0480 UPS DC1 Annual 061715
Transcript of 0480 UPS DC1 Annual 061715
EMCOR Facilities Services Joe Tate 4 Brocade PKWY Broomfield CO. 80021 303-884-1536 [email protected]
0480 BRM Brocade UPS Annual Testing UPS DC1 06/17/2015
Prepared for:
Broomfield Brocade Communications Systems, Inc Ron Anthony Facilities Maintenance and Operations (303) 319 - 8353 [email protected]
MDC: 6/17/2015
Voltage: Primary AIC as
metered ZΩ UPS Model:
E / A - BØ: 492.7 I / AØ: 118.2 AØ - ZΩ: 0.10 1 DC1
E / B - CØ: 492.7 I / BØ: 117.7 BØ - ZΩ: 0.11 0 DC2
E / C - AØ: 490.6 I / CØ: 118.2 CØ - ZΩ: 0.10 0 OEM
E / AØ: 284.5 kVA / AØ: 33.6 AMPS: 0 SQA
E / BØ: 284.5 kVA / BØ: 33.5 3Ø ASYM: 8263.3
E / CØ: 283.3 kVA / CØ: 33.5
kVA 3Ø: 100.6
UPS Unit: 6/16/2015 Panel :
IP: 78.8%
WO#
Voltage: Power Used: AØ - ZΩ: 0.33
A-Bø: 479.2 BØ - ZΩ: 0.24
B-Cø: 480.3 kVA / AØ: 26.5 CØ - ZΩ: 0.33
A-Cø: 479.0 kVA / BØ: 24.9 AMPS:
Aø: 276.7 kVA / CØ: 27.9 3Ø ASYM: 2831.9
Bø: 277.3 KVA 3ø: 79.3Cø: 276.6
Power Available:
Rated KVA: 500.0 0.8
Current: Rated KW: 400.0
Aø: 95.7 Actual PF%: 0.96
Bø: 89.8 KW: 76.1 DC1: 16 800
Cø: 100.9 KVA %: 15.9 DC2: 12 500
Nuet Amps: 9.6 KW%: 19.0 OEM: 12 550
N Inbal: 10.1% SQA: 12 550
DC1: 4/1/2013
Datasafe
16HX800F
Months in
Service: 27 KWh: # of Strings:2 E: 16.0 DC2: 1/1/2013
sprinter
S12V500F
DC String E: 521.5 768# Batteries: 30 I: 800.0 OEM: 3/1/2014
Sprinter
S12V550F
AC Ripple I: 3.2 Avg Float VDC: 17.38 kW: 12.8 SQA: 5/1/2015
Sprinter
S12V550F
<=.7
<=250mA
42.0MATH 140.1528 0.112083 9.4252729 74.666381
H2D1
UPS DC1 UHD1
Solarwinds
Battery Info:
ZΩ
UPS Efficiancy:
:Minutes RUN Time / On Battery
31915335
Rated UPS PF:
Secondary AIC as
metered
Single Cell :
Ω to Earth:
I on Ground:
Battery String Information:
DC1 Sinewaves
Line Side Voltage Sinewave
Line Side Current Sinewave
Load Side Voltage Sinewave
Load Side Current Sinewave
Page 2 EMCOR Facilites Services
554.2 1 16
1.338 0.1 800
1
DC VOLTS AC MV DC VOLTS AC MV
1 17.745 3111 21 17.710 3286
2 17.714 3115 22 17.669 3637Average dcV: 17.687 3 17.692 3115 23 17.605 3650
High dcV: 17.745 4 17.718 3630 24 17.652 3641low dcV: 17.563 5 17.706 3284 25 17.655 3296
6 17.714 3113 26 17.653 3643Average Ω: 3434.133 7 17.675 3463 27 17.605 3476
High Ω: 3652 8 17.719 3630 28 17.632 3650Low Ω: 3111 9 17.718 3630 29 17.621 365217.745 17.71 10 17.725 3282 30 17.563 348517.675 17.563 11 17.729 3627 3117.745 3652 12 17.718 3457 32
3111 3286 13 17.729 3282 33
14 17.706 3113 34
15 17.716 3457 35
16 17.729 3282 36
17 17.695 3634 37
18 17.677 3638 38
19 17.721 3457 39
20 17.695 3288 40
NOTES:
CELL AH:
UPS Name:
STRING VOLTAGE AC:
BATTERY STRING:
DC1
DC CURRENT:
STRING VOLTAGE DC:
AC RIPPLE CURRENT:
CELL VDC:
Datasafe 16HX800F
BATTERY MAKE:
Battery cab #:
17.25
17.50
17.75
18.00
18.25
2000
3000
4000
5000
CAB_1
Vol
tage
(V)
Int.
