04.00 GENERAL 04.02 POLE ATTACHMENTS POLE · PDF file#4 duplex secondary several wraps of the...
Transcript of 04.00 GENERAL 04.02 POLE ATTACHMENTS POLE · PDF file#4 duplex secondary several wraps of the...
04.00-00A
DWG.
04.00-01SECONDARIES & SERVICES
INDIVIDUAL 1 PHASE SECONDARY OVERHEAD LINE EXTENSIONS 04.00-02
04.04-06SECONDARY SPACER INSTALLATIONS
SECONDARY AND SERVICE CABLE SPLICES 04.00-10
INSULATED SERVICE ENTRANCE COMPRESSION CONNECTORS 04.00-12
MULTIPLEX SERVICE ATTACHMENTS TO POLES 04.02-06
OVERHEAD SERVICE POLE 04.05-06
SERVICE ATTACHMENT METHODS O4.05-00
TEMPORARY SERVICE POLE 04.05-08
BILLBOARD SERVICE ENTRANCE REQUIREMENTS METHOD "A" 04.05-10
BILLBOARD SERVICE ENTRANCE REQUIREMENTS METHOD "B" 04.05-12
SECTION 4 -
SECONDARY CONSTRUCTION OVERHEAD
TABLE OF CONTENTS
04.02-01POLE ATTACHMENT DEVICES
0
3
2
1
APPR.REVISED BY CK'D
04.04-08OVERHEAD TRIPLEX SECONDARIES
7/8/10
CECCONI GUINN ELKINS
04.05 SERVICES
04.04 SECONDARIES
04.02 POLE ATTACHMENTS
04.00 GENERAL
1. THE NEUTRAL SHALL BE COMMON TO BOTH PRIMARY AND SECONDARY CIRCUITS ON WYE SYSTEMS. THE
NEUTRAL SHALL BE MULTI-GROUNDED.
2. THE NEUTRAL CONDUCTOR SHALL ALWAYS BE IN THE TOP POSITION ON AN OPEN-WIRE SECONDARY CIRCUIT.
SIZING OF SECONDARY CONDUCTORS WILL DEPEND ON THE AMOUNT OF LOAD, THE TYPE OF LOAD (SUCH AS
MOTORS, ETC.), AND THE VOLTAGE DROP.
3. ALL SERVICE CONDUCTORS WILL BE OF COVERED ALUMINUM. THE REQUIRED SIZE, SHALL BE SPECIFIED BY
THE ENGINEER.
4. THE SERVICE ENTRANCE LOCATION WILL BE DETERMINED BY THE COMPANY AND MUST BE AGREED TO BY
THE CUSTOMER. CUSTOMER'S REQUESTS FOR NON-STANDARD LOCATIONS FREQUENTLY REQUIRE AN
ADDITIONAL CHARGE.
DWG.
04.00-01
10/18/12
BURLISON ADCOCK
SECONDARIES & SERVICES
GENERAL
R
WIRE SIZE
LIMIT FOR ALUMINUM CABLES NOT REQUIRING GUYING
40'
60'
70'
90'
150'
110'
150'
150'
336.4/350 QUADRUPLEX SERVICE
#4/0 QUADRUPLEX SECONDARY
350/500 TRIPLEX SERVICE
#4/0 TRIPLEX SERVICE
#1/0 TRIPLEX SERVICE/SECONDARY
#4 TRIPLEX SERVICE
#4 DUPLEX SECONDARY
SEVERAL WRAPS OF THE BINDING WIRE. COVER ENDS IF NOT IN USE.
CONTINUE ON, FIRST TAPE THE ENDS OF THE PHASE CONDUCTOR THEN BEND THEM BACK AND SECURE WITH
9. TO DEADEND THE PHASE CONDUCTORS OF AERIAL SECONDARY CABLE WHILE ALLOWING NEUTRAL TO
OF SCRAP LACING WIRE.
