SOUTH PARS GAS COMPLEX-IRAN

Authors:

Elaheh Esfandiari jahromi Salahedin Sadeghifard Leili Esmaeilani Rasul Shabanian

P t d bP t d b El h h E f di i J h iEl h h E f di i J h iPresented byPresented by: Elaheh Esfandiari Jahromi: Elaheh Esfandiari Jahromi

SOUTH PARS GAS COMPLEX-IRAN

Index

1. Introductionh b l f ll l b d2. The possibility of all alarms observation and 

analyze in “Monitoring System”3. Modification in alarms that were sent to DCS4. Decreasing the number of trips by temperature 4 g p y p

transmitter adjustment and hardware problem rectification

5. Monitoring system upgrading6 conclusion6. conclusion

SOUTH PARS GAS COMPLEX-IRAN

IntroductionIntroduction

Unit specification:pCompressors:

Two similar reciprocating type; manufactured by Two similar reciprocating type; manufactured by Nuovo Pignone italy

PLC  t ll PLC controller:MODICON of Schneider family, quantum series 

programming software: Concept   the monitoring system software :complicity.the monitoring system software :complicity.

SOUTH PARS GAS COMPLEX-IRAN

IntroductionIntroduction

SOUTH PARS GAS COMPLEX-IRAN

IntroductionConsequent result of each Trip

Introduction

Decreasing Production Rate Increasing Acid Gas Flaring Serious Damage to the compressor  equipment and  Serious Damage to the compressor, equipment and accessories

Bad affect on environment and human health Bad affect on environment and human health Presence of Maintenance personnel during each 

   start up 

SOUTH PARS GAS COMPLEX-IRAN

IntroductionIntroduction

According to the shutdown operation reports :“The number of these trips per year> 27”p p y 7

To make a solution for these shutdownsTo make a solution for these shutdowns

“Checking all the alarm lists in both DCS system and HMI in each shutdown “

SOUTH PARS GAS COMPLEX-IRAN

Introduction

SOUTH PARS GAS COMPLEX-IRAN

The possibility of all alarms observation and analyze in “Monitoring System”

MCC Fault as an consequent factor not main trip factorfactor

Sending false alarm as a Common alarm  Sending false alarm as a Common alarm represented for a group of alarms

Not working Hardware redundancy for all trip signals signals 

l t d f

SOUTH PARS GAS COMPLEX-IRAN

common alarm represented a group of alarms

SOUTH PARS GAS COMPLEX-IRAN

Previous and recent status of blocks in logic

First Logic to distinguish healthy channel among two redundant channelsamong two redundant channels

SOUTH PARS GAS COMPLEX-IRAN

Necessary modifications in order to "healthy channel selection" logic correctionhealthy channel selection  logic correction

SOUTH PARS GAS COMLPEX-IRAN

Modification in alarms that were sent to DCS

Necessity of sending real alarm list on time from UCP to y gDCS for operation team to rectify the consequence of trips as soon as possible

P i L i f di di i l i l d l DCS

SOUTH PARS GAS COMPLEX-IRAN

Primary Logic for sending digital signals and alarms to DCSAdding more vital signals to mod bus list according to operation 

requestrequest

SOUTH PARS GAS COMPLEX-IRAN

Applied modification to send more signals to DCS instead of spares

SOUTH PARS GAS COMPLEX-IRAN

First Logic for distinguishing first‐out alarmFirst out alarm from UCP to DCS did not sent correctlyFirst out alarm from UCP to DCS did not sent correctly

SOUTH PARS GAS COMPLEX-IRAN

Corrected Logic for distinguishing first‐out alarmalarm

SOUTH PARS GAS COMLPEX-IRAN

Temperature transmitter adjustment and hardware problem rectification

This part of modification Decreased number of trips caused by TTs and RTD sensorscaused by TTs and RTD sensors

Dedicating most trips to temperature transmitters Dedicating most trips to temperature transmitters when RTD tip braked

Change the setting of these transmitters

SOUTH PARS GAS COMPLEX-IRAN

Temperature transmitter adjustment

SOUTH PARS GAS COMPLEX-IRAN

Analog input channel problem

Problem: No alarm or fault status of di i     f  h   i  f  disconnecting one of the transmitters, from input modulesp

S l ti   tti     ll d   i t   ith Solution: putting a pull down resistance with the value of 2MΩ between negative and positive input channel

SOUTH PARS GAS COMPLEX-IRAN

Monitoring system upgradingUpgrading HMI and replacing old hardware was inevitable because of following reasons:because of following reasons:

Urgent components are not found in market Impossibility of doing any edition and modification on  Impossibility of doing any edition and modification on HMI

Using non industrial computers with long life componentsUsing non industrial computers with long life components Not being user friendly of old operating system Not automatic start up the computer to run cimplicityNot automatic start up the computer to run cimplicityservices and mentioned project

Continues locking this system Co ues oc g s sys e

SOUTH PARS GAS COMPLEX-IRAN

Optimization steps

Suitable and industrial hardware selection with long life components

Installation required softwares(win2000 and Installation required softwares(win2000 and proper antivirus, SQL software and Enterprise, complete cimplicity version and development co p ete c p c ty e s o a d de e op e tlicense)

investigation on communication files investigation on communication files Data base description and adjustment

SOUTH PARS GAS COMPLEX-IRAN

Optimization stepsTransferring the project to the new 

d d upgraded systemCreating printer queue bottom in HMI Creating printer queue bottom in HMI Limit the user’s accessibility Auto restart and auto log on capability without instrument personnel presence and p ppassword

SOUTH PARS GAS COMPLEX-IRAN

ConclusionSignificant reduction in the number of unwanted 

h td  b  fi di     l ti  f   h shutdowns by finding proper solutions for each cause.

bl h easiness troubleshooting  quick maintenance permanent monitoring possibility from far from the compressor station without maintenance ppersonnel 

security enhancement of monitoring system security enhancement of monitoring system