00919922.pdf
-
Upload
dmsoares1989 -
Category
Documents
-
view
217 -
download
0
Transcript of 00919922.pdf
-
8/11/2019 00919922.pdf
1/9
82
IEEE Transactions on Dielectrics and Electrical Insula ion
Vol 8 No 2 April 2001
FRP Rods for Brittle Fracture Resistant
Composite Insulators
M. Kuhl
CeramTecAG
Wunsiedel, Germany
A B S T R A C T
Brittle fracture of fiberglas reinforced polymer FRP) rods can lead to mechanical failures of
composite insulators even at low mechanical lo ads durin g operational service. Although th is
fact has been known for
20
years, it may still be a problem in some designs of composite
insulators at the present time. In order to find counterm easures against brittle fracture,
a
study
was carried out in the early eighties. It turned ou t that brittle fracture is a problem
of
FR P
material and that material compositions exist, resistant to brittle fracture. A brittle fracture
resistant
FRP
rod introduced 1983 n on e particular design of comp osite insulators resulted i n
a
15
year excellent service performance. This st udy deals w ith details of brittle fracture of
F R P
rods. Test setups were established to induce brittle fracture artificially It was realized that
brittle fracture is some kin d of stress corrosion related to the composition of th e
FRP
material.
A broad variety of
FRP
materials was evaluated, showin g the influence of the components of
FRP material on the brittle fracture behavior of
FRP
rods as well as the effects of dif ferent
manufa cturing processes. The comp ositions of brittle fracture resistant FRP
rods
are disclosed.
Th e results from artificial testing are compared with b rittle fracture of FRP rods that occurred
in com posite insulators in operational service. Although no quantitative correlation could b e
established, th e trend concerning th e material behavior of
FRP
rods is similar.
1 INTRODUCTION
OMPOSITE
insulators consist of a glass fiber reinforced plastic rod
C FRP
rod), a shed housing made of polymeric material covering the
FRP rod a nd metal end fittings attached to the ends of the FRP rod. The
housing protects the FRP rod from weathering and supplies the nec-
essary creepage distance. This composite structure consists of several
interfaces which have to be designed and manufactured properly in or-
der to avoid ingress
of
moisture, and pollutants from the surrounding
environment into the interior of the composite structure. Laboratory
tests carried ou t more than two decades ago revealed some typical elec-
trical and mechanical failures of composite ins ulator s of early designs
[l].However, in the late seventies a new kind of mechanical failure oc-
curred on
FRP
rods of composite insulators installed in
HV
lines
[Z-51,
never seen before dur ing laboratory testing. This kind of mechanical
failure is called 'brittle fracture' of a
FRP
rod d ue to the unusual fracture
pattern of the fracture area
of
the concerned FRP rods. The failures oc-
curred a t very low nominal operational mechanical service loads
[3,4].
The outer features of the fracture areas ar e characterized by a razor cut
fracture surface running perpendicular to the axis of the
FRP
rod [6]. In
those days it was thought that brittle fracture was initiated by ingress of
chemicals such as dilute acids into the composite structure [Z
4/51,
The
improvements carried out on composite insulators in the last decades
led to elastomeric housing materials such as silicone rubber and ethy-
lene propylene diene monomer
(EPDM)
rubber an d to better interfaces
between the different materials of the composite components. New de-
veloped test standards
[7,8]
are the tools to check the integrity of the
composite structure.
No broadly accepted test exists
so
far to check the composite struc-
ture regarding brittle fracture of the
FRP
rod. This may be based on
the fact that brittle fractu re occurred on a small number of insula tors
under operational service conditions in comparison to the big numb er
of installed composite insulators . In spite of this fact, a mechanical
failure of an overhead transmission insulator may cause line dropp ing
which results in an outage of the transmission line. Aging of composite
insulators, and in particular, aging
of
the interfaces of the composite
structure, may be one
of
the reasons for the infrequent occurrence of
brittle fracture. M anufacturing defects on a small number of insulato rs
may contribute to the failures as well as specific environmen ts. These
conditions cannot be simulated in a design test performed
on
a small
number of test specimens. The only possibility to eliminate brittle frac-
ture of composite insulators at all was considered by using a brittle
fracture resistant
FRP
rod as member of the composite structure. The
result of this stud y has led to such a rod. It was introduced in the man-
ufacturing of composite insulators consisting of a housin g mad e of high
temperature vulcanized
(HTV)
silicone rubber in
1983.
Such insulators
1070-9878111 $3.00
001 IEEE
-
8/11/2019 00919922.pdf
2/9
IEEE Transactions on Dielectrics and Electrical Insulation Vol. No April 2001
183
have been manufactured in large quantities d uring the last 15 years.
The number of brittle fractures from those insulators is zero.
It is interesting to note that for several designs of other composite
insulator types brittle fracture is still a cur ren t problem [9-121. Most of
the concerned insulators failed in the USA because there is the largest
market for composite insulators [H I.
Brittle fractures on
FRP
rods can be traced
to
stress corrosion of
E-
glass (electrical grade ) filaments. S tress corrosion involves an ion ex-
change mechanism. Sodium ions with a large ion radius are replaced
by hyd rogen ions with small radius, resulting in an increase of stress
in the g lass surface of the filaments [13]. E-glass filaments build up spi-
ral flaws on their surfaces after immersion in diluted acids [6,14,15].
