15 DK Cable Junction Boxes DK Cable Junction Boxes - 1.5 up to 240 mm² - Degree of protection IP 54-67 - Cable Junction Boxes are VDE tested in accordance with IEC 60670-22 i Assembling videos

description

dsad

Transcript of 01_DK_in

  • 15

    DK Cable Junction Boxes

    DK Cable Junction Boxes- 1.5 up to 240 mm

    - Degree of protection IP 54-67

    - Cable Junction Boxes are VDE tested in accordance with IEC 60670-22

    i

    Assembling videos

  • 16

    DK Cable Junction Boxes Content

    Criteria for selecting 18 - 19Box walls 20

    Box walls without knockoutsfrom 1.5 up to 50 mm2

    IP 65box walls without knockouts, can be drilled individually for customized requirements- without terminals 33 - 34- without terminals, for electrical equipment up to 63 A 35 - 36- Accessories 37 - 39

    With or without terminalsfrom 1.5 up to 240 mm2

    IP 65/IP 55cable entry via metric knockouts- with terminals for copper conductors 24 - 29- without terminals 30 - 31

    With FIXCONNECT plug-in technology for copper conductorsfrom 1.5 up to 16 mm2

    IP 65/IP 55cable entry via metric knockouts 22

    For aluminium- (Alu) and copper (Cu) conductorsfrom 1.5 up to 240 mm2

    IP 65/55cable entry via metric knockouts- with terminal blocks for aluminium- (Alu) and copper (Cu) conductors 54 - 60

    Cable entry via elastic membranes and integrated M20 threadup to 4 mm2

    IP 55- without terminals 41- with terminals for copper conductors 41

    Cable entry via cable, cable trunking and conduitsfrom 1.5 up to 4 mm2

    IP 54- with terminals for copper conductors 43 - without terminals, Accessories 44

    Cable entry via elastic membranesfrom 1.5 up to 4 mm2

    IP 55- with terminals for copper conductors, grey RAL 7035 46- without terminals, grey RAL 7035 47- with terminals for copper conductors, white RAL 9016 48- without terminals, white RAL 9016, Accessories 49

    Cable entry via elastic membranes from the rear and by box walls and lidfrom 1.5 up to 2.5 mm2

    IP 55for the clip-on attachment- with terminals for copper conductors, grey RAL 7035 51- without terminals, grey RAL 7035 51- with terminals for copper conductors, white RAL 9016 52- without terminals, white RAL 9016 52

    "Weatherproof" - for outdoor installation - harsh environment and/or outdoorfrom 1.5 up to 50 mm2

    IP 66cable/conduit entry via metric knockouts- with / without terminals, colours grey RAL 7032, black RAL 9011 62 - 69box walls without knockouts - without terminals, colours grey RAL 7032, black RAL 901 71 - 74

  • 17

    DK Cable Junction Boxes Content

    Additional information and planning tools (e.g. CAD parts libraries) can be found on the Internet at www.hensel-electric.in

    "Waterproof" - for outdoor installation - harsh environment and/or outdoorfrom 1,5 up to 10 mm2 cable entry via metric knockouts- for encapsulating, colours grey RAL 7032, black RAL 9011 NEW 80 - 84

    Tested for intrinsic fire resistance from 0.5 up to 16 mm2IP 65 / IP 66- material: duroplast, cable entry via included grommets, IP 65 94 - 95, 101- material: sheet steel, powder-coated, cable entry via mounted grommets, IP 66 96 - 100, 101

    For special applicationsfrom 1.5 up to 25 mm2

    IP 55 / IP 65cable entry via metric knockouts- for security lighting circuits, with red lid 103- for equipotential bonding conductors 104

    With main line branch terminals from 25 up to 35 mm2

    IP 55 / IP 65cable/conduit entry via metric knockouts- with terminal blocks for copper conductors 25 mm and 35 mm 106 - 107

    With terminal blocks for aluminium- (Alu) and copper conductors (Cu) from 1.5 up to 4 mm2

    IP 65cable/conduit entry via metric knockouts - Terminal boxes with terminal blocks 109 - 111

    Accessories 113 - 121

    "Weatherproof" - for outdoor installation - harsh environment and/or outdoorfrom 1.5 up to 50 mm2

    IP 66 / IP 65 with UL/CSA approval, (Nema 4X)box walls without knockouts, can be drilled individually- without terminals 76 - 77

    For offshore / heavy duty applicationsfrom 1.5 up to 35 mm2

    IP 66 / IP 67cable entry via metric knockouts - with / without terminals 86 - 90box walls without knockouts - without terminals 91 - 92

    Technical Details 123 - 134

  • 18

    DK Cable Junction Boxes Criteria for Selecting

    Applications FunctionsBranching andconnecting ofcopper conduc-tors

    Branching andconnecting ofaluminium and copper conduc-tors

    In rooms with dry climate In damp and wet environments Protected outdoors (refer to technical details) On fl ameable parts of buildings In buildings with mainly infl ammable materials In areas with a high risk of fi re

    Pages 22-52 Pages 54-60

    Cable trunking installation Pages 43-44

    Intrinsic fi re resistance Pages 94-101

    "Waterproof" for encapsulating Pages 80-84

    Weatherproof, for outdoor installation (harsh environment and/or outdoor)

    Improved behaviour in cases of fi re ame-resistant and halogen-free

    Pages 62-74

    Offshore applications Pages 86-92

    Security lighting circuits Page 103

    Equipotential bonding Page 104

    UL Approval Page 76-77

    DNV Approval Germanisch Lloyd Russian Maritime Register of Shipping

    Pages 62-92

    PA

  • 19

    DK Cable Junction Boxes Criteria for Selecting

    Connecting solid conductors and stranded conduc-tors

    Combining multi-ple control wires to one control cable

    2 circuits in one box

    Main line branch terminals

    Without terminals Box walls without knockouts

    Page 54-55Pages 109-111

    Pages 109-111 Pages 43-44DP 9220,DP 9221,DP 9222

    Page 106-107 Pages 30-36, Page 41 DN 2000, DN 2030,Page 44, 47Page 48 DE 9321, Page 49,Page 51 DE 9220,Page 52 DE 9221, Pages 64-65, 68-69, 71-74, 76-77, 89-92Page 103 D 9220, D 9240

    Pages 33-36all Boxes,Pages 71-74, 76-77Page 91-92

    Pages 43-44DP 9220,DP 9221,DP 9222

    Page 44

    Pages 64-65Pages 68-69Pages 71-74

    Pages 71-74

    Pages 89-92 Page 91-92

    Page 76-77

    Pages 64-65, 68-69Pages 71-74, 89-92

    Pages 71-74, 89-92

  • 20

    Assignment of box walls:

    The assignment of box walls is effected via wall symbols that are

    assigned to each product. The individual figures 2 give an indication,

    which wall is concerned.

    Wand4

    65 5

    Wall 18

    4 x M 253 x M 40/50

    Wall 19

    8 x M 324 x M 40/50

    Wall 20

    2 x M 2010 x M 251 x M 32/40

    Wall 21

    1 x M 204 x M 251 x M 32/403 x M 40/50

    Wall 22

    1 x Elastic membranes

    Wall 23

    2 x Elastic membranes

    Wall 24

    3 x Elastic membranes

    Wall 11 x M 20

    Wall 21 x M 20/25

    Wand 32 x M 20

    Wall 42 x M 20/25

    Wall 51 x M 20/251 x M 25/32

    Wall 62 x M 25/32

    Wall 72 x M 32

    Wall 82 x M 32/40

    Wall 92 x M 40

    Wall 102 x M 20/251 x M 25/32

    Wall 112 x M 20/251 x M 32/40

    Wall 121 x M 20/251 x M 25/321 x M 40/50

    Wall 131 x M 20/252 x M 40/50

    Wall 14

    3 x M 25/32

    Wall 15

    2 x M 25/321 x M 40/50

    Wall 16

    3 x M 32/40

    Wall 17

    4 x M 25/321 x M 40/50

    Wall 25

    1 x Removable-system

    Wall 26

    2 x Removable-system

    Wall 27

    3 x Removable-system

    Wall 28

    4 x Removable-system

    DK Cable junction boxes Box Walls

    All box walls are listed in the fold-out of the coverpages.

    Wall 29

    1 x M 63

    Wall 30

    2 x M 50

    Wall 31

    4 x up to 16 mm1 x up to 35 mm

  • 21

    DK Cable Junction Boxes with Terminals in Plug-in Technology Cable Entry via Metric Knockouts

    Plenty of space for the wiring: Wiring facilities both below the DIN rails and between the terminals.

    Different conductor types - rigid (r) and flexible (f) without treatment of conduc-tors - can be connected in one terminal.

    Conductors can be directly connected and disconnected with installed terminal.

    Stainless steel cover screws with quick fastening metric thread.Reducing cover xing time.

