UNIT DESIGNATION: SEQUENCE OF OPERATION OCCUPIED MODE · 2012-11-02 · OCCUPIED MODE: The HP fan...

Post on 05-Apr-2020

0 views 0 download

Transcript of UNIT DESIGNATION: SEQUENCE OF OPERATION OCCUPIED MODE · 2012-11-02 · OCCUPIED MODE: The HP fan...

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-3) SERVING: Asst. Principal Office A100A

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Sheet No. 1 of 3

A100A_HP-3

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 72 °F

c 69.9 °F

d 66.3 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 69.9 °F

d 57.3 °F

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Sheet No. 2 of 3

A100A_HP-3

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Heating Setpoint

Sheet No. 3 of 3

A100A_HP-3

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-1) SERVING: Conference A100B

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Sheet No. 1 of 3

A100B_HP-1

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 71.9 °F

d 75.1 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 71.9 °F

d 56.6 °F

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Sheet No. 2 of 3

A100B_HP-1

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Heating Setpoint

Sheet No. 3 of 3

A100B_HP-1

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-13) SERVING: Chemistry A101

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

A101_HP-13

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 72 °F

c 69.9 °F

d 63 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 70.4 °F

d 54.4 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

A101_HP-13

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

A101_HP-13

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-14) SERVING: Classroom A104

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

A104_HP-14

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 72 °F

c 70.3 °F

d 70.5 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 70.9 °F

d 59.8 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

A104_HP-14

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

A104_HP-14

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-12) SERVING: Special Ed. A114A

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

A114A_HP-12

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 68 °F

b 72 °F

c 69 °F

d 69.9 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 69.5 °F

d 57.9 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

A114A_HP-12

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

A114A_HP-12

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-12) SERVING: Special Ed. A114B

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

A114B_HP-12

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 68 °F

b 72 °F

c 69.1 °F

d 66.5 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 69.1 °F

d 54.5 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

A114B_HP-12

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

A114B_HP-12

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-15) SERVING: Classroom A116

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

A116_HP-15

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 68 °F

b 72 °F

c 70.1 °F

d 72 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 69.6 °F

d 61.5 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

A116_HP-15

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

A116_HP-15

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-14) SERVING: B.C.I.T. A119

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

A119_HP-14

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 72.6 °F

d 56.2 °F

6

7

8 Yes X No

a NA °F

b NA °F

c NA °F

d NA °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

A119_HP-14

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

A119_HP-14

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-14) SERVING: Classroom A122

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

A122_HP-14

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 72.4 °F

d 73.7 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 71.6 °F

d 59.3 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

A122_HP-14

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

A122_HP-14

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-7) SERVING: Lockers A140

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Sheet No. 1 of 3

A140_HP-7

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 68 °F

b 74 °F

c 72 °F

d 54.3 °F

6

7

8 Yes X No

a NA °F

b NA °F

c NA °F

d NA °F

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Sheet No. 2 of 3

A140_HP-7

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Heating Setpoint

Sheet No. 3 of 3

A140_HP-7

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-1) SERVING: Guidance Office A200F

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

Sheet No. 1 of 3

A200F_HP-1

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 76.5 °F

d 71.5 °F

6

7

8 Yes X No

a 70 °F

b 74 °F

c 75.8 °F

d 63.4 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Cooling Setpoint

Special Observations: _During the test, the SAT did not decrease below 63.4°F and the LWT

did not increase significantly (Before LWT=84.3°F; During LWT=86.3°F). The SAT should

ideally be below 60°F during full cooling mode in order to have proper response time.

