library.ukpowernetworks.co.uklibrary.ukpowernetworks.co.uk/library/asset/b591491d-46… · XLS...
Transcript of library.ukpowernetworks.co.uklibrary.ukpowernetworks.co.uk/library/asset/b591491d-46… · XLS...
EAS 01-0000aOverhead Line Material Lists
Version 1.0Date - 06/07/2016
EAS 05-0000a Protection Relays Materials List Version: 1.1 Date - 02/06/2017
#VALUE!Hyperlinked, Click to Jump To.
#VALUE!
#VALUE!
#VALUE!
#VALUE!
#VALUE!
#VALUE!
#VALUE!
#VALUE!
#VALUE!
#VALUE!
#VALUE!
#VALUE!
Suppliers
Autoswitching
EAS 05-0000a Protection Relays Materials List Version: 1.1 Date - 02/06/2017
UK Power Networks List of Approved Suppliers#VALUE!
Supplier GE Grid Solutions (formerly Alstom T&D)
Address
Contact Cyehun CECENContact No 01785-236808E/mail
Website
Supplier GE Multilin
Address
Contact Cyehun CECENContact No 01785-236808E/mailWebsite
Supplier Schneider Electric
Address
Contact Paul BrownContact No 07801-772203E/mail
Website
Supplier Siemens Reyrolle
Address
Contact Andy EllisonContact No 0191-4015240E/mail
Website
Supplier ABB Ltd.
Address
Contact Steve FreemanContact No 01925-741111E/mail
Website
Supplier Fundamentals Ltd.
Address
Contact Panos PapapanagouContact No 01793-575589E/mail
St Leonards BuildingRedhill Business ParkStaffordST16 1WTUnited Kingdom
http://www.gegridsolutions.com/alstomenergy/grid/products-services/product-catalogue/electrical-grid-new/digital-substation/substation-automation/agile-protection-relays/index.html
St Leonards BuildingRedhill Business ParkStaffordST16 1WTUnited Kingdom
[email protected]://www.gedigitalenergy.com/Protection_Control.htm
Schneider Electric9 Opal Way,Stone Business Park,StaffordshireST15 0SSUnited Kingdom
http://www.schneider-electric.com/products/ww/en/4700-protection-relays-by-range/
Siemens Protection Devices LimitedPO. Box 8North Farm RoadHebburnNE31 1TZUnited Kingdom
http://w3.siemens.com/smartgrid/global/en/products-systems-solutions/Protection/Pages/overview.aspx
Daresbury ParkDaresburyWarringtonChesireWA4 4BTUnited Kingdom
http://new.abb.com/substation-automation/products/protection-control/relion-product-family
4 Hillmead Enterprise ParkMarshall RoadSwindonWiltshireSN5 5FZUnited Kingdom
Website
Supplier VYSIION (formerly RFL Communications)
Address
Contact Michael GrimshawContact No 01249-446500E/mailWebsite
Supplier Eltime Controls
Address
Contact Brett KeyesContact No 01621-859500E/mailWebsite
Supplier Arteche Power Grid
Address
Contact Cameron E. DruryContact No 07786-421857E/mailWebsite
Supplier Schweitzer Engineering Laboratories
Address
Contact Prashant JulkaContact No 01138-8231932E/mailWebsite
Supplier Toshiba International (Europe) Ltd.
Address
Contact Gareth BarberContact No 07976086743E/mail [email protected] http://www.toshiba-tds.com/tandd/products
Supplier List for Drop DownGE Grid SolutionsGE MultilinSchneiderABBFundamentalsRFLEltimeSiemensReyrolleArtecheSchweitzerWestermoAshridgeToshiba
http://www.fundamentalsltd.co.uk
Connect 17Avon Way, Langley ParkChippenhamWiltshireSN15 1GGUnited Kingdom
[email protected]://www.vysiion.co.uk
Hall RoadMaldonEssexCM9 4NFUnited Kingdom
[email protected]://www.eltime.co.uk
Derio Bidea 28Zabalondo48100 MungiaBizkiaSpain
[email protected]://www.arteche.com
Suite 66-68ICON Business Centre4100 Park ApproachThorpe ParkLeedsLS15 8GBUnited Kingdom
[email protected]://www.selinc.com
3 Furzeground WayStockley ParkUxbridgeMiddlesexUnited KingdomUB11 1EZ
EAS 05-0000a Protection Relays Materials List Version: 1.1 Date - 02/06/2017
#VALUE! FALSE
Description Manufacturer Stores Code Generic Order Code Preffered Order Code Function Technical Details Typical Application Comments NOC FALSE#VALUE! FALSE
MiCOM P14N GE Grid Solutions N/A P14NB*1*3C0500A P14NB11C3C0500A Feeder Protection
Supply Voltage - 24-250Vdc, 110-240Vac
185
FALSE
I/O Availability - 11 / 12 FALSE
Function Keys - 3 FALSE
LEDs - 8 FALSE
CT Inputs - 3ph and N FALSE
CT Range- 1/5A FALSE
EF CT Range - Standard EF CT FALSE
TCS - Suitable For! FALSE
AR - No FALSE
Case Size - 30TE FALSE
Communication - IEC60870-5-103 Copper FALSE
Comms Ports- 1 FALSE
Other- N/A FALSE
MiCOM P14N GE Grid Solutions N/A P14NZ11*3B0500A P14NZ11A120500A
Supply Voltage - 24-250Vdc, 110-240Vac
KCGG Retrofit Use software version J only 185
FALSE
I/O Availability - 8 / 8 FALSE
Function Keys - 0 FALSE
LEDs - 4 FALSE
CT Inputs - 3ph and N FALSE
CT Range- 1/5A FALSE
EF CT Range - Standard EF CT FALSE
AR - 4 Shots FALSE
Case Size - 20TE FALSE
Communication - Courier Comms over Copper FALSE
Other- Adaptive field voltage for KCGG FALSE
MiCOM P116 Schneider N/A P116A1N2N14111111N P116A1N2N14111111N Dual Powered Feeder Protection
Supply Voltage - 24-60Vac/dc
RMU Feeder CB Protection 183
FALSE
I/O Availability - 6 / 6 FALSE
Function Keys - Trip / Close FALSE
LEDs - 8 FALSE
CT Inputs - 3ph and N FALSE
CT Range- 1A, 0.1-40In FALSE
EF CT Range - 0.01-8 Ien FALSE
TCS - Yes if Auxilary Supply Available FALSE
AR - Yes if Auxilary Supply Available FALSE
Case Size - 157mm*184mm FALSE
Communication - IEC60870-5-103 & Modbus Copper FALSE
Comms Ports- USB Front, RS485 rear FALSE
Other- N/A FALSE
MiCOM P120 Schneider N/A P120B00T312BF1 P120B00T312BF1 Single Phase Protection
Supply Voltage - 48-250Vdc,48-240Vac
Standby Earth Fault, Earth Fault Alarm Software 11.F 106
FALSE
I/O Availability - 2 / 4 FALSE
Function Keys - 0 FALSE
LEDs - 8 FALSE
CT Inputs - 1 ph FALSE
CT Range- 0.01 - 8Ion FALSE
EF CT Range - 0.01 - 8Ion FALSE
