Post on 12-Jan-2017
>
Ventilation Air Conditioning RefrigerationHeating
22ºCInside
OUTSIDEHUMIDITY
PROVIDED BYHEINEN & HOPMAN
35 C
90%
productsself contained units - AM
Self contained unitS
VK self-contained marine type air conditioning unit
• Nominal cooling loads: 3.5 kW / 5.25 kW / 7.0 kW • Sea-water-cooled through shell and tube condenser / fresh-water-cooled through plate heat exchanger• Refrigerant R404a • Electro-coated mild-steel casing with powder-coated paint finish RAL 9018 (grey)• Removable top and side panels for access and maintenance• Quick-release grille for air filter cleaning and replacement• Units supplied factory pre-charged only requiring suitable water and electrical connections• Electrical supply o 110V 1ph 60Hz (VK12 only) o 220V 1ph 50/60Hz o 440V 3ph 60Hz o 380V 3ph 50Hz• Available options o Refrigerant: R134a or R407c o Fresh-water shell and tube condenser o Color to suit operating environment o Electrical Heating
VK12 VK18 VK24
Nominal cooling load (kW) 3.5 5.2 7.0
Nominal air flow - low (m3/h) - high (m3/h)
400 500
500 675
800 100
Fan motor rating (kW) 0.0 0.0 0.0
Compressor motor power (kW) 1.8 2.2 2.8
Nominal sea-water quantity 0.7 0.8 1.3
Nominal fresh-water quantity 0.8 1.1 1.6
Dimensions H (mm) 450 550 550
W (mm) 760 760 106
D (mm) 380 380 380
Weight (kg) 85 95 130
Electric heating (optional) (kW) 1.5 1.5 3.0
Electric heating (kW) 3 4.5 9
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
VK air-cooled air conditioning unit
• Nominal cooling loads: 3.5 kW / 5.25 kW / 7.0 kW • Air-cooled• Refrigerant R407c• Internal section o Electro-coated mild-steel casing with powder-coated paint finish RAL 9018 (grey)• External section o Stainless-steel 316 casing with powder-coated paint finish RAL 9018 (grey) o Condenser fan motors to IP56 o Cu/Cu condenser coil• Removable top and side panels for access and maintenance• Quick-release grille for air filter cleaning and replacement• Units supplied factory pre-charged • Electrical supply o 220V 1ph 50/60Hz o 380V 3ph 50Hz o 440V 3ph 60Hz• Available options o Internal section stainless-steel 316 casing with powder-coated finish RAL 9018 (grey) o Color to suit operating environment o Split system version o Electric heating o Refrigerant R134a
VK12 VK18 VK24
Nominal cooling load (kW) 3.5 5.2 7.0
Nominal air flow - low (m3/h) - high (m3/h)
400 500
500 675
800 1000
Evaporator Fan motor rating (kW) 0.037 0.045 0.074
Compressor motor power (kW) 1.87 2.28 2.89
Condenser fan motor rating 0.18 0.25 0.18
Dimensions H (mm) 450 550 550
W (mm) 760 760 1060
Weight (kg) 125 135 195
Electric heating (optional) (kW) 1.5 1.5 3.0
our mission: to ensure you the perfect
climate indoors, regardless of the weather outside
“ “
tR self-contained marine air conditioning unit
• Nominal cooling loads 7.0 kW to 70.0 kW• Sea water / fresh water cooled through shell and tube condenser• Refrigerant R404a• Spigoted duct connection• Electro coated mild steel casing with powder coated paint finish RAL 9018 (Grey)• Removable panels for access and maintenance• Quick release grille for air filter cleaning and replacement• Units supplied factory precharged only requiring suitable water and electrical connections• Electrical supply 380V 3ph 50Hz or 440V 3ph 60Hz• Other options available o Color to suit operating environment o Fresh air connection o Fan pressures to suit application o Electric heating o 690V 3ph 60Hz electric supply o Plenum and grille discharge o Air flow through base of unit (Downward discharge) o Refrigerant R134a or R407c o See separate data sheet for air cooled TR unit
TR02 TR03 TR05 TR08 TR10 TR15 TR20
Nominal cooling load (kW) 7.0 10.5 17.5 28.0 35.0 56.0 70.0
Nominal air flow (m3/h) 1080 1530 2550 4075 5100 7725 10200
Plenum discharge fan motor rating 0.18 0.37 0.55 1.10 1.50 2.20 3.00
Compressor motor power (kW) 2.89 3.55 5.48 9.79 10.94 19.58 21.88
Nominal sea-water quantity (m3/h) 1.34 1.43 2.51 4.14 6.89 8.28 13.78
