TOYO AUTOMATICTRANSFER SWITCH
TSMC-200/200P
/200S
1
Each phase is enclosed separately to improve the breaking capacity and safety.
Each phase of TOYO instantaneous excitation type ATS is molded and enclosed individually to improve the breaking capacity and to increase the operation cycle of the product.
Every contact is enclosed with an individual arc extinction chamber to ensure the arc flash generated at switching is quenched to ensure the safety of personnel and equipment.
The main contacts and connection busbars are all silver coated ensuring the conductivity and performance of the ATS.
The operational cycle is semi-permanent since the arc time generated during the switching is short and contact consumption is small.
It ensures a steady and stable breaking capacity regardless of the operating voltage through an open operation using a separate breaking spring.
The safety of users has improved.
It strengthened the main contact protection and breaking capacity using a 4-pole pre-closing and post-breaking structural design.
The operational cycle of the product is long since it generates little arc due to a superior switching function.
It seems comfortable due to a compact design for the customers.
It enhance the user-friendly image by adopting a volumized shape and creates the innovativeness by applying a simple, elegant and advanced product image.
It stresses the reliability by adopting a streamlined form which is a simple and clean shape.
The products inside the panel board are arranged neatly by applying a clear color.
Safety
Compact
TSMC-200/200P
/200S
2
SPECIFICATION : ( TDS-type NO Neutral OFF )
150 operations / hour
50,000 operations
AC 2,500 V for 1 minute
Power source A: 1C (option: 2C)Power source B: 1C (option: 2C)
Switching capacity AC125V 15A, AC250V 10A , DC14V 15A
Frontal protection cover Manual operation handle
15kA
250,000 operations
200ms60ms
35kA
AC Class 3 (10Ie-Making , 8Ie-Breaking) Cos = 0.35DC Class (1.1Ie-Making , 1.1Ie-Breaking) L/R = 1ms
30ms 60ms
10kA
35kA
3P 4P 4P 2P 3P 4P
2.5 3 4 7.8 8 10.5
7.5A 11A
7.5A 11A
3.8A
7.5A
7.5A
3.8A 5.5A
Front
Single Throw
100A 400A
AC600V (50/60Hz) - DC125V
TDS 01 TDS 04
10A 10A
10kA
30ms
60ms
25kA
3P
3.5
200A
TDS 02
10A 10A
Model
Rated Voltage
Withstand voltage
Auxiliary switch
Accessories
Per
form
ance
Number of Poles
Ope
ratin
g C
urre
ntA
B
clo
sing
DC 110V
AC 100/110V
AC 200/220V
Weight (kg)
Rated Current (Ie)
Throw Type
Connection
Rated short-time current
Short circuit peak value (making capacity)
Switching capacity
Opening
Closing
Switching frequency
Operating time
EnduranceElectrical
Mechanical
A B Transfer sequence
CHARACTERISTIC :
One-Coil ApplicationOnly one coil is used for both service circuit and stand-by circuit switching. ATS has automatic power source selecting function, voltage detecting function of switch-ing A and B, power black-out and recovery checking function, and time adjusting function.
Reference StandardsJEM 1038 JEM 1465IEC 60947-3, 60947-6 UL1008
ORDERING FORM
TDS302A221 2 3Poles
2=2P 3=3P 4=4P
Operating Voltage
A22=AC220V15% (TDS-01/02 only has A22 coil)
A11=AC110V15% D11=DC110V15%
Rated Current
01=100A 02=200A 04=400A
1
2
3
with circuit breaker
SPECIFICATION : ( TDSN-type with Neutral OFF )
150 operations / hour
50,000 operations
AC 2,500 V for 1 minute
Power source A: 1C (option: 2C)Power source B: 1C (option: 2C)
Switching capacity AC125V 15A, AC250V 10A , DC14V 15A
Frontal protection cover Manual operation handle
35kA
50kA15kA
20ms
90ms
25ms
250,000 operations
20ms
80ms
20ms
20ms
35kA
80ms
20ms
AC Class 3 (10Ie-Making , 8Ie-Breaking) Cos = 0.35DC Class (1.1Ie-Making , 1.1Ie-Breaking) L/R = 1ms
55ms 55ms 60ms
10kA
35kA
AC/DC110V
AC/220V
1.4A
0.7A
2P 3P 4P 2P 4P 2P 3P 4P 3P 4P
4.5 6 8 4.5 8 6 8 10 14 17
4A 4A 5A 4A 5A 5A 7.2A 6.4A 9A
4A 4A 5A 4A 5A 5A 7.2A 6.4A 9A
2A 2A 2.5A
5A
5A
2.5A 3.6A 3.2A 4.5A
Front
Double Throw ( Aneutral offB )
100A 400A 600A
AC600V (50/60Hz) - DC125V
TDSN 01 TDSN 04 TDSN 06
2A 2.5A
10kA
80ms
20ms
55ms
20ms
25kA
3P
6
4A
4A
200A
TDSN 02
2A 2.5A
Model
Rated Voltage
Withstand voltage
Auxiliary switch
Accessories
Per
form
ance
Number of Poles
Ope
ratin
g C
urre
nt
Closing coil DC 110V
Closing coil AC 100/110V
Closing coil AC 200/220V
Tripping coil
Weight (kg)
Rated Current (Ie)
Throw Type
Connection
Rated short-time current
Short circuit peak value (making capacity)
Switching capacity
Closing
Tripping
Closing
Tripping
Switching frequency
Source A
Source B
Operating time
EnduranceElectrical
Mechanical
3A
1.5A
CHARACTERISTIC :
One-Coil ApplicationOnly one coil is used for both service circuit and stand-by circuit switching. ATS has automatic power source selecting function, voltage detecting function of switch-ing A and B, power black-out and recovery checking function, and time adjusting function.
