03-Presentation Directional Protection
-
Upload
rajesh-pillai -
Category
Documents
-
view
500 -
download
3
Transcript of 03-Presentation Directional Protection
![Page 1: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/1.jpg)
![Page 2: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/2.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Application of Directional Overcurrentand Earthfault Protection
![Page 3: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/3.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Directional Protection
![Page 4: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/4.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Need for Directional Control
Generally required if current can flow in both directions through a relay location
e.g. Parallel feeder circuitsRing Main Circuits
Relays operate for current flow in direction indicated. (Typical operating times shown).
0.9 0.10.5 0.90.50.1
![Page 5: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/5.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Ring Main Circuit
With ring closed :
Both load and fault current may flow in either direction along feeder circuits.
Thus, directional relays are required.
Note: Directional relays look into the feeder.
Need to establish principle for relay.
51 67
51
Load
67 67
Load
6767 67
Load
![Page 6: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/6.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Ring Main CircuitProcedure :1. Open ring at A
Grade : A' - E' - D' - C' - B'2. Open ring at A'
Grade : A - B - C - D - ETypical operating times shown.Note : Relays B, C, D’, E’ may be non-directional.
1.30.1
0.1 0.90.50.9
0.5
B'
A'
B
E E'
A
1.7
D'
D
1.7
1.3
C' C
![Page 7: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/7.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Ring System with Two Sources
Discrimination between all relays is not possible due to different requirements under different ring operating conditions.
For F1 :- B’ must operate before A’For F2 :- B’ must operate after A’
NotCompatible}
B' B C' C
D D'
F1
B
F2
A
A'
![Page 8: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/8.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Ring System with Two Sources
Option 1Trip least important source instantaneously then treat as normal ring main.Option 2Fit pilot wire protection to circuit A - B and consider as common source busbar.
A
B
Option 1Option 1Option 1
Option 2 Option 2
50
PW PW
![Page 9: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/9.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Parallel Feeders
Non-Directional Relays :-
“Conventional Grading” :-Grade ‘A’ with ‘C’
and Grade ‘B’ with ‘D’
Relays ‘A’ and ‘B’ have the same setting.
51
51
A
D
Load
‘F’
51 B
51 C
A & B
C & D
Fault levelat ‘F’
![Page 10: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/10.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Parallel Feeders
Consider fault on one feeder :-
Relays ‘C’ and ‘D’ see the same fault current (I2). As ‘C’ and ‘D’ have similar settings both feeders will be tipped.
51 A 51C
51 B 51D
LOAD
I1 + I2I1
I2
![Page 11: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/11.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Parallel Feeders
Solution:- Directional Control at ‘C’ and ‘D’
Relay ‘D’ does not operate due to current flow in the reverse direction.
51 A 67C
51 B 67D
LOAD
I1 + I2I1
I2
![Page 12: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/12.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Parallel Feeders
Setting philosophy for directional relays
Load current always flows in ‘non-operate’ direction.Any current flow in ‘operate’ direction is indicative of a fault condition.Thus Relays ‘C’ and ‘D’ may be set :-
- Sensitive (typically 50% load)- Fast operating time (i.e. TMS=0.1)
51 A 67E
51 B 67
C
D
Load
51
![Page 13: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/13.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Parallel Feeders
Usually, relays are set :-- 50% full load current (note thermal rating)- Minimum T.M.S. (0.1)
Grading procedure :-1. Grade ‘A’ (and ‘B’) with ‘E’ assuming one
feeder in service.2. Grade ‘A’ with ‘D’ (and ‘B’ with ‘C’) assuming
both feeders in service.
![Page 14: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/14.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Parallel Feeders - Application Note
QP
B
B
D
D
Load
Load
If2
If1:One FeederIf2:Two Feeders
A C
If2
If1If2/2 If2
If2/2
BCD
M
M = Margin
M
If
A
M
Grade B with C at If1Grade B with D at If2
(in practice)Grade A with B at If - but check that sufficient margin exists for bus fault at Q when relay A sees total fault current If2, but relay B sees only If2/2.
![Page 15: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/15.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Establishing Direction
![Page 16: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/16.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Establishing Direction:- Polarising Quantity
The DIRECTION of Alternating Current may only be determined with respect to a COMMON REFERENCE.
In relaying terms, the REFERENCE is called the POLARISING QUANTITY.
The most convenient reference quantity is POLARISING VOLTAGE taken from the Power System Voltages.
![Page 17: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/17.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Directional Decision by Phase Comparison (1)
S1 = Reference Direction = Polarising Signal = VPOL
S2 = Current Signal = I
OPERATION when S2 is within ±90° of S1 :-S 1
S 2
S 2
S 2S 2
S 2
S 2
S 2
![Page 18: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/18.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Directional Decision by Phase Comparison (2)
RESTRAINT when S2 lags S1 by between 90° and 270° :-
S2
S1
S2
S2
S2S2
S2
S2
![Page 19: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/19.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Polarising Voltage for ‘A’ Phase Overcurrent Relay
OPERATE SIGNAL = IA
POLARISING SIGNAL :- Which voltage to use ?Selectable from
VAVBVCVA-BVB-CVC-A
![Page 20: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/20.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Directional Relay
Applied Voltage : VAApplied Current : IA
Question :- is this connection suitable for a typical power system ?
