FAE: Chad Tseng
Telecom Power New Smart CSU Presentation
1
Telecom Power System
Telecommunication Power System
AC Input
Generator
U.P.S
AC
Distribution U
nit
Rectifier # 1
Control Supervisory Unit (CSU)
LOA
D (Sw
itch ,AD
SL…E.T.C
.)
Output D
C D
istribution Unit
LVDS
Rectifier # 3
Rectifier # 2
Rectifier # N
Battery
New Smart CSU System Function Block
NSCSURS-485
RS-232
Web Server SMNP Server
RectifiersSMR Shelf
Rectifiers
Max: 4 PCs ID, DCI, Alarm,S/N
RS-485
RectifiersSMR Shelf
Rectifiers
Max: 4 PCs ID, DCI, Alarm,S/N
RectifiersSMR Shelf
Rectifiers
Max: 4 PCs ID, DCI, Alarm,S/N
RS-485I.D.Address
RS-48 5I.D.Address
RS-48 5I.D.Address
IBUS IBUS
PDU DetectionI/O function
Analog Signal
PDU (Several Configurations)
Rectifier ESR-48/56A
Battery & Base
New Smart CSU (Main Board))
New Smart CSU (Relay Board))
19” Rectifier Shelf (SB-05N/HG A )
160W Heat-exchange
CCU (Climate Control Unit )
RS-485
New Smart CSU: DPS 2700 Series
Configuration,Supervision Terminal Interface
Web/SNMP Card
Ethernet
Configuration,Supervision
(web browser)
54Vdc/50A With SMR
AnalogSignal Detection
LCD Display
RS-485 X 3 With SMR
RS-485 With SMR
AnalogI.D address
New Smart Control and Supervisory Unit
To LCD display
Down S/W Program and RS232
Board Main Power
Main Board
Display 128 x 64
To Relay Output Terminal
Connector Board
Expand Board
New Smart Control and Supervisory Unit
Features:• System Input AC Voltage Detection 3 Phases • System Output DC Voltage Detection • LCD Display Dots 128 x 64 type (Option)• Four Switch Button for Display setting• System Battery Current Detection X 2 • system Load Current Detection X 1• Battery Fuse Detect X 4• Seven LED display On board
Features:•Breaker(Plug-in) Detect 2 Rails • Load Fuse/Breaker Detect X 13(Series Detection)
(Including GMT Fuse Detect X 1)• LVDS Control X 2 • Environment Temp. X1 and Batt. Temp.X 2• 8 Relay Alarm output (From C type ) • 3 switch function for setting (On Board)• External Buzzer Alarm X 1 (Option )
Transformer full waves
Acv Detect - LM358
CPU – M9S12E128MFU
Date Bus & Address BusRelay enable & CommunicationCrystal =11.0592Flash ROM 32K
EEPROM –24C16
Save all Parameters
Relay Out - 8 N.C.