Neutral Point MethodWhen uninterrupted power supply unit is used for the distribution system, it is recommended to switch power after checking the network rather than switching in instantly. ATS can be positioned at neutral point by its tripping mechanism. ATS control mode can be:
AoffB , BoffA , and AoffA , BoffB
Also, ATS can switch instantly to stand-by source when normal power service fails.
Reference StandardsJEM 1038 JEM 1465IEC 60947-3, 60947-6 UL1008
TSMC-200/200P
/200S
3
with circuit breaker
ORDERING FORM
Optional, please contact us for more information.
8A 10A 8A 10A
8A 10A 8A 10A
4A 5A 4A 5A
Front (Back ) Back
13A 16A 16A 18A
16A
4P 3P 4P
65 11985 93
3P 4P 3P 4P
2000A 3000A / 3200A800A / 1000A 1200A
TDSN 08 / 10 TDSN 12 TDSN 16
Double throw ( Aneutral offB )
AC 600V (50/60Hz) - DC 125V
TDSN 20 TDSN 30 / 32
3P
24 60 6523
18A
6.5A 8A 8A 9A
13A 16A
Frontal protection cover Manual operation handle
85kA 85kA
85kA 85kA
140ms
35ms
190ms
AC Class 3 (10Ie-Making , 8Ie-Breaking) Cos = 0.35DC Class (1.1Ie-Making , 1.1Ie-Breaking) L/R = 1ms
35ms
180ms
35ms
145ms
30ms 30ms
135ms
30ms 30ms
220ms
35ms
AC Class 2 (4Ie-Making , 4Ie-Breaking)Cos = 0.65
100ms
65kA
4A
2A
3A
1.5A
115ms
145ms
30ms
30ms
115ms
50kA 65kA
10,000 operations
50,000 operations
5,000 operations
10,000 operations
50kA
150 operations / hour 30 operations / hour
AC 2,500 V for 1 minute
Power source A: 1C (option: 2C)Power source B: 1C (option: 2C)
Switching capacity AC125V 15A, AC250V 10A , DC14V 15A
8A 10A
8A 10A
4A 5A
3P 4P
1600A
60 65
65kA
65kA
TDSN302A22F1 2 3 4
Poles
2=2P 3=3P 4=4P
Connect ion
F=Front B=Back
Operat ing Vol tage
A22=AC220V15% A11=AC110V15% D11=DC110V15% O=Optional
Rated Current
01=100A 02=200A . . . . . . 30=3000A
1
2
3
4
TSMC-200/200P
/200S
4
INTERIOR CIRCUIT DIAGRAM
LS
A2 B2
LS
SiCC
ATS2
AT2 BT2
BTS2
SCSi
Si
A1
AX
B1
BX
ATS1 BTS1
AT1 BT1
LOA
D
From B-power source
TC
41
AUX
5 6
From A-power source
2 3
TSMC-200/200P
/200S
5
CONTROLLER TSMC-200/200P/200S
Auxiliary Voltage
Power Consumption
Programmable Input/Output 4DI + 4DO + 2RO
Rated Frequency
Close/Open Relay Output
AC Voltage Input
IP55: waterproof gasket is added between controller and its panel
16A/7A 250VAC dry contact
RS485 isolated interface, MODBUS protocol
Temperaqture: -25~+70oC Humidity: 20~90% RH
Temperaqture: -30~+80oC
50/60Hz
16A 250VAC dry contact
Insulation LevelAC2.2kV/1min, among the input/output/power supply
leakage current
TSMC-200/200P
/200S
TSMC-200: AC/DC 90 ~ 280V continuous power supply.
Backlight LCD, Chinese and English display, push-button operation.
OV/UV and CO(TSMC-200P/S only), over/under frequency, phase loss, reverse phase sequence protection.
Synchronization close, voltage/frequency/phase angle difference check between sources (TSMC-200S only).
Automatic/Manual mode. In manual mode,