Res
. (u-
Ohm
s)
Cell Number 3 6 9 12 15 18 21 24 27Cell Number
Voltage 17.692 17.714 17.718 17.718 17.716 17.677 17.710 17.652 17.605Internal Res 3115.000 3113.000 3630.000 3457.000 3457.000 3638.000 3286.000 3641.000 3476.000
17.25
17.50
17.75
18.00
18.25
2000
3000
4000
Apr2015
May Jun
CAB_1V
olta
ge (V
)
In
t. R
es. (
u-O
hms)
Read Date
554.3 1 16
1.327 0.1 800
2
DC VOLTS AC MV DC VOLTS AC MV
1 18.366 3280 21 18.089 3630
2 18.399 3450 22 18.011 3290
Average dcV: 18.125 3 18.246 3459 23 18.06 3632
High dcV: 18.473 4 18.473 3623 24 18.062 3453
Low dcV: 17.773 5 18.359 3627 25 18.05 3634
6 18.299 3630 26 18.105 3810
Average Ω: 3449.233 7 18.164 3096 27 17.992 3288
High Ω: 3810 8 18.115 3270 28 17.962 3465
Low Ω: 3096 9 18.183 3096 29 17.912 3641
18.473 18.105 10 18.169 3268 30 17.923 3638
17.773 17.912 11 18.135 3098 31
3632 3810 12 18.091 3272 32
3096 3288 13 17.961 3286 33
14 17.773 3282 34
15 18.223 3450 35
16 18.131 3459 36
17 18.265 3632 37
18 18.125 3630 38
19 18.013 3461 39 20 18.095 3627 40
NOTES:
DC1UPS Name:
STRING VOLTAGE DC: STRING VOLTAGE AC:
DC CURRENT:
BATTERY MAKE:Batter cab #:
BATTERY STRING:
AC RIPPLE CURRENT:
Datasafe 16HX800F
CELL VDC:
CELL AH:
17.5
18.0
18.5
19.0
2000
3000
4000
5000
CAB_2
Vol
tage
(V)
Int.
Res
. (u-
Ohm
s)
Cell Number 3 6 9 12 15 18 21 24 27Cell Number
Voltage 18.246 18.299 18.183 18.091 18.223 18.125 18.089 18.062 17.992Internal Res 3459.000 3630.000 3096.000 3272.000 3450.000 3630.000 3630.000 3453.000 3288.000
17.75
18.00
18.25
18.50
18.75
2000
3000
4000
5000
Apr2015
May Jun
CAB_2V
olta
ge (V
)
In
t. R
es. (
u-O
hms)
Read Date
EMCOR Facilities Services
Summery page06/12/2014
Cabinet 1:
All batteries are showing good
Cabinet 2:
All batteries are showing good
Cabinet 3:
N/A
Summery:
UPS appears to be in very good working condition. No problems found.
If There are any questions please feel free to contact me
Joe Tate
EMCOR Facilities
Broomfield Brocade
303-884-1536
Replaced Filter Media.
UPS NameInstallation
Date:
Age in
months:
Battery Date
Code
Battery Age in
months
DC Oil filled
Capss:
DC_O age in
months
AC Oil filled
Caps:
AC_O age in
monthsFilters:
Filters Age in
months:Firmware:
Firmware age
in months*
DC Electrolitic
Caps
DC_E age in
months06/17/15
UPS DC1 3/1/2013 28 3/1/2013 28 3/1/2013 28 3/1/2013 28 6/18/2015 0 3/1/2013 28 3/1/2013 28
UPS DC2 6/10/2009 73 1/1/2013 30 6/10/2009 73 6/10/2009 73 6/17/2015 0 1/1/2013 30 6/10/2009 73
UPS OEM 8/22/2003 144 3/1/2014 16 5/24/2010 62 5/24/2010 62 6/16/2015 0 5/24/2010 62 8/22/2003 144
UPS SQA 8/22/2003 144 5/15/2015 1 5/24/2010 62 5/24/2010 62 6/16/2015 0 5/24/2010 62 8/22/2003 144
Watch closely at: 200 48 72 72 9 60 200
Recommend replace: 224 60 84 84 12 80 224
Needs Replacing!!! 248 72 96 96 15 100 248
* Firmware may not be available for older models. Contact OEM for details.
