Chapter 0 1 OptoSpan OTS-10 Advanced C/DWDM Platform System Overview

Transcript of  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Page 1:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 0 1

OptoSpan OTS-10

Advanced C/DWDM

Platform

System Overview

Page 2:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 0 i

OTS-10 System Overview System Overview

Copyright © 2018 OptoSpan. All rights reserved.

No part of this documentation may be reproduced in any form or by any means or used to make any derivative

work (such as translation, transformation, or adaptation) without prior, express and written permission from

OptoSpan.

OptoSpan reserves the right to revise this documentation and to make changes in content from time to time

without obligation on the part of OptoSpan to provide notification of such revision or changes.

OptoSpan provides this documentation without warranty of any kind, implied or expressed, including but not limited

to, the implied warranties of merchantability and fitness for a purpose. OptoSpan may make improvements or

changes in the product(s) and/or the program(s) described in this documentation at any time.

Other brand and product names may be registered trademarks or trademarks of their respective holders.

Any rights not expressly granted herein are firmly reserved.

Page 3:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 0 i

OTS-10 System Overview

Contents

Contents ..................................................................................................................... i

List of Tables ........................................................................................................... iv

List of Figures ........................................................................................................... v

About This Guide ...................................................................................................... 8

Introduction ........................................................................................................................ 8

Conventions ....................................................................................................................... 8

System Architecture ................................................................................................. 9

1.1 Overview ...................................................................................................................... 9

OTS-10 Introduction ...................................................................................................... 9

1.2 System Main Control Panel ....................................................................................... 10

Panel Function ............................................................................................................ 10

Main Control Panel Faceplate ..................................................................................... 11

1.3 Slot 1 - 1G/s ~10G Multi-rate Channels (1GbE, 2.5G, OC48, OC192, 10GE,) ........ 13

Channel Function ........................................................................................................ 14

Channel Faceplate ...................................................................................................... 15

1.4 Slots 2-3 Booster - Mini EDFA Card.......................................................................... 15

Card Function .............................................................................................................. 16

Card Faceplate ............................................................................................................ 17

1.5 Slots 2-3 Pre - Mini EDFA Card ................................................................................ 18

Card Function .............................................................................................................. 19

Card Faceplate ............................................................................................................ 19

1.6 Slot 4 MUX/DEMUX Card ......................................................................................... 20

Card Function .............................................................................................................. 21

Card Faceplate ............................................................................................................ 22

Card Function .............................................................................................................. 28

Card Faceplate ............................................................................................................ 28

1.7 Fan and Power .......................................................................................................... 29

Page 4:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 0 ii

OTS-10 System Overview

Power Supply .............................................................................................................. 29

DC-48V power corresponding type ............................................................................. 30

AC power corresponding type ..................................................................................... 30

System Functions and Features ............................................................................ 32

2.1 System Functions ...................................................................................................... 32

2.2 System Features ....................................................................................................... 35

System Access Capability ........................................................................................... 36

Ethernet Service Processing Capability ...................................................................... 36

Administration and Management........................................................................... 38

3.1 Introduction ................................................................................................................ 38

3.2 Web Graphical User Interface (WebGUI) .................................................................. 38

3.3 Command Line Interface (CLI) .................................................................................. 47

3.4 Helpful Tips ................................................................................................................ 48

Networking Applications and Configurations....................................................... 49

4.1 Application Advantages ............................................................................................. 49

High Integration ........................................................................................................... 49

Flexible Configuration .................................................................................................. 49

Network Management ................................................................................................. 50

4.2 Networking Application .............................................................................................. 53

Point-to-Point Network ................................................................................................ 53

Ring Application .......................................................................................................... 54

Stack Application ......................................................................................................... 56

Advanced Management .......................................................................................... 58

5.1 Fault Management .................................................................................................... 58

Alarm Hierarchy ........................................................................................................... 58

Alarm List..................................................................................................................... 59

5.2 Performance Monitoring ............................................................................................ 62

Performance Data ....................................................................................................... 62

Performance Data Reporting and Collection............................................................... 62

5.3 Memory Backup......................................................................................................... 63

Page 5:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 0 iii

OTS-10 System Overview

5.4 Configuration Management ....................................................................................... 63

Equipment Configuration ............................................................................................. 63

Page 6:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 0 iv

OTS-10 System Overview

List of Tables

Table 1 Names and functions of all parts at the front panel...................................................... 11

Table 2 Names and functions of all parts at the back panel ..................................................... 13

Table 3 1G/s ~ 10G/s Multi-Rate Card Faceplate Description .................................................. 15

Table 4 1G/s ~ 10G/s Multi-Rate Card Interface Description ................................................... 15

Table 5 Booster – Mini EDFA Card Spec Rated Gain ............................................................... 16

Table 6 Booster – Mini EDFA Card Faceplate Description ....................................................... 17

Table 7 Booster – Mini EDFA Interface Description ................................................................. 17

Table 8 Pre – Mini EDFA Card Spec ........................................................................................ 18

Table 9 Pre – Mini EDFA Card Faceplate Description .............................................................. 19

Table 10 Pre – Mini EDFA Interface Description ...................................................................... 20

Table 11 Card Faceplate Description ........................................................................................ 22

Table 12 Card Faceplate Description ........................................................................................ 29

Page 7:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 0 v

OTS-10 System Overview

List of Figures

Figure 1 OTS-10 Appearance ..................................................................................................... 9

Figure 2 Slot Arrangement ........................................................................................................ 10

Figure 3 Slot numbering............................................................................................................ 11

Figure 4 Indicates all parts of the front panel............................................................................ 11

Figure 5 Names of all parts at the back panel .......................................................................... 13

Figure 6 1G/s ~ 10G/s multi-rate card Slots ............................................................................. 13

Figure 7 1G/s ~ 10G/s multi-rate channel Faceplate ................................................................ 15

Figure 8 Booster – Mini EDFA card Slots ................................................................................. 15

Figure 9 Booster – Mini EDFA card Faceplate ......................................................................... 17

Figure 10 Pre – Mini EDFA card Slots ...................................................................................... 18

Figure 11 Pre – Mini EDFA card Faceplate .............................................................................. 19

Figure 12 Mux/Demux card Slots ............................................................................................. 20

Figure 13 Mux/Demux Faceplate .............................................................................................. 22

Figure 14 Mux/Demux Faceplate .............................................................................................. 28

Figure 15 DC power .................................................................................................................. 30

Figure 16 DC power .................................................................................................................. 30

Figure 17 Connecting the power cord ....................................................................................... 31

Figure 18 Login Prompt ..............................................................Error! Bookmark not defined.

Figure 19 Web GUI .....................................................................Error! Bookmark not defined.

Figure 20 Homepage ..................................................................Error! Bookmark not defined.

Figure 21 System Information .....................................................Error! Bookmark not defined.

Figure 22 Time ............................................................................Error! Bookmark not defined.

Figure 23 Overview .....................................................................Error! Bookmark not defined.

Figure 24 Interface ......................................................................Error! Bookmark not defined.

Figure 25 IP&Routing ..................................................................Error! Bookmark not defined.

Figure 26 Manage SNMP ...........................................................Error! Bookmark not defined.

Figure 27 Alarm ..........................................................................Error! Bookmark not defined.

Figure 28 Timeout .......................................................................Error! Bookmark not defined.

Page 8:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 0 vi

OTS-10 System Overview

Figure 29 Account .......................................................................Error! Bookmark not defined.

Figure 30 Save ............................................................................Error! Bookmark not defined.

Figure 31 Upload/Download .......................................................Error! Bookmark not defined.

Figure 32 System Log .................................................................Error! Bookmark not defined.

Figure 33 Fault Log .....................................................................Error! Bookmark not defined.

Figure 34 Reboot ........................................................................Error! Bookmark not defined.

Figure 35 Logout Prompt ............................................................Error! Bookmark not defined.

Figure 36 SNMP manager maps .............................................................................................. 50

Figure 37 Traps transmission ................................................................................................... 51

Figure 38 Static route solution .................................................................................................. 52

Figure 39 Dynamic route solution ............................................................................................. 52

Figure 40 Basic CWDM application .......................................................................................... 53

Figure 41 Figure 24 Basic DWDM applications ........................................................................ 53

Figure 42 DWDM applications with big span loss .................................................................... 53

Figure 43 DWDM 8 channel single fiber bi-directional transmission ........................................ 54

Figure 44 Single fiber, bi-directional, 1+1 protection or Ring without EDFA ............................ 55

Figure 45 Single fiber, bi-directional, 1+1 protection or Ring with pre-EDFA ........................... 55

Figure 46 Network management port stacking ......................................................................... 56

Figure 47 Block diagram of optical wavelength stack ............................................................... 57

Figure 48 Alarm Hierarchy Map ................................................................................................ 58

Page 9:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 1 7

OTS-10 System Overview

Warning!