8. BEFORE CUTTING THE LACING WIRE ON AERIAL SECONDARY CABLE, BIND THE LACING WITH SEVERAL TURNS
7. STREETLIGHT CIRCUITS ARE TO BE CONSIDERED AS SECONDARY.
6. USE INSULINKS OR INSTALL COVERS OVER SECONDARY CABLE OR SERVICE CABLE PHASE CONNECTORS.
MOST NUMBER OF RAISED RIBS WILL BE THE HIGH (208 VOLT) PHASE.
5. FOR THREE PHASE FOUR WIRE DELTA SECONDARY CABLE AND SERVICES, THE PHASE CONDUCTOR WITH THE
#1/0 QUADRUPLEX SECONDARY
50'
500 QUADRUPLEX SERVICE 40'
0
3
2
1
APPR.REVISED BY CK'D
#2 TRIPLEX SERVICE
**SPAN LENGTH
*NO CODE NAME
WALKING
LEPAS
VIATKA
SOLASTER
SANDCRAB
WHIPPET
CRAB
*NO CODE NAME
*NO CODE NAME
CODE NAME
* WIRE SIZE CUSTOM MADE IN FIELD
** BASED ON 350 LB. CUSTOMER MAST TENSION LIMIT AS INDICATED IN THE
REQUIREMENTS FOR ELECTRIC SERVICE AND METER INSTALLATIONS MANUAL.
7/8/10
BURLISON GUINN ELKINS
INDIVIDUAL 1 PHASE SECONDARY
OVERHEAD LINE EXTENSIONS0
3
2
1
APPR.REVISED BY CK'D
70'
USING OH SECONDARY LIFT POLES
NO EXTRA POLE CHARGE TO NORMAL P.O.D.
150'
150'
NORMAL POINT OF DELIVERY
5
0
'
WIRING BEYOND NORMAL POINT OF DELIVERY
4
0
'
NORMAL P.O.D. IS ON THE END OF THE
BUILDING NEAREST THE OVERHEAD SOURCE.
6
0
'
NORMAL POINT OF DELIVERY
NORMAL P.O.D.
NO CHARGE
4/1/11
SIMPSON SIMPSON ELKINS
5/2/13
SIMPSON SIMPSON ADCOCK
8/18/14
SIMPSON GUINN ADCOCK
04.00-02
DEFDEP
X
DEMDEC
POLE FEE AND PER FOOT CABLE CHARGES APPLY. CONTACT COMPANY REPRESENTATIVE FOR COSTS.
NOTE: DIMENSIONS SHOWN ARE FOR
ILLUSTRATIVE PURPOSES ONLY.
6"
6"6"
SEMI-TENSION SLEEVE
6"
6"
COMPRESSION CONNECTOR;
INSULATED SERVICE ENTRANCE
SEMI-TENSION SLEEVE
OCCUR.
6. PHASE CONDUCTORS SHALL BE POSITIONED SUCH THAT CONTACT WITH THE NEUTRAL SLEEVE WILL NOT
SPLICES PER SPAN.
SPAN. "REPAIR" TRIPLEX OR QUADRUPLEX SECONDARIES AND SERVICES MAY CONTAIN A MAXIMUM OF TWO
5. "NEW" TRIPLEX OR QUADRUPLEX SECONDARIES AND SERVICES MAY CONTAIN A MAXIMUM OF ONE SPLICE PER
3. CLEAN CONDUCTORS BY WIRE BRUSHING.
SLEEVE.
2. USE "BG" GROOVE OF BURNDY TOOL, OR EQUIVALENT TOOL WITH DIE FOR 5/8" SLEEVES. USE 840 DIE ON 4/0
AT SPLICE.
1. WHEN SPLICING NEUTRAL, CUT OFF ENOUGH CONDUCTOR TO ASSURE A LOOSE WRAP OF PHASE CONDUCTORS
NOTES:
DWG.
