00825-0100-4803
Transcript of 00825-0100-4803
-
7/27/2019 00825-0100-4803
1/48
www.emersonprocess.com/rosemount
00825-0100-4801J
HART
Quick Installation Guide00825-0100-4803, Rev AA
September 2008 Rosemount 3051SMV
Rosemount 3051S MultiVariable
Transmitter
Rosemount 3051SF Series Flowmeter
MultiVariable Transmitter
2008 Rosemount Inc. All rights reserved. All marks property of owner. Rosemount and theRosemount logotype are registered trademarks of Rosemount Inc.
Step 1: Mount the Transmitter
Step 2: Consider Housing Rotation
Step 3: Set Switches
Step 4: Connect Wiring and Power Up
Step 5: Flow ConfigurationStep 6: Verify Device Configuration
Step 7: Trim the Transmitter
Product Certifications
Start
End
-
7/27/2019 00825-0100-4803
2/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008Rosemount 3051SMV
2
Rosemount Inc.
8200 Market BoulevardChanhassen, MN USA 55317T (US) (800) 999-9307T (Intnl) (952) 906-8888F (952) 949-7001
Emerson Process Management
GmbH & Co. OHGArgelsrieder Feld 382234 WesslingGermanyT 49 (8153) 9390, F49 (8153) 939172
Emerson Process ManagementAsia Pacific Private Limited1 Pandan CrescentSingapore 128461T (65) 6777 8211
F (65) 6777 0947/65 6777 0743
Beijing Rosemount Far East InstrumentCo., LimitedNo. 6 North Street, Hepingli, Dong Cheng DistrictBeijing 100013, ChinaT (86) (10) 6428 2233
F (86) (10) 6422 8586
IMPORTANT NOTICE
This installation guide provides basic guidelines for the Rosemount 3051SMultiVariable transmitter (reference manual document number00809-0100-4803). It also provides the basic 3051S MultiVariable transmitterconfiguration guidelines for the 3051SFA (reference manual document number00809-0100-4809), 3051SFC (reference manual document number
00809-0100-4810), and 3051SFP (reference manual document number00809-0100-4686). It does not provide instructions for diagnostics,maintenance, service, or troubleshooting. Refer to the 3051S MultiVariabletransmitter reference manual for more instruction. All documents are availableelectronically at www.emersonprocess.com/rosemount.
WARNING
Explosions could result in death or serious injury:
Installation of this transmitter in an explosive environment must be inaccordance with the appropriate local, national, and international standards,codes, and practices. Please review the approvals section of the 3051SMultiVariable transmitter reference manual (00809-0100-4803) for anyrestrictions associated with a safe installation.
Before connecting a HART communicator in an explosive atmosphere,ensure the instruments in the loop are installed in accordance withintrinsically safe or non-incendive field wiring practices.
In an Explosion-proof/Flameproof installation, do not remove the
transmitter covers when power is applied to the unit.Process leaks may cause harm or result in death. Install and tighten process connectors before applying pressure.
Electrical shock can result in death or serious injury. Avoid contact with the leads and terminals. High voltage that may be
present on leads can cause electrical shock.
-
7/27/2019 00825-0100-4803
3/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008 Rosemount 3051SMV
3
STEP 1: MOUNTTHE TRANSMITTER
Liquid Flow Applications
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Mount the transmitter so that the
drain/vent valves are oriented
upward.
Gas Flow Applications
1. Place taps in the top or side of
the line.
2. Mount beside or above the taps.
Steam Flow Applications
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Fill impulse lines with water.
-
7/27/2019 00825-0100-4803
4/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008Rosemount 3051SMV
4
Mounting Brackets
Coplanar Flange
Traditional Flange
Pipe MountPanel Mount
Pipe MountPanel Mount
-
7/27/2019 00825-0100-4803
5/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008 Rosemount 3051SMV
5
Bolting Considerations
If the transmitter installation requires assembly of a process flange,
manifold, or flange adaptors, follow these assembly guidelines to
ensure a tight seal for optimal performance characteristics of the
transmitter. Only use bolts supplied with the transmitter or sold by
Emerson Process Management as spare parts. Figure 1 illustrates
common transmitter assemblies with the bolt length required for
proper transmitter assembly.
Figure 1. Common Transmitter Assemblies
4 x 1.75-in.(44 mm)
4 x 2.88-in.(73 mm)
A. Transmitter withCoplanar Flange
B. Transmitter withCoplanar Flange andOptional FlangeAdapters
C. Transmitter withTraditional Flange andOptional FlangeAdapters
D. Transmitter withCoplanar Flangeand OptionalManifold and FlangeAdapters
4 x 1.75-in.(44 mm)
4 x 1.50-in.(38 mm)
4 x 1.75-in.(44 mm)
4 x 2.25-in.
(57 mm)
-
7/27/2019 00825-0100-4803
6/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008Rosemount 3051SMV
6
Bolts are typically carbon steel or stainless steel. Confirm the material
by viewing the markings on the head of the bolt and referencingFigure 3. If bolt material is not shown in Figure 3, contact the local
Emerson Process Management representative for more information.