Major & Minor & ACDN
HV & TA Fail & RFA & LVDS& EQU
Power - 2843
Input 20Vdc-60Vdc +5V , S5V , R5V,
A±15V,B±15V
V+
V-
Differential Amplify
Batt Current Detect - OP07
Differential Amplify
DCV Detect – OP07
Buffer Translation
Temp Detect – LM258Digital
I/O
Photo isolate detect
Load Fuse Detect - TLP621
Photo isolate detect
Batt Fuse Detect – TPL621
Rail Function Board
Breaker Detect - LM358
New Smart CSU Function Block
Clock – DS1306N
Real Time Clock with Battery
LED Out - 8 LED
Major & Minor & ACDN
HV & TA Fail & RFA & LVDS& EQU
74541 /74573
Digital I/O
74541 /74573
User friendly operating interfaceLarge 128 x 64 Dot LCD DisplayEntry of alarm and system parameters from keypad
High reliable RS-485 communicationMulit- Language (Sim chinese Tri Chinese;English)Easy system configuration and expansionFeatured functions
Stand-alone operationProvisioning AlertGreen Energy ManagementTemperature & Voltage compensationBattery capacity and load testGenerator Control
Different possibilities for remote monitoringInternet/Local Access
New Smart CSU – Features and Benefits
User Interface
Main Board
CPU UE15
Down S/W Program
Main board Power
Note: Using Cyclone Pro Tools down load S/W
Main Board-Expand Board
Expand (Upgrade) Features:• System Input Expand to 3 Phases.• System Expand Analog Input X 4 • System Expand digital input X 2• System Battery Fuse Expand x 2
Connector I/P Board
Features:• System Input AC Voltage Detection 1 Phase
(Expand to 3 Phases)• System Output DC Voltage Detection • System Battery Current Detection X 2• System Load Current Detection X 1• Battery Fuse Detect X 2 (Expand 2)• Breaker(Plug-in) Detect 2 Rails • Load Fuse/Breaker Detect X 13(Series Detection)
(Including GMT Fuse Detect X 1)• LVDS Control X 2 • Environment Temp. X1 and Batt. Temp.X 2• 8 Relay Alarm output ( From C type ) • External Buzzer Alarm X 1 (Option )• Expand 4 Analog and 2 Digital I/P
Back Enter
Major LEDMinor LEDEQU LED
128 x 64 LCDDots Display
New Smart CSU: User Interfaces
Up Down
New Smart CSU Function Architecture* (Main\Data)
* Function architecture varies in different systems
RectifierI.D. Address
Output Current Status
Event LogAlarm Function Time
Recover Time
Current .settingDC Setting
Alarm SettingBatt.Setting
Other Setting
HomeDCVDCI
Sys Status(FL/EQU)Alarm Existing
Sys Info Sys Setting Current Alarm
Battery Batt. String I.D.
Batt.StatusBatt. Current
* DC/DC Data
AC & TempACV VoltageAmbient Temp.
Data & VersionDate/TimeH/W versionS/W version
New Smart CSU Function Architecture* (Main\Data)
* Function architecture varies in different systems
DC SettingDCV settingCL setting
Batt. SettingBatt. Par.T-Comp BDT Test B-EQU
PasswordNew PW Cfm PW Default (0000)
HomeDCVDCI
Sys Status(FL/EQU)Alarm Existing
Sys Info Sys Setting Current Alarm
Alarm Setting ACV,
DCV,LVDS, OTP,EQU, Batt.Test.
Password
Date SettingYear/month/
day/time
Alarm ResetReset HVSD
Reset Com-fail
GeneratorON/OFF
Language English
繁體中文簡體中文
Efficn.t Mgt.ON/OFF
Comm.ModbusBaudrate
Temp. UnitON/OFF
New Smart CSU Function Architecture* (Main\Alarm)
* Function architecture varies in different systems
HomeDCVDCI
Sys Status(FL/EQU)Alarm Existing
Sys Info Sys Setting Current Alarm
All Alarm Function show on Display
Show Real Information and Alarm Time in Event Log
Back Content
BATTERY CHARGE AND DISCHARGE CONTROL
Normal Operation
DistributionCapacity CountAC FailAC Fail
≧1 Hrs Cycle Count
Equalize Charge 1 Hrs
Capacity Charge Count
NO
YES
Equalize Charge
NOYESCharge Current
≦10% I10
ChargeComplete
NO
NO
YES
YES
Float
AC Restored
YES
NO
ContinuousEqualize Charge
1 Hrs
NO
NO
YES
Accumulated Equalize Charge
≦10Hrs
YES
Periodically Equalize Charge
Discharge <10%
Boost ChargeEQU Charge
By Controller
3 3 battery recharge modes : Periodic, Manual, Deeply discharge modebattery recharge modes : Periodic, Manual, Deeply discharge mode• Periodic mode: The battery was periodic recharge for compensating self-discharge of
battery.• Manual mode: Technician through LCD or Remote control system to system control.• Deeply discharge mode: After system deeply discharged (AC fail or battery test), system
need rapid recharge battery.