04.00-10
4. FOR DETAILS OF INSULATED COMPRESSION CONNECTOR INSTALLATION SEE DWG 04.00-12.
CATALOG NUMBER CONDUCTOR SIZE
SEMI-TENSION SLEEVES FOR SERVICE NEUTRALS
#2 ACSR OR ALLOY
#4 ACSR OR ALLOY
#6 ACSR OR ALLOY
11164100
11164001
11151610
11165602 #4/0 ACSR OR ALLOY
TRIPLEX CABLE SPLICE
QUADRUPLEX CABLE SPLICE
SECONDARY AND SERVICE CABLE SPLICES
0
3
2
1
APPR.REVISED BY CK'D
7/8/10
BURLISON GUINN ELKINS
INSTALLATION INSTRUCTIONS
AND CONNECTOR INFORMATION
SEE DWG 04.00-12 FOR
COMPRESSION CONNECTOR;
INSULATED SERVICE ENTRANCE
INSTALLATION INSTRUCTIONS
AND CONNECTOR INFORMATION
SEE DWG 04.00-12 FOR
STRIP
LENGTH
NOTE 1
NOTE 2
NOTE 3
NOTES:
1. STRIP INSULATION ON EACH CONDUCTOR FOR LENGTH SHOWN BY ARROWS ON SIDE OF CONNECTOR, CLEAN
CONDUCTOR BY WIRE BRUSHING.
2. INSERT CONDUCTORS THROUGH CAPS ON EACH END UNTIL THEY HIT THE CENTER STOP.
3. MAKE THREE COMPRESSIONS ON EACH END. ROTATE TOOL SO THAT CRIMPS DO NOT LINE UP. USE "BG"
GROOVE OF BURNDY TOOL, OR EQUIVALENT TOOL WITH DIE FOR 5/8" SLEEVES. REMOVE END CAPS WHEN
INSTALLED ON BARE NEUTRAL.
4. INSULATED COMPRESSION CONNECTOR IS TO BE USED FOR NON-TENSION JOINTS ONLY. NO TAPING OR
DWG.
04.00-12
ADDITIONAL INHIBITOR IS REQUIRED. SEE DWG. 04.00-10 FOR SERVICE DROP CABLE SPLICE.
INSULATED COMPRESSION CONNECTOR SIZE TABLE
CONDUCTOR SIZECONDUCTOR SIZE
END MARKINGS
END COLOR END COLOR
4
6
4
2
2
1/0
1/0
1/0
2
ORANGE
ORANGE
YELLOW
YELLOW
YELLOW
RED
RED
RED
BLUE
BLUE
BLUE
BLUE
ORANGE
RED
RED
YELLOW
ORANGE
ORANGE4
2
4
I/0
2
6
6
4
6
INSULATED SERVICE ENTRANCE
COMPRESSION CONNECTORS
R
0
3
2
1
APPR.REVISED BY CK'D
1/0 YELLOW GRAY2/0
PGN
CN
11180809
11180908
11181104
11181203
11181302
11180205
11180403
11180502
11180700
9220121498
9/14/12
BURLISON ADCOCK
1/O
4/O
1/O
PINK
YELLOW
YELLOW
PINK
PINK
BLACK3/0
4/O
4/0
9220121506
9220121511
9220121516
04.02-01
DWG.
INSULATOR, SECONDARY RACK
INSULATOR, SECONDARY SPOOL
POLE ATTACHMENT DEVICES
7/8/10
ELKINSBURLISON GUINN
RR
FOR TANGENT POLE
NEUTRAL SUPPORT
AND OPEN-WIRE
SECONDARY SUPPORT
(ANGLES 0 TO 5 DEGREES)
SECONDARY DEAD ENDS
AND OPEN-WIRE
NEUTRAL SUPPORT
FOR ANGLE POLE
10543007
011280 BOLT, SPOOL, 5/8 X 10, GALV, DUI WASHERS
WASHER, SQ, 2-1/4", 3/16, GALV.
10544005 WASHER, LOCK, 5/8, COIL, DOUBLE, GALV.
011282 BOLT, SPOOL, 5/8 X 12, GALV, DUI WASHERS
0
3
2
1
APPR.REVISED BY CK'D
1
BILL OF MATERIALS
CATALOG
DESCRIPTION
NSSB10C
NSSB12C 1
1
QTY
1
1
1
1
PER
CU
NUMBER
MACRO UNIT
-
CU
ITEM
NO.