Use the following bolt installation procedure:
1. Carbon steel bolts do not require lubrication and the stainless steel
bolts are coated with a lubricant to ease installation. However, no
additional lubricant should be applied when installing either type of
bolt.
2. Finger-tighten the bolts.
3. Torque the bolts to the initial torque value using a crossing pattern.
See Figure 3 for initial torque value.
4. Torque the bolts to the final torque value using the same crossing
pattern. See Figure 3 for final torque value.
5. Verify that the flange bolts are protruding through the module
isolator plate before applying pressure.
Figure 2. Module Isolator Plate
Figure 3. Torque Values for the Flange and Flange Adapter BoltsBolt Material Head Markings Initial Torque Final Torque
Carbon Steel(CS)
300 in.-lbs. 650 in.-lbs.
Stainless Steel
(SST)
150 in.-lbs. 300 in.-lbs.
Module Isolator Plate
Bolt
B7M
316
316
316
SW
316
STM316
R
B8M
-
7/27/2019 00825-0100-4803
7/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008 Rosemount 3051SMV
7
O-rings with Flange Adaptors
WARNING
Whenever the flange or adapters are removed, visually inspect the
o-rings. Replace them if there are any signs of damage, such as nicks
or cuts. If the o-rings are replaced, re-torque the flange bolts and
alignment screws after installation to compensate for seating of theo-rings.
Failure to install proper flange adapter o-rings may cause process leaks, whichcan result in death or serious injury. The two flange adapters are distinguishedby unique o-ring grooves. Only use the o-ring that is designed for its specific
flange adapter, as shown below.
Rosemount 3051S / 3051 / 2051 / 3001 / 3095 / 2024
Rosemount 1151
Flange Adapter
O-ring
Flange Adapter
O-ring
PTFE BasedElastomer
PTFEElastomer
-
7/27/2019 00825-0100-4803
8/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008Rosemount 3051SMV
8
STEP 2: CONSIDER HOUSING ROTATIONTo improve field access to wiring or to
better view the optional LCD display:
Figure 4. Transmitter HousingSet Screw
1. Loosen the housing rotation set
screw.
2. Turn the housing up to 180degrees left or right of its original
(as shipped) position.3. Retighten the housing rotation set
screw.
NOTEDo not rotate the housing more than 180 degrees without first performing adisassembly procedure (see Section 4 of the 3051S MultiVariable transmitterreference manual (00809-0100-4803) for more information). Over-rotation
may sever the electrical connection between the sensor module and thefeature board electronics.
Housing Rotation Set Screw(3/32-in.)
FeatureBoard
-
7/27/2019 00825-0100-4803
9/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008 Rosemount 3051SMV
9
STEP 3: SET SWITCHESThe transmitters default configuration sets the alarm condition to high
(HI) and the security to off.
1. If the transmitter is installed, secure the loop and remove power.
2. Remove the housing cover opposite the field terminals side. Do not
remove the housing cover in explosive environments.
3. Slide the security and alarm switches into the preferred position by
using a small screwdriver.
4. Reinstall the housing cover so that metal contacts metal to meet
explosion-proof requirements.
Figure 5. Transmitter Switch Configuration
AlarmSecurity
-
7/27/2019 00825-0100-4803
10/48
Quick Installation Guide
00825-0100-4803, Rev AA
September 2008Rosemount 3051SMV
10
STEP 4: CONNECT WIRINGAND POWER UP
NOTE
Do not connect the power across the test terminals. Power could damage thetest diode in the test connection. Twisted pairs yield best results. Use 24 AWG to14 AWG wire and do not exceed 5,000 feet (1500 meters).
Use the following steps to wire the transmitter:
1. Remove the cover on the field terminals side of the housing.
2. Connect the positive lead to the PWR/COMM + terminal, and the
negative lead to the PWR/COMM terminal.
3. If the optional process temperature input is not installed, plug and
seal the unused conduit connection. If the optional process
temperature input is being utilized, see Install Optional Process
Temperature Input (Pt 100 RTD Sensor) on page 13 for more
information.
IMPORTANT NOTICE
4. If applicable, install wiring with a drip loop. Arrange the drip loop
so the bottom is lower than the conduit connections and thetransmitter housing.
5. Reinstall the housing cover and tighten so that metal contacts
metal to meet explosion-proof requirements.
When the enclosed pipe plug is utilized in the conduit opening, it must beinstalled with a minimum engagement of five threads in order to comply withexplosion-proof requirements. Refer to the 3051S MultiVariable transmitterreference manual (document number 00809-0100-4803) for more information.
-
7/27/2019 00825-0100-4803
11/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008 Rosemount 3051SMV
11
Figure 6 shows the wiring connections necessary to power a 3051S
MultiVariable transmitter and enable communications with a hand-heldHART communicator.
Conduit Electrical Connector Wiring (Option GE or GM)
For 3051S MultiVariable transmitters with conduit electrical connectors
GE or GM, refer to the cordset manufacturers installation instructions
for wiring details. For FM Intrinsically Safe, Division 2 hazardous
locations, install in accordance with Rosemount drawing 03151-1009
to maintain outdoor rating (NEMA 4X and IP66.) SeeAppendix B ofthe 3051S MultiVariable transmitter reference manual
(00809-0100-4803).