Do not open the cover

Opening the cover of this equipment will void the warranty.

This product has an electric shock hazard.

Do not use if equipment is defective

In case of abnormal conditions like fumes, peculiar smell, strange sounds, etc., stop use of equipment immediately in case

fire or electric shock occurs

Unplug from its source. Do not damage the power wires

Do not scratch, damage, or stretch the power wires—the power wires may break and fire or electric shock may occur.

Hold the plug when plugging it in/out

When plugging in or pulling out the power wires, please make sure to hold the plug with your hand. Stretching the wires

may damage them and cause electric shock or fire.

Plug/junction board cleaning

Please note that if the plug and junction board are dusty upon connection, fire or electric shock may occur.

Don’t interfere with ventilation

Do not place the equipment in positions that will block ventilation, or place objects on or near the vents. The internal temperature may increase and cause fire or defects.

Placing the equipment at the following type of locations will shorten the life of the product and thereby cause faults: Very damp or dusty locations, locations which experience continuous vibration, direct sunlight, high-temperature locations

Page 10:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 1 8

OTS-10 System Overview

About This Guide

Introduction

This document includes an introduction to the OptoSpan exclusive OTS-10, including system architecture, card functions,

configuration, features, and network application.

Conventions

This section includes notes, diagrams, and images. These examples contain sample data that may vary from the actual

data on an installed system.

Page 11:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 1 System Architecture 9

OTS-10 System Overview

System Architecture

This chapter provides a system level overview of OptoSpan’s OTS-10 optical transport system.

This chapter contains the following topics:

OptoSpan’s OTS-10 overview

System Architecture

1.1 Overview

OTS-10 Introduction

The OTS-10 is a 1U mini-chassis multi-service platform with a flexible design. It supports 3 modular slots with two hot-

swappable EDFA cards and one MUX/DEMUX card. It has 8 channels of 1G support transport, 10G Ethernet services, and

OC48 and OC192 SONET services. The OTS-10 is a cost-effective solution specifically designed for carriers who require a

highly reliable network.

Sub-rack

The OTS-10 Unit is designed to be mounted on two vertical rack mounting rails in a standard 19” wide cabinet. Two front

mounting rails are used for four mounting points, using the flanges provided at the front of each OTS-10.

The positions for rails and how to install the OTS-10 are shown in Figure 1:

Figure 1 OTS-10 Appearance

With a design based on the 19-inch standard for widespread compatibility, OTS-10 can be installed in a 19-inch rack. The

OTS-10 unit is 44.4mm x 440mm x 393mm (height x width x depth). The OTS-10 chassis frame weight is 7.5kg without

cards.

1

Page 12:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 1 System Architecture 10

OTS-10 System Overview

Slot Description

The OTS-10 has a modular structure, utilizing pluggable cards that can be plugged into or pulled out of a sub-rack. There

are 4 slots in the OTS-10 unit chassis. Figure 2 illustrates the slot arrangement of an OTS-10 sub-rack.

Figure 2 Slot Arrangement

1. Slot 1: virtual slot with 8 channels - 1G, 10GE and other services.

2. Slots 2 – 3: mini-EDFA Cards.

3. Slot 4: Mux/Demux card

1.2 System Main Control Panel

The system main control panel integrates main control, real-time system control, terminal interface, network management

function, stacking function, and the auxiliary interface.

Panel Function

Main Control Module

The control module is equipped with communication CPU

CPU externally connects the following types of storage devices: large-capacity SDRAM and FLASH. Critical data of the

key databases is saved in the storage media.

OSC channel processing capability

Real-time clock function. The clock functions with Gregorian calendar dates between years 2000 to 2099

LOG information query

Auxiliary Interfaces

One Ethernet interface for network management system (10M BASE-T, RJ-45 connector)

One RS-232 standard serial interface is provided for debugging

OTS-10

Slot4

Slot2 Slot3

Page 13:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 1 System Architecture 11

OTS-10 System Overview

Main Control Panel Faceplate

The OTS-10 is a 1U Mini-chassis type Multi-service platform with a flexible configuration for various network applications.

The slots numbering is shown in Figure 3.

Figure 3 Slot numbering

The front panel is equipped with a variety of LED, CONSOLE ports, and expansion slots, as shown in Figure 4.

Figure 4 Indicates all parts of the front panel corresponding to Table 1

Table 1 Names and functions of all parts at the front panel

No. Names Silk Display Colors Description

(1) Power status LED PWR1 Green The output voltage of power supply unit 1 is normal.

Off The output voltage of power supply unit 1 is defective

or the corresponding power supply unit is not

installed.

PWR2 Green The output voltage of power supply unit 2 is normal

Off The output voltage of power supply unit 2 is defective

or the corresponding power supply unit is not installed

(2) Power and Fan fault

LED

PWR FAULT Red The two power supplies have low output or are not

installed

VViirrttuuaall SSlloott 11

Slot 2 Slot 3

Slot 4

Page 14:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 1 System Architecture 12

OTS-10 System Overview

Off The two power supplies have normal output

FAN FAULT Red One or more fans have stopped

Off All 6 fans are running normally

(3) CR LED Alarm Off No critical defect in the chassis

Red At least one critical alarm (such as LOS, bias alarm) is generated

(4) MJ LED Alarm Off No major alarm in the chassis.

Red At least one major alarm (such as Power, Fan alarm) is generated

(5) MN LED Alarm Off No minor alarm in the chassis.

Red At least one minor major alarm (such as Power, Fan alarm) is generated

(6) Node controller NC Green Node controller is NC

Off Node controller is not NC

(7) Mng LED LINK Green Management port link is established

Off Management port link is not established

ACT Blinking Green Management port send/receive frame is active

Off Management port is idle

(8) Up LINK Green Up port link is established

Off Up port link is not established

ACT Blinking Green Up port send/receive frame

(9)

Down LINK Green Down port link is established

Off Down port link is not established

ACT Blinking Green Down port send/receive frame

(10) Slot 2-4 2-3: EDFA slots

4: MUX/DEMUX slot

Page 15:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 1 System Architecture 13

OTS-10 System Overview

Figure 5 Names of all parts at the back panel

Table 2 Names and functions of all parts at the back panel

No Name Description

(1) Device Plate Displays the device’s model number

(2) Warning label Displays warning information

(3) DC/AC Terminal Terminal for connecting the power cable. There is no power switch. The Power turns on as soon as the cable is connected.

1.3 Slot 1 - 1G/s ~10G Multi-rate Channels (1GbE, 2.5G, OC48, OC192, 10GE,)

The 1G/s ~ 10G/s multi-rate channels provide 8 channels, each of which support multiple services in virtual slot 1. Long

Haul (LH) ports are the top ports and Short Haul (SH) ports are the bottom ports on the system. Compatibility is virtually

guaranteed as the OTS-10 can support many services, rates and protocols.

Figure 6 illustrates the slots used by the 1G/s ~ 10G/s multi-rate card in the OTS-10 system.

