00919922.pdf

download 00919922.pdf

of 9

Transcript of 00919922.pdf

  • 8/11/2019 00919922.pdf

    1/9

    82

    IEEE Transactions on Dielectrics and Electrical Insula ion

    Vol 8 No 2 April 2001

    FRP Rods for Brittle Fracture Resistant

    Composite Insulators

    M. Kuhl

    CeramTecAG

    Wunsiedel, Germany

    A B S T R A C T

    Brittle fracture of fiberglas reinforced polymer FRP) rods can lead to mechanical failures of

    composite insulators even at low mechanical lo ads durin g operational service. Although th is

    fact has been known for

    20

    years, it may still be a problem in some designs of composite

    insulators at the present time. In order to find counterm easures against brittle fracture,

    a

    study

    was carried out in the early eighties. It turned ou t that brittle fracture is a problem

    of

    FR P

    material and that material compositions exist, resistant to brittle fracture. A brittle fracture

    resistant

    FRP

    rod introduced 1983 n on e particular design of comp osite insulators resulted i n

    a

    15

    year excellent service performance. This st udy deals w ith details of brittle fracture of

    F R P

    rods. Test setups were established to induce brittle fracture artificially It was realized that

    brittle fracture is some kin d of stress corrosion related to the composition of th e

    FRP

    material.

    A broad variety of

    FRP

    materials was evaluated, showin g the influence of the components of

    FRP material on the brittle fracture behavior of

    FRP

    rods as well as the effects of dif ferent

    manufa cturing processes. The comp ositions of brittle fracture resistant FRP

    rods

    are disclosed.

    Th e results from artificial testing are compared with b rittle fracture of FRP rods that occurred

    in com posite insulators in operational service. Although no quantitative correlation could b e

    established, th e trend concerning th e material behavior of

    FRP

    rods is similar.

    1 INTRODUCTION

    OMPOSITE

    insulators consist of a glass fiber reinforced plastic rod

    C FRP

    rod), a shed housing made of polymeric material covering the

    FRP rod a nd metal end fittings attached to the ends of the FRP rod. The

    housing protects the FRP rod from weathering and supplies the nec-

    essary creepage distance. This composite structure consists of several

    interfaces which have to be designed and manufactured properly in or-

    der to avoid ingress

    of

    moisture, and pollutants from the surrounding

    environment into the interior of the composite structure. Laboratory

    tests carried ou t more than two decades ago revealed some typical elec-

    trical and mechanical failures of composite ins ulator s of early designs

    [l].However, in the late seventies a new kind of mechanical failure oc-

    curred on

    FRP

    rods of composite insulators installed in

    HV

    lines

    [Z-51,

    never seen before dur ing laboratory testing. This kind of mechanical

    failure is called 'brittle fracture' of a

    FRP

    rod d ue to the unusual fracture

    pattern of the fracture area

    of

    the concerned FRP rods. The failures oc-

    curred a t very low nominal operational mechanical service loads

    [3,4].

    The outer features of the fracture areas ar e characterized by a razor cut

    fracture surface running perpendicular to the axis of the

    FRP

    rod [6]. In

    those days it was thought that brittle fracture was initiated by ingress of

    chemicals such as dilute acids into the composite structure [Z

    4/51,

    The

    improvements carried out on composite insulators in the last decades

    led to elastomeric housing materials such as silicone rubber and ethy-

    lene propylene diene monomer

    (EPDM)

    rubber an d to better interfaces

    between the different materials of the composite components. New de-

    veloped test standards

    [7,8]

    are the tools to check the integrity of the

    composite structure.

    No broadly accepted test exists

    so

    far to check the composite struc-

    ture regarding brittle fracture of the

    FRP

    rod. This may be based on

    the fact that brittle fractu re occurred on a small number of insula tors

    under operational service conditions in comparison to the big numb er

    of installed composite insulators . In spite of this fact, a mechanical

    failure of an overhead transmission insulator may cause line dropp ing

    which results in an outage of the transmission line. Aging of composite

    insulators, and in particular, aging

    of

    the interfaces of the composite

    structure, may be one

    of

    the reasons for the infrequent occurrence of

    brittle fracture. M anufacturing defects on a small number of insulato rs

    may contribute to the failures as well as specific environmen ts. These

    conditions cannot be simulated in a design test performed

    on

    a small

    number of test specimens. The only possibility to eliminate brittle frac-

    ture of composite insulators at all was considered by using a brittle

    fracture resistant

    FRP

    rod as member of the composite structure. The

    result of this stud y has led to such a rod. It was introduced in the man-

    ufacturing of composite insulators consisting of a housin g mad e of high

    temperature vulcanized

    (HTV)

    silicone rubber in

    1983.

    Such insulators

    1070-9878111 $3.00

    001 IEEE

  • 8/11/2019 00919922.pdf

    2/9

    IEEE Transactions on Dielectrics and Electrical Insulation Vol. No April 2001

    183

    have been manufactured in large quantities d uring the last 15 years.

    The number of brittle fractures from those insulators is zero.

    It is interesting to note that for several designs of other composite

    insulator types brittle fracture is still a cur ren t problem [9-121. Most of

    the concerned insulators failed in the USA because there is the largest

    market for composite insulators [H I.

    Brittle fractures on

    FRP

    rods can be traced

    to

    stress corrosion of

    E-

    glass (electrical grade ) filaments. S tress corrosion involves an ion ex-

    change mechanism. Sodium ions with a large ion radius are replaced

    by hyd rogen ions with small radius, resulting in an increase of stress

    in the g lass surface of the filaments [13]. E-glass filaments build up spi-

    ral flaws on their surfaces after immersion in diluted acids [6,14,15].