____________________________________________________________________________

Sheet No. 2 of 3

A200F_HP-1

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Heating Setpoint

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Sheet No. 3 of 3

A200F_HP-1

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-1) SERVING: Security A200J

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

Sheet No. 1 of 3

A200J_HP-1

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 68 °F

b 72 °F

c 72.9 °F

d 73.7 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 73 °F

d 55.1 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Sheet No. 2 of 3

A200J_HP-1

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Heating Setpoint

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Sheet No. 3 of 3

A200J_HP-1

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-15) SERVING: Storage/Prep A203A

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

A203A_HP-15

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 71.2 °F

d 70.1 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 71.2 °F

d 56.8 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

A203A_HP-15

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

A203A_HP-15

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-18) SERVING: Science A203

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

A203_HP-18

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 71 °F

d 66.7 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 71.6 °F

d 52.8 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

A203_HP-18

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

A203_HP-18

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-15) SERVING: Classroom A208

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

A208_HP-15

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 71.2 °F

d 70.4 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 71 °F

d 59.3 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

A208_HP-15

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

A208_HP-15

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-15) SERVING: Classroom A210

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

A210_HP-15

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 72.1 °F

d 76.3 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 71.1 °F

d 61.7 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

A210_HP-15

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

A210_HP-15

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-13) SERVING: S.G.I. A211

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

A211_HP-13

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 71.1 °F

d 68.3 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 71.1 °F

d 52 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

A211_HP-13

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

A211_HP-13

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-17) SERVING: Science A223

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

A223_HP-17

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 68 °F

b 70 °F

c 69.3 °F

d 58 °F

6

7

8 Yes X No

a NA °F

b NA °F

c NA °F

d NA °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

A223_HP-17

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

A223_HP-17

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-17) SERVING: S.G.I. A226C

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

A226C_HP-17

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 71.9 °F

d 60.6 °F

6

7

8 Yes X No

a NA °F

b NA °F

c NA °F

d NA °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

A226C_HP-17

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

A226C_HP-17

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-2) SERVING: Conference B106

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Sheet No. 1 of 3

B106_HP-2

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 72.2 °F

d 73.7 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 70.7 °F

d 58.9 °F

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Sheet No. 2 of 3

B106_HP-2

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Heating Setpoint

Sheet No. 3 of 3

B106_HP-2

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-5) SERVING: Workroom B108

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Sheet No. 1 of 3

B108_HP-5

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 72 °F

c 70.2 °F

d 73.8 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 70.2 °F

d 55.6 °F

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Sheet No. 2 of 3

B108_HP-5

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Heating Setpoint

Sheet No. 3 of 3

B108_HP-5

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-9) SERVING: Computer Classroom B112

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Sheet No. 1 of 3

B112_HP-9

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 72 °F

c 70.7 °F

d 59.4 °F

6

7

8 Yes X No

a NA °F

b NA °F

c NA °F

d NA °F

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Sheet No. 2 of 3

B112_HP-9

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Heating Setpoint

Sheet No. 3 of 3

B112_HP-9

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-6) SERVING: E.L.L. B201

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Sheet No. 1 of 3

B201_HP-6

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 73.5 °F

d 72.7 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 73.5 °F

d 58.4 °F

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Sheet No. 2 of 3

B201_HP-6

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Sheet No. 3 of 3

B201_HP-6

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-3) SERVING: Psych B204

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Sheet No. 1 of 3

B204_HP-3

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 72.4 °F

d 71.8 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 72.4 °F

d 56.6 °F

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Sheet No. 2 of 3

B204_HP-3

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Sheet No. 3 of 3

B204_HP-3

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-9) SERVING: Computer Lab B208

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Sheet No. 1 of 3

B208_HP-9

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 68 °F

b 74 °F

c 72.6 °F

d 51.7 °F

6

7

8 Yes X No

a NA °F

b NA °F

c NA °F

d NA °F

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Sheet No. 2 of 3

B208_HP-9

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Sheet No. 3 of 3

B208_HP-9

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-3) SERVING: Asst. Principal Office C100A

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Sheet No. 1 of 3

C100A_HP-3

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 73.8 °F

d 74.7 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 73.8 °F

d 58.4 °F

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Sheet No. 2 of 3

C100A_HP-3

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Heating Setpoint

Sheet No. 3 of 3

C100A_HP-3

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-1) SERVING: Conference C100B