TCS - No FALSE
AR - No FALSE
Case Size - 20TE, 4U FALSE
Communication - IEC60870-5-103 Copper FALSE
Comms Ports- RS 485 rear FALSE
Other- Input 24-250Vdc FALSE
MiCOM P122 Schneider N/A P122BOOT312CF1 P122BOOT312CF1 Feeder Protection
Supply Voltage - 48-250Vdc,48-240Vac
106
FALSE
I/O Availability - 3 / 6 FALSE
Function Keys - 0 FALSE
LEDs - 8 FALSE
CT Inputs - 3ph and N FALSE
CT Range- 1-5A FALSE
EF CT Range - 0.01 - 8Ion FALSE
TCS - Yes FALSE
AR - No FALSE
Case Size - 20TE, 4U FALSE
Communication - IEC60870-5-103 Copper FALSE
Comms Ports- RS 485 rear FALSE
Other- Input 24-250Vdc, CBF FALSE
REF615 ABB N/A HBFEAEAGABG1BAA11E HBFEAEAGABG1BAA11E Feeder Protection
Supply Voltage - 48-250Vdc, 100-240Vac
ABB 33kV Switchgear Only 160
FALSE
I/O Availability - 16 / 10 FALSE
Function Keys - 0 FALSE
LEDs - 11 FALSE
CT Inputs - 3ph and N FALSE
CT Range- Io = 1-5A FALSE
TCS - Yes FALSE
AR - Yes FALSE
Communication - IEC60870-5-103 Copper FALSE
Comms Ports- IEC60870-5-103 Copper FALSE
Other- Version 4 FALSE
REF615 ABB N/A HBFHAEAGABC1ANN21G HBFHAEAGABC1ANN21G Feeder Protection
Supply Voltage - 24-60Vdc
In Progress
FALSE
I/O Availability - 16 / 10 FALSE
Function Keys - 0 FALSE
LEDs - 11 FALSE
CT Range- Io = 1/5A FALSE
Communication - IEC61850 & Modbus FALSE
Comms Ports- RS485 & Ethernet 100Base Tx FALSE
Other- Version 5.0 FALSE
Argus C Reyrolle N/A 7SR110*-1*A12-1*A0 7SR1102-1JA12-1AA0 Feeder Protection
Supply Voltage - 24/60Vdc
2436H80003R4b-3b Lucy 11kV RMU Only 156
FALSE
I/O Availability - 3 / 5 FALSE
LEDs - 10 FALSE
CT Inputs - 4CT FALSE
CT Range- 1-5A FALSE
TCS - Yes FALSE
Case Size - E4 FALSE
Communication - IEC60870-5-103 Copper FALSE
Comms Ports- Front USB, rear RS485 FALSE
Other- Binary Threshold 19Vdc FALSE
Argus C Reyrolle N/A 7SR110*-1*A12-2*A0 7SR1101-3GA12-2CA0 Non-Directional O/C Relay
Supply Voltage - 80-250Vdc/112Vac
2436H80003R4b-3b Replacing the Argus 1, AG1-104 156
FALSE
I/O Availability - 3 / 5 FALSE
Function Keys - Down and Right Arrow FALSE
LEDs - 10 FALSE
CT Inputs - 1CT FALSE
CT Range- 1-5A FALSE
EF CT Range - SEF Input FALSE
TCS - Yes FALSE
Case Size - E4 FALSE
Communication - IEC60870-5-103 Copper FALSE
Comms Ports- Front USB, rear RS485 FALSE
Other- Binary Threshold 19Vdc FALSE
Argus M Reyrolle N/A 7SR2102-1AA11-0CAA 7SR2102-1AA11-0CAA Non-Directional O/C Relay
Supply Voltage - 80-250Vdc/112Vac
2435H85008R8b-7f 151
FALSE
I/O Availability - 19/16 FALSE
LEDs - 10 FALSE
CT Inputs - 4 FALSE
TCS - Yes FALSE
AR - No FALSE
Case Size - E6 FALSE
Communication - IEC60870-5-103 Copper FALSE
Comms Ports- Front USB, rear RS485 FALSE
Other- Binary Threshold 19Vdc FALSE
Minor Software Variant if Applicable
11kV Feeder Protection and Rough Balance BB Protection
Tamco 33KV Switchgear,Use software version J only
Feeder Protection with ARKCGG Retrofit Option
Can be powered through USB phone cable
Replacing P124s
Basic Feeder Management, 132kV Backup.
CB Fail Output is reset dominantSoftware 12.F
Non Directional OC & Directional EFARC Flash not approved for use
Autoreclose ENA assessment ongoing
Central London Secondary Switchgear Only
Non Directional OC & Non Directional EFARC Flash not approved for use
Autoreclose ENA assessment ongoing
Standby Earth Fault, Earth Fault Alarm. High Impedance REF
11/33kV Feeder Protection, 11kV Busbar Protection
Consider using 7SR2204 to minimise variation.
Replacing the Argus 1, AG1-42*
EAS 05-0000a Protection Relays Materials List Version: 1.1 Date - 02/06/2017
#VALUE! FALSE
Description Manufacturer Stores Code Generic Order Code Preffered Order Code Function Technical Details Typical Application Comments NOC FALSE
#VALUE! FALSE
MiCOM P142 GE Grid Solutions N/A P14281E*3M0460J P14281EB3M0460J
Supply Voltage - 48-125Vdc, 40-100Vac
101
FALSE
I/O Availability - 12/11 FALSE
Function Keys - 2 FALSE
LEDs - 8 FALSE
CT Inputs - 5 FALSE
VT Inputs - 4 FALSE
CT Range- 1/5A FALSE
TCS - Yes, with resistors FALSE
AR - Yes FALSE
Case Size - 40TE FALSE
Communication - IEC60870-5-103 copper, InterMiCOM, FALSE
Comms Ports- Rear RS 485 and Courier RS232 FALSE
Other- N/A FALSE
MiCOM P144 GE Grid Solutions N/A P144847B1M0610P P144847B1M0610P Directional Feeder Management Relay
Supply Voltage - 48-125Vdc, 40-100Vac
For Trial Use Only N/A
FALSE
I/O Availability - 12/11 FALSE
Function Keys - 2 FALSE
LEDs - 8 FALSE
CT Inputs - 5 FALSE
VT Inputs - 5 FALSE
CT Range- 1/5A FALSE
TCS - Yes FALSE
AR - Yes FALSE
Case Size - 40TE FALSE
Communication - K Bus FALSE
Comms Ports- Courier Standard and Rear FALSE
Other- TGFD Function FALSE
MiCOM P145 GE Grid Solutions N/A P14581E*3M0460J P14581EJ3M0460J
Supply Voltage - 48-125Vdc, 40-100Vac
101
FALSE
I/O Availability - 24/20 (4 High Break) FALSE
Function Keys - 12 FALSE
LEDs - 18 FALSE
CT Inputs - 5 FALSE
VT Inputs - 5 FALSE
CT Range- 1/5A FALSE
TCS - Yes, with resistors FALSE
AR - Yes FALSE
Case Size - 60TE FALSE
Communication - IEC60870-5-103 copper, InterMiCOM, FALSE
Comms Ports- Rear RS 485 and Courier RS232 FALSE
Other- N/A FALSE
MiCOM P14D GE Grid Solutions N/A
Supply Voltage - 24-250Vdc (110-240Vac)
MV feeder protection. 186
FALSE
I/O Availability - 11/12 FALSE
Function Keys - 3 FALSE
LEDs - 8 FALSE
CT Inputs - 4 FALSE
VT Inputs - 4 FALSE
CT Range- 1/5A FALSE
EF CT Range - Sensitive EF CT FALSE
TCS - Yes FALSE
AR - Yes FALSE
Case Size - 30TE FALSE
Communication - IEC60870-5-103 copper FALSE
Comms Ports- USB Front Port and Rear RS485 FALSE
Other- N/A FALSE
