l 4 5.5 6.5

Weight approx. kg 300 350 400

13 Cooling LiquidZitrec M-25 (ready-to-use)

Part number 5 L packaging 0831 563 469

Part number 25 L packaging 0831 563 468

The cooling liquid Zitrec M-25 is ready-to-use and does not require additional water.

For further information, consult the website www.arteco-coolants.com.

14 OilVE 101

ISO-VG 100

Part number 1 L packaging 0831 000 099

Part number 5 L packaging 0831 000 100

Page 56: 0870203597 NC0100-0300B WCV Ex -0001 IM en

15 | EU Declaration of Conformity - ATEX 1G(i)/2G(o)

56 / 60 0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en

15 EU Declaration of Conformity - ATEX 1G(i)/2G(o)This Declaration of Conformity and the CE-mark affixed to the nameplate are valid for the machine within theBusch scope of delivery. This Declaration of Conformity is issued under the sole responsibility of the manufacturer.When this machine is integrated into a superordinate machinery the manufacturer of the superordinate machinery(this can be the operating company, too) must conduct the conformity assessment process for the superordinatemachine or plant, issue the Declaration of Conformity for it and affix the CE-mark.

The manufacturer Ateliers Busch S.A.Zone IndustrielleCH-2906 Chevenez

The notified bodyfor type examination

IBExU Institut fürSicherheitstechnik GmbHFuchsmühlenweg 7DE-09599 FreibergNB No 0637

The notified bodyfor production qual-ity assurance

InerisParc Technologique AlataF-60550 Verneuil-en-HalatteNB No 0080

declares that the machine(s): - COBRA ‘ATEX’ NC/NT/NX 0100 B (CE type examination certificate IBExU 04 ATEX 1122 X)

- COBRA ‘ATEX’ NC/NX 0200 B (CE type examination certificate IBExU 04 ATEX 1212 X)

- COBRA ‘ATEX’ NC/NT/NX 0300 B (CE type examination certificate IBExU 04 ATEX 1026 X)

with the serial number:

has (have) been manufactured in accordance with the European Directives:

– ‘Machinery’ 2006/42/EC

– ‘ATEX Directive’ 2014/34/EU, for use in potentially explosive areas according to classification written on themachine nameplate

– ‘Electromagnetic Compatibility’ 2014/30/EU

– ‘RoHS’ 2011/65/EU + Commission delegated directive (EU) 2015/863, restriction of the use of certain hazard-ous substances in electrical and electronic equipment

and following the standards.

Standard Title of the Standard

EN ISO 12100:2010 Safety of machinery - Basic concepts, general principles of design

EN ISO 13857:2008 Safety of machinery - Safety distances to prevent hazard zones being reached by the upper and lower limbs

EN 1012-1:2010

EN 1012-2:1996 + A1:2009

EN ISO 2151:2008 Acoustics - Noise test code for compressors and vacuum pumps - Engineering method (grade 2)

EN 60204-1:2006 + A1:2009 Safety of machinery - Electrical equipment of machines - Part 1: General requirements

EN 61000-6-2:2005 Electromagnetic compatibility (EMC) - Generic standards. Immunity for industrial environments

EN 61000-6-4:2007 + A1:2011 Electromagnetic compatibility (EMC) - Generic standards. Emission standard for industrial environments

EN ISO 13849-1:2015 (1) Safety of machinery - Safety-related parts of control systems - Part 1: General principles for design

EN 12874:2001 Flame arresters - Performance requirements, test methods and operating limits (A review against EN ISO 16852:2016 which is

harmonized shows no significant changes relevant to this equipment so EN 12874 :2001 continues to represent “State of the Art”.)

EN 13463-1:2009

Non-electrical equipment for potentially explosive atmospheres – Part 1: Basics methodology and requirements (A review against EN

ISO 80079-36:2016 which is harmonized shows no significant changes relevant to this equipment so EN 13463-1:2009 continues to

represent “State of the Art”.)

EN 13463-5:2011

Non-electrical equipment for potentially explosive atmospheres – Part 5: Protection by constructional safety “c“ (A review against EN

ISO 80079-37:2016 which is harmonized shows no significant changes relevant to this equipment so EN 13463-5:2011 continues to

represent “State of the Art”.)

EN 1127-1:2011 Explosive atmospheres - Explosion prevention and protection - Part 1: Basic concepts and methodology

Compressors and vacuum pumps - Safety requirements - Part 1 and Part 2

Person authorised to compile the technical file: Gerd RohwederBusch Dienste GmbHSchauinslandstr. 1DE-79689 Maulburg

Chevenez, 22.10.2019

Christian Hoffmann, General director(1) In case control systems are integrated.

fabrice.lallemand
CE Declaration
fabrice.lallemand
CE Declaration
fabrice.lallemand
CE Declaration
Page 57: 0870203597 NC0100-0300B WCV Ex -0001 IM en

EU Declaration of Conformity - ATEX 2G(i/o) and 3G(i/o) | 16

0870203597_NC0100-0300B_WCV_Ex_-0001_IM_en 57 / 60

16 EU Declaration of Conformity - ATEX 2G(i/o) and 3G(i/o)This Declaration of Conformity and the CE-mark affixed to the nameplate are valid for the machine within theBusch scope of delivery. This Declaration of Conformity is issued under the sole responsibility of the manufacturer.When this machine is integrated into a superordinate machinery the manufacturer of the superordinate machinery(this can be the operating company, too) must conduct the conformity assessment process for the superordinatemachine or plant, issue the Declaration of Conformity for it and affix the CE-mark.