Figure 6 1G/s ~ 10G/s multi-rate card Slot

The following is the user-site’s spec of the 1G/s ~ 10 G/s multi-rate channels:

Supports the SFP/SFP+ standard

Supports Line port with 8 channels CWDM or DWDM

VViirrttuuaall SSlloott 11

Slot 2 Slot 3

Slot 4

Slot 2 Slot 3

Slot 4

Page 16:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 1 System Architecture 14

OTS-10 System Overview

Supports the user’s port with 1G ~ 10G

Performance monitoring: TX power monitoring, Rx power monitoring, LOS, bias, and SFP temperature

For example:

eight user ports with SFP/SFP+

Rate: 1 G/s ~ 10G/s

Transmitter power: -9.5dBm ~ -4dBm (850nm), -5dBm ~ -11dBm(1310nm)

Receiver sensitivity: -18dBm(850nm), -20dBm(1310nm)

Max receiver power: 0dBm(850nm), -3dBm(1310nm)

Following is the LH site’s spec of the 1G/s ~ 10 G/s multi-rate cards

8 long reach ports with CWDM or DWDM SFP/SFP+: Standard SFP for either CWDM or ITU DWDM

Rate: 1G/s ~ 10G/s

Transmitter power: >+1dBm (specified by optical module)

Max receiver power: -8dBm (specified by optical module)

Receiver sensitivity: -30dBm (specified by optical module)

Path penalty: 2dB@1600ps/nm (1550 nm)

Performance monitoring: TX power monitor, Rx power monitoring, LOS, bias, and SFP temperature

CWDM/DWDM Wavelength: 1471nm, 1491nm, 1511nm, 1531nm, 1551nm, 1571nm, 1591nm, 1611nm, or100G grid ITU

DWDM wavelength

Wavelength range: Central wavelength +/6.5 nm for CWDM, +/0.1 nm for DWDM

Channel Function

The 1G/s ~ 10 G/s multi-rate channels support the following functions:

For CWDM applications, the OTS-10 can support 80 km SM fiber distance with a 26dB loss budget; the limitation will

come by either the fiber distance or fiber loss, whichever is reached first.

For DWDM applications, the OTS-10 uses Pre-mini EDFA and Post mini EDFA so that the loss budget can be increased

to 38dB. The fiber distance is 100km without DCF usage and 140km with DCF usage. With DCF and multiple in-line EDFA

usage, the fiber transmission distance can be 800~1000km.

Hot Swappable

Laser optical transmission power detection

Page 17:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 1 System Architecture 15

OTS-10 System Overview

Laser bias current detection

Channel Faceplate

The 1G/s ~ 10G/s multi-rate channel faceplate is shown in Figure 7

Figure 7 1G/s ~ 10G/s Multi-Rate Channel Faceplate

Symbols and indicators on the 1G/s ~ 10G/s multi-rate channel faceplate are described in Table 3

Table 3 1G/s ~ 10G/s Multi-Rate Card Faceplate Description

Symbol Color Status Description

SD (SH 1-8) Green OFF Optical Module of SH 1-8 port has a bad signal

ON Optical Module of SH 1-8 port has a normal signal

SD (LH 1-8) Green OFF Optical Module of LH 1-8 port has a bad signal

ON Optical Module of LH 1-8 port has a normal signal

Table 4 1G/s ~ 10G/s Multi-Rate Card Interface Description

Symbol Description

SH 1-8 Insert SFP/SFP+ into it, it is LC optical interface.

LH 1-8 Insert SFP/SFP+ into it, it is LC optical interface

1.4 Slots 2-3 Booster - Mini EDFA Card

Figure 8 illustrates the slots used by the Booster – Mini EDFA card in the OTS-10 system.

Figure 8 Booster – Mini EDFA card Slots

VViirrttuuaall SSlloott 11

Slot 2 Slot 3

Slot 4

Page 18:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 1 System Architecture 16

OTS-10 System Overview

The following lists the physical parameters of the Booster - Mini EDFA

Weight: 0.21kg

Dimensions : 203mm x 82mm x 16.3mm (D x W x H)

The spec of Booster – Mini EDFA card is shown in Table 5

Table 5 Booster – Mini EDFA Card Spec Rated Gain

Name Minimum Default Maximum Unit

Rated Gain 12 15 18 dB Gain tuning step is 0.5dB Input signal power (Pin) -7 5 6 dBm gain=12dB

-10 2 3 dBm gain=15dB -13 -1 0 dBm gain=18dB

Signal wavelength Range

1546 1561 nm Vacuum Nominal BW for 8 channels

Total Output Power (Pout)

17 17.5 dBm Gain range from 12dB to 18dB At the APC mode, the output power can be set and work well in the actual gain range 12~18dB

Booster output Power(channel)

8 10 dBm Including connector Gain range from 12dB to 18dB

Noise Figure 6 6.8 dB This noise figure does not include the insertion loss for the OSC Filter

Amplifier Gain ripple 1.75 dB Gain range from 12dB to 18dB Room temperature

Output Power Stability -0.15 0.15 dB -13dBm<Pin<6dBm Output Power Stability over temperature

-0.35 0.35 dB -13dBm<Pin<6dBm

OSC Wavelengths:1510nm and 1570nm

Card Function

The Booster – Mini EDFA card supports the following functions:

EDFA cards are used for DWDM applications when a longer link is desired. EDFA cards are not used in CWDM

application.

For DWDM application, the OTS-10 uses Pre-mini EDFA and Post mini EDFA so that the loss budget can be increased

to 38dB. The fiber distance is 100km without DCF usage, 140km with DCF usage. With DCF and multiple in-line EDFA

usage, the fiber transmission distance can be 800~1000km.

Hot Swappable

Laser optical transmission power detection

Page 19:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 1 System Architecture 17

OTS-10 System Overview

Laser bias current detection

Mux OSC signal and traffic signal

Card Faceplate

The Booster – Mini EDFA card faceplate is shown in Figure 9.

Figure 9 Booster – Mini EDFA Card Faceplate

Symbols and indicators on the Booster – Mini EDFA card faceplate are described in Table 6.

Table 6 Booster – Mini EDFA Card Faceplate Description

Symbol Color Status Description

SD Green OFF Optical Module has a bad signal

ON Optical Module has a normal signal

ALM Red OFF No alarm

ON There is an alarm

Table 7 Booster – Mini EDFA Interface Description

Symbol Description

IN Input optical interface of traffic of the LC interface.

Out Output optical interface of traffic and OSC of the LC interface.

OSC1 Input OSC channel of 1511nm

OSC2 Input OSC channel of 1571nm

Page 20:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 1 System Architecture 18

OTS-10 System Overview

1.5 Slots 2-3 Pre - Mini EDFA Card

Figure 10 illustrates the slots used by the Pre – Mini EDFA card in the OTS-10 system.

Figure 10 Pre – Mini EDFA card Slots

Following are the physical parameters of the Pre - Mini EDFA

Weight: 0.21kg

Dimensions : 203mm x 82mm x 16.3mm (D x W x H)

The spec of Pre – Mini EDFA card is shown in Table 8

Table 8 Pre – Mini EDFA Card Spec

Rated Gain 20 25 30 dB Gain tuning step is 0.5dB Input signal power (Pin)

-20 -8 -7 dBm gain=20dB -25 -13 -12 dBm gain=25dB -30 -18 -17 dBm gain=30dB

Signal wavelength Range

1546 1561 nm Vacuum Nominal BW for 8 channels

Total Output Power (Pout)

12 12.5 dBm Gain range from 20dB to 30dB At the APC mode, the output power ca be set and work well in the actual gain range 20~30dB

Pre-amp output Power(channel)

5 dBm Including connector Gain range from 20dB to 30dB

Noise Figure 6 6.8 dB This noise figure does not include the insertion loss for the OSC Filter

Amplifier Gain ripple 1.75 dB Gain=25dB @Room temperature Output Power Stability

-0.15 0.15 dB 30dBm<Pin<-7dBm

Output Power Stability over temperature

-0.35 0.35 dB 30dBm<Pin<-7dBm

OSC Wavelengths:1510nm and 1570nm

VViirrttuuaall SSlloott 11

Slot 2 Slot 3

Slot 4

Page 21:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 1 System Architecture 19

OTS-10 System Overview

Card Function

The Pre – Mini EDFA card supports the following functions:

EDFA cards are used for DWDM applications when a longer link is desired. EDFA cards are not used in CWDM

application.

For DWDM application, the OTS-10 uses Pre-mini EDFA and Post mini EDFA so that the loss budget can be increased

to 38dB. The fiber distance is 100km limitation without DCF usage,140km with DCF usage. With DCF and multiple in-line

EDFA usage, the fiber transmission distance can be 800~1000km.

Hot Swappable

Laser optical transmission power detection

Laser bias current detection

Demux OSC signal and traffic signal

Card Faceplate

The Pre – Mini EDFA card faceplate is shown in Figure 11.

Figure 11 Pre – Mini EDFA Card Faceplate

Symbols and indicators on the Pre – Mini EDFA card faceplate are described in Table 9.

Table 9 Pre – Mini EDFA Card Faceplate Description

Symbol Color Status Description

SD Green OFF Optical Module has a bad signal

ON Optical Module has a normal signal

ALM Red OFF No alarms

ON There is an alarm

Page 22:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 1 System Architecture 20

OTS-10 System Overview

Table 10 Pre – Mini EDFA Interface Description

Symbol Description

IN Input optical interface of traffic and OSC of the LC interface.