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Sheet No. 1 of 3

C100B_HP-1

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 71.5 °F

d 74.3 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 71.5 °F

d 57.8 °F

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Sheet No. 2 of 3

C100B_HP-1

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Heating Setpoint

Sheet No. 3 of 3

C100B_HP-1

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-1) SERVING: Security C100G

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Sheet No. 1 of 3

C100G_HP-1

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 73.2 °F

d 72.7 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 73.2 °F

d 58.1 °F

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Sheet No. 2 of 3

C100G_HP-1

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Heating Setpoint

Sheet No. 3 of 3

C100G_HP-1

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-17) SERVING: Science C103

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

C103_HP-17

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 68 °F

b 72 °F

c 69.6 °F

d 71.2 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 70.1 °F

d 57.8 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

C103_HP-17

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

C103_HP-17

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-14) SERVING: Classroom C104

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

C104_HP-14

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 68 °F

b 72 °F

c 69.8 °F

d 70 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 69.8 °F

d 58.6 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

C104_HP-14

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

C104_HP-14

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-14) SERVING: Classroom C110

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

C110_HP-14

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 71.8 °F

d 71.8 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 71.8 °F

d 61.2 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

C110_HP-14

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

C110_HP-14

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-15) SERVING: L.P.C. C112

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

C112_HP-15

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 68 °F

b 72 °F

c 69.3 °F

d 74.9 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 68.8 °F

d 60.2 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

C112_HP-15

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

C112_HP-15

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-14) SERVING: Classroom C115

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

C115_HP-14

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 72.8 °F

d 57.2 °F

6

7

8 Yes X No

a NA °F

b NA °F

c NA °F

d NA °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

C115_HP-14

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

C115_HP-14

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-14) SERVING: Career C122

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

C122_HP-14

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 72.1 °F

d 60.4 °F

6

7

8 Yes X No

a NA °F

b NA °F

c NA °F

d NA °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

C122_HP-14

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

C122_HP-14

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-12) SERVING: Corridor C125

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

C125_HP-12

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 72.3 °F

d 55.3 °F

6

7

8 Yes X No

a NA °F

b NA °F

c NA °F

d NA °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

C125_HP-12

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

C125_HP-12

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-3) SERVING: Asst. Principal Office C200A

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Sheet No. 1 of 3

C200A_HP-3

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 68 °F

b 72 °F

c 69.1 °F

d 63.7 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 69.1 °F

d 54.8 °F

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Sheet No. 2 of 3

C200A_HP-3

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Sheet No. 3 of 3

C200A_HP-3

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-17) SERVING: Storage/Prep. C210A

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

C201A_HP-17

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 72.2 °F

d 72.1 °F

6

7

8 Yes No X

a 65 °F

b 67 °F

c 72.2 °F

d 72.2 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations: During the test, the SAT did not decrease and the LWT did not increase

significantly (Before LWT=75.7°F; During LWT=80.7°F).

____________________________________________________________________________

____________________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

C201A_HP-17

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

C201A_HP-17

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-18) SERVING: Chemistry C201

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

C201_HP-18

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 72 °F

d 73.1 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 71.6 °F

d 50.4 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

C201_HP-18

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

C201_HP-18

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-15) SERVING: Classroom C204

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

C204_HP-15

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 71 °F

b 74 °F

c 71 °F

d 77.3 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 69 °F

d 61.8 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

C204_HP-15

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

C204_HP-15

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-15) SERVING: Classroom C210

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

C210_HP-15

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 74.6 °F

d 72.3 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 74.1 °F

d 55.8 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

C210_HP-15

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

C210_HP-15

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-14) SERVING: L.P.C. C212

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

C212_HP-14

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 72.7 °F

d 72.2 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 72.7 °F

d 54.9 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

C212_HP-14

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

C212_HP-14

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-18) SERVING: Chemistry C222

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

C222_HP-18

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 70.9 °F

d 66.2 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 70.9 °F

d 52.2 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

C222_HP-18

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

C222_HP-18

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-13) SERVING: S.G.I. C235

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

C235_HP-13

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 71.6 °F

d 72 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 71.6 °F

d 54.8 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

C235_HP-13

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

C235_HP-13

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-7) SERVING: Lockers C240

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Sheet No. 1 of 3

C240_HP-7

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 74 °F

d 74.7 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 74 °F

d 51.8 °F

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Sheet No. 2 of 3

C240_HP-7

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Sheet No. 3 of 3

C240_HP-7

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-19) SERVING: Penthouse C301 East Corridor