COMPATIBLE
UNIT
QTY
REQ'D
10034908
10543007 WASHER, SQ, 2-1/4", 3/16, GALV.
BOLT, MACH, SQ, 5/8-11 X 12, GALV
1
BILL OF MATERIALS
CATALOG
DESCRIPTION
NSSCC 1
QTY
1
1
PER
CU
NUMBER
MACRO UNIT
-
CU/CN
ITEM
NO.
COMPATIBLE
UNIT
QTY
REQ'D
10510204 CLEVIS, INSULATOR SPOOL, GALV, 3-1/8"1
10543007 WASHER, SQ, 2-1/4", 3/16, GALV.1
10544005 WASHER, LOCK, 5/8, COIL, DOUBLE, GALV.1
4/11/11
ELKINSBURLISON BURLISON
2 ISPLC 1 10512002 INSULATOR, SPOOL, 3 INCH1
2 ISPLC 1 10512002 INSULATOR, SPOOL, 3 INCH1
1 2
1
2
10/18/12
ADCOCKBURLISON
NOTES:
1. FOR FACTORY FORMED TIE INFORMATION, SEE DWG. 03.04-09.
4"
12"
WEDGE GRIP
EYENUT
WEDGE GRIP
ON OPPOSITE SIDE FROM EXISTING SECONDARY DEADEND
ON SAME SIDE AS EXISTING SECONDARY
NOTES:
2. APPLY INHIBITOR AND WIRE BRUSH ALL CONNECTIONS. USE ALUMINUM COMPRESSION CONNECTORS ON
COPPER TO ALUMINUM CONNECTIONS. INSTALL CONNECTORS SO THAT ALUMINUM IS ABOVE COPPER.
TO SOURCETO SERVICE
DWG.
04.02-06
CN 10321008
CU ISEYENUT58C
CN 10026201
CU ISEYEBOLT5810C
CU SERCLMPN2ALC
CN 11101805
CN 11101409
CONNECTIONS TO OPEN WIRE SECONDARIES
LIFT POLE ATTACHMENTS
LIFT POLE
GUYED LIFT POLE
MULTIPLEX SERVICE ATTACHMENTS TO POLES
1. FOR 4/0 AND LARGER TPX & QPX, SUBSTITUTE STRAIGHT DEAD END CLAMP ( CN 11104957) AND SALVAGED
AND SPOOL.
3. POLES WITH ONLY SECONDARY CONDUCTORS WILL NOT BE EQUIPPED WITH A POLE GROUND.
R
4"
7/8/10
BURLISON GUINN ELKINS
0
4
3
APPR.REVISED BY CK'D
CU SERCLMP40ALC
WEDGE GRIP
4/27/12
GUINN BURLISON ELKINS
10/18/12
BURLISON ADCOCK
4" STRAIN INSULATORS ( CN 11222908) FOR LOOP DEAD END CLAMP, AND EYEBOLT ( CN 10026201) FOR CLEVIS
12"
DETAIL SHOWN FOR
1/0 AND SMALLER
TPX AND QPX
(SEE NOTE 1)
DEAD END CLAMP
CN 11104957
USE MINIMUM 1/4" GUYSTRAND AND 6" SCREW
ANCHOR FOR ANGLE POLES AS NEEDED
5
1/18/13
SIMMONS GUINN ADCOCK
4. POLES WITH METERING EQUIPMENT TO BE EQUIPPED WITH A POLE GROUND (EITHER WRAP BUTT OR TWO
DRIVEN 5' GROUND RODS).
DWG.
04.04-06
NOTES:
1. SERVICE DROP INSTALLATIONS SHALL BE APPLIED ONLY
IN THOSE CASES WHERE THE ALTERNATIVE WOULD BE
RELOCATING EXISTING POLES OR INSTALLING ADDITIONAL
ONES TO SERVE CUSTOMERS.
2. SERVICE DROPS SHALL NOT BE SPECIFIED WHEN THE
LOCATION IS INACCESSIBLE TO A LADDER.