OUT Output optical interface of traffic of the LC interface.

OSC1 Output OSC channel of 1511nm

OSC2 Output OSC channel of 1571nm

1.6 Slot 4 MUX/DEMUX Card

Figure 12 illustrates the slots used by the Mux/Demux card in the OTS-10 .

Figure 12 Mux/Demux Card Slots

The OTS-10 uses different MUX/DEMUX for each kind of point-to-point or ring applications. Users can customize the

specific MUX/DEMUX for their own application.

OTS-DW-08-DSx

OTS-DW-08-DSx is an 8 channel DWDM MUX/DEMUX card used in dual fiber, bi-directional transmission. Sx (x=1 – 5)

represents one of five sub-bands. OSC channel (1511nm) add/drop is integrated in the MUX/DEMUX card.

OTS-DW-08-DS1: CH21 – CH28; OSC (1511nm)

OTS-DW-08-DS2: CH29 – CH36; OSC (1511nm)

OTS-DW-08-DS3: CH37 – CH44; OSC (1511nm)

OTS-DW-08-DS4: CH45 – CH52; OSC (1511nm)

OTS-DW-08-DS5: CH53 – CH60; OSC (1511nm)

Following are the physical parameters of Mux/Demux

VViirrttuuaall SSlloott 11

Slot 2 Slot 3

Slot 4

Page 23:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 1 System Architecture 21

OTS-10 System Overview

Weight: 0.5kg

Dimensions : 272 mm x 79.4 mm x 40.4mm (D x W x H)

The spec of OTS-DW-08-DS1 is provided in the following tables.

Note: IL excludes connector loss

* S1: Sub-band 1

PARAMETER SPECIFICATION UNITS NOTE Operation Temperature -5~ +65 °C

Operation Humidity 5 to 90%RH Not condensed %RH

Storage Temperature -40 ~ +85 °C

Storage Humidity 0 to 95%RH Not condensed %RH

Card Function

Extended temperature range

PARAMETER SPECIFICATION UNITS NOTE MIN. TYP. MAX.

Channel spacing 100 GHz Channel number 8 Port number 20 Pass band width λc ± 0.11 nm OSC 1511 wavelength range 1504.5 ~ 1517.5 m Insertion Loss Add/Drop demux mux dB

CH21 - CH28 3.5 3.5 OSC: 1511nm 0.8 dB

Isolation Adjacent Channel 30 dB non-adjacent Channel 45 dB

OSC 1511 Isolation 30 dB @1528 ~ 1568 Pass band ripple 0.5 dB Channel uniformity 1 dB Insertion loss thermal stability 0.005 dB/℃

Wavelength thermal stability 0.002 nm/℃

Directivity 55 dB PDL 0.15 dB PMD 0.10 ps Return loss 45 dB Optical operating power 300 mW

Page 24:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 1 System Architecture 22

OTS-10 System Overview

Flat and wide pass band

High mux/demux channel isolation

Card Faceplate

The Mux/Demux faceplate is shown in Figure 13.

Figure 13 Mux/Demux Faceplate

Symbols and indicators on the Mux/Demux faceplate are described in Table 11

Table 11 Card Faceplate Description

Symbol Description

CH-IN (1-8) Input optical interface of channel, LC interface.

CH-OUT (1-8) Output optical interface of channel, LC interface.

OSC-IN Input optical interface of OSC, LC interface.

OSC-OUT Output optical interface of OSC, LC interface.

COM-IN Input optical interface of traffic and OSC, LC interface.

COM-OUT Output optical interface of traffic and OSC, LC interface.

OTS-DW-08-DB series

The OTS-10 series WDM transport platform supports single fiber, bi-directional transmissions for which the OTS-DW-08-DB

series MUX/DEMUX cards are designed..

OTS-DW-08-DB includes two types of products: OTS-DW-08-DBU and OTS-DW-08-DBR. OTS-DW-08-DBU is a universal

MUX/DEMUX which covers most of the single fiber, 4 channels, 8 channel, point to point, 1+1 protection, and ring

applications. OTS-DW-08-DBR is used for single fiber, 4 channels, 1+1 protection, or ring applications with EDFA.

Following are the physical parameters of Mux/Demux:

Dimensions : 272 mm x 79.4 mm x 40.4mm (D x W x H)

Page 25:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 1 System Architecture 23

OTS-10 System Overview

The block diagram of OTS-DW-08-DBU is featured below.

Note: IL excludes connector loss.

OSC: 1491nm, 1511nm, 1571nm, 1591nm:

Page 26:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 1 System Architecture 24

OTS-10 System Overview

Specification of 8 channel MUX/DEMUX in OTS-DW-08-DBU:

Parameters Unit Value Note

100G Channel number NA 8

CWDM channel number NA 2

Central wavelength M/D: CH21 – CH28; CH31 - CH38;

Port Number NA 22

Channel Spacing GHz 100

100G Band [email protected] nm ≥0.3

100G Pass Band nm λ ITU-T±0.11

CWDM OSC pass band mm λ C±6.5

Ripple over Pass Band dB ≤0.5

Channel Insertion Loss dB ≤4.0

Uniformity dB ≤1.0

Adjacent Channel Isolation dB ≥28

Non-Adjacent Channel Isolation dB ≥45

OSC port Insertion Loss dB ≤1.5

OSC port Isolation dB ≥30

Insertion Loss Thermal Stability dB/℃ ≤0.008 *

Wavelength Thermal Stability nm/℃ ≤0.001 *

Return loss dB ≥45

Directivity dB ≥50 *

PDL dB ≤0.25 *

PMD PS ≤0.20 *

Power Handling mW 500 *

Page 27:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 1 System Architecture 25

OTS-10 System Overview

Specification of Red/Blue sub-band filter in OTS-DW-08-DB series:

Parameters Unit Value Note

Port Number NA 3

DWDM Channel Spacing GHz 100

100G Band [email protected] Nm ≥0.3

100G Pass Band Nm λ ITU-T±0.11

CWDM OSC pass band Mm λ C±6.5

Ripple over Pass Band dB ≤0.5

Insertion Loss

COM to C21~C28&1571 dB ≤2.0

COM to C31~C38&1511&1491 ≤1.2

Isolation C21~C28@other dB >25dB

1571@other >30dB

C31~C38@C21~C28&1571 >13dB

1491@C21~C28&1571 >13dB

1511@C21~C28&1571 >13dB

Return loss dB ≥45

Directivity dB ≥50 *

PDL dB ≤0.30 *

PMD PS ≤0.20 *

Power Handling mW 500 *

Page 28:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 1 System Architecture 26

OTS-10 System Overview

Block diagram of OTS-DW-04-DBR is featured below.

OSC: 1511nm; 1571nm

Page 29:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 1 System Architecture 27

OTS-10 System Overview

Specification of OTS-DW-04-DBR:

Parameters Unit Value Note

100G Channel number NA 2X4

CWDM channel number NA 1

Central wavelength M/D: CH21 – Ch24; CH31 – CH34

Port Number NA 22

Channel Spacing GHz 100

100G Band [email protected] nm ≥0.3

100G Pass Band nm λ ITU-T±0.11

CWDM OSC pass band mm λ C±6.5

Ripple over Pass Band dB ≤0.5

Channel Insertion Loss dB ≤2.5

Uniformity dB ≤0.5

Adjacent Channel Isolation dB ≥28

Non-Adjacent Channel Isolation dB ≥45

OSC port Insertion Loss dB ≤1.0

OSC port Isolation dB ≥30

Insertion Loss Thermal Stability dB/℃ ≤0.008 *

Wavelength Thermal Stability nm/℃ ≤0.001 *

Return loss dB ≥45

Directivity dB ≥50 *

PDL dB ≤0.25 *

PMD PS ≤0.20 *

Power Handling mW 500 *

Page 30:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 1 System Architecture 28

OTS-10 System Overview

PARAMETER SPECIFICATION UNITS NOTE Operation Temperature -5~ +65 °C

Operation Humidity 5 to 90%RH Not condensed %RH

Storage Temperature -40 ~ +85 °C

Storage Humidity 0 to 95%RH Not condensed %RH

Card Function

Extended temperature range

Flat and wide pass band

High mux/demux channel isolation

Card Faceplate

The Mux/Demux faceplate is shown in Figure 14.