Figure 6. Transmitter Wiring
3051SMV without Optional ProcessTemperature Connection
3051SMV with Optional ProcessTemperature Connection
NOTEInstallation of the transient protection terminal block does not provide transientprotection unless the 3051S MultiVariable transmitter housing is properly
grounded.
RL 250
Power
Supply
PowerSupply
RL 250
http://../MAN/4801/Rev%20CB/4801_b.pdfhttp://../MAN/4801/Rev%20CB/4801_b.pdf -
7/27/2019 00825-0100-4803
12/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008Rosemount 3051SMV
12
Power Supply
The dc power supply should provide power with less than two percent
ripple. The total resistance load is the sum of the resistance of the
signal leads and the load resistance of the controller, indicator, intrinsic
safety barriers, and related components.
Figure 7. Load Limitation
3051S MultiVariable TransmitterMaximum Loop Resistance = 43.5 x (Power Supply Voltage 12.0)
The HART communication requires a minimumloop resistance of 250..
Voltage (V dc)
Loa
d(Ohms)
OperatingRegion
1322
1000
500
012.0 20 30
42.4
-
7/27/2019 00825-0100-4803
13/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008 Rosemount 3051SMV
13
Install Optional Process Temperature Input
(Pt 100 RTD Sensor)
NOTETo meet ATEX/IECEx Flameproof certification, only ATEX/IECEx FlameproofCables (Temperature Input Code C30, C32, C33, or C34) may be used.
1. Mount the Pt 100 RTD Sensor in the appropriate location.
NOTE
Use shielded four-wire cable for the process temperature connection.
2. Connect the RTD cable to the 3051S MultiVariable transmitter by
inserting the cable wires through the unused housing conduit and
connect to the four screws on the transmitter terminal block. An
appropriate cable gland should be used to seal the conduit opening
around the cable.
3. Connect the RTD cable shield wire to the ground lug in the
housing.Figure 8. 3051S MultiVariable Transmitter RTD Wiring Connection
RTD Cable AssemblyWires
Red
White
Pt 100RTD
Sensor
Ground Lug
-
7/27/2019 00825-0100-4803
14/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008Rosemount 3051SMV
14
STEP 5: FLOW CONFIGURATION
Engineering Assistant 6.1 or Later
The 3051SMV Engineering Assistant 6.1 or later is PC-based software
that performs configuration, maintenance, diagnostic functions, and
serves as the primary communication interface to the 3051S
MultiVariable transmitter with the Fully Compensated Mass and
Energy Flow Feature Board.The 3051SMV Engineering Assistant software is required to complete
the flow configuration.
Installation and Initial Setup
The following are the minimum system requirements to install the
3051SMV Engineering Assistant software:
Pentium-grade Processor: 500 MHz or faster Operating System: Windows 2000 or Windows XP Professional
256 MB RAM
100 MB free hard disk space
RS232 serial port or USB port (for use with HART modem)
CD-ROM
-
7/27/2019 00825-0100-4803
15/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008 Rosemount 3051SMV
15
Installing 3051SMV Engineering Assistant 6.1 or Later
1. Insert the disk into the CD-ROM.
2. Windows should detect the presence of a CD and start the
installation program. Follow the on-screen prompts to finish the
installation. If Windows does not detect the CD, use Windows
Explorer or My Computer to view the contents of the CD-ROM, and
then double click the SETUP.EXE program.
3. A series of screens (Installation Wizard) will appear and assist in
the installation process. Follow the on-screen prompts. It isrecommended to use the default installation settings.
NOTEEngineering Assistant versions 6.1 or later require the use of Microsoft .NETFramework version 2.0 or later. If .NET version 2.0 is not currently installed, thesoftware will be automatically installed during the Engineering Assistantinstallation. Microsoft .NET version 2.0 requires an additional 200 MB of diskspace.
-
7/27/2019 00825-0100-4803
16/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008Rosemount 3051SMV
16
Connecting to a Personal Computer
Figure 9 shows how to connect a computer to a 3051S MultiVariable
transmitter .
Figure 9. Connecting a PC to the 3051S MultiVariable Transmitter
1. Remove the cover from the field terminals side of the housing.
2. Power the device as outlined in Step 4: Connect Wiring and Power
Up.
3. Connect the HART modem cable to the PC.
4. On the side of the transmitter marked Field Terminals, connect
the modem mini-grabbers to the two terminals marked
PWR/COMM.
5. Launch the 3051SMV Engineering Assistant software. For more
information on launching software, see Launching Engineering
Assistant 6.1 or Later on page 20.
6. Once the configuration is complete, replace cover and tighten until
metal contacts metal to meet explosion-proof requirements.
3051SMV without OptionalProcess Temperature Connection
3051SMV with Optional ProcessTemperature Connection
RL 250
PowerSupply
Modem
PowerSupply
RL 250
Modem
-
7/27/2019 00825-0100-4803
17/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008 Rosemount 3051SMV
17
Flow Configuration
The 3051SMV Engineering Assistant is designed to guide the user
through the setup of the flow configuration for a 3051S MultiVariable
transmitter. The flow configuration screens allow the user to specify
the fluid, operating conditions, and information about the primary
element, including inside pipe diameter. This information will be used
by the 3051SMV Engineering Assistant software to create flow
configuration parameters that will be sent to the transmitter or saved
for future use.