Nominal fresh-water quantity (m3/h) 1.02 1.11 2.10 3.30 4.26 6.60 8.52
Dimensions H (mm) 1300 1300 1600 1800 1800 2000 2100
W (mm) 700 900 900 1100 1250 1400 1800
D (mm) 450 450 550 650 650 850 850
P (mm) 110 120 180 230 230 300 330
Weight (kg) 169 193 246 312 365 557 668
Electric heating (optional) (kW) 1x3.0 1x4.5 2x4.5 2x9.0 2x9.0 3x9.0 4x9.0
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
tRa air-cooled split marine air conditioning unit
• Nominal cooling loads: 10.5 kW - 70.0 kW• Air-cooled• Refrigerant R407c • Internal section o Electro-coated mild-steel casing with powder-coated paint finish RAL 9018 (grey) o Removable panels for access and maintenance o Quick-release grille for air filter cleaning and replacement• External section o Electro-coated mild-steel with powder-coated paint finish RAL 9018 (grey) o Condenser coil with CU tubes and Cu fins• Units supplied factory pre-charged• Electrical supply: 380V 3ph 50 Hz / 440V 3ph 60Hz• Available options o Color to suit operating environment o Refrigerant R134a o Fan pressures to suit application o External section with horizontal air flow o Electric heating o Interconnecting piping cable o Electrical supply: 690V 3ph 60Hz o Refer to the separate data sheet for water-cooled units
TRA03 TRA05 TRA08 TRA10 TRA15 TRA20
Nominal cooling load (kW) 10.5 17.5 28.0 35.0 56.0 70.0
Nominal air flow evaporating 1530 2550 4075 5100 7725 10200
Plenum discharge fan motor rating 0.37 0.55 1.10 1.50 2.20 3.00
Compressor motor power (kW) 3.55 5.48 9.79 10.94 19.58 21.88
Nominal condensing load (kW) 14.42 21.42 33.24 47.44 77.78 94.88
Nominal air-flow condensing (m3/h) 6624 9360 14400 21600 28080 37440
Condenser fan motor rating (kW) 2@0.37 2@0.55 2@0.75 3@0.58 3@0.75 4@0.75
Electric heating (optional) (kW) 1 x 4.5 2 x 4.5 2 x 9.0 2 x 9.0 3 x 9.0 4 x 9.0
Internal Section
Dimensions H (mm) 1300 1600 1800 1800 2000 2100
W (mm) 900 900 1100 1250 1400 1800
D (mm) 450 550 650 650 850 850
P (mm) 120 180 230 230 300 330
Weight (kg) 178 219 284 328 501 594
External Section
Dimensions H (mm) 1380 1400 1420 1400 1420 1420
W (mm) 1200 1400 1700 2400 2600 3200
D (mm) 700 800 900 900 1100 1100
Weight (kg) 154 200 253 290 409 528
KW self-contained marine air conditioning unit
• Nominal cooling loads: 10.0 kW - 25.0 kW• Fresh-water-cooled through plate heat exchanger• Refrigerant R404a • Spigoted duct connection• Electro-coated mild-steel casing with powder-coated paint finish RAL 9018 (grey)• Removable front panel for access and maintenance• Quick-release grille for air filter cleaning and replacement• Units supplied factory pre-charged only requiring suitable water and electrical connections• Electrical supply o 380V 3ph 50Hz o 440V 3ph 60Hz• Available options o Sea-water-cooled through coaxial condenser o Fresh-air connection o Color to suit operating environment o Plenum and grille discharge o Electric or hot-water heating o Fan pressure to suit application o Refrigerant R134a or R407c o Refer to the separate data sheet for cooled KW units
KW10 KW15 KW20 KW25
Nominal cooling load (kW) 10 15 20 25
Nominal air flow (m3/h) 1500 2200 2950 3700
Fan motor rating (kW) 0.37 0.55 0.75 1.1
Compressor motor power (kW) 3.72 5.88 8.25 9.91
Nominal fresh-water quantity 2.41 3.45 4.56 6.01
Dimensions H (mm) 1500 1700 1950 1950
W (mm) 550 700 700 800
D (mm) 550 750 750 750
P (mm) 150 200 225 245
Weight (kg) 186 234 282 309
Electric heating (optional) (kW) 1 x 4.5 2 x 4.5 2 x 6.0 2 x 9.0
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
KWa air-cooled split marine air conditioning system
