04_MDS Selection Software

62
Technical Training 2007 Technical Training 2007 TECHNICAL TRAINING TECHNICAL TRAINING 2007 2007

Transcript of 04_MDS Selection Software

Page 1: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

TECHNICAL TRAINING TECHNICAL TRAINING

20072007

Page 2: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

SELECTION SOFTWARESELECTION SOFTWARE

Page 3: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Sample of Installation

Page 4: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Main Factors to consider during Piping SelectionMain Factors to consider during Piping Selection

• Location of equipmentLocation of equipment

• Indoor UnitIndoor Unit

• Outdoor UnitOutdoor Unit

• Refnet & Distributor JointRefnet & Distributor Joint

Unit & Piping Selection

These item will influence the piping layout and length of the design

Page 5: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Some other factors to consider during Piping SelectionSome other factors to consider during Piping Selection

• Equivalent Piping LengthEquivalent Piping Length

• Type of Joint for branchesType of Joint for branches

• Outdoor capacity factorOutdoor capacity factor

• Piping length & height factorPiping length & height factor

• Refrigerant Pipe SpecificationRefrigerant Pipe Specification

Unit & Piping Selection

Page 6: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Equivalent length is the converted length and includes parts such as elbow, which has pressure losses in the pipe. The formula is as follow:

Equivalent length= Real length of tubing + No. of elbow × Equivalent length of each elbow + No. of oil trap ×Equivalent length of each oil trap

Equivalent Piping Calculation

Elbow Oil Trap9.52 0.18 1.30

12.70 0.20 1.5015.88 0.25 2.0019.05 0.35 2.4022.02 0.40 3.0025.40 0.45 3.4028.58 0.50 3.7031.80 0.55 4.00

Diameter of Pipe

Equivalent Length

Page 7: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Restriction of Piping Length

3~5 Hp 6 Hp 8~10 Hp 12~30 Hp100 125 250 350

Actual piping length 50 70 125 150Equivalent length 60 80 150 200

25 30

Outdoor above 20 30Indoor above 20 30

Length (m)

Piping

Height

Maximum equivalent length from first branch to furthers unit

Maximum height between indoor unit

Maximum length of longest branch

Between further indoor and outdoor

Total equivalanet length

15

40

5040

Page 8: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Important Factor to Consider

Example:Outdoor Model : MDS100BRPipe Diameter : 28.6 mmMain Pipe : 80mBranch Length: 20mElbows: 10 unitsOil traps: 3 units

Elbow Oil Trap9.52 0.18 1.30

12.70 0.20 1.5015.88 0.25 2.0019.05 0.35 2.4022.02 0.40 3.0025.40 0.45 3.4028.58 0.50 3.7031.80 0.55 4.00

Diameter of Pipe

Equivalent Length

Equivalent Length

= Real length of tubing + No. of elbow × Equivalent length of each elbow + No. of oil trap ×Equivalent length of each oil trap= (80 + 20) + (10 X 0.5) + (3 X 3.7) = 116.1 m

Page 9: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

When the equivalent length is more than 90% of the maximal real length of the main tubing , the gas pipe need to be increase to one size bigger (diameter).

After expanded the gas pipe to a larger diameter, the equivalent length need to be recalculate. The formula is as follow:

Expanded Equivalent Length

= Equivalent length of main piping X 0.5 + equivalent length of the branch

Criteria 1

Criteria 2

Important Factor to Consider

Page 10: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Important Factor to Consider

3~5 Hp 6 Hp 8~10 Hp 12~30 Hp100 125 250 350

Actual piping length 50 70 125 150Equivalent length 60 80 150 200

25 30

Outdoor above 20 30Indoor above 20 30

Length (m)

Piping

Height

Maximum equivalent length from first branch to furthers unit

Maximum height between indoor unit

Maximum length of longest branch

Between further indoor and outdoor

Total equivalanet length

15

40

5040

Maximum allow actual length for 10Hp is 125mCalculated Equivalent Length is 116.1mRatio of Equivalent Length over Maximum allow Actual Length= 92.88%

Equivalent length is more than 90% of the maximal real length.Hence the gas Pipe of MDS100BR need to change.