Figure 14 Mux/Demux Faceplate

Page 31:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 1 System Architecture 29

OTS-10 System Overview

Table 12: Symbols and indicators on the Mux/Demux faceplate as described in Figure 14

Table 12 Card Faceplate Description

Symbol Description

CH (21-28) Optical interface of channel, LC interface.

CH (31-38) Optical interface of channel, LC interface.

1451/1471/1591/1571 Optical interface of OSC, LC interface.

RED Optical interface of RED band of R/B splitter, LC interface.

BLUE Optical interface of BLUE band of R/B splitter, LC interface.

R-COM Common port of RED band, SC interface.

B-COM Common port of BLUE band, SC interface.

COM Common port of R/B splitter, SC interface.

1.7 Fan and Power

Fan Alarm LED

The OTS-10 has a pluggable fan tray that includes five fans, an Alarm LED for the fans, and an Alarm LED for the power

supplies.

The OTS-10 provides a Fan Fault LED feature. This feature comprises of an LED light that stays off when the fans are

functioning normally but will turn red if the software detects any defects in a fan.

Power Alarm LED

The OTS-10 system provides two power supply modules. The monitoring system can monitor defects of the power supply

voltage and report the alarm information to the Network Management System.

The OTS-10 provides the PWR Fault LED feature. This feature comprises of an LED light that stays off when the power is

functioning normally but will turn red if the software detects any defect in association with the power supply.

Power Supply

The power supply must be stable with a voltage range as follows:

DC Power range: -48V~-55V DC 5.2A; 7A (The DC power itself has a fuse.)

Page 32:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 1 System Architecture 30

OTS-10 System Overview

AC Power range: 100/200V, 50/60Hz. 2.75/1.375A; (The AC power itself has no fuse)

DC-48V power corresponding type

Use power wires corresponding to the power distribution equipment. The recommended power wires should be AWG19

thickness or higher. Connect the equipment terminal of the power wire with the terminal panel on the back of the OTS-10.

1. Connect the power terminal of the power wire with DC power.

2. Connect the terminal indicated [0V] with DC 0V, the terminal indicated [-48V] with DC -48V, and the terminal indicated

[FG] with the ground of the setting site. It shows the power connection method of the OTS-10 (DC-48V power

corresponding types).

Figure 15 DC power

DC power connection

The DC power connection -48VDC is made in accordance with the -48V terminal lug for both power feeds.

Figure 16 DC power

Warning!

Power cables must be plugged in while there is no power running through the cables.

Note: If the power output does not stop, do not directly touch the metal parts of the OTS-10 DC power terminal or power cable terminal to prevent personal injury and damage to the system.

AC power corresponding type

When using AC power as the OTS-10 Series power source:

For power supply redundancy, two AC sources (preferably independent) are required. Each source should be capable of

supplying 100 watts per OTS-10 system. The AC power cables from the AC source attach to the AC power module that is

mounted at the rear of the OTS-10 system.

Page 33:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 1 System Architecture 31

OTS-10 System Overview

An AC circuit breaker is recommended for the AC power source. This circuit breaker should protect against excess currents

and short circuits and should adhere to national and local electrical codes.

Insert the device-side of the power cord into the OTS-10 Series AC inlet and insert the power source-side of the power cord

into the power source outlet.

Figure 17 Connecting the Power Cord

1. Insert the power cord plug firmly into the appropriate outlet.

2. Always use a grounded outlet.

3. Always connect both power cords.

Page 34:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 2 System Functions and Features 32

OTS-10 System Overview

System Functions and Features

This chapter provides an overview of the OTS-10’s functions and features.

OptoSpan’s OTS-10 Functions

OptoSpan’s OTS-10 Features

2.1 System Functions

Media Converter Function

Service frame transmission between the devices’ Mux/Demux occurs when connecting the Long Haul(LH) ports of two

OTS-10 devices with a pair of single mode fibers (SMF) or dispersion shift fibers (DSF). Transmission span loss is 35dB

with EDFA (when FEC is enabled). Dispersion tolerance is ±800 ps/nm (zero chirp) or 0 to +1600 ps/nm (negative chirp

depending on what SFP/SFP+ is used).

Network Management Function

When the SNMP manager requests MIB information or settings, the device conducts the appropriate processing to fulfill the

request and sends the response data to the SNMP manager.

The SNMP managers that connect to the OTS-10 can be restricted as follows:

SNMP manager access restriction

SNMP manager IP address

If an IP address is set, all access—except from the registered SNMP manager—will be ignored.

Read-only community name

Read-write community name

Setting and updating of management information (MIB)

Using the Internet standard MIB prescribed by MIB RFC1213 (MIB II Revision 2), a user can adjust the system and

interface settings.

2

Page 35:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 2 System Functions and Features 33

OTS-10 System Overview

OptoSpan proprietary MIB such as the operation management MIB for displaying the status of each port can be

adjusted and set.

Using the MIB prescribed by RFC2863 (interface group MIB), the device ifXEntry can be adjusted and set.

Trap send function

The OTS-10 system can send the following traps to a manager that has been set as the trap receiver:

Cold trap on startup

Power failure and recovery status

Cooling fan failure and recovery status

Self-diagnostic test failure

SNMP authentication failure

Link Up/Down

Sending short frames (63 bytes or less) or long frames (9,217 bytes or more) with the Long-Haul (LH) port.

In-band Management function

By connecting the local equipment’s management port to a management device, the remote OTS-10 can be managed

through In-band OSC channels.

Protect Switch Function

PSW Group

channel 1 and channel 2 are PSW group, peer of channel 1 is channel 2 and vice versa

channel 3 and channel 4 are PSW group, peer of channel 3 is channel 4 and vice versa

channel 5 and channel 6 are PSW group, peer of channel 5 is channel 6 and vice versa

channel 7 and channel 8 are PSW group, peer of channel 7 is channel 8 and vice versa

In a PSW group, one channel is a working channel while the other is a protection channel. These channels can be set up using the CLI or SNMP manager.

Configure PSW group Rule

PSW mode setting

The OTS-10 has three settings:

Page 36:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 2 System Functions and Features 34

OTS-10 System Overview

1. Standalone (default)

2. Working

3. Protection

The standalone mode is the default mode for the OTS-10. The OTS-10 needs to be in standalone mode prior to switching to working or protection modes.

Switch from working to protection

There are two ways to switch from the working to protection mode: one is the automatic switch and the other is the manual

switch.

Automatic switch

Must satisfy the following conditions to automatically switch:

PSW availability

Working channel generated LOS alarm in the LH port or the working/active daughter card was pulled out

Manual switch

The OTS-10 can switch from working to protection manually via command line when the PSW group is active. If the PSW

group is not active, the OTS-10 cannot switch manually.

Switch from protection to working

One method to switch from protection to working mode is via the command line, but the following conditions would need

to be met:

PSW availability

The working channel must not have an LOS alarm in the LH port

Pulling out a daughter card which is in protection/active mode, the system will automatically switch to another card.

Must satisfy the following conditions to switch from protection to working:

PSW availability

Protection/active channel generated LOS alarm in the LH port or protection/active SFP module was pulled out of the

LH port.

Working/standby channel power LH port, while LH port no LOS Alarm

Note: Unplugging an SH port SFP module or SH port LOS alarm will not lead to an automatic switch.

Page 37:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 2 System Functions and Features 35

OTS-10 System Overview

2.2 System Features

Performance Monitoring

Via the performance monitoring function, the OTS-10 can monitor the Long Haul (LH) and Short Haul (SH) port loss of

signal operational status items. This function also allows for users to check normal values from a MIB (OptoSpan

proprietary MIB), which monitors the performance of the system every 15 minutes and automatically generates daily logs.

Loopback Test

This device features a loopback test function implemented between the local device and the remote device to check the

status of the port connection. A loopback test is conducted by sending a test from the OTS-10 local device to the remote

device and then back to the local device. The test results are then recorded in a log. The following are different methods

one can conduct a loopback test:

Through the terminal using a serial connection with the loopback terminal command after entering configuration mode.

Through a telnet connection once a management IP address has been established.

Request the loopback test using an SNMP manager (MIB).

File Transfer

The OTS-10 features a TFTP client function, allowing it to download firmware updates, transfer logs, and upload and

download information to a server on the network.

Log Record

The OTS-10 can save log information when the reboot command is executed. A key feature of the OTS-10 is that it is

SYSLOG compatible. This feature enables logs to be sent automatically to a network-connected SYSLOG server.