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

C301_HP-19

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 77.8 °F

d 57.9 °F

6

7

8 Yes X No

a NA °F

b NA °F

c NA °F

d NA °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

C301_HP-19

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

C301_HP-19

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-6) SERVING: Training D102

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Sheet No. 1 of 3

D102_HP-6

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 72.2 °F

d 74.2 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 72.7 °F

d 58.7 °F

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Sheet No. 2 of 3

D102_HP-6

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Heating Setpoint

Sheet No. 3 of 3

D102_HP-6

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-7) SERVING: Fitness Center D106 (Gym-side)

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

Sheet No. 1 of 3

D106_HP-7

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 72.3 °F

d 50.8 °F

6

7

8 Yes X No

a NA °F

b NA °F

c NA °F

d NA °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Sheet No. 2 of 3

D106_HP-7

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Heating Setpoint

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Sheet No. 3 of 3

D106_HP-7

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-10) SERVING: Faculty Dining D110

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

Sheet No. 1 of 3

D110_HP-10

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 68 °F

b 72 °F

c 70.5 °F

d 55.4 °F

6

7

8 Yes X No

a NA °F

b NA °F

c NA °F

d NA °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Sheet No. 2 of 3

D110_HP-10

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Heating Setpoint

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Sheet No. 3 of 3

D110_HP-10

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-6) SERVING: Corridor D120

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

Sheet No. 1 of 3

D120_HP-6

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 72.3 °F

d 74.3 °F

6

7

8 Yes No X

a 65 °F

b 67 °F

c 71.4 °F

d 74.3 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Cooling Setpoint

Special Observations: During the test, the SAT did not decrease and the LWT did not increase

(Before LWT=78.7°F; During LWT=80.3°F).

____________________________________________________________________________

____________________________________________________________________________

Sheet No. 2 of 3

D120_HP-6

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Heating Setpoint

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Sheet No. 3 of 3

D120_HP-6

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-21) SERVING: Aux. Gymnasium D201 (North)

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Sheet No. 1 of 3

D201_N_HP-21

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 70.7 °F

d 71.6 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 69.8 °F

d 65.7 °F

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations: _During the test, the SAT did not decrease below 65.7°F although the

LWT did increase significantly (Before LWT=74.5°F; During LWT=90.2°F). The SAT should

ideally be below 60°F during full cooling mode in order to have proper response time.

____________________________________________________________________________

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Sheet No. 2 of 3

D201_N_HP-21

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Sheet No. 3 of 3

D201_N_HP-21

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-21) SERVING: Aux. Gymnasium D201 (South)

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Sheet No. 1 of 3

D201_S_HP-21

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 71 °F

d 71.8 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 70.7 °F

d 64.3 °F

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations: _During the test, the SAT did not decrease below 64.3°F and the LWT

did not increase significantly (Before LWT=82.3°F; During LWT=85.7°F). The SAT should

ideally be below 60°F during full cooling mode in order to have proper response time.

____________________________________________________________________________

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Sheet No. 2 of 3

D201_S_HP-21

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Sheet No. 3 of 3

D201_S_HP-21

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-3) SERVING: Reception E100

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

Sheet No. 1 of 3

E100_HP-3

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 71.2 °F

d 47.8 °F

6

7

8 Yes X No

a NA °F

b NA °F

c NA °F

d NA °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Sheet No. 2 of 3

E100_HP-3

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Heating Setpoint

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Sheet No. 3 of 3

E100_HP-3

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-5) SERVING: Treatment E101

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

Sheet No. 1 of 3

E101_HP-5

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 70.5 °F

d 37.9 °F

6

7

8 Yes X No

a NA °F

b NA °F

c NA °F

d NA °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Sheet No. 2 of 3

E101_HP-5

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Heating Setpoint

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Sheet No. 3 of 3

E101_HP-5

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-1) SERVING: Office E109

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

Sheet No. 1 of 3

E109_HP-1

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 74.3 °F

d 58.4 °F

6

7

8 Yes X No

a NA °F

b NA °F

c NA °F

d NA °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Sheet No. 2 of 3

E109_HP-1

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Heating Setpoint

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Sheet No. 3 of 3

E109_HP-1

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-10) SERVING: Lobby/Commons E113 (Middle)