    Burning behaviour:Glow wire test according to IEC 60 695-2-11: 750 C, flame-retardant, self-extinguishing

    Labelling system for circuit description Label template on the Internet at

    www.hensel-electric.de - in the Downloads area.

  • 22

    DK Cable Junction Boxes with Terminals in Plug-in Technology Cable Entry via Metric Knockouts

    KC 9045

    Wall10

    106 5

    1.5-4 mm, Cu 3~

    FIXCONNECT plug-in terminal technology 5-pole per pole 4 x 1 x 1,5-4 mm sol/f, terminal technology,

    see annex DK Cable junction boxes included cable entry: 4 ESM 25, sealing range 9-17 mm for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V current carrying capacity 32 A

    139

    119

    70

    KC 9255

    Wall16

    118 8

    2.5-10 mm, Cu 3~

    FIXCONNECT plug-in terminal technology 5-pole per pole 4 x 1 x 2.5-10 mm r/f included cable entry: 3 ESM 32, sealing range 9-23 mm for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V current carrying capacity 50 A

    98

    160

    200

    KC 9355

    Wall13

    1315 15

    2.5-16 mm, Cu 3~

    FIXCONNECT plug-in terminal technology 5-pole per pole 4 x 1 x 2.5-16 mm r/f included cable entry: 3 ESM 40, sealing range 17-30 mm for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V current carrying capacity 76 A

    117260

    210

  • 23

    DK Cable Junction Boxes Cable Entry via Metric Knockouts

    Variable terminal mounting positions (5 positions) and new terminal technology

    Included accessories as listed: grommets ESM = IP 55

    Hensel cable junction boxes can in general also be used in poor environmental conditions by using IP 65 cable glands AKM/ASM.

    Stainless steel cover screws with quick fastening metric thread. Reducing cover xing time.

    Burning behaviour:Glow wire test according to IEC 60 695-2-11: 750 C / 960 C, flame-retardant, self-extinguishing

    Labelling system for circuit description Label template on the Internet at

    www.hensel-electric.de - in the Downloads area.

  • 24

    DK Cable Junction Boxes Cable Entry via Metric Knockouts

    D 9025

    Wall

    3

    13 3

    1.5-2.5 mm, Cu 3~

    with terminals 5-pole per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol included cable entry: 4 ESM 20, sealing range 6-13 mm for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm

    5388

    88

    D 9125

    Wall

    3

    13 3

    1.5-2.5 mm, Cu 3~

    with terminals 5-pole per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol included cable entry: 4 ESM 20, sealing range 6-13 mm with external fixing for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm

    5388

    88

    D 9045

    Wall

    4

    24 4

    1.5-4 mm, Cu 3~

    with terminals 5-pole per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol,

    2 x 6 mm sol included cable entry: 4 ESM 25, sealing range 9-17 mm for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm

    98 61

    98

    D 9145

    Wall

    3

    13 3

    1.5-4 mm, Cu 3~

    with terminals 5-pole per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol,

    2 x 6 mm sol included cable entry: 4 ESM 20, sealing range 6-13 mm for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm

    98 61

    98

  • 25

    DK Cable Junction Boxes Cable Entry via Metric Knockouts

    K 9065

    Wall10

    106 5

    2.5-6 mm, Cu 3~

    with terminals 5-pole per pole 4 x 2.5 mm sol, 4 x 4 mm sol, 3 x 6 mm sol,

    2 x 10 mm sol included cable entry: 3 ESM 32, sealing range 9-23 mm for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V tightening torque for terminal 1,5 Nm

    139

    119

    70

    K 9105

    Wall14

    106 6

    4-10 mm, Cu 3~

    with terminals 5-pole per pole 6 x 2.5 mm sol, 4 x 4 mm sol, 4 x 6 mm sol,

    4 x 10 mm sol, 2 x 16 mm s included cable entry: 3 ESM 32, sealing range 9-23 mm for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V current carrying capacity 63 A tightening torque for terminal 2,0 Nm

    82167

    125

    K 9255

    Wall16

    118 8

    10-25 mm, Cu 3~

    with terminals 5-pole per pole 6 x 10 mm sol, 4 x 16 mm s, 4 x 25 mm s,

    2 x 35 mm s included cable entry: 3 ESM 40, sealing range 17-30 mm for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V current carrying capacity 102 A tightening torque for terminal 3,0 Nm

    98

    160

    200

    K 9502

    Wall12

    1217 17

    10-35 mm, Cu 3~

    with terminals 5-pole per pole 4 x 10 mm sol, 4 x 16 mm s, 4 x 25 mm s,

    2 x 35 mm s included cable entry: 3 ESM 40, sealing range 17-30 mm for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V current carrying capacity 102 A tightening torque for terminal 3,0 Nm

    310

    210 117

  • 26

    DK Cable Junction Boxes Cable Entry via Metric Knockouts

    K 9504

    Wall12

    1217 17

    16-50 mm, Cu 3~

    with terminals 4-pole per polel 6 x 16 mm s, 4 x 25 mm s, 4 x 35 mm s,

    4 x 50 mm s cable entry via knockouts,

    order AKM/ASM separately (refer to index cable entry systems) for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V current carrying capacity 150 A tightening torque for terminal 12,0 Nm

    310

    210 117

    K 9505

    Wall12

    1217 17

    16-50 mm, Cu 3~

    with terminals 5-pole per pole 6 x 16 mm s, 4 x 25 mm s, 4 x 35 mm s,

    4 x 50 mm s cable entry via knockouts,

    order AKM/ASM separately (refer to index cable entry systems) for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V current carrying capacity 150 A tightening torque for terminal 12,0 Nm

    310

    210 117

    K 7055

    Wall20

    2021 21

    16-50 mm, Cu 3~

    with terminals 5-pole per pole 6 x 16 mm s, 4 x 25 mm s, 4 x 35 mm s,

    4 x 50 mm s sealable Order cable glands, flanges and other accessories separately as

    required for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V current carrying capacity 150 A tightening torque for terminal 12,0 Nm

    450

    300 170

    K 9355

    Wall15

    1513 13

    16-35 mm, Cu 3~

    with terminals 5-pole per pole 6 x 16 mm s, 4 x 25 mm s, 4 x 35 mm s,

    2 x 50 mm s included cable entry: 3 ESM 40, sealing range 17-30 mm for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V current carrying capacity 125 A tightening torque for terminal 12,0 Nm

    117

    260

    210

  • 27

    DK Cable Junction Boxes Cable Entry via Metric Knockouts

    K 7004

    Wall20

    2021 21

    16-70 mm, Cu 3~

    with terminals 4-pole per pole 4 x 16-70 mm s sealable Order cable glands, flanges and other accessories separately as

    required for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V current carrying capacity 216 A tightening torque for terminal 10,0 Nm

    450

    300 170

    K 7005

    Wall20

    2021 21

    16-70 mm, Cu 3~

    with terminals 5-pole per polel 4 x 16-70 mm s sealable Order cable glands, flanges and other accessories separately as

    required for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V current carrying capacity 216 A tightening torque for terminal 10,0 Nm

    450

    300 170

    K 1204

    Wall20

    2021 21

    16-150 mm, Cu/Alu 3~

    with terminals 4-pole per pole 2 x 16-150 mm, 4 x 16-70 mm,

    conductors can be inserted from the front into the clamping unit, terminal technology, see annex DK Cable junction boxes

    sealable Order cable glands, flanges and other accessories separately as

    required Reference to the preparation of aluminum conductors:

    1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.

    for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V current carrying capacity 250 A tightening torque for terminal 20,0 Nm

    450

    300 170

  • 28

    DK Cable Junction Boxes Cable Entry via Metric Knockouts

    K 1205

    Wall20

    2021 21

    16-150 mm, Cu/Alu 3~

    with terminals 5-pole per pole 2 x 16-150 mm, 4 x 16-70 mm,

    conductors can be inserted from the front into the clamping unit, terminal technology, see annex DK Cable junction boxes

    sealable Order cable glands, flanges and other accessories separately as

    required Reference to the preparation of aluminum conductors:

    1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.

    for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V current carrying capacity 250 A tightening torque for terminal 20,0 Nm

    450

    300 170

    K 2404

    Wall20

    1819 19

    25-240 mm, Cu/Alu 3~

    with terminals 4-pole per pole 2 x 25-185/240 mm, 4 x 25-120 mm,

    conductors can be inserted from the front into the clamping unit, terminal technology, see annex DK Cable junction boxes

    sealable Order cable glands, flanges and other accessories separately as

    required Reference to the preparation of aluminum conductors:

    1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.

    for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V current carrying capacity 400 A tightening torque for terminal 40,0 Nm

