Toshiba Air Conditioning - RAV-GM Data Sheet

Post on 16-Oct-2021

2 views 0 download

Transcript of Toshiba Air Conditioning - RAV-GM Data Sheet

RAV-GM1101ATP-EOutdoor Unit

Featuresn Redesigned for use with refrigerant R32n Wide operating range (cooling mode –15°C to +46°C)n Auto-diagnostic functionn Flexible, can be utilised for single, twin, triple indoor applicationsn Compact size

Toshiba Air Conditioning - RAV-GM Data Sheet

www.cdlweb.info

All UK duties are based on Cooling Indoor air temperature 22°C DB/16°C WB Outdoor air temperature 28°C DB 50% RH, high fan speed, 5 m pipe run.Heating Indoor air temperature 20°C DB Outdoor air temperature –5°C DB 100% RH, high fan speed, 5 m pipe run. Values are based on the maximum compressor output.

Data obtained from Toshiba Air Conditioning Published Data July 2018.

Dimensional Drawings

Technical DataModel reference RAV-GM1101ATP-ENominal Cooling Capacity kW 9.5

Heating Capacity kW 11.2Operating Range Cooling/Heating °C -15 to 46/-15 to 15Air Flow High m3/h - l/s 4080 - 1133Sound Pressure High Cooling/Heating dB(A) 54/57

Power High Cooling/Heating dB(A) 70/74Unit Height x Width x Depth mm 890 x 900 x 320

Weight kg 68Pipe Connection Flare Connections (gas - liquid) inch 5/8 - 3/8

Min.-Max. Length m 5-50Maximum Height Difference m ±30Drain Port Connection mm 16

Refrigerant R32 Base Charge/Chargeless Length kg/m 2.1/30Additional Charge Liquid Side g/m 35

Run Current Maximum A 14.20Power Cable Outdoor to Indoor 3 core + earthPower Supply Suggested Fuse Size V/ph/Hz-A 220-240/1/50-20