002a Schneider Reclosers N-Series Recloser 1.0

17
Automated Overhead N-Series Recloser now with ‘N-green’ option 2014

description

Reclosers N- Series

Transcript of 002a Schneider Reclosers N-Series Recloser 1.0

Page 1: 002a Schneider Reclosers N-Series Recloser 1.0

Automated Overhead

N-Series Reclosernow with ‘N-green’ option

2014

Page 2: 002a Schneider Reclosers N-Series Recloser 1.0

2

Specification overview.

38 kV system voltage.

16 kA fault make capacity.

170 kV insulation level.

800 A continuous current.

N-Series Recloser

Page 3: 002a Schneider Reclosers N-Series Recloser 1.0

3

● Vacuum interrupters● SF6 gas filled 316 grade stainless steel tank /

optional dry air ‘N-green’ option.● Surge arrester mounting brackets on tank.● Field fitting kit includes mounting bracket, bushing

boots and 400 A, 3 m cable kits.● Current Transformers (CTs) on all 3 phases built

into tank.● Capacitive Voltage Transformers (CVTs) moulded

into all 6 bushings.● Open and Close solenoids controlled from control

cubicle.● SF6 gas / dry air pressure monitoring and lockout.● Clearly visible external pointer.● Hookstick trip lever provided.

N-Series – Overview & Operation

Page 4: 002a Schneider Reclosers N-Series Recloser 1.0

4

1 Tank2 SF6 insulating gas (dry air option)

3 Surge arrester bracket

4 HV cable tail

5 Bushing boot

6 Bushing

7 Central conductor

8 Capacitive Voltage Transformer

(CVT)

9 Current Transformer (CT)

10 Vacuum interrupter

11 Contacts

12 Flexible connection

N-Series – Cross Section

Page 5: 002a Schneider Reclosers N-Series Recloser 1.0

5

N-Series – “N-green” option – 38 kV

Silicone rubber insulators

Identical Performances to the standard N-Series (N38)

SF6 replaced with dry air at same pressure

General construction of tank remains unchanged

Components remain in a dry environment (no corrosion)

Use of Silicone rubber parts

Provides additional insulation due to the absence of SF6

Environment friendly

N series “N-Green” option

= N38 - SF6 + Silicone Rubber Shields + Dry Air

Page 6: 002a Schneider Reclosers N-Series Recloser 1.0

6

9 Current Transformer

N-Series – Current Transformer (CT)

Page 7: 002a Schneider Reclosers N-Series Recloser 1.0

7

8 Capacitive Voltage Transformer

N-Series – Capacitive Voltage Transformer (CVT)

Page 8: 002a Schneider Reclosers N-Series Recloser 1.0

8

10 Vacuum Interrupters

N-Series – Vacuum Interrupters

Page 9: 002a Schneider Reclosers N-Series Recloser 1.0

9

13 Push rod

14 Close solenoid

15 Mechanism plate

16 Opening spring

17 Contact spring

18 Latch

19 Trip bar

20 Trip bar armature

21 Trip solenoid

22 Manual trip lever

23 SCEM

24 Control cable

N-Series – Trip & Close Mechanisms

Page 10: 002a Schneider Reclosers N-Series Recloser 1.0

10

12 Flexible connection

13 Push rod

14 Close solenoid

15 Mechanism plate

16 Opening spring

17 Contact spring

18 Latch

19 Trip bar

20 Trip bar armature

21 Trip solenoid

22 Manual trip lever

Capacitor discharge in Close solenoid,

attracting the Mechanism Plate upward,

Push rods force contact close and

latch tongues rest on trip bar.

Contacts are held in closed positionby latch tongues.

N-Series – Close Mechanism

Page 11: 002a Schneider Reclosers N-Series Recloser 1.0

11

12 Flexible connection

13 Push rod

14 Close solenoid

15 Mechanism plate

16 Opening spring

17 Contact spring

18 Latch

19 Trip bar

20 Trip bar armature

21 Trip solenoid

22 Manual trip lever

Capacitor discharge in Trip solenoid,

attracting the Trip bar armature,

causing the Trip bar to rotate and

releasing latch & mechanism plate.

Energy stored in the Open andcontact springs opens contacts.

N-Series – Trip Mechanism

Page 12: 002a Schneider Reclosers N-Series Recloser 1.0

12

N-Series – Push Rods

Page 13: 002a Schneider Reclosers N-Series Recloser 1.0

13

23 SCEM Card

N-Series SCEM Card (11a)

Page 14: 002a Schneider Reclosers N-Series Recloser 1.0

14

23 SCEM Card

N-Series – SCEM 11a and Boss SCEM

Page 15: 002a Schneider Reclosers N-Series Recloser 1.0

15

●An N Series recloser has a:● 1 side

And a ● 2 side

●Bushings on each side are identified as● U● V● W

●The six bushings are identified as● U1, V1, W1, U2, V2, W2

●The bushing identifications do not designate which phase is connected – this is configurable via software.

N-Series – Terminal Designation

Page 16: 002a Schneider Reclosers N-Series Recloser 1.0

This completes the presentation – Thank you for your attention.

2014

Page 17: 002a Schneider Reclosers N-Series Recloser 1.0

17