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

Sheet No. 1 of 3

E113_HP-10

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 68 °F

b 72 °F

c 69.8 °F

d 43.1 °F

6

7

8 Yes X No

a NA °F

b NA °F

c NA °F

d NA °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Sheet No. 2 of 3

E113_HP-10

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Heating Setpoint

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Sheet No. 3 of 3

E113_HP-10

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-4) SERVING: Well-Being Center E123 (F102)

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

Sheet No. 1 of 3

E123_HP-4

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 72.9 °F

d 73.6 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 72.9 °F

d 57.4 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Sheet No. 2 of 3

E123_HP-4

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Heating Setpoint

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Sheet No. 3 of 3

E123_HP-4

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-19) SERVING: I.S.S. E203

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

E203_HP-19

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 68 °F

b 72 °F

c 72 °F

d 69.7 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 72 °F

d 52.5 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

E203_HP-19

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

E203_HP-19

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-20) SERVING: L.G.I. E211/Open Area

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

E211_HP-20

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 68 °F

b 72 °F

c 69.9 °F

d 49.6 °F

6

7

8 Yes X No

a NA °F

b NA °F

c NA °F

d NA °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

E211_HP-20

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

E211_HP-20

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-1) SERVING: Corridor EI101

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

Sheet No. 1 of 3

EI101_HP-1

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 71.6 °F

d 50.8 °F

6

7

8 Yes X No

a NA °F

b NA °F

c NA °F

d NA °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Sheet No. 2 of 3

EI101_HP-1

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Heating Setpoint

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Sheet No. 3 of 3

EI101_HP-1

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-1) SERVING: Office EI103A

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

Sheet No. 1 of 3

EI103A_HP-1

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 72.5 °F

d 57.1 °F

6

7

8 Yes X No

a NA °F

b NA °F

c NA °F

d NA °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Sheet No. 2 of 3

EI103A_HP-1

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Heating Setpoint

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Sheet No. 3 of 3

EI103A_HP-1

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-10) SERVING: Food Lab F101

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

Sheet No. 1 of 3

F101_HP-10

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 68 °F

b 74 °F

c 72.1 °F

d 72.6 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 72.1 °F

d 52.3 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Sheet No. 2 of 3

F101_HP-10

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Heating Setpoint

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Sheet No. 3 of 3

F101_HP-10

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-11) SERVING: LGI F103B

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

Sheet No. 1 of 3

F103B_HP-11

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 71 °F

d 71.7 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 71 °F

d 48.7 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Sheet No. 2 of 3

F103B_HP-11

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Heating Setpoint

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Sheet No. 3 of 3

F103B_HP-11

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-9) SERVING: Fab Lab F105A

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

Sheet No. 1 of 3

F105A_HP-9

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 70.9 °F

d 71.4 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 70.9 °F

d 56.6 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Sheet No. 2 of 3

F105A_HP-9

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Heating Setpoint

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Sheet No. 3 of 3

F105A_HP-9

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-7) SERVING: Instrument Storage F107A

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

Sheet No. 1 of 3

F107A_HP-7

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 71.9 °F

d 75 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 71.9 °F

d 56.4 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Sheet No. 2 of 3

F107A_HP-7

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Heating Setpoint

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Sheet No. 3 of 3

F107A_HP-7

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-10) SERVING: Band Room F107

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

F107_HP-10

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 71.8 °F

d 72.6 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 71.8 °F

d 50.7 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

F107_HP-10

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

F107_HP-10

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-7) SERVING: Digital Lab F111

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

Sheet No. 1 of 3

F111_HP-7

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 68 °F

b 72 °F

c 71.3 °F

d 72.6 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 71.8 °F

d 52.8 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Sheet No. 2 of 3

F111_HP-7

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Heating Setpoint

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Sheet No. 3 of 3

F111_HP-7

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-9) SERVING: Choral Room F115