    600

    300 170

  • 29

    DK Cable Junction Boxes Cable Entry via Metric Knockouts

    K 2405

    Wall20

    1819 19

    25-240 mm, Cu/Alu 3~

    with terminals 5-pole per pole 2 x 25-185/240 mm, 4 x 25-120 mm,

    conductors can be inserted from the front into the clamping unit, terminal technology, see annex DK Cable junction boxes

    sealable Order cable glands, flanges and other accessories separately as

    required Reference to the preparation of aluminum conductors:

    1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.

    for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V current carrying capacity 400 A tightening torque for terminal 40,0 Nm

    600

    300 170

  • 30

    DK Cable Junction Boxes Cable Entry via Metric Knockouts

    D 9020

    Wall

    3

    13 3

    without terminals included cable entry: 4 ESM 20, sealing range 6-13 mm for normal environment and protected outdoor

    5388

    88

    D 9120

    Wall

    3

    13 3

    without terminals with external fixing included cable entry: 4 ESM 20, sealing range 6-13 mm for normal environment and protected outdoor

    5388

    88

    D 9140

    Wall

    3

    13 3

    without terminals included cable entry: 4 ESM 20, sealing range 6-13 mm for normal environment and protected outdoor

    98 58

    98

    D 9040

    Wall

    4

    24 4

    without terminals included cable entry: 4 ESM 25, sealing range 9-17 mm for normal environment and protected outdoor

    98 61

    98

    K 9060

    Wall10

    106 5

    without terminals included cable entry: 3 ESM 32, sealing range 9-23 mm for normal environment and protected outdoor

    139

    119

    70

    K 9100

    Wall14

    106 6

    without terminals included cable entry: 3 ESM 32, sealing range 9-23 mm for normal environment and protected outdoor

    82167

    125

  • 31

    DK Cable Junction Boxes Cable Entry via Metric Knockouts

    K 9250

    Wall16

    118 8

    without terminals included cable entry: 3 ESM 40, sealing range 17-30 mm for normal environment and protected outdoor

    98

    160

    200

    K 9350

    Wall13

    1315 15

    without terminals included cable entry: 3 ESM 40, sealing range 17-30 mm for normal environment and protected outdoor

    117260

    210

    K 9500

    Wall12

    1217 17

    without terminals cable entry via knockouts, order AKM/ASM separately

    (refer to index cable entry systems) for normal environment and protected outdoor

    310

    210 117

  • 32

    DK Cable Junction Boxes Box Walls without Knockouts

    Cable entries can be drilled individually.

    Labelling system for circuit description Label template on the Internet at

    www.hensel-electric.de - in the Downloads area.

    Burning behaviour:Glow wire test according to IEC 60 695-2-11: 750 C, flame-retardant, self-extinguishing

    Stainless steel cover screws with quick fastening metric thread. Reducing cover xing time.

  • 33

    DK Cable Junction Boxes Box Walls without Knockouts

    D 8020

    without terminals box walls without knockouts wall surface can be drilled individually for cable entry max. M 20 for normal environment and protected outdoor

    wall thickness of the bottom part 2,3 mm

    5388

    88

    D 8120

    without terminals with external fixing box walls without knockouts wall surface can be drilled individually for cable entry max. M 20 for normal environment and protected outdoor

    wall thickness of the bottom part 2,3 mm

    5388

    88

    D 8040

    without terminals box walls without knockouts wall surface can be drilled individually for cable entry max. M 20 for normal environment and protected outdoor

    wall thickness of the bottom part 2,3 mm

    98 58

    98 K 8060

    without terminals box walls without knockouts wall surface can be drilled individually for cable entry max. M 32 for normal environment and protected outdoor

    wall thickness of the bottom part 2,6 mm

    139

    119

    70

    K 8100

    without terminals box walls without knockouts wall surface can be drilled individually for cable entry max. M 32 for normal environment and protected outdoor

    wall thickness of the bottom part 2,8 mm

    82167

    125

  • 34

    DK Cable Junction Boxes Box Walls without Knockouts

    K 8250

    without terminals box walls without knockouts wall surface can be drilled individually for cable entry max. M 40 for normal environment and protected outdoor

    wall thickness of the bottom part 3 mm

    98

    160

    200

    K 8350

    without terminals box walls without knockouts wall surface can be drilled individually for cable entry max. M 50 for normal environment and protected outdoor

    wall thickness of the bottom part 3 mm

    117260

    210

    K 8500

    without terminals box walls without knockouts wall surface can be drilled individually for cable entry max. M 50 for normal environment and protected outdoor

    wall thickness of the bottom part 3 mm

    31

    0

    210 117

  • 35

    DK Cable Junction Boxes Box Walls without Knockouts

    K 0100

    with transparent lid lid fasteners for tool operation box walls without knockouts please order DIN rails or mounting plates additionally for normal environment and protected outdoor

    rated current for electrical devices up to 63 A wall thickness of the bottom part 3,5 mm

    300 170

    150

    K 0200

    with transparent lid lid fasteners for tool operation box walls without knockouts please order DIN rails or mounting plates additionally for normal environment and protected outdoor

    rated current for electrical devices up to 63 A wall thickness of the bottom part 3,5 mm

    300 170

    300

    K 0300

    with transparent lid lid fasteners for tool operation box walls without knockouts please order DIN rails or mounting plates additionally for normal environment and protected outdoor

    rated current for electrical devices up to 63 A wall thickness of the bottom part 3,5 mm

    300 170

    450

    K 0400

    with transparent lid lid fasteners for tool operation box walls without knockouts please order DIN rails or mounting plates additionally for normal environment and protected outdoor

    rated current for electrical devices up to 63 A wall thickness of the bottom part 3,5 mm

    600

    300 170

  • 36

    DK Cable Junction Boxes Box Walls without Knockouts

    K 0101

    with opaque lid lid fasteners for tool operation box walls without knockouts please order DIN rails or mounting plates additionally for normal environment and protected outdoor

    rated current for electrical devices up to 63 A wall thickness of the bottom part 3,5 mm

    300 170

    150

    K 0201

    with opaque lid lid fasteners for tool operation box walls without knockouts please order DIN rails or mounting plates additionally for normal environment and protected outdoor

    rated current for electrical devices up to 63 A wall thickness of the bottom part 3,5 mm

    300 170

    300

    K 0301

    with opaque lid lid fasteners for tool operation box walls without knockouts please order DIN rails or mounting plates additionally for normal environment and protected outdoor

    rated current for electrical devices up to 63 A wall thickness of the bottom part 3,5 mm

    300 170

    450

    K 0401

    with opaque lid lid fasteners for tool operation box walls without knockouts please order DIN rails or mounting plates additionally for normal environment and protected outdoor

    rated current for electrical devices up to 63 A wall thickness of the bottom part 3,5 mm

    600

    300 170

  • 37

    DK Cable Junction Boxes Empty Boxes Accessories for Cable Junction Boxes K0x0x

    Mi TS 15

    DIN raillength 134 mm in accordance with DIN EN 60 715 for Mi Empty box size 1 for equipment or terminals with clip-on mounting with fixing screws

    35

    15134

    Mi TS 30

    DIN raillength 284 mm in accordance with DIN EN 60 715 for Mi empty box sizes 1 to 8 for equipment or terminals with clip-on mounting with fixing screws

    35

    15284

    Mi TS 45

    DIN raillength 434 mm in accordance with DIN EN 60 715 for Mi empty box size 3 for equipment or terminals with clip-on mounting with fixing screws

    35

    15434

    Mi TS 60

    DIN raillength 584 mm in accordance with DIN EN 60 715 for Mi empty box sizes 4 and 8 for equipment or terminals with clip-on mounting with fixing screws

    35

    15584

    Mi MP 1

    Mounting plateW 259 x H 115 mm material thickness 4 mm for Mi-Empty boxes sizes 1, 2, 3, 4 with fixing screws

    259

    115

    Mi MP 2

    Mounting plateW 265 x H 265 mm material thickness 4 mm for Mi-Empty boxes sizes 2 to 8 with fixing screws

    265

    265

  • 38

    DK Cable Junction Boxes Empty Boxes Accessories for Cable Junction Boxes K0x0x

    Mi MP 3

    Mounting plateW 265 x H 415 mm material thickness 4 mm for Mi-Empty boxes sizes 3, 4 with fixing screws

    415

    265

    Mi MP 4

    Mounting plateW 265 x H 565 mm material thickness 4 mm for Mi-Empty boxes sizes 4, 8 with fixing screws

    565

    265

    Mi PL 2

    Sealing cap 2 sealing caps for converting the lid fasteners

    Mi SR 4

    Conversion setfor manual operation on tool operation 4 fastening covers

    Mi SN 4

    Conversion setfor converting lid fasteners from tool to manual operation 4 manual actuators

  • 39

    DK Cable Junction Boxes Empty Boxes Accessories for Cable Junction Boxes K0x0x

    Mi DV 01

    L ocking device insertion only in connection with Mi PL 2, Mi SR 4 or Mi SN 4

    Mi ZS 11

    Lid lockwith locking device I Is being used instead of fasteners for hand or tool operation in

    order to prevent unauthorised opening of the lids consisting of: cylinder lock, keys, locking device insertion, dust

    cover

    Mi ZS 12

    Lid lockwith locking device II Is being used instead of fasteners for hand or tool operation in

    order to prevent unauthorised opening of the lids consisting of: cylinder lock, keys, locking device insertion, dust

    cover

    Mi DR 04

    Lid fastener for tool operationtriangle 8 mm is used instead of fasteners for hand- or tool operation, in order to

    make unauthorized opening of lids more difficult 4 locking devices with triangle 8 mm and key

    DS 1

    Triangular key 8 mm

    Mi AL 40

    4 stainless steel external brackets for external fixing of enclosures

  • 40

    DK Cable Junction Boxes Cable Entry via Elastic Membranes and Integrated M 20 Thread

    IP 55 with cable entry via elastic membranes.

