SUBMITTAL DATA - OUTDOOR UNIT VPA060H4M 2P · VRF HEAT PUMP Job: Location: Schedule No.: System...

Post on 06-Mar-2020

2 views 0 download

Transcript of SUBMITTAL DATA - OUTDOOR UNIT VPA060H4M 2P · VRF HEAT PUMP Job: Location: Schedule No.: System...

DISCLAIMER – Due to Lennox’ ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency. 495467 (201805) ©2018 Lennox Industries Inc.

SUBMITTAL DATA - OUTDOOR UNIT VPA060H4M-2P

VRF HEAT PUMP

Job:

Location:

Schedule No.:

System Designation:

FEATURES 

Two-pipe heat pump High efficiency twin rotary compressor

SPECIFICATIONS PERFORMANCECooling Capacity1 (Btu/h) 60,000

EER 9.009.5017.00

ELECTRICAL DATA Power Supply2 (V/Hz/Ph) 208-230/60/1

DIMENSIONS Unit Dimensions (in) Height 52-1/4

Width 35-3/8Depth 13-1/4

Liquid Pipe Connection (in) 3/8 Gas Pipe Connection (in) 3/4

Engineer:

Architect:

Date:

Smooth Sine wave DC inverter

17.20SEER

Heating Capacity1 (Btu/h)HSPF (Region IV)

66,000

9.809.90

Minimum Circuit Ampacity (A)Maximum Overcurrent Protection (A)Compressor RLA (A)No. of CompressorsOutdoor Fan Power Output (W)

4060

30.01

85/851.1/1.1

Max. # of Indoor UnitsSound Pressure Level (dBA) - CLG / HTG

Refrigerant typeFactory refrigerant charge

45% to 130%9 units44 / 44

R-410A8 lbs. 6 oz.

Shipping Weight (lb) 243Net Weight (lb) 220

NOTES

Outdoor Fan FLA (A) GENERAL DATA Connection Ratio

For: Reference Approval Review Construction

Outdoor Fan Total Air Volume (cfm) 4100

Non-Ducted Ducted

Non-Ducted Ducted

Non-Ducted Ducted

Built-in base pan heater Power meter interface Intelligent soft start

WARRANTY • Compressor - 10 year limited warranty• All other components - 10 year limited warranty

*See warranty for details

1. Cooling and Heating Capacity data is rated at thefollowing conditions:Cooling: 80°FDB / 67°FWB Indoor, 95°FDB OutdoorHeating: 70°FDB Indoor, 47°FDB / 43°FWB Indoor

2. Operating Voltage Range: 191V to 247V

DISCLAIMER – Due to Lennox’ ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency. 495467 (201805) ©2018 Lennox Industries Inc.

DIMENSIONS - INCHES (MM)

SUBMITTAL DATA - OUTDOOR UNIT VPA060H4M-2P

VRF HEAT PUMP

35-3/8 (899)

52-1/4(1327)

TOP VIEW

FRONT VIEW

14-1/4(362)

15-3/4(400)

13-1/4(337)

12-5/8(321)

3/4(19)

23-5/8 (600)6

(152)