Note: If the power is turned off without executing the reboot command, the log will not be saved.

NTP and Clock

Incorporating a real-time clock, the OTS-10 allows logs to be recorded at a time specified by the user. It is also NTP

compatible, allowing the use of a user-prepared server to synchronize the internal clock. The lithium battery saves the time

setting even when the power is turned off.

OSC

The main board in the OTS-10 main shelf consists of CPU and control circuit. This main board also supports in-band

capability by use of an Optical Service Channel (single OSC). With dual OSC, OTS-10 can be used in RING application.

Page 38:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 2 System Functions and Features 36

OTS-10 System Overview

System Access Capability

The interface types are as follow:

CWDM 10GbE optical interfaces

DWDM 10GbE optical interfaces

CWDM OC192 optical interfaces

DWDM OC192 optical interfaces

OC48 optical interfaces

1GbE optical interfaces

2.5GbE optical interfaces

EDFA interfaces

Ethernet Service Processing Capability

Network Interface Protocols

The following section lists the OTS-10 supported protocols:

IEEE802.3: 1000BASE-X

IEEE802.3/IEEE802.3u: 10BASE-T, 100BASE-TX

IEEE802.3ae: 10GBASE-R

Console Interfaces

ITU-T V.24/V.28

Network Management Protocols

RFC1157: SNMP (Simple Network Management Protocol)

Objects managed by the network

RFC1213: Internet standard MIB (Management Information Base) (system, interface)

RFC2863: Interface group MIB(ifXEntry)

OptoSpan private mib: OTS-10 -mibs.mib

Page 39:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 2 System Functions and Features 37

OTS-10 System Overview

Communication protocols

RFC793: TCP (Transmission Control Protocol)

RFC768:UDP(User Datagram Protocol)

RFC791: IP (Internet Protocol)

RFC826: ARP (Address Resolution Protocol)

RFC854: TELNET

RFC792: ICMP (Internet Control Message Protocol)

RFC1305: NTP

RFC3164: SYSLOG

Page 40:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 3 Administration and Management 38

OTS-10 System Overview

Administration and Management

The following chapter provides a detailed listing of how to manage and use the OTS-10 system through either the web

graphical user interface (GUI) or the command line interface (CLI).

Web Graphical User Interface (GUI)

Command Line Interface (CLI)

3.1 Introduction The OTS-10 has two default accounts set up. One is username “adpro” and the other is username “user”. Adpro is the

default admin account and user is the default user account. Both default accounts have no password, but a password can

be configured through the admin account.

The admin account has no restrictions when configuring the OTS-10. The user account does not have permissions to make

changes on the system but has permission to view all settings.

3.2 Web Graphical User Interface (WebGUI) The OTS-10 has a user-friendly GUI for users to configure the system. To access the web GUI the management IP address

must be configured using a serial port connection and the command line interface. Once the management IP address is

configured; the management IP address can be entered into any internet browser to access the web GUI.

To configure the OTS-10 through the GUI the account must have admin rank since user accounts only have access to view

setting. The GUI works by clicking to change a setting. Clicking on a field may either bring up a dropdown box for the user

to choose from or an empty textbox where the user must type in the information they wish to change the setting to.

Below are screenshots of each tab of the GUI when the system is running without any errors. The configuration of the

system during the screenshots is one SFP transceiver plugged into Long Haul (LH) port 1 and one SFP transceiver plugged

into Short Haul (SH) port 1.

3

Page 41:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 3 Administration and Management 39

OTS-10 System Overview

Figure 18 Login Prompt

Figure 18: Login prompt after management IP address entered into internet browser.

Figure 19 Web GUI

Figure 19: Web GUI after a successful logon.

Page 42:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 3 Administration and Management 40

OTS-10 System Overview

Figure 20 Homepage

Figure 20: Homepage of the GUI, which is the default page when a user logs in with proper credentials.

Figure 21 System Information

Figure 21: Systems information tab of the current running system. It displays all system pertinent information such

as model name, service number, service up time, and current modules plugged into the system.

Page 43:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 3 Administration and Management 41

OTS-10 System Overview

Figure 22 Time

Figure 22: Time tab which is used to alter the time and date information of the system.

Figure 23 Overview

Figure 23: Overview of the system with port and port setting information.

Page 44:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 3 Administration and Management 42

OTS-10 System Overview

Figure 24 Interface

Figure 24: Interface tab which configures the individual ports of the system. Here settings such as TLLF and tx-

sync can be configured.

Figure 25 IP&Routing

Figure 25: IP & Routing tab which configures the IP information of the system. The user can set up multiple IP

servers, a syslog server, and a radius server from this tab.

Page 45:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 3 Administration and Management 43

OTS-10 System Overview

Figure 26 Manage SNMP

Figure 26: SNMP tab where the user can configure a SNMP server to help maintain the system.

Figure 27 Alarm

Figure 27: Alarm tab where users can monitor alarms of the system. Shown is a system with no alarms.

Page 46:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 3 Administration and Management 44

OTS-10 System Overview

Figure 28 Timeout

Figure 28: Timeout tab where the user may set the timeout value of the system if the system does not receive a

response.

Figure 29 Account

Figure 29: Account tab which displays all account information for the system.

Page 47:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 3 Administration and Management 45

OTS-10 System Overview

Figure 30 Save

Figure 30: Save tab where saving current configuration, current logs, or restoration of previous configurations

happen.

Figure 31 Upload/Download

Figure 31: Upload/download tab where uploading and downloading through a TFTP server occurs.

Page 48:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 3 Administration and Management 46

OTS-10 System Overview

Figure 32 System Log

Figure 32: System log which tracks any modifications made on the system and when users log in and out.

Figure 33 Fault Log

Figure 33: Fault log which displays all fault information of the system.

Page 49:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 3 Administration and Management 47

OTS-10 System Overview

Figure 34 Reboot

Figure 34: Reboot tab where the system can be rebooted.

Figure 35 Logout Prompt

Figure 35: Prompt given before logging out of the system.

3.3 Command Line Interface (CLI)

Following are the two methods to connect with OTS-10 series for general parameter configuration via PC:

The managed device must first be configured correctly using the serial port. When connecting through the RS-232 port,

the entire auto configuration can be completed using RS-232 protocol. Using putty, the user can connect to the device

through the serial connection and configure the system.

The second method is to connect your computer with the management port of the OTS-10, then login to the OTS-10 via

Telnet session. This second method only works when the OTS-10 management port is connected to an existing LAN and

the IP address has been configured through the serial port.

Below is a list of the main menu commands in the OTS-10. For an all-encompassing list of commands available refer to the

OTS series command line document which provides detailed explanations and examples of all commands.

Show – show various system information

Configure – configure parameters

Page 50:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 3 Administration and Management 48

OTS-10 System Overview

Restore-config - Sets configurations to defaults except ip, ip mask & route.

Flush-config - Set all configurations to default

Write – write configurations/logs to memory

Upload – upload configurations/logs via TFTP, or output to display

Download – download configurations vis TFTP

Delete – delete a sub-card configuration

Ping – ping a destination ip (ctrl+c to exit)

Reboot – reboot system

System-download – download new system firmware via tftp

Version – show OS version and expansion card information

telnet – telnet to a destination ip

No – negate a command or reset to default values

Exit – logoff the system.

3.4 Helpful Tips Possible errors may arise when using the command line. If an “Ambiguous command” error appears, pressing TAB key will

show what information is needed to continue with the command. Another error may be “Invalid input detected” which simply

means the command you have entered is not a valid command.

When using the command line, it is highly recommended to consistently press the TAB key for any confusion as it will

directly state what the command is looking for or which commands are valid in the operation mode.

If the user wishes to logoff the system, they may do so using the EXIT command on the main menu.

Page 51:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 4 Networking Applications and Configurations 49

OTS-10 System Overview

Networking Applications and

Configurations

The OTS-10 is a cost-effective solution specially designed for carriers or service providers who require a highly reliable network.

It supports the transport of 1G-10G Ethernet services and OC48, OC192 SONET services.

This chapter contains the following topics regarding the typical network configurations and applications of the OTS-10:

Equipment Application Advantages

Typical Deployment Configurations

Network Design with OTS-10

4.1 Application Advantages

The OTS-10 is a 1U Mini-chassis type Multi-service platform with a flexible configuration compatible with various network

applications. The OTS-10 has the following remarkable application advantages brought about by the implementation of new

technologies.