3. INSTALLATIONS SHALL BE MADE SO THAT SAGS AND
TENSIONS OF THE SECONDARY SERVICE CABLE ARE
MAINTAINED FOR PROPER APPEARANCE.
4. MAXIMUM SIZE SERVICES PERMITTED FOR THIS
INSTALLATION ARE 80' OF #2 TRIPLEX OR 60' OF
#1/0 TRIPLEX.
5. MORE THAN ONE SERVICE PULL-OFF IN THE SAME SPAN
IS NOT PERMITTED EXCEPT FOR BACK-TO-BACK SERVICES.
6. SECONDARY SPACERS MAY BE INSTALLED AT APPROXIMATELY
50' INTERVALS TO PREVENT OUTAGES DUE TO SECONDARY
CONDUCTORS COMING TOGETHER IN LONG SPANS.
SECONDARY SPACER
DOUBLE SERVICE DROP
(TO BE USED ONLY WHERE SPECIFIED BY ENGINEER)
DOUBLE TAP
FOR 4/0 ACSR MAXIMUM
DOUBLE SERVICE BAIL
FOR SINGLE TAP
6/21/10
BURLISON GUINN ELKINS
SECONDARY SPACER INSTALLATIONS
8" SPACING (CN 11102100)
12" SPACING (CN 11102209)
USE SINGLE SERVICE BAIL (CN 11102308)
CN 11102407
0
3
2
1
APPR.REVISED BY CK'D
(TO BE USED ONLY WHERE SPECIFIED BY ENGINEER)
OR TO CLEAR POLE FOR CLIMBING
SERVICE DROP LOCATED TO AVOID OBSTACLES
(TO BE USED ONLY WHERE SPECIFIED BY ENGINEER)
SERVICE DROP FROM TRANSFORMER POLE
PRIMARIES
1. THE PREFERRED METHOD IS TO INSTALL THE TRIPLEX BENEATH THE PRIMARY NEUTRAL, CLEAR-SPANNING
2. THE TRIPLEX AT ITS LOWEST POINT MUST BE AT LEAST 30" ABOVE THE TELEPHONE/CATV LINES BELOW. IF
THERE ARE NO TELEPHONE/CATV LINES, THE TRIPLEX AT ITS LOWEST POINT MUST HAVE THE APPROPRIATE
3. IF THE SAG OF THE TRIPLEX ENCROACHES THE MINIMUM CLEARANCE TO THE TELEPHONE/CATV LINES OR
GROUND BELOW, THE TRIPLEX SHOULD BE ATTACHED TO THE PRIMARY NEUTRAL, AS SHOWN IN DETAIL A
4. ONLY #2 AND #4 TRIPLEX MAY BE ATTACHED TO THE PRIMARY NEUTRAL FOR ITS SUPPORT. THE LARGER SIZE
TRIPLEXES MUST BE CLEAR-SPANNED BETWEEN POLES AND NOT SUPPORTED BY THE PRIMARY NEUTRAL.
ABOVE, AS OFTEN AS NECESSARY TO ACHIEVE THE REQUIRED MINIMUM CLEARANCES.
NOTES:
TRIPLEX
BARE NEUT.
TPX
PHASE WIRES
PRIMARY NEUTRAL
TELEPHONE/CATV
NEUTRAL
PRIMARY
CLEAR.
MIN.
AT
POLE
PRI.-NEUT.
SPACING
EXISTING
GUY CLAMP
TRIPLEX
SECONDARY
FINAL GRADE
MINIMUM CLEARANCE
TO GROUND BELOW
CLEARANCE
30" MIN.
IN SPAN
40"
MINIMUM GROUND CLEARANCE GIVEN BY DWG. 10.02-11.
PER DWG. 09.00-01
7/8/10
BURLISON GUINN ELKINS
DETAIL "A"
GUY CLAMP CN
4/0 AL 10045714
NEUT. SIZE
PRIMARY
(SEE CHART FOR SIZE & CN)
*
FROM POLE TO POLE.