    The flaws in the filaments initiate the failure of the composite material

    which can be described by the mechanism of fracture mechanics [16].

    In order

    to

    improve the brittleness of

    FRP

    material, several measures

    were proposed. Gel coats can be applie d on the surface. The correct

    choice of the matrix resin as well as the use of an acid resistant glass

    composition for the glass filaments may be successful [17,18].

    2

    EXPERIMENTAL

    All HV insulators under operational service conditions ar e stressed

    frequently by electrical surface discharges when the surfaces of the in-

    sulators are polluted and humidity penetrates the pollution. Already

    Cave ndish found in 1784 the generation of nitric oxides and nitric acid

    by using electrical discharges in nitrogen and oxygen, while Birkeland

    and Eyde fo und an industrial process proposed in 1905 for generating

    nitric acid by using electrical discharges in hum id ai r [19]. It was very

    likely to assume that the electrical discharges on

    HV

    devices may also

    generate nitric oxides and derivatives such as nitric acid. In order to

    show that nitric acid can be generated from power frequency voltage in

    presence of air and humidity, a device according to Figure 1was built.

    The electrical discharge was carried out at 25 kV,,, (50 Hz ). Distilled

    water was fed through the filter paper wra pped around the energized

    electrode at a flow rate of 10 cm3/h . After a time spa n of 1h the con-

    tent of the water collector had a pH value of 2.9, and 2.52 mg nitrogen

    was measured. More evidence for the presence of nitric acid and ni-

    tric oxides and their derivatives were found on the surfaces of polluted

    insulators from experiments and tests. 110 kV silicone composite insu-

    lators showed 4 to 5 nitrogen in the pollution after 5 yr service. Salt

    was taken from the surface of a silicone composite insulator after pass-

    ing the 1000 h salt fog test described in [7]. The nitrogen content in

    the salt amounted to 2.5%. A huge pollution content of nitrogen was

    reported from dc insulators on the pacific coast of California [20]. The

    autho rs of [20] considered that the nitrogen in the pollu tion could be

    traced back to agricultural products and fertilizers.

    Mechanical failures of test specimens from stress corrosion implies

    the presence of two components, mechanical stress and simultaneous

    application of an environmental medium such as nitric acid. To check

    FRP

    rods concerning their stress resistance corrosion, some have sug-

    gested the use

    of

    bending stress. Experiments carried out by the author

    under ben ding stress showed that after crack initiation, delamination

    occurred lengthwise in

    FRP

    rods to different extents. The acid can run

    out and th e stress cannot be held constant du e to the delamination in

    the composite material. More reproducible results were obtained from

    Water f l o w r a t e 10cm3/h

    R e s u l t 2 52mg N/h

    pH

    2.9

    Figure 1

    Device for generating nitric acid at power frequency volt-

    age 25

    kV

    50 Hz.

    1: steel bar,

    2:

    supporter,

    3:

    insulated copper wire 1.5

    mm diameter, 4: filter paper wra pped around, 5 : holder (acrylic glass),

    6: PVC tube

    OD

    63 mm, ID 51 mm, 7: silver paint (ground electrode),

    8: water supply (de-ionized water), 9: acid collector.

    test specimens loaded under tension. The test arrangement for testing

    FRP rods under tensile loads is shown in Figure 2. The arrangement

    has the adv antage that assembled FRP rods can be evaluated. FRP rods

    clamped into the interior of the end fittings may undergo higher me-

    chanical stresses in the end fittings as can be expected for the free length

    of the rods between the end fitti ngs. In this way the influence of the

    stress in the end fittings can be estimated. Diluted nitric acid of 1 n

    H N0 3 were chosen for simultaneous application of the env ironmental

    medium

    1

    n is 63 g concentrated HN 03 added

    to

    937 g water).

    I

    i i

    Figure

    2

    Test arrangement for the evaluation

    of

    brittleness

    of

    F R P

    rods (tensile load an d 1

    n HN03,

    simultaneously). Procedure I End

    fittings under acid. Procedure I1Infus ion of

    HN03

    rocedure

    111

    Acid

    on the free rod length.

    Experiments with the three test arrangements shown in Figure 2

    resulted in rejecting Procedure I because the acid attacked the metal

    of the end fittings in such a way that the acidity suffered and led to

    unreliable test results. The best reproductio n of test results could be

  • 8/11/2019 00919922.pdf

    3/9

    184

    Table 1 Epoxy resins and hardeners used to manufacture the test

    Type

    F

    0164

    X18

    331

    XlOO

    MTHPA

    HHPA

    PSA mixt

    1102

    4,4 MDA

    DDS

    MNA

    EH 640

    specimens.

    Trade name

    Araldite F

    Ruetapox 0164

    Lekutherm X18

    D. E. R. 331

    Lekutherm XlOO

    Ruetapox HX

    Araldite 907

    Araldite 905

    Vers. Prod.1102

    Araldite 972

    Araldite 976

    Araldite 906

    VersamidEH 640

    obtained with Procedure 111, because there is no metal involved in the

    chemical stability of the diluted acid.

    To manufacture

    FRP

    rods for this study, two manufacturing meth-

    ods were used. For variation

    of

    different glass fibers a discontinuous

    manufacturing pro cedure ha s been established. The glass fibers were

    woun d up on a rotating wooden sheet forming loops of glass rovings

    of a predetermined number. The loops were impregnated with heated

    resin mixture in

    a

    tub and then pulled in steel tubes for crosslinking at

    elevated temperatures. For the variation of different resin mixtures, a

    continuous protrusion process was used. In this process it was simple

    to

    replace a resin mixture by another mixture. The glass content of the

    FRP rods from both manufacturing procedures am ounted to 63 to 69% of

    weight an d the mechanical properties of the rods from both procedures

    were most equal when the same components were used. All FRP rods

    were manufactured from an epoxy matrix resin because epoxy resin is

    the best resin for FRP rods used in

    HV

    application d ue to their excellent

    mechanical and electrical properties, although remarkable differences

    exist within epoxies. The resin mixtures were prepared in ratios given

    by the manufacturer of the resin mixtures. The curing state of the test

    specimens concerned a curing state at 130C for

    1 0

    h, when no other

    treatment is mentioned.