SqDHA3510001000A
Panel H2D1MLO
SqDMJ800AC Input
SqDMJ800Maint.Bypass
Input Breaker CB1
Maintenance Bypass Breaker
Static Switch
Input Contactor (K1) UPM1
Input Contactor (K1) UPM2
BackfeedContactor (K5)
Rectifier UPM1
Rectifier UPM2
InverterUPM1
Inverter UPM2
Output Contactor (K3)UPM1
Output Contactor (K3) UPM2
Battery ConverterUPM1
Battery ConverterUPM2
Battery Contactor (K2) UPM1
Battery Contactor (K2) UPM2
BatteryCabinet 1
Battery Cabinet 2
MaintenaceIsolation Breaker
MDC2 2500A Bus
1000A Bus
Single Feed Kit
EATON 9395
UPS DC1 "A Bus"
500kVA / 400kW
480V 3Ø - 480V 3Ø
Joe TateEMCOR Facilities ServicesBroomfield Brocade
EATON 9395MaintenanceBypassModule
AC 3Ø Critical Load
0480 BRM Brocade UPS Testing
Joe Tate | (303) 884-1536 | [email protected]
Inspection Summary
File name UPS DC1 (1).is2 Inspection Date and Time 1/1/2000 3:45:56 PM
Severity
File name UPS DC1 (2).is2 Inspection Date and Time 1/1/2000 3:46:29 PM
Severity
File name UPS DC1 (3).is2 Inspection Date and Time 1/1/2000 3:46:47 PM
Severity
File name UPS DC1 (4).is2 Inspection Date and Time 1/1/2000 3:47:17 PM
Severity
File name UPS DC1 (5).is2 Inspection Date and Time 1/1/2000 3:47:38 PM
Severity
File name UPS DC1 (6).is2 Inspection Date and Time 1/1/2000 3:47:57 PM
Severity
0480 BRM Brocade UPS Testing
Joe Tate | (303) 884-1536 | [email protected]
UPS DC1 (1).is2 1/1/2000 3:45:56 PM
Visible Light Image
Graph
Image Info IR Sensor Size 160 x 120
0480 BRM Brocade UPS Testing
Joe Tate | (303) 884-1536 | [email protected]
UPS DC1 (2).is2 1/1/2000 3:46:29 PM
Visible Light Image
Graph
Image Info IR Sensor Size 160 x 120
0480 BRM Brocade UPS Testing
Joe Tate | (303) 884-1536 | [email protected]
UPS DC1 (3).is2 1/1/2000 3:46:47 PM
Visible Light Image
Graph
Image Info IR Sensor Size 160 x 120
0480 BRM Brocade UPS Testing
Joe Tate | (303) 884-1536 | [email protected]
UPS DC1 (4).is2 1/1/2000 3:47:17 PM
Visible Light Image
Graph
Image Info IR Sensor Size 160 x 120
0480 BRM Brocade UPS Testing
Joe Tate | (303) 884-1536 | [email protected]
UPS DC1 (5).is2 1/1/2000 3:47:38 PM
Visible Light Image
Graph
Image Info IR Sensor Size 160 x 120
0480 BRM Brocade UPS Testing
Joe Tate | (303) 884-1536 | [email protected]
UPS DC1 (6).is2 1/1/2000 3:47:57 PM
Visible Light Image
Graph
Image Info IR Sensor Size 160 x 120
0480 BRM Brocade UPS Testing
Joe Tate | (303) 884-1536 | [email protected]
Summary ref#0480 BRM Broomfield UPS Testing All Batteriy Temps and associated DC Breakers are within range for the low current that is passing through them. Thanks Joe Tate EET / Master Electrician