OVERHEAD TRIPLEX SECONDARIES
#4 - #1/0 AL 11159001
SEE DETAIL A
0
3
2
1
APPR.REVISED BY CK'D
8/6/14
EANES EANES ADCOCK
04.04-08
DEFDEP
X
DEMDEC
5. THE SERVICE POINT OF ATTACHMENT SHOULD BE LOCATED BELOW THE LEVEL OF THE WEATHERHEAD OR
4. SERVICE ENTRANCE CONNECTORS SHALL BE INSULATED PER NEC RULE 230-22.
MAST BRACKET
FASCIA
FASCIA
STEEL CONDUIT ONLY
MADE BELOW THE LEVEL OF THE SERVICE WEATHERHEAD.
2. THE CONNECTIONS OF THE SERVICE DROP CONDUCTORS TO THE SERVICE ENTRANCE CONDUCTORS SHALL BE
1. DRIP LOOPS SHALL BE FORMED ON SERVICE DROP SERVICE ENTRANCE CONDUCTORS.
LARGER MAST SIZE OR SPECIAL SAG.
TO 4'. LONGER MAST HEIGHTS REQUIRE GUYING, BRACING,
2. 2" RIGID STEEL CONDUIT IS REQUIRED FOR MASTS UP
A MAXMIUM TENSION FORCE OF 350 LBS. IMPOSED BY
BE SUPPORTED BY A GUY OR BRACE TO WITHSTAND
1. SERVICE MAST SHALL BE OF ADEQUATE STRENGTH OR
NOTES:
OR EQUIVALENT SUPPORT.
1. HOUSE BRACKETS MUST BE INSTALLED IN STUDS (2" X 4")
HOUSE BRACKET
3. SEE DWGS. 10.02-01 AND 10.02-03 FOR SERVICE GROUND CLEARANCES AND DWGS. 10.04-09A AND 10.04-09B
HOUSE BRACKETS
SERVICE MAST
NOTES:
NOTES:
SERVICE ATTACHMENT METHODS
7/8/10
ELKINSBURLISON GUINN
1 1/4" - 2 1/2"
3" - 4"
FOR SERVICE CLEARANCES AT BUILDINGS.
GOOSENECK. IF THIS IS IMPRACTICAL, THE POINT OF ATTACHMENT MUST BE LOCATED WITHIN 24" OF THE
WEATHERHEAD OR GOOSENECK (REF. NEC 230-54C).
6. CUSTOMER IS RESPONSIBLE FOR PROVIDING AN ATTACHMENT POINT FOR MASONRY AND STEEL BUILDINGS.
CN 11101003
CU SDEMASTCLMPLGC
CU SDEMASTCLMPSMC
GUY WIRE
OR BRACE
CUSTOMER'S
0
3
2
1
APPR.REVISED BY CK'D
CN 11101508
CN 11101607
10/18/12
ADCOCKBURLISON
SERVICE DROP.
7. SEE DWG. 04.02-06 FOR SERVICE CLAMP COMPATIBLE UNITS.
04.05-00
DEFDEP
X
DEMDEC
8/6/14
ADCOCKEANES EANES
POINT OF DELIVERY
NOTES:
3'-0" TO
5'-6"
CUSTOMER'S POLE
(SEE NOTE 1A)
CUSTOMER'S
EQUIPMENT
(SEE NOTE 1B)
METER SOCKET
(SEE NOTE 2)
1. OWNER PROVIDE AND INSTALL
A. A 20' CLASS 9 SOUTHERN YELLOW PINE (SYP) POLE OR A 6" X 6" SYP POST THAT IS PROPERLY TREATED WITH A WOOD
PRESERVATIVE FOR EARTH CONTACT. SET POLE IN ACCORDANCE WITH OPTION A, B OR C.
2. OWNER WILL INSTALL
A. METER SOCKET IN ACCORDANCE WITH N.E.C.
5'-5"
POLE
BACKFILL WITH SOIL AND
TAMP IN 6" LAYERS. HOLE
DIAMETER SHALL BE JUST
WIDE ENOUGH TO ALLOW
TAMPING.