    Table 1 ists the applied epoxy resins and hardeners. The resins F,

    0164 and 331 are aromatic diglycidylether (bisphenol A base) with an

    epoxy equivalent of

    90. X18

    is a distilled version of the epoxy resin

    mentioned before (high purit y),

    XlOO

    is

    a

    cycloaliphatic diglycidylester

    (HHPA base) with an epoxy equivalent of 185. The hardeners MTHPA,

    PSA mixt, 1102 and MNA are liquid at room temperature. The harden-

    ers HHPA, 4.4 MDA and

    DDS

    are solid at room temperature. Hardener

    EH

    640 is a 4.4 MDA diluted in 30% glycolene.

    The glass fibers used consisted of either assembled or direct rovings

    in 2400 or 4800 g/km. They were supplied f rom the companies Silenka,

    PPG (Pittsburgh), OCF (Owens Corning), Bayer AG, Ahlstrom, Norsk

    (Norsk Fiberglass), Vitrofil S.p.A., Gevetex (Stratifil), and were used as

    delivered.

    All test specimens were tested under constant static load as show n

    in Figure 3. After loading diluted nitric acid of a concentration

    of

    1n

    was applied immediately and the time to break was recorded by an

    electrical clock connected via movement of the lever arm of the test

    Kuhl:

    FRP Rods

    fo r Composite Insulators

    setup indicating hours, minu tes and seconds. The tests were carried

    out indoors at room temperature.

    sample

    Figure 3

    Test setup to cause

    artificial

    brittle fractures on assembled

    FRP

    rods.

    3

    FEATURESOF BRITTLE

    FRACTURE

    The first brittle fracture on a 420 kV silicone rubber insulator oc-

    curred in 1978 [ 5 ]on a 24 mm FRP rod assembled with en d fittings with

    a wide cleavage (Figure 4). The sealing of the end fitting was opened,

    so that chemicals could enter the interior of the end fitting.

    Figure

    4

    Brittle fracture

    of a

    420 kV silicone rubber suspension in-

    sulator after 3 yr of service.

    The broken insulator was part of

    a

    double suspension insulator

    string. The parallel insulator held the line and was brought down for

    evaluation purposes. Mechanical tests carried out on this insulator re-

    sulted in no reduction of the ultimate tensile load . Brittle fractu re can be

    simulated by means of test Procedure I1 (Figure 2). Both fractures, the

    natur al brittle fracture (Figure 4) as well as th e artificial brittle fracture

    (Figure

    5 )

    show fracture surfaces arranged perpendicular to the axis

    of the FRP rods and characteristic patterns of stress corrosion fractures

    which cannot be simulated any other way.

    Several tests performed with cyclic loads on test specimens without

    simultaneous application of acid resulted in different fracture patterns.

    Hence, they were obtained by much higher l oads and required longer

    times to failure than necessary for stress corrosion failure.

  • 8/11/2019 00919922.pdf

    4/9

    IEEE Transactions on Dielectrics and Electrical Insulation Vol 8 No 2 April 2001

    I85

    Composition

    Glass

    B 2 0 3 YO

    Silenka

    6.7

    Silenka

    5.1

    PPG

    4.9

    Bayer 4.8

    Vitrofil

    4.6

    OCF8 9

    4 3

    Ahlstrom

    4 0

    OCF424 3.3

    Norsk

    2.6

    Norsk ECR 18720

    Figure 5 Brittle fracture

    of

    a test specimen according

    to

    test Proce-

    dure

    11.

    The experience with brittle fracture of silicone insulators showed

    that in every case failure of the sealing between the housing and at

    least one of the end fittings was invo lved. Brittle fractures on the free

    length of the

    F R P

    rod had never been found for this particular insulator

    design. Tests carried out on test specimen with and without silicone

    sheath according to Figure 2, test Procedure 111, found that artificial

    brittle fractures of the

    FRP

    rods can be obtained only from naked rods.

    4

    ARTIFICIAL BRITTLE

    FRACTURES

    4.1 INFLUENCE OF NOMINAL

    TENSILE

    STRESS

    The results shown in this study refer to nominal tensile stresses.

    They are defined as those tensile stresses calculated from the applied

    static tensile load divide d by the unloa ded cross section of the

    FRP

    rod.

    This also is applicable for the e nd fittings; however, it is a stress indica-

    tion only and does not specify any real stresses quantitatively.

    The general characteristics of brittle fracture of FRP rods obtained

    from nomin al tensile stress and simultaneous application of

    1

    n nitric

    acid is shown in Figure 6.

    These results were obtained from

    24

    mm rods made of E-glass in

    postcured condition (180C for 16 h). In Figure 6curve1envelops the

    most resistant E-glass composition (glass type OCF 859/resin type

    BAY

    XlOO/HHPA) and cu rve 2 envelo ps one of the most susceptible E-glass

    composition (glass type Silenka/resin type BAK/M THP A). oth curves

    represent artifici al brittl e fractures obtained from the free length of FRP

    rods. Curve 3 envelops failures of FRP rods within end fittings designed

    as wide cleavage of the cone wedge type. It can be seen that the stress

    caused by end fittings can lead to a drastic reduction of the time to

    failure

    (FRP

    composition from curve 2). The section between curves

    1

    and 2 also represents the load time characteristics of all evaluated FRP

    rods from 16 to 37 mm m ade of E-glass. It can be seen that considerable

    differences exist regard ing the brittleness of FRP rods mad e of E-glass

    caused by stress corrosion. For all

    FRP

    rods ma de of E-glass,a load level

    exists indicating that at loads below this level brittle fracture does not

    occur. For the free length of the rods, the level may exist at 60 MPa and

    for the rod ends at 15 MPa under the above described test parameters.

