L1-00-System Terminology - Rev G - P 2GSE
1.1) Summary
06-Computer Maintenance Tool
07-DS Agile OI Overview
08-DS Agile SCE Overview
09-DS Agile SMT Overview
10-DS Agile GTW Overview
11-DS Agile Management
00-System-Terminology
01-DS AGILE Presentation
02- DS Agile Architecture
03-MiCOM C264 Hardware
04-MiCOM C264 HMI
05-MiCOM C264 Overview
12-Synthesis and Questionary
L1-00-System Terminology - Rev G - P 3GSE
Summary
1) Generalities Page 4
2) Datapoint Terminology Page 9
L1-00-System Terminology - Rev G - P 4GSE
1.1) Electric Terminology
SITE
SUBSTATIONVOLTAGE
LEVEL
BAY
MODULE
L1-00-System Terminology - Rev G - P 5GSE
1.2) SCE Pre-view
SITE
SUBSTATION SUBSTATION
VOLTAGE LEVEL 1
VOLTAGE LEVEL 2
BAY FEEDER 1 BAY FEEDER 2BAY TRANSFO
SW 1 TR 1 SW 2CB 1
Position
Control
TPI
Control
Position
Control
VOLTAGE LEVEL N
L1-00-System Terminology - Rev G - P 6GSE
Primary Equipment
Control Centre Level
Process Level
Bay Level
SUBSTATION Level
1.3) Levels of Substation Control philosophy
L1-00-System Terminology - Rev G - P 7GSE
1.4) Electric definitions
SubstationSite Partition => Local/Remote substationSubstation Control Uniqueness(nb=1) The Business DB (except Cascade)
Voltage LevelAssociation of Bus Bars for Auto Volt. Regul.Often only one BB (nb 4-5-x)
BayANSI => 1 CB with associate circuits & protectionsAssociation of switchgears/transformers & functionsLocal/Remote Bay, SBMC, Bay Control UniquenessSpecial (coupler, section, feeder, transformer)Often Generic (more easy)Bay belongs to only one C264
ModulePrimary Electric Device, ANSI functions, Group of DPSpecial (CB, disconnector, transformer, AR, Sync)Often Generic (DPS/DPC association possible)
Data PointReal Time information (95% electric)At any level
L1-00-System Terminology - Rev G - P 8GSE
Summary
1) Generalities Page 4
2) Datapoint Terminology Page 9
1) Generalities
L1-00-System Terminology - Rev G - P 9GSE
2) Datapoint Terminology
REAL TIME DATA = DATAPOINTSSeveral KIND of DP
SPS Single Point StatusDPS Double Point StatusMPS Multiple Point Status
MV Measurement ValueTPI Tap Position IndicationDM Digital Measurement
SCT Single CounTerDCT Double CounTer
SPC Single Point ControlDPC Double Point ControlSP Set Point
BINARY
INPUTS
MEASUR.
&
COUNTERS
OUTPUTS
IEC61850
SPS_ST , SPC_STDPS_ST, DPC_STINS_ST
MV, WYE_MX, DEL
BCR_ST
SPC_CODPC_CO,BST_CO
L1-00-System Terminology - Rev G - P 10GSE
2.1) Supervision Datapoint Attributes
Common Invalid Unknown (IED), Self-Check Fault (Hard)+DPS invalid Jammed (00) Undefined (11)+MV, xCT invalid Open Circuit, Undefined, OverRange
Supervision
SPS,
DPS,
MPS
MV, TPI, DM
SCT, DCT
Status/Value Quality
Reset/Set Valid / FSS / Invalid
Open(01)/Close(10) Valid / FSS / Invalid
State16 Valid / FSS / Invalid
Value (Float32) Valid / FSS / Threshold / Invalid
FSS Force (auto/Manu) an Invalid DPSuppress (Make DP invalid)Substitute (Force the Status/Value of DP)
Threshold For Alarm, L,LL,LLL, H, HH, HHH with hysteresis
L1-00-System Terminology - Rev G - P 11GSE
2.2) Control Datapoint
SPC, DPC, SP
KindDirect Execute Select Before Operate One Shot Selection / Wait(cancel) / ExecuteMedium/Low Volt. HV + Control Uniqueness => order run Bay
Where Direct Execute Select Before Operate
1) SBUS/C264 DE SBOSelect Open/CloseExecute Open/Close
2) SupervisionOI DE, SBO like pop-up SBO pop-upSCADA DE DE, SBO
3) Hardware/IED DE SBO
L1-00-System Terminology - Rev G - P 12GSE
2.3) Controls
StationOperator Right / Gateway channel in controlRemote/Local StationDevice operating mode (operational, not stand-by…)Control Uniqueness Station (GOOSE)Topological ILK
BayControl Uniqueness Bay (order running)Remote/Local Bay
Module (switch, transformer..)Current Module State/Value
Bay interlock open/close (including module specific conditions)LockingAuto/Manu Dependency (automation running)Recuperation Time
Inner Simple “Built-in” AutomationOutput / feedback input Delays….Physical SBO, Direct Execute, 3 phases, Communication IED