Battery Maintenance - Benefit
Cha
rge
Vol
tage
an
d C
harg
e C
urre
nt
Time
Stage - 1 Current Limit
Stage - 2 Current Limit
Stage - 3 Current Limit
Float Voltage
Deeply Discharge Voltage
EqulizeVoltage
Battery current
0V / 0A EQU stop current
Deeply discharge mode:Deeply discharge mode:After system deeply discharged, system provide rapid and suitable battery recharge process to avoid battery damage and keep fully battery capacity anytime. Adjustable parameters easy conform different battery characteristic.
Battery Charge FunctionBattery Charge Function
• Temperature compensation is to prevent the thermal runaway of battery when it is used in high temperature conditions and to secure to sufficient charging of battery when it is used in low temperature conditions.
2 battery compensation modes: Easy and professional compensation process to satisfy battery characteristic.
Linear mode:Sample coefficients depict battery compensation characteristic to satisfy general battery operation.
Temperature Reference(Default: 25℃)
Battery Temperature (℃)
Output Voltage (V)
Float Voltage
Slope: Temperature coefficient (mV/℃)
Curve mode:Several parameters precise depict specific battery compensation characteristic to satisfy professional battery operation
Coefficient 2
Battery Temperature (℃)
Coefficient 3
Coefficient 1
Output Voltage (V)
-15℃ 10℃ 30℃ 50℃
Coefficient 4
Battery Maintenance - BenefitBattery Temperature CompensationBattery Temperature Compensation
Battery Discharge TestBattery Discharge Test
The propose of battery test is battery backup function confirmation. Controller bases on accuracy discharge current (Constant current) and discharge time to calculate battery lost capacity. Measurement of discharge current is according to load discharge current.Operation mode: Periodic, Manual mode
Test Voltage
Test Time
System voltagein floating mode
Time
Voltage
OK
Fail
Battery Maintenance - Benefit
Periodic battery test:Some easy parameter settings (Month, Day, Hour, Cycle) to regular monitoring battery heath status. Contact discharge current and adjustable test time precise simulate battery characteristic to enhance test result accuracy.
Green Energy Management - Benefit
Standby Standby Standby
Standby Standby Standby
Working Rectifiers
Effic
ienc
y (%
)9 8 7 6 5 4
3
20
30
40
50
60
70
80
90
1
00
Rectifier Loading (%)
Efficient Curve AreaExample: 6000W load
Green Energy Management –Control Philosophy
•System is operating efficiency varies with O/P load. •The “sweet spot” is 50% and 90% of rated capacity. •Optimize operating efficiency to keep lowest operational costs. •Real-Time load calculate & gradually turn off & on rectifier to ensure system reliability.
TrueFalse
Load < 50%
Turn On One SMR
FalseLoad >
60%
Turn On Off OneSMR
True
FalseTurn On One SMRTurn Off One SMR
True
Time Elapsed > 12hr
False
True
Turn On All SMR
True
FalseLoad >
80% OR Alarm
While True
Delta Power System Monitoring & Control
Build in HTTP Web Server
AC Distribution Rectifiers
DC Distribution
Battery Management
Environment Data
Acquisition
Control &Supervisory
Unit
Client User
Client User
Internet
Telecom Power Manage Program
Local
Client User
Mini USB
Local Access
Mini USB
NRMS Monitor software
Web Server Function and Feature (Optional)Features:
Applied in TCP/IP Internet/Intranet Environment
Complete Supervising to Power System
User-friendly Graphic Interface
Dynamic information presentation
Password function
Multi Language Support
Microsoft Explorer and Netscape SupportMain Screen
StatusParameter Setting
Alarm Configuration
Q & A