    10

    1

    1000

    io000 i ooooa

    Breaking

    Time

    [minutes]

    Figure

    6

    Load time characteristics of brittle fractures of F R P rods

    24 mm

    diameter. Curves 1 and

    2:

    Test Procedure 111, Curve

    3:

    Test

    Procedure

    11,

    wide cleavage.

    Table 2 Variation

    of

    glass fibers. Breaking time (min)

    of

    24 m m FR P

    rods at nominal stress

    of 77

    MPa, test Procedure

    11,

    end fittings

    with

    wide cleavage.

    [ydrolysis

    :ant

    3

    61

    34

    51

    114

    >18720

    ptible

    U

    Cured

    617

    40

    1

    ~

    5821

    'ostcurec

    508

    180

    2982

    levels can be assumed at operational service. From this point of view

    it is most likely that brittle fracture may occur on composite insulators

    under operational service conditions if the FRP rod is manufactured

    from E-glass.

    4.2

    BRITTLE FRACTURE

    RESISTANT FRP

    RODS

    The brittleness of

    FRP

    rods caused by stress corrosion can be influ-

    enced by the glass composition as well as by the epoxy resin matrix and

    the interface between glass fibers and matrix.

    Table 2shows several parameters influencing the brittleness of

    FRP

    rods. As can be seen, the boron content of the glass fibers is of great

    importance. Boron free glasses

    B203

    content 0.15%) result in brittle

    fracture resistant FRP rods. A part from the boron free glass type Norsk

    ECR

    mentioned inTable

    2

    there exist some more boron-free glass fibers

    as Stratifil (Gevetex), NT712 (PPG) and S2 (OCF). 24 mm FRP rods made

    of

    these glass fibers show the same or even better brittle fracture resis-

    tance as found from Norsk ECR. Although boron free glass fibers used

    in

    FRP

    rods result in brittle fractu re resistant

    FRP

    ods, the role of boro n

    oxide in the glass composition is still unclear.

  • 8/11/2019 00919922.pdf

    5/9

    186

    Resin Hardener Break time (min)

    type cured postcured

    F HHPA

    333 2 5 3

    0164 HHPA

    368

    118

    X18 HHPA 416 106

    F PSAmix 661 220

    0164 PSAmix

    551

    231

    F 1102 217 79

    F

    HHPA 333 263

    F THPA 374 309

    F 4,4MDA 459

    F

    EH640

    >1300*

    F DDS

    67

    17

    Kuhl:FRP

    Rods for

    Composite Insulators

    Resin i

    characteristic

    bisph.Amixture

    bi5ph.A regular

    bisph.Adistilled

    9

    6

    8

    10

    15

    30

    50

    glass fibers itself. For the curing state of the matrix and the interface,

    some effects can be assumed. Thus, some evaluations

    on

    the postcuring

    state of epoxy matrix systems were carried out. Test specimens were

    molded of various epoxy matrix systems and treated with various cur-

    ing states. The test specimens were tested for bending strength and

    deflection [21], tensile strength and elongation [22], Youngs modulus

    [22] and density [23]. The curing state was determined by measuring

    the softening temperature of the resin according to Martens [24],called

    T temperature (Martins temperature).

    3 pt

    bending Def lect ion

    Tensile

    Pa

    O L

    O 100

    120

    Figure

    7 Properties of an epoxy matrix depending on the softening

    temperature T . System DOW331/MNA.

    Figure 7shows the results obtained from the System 331/MNA be-

    cause this system exhibits the post curing effect most impressively

    As

    known from cast resin, the mechanical prope rties of epoxy resin

    sys-

    tems improve with increasing curing state. This is also the case for

    the system 331/MNA, One can assume that the increasing curing state

    means an increasing density of crosslinking what results in a higher

    stiffness of the material a nd in a more dense material,

    Figure 7shows that these assumptions a re incorrect, It was found

    that all evaluated epoxy systems showed a decreasing Youngs Modu-

    lus and a decreasing density w ith increasing curing state to a different

    extent. Curing and postcuring of epoxy matrixes mean that the matrix

    duri ng crosslinking is subjected to a swelling effect [25,26]. In case of

    reinforced epoxy

    it

    can be assumed that a compression force acts an

    the interface between the

    glass

    fibers and the epoxy matrix. Postcur.

    ing means also tha t the finish layer on the surface of the gla ss fibers

    is hardening . Both effects result in propagation of cracks due to stress

    corrosion that is not stopped at the interface, and that time to failure

    due to stress corrosion can be expected earlier than in

    the

    case of

    non.

    postcured systems.

    Figure

    8

    shows the scattering of time to fililure of the most brittle PRP

    rod found d uring this stud y It was also found that the more brittle a PRP

  • 8/11/2019 00919922.pdf

    6/9

    IEEE Transactions

    on

    Dielectrics and Electrical Insulation

    Vol.8

    No

    2 April 2001

    187

    1 2

    3

    4 5

    6

    7

    8

    9 1 0 1 1

    Rod No.

    Figure 8 Scattering of time

    to

    failure.