BACKFILL WITH CONCRETE
IN A 15" (MIN.) DIAMETER
BACKFILL WITH SOIL AND
TAMP IN 6" LAYERS. HOLE
DIAMETER SHALL BE JUST
WIDE ENOUGH TO ALLOW
TAMPING.
GUY AND ANCHOR
INSTALLATION MUST
BE APPROVED BY
LOCAL ENGINEER.
4' DEPTH
POLE
CONCRETE
3
1
4' DEPTH
4" SCREW ANCHOR
MINIMUM
7-STRAND
GUY (MIN.)
B. SERVICE ENTRANCE TO BE GROUNDED IN ACCORDANCE WITH N.E.C.
4. THIS DRAWING MAY BE USED FOR VARIOUS TYPES OF OVERHEAD SERVICES:
B. NON-RESIDENTIAL SERVICES
4" MIN.
POLE
16'
16'
14'-7"
DWG.
04.05-06
1/4",
HOLE.
OPTION A
NOT TO SCALE
NOT TO SCALE
OPTION B
NOT TO SCALE
OPTION C
OVERHEAD SERVICE POLE
A. OVERHEAD MOBILE HOME SERVICES
3. SETTING DEPTHS FOR THE THREE OPTIONS ARE FOR 350 LB. ICE TENSIONS.
SECURE TO POLE USING
HOUSE BRACKET SCREW OR
DRIVE HOOK SCREW MOUNTED
IN THE SIDE OF POLE. DO
NOT ATTACH TO TOP OF POLE.
12'-6" MIN.
ANYWHERE IN
THE SPAN
(18' MIN.
IF OVER
ROADS OR
AREAS SUBJECT
TO VEHICULAR
TRAFFIC)
7/8/10
BURLISON GUINN ELKINS
2/28/12
SIMPSON SIMPSON ELKINS
0
3
2
1
APPR.REVISED BY CK'D
PER N.E.C.
GROUNDING ELECTRODE
8/13/13
SIMPSON SIMPSON ADCOCK
6/21/10
BURLISON GUINN ELKINS
TEMPORARY SERVICE POLE
0
3
2
1
APPR.REVISED BY CK'D
3' MIN.
2" X 4" STAKES
4' MIN.
6'
6'
GROUND WIRE
2" X 4" BRACE
12'-6" MINIMUM
ANYWHERE
IN SPAN
IF OVER ROADS OR
AREAS SUBJECT TO
VEHICULAR TRAFFIC)
WEATHERPROOF
SWITCH BOX
TREATED WOOD
POLE WITH MIN.
DIAMETER OF 4"
8'
3'-0"
TO
2" X 4"
NOTES:
1. ALL DIMENSIONS SHOWN ARE MINIMUM.
2. MINIMUM 20' POLE REQUIRED. TALLER
3. ONE BRACE TO BE IN DIRECTION OF
SERVICE. AT LEAST ONE ADDITIONAL
BRACE TO BE LOCATED AT 90° TO
DIRECTION OF SERVICE.
4. SOIL TO BE FIRMLY TAMPED AROUND
POLE AND STAKES DRIVEN INTO FIRM
EARTH.
5. CUSTOMER FURNISHES ALL ITEMS EXCEPT
METER. THE METER BASE, WIRING,
EQUIPMENT SERVICE EQUIPMENT
GROUND ON THE POLE ARE TO BE
INSTALLED BY THE CUSTOMER'S
ELECTRICIAN IN ACCORDANCE WITH THE
N.E.C AND LOCAL ORDINANCES.
6. SOLID, ONE PIECE, 4" X 4" WOOD
POST MAY BE SUBSTITUTED WITH
ENGINEER'S APPROVAL.
7. SERVICES SHALL NOT BE RUN TO
TEMPORARY POLES NOT MEETING THE
REQUIREMENTS SET FORTH HEREIN
WITHOUT APPROVAL OF THE LOCAL
ENGINEER ON SPECIFIC CASES.