The flaws in the filaments initiate the failure of the composite material
which can be described by the mechanism of fracture mechanics [16].
In order
to
improve the brittleness of
FRP
material, several measures
were proposed. Gel coats can be applie d on the surface. The correct
choice of the matrix resin as well as the use of an acid resistant glass
composition for the glass filaments may be successful [17,18].
2
EXPERIMENTAL
All HV insulators under operational service conditions ar e stressed
frequently by electrical surface discharges when the surfaces of the in-
sulators are polluted and humidity penetrates the pollution. Already
Cave ndish found in 1784 the generation of nitric oxides and nitric acid
by using electrical discharges in nitrogen and oxygen, while Birkeland
and Eyde fo und an industrial process proposed in 1905 for generating
nitric acid by using electrical discharges in hum id ai r [19]. It was very
likely to assume that the electrical discharges on
HV
devices may also
generate nitric oxides and derivatives such as nitric acid. In order to
show that nitric acid can be generated from power frequency voltage in
presence of air and humidity, a device according to Figure 1was built.
The electrical discharge was carried out at 25 kV,,, (50 Hz ). Distilled
water was fed through the filter paper wra pped around the energized
electrode at a flow rate of 10 cm3/h . After a time spa n of 1h the con-
tent of the water collector had a pH value of 2.9, and 2.52 mg nitrogen
was measured. More evidence for the presence of nitric acid and ni-
tric oxides and their derivatives were found on the surfaces of polluted
insulators from experiments and tests. 110 kV silicone composite insu-
lators showed 4 to 5 nitrogen in the pollution after 5 yr service. Salt
was taken from the surface of a silicone composite insulator after pass-
ing the 1000 h salt fog test described in [7]. The nitrogen content in
the salt amounted to 2.5%. A huge pollution content of nitrogen was
reported from dc insulators on the pacific coast of California [20]. The
autho rs of [20] considered that the nitrogen in the pollu tion could be
traced back to agricultural products and fertilizers.
Mechanical failures of test specimens from stress corrosion implies
the presence of two components, mechanical stress and simultaneous
application of an environmental medium such as nitric acid. To check
FRP
rods concerning their stress resistance corrosion, some have sug-
gested the use
of
bending stress. Experiments carried out by the author
under ben ding stress showed that after crack initiation, delamination
occurred lengthwise in
FRP
rods to different extents. The acid can run
out and th e stress cannot be held constant du e to the delamination in
the composite material. More reproducible results were obtained from
Water f l o w r a t e 10cm3/h
R e s u l t 2 52mg N/h
pH
2.9
Figure 1
Device for generating nitric acid at power frequency volt-
age 25
kV
50 Hz.
1: steel bar,
2:
supporter,
3:
insulated copper wire 1.5
mm diameter, 4: filter paper wra pped around, 5 : holder (acrylic glass),
6: PVC tube
OD
63 mm, ID 51 mm, 7: silver paint (ground electrode),
8: water supply (de-ionized water), 9: acid collector.
test specimens loaded under tension. The test arrangement for testing
FRP rods under tensile loads is shown in Figure 2. The arrangement
has the adv antage that assembled FRP rods can be evaluated. FRP rods
clamped into the interior of the end fittings may undergo higher me-
chanical stresses in the end fittings as can be expected for the free length
of the rods between the end fitti ngs. In this way the influence of the
stress in the end fittings can be estimated. Diluted nitric acid of 1 n
H N0 3 were chosen for simultaneous application of the env ironmental
medium
1
n is 63 g concentrated HN 03 added
to
937 g water).
I
i i
Figure
2
Test arrangement for the evaluation
of
brittleness
of
F R P
rods (tensile load an d 1
n HN03,
simultaneously). Procedure I End
fittings under acid. Procedure I1Infus ion of
HN03
rocedure
111
Acid
on the free rod length.
Experiments with the three test arrangements shown in Figure 2
resulted in rejecting Procedure I because the acid attacked the metal
of the end fittings in such a way that the acidity suffered and led to
unreliable test results. The best reproductio n of test results could be
-
8/11/2019 00919922.pdf
3/9
184
Table 1 Epoxy resins and hardeners used to manufacture the test
Type
F
0164
X18
331
XlOO
MTHPA
HHPA
PSA mixt
1102
4,4 MDA
DDS
MNA
EH 640
specimens.
Trade name
Araldite F
Ruetapox 0164
Lekutherm X18
D. E. R. 331
Lekutherm XlOO
Ruetapox HX
Araldite 907
Araldite 905
Vers. Prod.1102
Araldite 972
Araldite 976
Araldite 906
VersamidEH 640
obtained with Procedure 111, because there is no metal involved in the
chemical stability of the diluted acid.