Example:

Page 11: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Refrigerant Copper Pipe Specification : MDS-B

Unit & Piping Selection

Page 12: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Important Factor to ConsiderExample:Hence the gas Pipe of MDS100BR need to change from 28.6 mm to 31.75 mmAfter expanded the gas pipe to a larger diameter, the equivalent length need to be recalculate.

Expanded Equivalent Length = Equivalent length of main piping X 0.5 + equivalent length of the branch

Main Pipe : 80mBranch Length: 20mElbows: 10 unitsOil traps: 3 units

Equivalent Length

= Real length of tubing + No. of elbow × Equivalent length of each elbow + No. of oil trap ×Equivalent length of each oil trap= (80 + 20) + (10 X 0.5) + (3 X 3.7) = 116.1 m

Expanded Equivalent Length = [80 + (10 X 0.5) + (3 X 3.7)] X 0.5 + 20

Expanded Equivalent Length = 68.05 m

Page 13: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

• Type of Joint for branchesType of Joint for branches

• Influence the piping layout designInfluence the piping layout design

• Outdoor capacity factorOutdoor capacity factor

• Influence by the design ambient temperature and Influence by the design ambient temperature and indoor temperatureindoor temperature

• Piping length & height factor Piping length & height factor

• Influence by the location of outdoor and the total Influence by the location of outdoor and the total piping lengthpiping length

• Refrigerant Pipe SpecificationRefrigerant Pipe Specification

• Use to determine the branches diameterUse to determine the branches diameter

Unit & Piping Selection

Page 14: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Selection of branch joint / distributors for MDS

Unit & Piping Selection

ModelMDS-Y1MDS-Y2MDS-Y3MDS-Y4MDS-Y6MDS-Y7MDS-C1MDS-C2MDS-C3

Refnet Joint (2 Branches)

Distributors Header (4 Branches)

Page 15: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

MDS-Y1~Y4 dimensional drawing

A B C D E

(outer diameter)

F G H I

(outer diameter)

J K L M N

(outer diameter)

O P Q R

MDS-Y1 553 172 293 120 28.6 28.9 25.7 22.5 28.6 28.9 25.7 22.5 19.3 22.2 19.3 16.1 12.9 9.7MDS-Y2 420 142 223 80 15.88 16.1 12.9 9.7 12.7 12.9 9.7 6.5 12.7 12.9 9.7 6.5MDS-Y3 420 142 223 80 15.88 16.1 12.9 9.7 12.7 12.9 9.7 6.5 15.88 16.1 12.9 9.7MDS-Y4 493 142 223 80 22.2 22.5 19.3 16.1 19.1 19.3 16.1 12.9 9.7 19.1 19.3 16.1 12.9

Diameter (mm)Refnet model

Length(mm) Diameter (mm) Diameter (mm)

Unit & Piping Selection

Page 16: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

MDS-Y6 dimensional drawing

Unit & Piping Selection

Page 17: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

MDS-Y7 dimensional drawing

Unit & Piping Selection

Page 18: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

MDS-C1 dimensional drawing

Unit & Piping Selection

Page 19: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

MDS-C2~C3 dimensional drawing

Unit & Piping Selection

Page 20: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Using Distribution Header may lead to imbalance refrigerant flow.

Unit & Piping Selection

Page 21: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Connection Type of Refnet Joint/Distributors

Refnet Joint

Unit & Piping Selection

Page 22: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Connection Type of Refnet Joint/Distributor

Distributor

Unit & Piping Selection

Page 23: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Connection Type of Refnet Joint/Distributors

Unit & Piping Selection

Refnet Joint Distributor

Page 24: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Connection Type of Refnet Joint/Distributors

Unit & Piping Selection

Refnet Joint Distributor

Page 25: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Cooling Capacity Correction Factor

Unit & Piping Selection

Page 26: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Heating Capacity Correction Factor

Unit & Piping Selection

Page 27: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Cooling cap. factor

Cooling Capacity Correction Factor

Unit & Piping Selection

Page 28: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Heating Capacity Correction Factor

Unit & Piping Selection

Page 29: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Refrigerant Pipe Specification : MDS-A

Unit & Piping Selection

Page 30: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Refrigerant Pipe Specification : MDS-B