Online and Offline Modes
The Engineering Assistant software can be used in two modes: Online
and Offline. In Online mode, the user can receive the configuration
from the transmitter, edit the configuration, send the changed
configuration to the transmitter, or save the configuration to a file. In
Offline mode, the user can create a new flow configuration and savethe configuration to a file or open and modify an existing file.
The following pages provide instructions on creating a new flow
configuration in Offline Mode. For more information on other
functionality, see the 3051S MultiVariable transmitter reference
manual (00809-0100-4803).
-
7/27/2019 00825-0100-4803
18/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008Rosemount 3051SMV
18
Basic Navigation Overview
Figure 10. Engineering Assistant Basic Navigation Overview
The Engineering Assistant software can be navigated in a variety of
ways. The numbers below correspond to the numbers shown in
Figure 10.1. The navigation tabs contain the flow configuration information. In
Offline mode, each tab will not become active until the required
fields on the previous tab are completed. In Online mode, these
tabs will be functional at all times.
-
7/27/2019 00825-0100-4803
19/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008 Rosemount 3051SMV
19
2. The Reset button will return each field within all of the flow
configuration tabs (Fluid Selection, Fluid Properties,and PrimaryElement Selection) to the values initially displayed at the start of
the configuration.
a. In Online Mode, the values will return to the initial valuesreceived from the device before the start of the configuration.
b. If editing a previously saved flow configuration, the values willreturn to those that were last saved. If starting a new flow
configuration, all entered values will be erased.3. The Back button is used to step backward through the flow
configuration tabs.
4. The Next button is used to step forward through the flow
configuration tabs. In Offline mode, the Next button will not
become active until all required fields on the current page are
completed.
5. The Help button can be clicked at any time to get a detailedexplanation of the information is required on the current
configuration tab.
6. Any configuration information that needs to be entered or reviewed
will appear in this portion of the screen.
7. These menus navigate to the Configure Flow, Basic Setup,
Device, Variables, Calibration, and Save/Send Configuration
tabs.8. These buttons navigate to Config/Setup, Device Diagnostics or
Process Variables sections.
-
7/27/2019 00825-0100-4803
20/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008Rosemount 3051SMV
20
Launching Engineering Assistant 6.1 or Later
Flow configuration for the 3051S MultiVariable transmitter is achieved
by launching the Engineering Assistant software from the START
Menu.
1. Select the Start menu >All Programs > Engineering Assistant.
Engineering Assistant will open to the screen shown in Figure 11.
2. Click the Offline button located in the lower right hand corner of the
screen shown in Figure 11.
Figure 11. Engineering Assistant Device Connection screen
-
7/27/2019 00825-0100-4803
21/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008 Rosemount 3051SMV
21
Preferences
The Preferences tab, shown in Figure 12, allows the user to select the
preferred engineering units to display and specify flow configuration
information.
1. Select the preferred engineering units.
2. If Custom Units are selected, configure the Individual Parameters.
3. Check the box if unit preferences should be retained for future
Engineering Assistant sessions.
Figure 12. Preferences Tab
-
7/27/2019 00825-0100-4803
22/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008Rosemount 3051SMV
22
Fluid Selection for Database Liquid/Gas
The Fluid Selection tab shown in Figure allows the user to choose the
process fluid.
Figure 13. Fluid Selection Tab
NOTEThe following example will show a flow configuration for the Database Gas Airused with a 405C Conditioning Orifice Plate as the primary element. Theprocedure to set up any other fluid with any other primary element will be similarto this example. Natural gases, custom liquids, and custom gases requireadditional steps during the configuration. See Section 3 of the 3051SMultiVariable transmitter reference manual (00809-0100-4803) for moreinformation.
1. Engineering Assistant may open to the Preferences tab. Using the
tabs at the top of the screen, navigate to the Fluid Selection tab.
2. Expand the Gas category (click on the + icon).
-
7/27/2019 00825-0100-4803
23/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008 Rosemount 3051SMV
23
3. Expand the Database Gas category.
4. Select Airfrom the list of database fluids.5. Enter the Nominal Operating Pressure, press the EnterorTab key.
6. Enter the Nominal Operating Temperature, press the EnterorTab
key. Engineering Assistant will automatically fill in suggested
operating ranges, as shown in Figure . These values may be edited
as needed by the user.
7. Verify that the Reference / Atmospheric Conditions are correct for
the application. These values may be edited as needed.
NOTEReference pressure and temperature values are used by Engineering Assistantto convert the flow rate from mass units to mass units expressed as standard ornormal volumetric units.
8. Click Next > to proceed to the Fluid Properties tab.
-
7/27/2019 00825-0100-4803
24/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008Rosemount 3051SMV
24
Fluid Properties
NOTEThe Fluid Properties tab is an optional step and is not required to complete aflow configuration.
The Fluid Properties tab for the database gas air is shown in
Figure 14. The user may verify that the properties of the chosen fluid
are acceptable.
1. To check density, compressibility, and viscosity of the selected fluidat other pressure and temperature values, enter a Pressure and
Temperature and click Calculate.