To manufacture
FRP
rods for this study, two manufacturing meth-
ods were used. For variation
of
different glass fibers a discontinuous
manufacturing pro cedure ha s been established. The glass fibers were
woun d up on a rotating wooden sheet forming loops of glass rovings
of a predetermined number. The loops were impregnated with heated
resin mixture in
a
tub and then pulled in steel tubes for crosslinking at
elevated temperatures. For the variation of different resin mixtures, a
continuous protrusion process was used. In this process it was simple
to
replace a resin mixture by another mixture. The glass content of the
FRP rods from both manufacturing procedures am ounted to 63 to 69% of
weight an d the mechanical properties of the rods from both procedures
were most equal when the same components were used. All FRP rods
were manufactured from an epoxy matrix resin because epoxy resin is
the best resin for FRP rods used in
HV
application d ue to their excellent
mechanical and electrical properties, although remarkable differences
exist within epoxies. The resin mixtures were prepared in ratios given
by the manufacturer of the resin mixtures. The curing state of the test
specimens concerned a curing state at 130C for
1 0
h, when no other
treatment is mentioned.
Table 1 ists the applied epoxy resins and hardeners. The resins F,
0164 and 331 are aromatic diglycidylether (bisphenol A base) with an
epoxy equivalent of
90. X18
is a distilled version of the epoxy resin
mentioned before (high purit y),
XlOO
is
a
cycloaliphatic diglycidylester
(HHPA base) with an epoxy equivalent of 185. The hardeners MTHPA,
PSA mixt, 1102 and MNA are liquid at room temperature. The harden-
ers HHPA, 4.4 MDA and
DDS
are solid at room temperature. Hardener
EH
640 is a 4.4 MDA diluted in 30% glycolene.
The glass fibers used consisted of either assembled or direct rovings
in 2400 or 4800 g/km. They were supplied f rom the companies Silenka,
PPG (Pittsburgh), OCF (Owens Corning), Bayer AG, Ahlstrom, Norsk
(Norsk Fiberglass), Vitrofil S.p.A., Gevetex (Stratifil), and were used as
delivered.
All test specimens were tested under constant static load as show n
in Figure 3. After loading diluted nitric acid of a concentration
of
1n
was applied immediately and the time to break was recorded by an
electrical clock connected via movement of the lever arm of the test
Kuhl:
FRP Rods
fo r Composite Insulators
setup indicating hours, minu tes and seconds. The tests were carried
out indoors at room temperature.
sample
Figure 3
Test setup to cause
artificial
brittle fractures on assembled
FRP
rods.
3
FEATURESOF BRITTLE
FRACTURE
The first brittle fracture on a 420 kV silicone rubber insulator oc-
curred in 1978 [ 5 ]on a 24 mm FRP rod assembled with en d fittings with
a wide cleavage (Figure 4). The sealing of the end fitting was opened,
so that chemicals could enter the interior of the end fitting.
Figure
4
Brittle fracture
of a
420 kV silicone rubber suspension in-
sulator after 3 yr of service.
The broken insulator was part of
a
double suspension insulator
string. The parallel insulator held the line and was brought down for
evaluation purposes. Mechanical tests carried out on this insulator re-
sulted in no reduction of the ultimate tensile load . Brittle fractu re can be
simulated by means of test Procedure I1 (Figure 2). Both fractures, the
natur al brittle fracture (Figure 4) as well as th e artificial brittle fracture
(Figure
5 )
show fracture surfaces arranged perpendicular to the axis
of the FRP rods and characteristic patterns of stress corrosion fractures
which cannot be simulated any other way.
Several tests performed with cyclic loads on test specimens without
simultaneous application of acid resulted in different fracture patterns.
Hence, they were obtained by much higher l oads and required longer
times to failure than necessary for stress corrosion failure.
-
8/11/2019 00919922.pdf
4/9
IEEE Transactions on Dielectrics and Electrical Insulation Vol 8 No 2 April 2001
I85
Composition
Glass
B 2 0 3 YO
Silenka
6.7
Silenka
5.1
PPG
4.9
Bayer 4.8
Vitrofil
4.6
OCF8 9
4 3
Ahlstrom
4 0
OCF424 3.3
Norsk
2.6
Norsk ECR 18720
Figure 5 Brittle fracture
of
a test specimen according
to
test Proce-
dure
11.
The experience with brittle fracture of silicone insulators showed
that in every case failure of the sealing between the housing and at
least one of the end fittings was invo lved. Brittle fractures on the free
length of the
F R P
rod had never been found for this particular insulator
design. Tests carried out on test specimen with and without silicone
sheath according to Figure 2, test Procedure 111, found that artificial
brittle fractures of the
FRP
rods can be obtained only from naked rods.
4
ARTIFICIAL BRITTLE
FRACTURES
4.1 INFLUENCE OF NOMINAL
TENSILE
STRESS
The results shown in this study refer to nominal tensile stresses.
They are defined as those tensile stresses calculated from the applied
static tensile load divide d by the unloa ded cross section of the
FRP
rod.
This also is applicable for the e nd fittings; however, it is a stress indica-
tion only and does not specify any real stresses quantitatively.
The general characteristics of brittle fracture of FRP rods obtained
from nomin al tensile stress and simultaneous application of
1
n nitric
acid is shown in Figure 6.