    FRP

    rod

    37

    mm ystem DOW

    331/MNA/PPG

    E-glass, test Procedure I1 (wide cleavage) nominal

    stress77

    MPa.

    rod system is, the more is the scattering of the test results. Apar t from

    that, the results from the end fittings (test Procedure 11) scatter more

    than from free length of

    FRP

    rods ( test Procedure 111). Test Procedure 111

    may be

    a

    tool to check the brittleness of

    FRP

    rods in general. The test

    is easy to perform in the test ar rangement shown in Figure

    3

    with test

    specimens show n in Figure 2 (Procedure 111). The acid container made

    of polyethylene should have such a size that the FRP rod is surrounded

    by liquid thickness not

    3

    1cm and a liquid level of

    > 4

    cm. The lower

    end of the acid container ha s to be attached and sealed to the surface of

    the FR P rod in ord er to prevent the acid from coming in contact with the

    lower end fitting of the FRP rod. The acid container should be covered

    to prevent evaporation of the liquid >5 of its volume du ring the test

    period,

    The test specimen prepared this way can be loaded in the test setup

    shown in Figure 3with a load high enough to cause a tensile stress of

    340 MPa with in the cross section of the free length of the FRP rod and

    maintain this stress for

    a

    time span of 96 h. Immediately after app lying

    the load,

    a

    nitric acid of a concentration of

    1

    n

    HN03

    can be poured

    into the acid container. The acid must not come into contact with the

    end fittings of the test specimen. Brittle fracture resistant

    FRP

    rods can

    be realized, if no fracture of the

    FRP

    rod occurs during the test period

    of

    96 h [14], see also Figure 6.

    Brittle fracture

    of FR P

    rods made of E-glass can be initiated by any

    other diluted acid with pH values t 4 . Tests performed with strong

    organic acids (checked were formic acid, chlorinated acetic acid and ox-

    alic acid) showed that these acids also can attack FRP rods. On the other

    hand, FRP rods made of boron-free

    glass

    fibers withstood all diluted

    acids. Water did not affect any of the eva luated

    FRP

    rod systems.

    Glass monofilaments may contain tiny capillaries related to gase-

    ous

    bubbles in the molten glass during manufacturing of the monofila-

    ments. This was discovered in the seventies for E-glass. Some interest-

    ing effects concerning the electrical performance of

    FRP

    rods containing

    capillaries were foun d by the author. Test standards were developed in

    order

    to

    quan tify capillarity fo r the selection of

    FRP

    rods suitable for

    HV

    applications. A link between capillarity and bri ttle fracture of

    FRP

    rods

    could not be estab lished , Today capillarity of FRP rods is not

    a

    problem

    anymore. Both E-glass as well as boron-free glass exist that are nearly

    fre e from capillaries.

    4.3

    CONCLUSIONS FROM

    ARTIFICIAL BRITTLE

    FRACTURE

    Brittle fracture of

    FRP

    rods made of E-glass can be simulated by ap-

    plying tensile stress and simultaneous application of diluted acids. The

    fracture patte rns of artificial brittle fractures are very close to the frac-

    ture patterns of brittle fractures of broken composite insulators out of

    service. Tests conducted with test specimens under static and dynamic

    loads without application of acid led to fracture patterns not compara-

    ble

    to

    brittle fracture patterns. Brittle fracture of FRP rods occurred in

    service

    at

    load levels far lower than the ultimate failing load of com-

    posite insulators. This is consistent with load levels found for artificial

    brittle fractures simulated with tensile stress and simultaneous applica-

    tion of dilute d acids. These facts have led to the conclusion that brittle

    fractures of composite insulators in service are the result of stress cor-

    rosion, initiated by diluted acid at the surface of E-glass fibers under

    tensile stress.

    Brittle fracture of composite in sulato rs can be avoided by using FRP

    rods made of boron-free glass fibers. This class

    of

    glass fibers is re-

    sistant to acids and stress corrosion at load levels known from service

    experience [14].

    In general brittle fracture failure of

    FR P

    rods made of E-glass can

    vary in a wide span of time. The fractures are subjected to a load time

    characteristic depending on the applied tensile stress and the p H value

    of the corrosive medium. The nominal stress can be enhanced by the

    design of the end fittings at the end s of the FRP rods. Other general

    factors influencing the brittle fracture failures are the boron content of

    the glass fibers, the toughness of the resin matrix and the curing state

    of the resin matrix.

    These results obtained from artificia l testing of FRP rods made of E-

    glass showed tha t the choice of the m aterial components (glass, resin,

    hardener) can also lead to an unpredictable brittle fracture behavior,

    In the frame of this stud y 62 variations of FRP rods have been evalu-

    ated. Although some general trend s resulting from the

    FRP

    material

    components could be found, there were some results which could not

    be explained, such as shown in Table 2for the glass OCF 859 in combi-

    nation with two different resins.

    5 NATURAL BRITTLE

    5 1 FRP RODS EXPOSED

    FRACTURES

    OUTDOORS

    It is common practice for manufacturers of composite insulators to

    evaluate the load time characteristic

    of

    FRP

    rods under static loads

    as

    described in

    [7].

    In most cases it takes several years

    to

    obtain a load

    time curve for a particular assembled

    FRP

    rod, Up to now, nothing is

    specified about the condition of test specimens for the realization of the

    load time curves. Knowing the impact of postcuring on brittle fractures,

    24 mm

    F R P

    rods were exposed outdoors under static loads in a test

    device similar to Figure 3.Rods with and without a sheath of silicone

    elastomer in postcured condition (180C for 16 h) were tested.

  • 8/11/2019 00919922.pdf

    7/9

    288

    t

    Y

    3.5

    6

    9

    14

    Kuhl: FRP Rods for Composite Insulators

    Observation

    cracks and

    delamination on

    FRP

    rod surfaces.

    less surface erosion

    brittle fracture on

    free

    F R P

    rod length

    surface erosion

    F R P

    rod surface

    strongly eroded

    1crack near end

    fitting. minor

    erosion

    During the first three years of o utdoor testing

    no

    difference could

    be observed between test specimens with and witho ut silicone sheath.