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

Sheet No. 1 of 3

F115_HP-9

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 69.9 °F

d 72.8 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 69.9 °F

d 53.8 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Sheet No. 2 of 3

F115_HP-9

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Heating Setpoint

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Sheet No. 3 of 3

F115_HP-9

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-9) SERVING: Ceramics F201

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

F201_HP-9

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 71.1 °F

d 72.8 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 71.1 °F

d 49.9 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

F201_HP-9

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

F201_HP-9

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-8) SERVING: Photography F205

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

F205_HP-8

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 72.9 °F

d 73.9 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 72.9 °F

d 57 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

F205_HP-8

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

F205_HP-8

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-5) SERVING: Corridor F216 (Middle)

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

F216_HP-5

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 72.3 °F

d 50.3 °F

6

7

8 Yes X No

a NA °F

b NA °F

c NA °F

d NA °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

F216_HP-5

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

F216_HP-5

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-10) SERVING: I.T. Office F225

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj) Cooling Setpoint (°F, adj)

Sheet No. 1 of 3

F225_HP-10

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 68 °F

b 72 °F

c 74.1 °F

d 75 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 74.1 °F

d 55.8 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

SUMMER

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Night setup Set point:

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Supply Air Temperature

Sheet No. 2 of 3

F225_HP-10

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

Heating Setpoint

Zone Temperature

Was the HP found to be heating as expected?

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Sheet No. 3 of 3

F225_HP-10

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-1) SERVING: Office G004

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Sheet No. 1 of 3

G004_HP-1

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 68 °F

b 70 °F

c 71.8 °F

d 55.9 °F

6

7

8 Yes X No

a NA °F

b NA °F

c NA °F

d NA °F

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Sheet No. 2 of 3

G004_HP-1

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Heating Setpoint

Sheet No. 3 of 3

G004_HP-1

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-2) SERVING: Food Storage G009

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Sheet No. 1 of 3

G009_HP-2

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 70.5 °F

d 71.2 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 70.5 °F

d 57.8 °F

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Sheet No. 2 of 3

G009_HP-2

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Heating Setpoint

Sheet No. 3 of 3

G009_HP-2

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-9) SERVING: Dish Washing G103

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

Sheet No. 1 of 3

G103_HP-9

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 75.4 °F

d 53.5 °F

6

7

8 Yes X No

a NA °F

b NA °F

c NA °F

d NA °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Sheet No. 2 of 3

G103_HP-9

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Heating Setpoint

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Sheet No. 3 of 3

G103_HP-9

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

70 74

65 80

ALARMS: The controller will monitor the heat pump conditions and shall report back to the BAS

any of the following alarm conditions: High or Low Pressure in the refrigerant circuit; High or Low

Discharge Air Temperature (SAT >70°F in cooling mode or <75°F in heating mode); High or Low

Leaving Water Temperature (LWT >135°F or <35°F) or Sensor Failure; Freeze Protection;

Condensate; or Brownout.

Cooling Setpoint (°F, adj)

PROJECT: Centennial SD - William Tennent HS

UNIT DESIGNATION: Heat Pump (HP-2) SERVING: Dry Storage G111

UNOCCUPIED MODE: The HP is controlled using the Unoccupied space temperature setpoint

shown below. The HP fan will only operate when the compressor is energized The controller will

cycle the HP fan, reversing valve and compressor to maintain the Unoccupied temperatures. A timed

local override control will allow an occupant to place the unit into an Occupied mode for a set period

of time (adj). Control will automatically return to the software schedule upon the time expiration.

OCCUPIED MODE: The HP fan is on and runs continuously. The controller maintains the room

temperature set point (adjustable, as shown below) by cycling the unit's reversing valve and

compressor. There will be a 1-minute delay when transitioning between heating and cooling modes.

The reversing valve shall fail open to the heating mode. The unit shall have a random-start timer that

prevents operation of the compressor for a random period of time whenever the compressor is called

to run. Supplemental heating shall be available to maintain the heating setpoint should the

compressors not meet the heating demand. There will be a 5-minute delay on the electric heater to

prevent short cycling and to allow the compressors time to meet the space requirements.