These results were obtained from
24
mm rods made of E-glass in
postcured condition (180C for 16 h). In Figure 6curve1envelops the
most resistant E-glass composition (glass type OCF 859/resin type
BAY
XlOO/HHPA) and cu rve 2 envelo ps one of the most susceptible E-glass
composition (glass type Silenka/resin type BAK/M THP A). oth curves
represent artifici al brittl e fractures obtained from the free length of FRP
rods. Curve 3 envelops failures of FRP rods within end fittings designed
as wide cleavage of the cone wedge type. It can be seen that the stress
caused by end fittings can lead to a drastic reduction of the time to
failure
(FRP
composition from curve 2). The section between curves
1
and 2 also represents the load time characteristics of all evaluated FRP
rods from 16 to 37 mm m ade of E-glass. It can be seen that considerable
differences exist regard ing the brittleness of FRP rods mad e of E-glass
caused by stress corrosion. For all
FRP
rods ma de of E-glass,a load level
exists indicating that at loads below this level brittle fracture does not
occur. For the free length of the rods, the level may exist at 60 MPa and
for the rod ends at 15 MPa under the above described test parameters.
10
1
1000
io000 i ooooa
Breaking
Time
[minutes]
Figure
6
Load time characteristics of brittle fractures of F R P rods
24 mm
diameter. Curves 1 and
2:
Test Procedure 111, Curve
3:
Test
Procedure
11,
wide cleavage.
Table 2 Variation
of
glass fibers. Breaking time (min)
of
24 m m FR P
rods at nominal stress
of 77
MPa, test Procedure
11,
end fittings
with
wide cleavage.
[ydrolysis
:ant
3
61
34
51
114
>18720
ptible
U
Cured
617
40
1
~
5821
'ostcurec
508
180
2982
levels can be assumed at operational service. From this point of view
it is most likely that brittle fracture may occur on composite insulators
under operational service conditions if the FRP rod is manufactured
from E-glass.
4.2
BRITTLE FRACTURE
RESISTANT FRP
RODS
The brittleness of
FRP
rods caused by stress corrosion can be influ-
enced by the glass composition as well as by the epoxy resin matrix and
the interface between glass fibers and matrix.
Table 2shows several parameters influencing the brittleness of
FRP
rods. As can be seen, the boron content of the glass fibers is of great
importance. Boron free glasses
B203
content 0.15%) result in brittle
fracture resistant FRP rods. A part from the boron free glass type Norsk
ECR
mentioned inTable
2
there exist some more boron-free glass fibers
as Stratifil (Gevetex), NT712 (PPG) and S2 (OCF). 24 mm FRP rods made
of
these glass fibers show the same or even better brittle fracture resis-
tance as found from Norsk ECR. Although boron free glass fibers used
in
FRP
rods result in brittle fractu re resistant
FRP
ods, the role of boro n
oxide in the glass composition is still unclear.
-
8/11/2019 00919922.pdf
5/9
186
Resin Hardener Break time (min)
type cured postcured
F HHPA
333 2 5 3
0164 HHPA
368
118
X18 HHPA 416 106
F PSAmix 661 220
0164 PSAmix
551
231
F 1102 217 79
F
HHPA 333 263
F THPA 374 309
F 4,4MDA 459
F
EH640
>1300*
F DDS
67
17
Kuhl:FRP
Rods for
Composite Insulators
Resin i
characteristic
bisph.Amixture
bi5ph.A regular
bisph.Adistilled
9
6
8
10
15
30
50
glass fibers itself. For the curing state of the matrix and the interface,
some effects can be assumed. Thus, some evaluations
on
the postcuring
state of epoxy matrix systems were carried out. Test specimens were
molded of various epoxy matrix systems and treated with various cur-
ing states. The test specimens were tested for bending strength and
deflection [21], tensile strength and elongation [22], Youngs modulus
[22] and density [23]. The curing state was determined by measuring
the softening temperature of the resin according to Martens [24],called
T temperature (Martins temperature).
3 pt
bending Def lect ion
Tensile
Pa
O L
O 100
120
Figure
7 Properties of an epoxy matrix depending on the softening
temperature T . System DOW331/MNA.
Figure 7shows the results obtained from the System 331/MNA be-
cause this system exhibits the post curing effect most impressively
As
known from cast resin, the mechanical prope rties of epoxy resin
sys-
tems improve with increasing curing state. This is also the case for
the system 331/MNA, One can assume that the increasing curing state
means an increasing density of crosslinking what results in a higher
stiffness of the material a nd in a more dense material,
Figure 7shows that these assumptions a re incorrect, It was found
that all evaluated epoxy systems showed a decreasing Youngs Modu-
lus and a decreasing density w ith increasing curing state to a different
extent. Curing and postcuring of epoxy matrixes mean that the matrix
duri ng crosslinking is subjected to a swelling effect [25,26]. In case of
reinforced epoxy
it
can be assumed that a compression force acts an
the interface between the
glass
fibers and the epoxy matrix. Postcur.
ing means also tha t the finish layer on the surface of the gla ss fibers
is hardening . Both effects result in propagation of cracks due to stress
corrosion that is not stopped at the interface, and that time to failure
due to stress corrosion can be expected earlier than in
the
case of
non.
postcured systems.
Figure
8
shows the scattering of time to fililure of the most brittle PRP
rod found d uring this stud y It was also found that the more brittle a PRP
-
8/11/2019 00919922.pdf
6/9
IEEE Transactions
on
Dielectrics and Electrical Insulation
Vol.8
No
2 April 2001
187
1 2
3
4 5
6
7
8
9 1 0 1 1
Rod No.
Figure 8 Scattering of time
to
failure.