NOTEChanging the pressure and temperature values on the Fluid Properties tab doesnot affect the fluid configuration.
Figure 14. Fluid Properties Tab
-
7/27/2019 00825-0100-4803
25/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008 Rosemount 3051SMV
25
Primary Element Selection
The Primary Element Selection tab shown in Figure 15 allows the user
to choose the primary element.
Figure 15. Primary Element Selection Tab
Continuing with the example configuration:
1. Expand the Conditioning Orifice Plate category.
2. Select 405C/3051SFC.
3. Enter theMeasured Meter Tube Diameter (pipe ID) at a Reference
Temperature. If the meter tube diameter cannot be measured,
select a Nominal Pipe Size and Pipe Schedule to input an
estimated value for the meter tube diameter (English units only).
-
7/27/2019 00825-0100-4803
26/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008Rosemount 3051SMV
26
4. If necessary, edit the Meter Tube Material.
5. Enter the Line Size and select the Beta of the Conditioning OrificePlate. The required primary element sizing parameters will be
different depending on what primary element was selected.
6. If necessary, select a Primary Element Materialfrom the drop-down
menu.
7. Click Next > to advance to the Save / Send Configuration tab.
NOTETo be in compliance with appropriate national or international standards, betaratios and differential producer diameters should be within the limits as listed inthe applicable standards. The Engineering Assistant software will alert the user ifa primary element value exceeds these limits, but will allow the user to proceedwith the flow configuration.
-
7/27/2019 00825-0100-4803
27/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008 Rosemount 3051SMV
27
Save / Send Configuration
The Save / Send Configuration tab shown in Figure 16 allows the user
to verify, save, and send the configuration information to the 3051S
MultiVariable transmitter with the Fully Compensated Mass and
Energy Flow Feature Board.
1. Review the information under the Flow Configuration heading and
Device Configuration heading.
NOTEFor more information on device configuration, see Step 6: Verify DeviceConfiguration.
Figure 16. Save / Send Configuration Tab
-
7/27/2019 00825-0100-4803
28/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008Rosemount 3051SMV
28
2. Click on the icon above each window to edit the configuration
information in these windows. When all information is correct,move to step 3.
NOTEThe user will be notified if the configuration has been modified since it was lastsent to the transmitter. A warning message will be shown to the right of the SendFlow Data and/orSend Transmitter Data check boxes.
3. To send the configuration, click the Send To button.
NOTEThe Send Flow Data and Send Transmitter Data check boxes can be used toselect what configuration data is sent to the transmitter. If either check box isunselected, the corresponding data will not be sent.
4. The Engineering Assistant Device Connection screen will appear,
see Figure 17.
Figure 17. Engineering Assistant Device Connection Screen
-
7/27/2019 00825-0100-4803
29/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008 Rosemount 3051SMV
29
5. Click the Search button located in the lower right hand corner of
the screen. Engineering Assistant will begin to search forconnected devices.
6. When the search is completed, choose the device to communicate
with and click Send Configuration.
7. Once the configuration is finished being sent to the device, the user
will be notified by a pop-up dialog box.
NOTEAfter the configuration is sent to the device, saving the configuration file isrecommended. For more information on saving a configuration file, see the3051S MultiVariable transmitter reference manual (00809-0100-4803).
8. If finished with the configuration process, the user may close
Engineering Assistant.
-
7/27/2019 00825-0100-4803
30/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008Rosemount 3051SMV
30
STEP 6: VERIFY DEVICE CONFIGURATIONUse 3051SMV Engineering Assistant or any HART-compliant master
to communicate with and verify configuration of the 3051S
MultiVariable transmitter.
Table 1 shows the 375 Field Communicator fast keys for the Fully
Compensated Mass and Energy Flow. Table 2 shows the fast keys for
the Direct Process Variable Output.
NOTEDevice configuration procedures are given for 3051SMV Engineering Assistant6.1 or later and AMS Device Manager 9.0 or later in the 3051S MultiVariabletransmitter reference manual (00809-0100-4803).