The heat pump (HP) is controlled by a manufacturer-provided control system while the Building

Automation System (BAS) will monitor the system controller. The HP will operate in the Occupied

and Unoccupied modes as follows:

OCCUPANCY MODES: The BAS will control the HP operation and space temperature setpoints

according to the following schedule:

HOBO data loggers will be used to measure unit's supply temperature, space temperature and space

humidity in the space served by the HP. The purpose of the logger is to record space temperature

and humidity over time and corresponding discharge air temperature. Results will show actual space

environmental conditions to compare with desired performance as well as occupied /unoccupied

temperature conditions. The deployment of logger should be for a minimum of 48 hours to record a

minimum of two (2) separate occupancy cycles.

SEQUENCE OF OPERATION

OPERATIONAL TREND LOGS

Unoccupied Mode

Occupied Mode

Heating Setpoint (°F, adj)

Sheet No. 1 of 3

G111_HP-2

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

1

2

°F

% °F

°F °F

°F %

3

A am to pm

B (day) thru (day)

4

5

6

a 70 °F

b 74 °F

c 71.1 °F

d 67.9 °F

6

7

8 Yes X No

a 65 °F

b 67 °F

c 71.1 °F

d 57.6 °F

Heating Setpoint

Night setback Set point:

RH Sensor Set point:

Temp Sensor Set point:

Rm Logger # SA Logger #

Record the following information pertaining to the deployment of the data Logger.

Record the space sensor displayed "set points" for the HP.

SUMMER

Night setup Set point:

The occupied time of day schedule for the HP as displayed at the BMS Workstation is:

FUNCTIONAL PERFORMANCE TESTING

Actual Rm Temp

SPACE OPERATING STATUS

Room Temp @ Stat:

M F

6 6

Tests will be conducted "seasonally" during periods where considerable heating and

cooling is required to maintain set points. Functional performance of the HP will be

determined utilizing data logger results. Indicate below the season that the initial data

logger tests were run.

WINTER

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full cooling mode by adjusting the cooling set point of the room

sensor to 5 °F below the actual room temperature.

Room RH @ BMS:

Zone Temperature

Supply Air Temperature

Record the initial conditions prior to running the cooling test.

Heating Setpoint

Cooling Setpoint

The expected result is: The HP will be forced to full cooling, the compressor will be

energized in cooling and the BAS displayed room temperature will be above the room

sensor set point.

Was the HP found to be cooling as expected?

Cooling Setpoint

Special Observations:

____________________________________________________________________________

____________________________________________________________________________

________________________________________________________________

Sheet No. 2 of 3

G111_HP-2

REYNOLDS CONSULTING ENGINEERS

COMMISSIONING PROCEDURES

6

a °F

b °F

c °F

d °F

9

10

11 Yes No

a °F

b °F

c °F

d °F

12

A

B

13

14

Complete items "A" or "B" below in accordance with the season indicated above.

A data logger test will be conducted to prove season temperature maintenance.

Attach data logger results to final report.

Was the HP found to be heating as expected?

Were the summer occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? _____ Yes _______ No (confirmed by data

loggers)

Were the winter occupied and unoccupied temperatures and humidity indicated in

item #2 above maintained? ______ Yes _______ No (confirmed by data

loggers)

Special Observations:

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_______________________________________________________________________

_____________________________________________

The results of the performance testing for the Water Source Heat Pump are in

compliance with the project specifications and the BAS approved sequences.

Yes No

Cooling Setpoint

Record the initial conditions prior to running the heating test.

Heating Setpoint

Cooling Setpoint

Heating Setpoint

Zone Temperature

Supply Air Temperature

Zone Temperature

Supply Air Temperature

Force the HP to operate in the full heating mode by adjusting the heating set point of the room

sensor to 5 °F above the actual room temperature.

The expected result is: The HP will be forced to full heating, the compressor will be

energized in heating and the BAS displayed room temperature will be below the room

sensor set point.

Sheet No. 3 of 3

G111_HP-2