    IP 65 with ADM 20 cable gland without locknut. The gland is secured by an integrated M 20 thread.

    Captive cover screws with quick-release lock.

    Burning behaviour:Glow wire test according to IEC 60 695-2-11: 750 C, flame-retardant, self-extinguishing

  • 41

    DK Cable Junction boxes Cable Entry via Elastic Membranes and Integrated M 20 Thread

    DN 2035

    Wall

    3

    33 3

    1.5-2.5 mm, Cu 3~

    with terminals 5-pole per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol cable entry via elastic membranes and integrated M 20 thread 8 elastic membranes, closed, sealing range 3-12 mm included cable entry: 3 ADM 20, sealing range 6,5-13,5 mm for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm

    DN 2005

    Wall

    3

    33 3

    1.5-2.5 mm, Cu 3~

    with terminals 5-pole per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol cable entry via elastic membranes and integrated M 20 thread 8 elastic membranes, closed, sealing range 3-12 mm for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm

    DN 2030

    Wall

    3

    33 3

    without terminals cable entry via elastic membranes and integrated M 20 thread 8 elastic membranes, closed, sealing range 3-12 mm included cable entry: 3 ADM 20, sealing range 6,5-13,5 mm

    DN 2000

    Wall

    3

    33 3

    without terminals cable entry via elastic membranes and integrated M 20 thread 8 elastic membranes, closed, sealing range 3-12 mm for normal environment and protected outdoor

    ADM 20

    ISO thread M 20 x 1.5

    sealing range 6,5-13,5 mm with strain relief for indoor - normal environment and (or) protected outdoor installation ambient temperature - 25 to + 35 C glow wire test IEC 60 695-2-11: 750 C

    tightening torque 2,0 Nm

  • 42

    DK Cable Junction Boxes Cable Entry via Knockouts for Cable Trunking and Conduit Installation

    Simply cut out cable trunking wall to the required width.

    The cables can be inserted from the front! No threading of cables neccessary!

    Supplied accessory grommets DPS 02 = IP 54

    The clean installation solution for cable trunking!

    Removable trunking adapters for connection of cable trunkings to junction boxes.

    Stainless steel cover screws with quick fastening metric thread. Reducing cover xing time.

    Burning behaviour:Glow wire test according to IEC 60 695-2-11: 750 C, flame-retardant, self-extinguishing

    Labelling system for circuit description Label template on the Internet at

    www.hensel-electric.de - in the Downloads area.

  • 43

    DK Cable Junction Boxes Cable Entry via Knockouts for Cable Trunking and Conduit Installation

    DP 9025

    Wall26

    2526 26

    1.5-2.5 mm, Cu 3~

    with terminals 5-pole per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol for cable trunking and conduit installation included cable entry: 4 DPS 02, sealing range 10-13,5 mm for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm

    5088

    88

    DP 9221

    Wall28

    2727 27

    1.5-2.5 mm, Cu 3~

    with terminals 5-pole per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol for cable trunking and conduit installation included cable entry: 7 DPS 02, sealing range 10-13,5 mm for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm

    50139

    119

    DP 9222

    Wall28

    2727 27

    1.5-2.5 mm, Cu 3~

    with 2 terminals 5-pole per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol for cable trunking and conduit installation included cable entry: 7 DPS 02, sealing range 10-13,5 mm for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm

    50139

    119

    DPC 9225

    Wall28

    2727 27

    1.5-2.5 mm, Cu 3~

    FIXCONNECT plug-in terminal technology 5-pole per pole 4 x 1 x 1.5-2.5 mm sol/f, terminal technology,

    see annex DK Cable junction boxes for cable trunking and conduit installation included cable entry: 4 DPS 02, sealing range 10-13,5 mm for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V current carrying capacity 32 A

    50139

    119

  • 44

    DK Cable Junction Boxes Cable Entry via Knockouts for Cable Trunking and Conduit Installation

    DP 9020

    Wall26

    2526 26

    without terminals for cable trunking and conduit installation included cable entry: 4 DPS 02, sealing range 10-13,5 mm for normal environment and protected outdoor

    5088

    88

    DP 9220

    Wall28

    2727 27

    without terminals for cable trunking and conduit installation included cable entry: 7 DPS 02, sealing range 10-13,5 mm for normal environment and protected outdoor

    50139

    119

    DPS 02

    Removable grommet

    degree of protection: IP 54 sealing range 10-13.5 mm for retrofitting for cable junction boxes DP 9020, DP 9220, DP 9025, DP 9221, DP 9222, DP 9026, DPC 9225

    ERA 20

    Removable conduit adapter

    degree of protection: IP 54 sealing range 10-13.5 mm for wiring conduits M 20 for cable junction boxes DP 9020, DP 9220, DP 9025, DP 9221, DP 9222, DP 9026, DPC 9225

    EKA 20

    Removable trunking adapter

    degree of protection: IP 54 sealing range 10-13.5 mm for mini trunking up to 20 x 20 mm for cable junction boxes DP 9020, DP 9220, DP 9025, DP 9221, DP 9222, DP 9026, DPC 9225

  • 45

    DK Cable Junction Boxes Cable Entry via Elastic Membranes

    No punching tool required - insert the conductor and its done

    Degree of protection IP 55

    Grommet supplied for sealing membra-nes in case of modifications.

    Box wall with 3 cable entries Stainless steel cover screws with quick fastening metric thread. Reducing cover xing time.

    Burning behaviour:Glow wire test according to IEC 60 695-2-11: 750 C, flame-retardant, self-extinguishing

    Labelling system for circuit description Label template on the Internet at

    www.hensel-electric.de - in the Downloads area.

  • 46

    DK Cable Junction Boxes Cable Entry via Elastic Membranes

    DE 9325

    Wall24

    2423 23

    1.5-2.5 mm, Cu 3~

    with terminals 5-pole per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol 10 elastic membranes, closed cable entries,

    sealing range 6.5-16 mm for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm

    4788

    88

    DE 9345

    Wall24

    2423 23

    1.5-4 mm, Cu 3~

    with terminals 5-pole per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol,

    2 x 6 mm sol 10 elastic membranes, closed cable entries,

    sealing range 6.5-18 mm for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm

    98

    98 52

    DE 9335

    Wall24

    2423 23

    1.5-4 mm, Cu 3~

    terminals with wire protection 5-pole per pole 4 x 1.5 mm sol/s/f, 4 x 2.5 mm sol/s/f,

    2 x 4 mm sol/s/f 10 elastic membranes, closed cable entries,

    sealing range 6.5-16 mm with cable retention (2 pc.) for cable tie up to 6.5 mm width for normal environment and protected outdoor

    rated insulation voltage AC/DC 500 V rated current 32 A tightening torque for terminal 0,8 Nm Dismantling length 6 mm

    4788

    88

  • 47

    DK Cable Junction Boxes Cable Entry via Elastic Membranes

    DE 9320

    Wall24

    2423 23

    without terminals 10 elastic membranes, closed cable entries,

    sealing range 6.5-16 mm for normal environment and protected outdoor

    4788

    88

    DE 9340

    Wall24

    2423 23

    without terminals 10 elastic membranes, closed cable entries,

    sealing range 6.5-18 mm for normal environment and protected outdoor

    98

    98 52

    DE 9330

    Wall24

    2423 23

    without terminals 10 elastic membranes, closed cable entries,

    sealing range 6.5-16 mm with cable retention (2 pc.) for cable tie up to 6.5 mm width for normal environment and protected outdoor

    4788

    88

    DE 9350

    Wall24

    2423 23

    without terminals 10 elastic membranes, closed cable entries,

    sealing range 6.5-18 mm with cable retention (2 pc.) for cable tie up to 6.5 mm width for normal environment and protected outdoor

    98

    98 52

  • 48

    DK Cable Junction Boxes Cable Entry via Elastic Membranes

    DE 9326

    Wall24

    2423 23

    1.5-2.5 mm, Cu 3~

    with terminals 5-pole per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol 10 elastic membranes, closed cable entries,

    sealing range 6.5-16 mm for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm

    4788

    88

    DE 9346

    Wall24

    2423 23

    1.5-4 mm, Cu 3~

    with terminals 5-pole per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol,

    2 x 6 mm sol 10 elastic membranes, closed cable entries,

    sealing range 6.5-18 mm for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm

    98

    98 52

    DE 9336

    Wall24

    2423 23

    1.5-2.5 mm, Cu 3~

    terminals with wire protection 5-pole per pole 4 x 1.5 mm sol/s/f, 4 x 2.5 mm sol/s/f,

    2 x 4 mm sol/s/f 10 elastic membranes, closed cable entries,

    sealing range 6.5-16 mm with cable retention (2 pc.) for cable tie up to 6.5 mm width for normal environment and protected outdoor

    rated insulation voltage AC/DC 500 V rated current 32 A tightening torque for terminal 0,8 Nm Dismantling length 11 mm

    4788

    88

    DE 9321

    Wall24

    2423 23

    without terminals 10 elastic membranes, closed cable entries,

    sealing range 6.5-16 mm for normal environment and protected outdoor

    4788

    88

  • 49

    DK Cable Junction Boxes Cable Entry via Elastic Membranes

    DE 9341

    Wall24

    2423 23

    without terminals 10 elastic membranes, closed cable entries,

    sealing range 6.5-18 mm for normal environment and protected outdoor

    98

    98 52

    DE 9331

    Wall24

    2423 23

    without terminals 10 elastic membranes, closed cable entries,

    sealing range 6.5-16 mm with cable retention (2 pc.) for cable tie up to 6.5 mm width for normal environment and protected outdoor

    4788

    88

    DE 9351

    Wall24

    2423 23

    without terminals 10 elastic membranes, closed cable entries,

    sealing range 6.5-18 mm with cable retention (2 pc.) for cable tie up to 6.5 mm width for normal environment and protected outdoor

    98

    98 52

    KHR 01

    Cable retentionfor cable diameter 6,5 - 14 mm set with 10 x 6 cable rentention rings 30 pieces for cable diameter 6,5 - 10 mm 30 pieces for cable diameter 10 - 14 mm

    KHR 02

    Cable retentionfor cable diameter 10 - 16 mm set with 10 x 6 cable rentention rings 30 pieces for cable diameter 10 - 14 mm 30 pieces for cable diameter 13 - 16 mm

    DK ZE 10

    Cable retention set with 10 pieces for fixing in the bottom part of DK-cable junction boxes cable retention with cable clip up to 6.5 mm

  • 50

    DK Cable Junction Boxes Cable Entry via Elastic Membranes in Bottom and Box Walls

    Cable entry from the rear via elastic membranes in the bottom

    Lid for clip-on attachment. Reducing cover xing time

    Flexible elastic membranes -no cable glands required. Push through and tight!

    Cable entry via elastic membranes in box walls

    Burning behaviour:Glow wire test according to IEC 60 695-2-11: 750 C, flame-retardant, self-extinguishing

  • 51

    DK Cable Junction Boxes Cable Entry via Elastic Membranes in Bottom and Box Walls

    DE 9225

    Wall23

    2324 24

    1.5-2.5 mm, Cu 3~

    with terminals 5-pole per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol box walls with 10 elastic membranes, closed, sealing range

    3-14 mm, bottom with 2 elastic membranes, closed lid with clip-on attachment for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm

    DE 9220

    Wall23

    2324 24

    without terminals box walls with 10 elastic membranes, closed, sealing range

    3-14 mm, bottom with 2 elastic membranes, closed lid with clip-on attachment with cable retention (2 pc.) for cable tie up to 6.5 mm width for normal environment and protected outdoor

    DK ZE 10

    Cable retention set with 10 pieces for fixing in the bottom part of DK-cable junction boxes cable retention with cable clip up to 6.5 mm

    KHR 01

    Cable retentionfor cable diameter 6,5 - 14 mm set with 10 x 6 cable rentention rings 30 pieces for cable diameter 6,5 - 10 mm 30 pieces for cable diameter 10 - 14 mm

    KHR 02

    Cable retentionfor cable diameter 10 - 16 mm set with 10 x 6 cable rentention rings 30 pieces for cable diameter 10 - 14 mm 30 pieces for cable diameter 13 - 16 mm

    DE MB 10

    Assembly bracket external brackets 10 units material: thermoplastics for quick installation of cable junction boxes DE 922. and DN 20..

  • 52

    DK Cable Junction Boxes Cable Entry via Elastic Membranes in Bottom and Box Walls

    DE 9226

    Wall23

    2324 24

    1.5-2.5 mm, Cu 3~

    with terminals 5-pole per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol box walls with 10 elastic membranes, closed, sealing range

    3-14 mm, bottom with 2 elastic membranes, closed lid with clip-on attachment for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm

    DE 9221

    Wall23

    2324 24

    without terminals box walls with 10 elastic membranes, closed, sealing range

    3-14 mm, bottom with 2 elastic membranes, closed lid with clip-on attachment with cable retention (2 pc.) for cable tie up to 6.5 mm width for normal environment and protected outdoor

    DK ZE 10

    Cable retention set with 10 pieces for fixing in the bottom part of DK-cable junction boxes cable retention with cable clip up to 6.5 mm

    KHR 01

    Cable retentionfor cable diameter 6,5 - 14 mm set with 10 x 6 cable rentention rings 30 pieces for cable diameter 6,5 - 10 mm 30 pieces for cable diameter 10 - 14 mm

    KHR 02

    Cable retentionfor cable diameter 10 - 16 mm set with 10 x 6 cable rentention rings 30 pieces for cable diameter 10 - 14 mm 30 pieces for cable diameter 13 - 16 mm

    DE MB 10

    Assembly bracket external brackets 10 units material: thermoplastics for quick installation of cable junction boxes DE 922. and DN 20..

  • 53

    DK Cable Junction Boxes with Terminals for Aluminium and Copper Conductors Cable Entry via Metric Knockouts

    Degree of protection up to IP 65. In the case of twisted cables, cable glands are required in principle to achieve the degree of protection IP 54.

    Separate clamping units for aluminium and copper conductors

    Stainless steel cover screws with quick fastening metric thread. Reducing cover xing time.

    Burning behaviour:Glow wire test according to IEC 60 695-2-11: 750 C, flame-retardant, self-extinguishing

    Labelling system for circuit description. Label template on the Internet at

    www.hensel-electric.de - in the Downloads area.

  • 54

    DK Cable Junction Boxes with Terminals for Aluminium and Copper Conductors Cable Entry via Metric Knockouts

    D 9041

    Wall

    4

    24 4

    1.5-2.5 mm, Cu/Alu 3~

    with terminals 5-pole per polel 4 x 1.5 mm sol/f, 4 x 2.5 mm sol/f, conductors

    are inserted into the screw-type terminal, terminal technology, see annex DK Cable junction boxes

    included cable entry: 4 ESM 25, sealing range 9-17 mm In the case of twisted cables, cable glands are required in

    principle to achieve the degree of protection IP 54. Reference to the preparation of aluminum conductors:

    1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.

    for normal environment and protected outdoor

    rated insulation voltage AC/DC 250 V current carrying capacity 20 A tightening torque for terminal 0,5 Nm

    98 61

    98

    K 9061

    Wall10

    106 5

    1.5-4 mm, Cu/Alu 3~

    with terminals 5-pole per pole 4 x 1.5 mm sol/f, 4 x 2.5 mm sol/f, 4 x 4 mm

    sol/f, conductors are inserted into the screw-type terminal, terminal technology, see annex DK Cable junction boxes

    included cable entry: 3 ESM 32, sealing range 9-23 mm In the case of twisted cables, cable glands are required in

    principle to achieve the degree of protection IP 54. Reference to the preparation of aluminum conductors:

    1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.

    for normal environment and protected outdoor

    rated insulation voltage AC/DC 400 V current carrying capacity 20 A tightening torque for terminal 0,6 Nm

    139

    119

    70

  • 55

    DK Cable Junction Boxes with Terminals for Aluminium and Copper Conductors Cable Entry via Metric Knockouts

    K 9351

    Wall13

    1315 15

    6-16 mm, Cu/Alu 3~

    with terminals 5-pole per polel 4 x 6 mm sol/f, 4 x 10 mm sol/f, 4 x 16 mm

    sol/s/f, conductors are inserted into the screw-type terminal, terminal technology, see annex DK Cable junction boxes

    included cable entry: 3 ESM 40, sealing range 17-30 mm In the case of twisted cables, cable glands are required in

    principle to achieve the degree of protection IP 54. Reference to the preparation of aluminum conductors:

    1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.

    for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V current carrying capacity 76 A tightening torque for terminal 3,0 Nm