A check () indicates the basic configuration parameters. At aminimum, these parameters should be verified as part of the
configuration and startup procedure.Table 1. Fast Keys for Fully Compensated Mass and Energy Flow
Function Fast Key Sequence
Absolute Pressure Reading and Status 1,4,2,1,5
Absolute Pressure Sensor Limits 1,4,1,5,8
Absolute Pressure Units 1,3,3,5
Alarm and Saturation Level Configuration 1,4,2,6,6
Alarm and Saturation Levels 1,4,2,6
Analog Output Trim Options 1,2,5,2Burst Mode Setup 1,4,3,3,3
Burst Mode Options 1,4,3,3,4
Callendar-van Dusen Sensor Matching 1,2,5,5,4
Configure Fixed Variables 1,2,4 Damping 1,3,7Diaphragm Seals Information 1,4,4,5 Differential Pressure Low Flow Cutoff 1,4,1,1,6Differential Pressure Reading and Status 1,4,2,1,4
Differential Pressure Sensor Trim Options 1,2,5,3 Differential Pressure Zero Trim 1,2,5,3,1Continued on Next Page
-
7/27/2019 00825-0100-4803
31/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008 Rosemount 3051SMV
31
Differential Pressure Units 1,3,3,4
Energy Rate Units 1,3,3,2
Energy Reading and Status 1,4,2,1,2
Equipped Sensors 1,4,4,4
Field Device Information 1,4,4,1
Flow Calculation Type 1,4,1,1,2
Flow Rate Units 1,3,3,1Flow Reading and Status 1,4,2,1,1Gage Pressure Reading and Status 1,4,2,1,6
Gage Pressure Sensor Limits 1,4,1,5,9
Gage Pressure Units 1,3,3,6
LCD Configuration 1,3,8
Loop Test 1,2,2
Module Temperature Reading and Status 1,4,2,1,8
Module Temperature Units 1,3,3,8Poll Address 1,4,3,3,1
Process Temperature Reading and Status 1,4,2,1,7 Process Temperature Sensor Mode 1,4,1,6,8Process Temperature Sensor Trim Options 1,2,5,5
Process Temperature Unit 1,3,3,7 Ranging the Analog Output 1,2,5,1Recall Factory Trim Settings 1,2,5,2,3
Sensor Information 1,4,4,2
Static Pressure Sensor Lower Trim (AP Sensor) 1,2,5,4,2
Static Pressure Sensor Trim Options 1,2,5,4
Static Pressure Sensor Zero Trim (GP Sensor) 1,2,5,4,1
Status 1,2,1 Tag 1,3,1Test Flow Calculation 1,2,3
Totalizer Configuration 1,4,1,3Totalizer Reading and Status 1,4,2,1,3
Totalizer Units 1,3,3,3
Variable Mapping 1,4,3,4
Write Protect 1,3,5,4
Table 1. Fast Keys for Fully Compensated Mass and Energy Flow
Function Fast Key Sequence
-
7/27/2019 00825-0100-4803
32/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008Rosemount 3051SMV
32
Table 2. Fast Keys for Direct Process Variable Output
Function Fast Key Sequence
Absolute Pressure Reading and Status 1,4,2,1,2
Absolute Pressure Sensor Limits 1,4,1,2,8
Absolute Pressure Units 1,3,3,2
Alarm and Saturation Level Configuration 1,4,2,6,6
Alarm and Saturation Levels 1,4,2,6
Analog Output Trim Options 1,2,4,2
Burst Mode Setup 1,4,3,3,3Burst Mode Options 1,4,3,3,4
Callendar-van Dusen Sensor Matching 1,2,4,5,4 Damping 1,3,7Diaphragm Seals Information 1,4,4,4
Differential Pressure Reading and Status 1,4,2,1,1
Differential Pressure Sensor Trim Options 1,2,4,3 Differential Pressure Zero Trim 1,2,4,3,1 Differential Pressure Units 1,3,3,1
Equipped Sensors 1,4,4,3
Field Device Information 1,4,4,1
Gage Pressure Reading and Status 1,4,2,1,3
Gage Pressure Sensor Limits 1,4,1,2,9
Gage Pressure Units 1,3,3,3
LCD Configuration 1,3,8
Loop Test 1,2,2
Module Temperature Reading and Status 1,4,2,1,5
Module Temperature Units 1,3,3,5
Poll Address 1,4,3,3,1
Process Temperature Reading and Status 1,4,2,1,4
Process Temperature Sensor Trim Options 1,2,4,5
Process Temperature Unit 1,3,3,4 Ranging the Analog Output 1,2,4,1Recall Factory Trim Settings 1,2,4,2,3Sensor Information 1,4,4,2
Continued on Next Page
-
7/27/2019 00825-0100-4803
33/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008 Rosemount 3051SMV
33
Static Pressure Sensor Lower Trim (AP Sensor) 1,2,4,4,2
Static Pressure Sensor Trim Options 1,2,4,4
Static Pressure Sensor Zero Trim (GP Sensor) 1,2,4,4,1
Status 1,2,1 Tag 1,3,1 Transfer Function 1,3,6Variable Mapping 1,4,3,4Write Protect 1,3,5,4
Table 2. Fast Keys for Direct Process Variable Output
Function Fast Key Sequence
-
7/27/2019 00825-0100-4803
34/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008Rosemount 3051SMV
34
STEP 7: TRIMTHE TRANSMITTER
Transmitters are shipped fully calibrated per request or by the factory
default of full scale.
Zero Trim
A zero trim is a single-point adjustment used for compensating
mounting position and line pressure effects on static and differential
pressure sensors. When performing a zero trim, ensure that the
equalizing valve is open and all wet legs are filled to the correct level.
The transmitter will only allow up to 5% of URL zero error to be
trimmed.
Performing a Zero Trim Using the 375 Field Communicator
1. Equalize or vent the transmitter and connect the 375 (for more
information on connecting the 375, see Figure 6 on page 11).
2. If the device is equipped with a static pressure sensor, zero thesensor by inputting the following fast key sequence at the 3051S
MultiVariable transmitter menu:
3. Use the zero trim (selection 1) for a transmitter equipped with a
gage static pressure sensor or lower sensor trim (selection 2) for a
transmitted equipped with an absolute static pressure sensor.