8. HOUSE BRACKET MOUNTING
LOCATION SHALL BE IN THE
SIDE OF THE SERVICE POLE
NOT IN THE TOP.
5'-6"
BRACE
SEE NOTE 3
90°
PLAN VIEW
2' MIN.
SEE NOTE 9
90°
DIRECTION OF
SERVICE
(18'-0" MINIMUM
9. IF THE 4 FOOT MINIMUM DEPTH
CANNOT BE OBTAINED DUE TO
ROCK, TWO ADDITIONAL BRACES
90 DEGREES TO THE BRACES
SHOWN MUST BE INSTALLED
(FOUR BRACES TOTAL). IN NO
CIRCUMSTANCES SHOULD THE
EMBEDMENT DEPTH BE LESS
THAN 2 FEET.
4/1/11
SIMPSON SIMPSON ELKINS
DIRECTION OF SERVICE
LOCATION 90° FROM
ALTERNATE BRACE
8/13/13
SIMPSON SIMPSON ADCOCK
GROUNDING ELECTRODE
PER N.E.C.
MAY BE NEEDED TO MEET SERVICE SAG
REQUIREMENTS. MINIMUM 16' POLE
ALLOWED IF SET WITHIN 10' OF SOURCE
COMPANY POLE.
04.05-08
DEFDEP
X
DEMDEC
12/1/14
SIMPSON GUINN ADCOCK
BILLBOARD COMPANY SERVICE WIRE
LADDER LOCATION
SERVICE RISER
METER AND BASE
FINAL GRADE
3'-0" TO 5'-6" MT.HT.
3' EXTENSION BRACKET
MUST PROVIDE REQUIRED
SERVICE DROP CLEARANCES
CATWALKS
BILLBOARDS
LADDER LOCATION
NO COMPANY SERVICE SHALL BE ATTACHED
LADDER LOCATION
SERVICE MASTHEAD
AND RISER
TO ANY PART OF THE CATWALKS
3' EXTENSION BRACKET (SUPPLIED
COMPANY SERVICE WIRE ENTRANCE TO BE
SPOTTED BY COMPANY ENGINEER
MAX.
NOTE:
BY CUSTOMER)
2'
7/8/10
BURLISONGUINN
ELKINS
SEE DWG. 10.02-01 AND 10.02-03
ELEVATION
BILLBOARD SERVICE ENTRANCE REQUIREMENTS
METHOD "A"
PLAN VIEW
MASTHEAD
0
3
2
1
APPR.REVISED BY CK'D
1. DO NOT PROVIDE SERVICE TO SIGN WHICH DOES NOT HAVE CLEARANCES FROM ADJACENT OVERHEAD
CONDUCTORS AS REQUIRED BY N.E.S.C. AND ANY ADDITIONAL COMPANY SPECIFICATIONS.
4/1/11
SIMPSON SIMPSON ELKINS
04.05-10
DEFDEP
X
DEMDEC
8/6/14
EANES EANES ADCOCK
COMPANY SERVICE WIRE
SERVICE RISER AND MASTHEAD
STEEL POLE
OVERHEAD SERVICE WIRE MAY BE LOCATED
ANYWHERE IN THIS AREA. CALL LOCAL COMPANY
OFFICE FOR SERVICE ENTRANCE SPOTTING.
3
'
M
I
N
.
3
'
M
I
N
.
NO PART OF COMPANY
SERVICE WIRE WILL
BE RUN WITHIN
3' OF LADDER
3' MIN.
BILLBOARD
COMPANY SERVICE WIRE
LADDER LOCATION
SERVICE RISER
METER AND BASE
FINAL GRADE
MT. HT.
3'-0" TO 5'-6"
7/8/10
BURLISON GUINN ELKINS
SEE DWGS. 10.02-01 AND 10.02-03
ELEVATION
PLAN VIEW
BILLBOARD SERVICE ENTRANCE REQUIREMENTS
METHOD "B"O
3
2
1
APPR.REVISED BY CK'D
04.05-12
DEFDEP
X
DEMDEC
8/6/14
EANES EANES ADCOCK