    117260

    210

    KF 9251

    Wall16

    118 8

    1.5-50 mm, Cu/Alu 3~

    with connecting terminal 5-pole per pole 2 x 1 x 1.5-50 mm, conductors are inserted into

    the screw-type terminal, terminal technology, see annex DK Cable junction boxes

    included cable entry: 2 EDK 40, sealing range 11-30 mm Reference to the preparation of aluminum conductors:

    1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.

    for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V current carrying capacity 160 A tightening torque for terminal 1.5 Nm 1.5-2.5 mm

    5.0 Nm 4-10 mm 12,0 Nm 16-50 mm

    98

    160

    200

  • 56

    DK Cable Junction Boxes with Terminals for Aluminium and Copper Conductors Cable Entry via Metric Knockouts

    KF 9501

    Wall12

    1217 17

    1.5-50 mm, Cu/Alu 3~

    with connecting terminal 5-pole per pole 2 x 1 x 1.5-50 mm, conductors are inserted into

    the screw-type terminal, terminal technology, see annex DK Cable junction boxes

    included cable entry: 2 EDK 40, sealing range 11-30 mm Reference to the preparation of aluminum conductors:

    1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.

    for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V current carrying capacity 160 A tightening torque for terminal 1.5 Nm 1.5-2.5 mm

    5.0 Nm 4-10 mm 12,0 Nm 16-50 mm

    310

    210 117

    K 7051

    Wall20

    2021 21

    2.5-50 mm, Cu/Alu 3~

    with terminals 5-pole per pole 4 x 2.5-50 mm, conductors are inserted into the

    screw-type terminal, terminal technology, see annex DK Cable junction boxes

    sealable Order cable glands, flanges and other accessories separately as

    required Reference to the preparation of aluminum conductors:

    1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.

    for normal environment and protected outdoor

    rated insulation voltage AC/DC 750 V current carrying capacity Cu, 150 A

    Alu, 120 A tightening torque for terminal 10,0 Nm

    450

    300 170

  • 57

    DK Cable Junction Boxes with Terminals for Aluminium and Copper Conductors Cable Entry via Metric Knockouts

    K 7042

    Wall20

    2021 21

    10-95 mm Cu/Alu 3~

    with terminals 4-pole per pole 2 x 10-95 mm, conductors can be inserted from

    the front into the clamping unit, terminal technology, see annex DK Cable junction boxes

    sealable Order cable glands, flanges and other accessories separately as

    required Reference to the preparation of aluminum conductors:

    1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.

    for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V current carrying capacity 160 A tightening torque for terminal 20,0 Nm

    450

    300 170

    K 7052

    Wall20

    2021 21

    10-95 mm Cu/Alu 3~

    with terminals 5-pole per pole 2 x 10-95 mm, conductors can be inserted from

    the front into the clamping unit, terminal technology, see annex DK Cable junction boxes

    sealable Order cable glands, flanges and other accessories separately as

    required Reference to the preparation of aluminum conductors:

    1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.

    for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V current carrying capacity 160 A tightening torque for terminal 20,0 Nm

    450

    300 170

  • 58

    DK Cable Junction Boxes with Terminals for Aluminium and Copper Conductors Cable Entry via Metric Knockouts

    K 9951

    Wall20

    2021 21

    6-95 mm, Cu/Alu 3~

    with terminals 5-pole per pole 4 x 6-95 mm, conductors are inserted into the

    screw-type terminal, terminal technology, see annex DK Cable junction boxes

    Order cable glands, flanges and other accessories separately as required

    Reference to the preparation of aluminum conductors: 1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.

    for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V current carrying capacity 490 A tightening torque for terminal 12.0 Nm 6-25 mm

    22.0 Nm 35-95 mm

    450

    300 170

    K 1204

    Wall20

    2021 21

    16-150 mm, Cu/Alu 3~

    with terminals 4-pole per pole 2 x 16-150 mm, 4 x 16-70 mm, conductors can

    be inserted from the front into the clamping unit, terminal technology, see annex DK Cable junction boxes

    sealable Order cable glands, flanges and other accessories separately as

    required Reference to the preparation of aluminum conductors:

    1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.

    for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V current carrying capacity 250 A tightening torque for terminal 20,0 Nm

    450

    300 170

  • 59

    DK Cable Junction Boxes with Terminals for Aluminium and Copper Conductors Cable Entry via Metric Knockouts

    K 1205

    Wall20

    2021 21

    16-150 mm, Cu/Alu 3~

    with terminals 5-pole per pole 2 x 16-150 mm, 4 x 16-70 mm,

    conductors can be inserted from the front into the clamping unit, terminal technology, see annex DK Cable junction boxes

    sealable Order cable glands, flanges and other accessories separately as

    required Reference to the preparation of aluminum conductors:

    1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.

    for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V current carrying capacity 250 A tightening torque for terminal 20,0 Nm

    450

    300 170

    K 2404

    Wall20

    1819 19

    25-240 mm, Cu/Alu 3~

    with terminals 4-pole per pole 2 x 25-185/240 mm, 4 x 25-120 mm,

    conductors can be inserted from the front into the clamping unit, terminal technology, see annex DK Cable junction boxes

    sealable Order cable glands, flanges and other accessories separately as

    required Reference to the preparation of aluminum conductors:

    1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.

    for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V current carrying capacity 400 A tightening torque for terminal 40,0 Nm

    600

    300 170

  • 60

    DK Cable Junction Boxes with Terminals for Aluminium and Copper Conductors Cable Entry via Metric Knockouts

    K 2405

    Wall20

    1819 19

    25-240 mm, Cu/Alu 3~

    with terminals 5-pole per pole 2 x 25-185/240 mm, 4 x 25-120 mm,

    conductors can be inserted from the front into the clamping unit, terminal technology, see annex DK Cable junction boxes

    sealable Order cable glands, flanges and other accessories separately as

    required Reference to the preparation of aluminum conductors:

    1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.

    for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V current carrying capacity 400 A tightening torque for terminal 40,0 Nm

    600

    300 170

    K 2401

    Wall20

    1819 19

    35-240 mm, Cu/Alu 3~

    with terminals 5-pole per pole 4 x 35-240 mm, conductors are inserted into the

    screw-type terminal, terminal technology, see annex DK Cable junction boxes

    sealable Order cable glands, flanges and other accessories separately as

    required Reference to the preparation of aluminum conductors:

    1. Clean the bared conductor end carefully by scraping off the oxide film, for example with a knife, (Please do not use rasps, emery paper or brushes!). 2. Immediately after removing the oxide film the conductor end is to rub in with acid and alkali free fat for example vaseline, and immediately to be connected in the terminal. 3. The prementioned processing steps are to be repeated, if the conductor was disconnected and connected again. 4. Due to the disposition to flowing of aluminum the terminals are to be re-tightened before start-up and after the first 200 operation hours.

    for normal environment and protected outdoor

    rated insulation voltage AC/DC 690 V current carrying capacity 850 A tightening torque for terminal 26.0 Nm 35-120 mm

    55.0 Nm 150-240 mm

    600

    300 170

  • 61

    DK Cable Junction Boxes Weatherproof, for Outdoor Installation Cable Entry via Metric Knockouts

    Degree of protection IP 66 Flame retardant, self-extinguishing,

    made of high-grade material:PC-GFS, glass- bre reinforced thermoplastics, impact proof

    KF-Cable junction boxes comply with regulatory restrictions for buildings with requirements regarding the structural fire protection!

    halogen-free, silicone-free:low toxicity, low fume development

    Stainless steel cover screws with quick fastening metric thread. Reducing cover xing time.

    Burning behaviour:Glow-wire test 960C according to IEC 60 695-2-11, UL Subject 94: V-0 ame-retardant, self-extinguishing

    Degree of protection IP 66 using cable glands ASS.. (colour black) or cable glands ASM.. (colour grey), available as an accessory.