NOTEWhen performing a lower sensor trim on an absolute pressure sensor, it ispossible to degrade the performance of the sensor if inaccurate calibrationequipment is used. Use a barometer that is at least three times as accurate asthe absolute sensor of the 3051S MultiVariable transmitter.
4. Zero the differential pressure sensor by inputting the following fastkey sequence at the 3051S MultiVariable transmitter menu:
FlowFast Keys
Direct OutputFast Keys Description
1,2,5,4 1,2,4,4 Static Pressure Sensor Trim Options
FlowFast Keys
Direct OutputFast Keys Description
1,2,5,3,1 1,2,4,3,1 Differential Pressure Sensor Zero Trim
-
7/27/2019 00825-0100-4803
35/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008 Rosemount 3051SMV
35
PRODUCT CERTIFICATIONS
Approved Manufacturing Locations
Rosemount Inc. Chanhassen, Minnesota USA
Emerson Process Management GmbH & Co. Wessling, Germany
Emerson Process Management Asia Pacific Private Limited
Singapore
Beijing Rosemount Far East Instrument Co., LTD Beijing, China
Ordinary Location Certification for FM
As standard, the transmitter has been examined and tested to
determine that the design meets basic electrical, mechanical, and fire
protection requirements by FM, a nationally recognized testing
laboratory (NRTL) as accredited by the Federal Occupational Safety
and Health Administration (OSHA).
European Directive Information
The EC declaration of conformity for all applicable European directives
for this product can be found at
www.emersonprocess.com/rosemount. A hard copy may be obtained
by contacting an Emerson Process Management representative.
ATEX Directive (94/9/EC)Emerson Process Management complies with the ATEX Directive.
-
7/27/2019 00825-0100-4803
36/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008Rosemount 3051SMV
36
European Pressure Equipment Directive (PED) (97/23/EC)
Models with Differential Pressure Ranges = 2 to 5 inclusive with
Static Pressure = Range 4 only. P9 and P0 options also.
All other Model 3051SMV Pressure Transmitters
Sound Engineering Practice
Transmitter Attachments: Diaphragm Seal - Process Flange -
Manifold Sound Engineering Practice
Primary Elements, Flowmeter
See appropriate Primary Element QIG
Electro Magnetic Compatibility (EMC) (2004/108/EC)
EN 61326-1:2006 and EN 61326-2-3:2006
Hazardous Locations Certifications
North American Certifications
FM ApprovalsE5 Explosion-proof for Class I, Division 1, Groups B, C, and D;
dust-ignition proof for Class II and Class III, Division 1, Groups E,
F, and G; hazardous locations; enclosure Type 4X, conduit seal
not required.
I5 Intrinsically Safe for use in Class I, Division 1, Groups A, B, C,
and D; Class II, Division 1, Groups E, F, and G; Class III, Division
1; Class I, Zone 0 AEx ia IIC when connected in accordance withRosemount drawing 03151-1206; Non-incendive for Class I,
Division 2, Groups A, B, C, and D Enclosure Type 4X
For entity parameters see control drawing 03151-1206.
-
7/27/2019 00825-0100-4803
37/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008 Rosemount 3051SMV
37
Canadian Standards Association (CSA)
All CSA hazardous approved transmitters are dual seal certifiedper ANSI/ISA 12.27.01-2003.
E6 Explosion-proof for Class I, Division 1, Groups B, C, and D;
Dust-Ignition-Proof for Class II and Class III, Division 1, Groups
E, F, and G; suitable for Class I, Division 2, Groups A, B, C, and
D, CSA Enclosure Type 4X; conduit seal not required.
I6 Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D
when connected in accordance with Rosemount drawings03151-1207;
For entity parameters see control drawing 03151-1207.
European Certifications
I1 ATEX Intrinsic Safety
Certificate No.: 08ATEX0064X II 1G
Ex ia IIC T4 (Ta = -60 C to 70 C) -HART
1180
Special conditions for safe use (x)
The apparatus is not capable of withstanding the 500V test as defined
in Clause 6.3.12 of EN 60079-11. This must be considered during
installation.
N1 ATEX Type n
Certificate No.: Baseefa 08ATEX0065X II 3 GEx nA nL IIC T4 (Ta = -40 C TO 70 C)
Ui = 45 Vdc max
IP66
Input Parameters
Loop / Power Groups
Ui = 30 V HART
Ii = 300 mA HART
Pi = 1.0 W HART
Ci = 14.8 nF HART
Li = 0 HART
-
7/27/2019 00825-0100-4803
38/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008Rosemount 3051SMV
38
Special conditions for safe use (x)
The apparatus is not capable of withstanding the 500V insulation testrequired by Clause 6.8.1 of EN 60079-15. This must be taken into
account when installing the apparatus.
ND ATEX Dust
Certificate No.: BAS01ATEX1303X II 1 D
T105C (-20 C Tamb 85 C)
Vmax = 42.4 volts max
A = 24 mAIP66
1180
Special conditions for safe use (x)
1. The user must ensure that the maximum rated voltage and current
(42.4 volts, 22 milliampere, DC) are not exceeded. All connections
to other apparatus or associated apparatus shall have control overthis voltage and current equivalent to a category ib circuit
according to EN 60079-11.