FRP
rod
37
mm ystem DOW
331/MNA/PPG
E-glass, test Procedure I1 (wide cleavage) nominal
stress77
MPa.
rod system is, the more is the scattering of the test results. Apar t from
that, the results from the end fittings (test Procedure 11) scatter more
than from free length of
FRP
rods ( test Procedure 111). Test Procedure 111
may be
a
tool to check the brittleness of
FRP
rods in general. The test
is easy to perform in the test ar rangement shown in Figure
3
with test
specimens show n in Figure 2 (Procedure 111). The acid container made
of polyethylene should have such a size that the FRP rod is surrounded
by liquid thickness not
3
1cm and a liquid level of
> 4
cm. The lower
end of the acid container ha s to be attached and sealed to the surface of
the FR P rod in ord er to prevent the acid from coming in contact with the
lower end fitting of the FRP rod. The acid container should be covered
to prevent evaporation of the liquid >5 of its volume du ring the test
period,
The test specimen prepared this way can be loaded in the test setup
shown in Figure 3with a load high enough to cause a tensile stress of
340 MPa with in the cross section of the free length of the FRP rod and
maintain this stress for
a
time span of 96 h. Immediately after app lying
the load,
a
nitric acid of a concentration of
1
n
HN03
can be poured
into the acid container. The acid must not come into contact with the
end fittings of the test specimen. Brittle fracture resistant
FRP
rods can
be realized, if no fracture of the
FRP
rod occurs during the test period
of
96 h [14], see also Figure 6.
Brittle fracture
of FR P
rods made of E-glass can be initiated by any
other diluted acid with pH values t 4 . Tests performed with strong
organic acids (checked were formic acid, chlorinated acetic acid and ox-
alic acid) showed that these acids also can attack FRP rods. On the other
hand, FRP rods made of boron-free
glass
fibers withstood all diluted
acids. Water did not affect any of the eva luated
FRP
rod systems.
Glass monofilaments may contain tiny capillaries related to gase-
ous
bubbles in the molten glass during manufacturing of the monofila-
ments. This was discovered in the seventies for E-glass. Some interest-
ing effects concerning the electrical performance of
FRP
rods containing
capillaries were foun d by the author. Test standards were developed in
order
to
quan tify capillarity fo r the selection of
FRP
rods suitable for
HV
applications. A link between capillarity and bri ttle fracture of
FRP
rods
could not be estab lished , Today capillarity of FRP rods is not
a
problem
anymore. Both E-glass as well as boron-free glass exist that are nearly
fre e from capillaries.
4.3
CONCLUSIONS FROM
ARTIFICIAL BRITTLE
FRACTURE
Brittle fracture of
FRP
rods made of E-glass can be simulated by ap-
plying tensile stress and simultaneous application of diluted acids. The
fracture patte rns of artificial brittle fractures are very close to the frac-
ture patterns of brittle fractures of broken composite insulators out of
service. Tests conducted with test specimens under static and dynamic
loads without application of acid led to fracture patterns not compara-
ble
to
brittle fracture patterns. Brittle fracture of FRP rods occurred in
service
at
load levels far lower than the ultimate failing load of com-
posite insulators. This is consistent with load levels found for artificial
brittle fractures simulated with tensile stress and simultaneous applica-
tion of dilute d acids. These facts have led to the conclusion that brittle
fractures of composite insulators in service are the result of stress cor-
rosion, initiated by diluted acid at the surface of E-glass fibers under
tensile stress.
Brittle fracture of composite in sulato rs can be avoided by using FRP
rods made of boron-free glass fibers. This class
of
glass fibers is re-
sistant to acids and stress corrosion at load levels known from service
experience [14].
In general brittle fracture failure of
FR P
rods made of E-glass can
vary in a wide span of time. The fractures are subjected to a load time
characteristic depending on the applied tensile stress and the p H value
of the corrosive medium. The nominal stress can be enhanced by the
design of the end fittings at the end s of the FRP rods. Other general
factors influencing the brittle fracture failures are the boron content of
the glass fibers, the toughness of the resin matrix and the curing state
of the resin matrix.
These results obtained from artificia l testing of FRP rods made of E-
glass showed tha t the choice of the m aterial components (glass, resin,
hardener) can also lead to an unpredictable brittle fracture behavior,
In the frame of this stud y 62 variations of FRP rods have been evalu-
ated. Although some general trend s resulting from the
FRP
material
components could be found, there were some results which could not
be explained, such as shown in Table 2for the glass OCF 859 in combi-
nation with two different resins.
5 NATURAL BRITTLE
5 1 FRP RODS EXPOSED
FRACTURES
OUTDOORS
It is common practice for manufacturers of composite insulators to
evaluate the load time characteristic
of
FRP
rods under static loads
as
described in
[7].
In most cases it takes several years
to
obtain a load
time curve for a particular assembled
FRP
rod, Up to now, nothing is
specified about the condition of test specimens for the realization of the
load time curves. Knowing the impact of postcuring on brittle fractures,
24 mm
F R P
rods were exposed outdoors under static loads in a test
device similar to Figure 3.Rods with and without a sheath of silicone
elastomer in postcured condition (180C for 16 h) were tested.