MiCOM P14D GE Grid Solutions N/A
Supply Voltage - 24-250Vdc (110-240Vac)
SEF or High Impedance Fault Detection Software 50J only approved 186
FALSE
I/O Availability - 11/12 FALSE
Function Keys - 3 FALSE
LEDs - 8 FALSE
CT Inputs - 4 FALSE
VT Inputs - 4 FALSE
CT Range- 1/5A FALSE
EF CT Range - Sensitive EF CT FALSE
TCS - Yes FALSE
AR - Yes FALSE
Case Size - 30TE FALSE
Communication - IEC60870-5-103 copper FALSE
Comms Ports- USB Front Port and Rear RS485 FALSE
Other- N/A FALSE
MiCOM P14D GE Grid Solutions N/A Directional Feeder Protection
Supply Voltage - 24-250Vdc (110-240Vac)
KCEG Series Retrofit. 186
FALSE
I/O Availability - 8/8 FALSE
Function Keys - 3 FALSE
LEDs - 8 FALSE
CT Inputs - 4 FALSE
VT Inputs - 4 FALSE
CT Range- 1/5A FALSE
EF CT Range - Standard EF CT FALSE
TCS - Yes FALSE
AR - YES FALSE
Case Size - 30TE FALSE
Communication - Courier comms copper FALSE
Comms Ports- USB Front Port and Rear RS485 FALSE
Other- N/A FALSE
Argus M 7SR22 Reyrolle N/A 7SR220*-2AA11-0DA0 7SR2204-2AA11-0DA0 Directional Feeder Protection
Supply Voltage - 30-220V DC, 19V DC Binary Input Threshold
2435H85009R8b-7f Replacing Reyrolle Argus 2 AG2-412 151
FALSE
I/O Availability - 13/14 FALSE
Function Keys - 6 FALSE
LEDs - 8 FALSE
CT Inputs - 5 FALSE
VT Inputs - 4 FALSE
CT Range- 1/5A FALSE
TCS - YES FALSE
AR - YES FALSE
Case Size - E8 FALSE
Communication - IEC60870-5-103 copper via RS 485 FALSE
Comms Ports- Front USB and Rear RS485 FALSE
Other- N/A FALSE
Minor Software Variant if Applicable
Directional Feeder Management RelayMulti-function
Advanced Feeder Protection where high I/O is required
11kV busbar and feeder protection
Consider the P14D where the I/O requirements can be met.
Note:NVD protection can be configured from derived and measured residual voltage.
In the case of residual voltage measurement one of the relay voltage elements is utilised, hence SCADA cct.
Analogue data is not available.
TGFD Trial OnlyOHL on Peterson Coil Earthed Networks
Directional and non-directional OC and EF distribution feeder management
relay.Multi-function (as per P142 with check
synchronising).
Directional Auto-Reclose and Check Sync.
132kV Backup & Check Sync, 33kV Transformer Backup
P14D**1C3C0500A P14DL11C3C0500A Advanced Directional Feeder Protection (incl. Auto reclose and Directional Load
Blinding).
33kV Feeder HSOC and Backup Protection on MV Switchgear.Software 50J only approved
P14D**1C3C0500A P14DZ21C3C0500A Advanced Directional Feeder Protection (incl. Auto reclose and Directional Load
Blinding). SEF CT Input and HIF function
P14D*11A130500A P14DL11A130500A Adapted Field Voltage for KCEG RetrofitSoftware 50J only approved
MV Switchgear Feeder and RB, without fibre
EAS 05-0000a Protection Relays Materials List Version: 1.1 Date - 02/06/2017
#VALUE! FALSE
Description Manufacturer Stores Code Generic Order Code Preffered Order Code Function Technical Details Typical Application Comments NOC FALSE
#VALUE! FALSE
MiCOM P94V GE Grid Solutions N/A P94V*11*3*0500A
Supply Voltage - 24-250Vdc (110-240Vac)
NVD protection (open delta winding) 187
FALSE
I/O Availability - 8/8 FALSE
Function Keys - 0 FALSE
LEDs - 4 FALSE
CT Inputs - 0 FALSE
VT Inputs - 4 FALSE
CT Range- N/A FALSE
EF CT Range - N/A FALSE
TCS - No FALSE
AR - No FALSE
Case Size - 20TE FALSE
Communication - IEC60870-5-103 copper FALSE
Comms Ports- USB Front Port and Rear RS485 FALSE
Other- N/A FALSE
MiCOM P94V GE Grid Solutions N/A P94VP11*3*0500A P94VB11A3B0500A
Supply Voltage - 24-250Vdc (110-240Vac)
NVD protection (5 limb VT only) 187
FALSE
I/O Availability - 8/8 FALSE
Function Keys - 0 FALSE
LEDs - 4 FALSE
CT Inputs - 0 FALSE
VT Inputs - 4 FALSE
CT Range- N/A FALSE
EF CT Range - N/A FALSE
TCS - YES FALSE
AR - No FALSE
Case Size - 20TE FALSE
Communication - IEC60870-5-103 copper FALSE
Comms Ports- USB Front Port and Rear RS485 FALSE
Other- N/A FALSE
MiCOM P921 Schneider N/A P9210AST312CD1 P9210AST312CD1 Voltage Protection
Supply Voltage - 48-250Vdc (48-240Vac)
NVD protection (open delta winding) 129
FALSE
I/O Availability - 2/4 FALSE
Function Keys - 0 FALSE
LEDs - 4 FALSE
CT Inputs - 0 FALSE
VT Inputs - 5 FALSE
CT Range- N/A FALSE
EF CT Range - N/A FALSE
TCS - No FALSE
AR - No FALSE
Case Size - 20TE FALSE
Communication - IEC60870-5-103 copper FALSE
Other- N/A FALSE
Argus 7SR157 Reyrolle N/A 7SG15157*-5GA12-2CA0 7SG1577-5GA12-2CA0 Check and System Synchronising
Supply Voltage - 80-250 Vdc (115Vac)
2436H80010R4e-2a Not Complete
FALSE
I/O Availability - 3/5 FALSE
Function Keys - 0 FALSE
LEDs - 10 FALSE
CT Inputs - 0 FALSE
VT Inputs - 2 FALSE
CT Range- N/A FALSE
EF CT Range - N/A FALSE
TCS - No FALSE
AR - No FALSE
Case Size - E4 FALSE
Communication - IEC60870-5-103 FALSE
Comms Ports- Front USB Port and Rear RS485 FALSE
Other- 19V Binary Input Threshold FALSE
Argus 7SR158 Reyrolle N/A 7SG1587-5GA12-2*A0 7SG1587-5GA12-2DA0 Voltage and Frequency Protection.
Supply Voltage - 80-250 Vdc (115Vac)
2436H80011R2d-1a Low Frequency Demand Discinnection 196
FALSE
I/O Availability - 6/8 FALSE
Function Keys - 0 FALSE
LEDs - 10 FALSE
CT Inputs - 0 FALSE
VT Inputs - 3 FALSE
CT Range- n/a FALSE
EF CT Range - n/a FALSE
TCS - n/a FALSE
AR - n/a FALSE
Case Size - E4 FALSE
Communication - IEC60870-5-103 FALSE
Comms Ports- Front USB Port and Rear RS485 FALSE
Other- 19V Binary Input Threshold FALSE
Minor Software Variant if Applicable
P94VB11A3B0500A Voltage and Frequency Protection with RoCoF and measured NVD.