High Integration

The cabinet is 44.4mm x 440mm x 450mm (height x width x depth). The OTS-10 chassis frame weight is 7.3kg without

cards, and it is 9kg with two mini EDFA cards. With this 1U design, multiple OTS-10s can fit in the average network

equipment room.

Flexible Configuration

The OTS-10 provides 8 data traffic expansion channels. These data channels can be plugged in any combination of any

type of high speed 10 G module (OC192, and 10 GbE) or low speed multi-rate module (1 GbE, 1xFC, 2xFC, OC48) for

widespread compatibility.

4

Page 52:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 4 Networking Applications and Configurations 50

OTS-10 System Overview

Network Management

When the SNMP manager of the OTS-10 requests MIB information or settings, the device conducts the appropriate

processing to fulfill the request and sends response data to the SNMP manager. The OTS-10 contains management

information and responds to requests from the manager for retrieving information and when settings to be adjusted. SNMP

supports both V1 and V2 versions at the same time, allowing for the Client side to determine the version according to

preference.

The SNMP managers that connect to the OTS-10 can be restricted as follows:

• SNMP manager access restriction: read-only, read-write.

If an IP address is set, all access except from the registered SNMP manager will be ignored.

Read-only community name

Read-write community name

Managing via SNMP

When the SNMP manager requires reading or setting of the MIB contents the OTS-10 will transmit the response data to the

SNMP manager according to the request.

Figure 36 SNMP manager maps

• Setting and updating of management information (MIB)

OTS-10

Page 53:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 4 Networking Applications and Configurations 51

OTS-10 System Overview

Using the internet standard MIB prescribed by MIB RFC1213, the device can set and change system and interface settings.

OptoSpan proprietary MIB—such as the operation management MIB for displaying the status of each port— can be set and changed.

Using the MIB prescribed by RFC2863 (interface group MIB), the device can set and change ifXEntry.

• Trap sends function

The OTS-10 can send the following traps to a manager that has been set as the trap receiver.

Cold trap on startup

Power failure and recovery status

Cooling fan failure and recovery status

SNMP authentication failure

LINK UP/DOWN

Traps Transmission

The equipment works as a trap source and transmits the traps to the preset managers. The connection method is as follow Figure 37.

Figure 37 Traps transmission

OTS-10

Page 54:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 4 Networking Applications and Configurations 52

OTS-10 System Overview

The OTS-10 connection method includes both ring and point-to-point configurations.

Two methods of in band management are outlined:

1) Static route configuration:

Figure 38 Static route solution

2) Dynamic route solution:

Figure 39 Dynamic route solution

OTS-10 A OTS-10 B

OTS-10 A OTS-10 B

Page 55:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 4 Networking Applications and Configurations 53

OTS-10 System Overview

4.2 Networking Application

Point-to-Point Network

The OTS-10 connection method includes both ring and point-to-point configurations.

Four methods of in band management are outlined:

Figure 40 Basic CWDM application

Figure 40 illustrates the basic 8 channel CWDM 80km P2P application, where the user traffic can be 1G ~10G multi-rate,

or mixed.

Figure 41 Basic DWDM applications

Figure 41 illustrates the basic 8 channel DWDM 80km P2P application, where the user traffic can be 1G ~10G multi-rate,

or mixed.

Figure 42 DWDM applications with big span loss

OTS-10 OTS-CW-08-C

OTS-10 OTS-CW-08-C

80km

OTS-10 OTS-DW-08-

DS1

OTS-10 oW2208D

80km

Wavelength: 1471nm, 1491nm, 1511nm, 1531nm, 1551nm, 1571nm, 1591nm, 1611nm OSC channel: 1451nm MUX/DEMUX: OTS-CW-08-C

Wavelength: D21, D22, D23, D24, D25, D26, D27, D28 OSC channel: 1510nm MUX/DEMUX: OTS-DW-08-DS1

OTS-10 OTS-DW-08-DS1

OTS-10 OTS-DW-08-DS1

EDFA EDFA EDFA EDFA

Wavelength: D21, D22, D23, D24, D25, D26, D27, D28 OSC channel: 1510nm MUX/DEMUX: OTS-DW-08-DS1 Pre-EDFA: OTS-AMP-12-RP Boost EDFA: OTS-AMP-17-RB

OTS-DW-08-DS1 OTS-DW-08-DS1

OTS-DW-08-DS1 OTS-DW-08-DS1

Page 56:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 4 Networking Applications and Configurations 54

OTS-10 System Overview

Figure 42 is an application when the span loss can be up to 38dB. When using DWDM, both mini EDFA for Boost optical

amplifier and pre-amplifier can be used. External DCF or DCM card can also be used for long distance transmissions.

Figure 43 DWDM 8 channel single fiber bi-directional transmission

Figure 43 is an example of the 8 channel, single fiber bi-directional DWDM transmission. For this transmission, the user

traffic can mix with10 GbE (or 10 G SONET OC192) and the low bit rate. EDFA can be where power may be limited.

External DCF or DCM card is used in the case of long distance.

Ring Application

General Description

The OTS-10 supports 2 types of Ring or linear protection application: single fiber bi-direction or dual fiber bi-direction. OTS-

DW-04-DBR supports dual fiber bi-direction protection, which divides 8 channels into two groups, one for WEST direction,

and the other for EAST direction. Each group can be configured as a working protection path by software. OSC channel is

set as 1510nm for DWDM application in both working and protection paths. For single fiber bi-direction, there are two

MUX/DEMUX used. OTS-DW-08-DBU supports signal fiber bi-directional protection without EDFA. For signal fiber bi-

directional protection with EDFA, OTS-DW-04-DBR should be used.

OTS-10

OTS-10

OTS-DW-08-DBU

OTS-DW-08-DBU

Red Band: CH21 – Ch28

Blue Band: CH31 – CH38 EDFA EDFA

EDFA EDFA

Wavelength: Red Band (A-B): CH21 – Ch28 Blue Band (B-A): CH31 – CH38 OSC channel: 1511nm, 1571nm MUX/DEMUX: OTS-DW-08-DBU EDFA: OTS-AMP-17-RB, OTS-AMP-12-RP

Page 57:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 4 Networking Applications and Configurations 55

OTS-10 System Overview

Figure 44 Single fiber, bi-directional, 1+1 protection or Ring without EDFA

Figure 44 is an example of single fiber bi-direction protection without EDFA, in which case OTS-DW-08-DBU is used. This is suitable for a low cost, yet highly reliable application. Four channel DWDM transmissions with 1+1 protection are supported. User ports support 1-10G, or mixed.

Figure 45 Single fiber, bi-directional, 1+1 protection or Ring with pre-EDFA

Figure 45 shows the case of single fiber bi-direction protection with pre-EDFA where OTS-DW-04-DBR is used. This is very suitable for low cost, high reliable applications. 4 channel DWDM transmissions with 1+1 protection are supported. User ports support 1-10G, or mixed.

OTS-10

OTS-10

OTS-DW-08-DBU

OTS-DW-08-DBU

CH25 – Ch28

CH21 – CH24

CH31 – Ch34

CH35 – CH38

WEST EAST

WEST EAST Working Protection

Wavelength: Working (W -> E): CH21 – Ch24 Working (E -> W): CH25 – CH28 Protection (W -> E): CH35 – Ch38 Protection (E -> W): CH31 – Ch34 OSC channel: Working -- 1511nm, 1571nm Protection -- 1491nm, 1511nm MUX/DEMUX: OTS-DW-08-DBU

OTS-10

OTS-10

OTS-DW-04-DBR

OTS-DW-04-DBR

CH31 – Ch34

CH21 – CH24

CH31 – Ch34

CH21 – CH24

WEST EAST

WEST EAST Working Protection

Wavelength: Working (W -> E): CH21 – Ch24 Working (E -> W): CH31 – CH34 Protection (W -> E): CH21 – Ch24 Protection (E -> W): CH31 – Ch34 OSC channel: Working -- 1511nm, 1571nm Protection -- 1511nm, 1571nm MUX/DEMUX: OTS-DW-04-DBR Pre-EDFA: OTS-AMP-12-RP

EDFA

EDFA

EDFA

EDFA

Page 58:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 4 Networking Applications and Configurations 56

OTS-10 System Overview

Stack Application

General Description

Not including the OSC channel, the OTS-10 can support a maximum of 8 channels. To support an application beyond 8

channels per one node, the OTS-10 can stack at least 5 mini-chassis, which means it can support at least 32 channels,

known as network management port stacking and optical wavelength stacking.