Unit & Piping Selection

Page 31: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Example

C

A B

D

E

F

Building Type: Bungalow

Unit & Piping Selection

Page 32: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

RequirementRequirementCooling only modelCooling only model

• Ambient temperature : 40.0 Ambient temperature : 40.0 °C°C

• Indoor temperature : 21.0 Indoor temperature : 21.0 °C°C

Other InformationOther Information

• Piping lengthPiping length :: 70m70m

• Height between I/OHeight between I/O :: 4m4m

• Outdoor Unit located below indoorsOutdoor Unit located below indoors

Unit - AWall

Mounted

Unit - BWall

Mounted

Unit - CWall

Mounted

Unit - DWall

Mounted

Unit - ECeiling

Cassette

Unit - FCeiling

Concealed

2.7 2.7 5.0 5.4 8.8 6.4

Required Cooling Capacity

(kW)

Unit & Piping Selection

Example

Page 33: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Indoor RequirementWall Mounted

WMD 09G WMD 10G WMD 15G WMD 20G WMD 25GBtu/h 8,500 9,600 12,300 19,100 22,200kW 2.5 2.8 3.6 5.6 6.5

Ceiling CassetteCKD 10C CKD 15C CKD 20C

Btu/h 9,600 12,300 19,100kW 2.8 3.6 5.6

Ceiling CassetteCKD 20A CKD 25A CKD 30A CKD 40A CKD 50A

Btu/h 19,100 22,200 30,700 38,200 47,800kW 5.6 6.5 9.0 11.2 14.0

Ceiling ConcealedCCD 10C CCD 15C CCD 20C CCD 25C CCD 28C

Btu/h 9,600 12,300 19,100 22,200 27,300kW 2.8 3.6 5.6 6.5 8.0

Ceiling ConcealedCCD 30C CCD 38C CCD 40C CCD 50C CCD 60C

Btu/h 30,700 34,100 38,200 47,800 56,000kW 9.0 10.0 11.2 14.0 16.4

COOLING ONLY MODEL

NOMINAL CAPACITY

COOLING ONLY MODEL

COOLING ONLY MODEL

COOLING ONLY MODEL

NOMINAL CAPACITY

COOLING ONLY MODEL

NOMINAL CAPACITY

NOMINAL CAPACITY

NOMINAL CAPACITYUnit - A Wall Mounted 2.7Unit - B Wall Mounted 2.7Unit - C Wall Mounted 5.0Unit - D Wall Mounted 5.4Unit - E Ceiling Cassette 8.8Unit - F Ceiling Concealed 6.4

Required Cooling Capacity(kW)

Unit & Piping Selection

Page 34: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Example

A B C D E F

Capacity, kW 1.8 2.0 2.2 4.0 5.0 5.8

Model 10 10 20 20 30 25

HP of indoor unit 2.8 2.8 5.6 5.6 9.0 6.5

• Total Indoor capacity is 32.3 kW

Unit & Piping Selection

Page 35: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Example

Selection CriteriaSelection Criteria

• Total Indoor capacity must be range between 50% ~ Total Indoor capacity must be range between 50% ~ 120% of the outdoor capacity.120% of the outdoor capacity.

• We recommend that the outdoor capacity equals to the We recommend that the outdoor capacity equals to the total indoor capacity or a little larger than the indoor total indoor capacity or a little larger than the indoor capacitycapacity

Unit & Piping Selection

Page 36: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Example

Selected Outdoor Selected Outdoor : : MDS120BMDS120B

Cooling CapacityCooling Capacity : 32.5kW: 32.5kW

%38.99

%1005.323.32

%100

/

CapacityOutdoorCapacityIndoorTotal

RatioOI

Comply to selection criteria

kWMDS080 24.5MDS100 28.0MDS120 32.5MDS150 40.0MDS180 47.5MDS200 50.0MDS220 55.0MDS240 65.0MDS260 70.0MDS280 75.0MDS300 80.0

ModelCooling Capacity

Unit & Piping Selection

Page 37: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Example• Selected Outdoor and Indoor ModelSelected Outdoor and Indoor Model