Software Version 50J OnlyRefer to manufacturer for limitations on
Frequency Protection
Voltage and Frequency Protection with RoCoF and measured NVD.
Software Version 50J OnlyRefer to manufacturer for limitations on
Frequency Protection
UPKN Approved IED for LFDD40-160V, 50/60Hz
EAS 05-0000a Protection Relays Materials List Version: 1.1 Date - 02/06/2017
#VALUE! FALSE
Description Manufacturer Stores Code Generic Order Code Preffered Order Code Function Technical Details Typical Application Comments NOC FALSE
#VALUE! FALSE
MFAC GE Grid Solutions N/A MFAC14S1A*0001A MFAC14S1AC0001A
Supply Voltage - 15-185Vac Setting Range
137
FALSE
I/O Availability - 4 NO Contacts FALSE
CT Inputs - N/A FALSE
VT Inputs - N/A FALSE
CT Range- N/A FALSE
EF CT Range - N/A FALSE
Case Size - Single Element, MiDOS Size 3 (15TE) FALSE
Other- Standard 6inch Metrosil FALSE
MFAC GE Grid Solutions N/A MFAC34V1A*3001A MFAC34V1AA3001A
Supply Voltage - 25-175Vac Setting Range
137
FALSE
I/O Availability - 2 NO Contacts FALSE
CT Inputs - N/A FALSE
VT Inputs - N/A FALSE
CT Range- N/A FALSE
EF CT Range - N/A FALSE
Case Size - Three Element, MiDOS Size 6 (30TE) FALSE
Other- Standard 6inch Metrosil FALSE
MCAG GE Grid Solutions N/A MCAG14SSB*0**0A MCAG14SSBE0220A
Supply Voltage - N/A
137
FALSE
I/O Availability - 2 NO, Segregated FALSE
CT Inputs - 1 FALSE
VT Inputs - N/A FALSE
CT Range- 1A FALSE
EF CT Range - N/A FALSE
Case Size - Single Element, MiDOS Size 3 (15TE) FALSE
Other- 220ohm Resistor FALSE
MCAG GE Grid Solutions N/A MCAG14SSB*0**0A MCAG14SSBC0000A
Supply Voltage - N/A
10-40% range based on 1A input. 137
FALSE
I/O Availability - 2 NO, Segregated FALSE
CT Inputs - 1 FALSE
VT Inputs - N/A FALSE
CT Range- 1A FALSE
EF CT Range - N/A FALSE
Case Size - Single Element, MiDOS Size 3 (15TE) FALSE
Other- N/A FALSE
MCAG GE Grid Solutions N/A MCAG34VSBE0220A MCAG34VSBE0220A
Supply Voltage - N/A
High Impedance BZ Protection Schemes 137
FALSE
I/O Availability - 2 NO, Segregated FALSE
CT Inputs - 3 FALSE
VT Inputs - N/A FALSE
CT Range- 1A FALSE
EF CT Range - N/A FALSE
Case Size - Three Element, MiDOS Size 6 (30TE) FALSE
Other- Hnad Reset Flag/ 220 ohm Resistor FALSE
MBCI/Translay S GE Grid Solutions N/A MBCI01V1AB0761B MBCI01V1AB0761B
Supply Voltage - 110-125Vdc
132kV feeder diversions AN 39
FALSE
I/O Availability - 40 FALSE
Function Keys - N/A FALSE
LEDs - N/A FALSE
CT Inputs - N/A FALSE
VT Inputs - N/A FALSE
CT Range- 1A FALSE
EF CT Range - N/A FALSE
TCS - N/A FALSE
AR - N/A FALSE
Case Size - Size 6 (30TE) FALSE
Communication - N/A FALSE
Inter-Relay Fibre- N/A FALSE
Comms Ports- N/A FALSE
Other- Private Pilots Only FALSE
5B3 Reyrolle N/A 7PG2311-1DA30-1BA0 7PG2311-1DA30-1BA0 Single Element High Impedance Relay
Supply Voltage - 15-270Vac
AN
FALSE
I/O Availability - 3NO FALSE
CT Inputs - N/A FALSE
VT Inputs - N/A FALSE
CT Range- N/A FALSE
EF CT Range - N/A FALSE
Case Size - E3 case 4U high FALSE
Other- N/A FALSE
Solkor Rf Reyrolle N/A 7PG2111-1DA30-0D*0 7PG2111-1DA30-0DD0 Line Differential
Supply Voltage - N/A
AN
FALSE
I/O Availability - 3NO FALSE
CT Inputs - N/A FALSE
VT Inputs - N/A FALSE
CT Range- 5A FALSE
Case Size - E6, 4U High FALSE
Other- N/A FALSE
Solkor Rf Reyrolle N/A 7PG2111-1DA30-0D*0 7PG2111-1DA30-0DB0 Line Differential
Supply Voltage - N/A
AN
FALSE
I/O Availability - 3NO FALSE
CT Inputs - 1A FALSE
VT Inputs - N/A FALSE
CT Range- N/A FALSE
Case Size - E6, 4U High FALSE
Other- Solkor R/Rf mode FALSE
Solkor R/Rf Reyrolle N/A 7PG2112-0AA00-0AA0 15kV Isolation Transformer
Supply Voltage - N/A
For use with Solkor Rf AN
FALSE
CT Inputs - N/A FALSE
VT Inputs - N/A FALSE
CT Range- N/A FALSE
EF CT Range - N/A FALSE
Other- N/A FALSE
Solkor Rf Reyrolle N/A 7PG21**-1DA30-0**0 7PG2132-1CC40-1AA0 Pilot Supervision
Supply Voltage - 110Vac
Hand Reset Flag AN
FALSE
I/O Availability - 2NO, 2NC FALSE
CT Inputs - N/A FALSE
VT Inputs - N/A FALSE
CT Range- N/A FALSE
EF CT Range - N/A FALSE
Case Size - E4, 4U High FALSE
Other- 50Hz FALSE
Solkor Rf Reyrolle N/A 7PG21**-1DA30-0D*0 7PG2144-1CC40-1CE0 Pilot Supervision
Supply Voltage - 125Vdc
AN
FALSE
I/O Availability - 2NO, 2NC FALSE
CT Inputs - N/A FALSE
VT Inputs - N/A FALSE
CT Range- N/A FALSE
EF CT Range - N/A FALSE
Case Size - E4, 4U High FALSE
Other- N/A FALSE
Minor Software Variant if Applicable
Voltage Calibrated High Speed Differential Protection
High Impedance Schemes.BEF and REF Protection
Used in TAMCO 33kV Switchgear Tender
Voltage Calibrated High Speed Differential Protection
High Impedance Schemes.BBP and BZ Protection
Current Calibrated High Speed Differnetial Protection
High Impedance Schemes.REF Protection
20-80% range based on 1A input. Standard 220 ohm resistor for 1A CT
Current Calibrated High Speed Differnetial Protection
LPN High Impedance Schemes. LV/HVREF on impedance earthed
transformers.