IA
VA
Operate
Restrain
VAF
IAF
![Page 21: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/21.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Polarising Voltage
IA
VBC
ZERO SENSITIVITYLINE
VA
IAF
IVBC
ØVBC
MAXIMUM SENSITIVITY LINE
Applied Voltage : VBCApplied Current : IA
Polarising voltage remains healthyFault current in centre of characteristic
![Page 22: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/22.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Relay Connection Angle
The angle between the current applied to the relay and the voltage applied to the relay at system unity power factor
e.g. 90° (Quadrature) Connection : IA and VBC
The 90° connection is now used for all overcurrent relays. 30° and 60° connections were also used in the past, but no longer, as the 90° connection gives better performance.
IA
VA
90°VBC
VC VB
![Page 23: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/23.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Relay Characteristic Angle (R.C.A.) for Electronic Relays
The angle by which the current applied to the relay must be displaced from the voltage applied to the relay to produce maximum operational sensitivity
e.g. 45°OPERATE
IA FOR MAXIMUM OPERATESENSITIVITYRESTRAIN
45°
VA
RCAVBC
![Page 24: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/24.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
90° Connection - 45° R.C.A.
IA
VA
90°
VBVC
MAX SENSITIVITYLINEOPERATE
IA FOR MAXSENSITIVITYRESTRAIN
45°45°
135°
VA
VBC VBC
RELAY CURRENT VOLTAGEA IA VBC
B IB VCA
C IC VAB
![Page 25: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/25.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
90° Connection - 30° R.C.A.
IA
VA
90°
VBVC
VBC
RELAY CURRENT VOLTAGEA IA VBC
B IB VCA
C IC VAB
30°
30°
OPERATEMAX SENSITIVITYLINERESTRAIN
IA FOR MAXSENSITIVITY
150°
VA
VBC
![Page 26: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/26.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Selection of R.C.A. (1)
90° connection 30° RCA (lead)Plain feeder, zero sequence source behind relay
Overcurrent Relays
![Page 27: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/27.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Selection of R.C.A. (2)
90° connection 45° RCA (lead)Plain or Transformer Feeder :- Zero Sequence Source in Front of Relay
Transformer Feeder :- Delta/Star Transformer in Front of Relay
![Page 28: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/28.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Directional Earthfault Protection
![Page 29: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/29.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Directional Earth Fault
Requirements are similar to directional overcurrenti.e. need operating signal
and polarising signal
Operating Signalobtained from residual connection of line CT'si.e. Iop = 3Io
Polarising SignalThe use of either phase-neutral or phase-phase voltage as the reference becomes inappropriate for the comparison with residual current.Most appropriate polarising signal is the residual voltage.
![Page 30: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/30.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Residual VoltageMay be obtained from ‘broken’ delta V.T. secondary.
VRES = VA-G + VB-G + VC-G = 3V0
Notes :1. VT primary must be earthed.2. VT must be of the '5 limb' construction (or 3 x single
phase units)
ABC
VRES
VC-GVB-GVA-G
![Page 31: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/31.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Directional Earth Fault Relays
Relay Characteristic Angle
0 - Resistance earthed systems
45 (I lags V) - Distribution systems (solidly earthed)
60 (I lags V) - Transmission systems (solidly earthed)
![Page 32: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/32.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Residual Voltage
Solidly Earthed System E S R FZLZS
A-G
VCVC VC
VB VBVB
VRESVA
VA VRES
VBVCVCVC VBVB
VAVA
Residual Voltage at R (relaying point) is dependant upon ZS / ZL ratio.
3Ex Z 2Z Z 2Z
Z VL0L1S0S1
S0RES +++=
![Page 33: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/33.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Residual Voltage
Resistance Earthed System
3Ex 3Z Z 2Z Z 2Z
3ZZ VEL0L1S0S1
ES0RES +++++
=
VA-G
VA-GVA-G
SR
SR
S VA-G
VB-GVC-G
G.FG.F
VB-G
VRES VRESVRES
VC-GVC-GVC-G
VC-G VB-GVC-G
VB-G VB-G VB-G
EN
G
S R FZLZS
ZE A-G
G.F
![Page 34: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/34.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Directional Earth Fault Relays
Relay Characteristic Angle0 - Resistance earthed systems45 (I lags V) - Distribution systems (solidly earthed)60 (I lags V) - Tranmission systems (solidly earthed)
Zero sequence network :-
V0 = ( - ) I0 (ZS0 + 3R)
ZL0ZS0 I0
V03R
![Page 35: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/35.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Current Polarising
A solidly earthed, high fault level (low source impedance) system may result in a small value of residual voltage at the relaying point. If residual voltage is too low to provide a reliable polarising signal then a current polarising signal may be used as an alternative.The current polarising signal may be derived from a CT located in a suitable system neutral to earth connection.e.g.
POLOP
DEF Relay
![Page 36: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/36.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Directional Control
Static Relay (METI + MCGG)
Characteristic Selectable
51 I
Overcurrent Unit(Static)
67
V
I
M.T.A. Selectable
Directional Unit(Static)
![Page 37: 03-Presentation Directional Protection](https://reader035.fdocuments.us/reader035/viewer/2022081312/5523b6444a7959505e8b4df7/html5/thumbnails/37.jpg)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Numerical Relay Directional Characteristic
Characteristic angle ØcØc = -180° --- 0° --- + 180°
Polarising thresholdsVp > 0.6VVop > 0.6 to 80V
in 0.2V stepsfor example
in 1° steps
Zone offorward start
forward operation
Reverse start
Øc - 90° Øc + 90°Øc
+Is
-Is