-
8/11/2019 00919922.pdf
7/9
288
t
Y
3.5
6
9
14
Kuhl: FRP Rods for Composite Insulators
Observation
cracks and
delamination on
FRP
rod surfaces.
less surface erosion
brittle fracture on
free
F R P
rod length
surface erosion
F R P
rod surface
strongly eroded
1crack near end
fitting. minor
erosion
During the first three years of o utdoor testing
no
difference could
be observed between test specimens with and witho ut silicone sheath.
The obtained load time curves were similar. However, after three years
of lo ading visual in spection of th e naked FRP rods revea led some differ-
ences between
F R P
rods of differen t compositions as well
as
differences
between naked and sheathed rods. While the sheathed rods showed
minor influence of w eathering , all naked rods made of aromatic epoxy
systems showed strong discolo ration and stro ng erosion on their sur-
faces. A layer of loose gla ss fibers covered th e surfaces of the rods
due to ero sion of t he arom atic epoxy matrix; the more, the longer the
time of exposure . The rods compo sed from cycloaliphatic epoxy matrix
showed far less surface erosion for the same exposu re time.
Table 4shows the most interesting results from24 mm rods exposed
outdoor s under static loads in the plant location of CeramTec AG. The
environm ent of this plant ca n be characte rized by a relatively clean at-
mosphere,
M
500 m above sea level.
A
lot of forests and agriculture
domina te this area of m oderate clima te. The most interesting observa-
tion made was the fact that one brittle fracture occurred on one aromatic
epoxy system and rods from other systems showed some cracks run-
ning perp endicular to the ro d axis on its free length like a start of brittle
fracture.
In Table 4are listed also three epoxy systems and their time to break
from artificial brittle fractur e testing with nitric acid. There might be
a correlatio n between artificial brittle fracture testing and those obser-
vations made in outdoor exposure of
FRP
rods. Questions arose why
the aromatic F system from Table 4did not brea k. Microscopic evalua-
tion of the sur face of those r ods revealed s ome differences to the 0164
system. U nder the microscope the same cracks could be seen
on
the F
system
as
seen macroscopically on t he 0164 system; however, the de-
gree of matrix erosion due to weatherin g on the F system exceeded by
far the erosion seen on the 0164 system. It can be a ssumed th at crack
propag ation du e to brittle fracture caused by stress corrosion of th e
glass fibers and the speed of matrix erosion caused by wea thering are
in competition w ith each other. The high s peed of the matrix erosio n of
the F system inhibits crack propagation d ue to stress corrosi on.
The reason for brittle fractures observed on naked F R P rods exposed
outdoor s (without voltage, without acid) are still unknown. It can be ar-
gued th at diluted acid can exist in every moderate climatic atmosph ere
as
can be found in Germany. On the other hand, the evaluated epoxy
systems are mostly crosslinked with acidic hardeners. Hydrol ytic ef-
fects on the matrix system may play a role. It can also be assum ed that
the ultraviolet
UV)
part of the solar radiation may cause nitric acid for
crack initiation on the surface of FRP rods. The FRP rods covered with
silicone elastomer did not show any signs of brittle fra cture. For the
naked rods it can be concluded fromTable4that the observations made
on them follow the same trend
as
found for the results from artificial
testing.
5.2 FRACTURES ON SILICONE
COMPOSITE
NS
U LATO
R
S
Table 5lists the brittle fractu res
of
FRP
rods ma de of E-glass used in
silicone composite insulato rs from o perationa l service.
As
shown, the
majority of the broken in sulators were installed at harsh environm ental
condition s at high service voltages.
Table 4. Observations made on 24 mm F R P rods exposed outdoors
under static load. t b is the time to break under test procedure
2,
t
the exposure time under
a
tensile stress St
Matrix
0164
MTHPA
F PSA mixture
X100 HHPA
Art. test
t
MPa
6 1
102
252
217
In all cases the sealing between housi ng and the end fitting opened
and, except in one case, the live end fitting sides of the insulato rs were
involved . Brittle fracture on the free length
of
the
FRP
rods did no t occur
in contrast to what is reported in
[ 2 ]
and [ll] A corr elation between
the expected service tensile stresses and the time to f ailure could not
be found . However, 13 brittle fractur es out of 19 occurred on tension
insulators . The numb er of tension insulators in a
HV
transmissi on line
is small compared to the num ber of suspensi on insulators. In spite of
this fact brittle fracture occurred preferably on tension insulator s which
are usually more highly loaded than suspension insulators. This may
be an indication that tensile stress from service loading plays
a
role
concerning the statistical occurrence of brittle fr actures.
Table
5
pre sent s the result s of artificial testing of
FRP
rods from test
Procedure
11.
The compariso n between the time to failure from artificial
testing and from operationa l service leads to
a
similar trend concern-
ing the evaluated material composition. The resin matrix 331/MNA
combined with th e E-glass type PPG 712 was foun d to be the most
sus-
ceptible system concerning brittle fractu re during artificial testing, see
also Figure 8.
This system was also most susceptible under operational service
conditio ns. The systems 0164/MTHPA/Silenka and F/PSA mix t/OCF
859 resulted in sm all differences from artificial testing.