Stack of Management port

The OTS-10 features two 10M/100M management ports for network management stacking. Connecting the UP port to the

DOWN port of each stacking mini-chassis allows for a simpler, streamlined software management of each mini-chassis.

Figure 46 displays the network management stack.

Figure 46 Network management port stacking

Stack of optical wavelength

When stacking the management ports, a band filter card is used. A band filter card divides all wavelengths into several sub-

bands. Every OTS-10 mini-chassis supports one sub-band. For example, for the DWDM system, five mini-chassis can be

stacked to support 100G grids allowing for the transmission 40 channels, as displayed in Figure 47. OTS-10-BF-05-D is the

5 sub-band band filter card which divides the full C-band (from CH21 to CH60) into a 5 sub-band. Every sub-band feeds

into one 1RU mini-chassis. Through this arrangement, a 5RU mini-chassis can support 400G transmission.

Page 59:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 4 Networking Applications and Configurations 57

OTS-10 System Overview

Figure 47 Block diagram of optical wavelength stack

OTS-10

OTS-10

OTS-10

Wavelength: Totally 40 channel. ITU D21 – D60 OSC: 1510nm Band filter: OTS-10-BF-05-D (can be plugged into EDFA slot) MUX/DEMUX: OTS-DW-08-DS1 OTS-DW-08-DS2 OTS-DW-08-DS3 OTS-DW-08-DS4 OTS-DW-08-DS5

OTS-DW-08-DS5

OTS-10

OTS-10

OTS-10-BF-05-D

ITU 21, 22…28

ITU 29, 30…36

ITU 37, 38…44

ITU 45, 48, 52

ITU 53, 54, 60

OTS-DW-08-DS4

OTS-DW-08-DS3

OTS-DW-08-DS2

OTS-DW-08-DS1

Page 60:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 5 Advanced Management 58

OTS-10 System Overview

Advanced Management

The following chapter is an overview of additional details of the OTS-10 management.

5.1 Fault Management

Alarm surveillance involves detection and report of the related events and conditions happening in the network. An alarm is

generated automatically by each event and input signal. There are 5 severity levels of the alarms in the OTS-10. They are

Critical, Major, Minor, Information and Clear. The alarm and its level are shown through the alarm indicator on the OTS-10

sub-rack. After the alarm is sent to the network management system, the system can automatically analyze the detailed

description of the alarm and determine the probable cause to help with troubleshooting.

Alarm Hierarchy

Figure 48 Alarm Hierarchy Map

The following should be noted:

• There is no alarm hierarchy for OAMP interface.

• Wavelength Mismatch includes reading wavelength failure.

• “LC HW Failure” alarms can indicate a problem regardless of the configured state of the LC.

• Alarm hierarchy is used for reporting the highest priority failure for defects appearing at the same time and does not apply

to independent failures happening at different times.

5

Transceiver Absent

Bias Alarm Temperature Alarm

LOS FSR Force Down

LC HW Failure

Page 61:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 5 Advanced Management 59

OTS-10 System Overview

Alarm List

Supported alarms are as follows:

Alarm Level

(1) Critical (2) Major (3) Minor (4) Information (5) Clear

“*” means trap only, there is no associated condition

Table 13 System Alarm List

Content Level

System Alarm List

* System Cold Reboot Information

* System Warm Reboot Information

* Authentication Failure Information

Shelf alarm lists---shelf

Fan Fault Major/ Critical

* Fan Fault Clear Clear

Power Fault Major

* Power Fault Clear Clear

* SC Disconnection Information

* SC Connection Information

* Duplicate SC Conflict Information

* Duplicate NC Conflict Information

* Shelf Delete Information

* Shelf Cold Reboot Information

* Shelf Warm Reboot Information

Line Card or MUX/DEM Alarm List---shelf/slot

Page 62:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 5 Advanced Management 60

OTS-10 System Overview

* Line Card Insert Information

* Line Card Remove Information

* Line Card Delete Information

Line Card hw Fault Critical

* Line Card hw Fault clear Clear

XCVR Alarm List---shelf/slot/port(1G/2.5G/10G-SH,1G/2.5G-LH)

Transceiver Module Absent Information

* Transceiver Module Absent clear Clear

Transceiver Module Mismatch Major

* Transceiver Module Mismatch clear Clear

1G card Alarm List---shelf/slot/port

Loss of Signal Critical

* Loss of Signal Clear Clear

Laser Temperature Failure Critical

* Laser Temperature Clear Clear

Laser Bias Failure Critical

* Laser Bias Clear Clear

Remote Defect Indication Information

* Remote Defect Indication Clear Clear

DB Alarm List

* DB LC Change Information

* DB Change Information

* DB Corruption Critical

Management Port

Page 63:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 5 Advanced Management 61

OTS-10 System Overview

* Port Link Up Clear

Port Link Down Information

OSC Port---shelf

* Link Up Clear

Link down Information

Transceiver Module Absent Information

* Transceiver Module Absent clear Clear

Laser Temperature Failure Critical

* Laser Temperature Clear Clear

Laser Bias Failure Critical

* Laser Bias Clear Information

EDFA OAMP Port---shelf/slot/port

EDFA Pump Temperature Alarm Critical

* EDFA Pump Temperature Alarm Clear Clear

EDFA Pump Bias Alarm Critical

* EDFA Pump Bias Alarm Clear Clear

EDFA Input Power Alarm Critical

* EDFA Input Power Alarm Clear Clear

EDFA Output Power Alarm Critical

* EDFA Output Power Alarm Clear Clear

EDFA Temperature Alarm Critical

* EDFA Temperature Alarm Clear Clear

PSW---shelf

* PSW switch Information

Page 64:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 5 Advanced Management 62

OTS-10 System Overview

* PSW mode mismatch Information

* PSW status mismatch Information

Note: When an interface is disabled, Bias alarm should not be raised.

5.2 Performance Monitoring

The OTS-10 can monitor the following operational status items: Long Haul and Short Haul port loss of signal. The

performance monitor function can also check normal values from an MIB (OptoSpan proprietary MIB). This function can

separately count in every 15 minutes and log daily.

Performance Monitoring (PM) collects the NE performance primitive data and status of the equipment by continuously

tracking system, network, and service activities to report and evaluate the performance of network and NE. The PM

parameters are derived from performance primitives associated with SDH frame formats defined in ITU-T G.707. The

performance parameters specified for Section and Path layers are included. Two tables are provided, one for SDH and the

other for the Ethernet interface.

Performance Data

The OTS-10 uses one 15-minute register and one 24-hour register for every performance parameter to save current performance data. After the sampling period, data will be saved to the history register which is composed of ninety-six 15-minute registers (one previous and fifteen recent) and seven 24-hour registers (one previous and five recent). Further, there is a register for saving the current performance value for each Ethernet performance parameter.

The card PM data information is as follows:

1GBE Card

Performance Monitoring Data contents include Loss of Signal Seconds (LOSS), Laser bias current (LBC), Optical power TX

(OPT) and Optical power RX (OPR).

Performance Data Reporting and Collection

Performance Monitoring records information every 15 minutes, with statistics gathered from the system within the first 15-

minute border. Statistic times should be real-time RTC of the system and the point of collection should be 15-minute

intervals, such as 12:00, 12:15, 12:30. Time stamps should adopt the ending time of each 15-minute period and the PM

function retains the last 96 historical statistics.

Page 65:  · Chapter 0 i . OTS-10 System Overview . Contents . Contents ...

Chapter 5 Advanced Management 63

OTS-10 System Overview

The PM function retains historical statistical data of up to 7 days prior.

5.3 Memory Backup

The OTS-10 provides multiple backup methods for data configuration. This system supports “write flash-memory” command.

Configuration data in the RAM can be backed up to FLASH database through the network management system, or CLI, to

prevent the loss of configuration in case of a power failure.

5.4 Configuration Management

The OTS-10 provides a configuration log to store all operation commands.

Equipment Configuration

The OTS-10 supports off-line card configuration and allows the operator to configure its card type and associated software.

This software can be backed up and upgraded without interrupting the services. The OTS-10 also boasts a built-in failover

mechanism. The software can roll back to the previous working version by re-load.