Outdoor Model MDS 120B 32.5 kW

Indoor A WMD 10G 2.8 kW

Indoor B WMD 10G 2.8 kW

Indoor C WMD 20G 5.6 kW

Indoor D WMD 20G 5.6 kW

Indoor E CKD 30A 9.0 kW

Indoor F CCD 25C 6.5 kW

Unit & Piping Selection

Page 38: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

ExampleOutdoor Capacity factorOutdoor Capacity factor

• Cooling only modelCooling only model

• Ambient temperature : 40.0 Ambient temperature : 40.0 °C°C

• Indoor temperature : 22.0 Indoor temperature : 22.0 °C°C1.03

Unit & Piping Selection

Page 39: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

ExamplePiping length & height factorPiping length & height factor

• Piping lengthPiping length :: 70m70m

• Height between I/OHeight between I/O :: 4m4m

• Outdoor Unit located below indoorsOutdoor Unit located below indoors

91%

Unit & Piping Selection

Page 40: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Example

Total Capacity Total Capacity

• = Outdoor Capacity X Outdoor Capacity Factor = Outdoor Capacity X Outdoor Capacity Factor

• X Piping length & height FactorX Piping length & height Factor

• = 32.5 kW X 1.03 X 94%= 32.5 kW X 1.03 X 94%

• = 31.47 kW= 31.47 kW

Unit - A Wall Mounted 2.7Unit - B Wall Mounted 2.7Unit - C Wall Mounted 5.0Unit - D Wall Mounted 5.4Unit - E Ceiling Cassette 8.8Unit - F Ceiling Concealed 6.4Total Required Capacity 31.0

Required Cooling Capacity(kW)

Comply to requirement

Unit & Piping Selection

Page 41: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Example

C

A B

D

E

F

Unit & Piping Selection

Building Type: Bungalow

Page 42: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Example 1.1. Selection pipe diameterSelection pipe diameter

A B C

D E

MDS120B

CCD 25C WMD 20G WMD 10G

WMD 20GCKD 30A WMD 10G

6.5 kW5.6 kW 2.8 kW

5.6 kW9.0 kW

2.8 kW

Unit & Piping Selection

Page 43: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Refrigerant Pipe Specification : MDS-B

Unit & Piping Selection

Page 44: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Example

A B C

D E

MDS120B

CCD 25C WMD 20G WMD 10G

WMD 20GCKD 30A WMD 10G

6.5 kW5.6 kW 2.8 kW

5.6 kW9.0 kW

2.8 kW

Main pipeMain pipe diameter : diameter : ø ø 15.8815.88mm / ø mm / ø 28.628.6mmmm

Downstream capacityDownstream capacity

Point APoint A A-B-C : 14.9 kWA-B-C : 14.9 kWA-D-E : 17.4 kW A-D-E : 17.4 kW

Point BPoint B B-C : 8.4 kWB-C : 8.4 kWD-E : 8.4 kWD-E : 8.4 kW

Unit & Piping Selection

Page 45: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Refrigerant Pipe Specification : MDS-B

Point APoint AA-B-C : 14.9 kWA-B-C : 14.9 kWA-D-E : 17.4 kWA-D-E : 17.4 kW

Unit & Piping Selection

Page 46: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Example

A B C

D E

MDS120B

CCD 25C WMD 20G WMD 10G

WMD 20GCKD 30A WMD 10G

6.5 kW5.6 kW 2.8 kW

5.6 kW9.0 kW

2.8 kW

Main pipeMain pipe diameter : diameter : ø ø 15.8815.88mm / ø mm / ø 28.628.6mmmm

A-D diameter : ø 12.7mm / ø 25.4mm

A-B diameter : A-B diameter : ø ø 9.529.52mm / ø mm / ø 19.0519.05mmmm

Unit & Piping Selection

Page 47: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Example

A B C

D E

MDS120B

CCD 25C WMD 20G WMD 10G

WMD 20GCKD 30A WMD 10G

6.5 kW5.6 kW 2.8 kW

5.6 kW9.0 kW

2.8 kW

Point BPoint BB-C : 8.4 kWB-C : 8.4 kWB-CCD25C : 6.5 kWB-CCD25C : 6.5 kW

Unit & Piping Selection

Page 48: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Refrigerant Pipe Specification : MDS-B