The manufacturer Ateliers Busch S.A.Zone IndustrielleCH-2906 Chevenez

declares that the machine(s) COBRA ‘ATEX’ NC/NT/NX 0100 B; NC/NX 0200 B; NC/NT/NX 0300 B

with the serial number:

has (have) been manufactured in accordance with the European Directives:

– ‘Machinery’ 2006/42/EC

– ‘ATEX Directive’ 2014/34/EU, for use in potentially explosive areas according to classification written on themachine nameplate

– ‘Electromagnetic Compatibility’ 2014/30/EU

– ‘RoHS’ 2011/65/EU + Commission delegated directive (EU) 2015/863, restriction of the use of certain hazard-ous substances in electrical and electronic equipment

and following the standards.

Standard Title of the Standard

EN ISO 12100:2010 Safety of machinery - Basic concepts, general principles of design

EN ISO 13857:2008 Safety of machinery - Safety distances to prevent hazard zones being reached by the upper and lower limbs

EN 1012-1:2010EN 1012-2:1996 + A1:2009EN ISO 2151:2008 Acoustics - Noise test code for compressors and vacuum pumps - Engineering method (grade 2)EN 60204-1:2006 + A1:2009 Safety of machinery - Electrical equipment of machines - Part 1: General requirementsEN 61000-6-2:2005 Electromagnetic compatibility (EMC) - Generic standards. Immunity for industrial environmentsEN 61000-6-4:2007 + A1:2011 Electromagnetic compatibility (EMC) - Generic standards. Emission standard for industrial environments

EN ISO 13849-1:2015 (1) Safety of machinery - Safety-related parts of control systems - Part 1: General principles for design

EN ISO 80079-36:2016Explosive atmospheres - Part 36: Non-electrical equipment for explosive atmospheres - Basic method and requirements

EN ISO 80079-37:2016Explosive atmospheres - Part 37: Non-electrical equipment for explosive atmospheres - Non electrical type of protection constructional safety “c”, control of ignition source “b”, liquid immersion “k”

EN 1127-1:2011 Explosive atmospheres - Explosion prevention and protection - Part 1: Basic concepts and methodology

Compressors and vacuum pumps - Safety requirements - Part 1 and Part 2

Person authorised to compile the technical file: Gerd RohwederBusch Dienste GmbHSchauinslandstr. 1DE-79689 Maulburg

Chevenez, 24.04.2019

Christian Hoffmann, General director(1) In case control systems are integrated.

fabrice.lallemand
CE Declaration
fabrice.lallemand
CE Declaration
fabrice.lallemand
CE Declaration
Page 58: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Note

Page 59: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Note

Page 60: 0870203597 NC0100-0300B WCV Ex -0001 IM en

Argentinawww.buschvacuum.com/[email protected]

Australiawww.buschvacuum.com/[email protected]

Austriawww.buschvacuum.com/[email protected]

Bangladeshwww.buschvacuum.com/[email protected]

Belgiumwww.buschvacuum.com/[email protected]

Brazilwww.buschvacuum.com/[email protected]

Canadawww.buschvacuum.com/[email protected]

Chilewww.buschvacuum.com/[email protected]

Chinawww.buschvacuum.com/cn/[email protected]

Colombiawww.buschvacuum.com/[email protected]

Czech Republicwww.buschvacuum.com/[email protected]

Denmarkwww.buschvacuum.com/[email protected]

Finlandwww.buschvacuum.com/[email protected]

Francewww.buschvacuum.com/[email protected]

Germanywww.buschvacuum.com/[email protected]

Hungarywww.buschvacuum.com/[email protected]

Indiawww.buschvacuum.com/[email protected]

Irelandwww.buschvacuum.com/[email protected]

Israelwww.buschvacuum.com/[email protected]

Italywww.buschvacuum.com/[email protected]

Japanwww.buschvacuum.com/[email protected]

Koreawww.buschvacuum.com/[email protected]

[email protected]

Mexicowww.buschvacuum.com/[email protected]

Netherlandswww.buschvacuum.com/[email protected]

New Zealandwww.buschvacuum.com/[email protected]

Norwaywww.buschvacuum.com/[email protected]

Peruwww.buschvacuum.com/[email protected]

Polandwww.buschvacuum.com/[email protected]

Portugalwww.buschvacuum.com/[email protected]

Romaniawww.buschvacuum.com/[email protected]

Russiawww.buschvacuum.com/[email protected]

Singaporewww.buschvacuum.com/[email protected]

South Africawww.buschvacuum.com/[email protected]

Spainwww.buschvacuum.com/[email protected]

Swedenwww.buschvacuum.com/[email protected]

Switzerlandwww.buschvacuum.com/[email protected]

Taiwanwww.buschvacuum.com/[email protected]

Thailandwww.buschvacuum.com/[email protected]

Turkeywww.buschvacuum.com/[email protected]

United Arab Emirateswww.buschvacuum.com/[email protected]

United Kingdomwww.buschvacuum.com/[email protected]

USAwww.buschvacuum.com/[email protected]

www.buschvacuum.com

Busch Vacuum Pumpsand SystemsAll over the World in Industry

0870203597/-0001_en / © Ateliers Busch S.A.