    The obtained load time curves were similar. However, after three years

    of lo ading visual in spection of th e naked FRP rods revea led some differ-

    ences between

    F R P

    rods of differen t compositions as well

    as

    differences

    between naked and sheathed rods. While the sheathed rods showed

    minor influence of w eathering , all naked rods made of aromatic epoxy

    systems showed strong discolo ration and stro ng erosion on their sur-

    faces. A layer of loose gla ss fibers covered th e surfaces of the rods

    due to ero sion of t he arom atic epoxy matrix; the more, the longer the

    time of exposure . The rods compo sed from cycloaliphatic epoxy matrix

    showed far less surface erosion for the same exposu re time.

    Table 4shows the most interesting results from24 mm rods exposed

    outdoor s under static loads in the plant location of CeramTec AG. The

    environm ent of this plant ca n be characte rized by a relatively clean at-

    mosphere,

    M

    500 m above sea level.

    A

    lot of forests and agriculture

    domina te this area of m oderate clima te. The most interesting observa-

    tion made was the fact that one brittle fracture occurred on one aromatic

    epoxy system and rods from other systems showed some cracks run-

    ning perp endicular to the ro d axis on its free length like a start of brittle

    fracture.

    In Table 4are listed also three epoxy systems and their time to break

    from artificial brittle fractur e testing with nitric acid. There might be

    a correlatio n between artificial brittle fracture testing and those obser-

    vations made in outdoor exposure of

    FRP

    rods. Questions arose why

    the aromatic F system from Table 4did not brea k. Microscopic evalua-

    tion of the sur face of those r ods revealed s ome differences to the 0164

    system. U nder the microscope the same cracks could be seen

    on

    the F

    system

    as

    seen macroscopically on t he 0164 system; however, the de-

    gree of matrix erosion due to weatherin g on the F system exceeded by

    far the erosion seen on the 0164 system. It can be a ssumed th at crack

    propag ation du e to brittle fracture caused by stress corrosion of th e

    glass fibers and the speed of matrix erosion caused by wea thering are

    in competition w ith each other. The high s peed of the matrix erosio n of

    the F system inhibits crack propagation d ue to stress corrosi on.

    The reason for brittle fractures observed on naked F R P rods exposed

    outdoor s (without voltage, without acid) are still unknown. It can be ar-

    gued th at diluted acid can exist in every moderate climatic atmosph ere

    as

    can be found in Germany. On the other hand, the evaluated epoxy

    systems are mostly crosslinked with acidic hardeners. Hydrol ytic ef-

    fects on the matrix system may play a role. It can also be assum ed that

    the ultraviolet

    UV)

    part of the solar radiation may cause nitric acid for

    crack initiation on the surface of FRP rods. The FRP rods covered with

    silicone elastomer did not show any signs of brittle fra cture. For the

    naked rods it can be concluded fromTable4that the observations made

    on them follow the same trend

    as

    found for the results from artificial

    testing.

    5.2 FRACTURES ON SILICONE

    COMPOSITE

    NS

    U LATO

    R

    S

    Table 5lists the brittle fractu res

    of

    FRP

    rods ma de of E-glass used in

    silicone composite insulato rs from o perationa l service.

    As

    shown, the

    majority of the broken in sulators were installed at harsh environm ental

    condition s at high service voltages.

    Table 4. Observations made on 24 mm F R P rods exposed outdoors

    under static load. t b is the time to break under test procedure

    2,

    t

    the exposure time under

    a

    tensile stress St

    Matrix

    0164

    MTHPA

    F PSA mixture

    X100 HHPA

    Art. test

    t

    MPa

    6 1

    102

    252

    217

    In all cases the sealing between housi ng and the end fitting opened

    and, except in one case, the live end fitting sides of the insulato rs were

    involved . Brittle fracture on the free length

    of

    the

    FRP

    rods did no t occur

    in contrast to what is reported in

    [ 2 ]

    and [ll] A corr elation between

    the expected service tensile stresses and the time to f ailure could not

    be found . However, 13 brittle fractur es out of 19 occurred on tension

    insulators . The numb er of tension insulators in a

    HV

    transmissi on line

    is small compared to the num ber of suspensi on insulators. In spite of

    this fact brittle fracture occurred preferably on tension insulator s which

    are usually more highly loaded than suspension insulators. This may

    be an indication that tensile stress from service loading plays

    a

    role

    concerning the statistical occurrence of brittle fr actures.

    Table

    5

    pre sent s the result s of artificial testing of

    FRP

    rods from test

    Procedure

    11.

    The compariso n between the time to failure from artificial

    testing and from operationa l service leads to

    a

    similar trend concern-

    ing the evaluated material composition. The resin matrix 331/MNA

    combined with th e E-glass type PPG 712 was foun d to be the most

    sus-

    ceptible system concerning brittle fractu re during artificial testing, see

    also Figure 8.

    This system was also most susceptible under operational service

    conditio ns. The systems 0164/MTHPA/Silenka and F/PSA mix t/OCF

    859 resulted in sm all differences from artificial testing.