Point BPoint BB-C : 8.4 kWB-C : 8.4 kWB-CCD25C : 6.5 kWB-CCD25C : 6.5 kW

Unit & Piping Selection

Page 49: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Example

A B C

D E

MDS120B

CCD 25C WMD 20G WMD 10G

WMD 20GCKD 30A WMD 10G

6.5 kW5.6 kW 2.8 kW

5.6 kW9.0 kW

2.8 kW

A-B: A-B: ø ø 9.529.52

/ ø / ø 19.0519.05

B-CCD25C: B-CCD25C: ø 9.52 / ø1ø 9.52 / ø15.885.88

B-C: B-C: ø 9.52 / ø1ø 9.52 / ø15.885.88

Unit & Piping Selection

Page 50: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Example

Inlet Outlet Inlet OutletTo B & C 14.90 9.52 19.05To D & E 17.40 12.70 25.40To CCD25C 6.50 9.52 15.88To C 8.40 9.52 15.88To WM D20G 5.60 6.35 15.88To WM D10G 2.80 6.35 9.52To CKD30A 9.00 9.52 19.05To E 8.40 9.52 15.88To WM D20G 5.60 6.35 15.88To WM D10G 2.80 6.35 9.52

15.88

28.60

19.05

15.88

Point E

15.88

9.52

9.52

12.70

9.52

Point A

Point B

Point C

Point D

Liquid pipe (ø, mm) Gas pipe (ø, mm)Location

Capacity (kW)

Branch

25.40

Unit & Piping Selection

Page 51: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Example

A B C

D E

MDS120B

CCD 25C WMD 20G WMD 10G

WMD 20GCKD 30A WMD 10G

6.5 kW5.6 kW 2.8 kW

5.6 kW

9.0 kW

2.8 kW

Main Pipe: ø Main Pipe: ø 15.8815.88 / ø / ø 28.628.6

B-C: ø 9.52 / ø1B-C: ø 9.52 / ø15.885.88

A-B: ø 9.52 / ø1A-B: ø 9.52 / ø19.059.05

A-D: ø12.7 / ø25.4A-D: ø12.7 / ø25.4 D-E: ø9.52 / ø1D-E: ø9.52 / ø15.885.88

Unit & Piping Selection

Page 52: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Example Selection of branchSelection of branch

Select the refnet joint of point ASelect the refnet joint of point A

A (liquid) A (liquid) : MDS-: MDS-Y2Y2

A (gas) A (gas) : MDS-: MDS-Y1Y1

A B C D E

(outer diameter)

F G H I

(outer diameter)

J K L M N

(outer diameter)

O P Q R

MDS-Y1 553 172 293 120 28.6 28.9 25.7 22.5 28.6 28.9 25.7 22.5 19.3 22.2 19.3 16.1 12.9 9.7MDS-Y2 420 142 223 80 15.88 16.1 12.9 9.7 12.7 12.9 9.7 6.5 12.7 12.9 9.7 6.5MDS-Y3 420 142 223 80 15.88 16.1 12.9 9.7 12.7 12.9 9.7 6.5 15.88 16.1 12.9 9.7MDS-Y4 493 142 223 80 22.2 22.5 19.3 16.1 19.1 19.3 16.1 12.9 9.7 19.1 19.3 16.1 12.9

Diameter (mm)Refnet model

Length(mm) Diameter (mm) Diameter (mm)

A-D diameter : A-D diameter : ø 12.7 / ø 25.4ø 12.7 / ø 25.4

A-B diameter : A-B diameter : ø 9.52 / ø 19.05ø 9.52 / ø 19.05

All unit in mm

AA

Main Pipe diameter : Main Pipe diameter : ø 15.88 / ø 28.6ø 15.88 / ø 28.6

Unit & Piping Selection

Page 53: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Example

A B C

D E

MDS120B

CCD 25C WMD 20G WMD 10G

WMD 20GCKD 30A WMD 10G

6.5 kW5.6 kW 2.8 kW

5.6 kW9.0 kW2.8 kW

Main Pipe: ø Main Pipe: ø 15.8815.88 / ø / ø 28.628.6

B-C: B-C: ø 9.52 / ø1ø 9.52 / ø15.885.88

A-B: ø 9.52 / ø1A-B: ø 9.52 / ø19.059.05

A-D: ø12.7 / ø25.4A-D: ø12.7 / ø25.4 D-E: ø9.52 / ø1D-E: ø9.52 / ø15.885.88

Liquid GasWMD 10G 6.35 9.52WMD 20G 6.35 15.88CCD 25C 9.52 15.88CKD 30A 9.52 15.88