Current Calibrated High Speed Differnetial Protection
20-80% range based on 1A input. Standard 220 ohm resistor for 1A CT
Differential feeder protection and Intertripping over private metallic pilots
Optional Extras: - 1. Pilot Isolation Tx with Filter –
HN0068002.2. Pilot Isolation Tx without Filter –
ZC0244002.3. Pilot Supervision Isolation Tx –
ZC0243003. Extras include;-
MRTP, MRTP02T1AA0001C – pilot supervision.
MVTW, MVTW03T1AA0751D – destabilising and intertripping.
BEF, 33kV Feeder, Restricted Earth Fault (HV and LV)
Used in Siemens NXPlus MV Framework for 33kV Feeder Main Protection.
Metallic Pilot for use on 33 and 11kV feeder protection
Metallic Pilot for use on 33 and 11kV feeder protection
For use on Solkor Rf schemes, Send End. 110V ac
For use on Solkor Rf schemes, Receive End
5kV Isolation, Self Reset Flag and Contacts
EAS 05-0000a Protection Relays Materials List Version: 1.1 Date - 02/06/2017
#VALUE! FALSE
Description Manufacturer Stores Code Generic Order Code Preffered Order Code Function Technical Details Typical Application Comments NOC FALSE
#VALUE! FALSE
MiCOM P443 GE Grid Solutions N/A P44381E*3M0710M P44381EP3M0710M
Supply Voltage - 48-125Vdc (40-100Vac)
132kV feeder distance protection 128
FALSE
I/O Availability - 24/16 8 HB FALSE
Function Keys - 10 FALSE
LEDs - 18 FALSE
CT Inputs - 4 FALSE
VT Inputs - 5 FALSE
CT Range- 1/5A FALSE
TCS - Yes FALSE
AR - Yes FALSE
Case Size - 80TE FALSE
Communication - IEC60870-5-103 copper FALSE
Inter-Relay Fibre- Dual channel 1300nm single-mode fi FALSE
Comms Ports- InterMiCOM and Courier Rear Port. FALSE
Other- N/A FALSE
MiCOM P445 GE Grid Solutions N/A P445817*3M0350J P445817D3M0350J Distance protection
Supply Voltage - 48-125Vdc (40-100Vac)
142
FALSE
I/O Availability - 16/8 4HB FALSE
Function Keys - 2 FALSE
LEDs - 8 FALSE
CT Inputs - 4 FALSE
VT Inputs - 5 FALSE
CT Range- 1/5A FALSE
TCS - Yes FALSE
AR - Yes FALSE
Case Size - 60TE FALSE
Communication - IEC60870-5-103 fiber or copper FALSE
Comms Ports- InterMiCOM and Courier Rear Port. FALSE
Other- N/A FALSE
Siprotec 7SA522 Siemens N/A 7SA5221-5AB22-0EA0 Distance protection
Supply Voltage - 110-250Vdc (115-230Vac)
V4.74 Feeder Protection 58
FALSE
I/O Availability - 8/16 FALSE
Function Keys - 4 FALSE
LEDs - 14 FALSE
CT Inputs - 4 FALSE
VT Inputs - 4 FALSE
CT Range- 1A FALSE
TCS - Yes FALSE
AR - No FALSE
Case Size - 1/2 19” FALSE
Communication - IEC60870-5-103 copper FALSE
Other- N/A FALSE
Minor Software Variant if Applicable
Distance protection with subcycle tripping and blocking Single Mode Fibre Option!
Advanced Option, Consider P543/6
Basic distance protection, 33kV and 132kVretrofit option for size restricted
retrofit
Purchased without a FO option to keep Case size at 60TE.
Autoreclose and Check Sync Not Assessed
Limited I/O and protection options, see technical brochure.
3 pole tripping mode only.
EAS 05-0000a Protection Relays Materials List Version: 1.1 Date - 02/06/2017
#VALUE! FALSE
Description Manufacturer Stores Code Generic Order Code Preffered Order Code Function Technical Details Typical Application Comments NOC FALSE
#VALUE! FALSE
MiCOM P543 GE Grid Solutions N/A P54381E*3M0610M P54381ES3M0610M
Supply Voltage - 48-125 Vdc (40-100 Vac)
116
FALSE
I/O Availability - 16/7 + 4HB FALSE
Function Keys - 10 FALSE
LEDs - 18 FALSE
CT Inputs - 5 FALSE
VT Inputs - 5 FALSE
CT Range- 1/5A FALSE
TCS - Yes FALSE
AR - Yes FALSE
Case Size - 60TE FALSE
Communication - IEC60870-5-103 copper FALSE
Inter-Relay Fibre- Unit via 850nm multi-mode, dual cha FALSE
Comms Ports- RS485, InterMicom & Courier Rear FALSE
Other- N/A FALSE
MiCOM P544 GE Grid Solutions N/A P54481E*3M0610M P54481ES3M0610M
Supply Voltage - 48-125 Vdc (40-100 Vac)
116
FALSE
I/O Availability - 16/7 + 4HB FALSE
Function Keys - 10 FALSE
LEDs - 18 FALSE
CT Inputs - 5 FALSE
VT Inputs - 5 FALSE
CT Range- 1/5A FALSE
TCS - Yes FALSE
AR - Yes FALSE
Case Size - 60TE FALSE
Communication - IEC60870-5-103 copper FALSE
Inter-Relay Fibre- Unit via 850nm multi-mode, dual cha FALSE
Comms Ports- RS485, InterMicom & Courier Rear FALSE
Other- N/A FALSE
MiCOM P546 GE Grid Solutions N/A P54681E*3M0710M P54681ES3M0710M
Supply Voltage - 48-125 Vdc (40-100 Vac)
116
FALSE
I/O Availability - 24/16 + 8HB FALSE
Function Keys - 10 FALSE
LEDs - 18 FALSE
CT Inputs - 8 FALSE
VT Inputs - 5 FALSE
CT Range- 1/5A FALSE
TCS - Yes FALSE
AR - Yes FALSE
Case Size - 80TE FALSE
Communication - IEC60870-5-103 copper FALSE
Inter-Relay Fibre- Unit via 850nm multi-mode, dual cha FALSE
Comms Ports- RS485, InterMicom & Courier Rear FALSE
Other- N/A FALSE
MiCOM P521 Schneider N/A P521BOGT312DE1
Supply Voltage - 24-250Vdc
130
FALSE
I/O Availability - 5/8 FALSE
Function Keys - 0 FALSE
LEDs - 4 FALSE
CT Inputs - 4 FALSE
VT Inputs - 0 FALSE
TCS - Yes FALSE
AR - No FALSE
Case Size - 30TE FALSE
Communication - IEC60870-5-103 copper FALSE
Inter-Relay Fibre- 1300nm single-mode, single channel. FALSE
Other- N/A FALSE
Solkor N Reyrolle N/A 7SG1811-*DC10-0EC0 7SG1811-7DC10-0EC0 Line Differential
Supply Voltage - 110/220Vdc
2646H80006R6 108
FALSE
I/O Availability - 9/7 FALSE
CT Inputs - 4 FALSE
VT Inputs - 0 FALSE
CT Range- 1/5A FALSE
AR - No FALSE
Case Size - E8 Case 4U High FALSE
Communication - IEC60870-5-103 copper FALSE
Inter-Relay Fibre- 1300nm optical fibre 49km FALSE
Comms Ports- RS485 FALSE
Other- N/A FALSE
RED ABB N/A Line Differential
Supply Voltage - 24-60Vdc
LPN Central Network Ongoing
FALSE
I/O Availability - 16/10 FALSE
LEDs - 11 FALSE
CT Inputs - 4 FALSE
CT Range- 1/5A FALSE
TCS - Yes FALSE
Communication - IEC 61850 and Modbus FALSE
Comms Ports- RS485 & Ethernet 100Base Tx FALSE
Other- Product Version 5 FP1 FALSE
GRL150 Toshiba N/A GRL150-410A-10-10 GRL150-410A-10-10
Supply Voltage - 110Vdc
145
FALSE
CT Inputs - 4 FALSE
VT Inputs - N/A FALSE
CT Range- 1/5A FALSE
EF CT Range - N/A FALSE
Inter-Relay Fibre- 1300nm Single Mode FALSE
Comms Ports- RS485 Comms Port FALSE
Other- 3ph Oc and EF protection FALSE
EB 110 Toshiba N/A EB-110 EB-110 20kv Isolation Tx
Supply Voltage - N/A
For use with GRL150 N/A
FALSE
CT Inputs - N/A FALSE
VT Inputs - N/A FALSE
CT Range- N/A FALSE
EF CT Range - N/A FALSE
Communication - N/A FALSE
Other- N/A FALSE
Minor Software Variant if Applicable
Line Differential for 33 and 132kV applications
33 & 132kV Feeder Unit Protection, with check sync, subcycle differential and in
zone transformer protection
Multimode Mode Fibre Unit Channel with c37.94 compatibility for UMUX. For
Single Mode applications use 'U' optionAutoreclose and Check Sync Not
Assessed
Line Differential for 33 and 132kV applications
33 & 132kV Feeder Unit Protection, no check sync
Multimode Mode Fibre Unit Channel with c37.94 compatibility for UMUX. For
Single Mode applications use 'U' optionAutoreclose and Check Sync Not
Assessed
Line Differential for 132kV applications, includes revert to distance functionality.