2. Cable entries must be used which maintain the ingress protection
of the enclosure to at least IP66.
3. Unused cable entries must be filled with suitable blanking plugs
which maintain the ingress protection of the enclosure to at least
IP66.
-
7/27/2019 00825-0100-4803
39/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008 Rosemount 3051SMV
39
4. Cable entries and blanking plugs must be suitable for the ambient
range of the apparatus and capable of withstanding a 7J impacttest.
5. The 3051S-* must be securely screwed in place to maintain the
ingress protection of the enclosure.
E1 ATEX Flameproof
Certificate No.: KEMA 00ATEX2143X II 1/2 G
Ex d IIC T6 (-50 C Tamb 65 C)
Ex d IIC T5 (-50 C Tamb 80 C)Vmax = 42.4V
1180
Special conditions for safe use (x)
1. Appropriate ex d blanking plugs, cable glands, and wiring needs to
be suitable for a temperature of 90 C.
2. This device contains a thin wall diaphragm. Installation,
maintenance and use shall take into account the environmental
conditions to which the diaphragm will be subjected. The
manufacturers instructions for maintenance shall be followed in
detail to assure safety during its expected lifetime.
3. The 3051SMV does not comply with the requirements of IEC
60079-1 Clause 5.2, Table 2 for all joints. Contact Emerson
Process Management for information on the dimensions of
flameproof joints.
Japanese Certifications
E4 TIIS Flameproof
Consult factory for availability
I4 TIIS Intrinsically Safe
Consult factory for availability
-
7/27/2019 00825-0100-4803
40/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008Rosemount 3051SMV
40
INMETRO Certifications
E2 INMETRO Flameproof
BR-Ex d IIC T6/T5
I2 INMETRO Intrinsic Safety
BR-Ex ia IIC T4
China (NEPSI) Certifications
E3 China Flameproof
Ex d II B+H2T3~T5I3 China Intrinsic Safety
Ex ia IIC T3/T4
IECEx Certifications
I7 IECEx Intrinsic Safety
Certificate No.: IECExBAS08.0025X
Ex ia IIC T4 (Ta = -60 C to 70 C) -HART
IP66
Special conditions for safe use (x)
The 3051SMV HART 4-20mA is not capable of withstanding the 500V
test as defined in clause 6.3.12 of IEC 60079-11. This must be taken
into account during installation.
Input Parameters
Loop / Power Groups
Ui = 30 V HART
Ii = 300 mA HART
Pi = 1.0 W HART
Ci = 14.8 nF HART
Li = 0 HART
-
7/27/2019 00825-0100-4803
41/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008 Rosemount 3051SMV
41
N7 IECEx Type n
Certificate No.: IECExBAS08.0026XEx nAnL IIC T4 (Ta = -40 C to 70 C)
Ui = 45 Vdc MAX
IP66
Special conditions for safe use (x)
The apparatus is not capable of withstanding the 500 V insulation test
required by Clause 6.8.1 of IEC 60079-15.
E7 IECEx Flameproof
Certificate No.: IECExKEM08.0010X
Ex d IIC T6 (-50 C Tamb 65 C)
Ex d IIC T5 (-50 C Tamb 80 C)
Vmax = 42.4V
Special conditions for safe use (x)
1. Appropriate ex d blanking plugs, cable glands, and wiring needs tobe suitable for a temperature of 90 C.
2. This device contains a thin wall diaphragm. Installation,
maintenance and use shall take into account the environmental
conditions to which the diaphragm will be subjected. The
manufacturers instructions for maintenance shall be followed in
detail to assure safety during its expected lifetime.
3. The 3051SMV does not comply with the requirements of IEC60079-1 Clause 5.2, Table 2 for all joints. Contact Emerson
Process Management for information on the dimensions of
flameproof joints.
-
7/27/2019 00825-0100-4803
42/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008Rosemount 3051SMV
42
Combinations of Certifications
Stainless steel certification tag is provided when optional approval is
specified. Once a device labeled with multiple approval types is
installed, it should not be reinstalled using any other approval types.
Permanently mark the approval label to distinguish it from unused
approval types.
K1 Combination of E1, I1, N1, and ND
K2 Combination of E2 and I2
K4 Combination of E4 and I4
K5 Combination of E5 and I5
K6 Combination of E6 and I6
K7 Combination of E7, I7, and N7
KA Combination of E1, E6, I1, and I6
KB Combination of E5, E6, I5, and I6
KC Combination of E5, E1, I5 and I1KD Combination of E5, E6, E1, I5, I6, and I1
-
7/27/2019 00825-0100-4803
43/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008 Rosemount 3051SMV
43
-
7/27/2019 00825-0100-4803
44/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008Rosemount 3051SMV
44
-
7/27/2019 00825-0100-4803
45/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008 Rosemount 3051SMV
45
-
7/27/2019 00825-0100-4803
46/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008Rosemount 3051SMV
46
NOTES
-
7/27/2019 00825-0100-4803
47/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008 Rosemount 3051SMV
47
NOTES
-
7/27/2019 00825-0100-4803
48/48
Quick Installation Guide00825-0100-4803, Rev AA
September 2008Rosemount 3051SMV
NOTES