ModelIndoor Valve Size (Ø, mm)

Unit & Piping Selection

Page 54: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Example

A B C

D E

MDS120B

CCD 25C WMD 20G WMD 10G

WMD 20GCKD 30A WMD 10G

6.5 kW5.6 kW 2.8 kW

5.6 kW9.0 kW

2.8 kW

Liquid GasTo B & CTo D & ETo CCD25CTo CTo WM D20GTo WM D10GTo CKD30ATo ETo WM D20GTo WM D10G

MDS-Y2 MDS-Y4

MDS-Y2 MDS-Y1

MDS-Y2 MDS-Y1

Refnet Joint

MDS-Y2 MDS-Y4

MDS-Y2 MDS-Y4

Point E

Point A

Point B

Point C

Point D

Location Branch

Unit & Piping Selection

Page 55: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Example

Formula:

G = ∑ Li* Gi

Using liquid tube length to calculate required refrigerant. Add in refrigerant.

G : Refrigerant charge amountLi : The each section of liquid tube length in all (m)Gi : Charge amount per length ( g/m)

Unit & Piping Selection

Page 56: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Example

A B C

D E

MDS120B

CCD 25C WMD 20G WMD 10G

WMD 20GCKD 30A

WMD 10G

6.5 kW5.6 kW 2.8 kW

5.6 kW9.0 kW 2.8 kW

ø ø 15.88 (10m)15.88 (10m)

ø ø 9.52 (5m)9.52 (5m)

ø ø 9.52 (2m)9.52 (2m)

ø ø 9.52 (4m)9.52 (4m)ø ø 6.35 (2m)6.35 (2m)

ø ø 6.35 (5m)6.35 (5m)

ø ø 6.35 (5m)6.35 (5m)

ø ø 6.35 (2m)6.35 (2m)

ø ø 9.52 (5m)9.52 (5m)

ø ø 9.52 (5m)9.52 (5m)

ø ø 12.7 (25m)12.7 (25m)

Total Piping Length15.88mm – 10m12.7mm – 25m9.52mm – 21m6.35mm – 14m

Unit & Piping Selection

Page 57: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Example

Additional charge amount :

= ∑ Li* Gi

= (Piping Length for 15.88mm X Refrigerant Charge Amount)

+ (Piping Length for 12.7mm X Refrigerant Charge Amount)

+ (Piping Length for 9.52mm X Refrigerant Charge Amount)

+ (Piping Length for 6.35mm X Refrigerant Charge Amount)

= (10 X 180) + (25 x 120) + (21 x 80) + (14 x 50)

= 7180 g

Liquid tube diameter (mm) 6.35 9.52 12.7 15.88

Refrigerant charge amount (g/m) 50 80 120 180

Total Piping Length15.88mm – 10m 12.7mm – 25m9.52mm – 21m 6.35mm – 14m

Unit & Piping Selection

Page 58: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

EXV BoxEXV BoxEXV BoxEXV Box

Electronic Expansion Valve

Unit & Piping Selection

Page 59: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Indoor Unit EXV Box ModelCCD 10/15CKD 10/15WMD 10/15 MEX-16-2SAP-B

CCD 20CKD 20CED20WMD 20 MEX-20-2SAP-BCCD 25CKD 25

CED 25/28WMD 25 MEX-20-3SAP-B

CKD 30/40/50CCD 30/40/50/60

CED 40/50/62

MEX-16-2SAP-A

MEX-20-3SAP-A

MEX-20-2SAP-A

MEX-25-3SAP-A

Electronic Expansion Valve

2 units

1 unit

1 unit

2 units

Unit & Piping Selection

Page 60: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Unit & Piping Selection

Page 61: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Software DemoSoftware Demo

Page 62: 04_MDS Selection Software

Technical Training 2007Technical Training 2007

Thank YouThank You