    Under operation al service the performance of these two systems can

    be considered as equal. The average time

    to

    failure of both systems

    under operational service conditions results in 9,l years (one can also

    assume that the time until ope ning of th e sealing between housing and

    the end fitting is eq ual statistically). The system XlOO/HHPA/OCF859

    exhibited

    a

    remarkable resistance

    o

    the occurrence of brittle fractur e in

    artificial testing

    as

    well

    as

    under operational service. Although some

    thousand silicone composite insulators still exist utilizing this type

    of

    FRP

    rod in lin es up to 245 kV with end fittings of wide cleavage,

    only one brittle fracture under operatio nal service conditions occurred

    within a service time of more than 25 yr. Finally,

    a

    vast number of sili-

    cone rubber insulators have been installed since 1983 utilizing

    FRP

    rods

    containin g boron free acid resista nt glass fibers from which is k nown

    the rate of brittle frac tures is zero. This fact is also consi stent with th e

    resu lts of artificial testi ng.

  • 8/11/2019 00919922.pdf

    8/9

    IEEE Transactionson Dielectrics and Electrical Insulation

    Vol.

    8 No 2 April 2001

    Line

    roltage

    kV

    420

    420

    420

    420

    420

    420

    420

    123

    123

    420

    230

    420

    420

    420

    420

    123

    420

    420

    420

    15

    89

    String

    config.

    triple tension

    dto

    inv.V

    suspens

    double

    tension

    dto

    dto

    dto

    double

    suspens

    triple tension

    double

    tension

    double

    suspens

    dto

    invertv

    double

    tension

    spacer

    suspens

    spacer

    double

    tension

    tension

    Resin

    system

    11

    MNA

    164

    MTHPA

    PSA

    mixt

    100 HHPA

    t

    nounted

    Y

    0.08

    0.08

    0.4

    1.3

    10

    10

    1

    6

    15

    12

    2

    g

    a

    ss

    type

    PG 712

    jilenka

    m

    CF 859

    ~

    Pos.

    Reason

    fracture fracture

    life end bad sealing

    groundend dto

    lifeend dto

    dto dto

    dto dto

    dto dto

    dto dto

    dto dto

    dto dto

    dto dto

    dtoto

    Table 5 Brittle fractures experienced on silicone composite insulators.

    4

    6

    7

    12

    7

    20

    19

    29

    RP

    rod

    diam.

    mm

    37

    37

    37

    37

    24

    24

    24

    24

    24

    24

    24

    24

    24

    37

    37

    24

    24

    24

    37

    dto dto

    dto bad sealing

    dto dto

    dto bad sealing

    dto dto

    dto

    dto

    dto wide cleavage

    range

    t b

    iostcurec

    min

    21

    121

    220

    2982

    anuf

    year

    979

    1979

    1979

    1979

    1981

    1981

    1981

    1979

    1979

    1979

    1981

    ~

    1975

    1975

    1975

    1975

    1977

    1975

    1975

    1976

    1968

    ~

    Env.

    very severe, coast

    dto

    dto

    dto

    coastal severe

    dto

    dto

    medium

    medium

    medium

    rural

    dto

    coastal severe

    severe

    Alps

    very severe

    severe

    very severe

    very severe

    railway

    6 CONCLUSIONS

    OMPOSITE

    insulators installed outdoors in HV lines can suffer from

    C

    atastrophic mechanical failures at tensile loads far below their ul-

    timate tensile strength. This fact, together with the unusual fracture

    pattern of the

    F R P

    rods, leads to the assumption that brittle fracture of

    FRP

    rods is initiated by stres s corrosion. Nitric acid can be formed by

    electrical discharge in hum id air and m ay hav e access to the surface of

    FRP

    rods.

    FRP

    rods have been tested artificially under tensile stress and simul-

    taneous application of 1n nitric acid. The results from this testing lead

    to the conclusions that brittle fracture of FRP rods

    1. is

    a

    matter of stress corrosion,

    2. follows the rules

    of

    fracture mechanics,

    3. can be initiated by diluted acids and simultaneous application of tensile

    4. is a matter

    of

    stress corrosion of

    glass

    fibers containing boron oxide

    5 . can be prevented by using boron-free glass fibers.

    A

    broad variety of

    FRP

    rods made of different material components

    were evaluated. It was sho wn that all E-glass fibers used in F R P rods

    lead to rods susceptible to stress corrosion to different extent. Consid-

    ering the para meter s of influence found, the occurrence of catastrophic

    mechanical failures of composite insulators installed outdoors on H V

    lines can be related to incidents and reasons:

    1. Defect of the sealing between end fitting and FR P rod. Moisture pen-

    etration into the inside of the end fitting with generation of an acidic

    stress,

    solution due

    to

    electrical activity (corona) in the area near the end fit-

    ting. Acid attack upon non-brittle fracture resistant FRP

    rods

    which are

    permanently under mechanical load.

    2. Glass fibres used for

    FRP

    rods contain 8203

    3. Epoxy matrix is not suitable. The main parameters that influence the

    brittle fracture resistance are the curing state, the

    toughness

    and the

    swelling characteristic of the matrix.

    4. Interface between matrix and fibres is weak. Moisture in the interface,

    missing coupling agents and bad sizing can lead to a weak fibre-matrix

    bonding. FR P rods with weak fibre-matrix bondings are expected to be

    more sensitive to brittle fracture.

    It is most likely that more than one of these parameters determines

    the time to failure of a particular composite insulator installed on a HV

    line, as long as FRP rods are used made of

    E-glass.

    The brittleness of

    FRP

    rods can be checked simply by means of ten-

    sile stress in the simultaneous presence of di luted acids ( test Proce-

    dure 111). The test r esults obtained from this testing are consistent

    qual-

    itatively with the experience obtained from operational service of com-

    posite insulators installed in outdoor

    HV

    lines. The use of boron-free

    glass fibers in

    FRP

    rods have led

    to

    a new generation of silicone com-

    posite insulators free

    of

    brittle fracture in 1983. This is proven by the

    vast number of suc h insulators manufactured during the last

    15

    yr. The

    number of brittle fractures from those insulators is zero.