132kV Feeder Unit Protection breaker and a half & mesh feeder topologies.
Double set of 3ph VT’s.No Check Sync
Multimode Mode Fibre Unit Channel with c37.94 compatibility for UMUX. For
Single Mode applications use 'U' optionAutoreclose and Check Sync Not
Assessed
Two Ended Current (Line) Differential, Feeder Unit Protection.
Basic Unit Feeder unit protection, 33kV and 11kV feeders
Fibre Pilot for use on 132, 33 and 11kV feeder protection.
Replacing 7SG1811-7CC10-0EB0, Fibre Comms and 48V Input Voltage.
RED615 HBDDAEAGAHC1ANA21G
RED615 HBDDAEAGAHC1ANA21G
Any additional usage to be agreed with Asset Management.
Line Differential with Intertripping with Integrated 5kV Isolation
Pilot Wire Based Protection (capable of function on low quality pilots)
Includes CT Ratio Matching, Relay Logic, Inrush Current Detection, Integral
IT Scheme
Included for Trial. Please consider for 11 & 33kV Unit Protection
Included for Trial. Please consider for 11 & 33kV Unit Protection
EAS 05-0000a Protection Relays Materials List Version: 1.1 Date - 02/06/2017
#VALUE! FALSE
Description Manufacturer Stores Code Generic Order Code Preffered Order Code Function Technical Details Typical Application Comments NOC FALSE
#VALUE! FALSE
MiCOM P642 GE Grid Solutions N/A P6428*7E3M0040J P642827E3M0040J
Supply Voltage - 48-125 Vdc (40-100 Vac)
153
FALSE
I/O Availability - 8/8 + 4HB FALSE
Function Keys - Yes FALSE
LEDs - 18 FALSE
CT Inputs - 8 FALSE
VT Inputs - 2 FALSE
CT Range- 1/5A FALSE
TCS - Yes FALSE
AR - N/A FALSE
Case Size - 40TE FALSE
Communication - IEC60870-5-103 copper FALSE
Comms Ports- RS485 and Second Rear Courier FALSE
Other- N/A FALSE
MiCOM P643 GE Grid Solutions N/A P6438*7F3M0040K P643827F3M0040K
Supply Voltage - 48-125 Vdc (40-100 Vac)
153
FALSE
I/O Availability - 16/16 + 4HB FALSE
Function Keys - Yes FALSE
LEDs - 18 FALSE
CT Inputs - 12 FALSE
VT Inputs - 4 FALSE
CT Range- 1/5A FALSE
TCS - Yes FALSE
AR - N/A FALSE
Case Size - 60TE FALSE
Communication - IEC60870-5-103 copper FALSE
Comms Ports- RS485 and Second Rear Courier FALSE
Other- N/A FALSE
Duobias M 7SR242 Reyrolle N/A 7SR2423-2AA11-0AA0 Transformer Protection, 2 winding
Supply Voltage - 30-220Vdc
2662H85001R8b-7c Grid Transformer Differential 150
FALSE
I/O Availability - 19/14 FALSE
LEDs - 24 FALSE
CT Inputs - 6 + 2EF FALSE
VT Inputs - 1 FALSE
CT Range- 1/5A FALSE
TCS - Yes FALSE
Case Size - E10 Case 4U High FALSE
Communication - IEC60870-5-103 over Copper FALSE
Comms Ports- RS 485 rear port and front USB FALSE
Other- 19V Binary Threshold FALSE
Siprotec 7UT613 Siemens N/A 7UT613*-4EB22-1AA0 7UT6131-4EB22-1AA0 Transformer Protection, 3 winding.
Supply Voltage - 60-125Vdc
V4.67 Grid Transformer Differential 113, Ongoing
FALSE
I/O Availability - 5/8 FALSE
Function Keys - 4 FALSE
LEDs - 14 FALSE
CT Inputs - 12 FALSE
CT Range- 1A Only FALSE
TCS - No FALSE
AR - No FALSE
Case Size - 1/2 19" FALSE
Communication - IEC60870-5-103 copper FALSE
Comms Ports- RS485 FALSE
Other- trigger level 19V FALSE
Argus 7SR23 DAD Reyrolle N/A 7SR2302-1AA12-0CA0 7SR2302-1AA12-0CA0
Supply Voltage - 30-220 Vdc
2435H85014R8b-1b 132kV Transformer Protection Replacement for the DAD-N 184
FALSE
I/O Availability - 9/8 FALSE
LEDs - 8 FALSE
CT Inputs - 4 FALSE
CT Range- 1/5A FALSE
TCS - Yes FALSE
AR - No FALSE
Case Size - E6 FALSE
Communication - IEC60870-5-103 copper FALSE
Comms Ports- RS485 plus front USB FALSE
Other- Binary Threshold - 19V FALSE
7SR23 Reyrolle N/A 7XG1520-3AA00-0DA0 7XG1520-3AA00-0DA0 Setting Resistor and Metrosil Unit
Supply Voltage - N/A
For 7SR23 N/A
FALSE
CT Inputs - N/A FALSE
VT Inputs - N/A FALSE
CT Range- N/A FALSE
EF CT Range - N/A FALSE
Other- N/A FALSE
Minor Software Variant if Applicable
Transformer Differential Protection, up to 2 winding applications
2 Winding Transformer Differential Protection
Transformer Differential Protection, up to 3 winding applications
3 Winding Transformer Differential Protection
Replacing relays above Duobias M200.For ESI immunity, Binary Input delays
required
Replacing relays above Duobias M300.Refer to manufacturer DC Supply Limitations and Opto Immunity
Numerical High Impedance Circulation Current Protection
3*Three inch, single phase metrosil (B=0.22-0.25, C=1000)
2000/1000/500 ohm resistors
EAS 05-0000a Protection Relays Materials List Version: 1.1 Date - 02/06/2017
#VALUE! FALSE
Description Manufacturer Stores Code Generic Order Code Preffered Order Code Function Technical Details Typical Application Comments NOC FALSE
#VALUE! FALSE
SuperTapp N+ Fundamentals N/A EDS 05-0001 0354 rev C
Supply Voltage - 90-140Vdc/80-260Vac
Transformer Auto Voltage Control
FALSE
I/O Availability - 6/6 FALSE
CT Inputs - 3 FALSE
VT Inputs - 2 FALSE
EF CT Range - N/A FALSE
TCS - N/A FALSE
AR - N/A FALSE
Case Size - Varies FALSE
Communication - RS 485 or Modbus FALSE
Comms Ports- Through DAM FALSE
Other- N/A FALSE
Minor Software Variant if Applicable
Transformer Automatic Voltage Controller
Parts Include;DAM FP1026
ENVOY EV10-0200Interposing Tx FP1030
Tpi Trans FTPT/2Voltage Controller FP1014-V2C3
VM & Protection RTMU/2MVT Tranducer EVCC P1 (110V) EO X10
F50
ENATS 48-5 Assessed.