  • 62

    DK Cable Junction Boxes Weatherproof, for Outdoor Installation Cable Entry via Metric Knockouts

    KF 9025

    Wall

    3

    13 3

    1.5-2.5 mm, Cu 3~

    with terminals 5-pole per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol cable entry via knockouts, order ASM separately

    (refer to index cable entry systems) "Outdoor - harsh environment and (or) outdoor"

    rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm

    5388

    88

    KF 9045

    Wall

    4

    24 4

    1.5-4 mm, Cu 3~

    with terminals 5-pole per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol,

    2 x 6 mm sol cable entry via knockouts, order ASM separately

    (refer to index cable entry systems) "Outdoor - harsh environment and (or) outdoor"

    rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm

    98 61

    98

    KF 9065

    Wall10

    106 5

    2.5-6 mm, Cu 3~

    with terminals 5-pole per pole 4 x 2.5 mm sol, 4 x 4 mm sol, 3 x 6 mm sol,

    2 x 10 mm sol cable entry via knockouts, order ASM separately

    (refer to index cable entry systems) "Outdoor - harsh environment and (or) outdoor"

    rated insulation voltage AC/DC 690 V tightening torque for terminal 1,5 Nm

    139

    119

    70

    KF 9105

    Wall14

    106 6

    4-10 mm, Cu 3~

    with terminals 5-pole per pole 6 x 2.5 mm sol, 4 x 4 mm sol, 4 x 6 mm sol,

    4 x 10 mm sol, 2 x 16 mm s cable entry via knockouts, order ASM separately

    (refer to index cable entry systems) "Outdoor - harsh environment and (or) outdoor"

    rated insulation voltage AC/DC 690 V current carrying capacity 63 A tightening torque for terminal 2,0 Nm

    82167

    125

  • 63

    DK Cable Junction Boxes Weatherproof, for Outdoor Installation Cable Entry via Metric Knockouts

    KF 9255

    Wall16

    118 8

    10-25 mm, Cu 3~

    with terminals 5-pole per pole 6 x 10 mm sol, 4 x 16 mm s, 4 x 25 mm s,

    2 x 35 mm s cable entry via knockouts, order ASM separately

    (refer to index cable entry systems) "Outdoor - harsh environment and (or) outdoor"

    rated insulation voltage AC/DC 690 V current carrying capacity 102 A tightening torque for terminal 3,0 Nm

    98

    160

    200

    KF 9355

    Wall15

    1513 13

    16-35 mm, Cu 3~

    with terminals 5-pole per pole 6 x 16 mm s, 4 x 25 mm s, 4 x 35 mm s,

    2 x 50 mm s cable entry via knockouts, order ASM separately

    (refer to index cable entry systems) "Outdoor - harsh environment and (or) outdoor"

    rated insulation voltage AC/DC 690 V current carrying capacity 125 A tightening torque for terminal 12,0 Nm

    117

    260

    210

    KF 9505

    Wall12

    1217 17

    16-50 mm, Cu 3~

    with terminals 5-pole per pole 6 x 16 mm s, 4 x 25 mm s, 4 x 35 mm s,

    4 x 50 mm s cable entry via knockouts, order ASM separately

    (refer to index cable entry systems) "Outdoor - harsh environment and (or) outdoor"

    rated insulation voltage AC/DC 690 V current carrying capacity 150 A tightening torque for terminal 12,0 Nm

    310

    210 117

  • 64

    DK Cable Junction Boxes Weatherproof, for Outdoor Installation Cable Entry via Metric Knockouts

    KF 9020

    Wall

    3

    13 3

    without terminals cable entry via knockouts, order ASM separately

    (refer to index cable entry systems) "Outdoor - harsh environment and (or) outdoor"

    5388

    88

    KF 9040

    Wall

    4

    24 4

    without terminals cable entry via knockouts, order ASM separately

    (refer to index cable entry systems) "Outdoor - harsh environment and (or) outdoor"

    98 61

    98

    KF 9060

    Wall10

    106 5

    without terminals cable entry via knockouts, order ASM separately

    (refer to index cable entry systems) "Outdoor - harsh environment and (or) outdoor"

    139

    119

    70

    KF 9100

    Wall14

    106 6

    without terminals cable entry via knockouts, order ASM separately

    (refer to index cable entry systems) "Outdoor - harsh environment and (or) outdoor"

    82167

    125

    KF 9250

    Wall16

    118 8

    without terminals cable entry via knockouts, order ASM separately

    (refer to index cable entry systems) "Outdoor - harsh environment and (or) outdoor"

    98

    160

    200

  • 65

    DK Cable Junction Boxes Weatherproof, for Outdoor Installation Cable Entry via Metric Knockouts

    KF 9350

    Wall13

    1315 15

    without terminals cable entry via knockouts, order ASM separately

    (refer to index cable entry systems) "Outdoor - harsh environment and (or) outdoor"

    117260

    210

    KF 9500

    Wall12

    1217 17

    without terminals cable entry via knockouts, order ASM separately

    (refer to index cable entry systems) "Outdoor - harsh environment and (or) outdoor"

    310

    210 117

  • 66

    DK Cable Junction Boxes Weatherproof, for Outdoor Installation Cable Entry via Metric Knockouts

    KF 5025

    Wall

    3

    13 3

    1.5-2.5 mm, Cu 3~

    with terminals 5-pole per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol cable entry via knockouts, order ASS separately

    (refer to index cable entry systems) "Outdoor - harsh environment and (or) outdoor"

    rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm

    5388

    88

    KF 5045

    Wall

    4

    24 4

    1.5-4 mm, Cu 3~

    with terminals 5-pole per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol,

    2 x 6 mm sol cable entry via knockouts, order ASS separately

    (refer to index cable entry systems) "Outdoor - harsh environment and (or) outdoor"

    rated insulation voltage AC/DC 690 V tightening torque for terminal 1,2 Nm

    98 61

    98

    KF 5065

    Wall10

    106 5

    2.5-6 mm, Cu 3~

    with terminals 5-pole per pole 4 x 2.5 mm sol, 4 x 4 mm sol, 3 x 6 mm sol,

    2 x 10 mm sol cable entry via knockouts, order ASS separately

    (refer to index cable entry systems) "Outdoor - harsh environment and (or) outdoor"

    rated insulation voltage AC/DC 690 V tightening torque for terminal 1,5 Nm

    139

    119

    70

    KF 5105

    Wall14

    106 6

    4-10 mm, Cu 3~

    with terminals 5-pole per pole 6 x 2.5 mm sol, 4 x 4 mm sol, 4 x 6 mm sol,

    4 x 10 mm sol, 2 x 16 mm s cable entry via knockouts, order ASS separately

    (refer to index cable entry systems) "Outdoor - harsh environment and (or) outdoor"

    rated insulation voltage AC/DC 690 V current carrying capacity 63 A tightening torque for terminal 2,0 Nm

    82167

    125

  • 67

    DK Cable Junction Boxes Weatherproof, for Outdoor Installation Cable Entry via Metric Knockouts

    KF 5255

    Wall16

    118 8

    10-25 mm, Cu 3~

    with terminals 5-pole per pole 6 x 10 mm sol, 4 x 16 mm s, 4 x 25 mm s,

    2 x 35 mm s cable entry via knockouts, order ASS separately

    (refer to index cable entry systems) "Outdoor - harsh environment and (or) outdoor"

    rated insulation voltage AC/DC 690 V current carrying capacity 102 A tightening torque for terminal 3,0 Nm

    98

    160

    200

    KF 5355

    Wall15

    1513 13

    16-35 mm, Cu 3~

    with terminals 5-pole per pole 6 x 16 mm s, 4 x 25 mm s, 4 x 35 mm s,

    2 x 50 mm s cable entry via knockouts, order ASS separately

    (refer to index cable entry systems) "Outdoor - harsh environment and (or) outdoor"

    rated insulation voltage AC/DC 690 V current carrying capacity 125 A tightening torque for terminal 12,0 Nm

    117

    260

    210

    KF 5505

    Wall12

    1217 17

    16-50 mm, Cu 3~

    with terminals 5-pole per pole 6 x 16 mm s, 4 x 25 mm s, 4 x 35 mm s,

    4 x 50 mm s cable entry via knockouts, order ASS separately

    (refer to index cable entry systems) "Outdoor - harsh environment and (or) outdoor"

    rated insulation voltage AC/DC 690 V current carrying capacity 150 A tightening torque for terminal 12,0 Nm

    310

    210 117

  • 68

    DK Cable Junction Boxes Weatherproof, for Outdoor Installation Cable Entry via Metric Knockouts

    KF 5020

    Wall

    3

    13 3

    without terminals cable entry via knockouts, order ASS separately

    (refer to index cable entry systems) "Outdoor - harsh environment and (or) outdoor"

    5388

    88

    KF 5040

    Wall

    4

    24 4

    without terminals cable entry via knockouts, order ASS separately

    (refer to index cable entry systems) "Outdoor - harsh environment and (or) outdoor"

    98 61

    98

    KF 5060

    Wall10

    106 5

    without terminals cable entry via knockouts, order ASS separately

    (refer to index cable entry systems) "Outdoor - harsh environment and (or) outdoor"

    139

    119

    70

    KF 5100

    Wall14

    106 6

    without terminals cable entry via knockouts, order ASS separately

    (refer to index cable entry systems) "Outdoor - harsh environment and (or) outdoor"

    82167

    125

    KF 5250

    Wall16

    118 8

    without terminals cable entry via knockouts, order ASS separately

    (refer to index cable entry systems) "Outdoor - harsh environment and (or) outdoor"

    98

    160

    200

  • 69

    DK Cable Junction Boxes Weatherproof, for Outdoor Installation Cable Entry via Metric Knockouts

    KF 5350

    Wall13

    1315 15

    without terminals cable entry via knockouts, order ASS separately

    (refer to index cable entry systems) "Outdoor - harsh environment and (or) outdoor"

    117260

    210

    KF 5500

    Wall12

    1217 17

    without terminals cable entry via knockouts, order ASS separately

    (refer to index cable entry systems) "Outdoor - harsh environment and (or) outdoor"

    310

    210 117

  • 70

    DK Cable Junction Boxes Weatherproof, for Outdoor Installation Box Walls without Knockouts

    Cable entries can be drilled individually Stainless steel cover screws with quick fastening metric thread. Reducing cover xing time.