Under operation al service the performance of these two systems can
be considered as equal. The average time
to
failure of both systems
under operational service conditions results in 9,l years (one can also
assume that the time until ope ning of th e sealing between housing and
the end fitting is eq ual statistically). The system XlOO/HHPA/OCF859
exhibited
a
remarkable resistance
o
the occurrence of brittle fractur e in
artificial testing
as
well
as
under operational service. Although some
thousand silicone composite insulators still exist utilizing this type
of
FRP
rod in lin es up to 245 kV with end fittings of wide cleavage,
only one brittle fracture under operatio nal service conditions occurred
within a service time of more than 25 yr. Finally,
a
vast number of sili-
cone rubber insulators have been installed since 1983 utilizing
FRP
rods
containin g boron free acid resista nt glass fibers from which is k nown
the rate of brittle frac tures is zero. This fact is also consi stent with th e
resu lts of artificial testi ng.
-
8/11/2019 00919922.pdf
8/9
IEEE Transactionson Dielectrics and Electrical Insulation
Vol.
8 No 2 April 2001
Line
roltage
kV
420
420
420
420
420
420
420
123
123
420
230
420
420
420
420
123
420
420
420
15
89
String
config.
triple tension
dto
inv.V
suspens
double
tension
dto
dto
dto
double
suspens
triple tension
double
tension
double
suspens
dto
invertv
double
tension
spacer
suspens
spacer
double
tension
tension
Resin
system
11
MNA
164
MTHPA
PSA
mixt
100 HHPA
t
nounted
Y
0.08
0.08
0.4
1.3
10
10
1
6
15
12
2
g
a
ss
type
PG 712
jilenka
m
CF 859
~
Pos.
Reason
fracture fracture
life end bad sealing
groundend dto
lifeend dto
dto dto
dto dto
dto dto
dto dto
dto dto
dto dto
dto dto
dtoto
Table 5 Brittle fractures experienced on silicone composite insulators.
4
6
7
12
7
20
19
29
RP
rod
diam.
mm
37
37
37
37
24
24
24
24
24
24
24
24
24
37
37
24
24
24
37
dto dto
dto bad sealing
dto dto
dto bad sealing
dto dto
dto
dto
dto wide cleavage
range
t b
iostcurec
min
21
121
220
2982
anuf
year
979
1979
1979
1979
1981
1981
1981
1979
1979
1979
1981
~
1975
1975
1975
1975
1977
1975
1975
1976
1968
~
Env.
very severe, coast
dto
dto
dto
coastal severe
dto
dto
medium
medium
medium
rural
dto
coastal severe
severe
Alps
very severe
severe
very severe
very severe
railway
6 CONCLUSIONS
OMPOSITE
insulators installed outdoors in HV lines can suffer from
C
atastrophic mechanical failures at tensile loads far below their ul-
timate tensile strength. This fact, together with the unusual fracture
pattern of the
F R P
rods, leads to the assumption that brittle fracture of
FRP
rods is initiated by stres s corrosion. Nitric acid can be formed by
electrical discharge in hum id air and m ay hav e access to the surface of
FRP
rods.
FRP
rods have been tested artificially under tensile stress and simul-
taneous application of 1n nitric acid. The results from this testing lead
to the conclusions that brittle fracture of FRP rods
1. is
a
matter of stress corrosion,
2. follows the rules
of
fracture mechanics,
3. can be initiated by diluted acids and simultaneous application of tensile
4. is a matter
of
stress corrosion of
glass
fibers containing boron oxide
5 . can be prevented by using boron-free glass fibers.
A
broad variety of
FRP
rods made of different material components
were evaluated. It was sho wn that all E-glass fibers used in F R P rods
lead to rods susceptible to stress corrosion to different extent. Consid-
ering the para meter s of influence found, the occurrence of catastrophic
mechanical failures of composite insulators installed outdoors on H V
lines can be related to incidents and reasons:
1. Defect of the sealing between end fitting and FR P rod. Moisture pen-
etration into the inside of the end fitting with generation of an acidic
stress,
solution due
to
electrical activity (corona) in the area near the end fit-
ting. Acid attack upon non-brittle fracture resistant FRP
rods
which are
permanently under mechanical load.
2. Glass fibres used for
FRP
rods contain 8203
3. Epoxy matrix is not suitable. The main parameters that influence the
brittle fracture resistance are the curing state, the
toughness
and the
swelling characteristic of the matrix.
4. Interface between matrix and fibres is weak. Moisture in the interface,
missing coupling agents and bad sizing can lead to a weak fibre-matrix
bonding. FR P rods with weak fibre-matrix bondings are expected to be
more sensitive to brittle fracture.
It is most likely that more than one of these parameters determines
the time to failure of a particular composite insulator installed on a HV
line, as long as FRP rods are used made of
E-glass.
The brittleness of
FRP
rods can be checked simply by means of ten-
sile stress in the simultaneous presence of di luted acids ( test Proce-
dure 111). The test r esults obtained from this testing are consistent
qual-
itatively with the experience obtained from operational service of com-
posite insulators installed in outdoor
HV
lines. The use of boron-free
glass fibers in
FRP
rods have led
to
a new generation of silicone com-
posite insulators free
of
brittle fracture in 1983. This is proven by the
vast number of suc h insulators manufactured during the last
15
yr. The
number of brittle fractures from those insulators is zero.
REFERENCES
[l]G. Karady, R. Vinet and N. Souchereau, New Test Methods for Synthetic insula-
tors , CIGRE 1976 Session, paper 22-15.