EAS 05-0000a Protection Relays Materials List Version: 1.1 Date - 02/06/2017
#VALUE! FALSE
Description Manufacturer Stores Code Generic Order Code Preffered Order Code Function Technical Details Typical Application Comments NOC FALSE
#VALUE! FALSE
GCM05 GE Grid Solutions N/A GCM05XX0752 GCM05XX0752 Voltage based Intertripping
Supply Voltage - 24-125 Vdc
33kV Transformer HV protection AN 54 (Schneider)
FALSE
I/O Availability - 3NO/1NC on Intertrip Receive FALSE
CT Inputs - N/A FALSE
VT Inputs - N/A FALSE
CT Range- N/A FALSE
EF CT Range - N/A FALSE
TCS - N/A FALSE
AR - N/A FALSE
Inter-Relay Fibre- N/A FALSE
Other- N/A FALSE
C30 GE Multilin N/A Bay Controller
Supply Voltage - 125/250V AC/DC FALSE
I/O Availability - 4/2 FALSE
Case Size - 19" rack FALSE
Communication - IEC60870-5-103 copper FALSE
Inter-Relay Fibre- 1300nm Single Mode FALSE
Other- N/A FALSE
GRL150 Toshiba N/A
Supply Voltage - 110Vdc FALSE
CT Inputs - 4 FALSE
VT Inputs - N/A FALSE
CT Range- 1/5A FALSE
EF CT Range - N/A FALSE
Inter-Relay Fibre- 1300nm Single Mode FALSE
Comms Ports- RS485 Comms Port FALSE
Other- 3ph Oc and EF protection FALSE
MBCI GE Grid Solutions N/A
Supply Voltage - N/A FALSE
I/O Availability - N/A FALSE
Function Keys - N/A FALSE
LEDs - N/A FALSE
CT Inputs - N/A FALSE
VT Inputs - N/A FALSE
CT Range- N/A FALSE
EF CT Range - N/A FALSE
TCS - N/A FALSE
AR - N/A FALSE
Case Size - Size 6 (30TE) FALSE
Communication - N/A FALSE
Inter-Relay Fibre- N/A FALSE
Comms Ports- N/A FALSE
Other- Private Pilots Only FALSE
RFL 9745 GD RFL N/A GD2A0E1-00-Z09Z09 GD2A0E1-00-Z09Z09 Voice Frequency Fibre IT Multiplexer
Supply Voltage - 48/125Vdc
149
FALSE
CT Inputs - N/A FALSE
VT Inputs - N/A FALSE
CT Range- N/A FALSE
EF CT Range - N/A FALSE
Inter-Relay Fibre- Single Mode 1300nm FALSE
Other- Voice Frequency FALSE
Minor Software Variant if Applicable
Two way group intertripping of up to 4 remotely connected sites.Operates using conventional metallic pilot wires (pilot resistance from 0 to 2kΩ). Inherent 15kV isolation eliminates the need for isolated intertripping batteries. Powered directly from substation battery. Inherent self and pilot wire supervision. GCM05XX0751A = 751A - 4NO
C30-E00-HLH-F6S-HXX-MXX-PXX-UXX-W7C
C30-E00-HLH-F6S-HXX-MXX-PXX-UXX-W7C
132kV feederFibre based Inter-Tripping
Only to be used if required to match existing protection. Consider Toshiba
GRL150 or RFL9745198 ongoing assessment
Link to Numerical Current Differential Line Differential with Intertripping with Integrated 5kV Isolation
Link to Electro-Mechanical Differential Differential feeder protection and Intertripping over private metallic pilots
132kV feederFibre based Inter-Tripping For More information and Specific order
details contact RFL/Vysiion
EAS 05-0000a Protection Relays Materials List Version: 1.1 Date - 02/06/2017
#VALUE! FALSEDescription Manfacturer Stores Code Generic Order Code Preffered Order Code Function Technical Details Typical Application Comments NOC FALSE#VALUE! FALSE
SICAM BC 1703 Siemens N/A CP-5014, SM-2551 Integrated Bay Controller
Supply Voltage - 110/220Vdc, 230Vac/80W
N/A
FALSE
I/O Availability - 3.2 Cards FALSE
CT Inputs - No FALSE
VT Inputs - No FALSE
Case Size - 19 inch Rack, FALSE
Communication - IEC60870-5-103 copper FALSE
Other- User Defined Config FALSE
Recloser M 7SR224 Reyrolle N/A 7SR2243-2BB12-0CA0 7SR2243-2BB12-0CA0 Directional OC Recloser Relay
Supply Voltage - 30-220Vdc
2435H85010R8b-7d Sequence Close and Auto Switching IOTA Replacement 151
FALSE
I/O Availability - 23/22 FALSE
Function Keys - 12 FALSE
LEDs - 8 FALSE
CT Inputs - 4 FALSE
VT Inputs - 4 FALSE
CT Range- 1/5A FALSE
EF CT Range - n/a FALSE
TCS - Yes FALSE
Case Size - E10, 4U High FALSE
Communication - IEC60870-5-103 copper FALSE
Comms Ports- RS485 Rear, USB Front FALSE
Other- 88V Binary Input Threshold FALSE
LPN Complex Programmable Auto-Switching
Parts Include;CPU - CP5014, SM2551Digital Output - DO5203
Digital Input - DI5110Power Supply - PS5622
EAS 05-0000a Protection Relays Materials List Version: 1.1 Date - 02/06/2017
#VALUE! FALSE
Description Manufacturer Stores Code Generic Order Code Preffered Order Code Function Technical Details Typical Application Comments NOC FALSE
#VALUE! FALSE
MiCOM P341 GE Grid Solutions N/A P341817B3M0700J P341813B3M0700J
Supply Voltage - 48-125V (40-100V AC)
Dynamic Line Rating Only 104 issue 4
FALSE
I/O Availability - 8/7 FALSE
Function Keys - 0 FALSE
LEDs - 8 FALSE
CT Inputs - 4 FALSE
VT Inputs - 5 FALSE
CT Range- 1/5A FALSE
TCS - Yes FALSE
AR - Yes FALSE
Case Size - 40TE FALSE
Communication - IEC60870-5-103 copper FALSE
Comms Ports- RS485 plus secon Rear FALSE
Other- DLR Functionality FALSE
ION7650 Schneider N/A M7650*1*0B5E0A0E M7650B1E0B5E0A0E Panel Mounted Power Quality Meter.