    Labelling system for circuit description. Label template on the Internet at

    www.hensel-electric.de - in the Downloads area.

    Burning behaviour:Glow-wire test 960 C according to IEC 60 695-2-11, UL Subject 94: V-0 ame-retardant, self-extinguishing

  • 71

    DK Cable Junction Boxes Weatherproof, for Outdoor Installation Box Walls without Knockouts

    KF 8020

    without terminals box walls without knockouts wall surface can be drilled individually for cable entry max. M 20 "Outdoor - harsh environment and (or) outdoor"

    wall thickness of the bottom part 2,3 mm

    5388

    88

    KF 8040

    without terminals box walls without knockouts wall surface can be drilled individually for cable entry max. M 20 "Outdoor - harsh environment and (or) outdoor"

    wall thickness of the bottom part 2,3 mm

    98 58

    98

    KF 8060

    without terminals box walls without knockouts wall surface can be drilled individually for cable entry max. M 32 "Outdoor - harsh environment and (or) outdoor"

    wall thickness of the bottom part 2,6 mm

    139

    119

    70

    KF 8100

    without terminals box walls without knockouts wall surface can be drilled individually for cable entry max. M 32 "Outdoor - harsh environment and (or) outdoor"

    wall thickness of the bottom part 2,8 mm

    82167

    125

  • 72

    DK Cable Junction Boxes Weatherproof, for Outdoor Installation Box Walls without Knockouts

    KF 8250

    without terminals box walls without knockouts wall surface can be drilled individually for cable entry max. M 40 "Outdoor - harsh environment and (or) outdoor"

    wall thickness of the bottom part 3 mm

    98

    160

    200

    KF 8350

    without terminals box walls without knockouts wall surface can be drilled individually for cable entry max. M 50 "Outdoor - harsh environment and (or) outdoor"

    wall thickness of the bottom part 3 mm

    117260

    210

    KF 8500

    without terminals box walls without knockouts wall surface can be drilled individually for cable entry max. M 50 "Outdoor - harsh environment and (or) outdoor"

    wall thickness of the bottom part 3 mm

    310

    210 117

  • 73

    DK Cable Junction Boxes Weatherproof, for Outdoor Installation Box Walls without Knockouts

    KF 4020

    without terminals box walls without knockouts wall surface can be drilled individually for cable entry max. M 20 "Outdoor - harsh environment and (or) outdoor"

    wall thickness of the bottom part 2,3 mm

    5388

    88

    KF 4040

    without terminals box walls without knockouts wall surface can be drilled individually for cable entry max. M 20 "Outdoor - harsh environment and (or) outdoor"

    wall thickness of the bottom part 2,3 mm

    98 58

    98

    KF 4060

    without terminals box walls without knockouts wall surface can be drilled individually for cable entry max. M 32 "Outdoor - harsh environment and (or) outdoor"

    wall thickness of the bottom part 2,6 mm

    139

    119

    70

    KF 4100

    without terminals box walls without knockouts wall surface can be drilled individually for cable entry max. M 32 "Outdoor - harsh environment and (or) outdoor"

    wall thickness of the bottom part 2,8 mm

    82167

    125

  • 74

    DK Cable Junction Boxes Weatherproof, for Outdoor Installation Box Walls without Knockouts

    KF 4250

    without terminals box walls without knockouts wall surface can be drilled individually for cable entry max. M 40 "Outdoor - harsh environment and (or) outdoor"

    wall thickness of the bottom part 3 mm

    98

    160

    200

    KF 4350

    without terminals box walls without knockouts wall surface can be drilled individually for cable entry max. M 50 "Outdoor - harsh environment and (or) outdoor"

    wall thickness of the bottom part 3 mm

    117260

    210

    KF 4500

    without terminals box walls without knockouts wall surface can be drilled individually for cable entry max. M 50 "Outdoor - harsh environment and (or) outdoor"

    wall thickness of the bottom part 3 mm

    310

    210 117

  • 75

    Stainless steel cover screws with quick fastening metric thread. Reducing cover xing time.

    Labelling system for circuit description. Label template on the Internet at

    www.hensel-electric.de - in the Downloads area.

    Burning behaviour:Glow-wire test 960 C according to IEC 60 695-2-11, UL Subject 94: V-0 ame-retardant, self-extinguishing

    DK Cable Junction Boxes Weatherproof, for Outdoor InstallationApproved for United States and Canada (UL/CSA)Box Walls without Knockouts

    Cable junction boxes with external brackets made of stainless steel.

    Cable entries can be drilled individually.

    Approved for United States and Canada

  • 76

    DK Cable Junction Boxes Weatherproof, for Outdoor InstallationApproved for United States and Canada (UL/CSA)Box Walls without Knockouts

    KF 7020

    without terminals with UL/CSA approval box walls without knockouts wall surface can be drilled individually for cable entry M 20,

    NPT 3/8" and NPT 1/2"

    wall thickness of the bottom part 2,3 mm external brackets 2

    5388

    88

    KF 7040

    without terminals with UL/CSA approval box walls without knockouts wall surface can be drilled individually for cable entry M 20,

    NPT 3/8" and NPT 1/2"

    wall thickness of the bottom part 2,3 mm external brackets 2

    98 58

    98

    KF 7060

    without terminals with UL/CSA approval box walls without knockouts wall surface can be drilled individually for cable entry M 20/25/32,

    NPT 3/8", NPT 1/2" and NPT 3/4"

    wall thickness of the bottom part 2,6 mm external brackets 2

    139

    119

    70

    KF 7100

    without terminals with UL/CSA approval box walls without knockouts wall surface can be drilled individually for cable entry M 20/25/32,

    NPT 3/8", NPT 1/2", NPT 3/4" and 1"

    wall thickness of the bottom part 2,8 mm external brackets 2

    82167

    125

  • 77

    DK Cable Junction Boxes Weatherproof, for Outdoor InstallationApproved for United States and Canada (UL/CSA)Box Walls without Knockouts

    KF 7250

    without terminals with UL/CSA approval box walls without knockouts wall surface can be drilled individually for cable entry M 20/25/32,

    NPT 3/8", NPT 1/2", NPT 3/4" and 1"

    wall thickness of the bottom part 3 mm external brackets 4

    98

    160

    200

  • 78

    DK Cable Junction Boxes Waterproof , for Encapsulating

    Cable junction boxes for encapsulating In case of re-installation or testing the sealing compound can be removed easily

    Stainless steel cover screws with quick fastening metric thread. Reducing cover xing time.

    Scope of application:Ground level installations

    Scope of application:Pump shafts

    Scope of application:Flood areas close to rivers orunprotected outdoor installations which are in close proximity to the ground

    The ingress of water and formation of condensation are completely prevented.The sealing compound can be easily removed for subsequent installations or inspections.

  • 79

    DK Cable Junction Boxes Waterproof , for Encapsulating

    Permanent waterproof

    connection -

    Cable junction boxes

    for encapsulating

    in accordance with

    DIN VDE V 0606-22-100

    Time and time again, electricians come across installation envi-ronments whereby the ingress of water into an enclosure must be safely excluded. Even enclo-sures which have a high degree of protection cannot guarantee this. The IP degree of protection allows the ingress of non-harmful quantities of water in the interior of an enclosure.

    Under extreme environmental conditions, for example, the ac-cumulation of condensation may result in damage to the electrical installation or devices or cause these to malfunction.

    Ventilation measures will often suffice to prevent harmful con-densation from forming.

    In many cases, however, ventila-tion is not possible, e.g. because the cable junction boxes are in-stalled close to rivers and water could enter through the vent holes.

    Which applications require waterproof connections?

    Pump shafts Ground-level installation ducts

    in outdoor areas

    Flood areas close to rivers Unprotected outdoor instal-

    lations which are in close proximity to the ground

    Why is the IP degree of pro-tection alone not sufficient?

    All degrees of protection al-lowed Water ingress

    The accumulation of con-densation cannot always be prevented

    Ventilation measures cannot be applied in all environments

    The waterproof connection

    Sealing the cable junction boxes with a fast setting, permanently elastic sealing compound com-pletely the ingress of water and the

    excludes forming of condensation.

    The sealing compound fea-tures outstanding insula-tion properties. As the com-pound is transparent, it is possible for visual inspections of the installation to be carried out at any time. The durable elastic material is self-sealing, therefore it is also easy for the electrical con-nections to b