    REFERENCES

    [l]G. Karady, R. Vinet and N. Souchereau, New Test Methods for Synthetic insula-

    tors , CIGRE 1976 Session, paper 22-15.

  • 8/11/2019 00919922.pdf

    9/9

    290 Kuhl:FRP

    Rods

    for

    Composife

    Insulators

    [2] H. Weihe, R. E. Macey and J. I? Rynders, Field Experience and Testing of New

    Insulator Types in South Africa , CIGRE 1980 session , paper 22-03.

    [3] M. Cojan,

    J.

    Perret, C. Malaguti,

    I

    Nicolini, J.

    S.T.

    Looms and A.

    W

    tannet, Poly-

    meric Transmission Insulators: T heir Application in France, Italy and the U K , CI-

    GRE 1980 session, paper 22-10.

    [4] A. Bradwell and J. C. G. Wheeler, Evaluation of Plastics Insulators for Use

    on

    Britis h Railways 25 kV Overhead Line Electrification , IEE Proc. Vol. 129, Pt.

    B,

    No.

    3 May 1982, pp. 101-110.

    [5] E. Bauer, H. Karner, K. H. Muller a nd

    P.

    Verma, Service Experi ence with the Ger-

    man Composite Long Rod

    Insulator

    with Silicone-RubberSheds since 1967 , CIGRE

    1980 session, Paper 22-11.

    [6] CIGRE WG 22 43 , Guide for the Identif icatio n of Brittl e Fractu re of Compo site

    Insulators FRP rod , ELECTRA

    No.

    143,199 2, pp. 61-69.

    IEC 1109, Composite Insulators for ac Overhead L ines with a Nominal Voltage

    greater t han 1000 V Definitions, Test Methods and Acceptance Criteria , 1995.

    C29.

    11ANSI, American National Standard for Composite Suspension Insulators

    for Overhead Transmission Lines Tests , 1989.

    Interview with J.

    S.

    T. Looms , Insulator News and Market Report Vol. 2, No. 1,

    Jan./Feb. 1994, pp. 19-23.

    C. N. Ravera,

    I

    J. Olivier, ac Britten and D. J. Swift, Silicone Rubber Insulators on

    ESKOM'S AC Transmission Lines , ac and dc Power Transmission, 29 April 3 May

    1996, Conf. Publ. N o. 423 IEE, 1996, pp . 70-75.

    Research of Brittle Fractures in Composite Insulators, Interview with Maciej Ku-

    mosa of the University of Denver , Insulator News and Market Report, July/August

    M.

    Portillo Belinchon, Technical Workshop on Composite Insulation for Power

    Lines , Final Report, CIGRE SC 22 Espana, Madrid, May 29,1997.

    A. G. Metcalf and G. K. Schmi tz, Mech anism of Stress Corrosion in E-Glass Fila-

    ments , G lass Technology, Vol. 13, No. 1, Februa ry 1972, pp. 5-16.

    H.

    Dietz, H. Karner, K. H. Muller, H. Patrunky,

    G.

    Schenk,

    l?

    Verma and H. J. Voss,

    Latest Developments and Expe rience with Composite Longrod Insulators , CIGRE

    1986 session , paper 15-09.

    1997, pp. 46-51.

    [15] G.W hrenstein and H. Spaude, Ril3bildung in Elementarfasern durch Einwirkung

    korrosiver Medien und erhohter Temperatur ,

    Z.

    Werkstofftechn. Vol. 14,1983 pp ,

    [16] J. Aveston and

    J.

    M. Sillwood , Long Term Strength of

    Glass

    Reinforced Plastics in

    Dilute Sulfuric Acid , Journal Mat. Sci.,

    Vol.

    17,1982 p p. 3491-3498.

    [17] I?

    J.

    Hogg, Factors affecting the Stress Corrosion of GRP in Acid Environments ,

    Compo sites, Vol. 14, No.

    3, July

    1983, pp . 254-261.

    [18]

    S.

    Torp,

    0.

    Syromsod and M. Onarheim, Influence of Glass Fiber Type on Laminate

    Corrosion Resistance , 37th Annual Reinforced PlasticsiComposite Institute, The

    Society of Plastics Industry, Inc. January 11-15,1982, Session 9-E, pp, 1-5.

    [19]

    H.

    Rompp, Chemie-Lexikon 6. Aufl., Frankh'sche Ver lagshandlung Stuttgart, 1966,

    pp. 6155.

    [20]

    T.

    C. Cheng and C. T. Wu, On the deletrious Effects of Nitrates on Insulator Surfaces

    under HVDC Conditions , IEEE Trans. Electr. Ins., Vol. 14, No. 3, June 1979, pp,

    73-81.

    171-174.

    [21] DIN 53 452, Testing of Plasti cs; Bending test , April 1977.

    [22] DIN 53 445, Testing of Plasti cs; Tensile Test , Augu st 1981.

    [23] DIN 53 479, Testing of Plastics and Elastomers; Determination of the Density, July

    1976.

    [24] DIN 53 458, Testing

    of

    Plastics; De termination

    of

    Temperature of Deflection under

    Load (Martens Method).

    [25] W isch, W. Hofmann and R. Schmid, Influence of Structure and Curing Condi-

    tions on the Density, Degree of Cure and Glass Transition Temperature During the

    Curing of Epoxid e Resins , Journal of app l. Polymer Science, Vol. 13, pp, 295-308,

    1969.

    [26] H.-J.

    Booss

    and

    K.

    R. Hauschild, Volumeneffekt bei der Vernetzung von Epoxid-

    harzen , Ku nststof fe, Vol. 70,1980 pp, 48-50.

    Manuscript was received on 4 May

    1999,

    in final form 1 October

    2000,