-
8/11/2019 00919922.pdf
9/9
290 Kuhl:FRP
Rods
for
Composife
Insulators
[2] H. Weihe, R. E. Macey and J. I? Rynders, Field Experience and Testing of New
Insulator Types in South Africa , CIGRE 1980 session , paper 22-03.
[3] M. Cojan,
J.
Perret, C. Malaguti,
I
Nicolini, J.
S.T.
Looms and A.
W
tannet, Poly-
meric Transmission Insulators: T heir Application in France, Italy and the U K , CI-
GRE 1980 session, paper 22-10.
[4] A. Bradwell and J. C. G. Wheeler, Evaluation of Plastics Insulators for Use
on
Britis h Railways 25 kV Overhead Line Electrification , IEE Proc. Vol. 129, Pt.
B,
No.
3 May 1982, pp. 101-110.
[5] E. Bauer, H. Karner, K. H. Muller a nd
P.
Verma, Service Experi ence with the Ger-
man Composite Long Rod
Insulator
with Silicone-RubberSheds since 1967 , CIGRE
1980 session, Paper 22-11.
[6] CIGRE WG 22 43 , Guide for the Identif icatio n of Brittl e Fractu re of Compo site
Insulators FRP rod , ELECTRA
No.
143,199 2, pp. 61-69.
IEC 1109, Composite Insulators for ac Overhead L ines with a Nominal Voltage
greater t han 1000 V Definitions, Test Methods and Acceptance Criteria , 1995.
C29.
11ANSI, American National Standard for Composite Suspension Insulators
for Overhead Transmission Lines Tests , 1989.
Interview with J.
S.
T. Looms , Insulator News and Market Report Vol. 2, No. 1,
Jan./Feb. 1994, pp. 19-23.
C. N. Ravera,
I
J. Olivier, ac Britten and D. J. Swift, Silicone Rubber Insulators on
ESKOM'S AC Transmission Lines , ac and dc Power Transmission, 29 April 3 May
1996, Conf. Publ. N o. 423 IEE, 1996, pp . 70-75.
Research of Brittle Fractures in Composite Insulators, Interview with Maciej Ku-
mosa of the University of Denver , Insulator News and Market Report, July/August
M.
Portillo Belinchon, Technical Workshop on Composite Insulation for Power
Lines , Final Report, CIGRE SC 22 Espana, Madrid, May 29,1997.
A. G. Metcalf and G. K. Schmi tz, Mech anism of Stress Corrosion in E-Glass Fila-
ments , G lass Technology, Vol. 13, No. 1, Februa ry 1972, pp. 5-16.
H.
Dietz, H. Karner, K. H. Muller, H. Patrunky,
G.
Schenk,
l?
Verma and H. J. Voss,
Latest Developments and Expe rience with Composite Longrod Insulators , CIGRE
1986 session , paper 15-09.
1997, pp. 46-51.
[15] G.W hrenstein and H. Spaude, Ril3bildung in Elementarfasern durch Einwirkung
korrosiver Medien und erhohter Temperatur ,
Z.
Werkstofftechn. Vol. 14,1983 pp ,
[16] J. Aveston and
J.
M. Sillwood , Long Term Strength of
Glass
Reinforced Plastics in
Dilute Sulfuric Acid , Journal Mat. Sci.,
Vol.
17,1982 p p. 3491-3498.
[17] I?
J.
Hogg, Factors affecting the Stress Corrosion of GRP in Acid Environments ,
Compo sites, Vol. 14, No.
3, July
1983, pp . 254-261.
[18]
S.
Torp,
0.
Syromsod and M. Onarheim, Influence of Glass Fiber Type on Laminate
Corrosion Resistance , 37th Annual Reinforced PlasticsiComposite Institute, The
Society of Plastics Industry, Inc. January 11-15,1982, Session 9-E, pp, 1-5.
[19]
H.
Rompp, Chemie-Lexikon 6. Aufl., Frankh'sche Ver lagshandlung Stuttgart, 1966,
pp. 6155.
[20]
T.
C. Cheng and C. T. Wu, On the deletrious Effects of Nitrates on Insulator Surfaces
under HVDC Conditions , IEEE Trans. Electr. Ins., Vol. 14, No. 3, June 1979, pp,
73-81.
171-174.
[21] DIN 53 452, Testing of Plasti cs; Bending test , April 1977.
[22] DIN 53 445, Testing of Plasti cs; Tensile Test , Augu st 1981.
[23] DIN 53 479, Testing of Plastics and Elastomers; Determination of the Density, July
1976.
[24] DIN 53 458, Testing
of
Plastics; De termination
of
Temperature of Deflection under
Load (Martens Method).
[25] W isch, W. Hofmann and R. Schmid, Influence of Structure and Curing Condi-
tions on the Density, Degree of Cure and Glass Transition Temperature During the
Curing of Epoxid e Resins , Journal of app l. Polymer Science, Vol. 13, pp, 295-308,
1969.
[26] H.-J.
Booss
and
K.
R. Hauschild, Volumeneffekt bei der Vernetzung von Epoxid-
harzen , Ku nststof fe, Vol. 70,1980 pp, 48-50.
Manuscript was received on 4 May
1999,
in final form 1 October
2000,