Supply Voltage - 110-300Vdc
N/A
FALSE
I/O Availability - 8/7 FALSE
CT Inputs - Class 0.2 FALSE
VT Inputs - 100-600V FALSE
CT Range- 1-10A FALSE
Communication - Ethernet Serial Comms FALSE
Other- 10MB Memory FALSE
852plus Ashridge N/A 852Plus-W-V32-USB 852Plus-W-V32-USB
Supply Voltage - 82-265Vac, 90-260Vdc
132kV and 33kV transformer N/A
FALSE
I/O Availability - 0-10,0-20, 4-20mA. 4DO FALSE
CT Range- 0.25-10A FALSE
Case Size - 241*185*105mm FALSE
Comms Ports- USB Socket FALSE
Other- 3 wire PT100 input FALSE
Minor Software Variant if Applicable
Distributed generation interconnection protection relay with dynamic line rating.
Primary and Grid Substation Incomer Power Quality Monitoring
Refer to EDS 08-5040 Guidelines for the Provision of System Monitoring.
110V AC Supply
Single Winding Transformer Winding Temperature Indicator and Cooling
Controller
Wall Mounted with Auto Cool Mode. Isolated USB socket and configuration
Software.
EAS 05-0000a Protection Relays Materials List Version: 1.1 Date - 02/06/2017
#VALUE! FALSE
Discription Manufacturer Stores Code Generic Order Code Preffered Order Code Function Technical Details Typical Application Comments NOC FALSE
#VALUE! FALSE
ISTAT500 GE Grid Solutions N/A I5MTX2H3SCLLLCRX
Supply Voltage - 80-276Vac / 70-300Vdc
N/A
FALSE
I/O Availability - 3 analogue outputs one serial FALSE
CT Inputs - Class 0.2 Measured FALSE
VT Inputs - upto 4 FALSE
CT Range- Configuarable FALSE
TCS - N/A FALSE
Case Size - 160*75*124mm FALSE
Communication - Modbus RTU/TCP FALSE
Comms Ports- USB and Serial RS485 FALSE
Other- Ring Terminals FALSE
ECCC Eltime N/A ECCC-C1-E0-X10-F50
Supply Voltage - Self Powered
N/A
FALSE
I/O Availability - 0-10mA Output FALSE
CT Inputs - 0.25 Accurancy FALSE
VT Inputs - 4kV 50Hz 1 Min Isolation FALSE
CT Range- 0-1A FALSE
Other- AC Current Tranducer FALSE
EVCC Eltime N/A EVCC-P1(110)-E0-X10-F50
Supply Voltage - Self Powered
N/A
FALSE
I/O Availability - 0-10mA Output FALSE
CT Inputs - 0.25 Accurancy FALSE
VT Inputs - 4kV 50Hz 1 Min Isolation FALSE
VT Range- 110V FALSE
Other- AC Voltage Transducer FALSE
Minor Software Variant if Applicable
Advanced 3ph Transducer, V, I, P, Q, S, PF, PA, f, %THD, MD
SCADA Analogues where CT/VT arrangement is uncertain and RTU has
no serial capability.
AC Current Transducer, Self-Powered Zero Based Output.
SCADA Analogues where CT/VT arrangement are known and RTU has no
serial capability.
0.25 Accuracy, 4kV 50Hz 1 minute isolation. 0-1A CT Input, Self-Powered,
0-10mA Output.
AC Voltage Transducer, Self-Powered Zero Based Output.
SCADA Analogues where CT/VT arrangement are known and RTU has no
serial capability.
0.25 Accuracy, 4kV 50Hz 1 minute isolation. 110V Input Voltage, Self-
Powered, 0-10mA Output,
EAS 05-0000a Protection Relays Materials List Version: 1.1 Date - 02/06/2017
#VALUE! FALSE
Description Manufacturer Stores Code Generic Order Code Preffered Order Code Function Technical Details Typical Application Comments NOC FALSE
#VALUE! FALSE
MiCOM P593 GE Grid Solutions N/A P593601A0M000* P593601A0M0000B Fibre Optic to Electrical signal Interface.
Supply Voltage - 19 -300Vdc
155
FALSE
I/O Availability - N/A FALSE
Function Keys - N/A FALSE
CT Inputs - N/A FALSE
Case Size - 20TE FALSE
Communication - fibre to X.21 FALSE
Other- X.21 Interface FALSE
KITZ102 GE Grid Solutions N/A KITZ10201####2AE* KITZ10201####2AE*
Supply Voltage - 24-105Vdc
Relay SCADA Comms N/A
FALSE
CT Inputs - N/A FALSE
VT Inputs - N/A FALSE
CT Range- N/A FALSE
Case Size - 57.5 x 163 x 216 mm FALSE
Communication - K-Bus to RS232 FALSE
Other- N/A FALSE
MDW-45 Westermo N/A 3617-0001 RS232 – 485 Converter
Supply Voltage - 9.6-57.6Vdc
Relay SCADA Comms N/A
FALSE
CT Inputs - N/A FALSE
VT Inputs - N/A FALSE
CT Range- N/A FALSE
Case Size - 34 x 123 x 121 mm FALSE
Other- N/A FALSE
7XV5650 Siemens N/A 7XV5650-0BA00 7XV5650-0BA00 820nm Fibre – RS485 Converter
Supply Voltage - 24-250Vdc (110-220Vac)
Relay SCADA Comms N/A
FALSE
CT Inputs - N/A FALSE
VT Inputs - N/A FALSE
CT Range- N/A FALSE
EF CT Range - N/A FALSE
Case Size - 90 x 75 x 105 mm FALSE
Inter-Relay Fibre- RS485 D 9pin & 850nm ST FALSE
Other- DIN-rail mounted FALSE
7XV5662 Siemens N/A 7XV5662-0AC00 7XV5662-0AC00 Fibre to Pilot converter.
Supply Voltage - 24-250Vdc (110-220Vac)
N/A
FALSE
CT Inputs - N/A FALSE
VT Inputs - N/A FALSE
CT Range- N/A FALSE
EF CT Range - N/A FALSE
Other- 128 kBit/s38.4 kBit/s FALSE
Minor Software Variant if Applicable
Optical/Electrical and Electrical/Optical signal conversion between a MiCOM P54* relay and Telecoms equipment
K-Bus to RS232 communications Interface for Courier Protocol.
(1 optical channel) Not suited for PROFIBUS applications. Serial line
structure up to 115kBaud. Connection to protection relays with RS485 interface via 9-pole SUB-D-plug. Connection to PC or modem via optical fibre 820nm,
ST-plug for optical fibre 62.5/125μm. For mounting on DIN-rail.
Unit protection fibre to copper converterFor synchronous operation with 7SD52,
7SD610, 7SA6, 7SA52
5-kV isolation of unit analogue outputs towards the pilot wires. Connection to
protection unit via FO cable for 62.5/125 μm and 820nm wavelength, max. distance 1.5 km, ST-connectors,
Synchronous serial data 128 kBit/s, Asynchronous serial data rate max. 38,4
kBit/s