• Nominal cooling loads: 10 kW - 25 kW • Air-cooled• Refrigerant R407c• Internal section o Electro-coated mild-steel casing with powder-coated paint finish RAL 9018 (grey) o Removable panels for access and maintenance o Quick-release grille for air filter cleaning and replacement• External section o Electro-coated mild-steel with powder-coated paint finish RAL 9018 (grey) o Condenser coil with CU tubes and Cu fins• Units supplied factory pre-charged• Electrical supply: 380V 3ph 50 Hz / 440V 3ph 60Hz• Available options o Color to suit operating environment o Refrigerant R134a o Fan pressures to suit application o External section with horizontal air flow o Electric heating o Interconnecting piping cable o Electrical supply: 690V 3ph 60Hz o Refer to the separate data sheet for water-cooled units
KWA10 KWA15 KWA20 KWA25
Nominal cooling load (kW) 10 15 20 25
Nominal air flow (evaporating) (m3/h) 1500 2200 2950 3700
Plenum discharge fan motor rating 0.37 0.55 0.55 1.10
Compressor motor power (kW) 3.55 5.48 5.48 9.91
Nominal condensing load (kW) 13.92 21.03 26.03 36.01
Nominal air flow (condensing) (m3/h) 6624 8022 10670 14400
Condenser fan motor rating (kW) 2@0.37 2@0.55 2@0.55 3@0.75
Electric heating (optional) (kW) 1 x 4.5 2 x 4.5 2 x 6.0 2 x 9.0
Internal Section
Dimensions H (mm) 1500 1700 1950 1950
W (mm) 550 700 700 800
D (mm) 550 750 750 750
P (mm) 150 200 225 245
Weight (kg) 186 234 273 308
External Section
Dimensions H (mm) 1380 1400 1400 1420
W (mm) 1200 1400 1400 1700
D (mm) 700 800 800 900
Weight (kg) 154 200 200 253
acc (H&V) marine air-cooled condenser
• Electro-coated mild-steel casing with powder-coated paint finish RAL 9018 (grey)• Condenser coil with Cu and Cu fins• Refrigerant R407c• Electrical supply o 380V 3ph 50Hz o 440V 3ph 60Hz• Available options o Stainless-steel 316 Casing o Protective coating to coil o Atex II 2 G Eex IIB T4 for hazardous areas o Refrigerant R134a
ACCV3 ACCV5 ACCV8 ACCV10 ACCV15 ACCV20
Nominal Condensing load (kW) 14.42 21.42 33.24 47.44 77.78 94.88
Nominal air flow (m³/h) 6624 9360 14400 21600 28080 37440
Fan motor rating (total) (Kw) 2@0.37 2@0.55 2@0.75 3@0.58 3@0.75 4@0.75
Unit dimensions (Vertical) H(mm) 1380 1400 1420 1400 1420 1420
W(mm) 1200 1400 1700 2400 2600 3200
D(mm) 700 800 900 900 1100 1100
Unit weight (kg) 154 200 253 290 409 528
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
“
ACCH3 ACCH5 ACCH8 ACCH10 ACCH15 ACCH20
Nominal Condensing load (kW) 14.42 21.42 33.24 47.44 77.78 94.88
Nominal air flow (m³/h) 6624 9360 14400 21600 28080 37440
Fan motor rating (total) 2@0.37 2@0.55 2@0.75 3@0.58 3@0.75 4@0.75
Unit dimensions (Horizontal) H 900 1000 1100 1100 1300 1300
W (mm) 1200 1400 1700 2000 2600 3200
D (mm) 700 700 700 700 700 700
Unit weight (kg) 174 216 287 330 449 558
Nominal duties are based on ambient air at 40°C
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
fP air-cooled hazardous area air conditioning unit
• Nominal cooling loads: 3.5 kW / 5.25 kW / 7.0 kW • Air-cooled• Refrigerant R407c• A60-class fire-resistant division between internal and external section• Internal section o Suitable for non-hazardous area o Electro-coated mild-steel casing with powder-coated paint finish RAL 9018 (grey)• External section o ATEX II 2 G EEx d IIB T4 suitable for hazardous area o Cu/Cu condenser coil o Stainless-steel 316 casing with powder-coated paint finish RAL 9018 (grey)• Removable top and side panels for access and maintenance• Quick-release grille for air filter cleaning and replacement• Units supplied factory pre-charged • Electrical supply o 220V 1ph 50/60Hz o 380V 3ph 50Hz o 440V 3ph 60Hz• Available options o Color to suit operating environment o Split system version o Electric heating o Refrigerant R134a
FP12 FP18 FP24
Nominal cooling load (kW) 3.50 5.25 7.00
Nominal air flow - low (m3/h) - high (m3/h)
400 500
500 675
800 1000
Evaporator Fan motor rating (kW) 0.037 0.045 0.074
Compressor motor power (kW) 1.87 2.28 2.89
Condenser fan motor rating (kW) 0.18 0.25 2@0.18
Dimensions H (mm) 450 550 550
W (mm) 760 760 1060
Weight (kg) 125 135 195
Electric heating (optional) (kW) 1.5 1.5 3.0
to serve the fleet with the most reliable HVac
systems
“ “
KWG galley self-contained air conditioning unit
• Unit designed to meet SOLAS 2000 requirement• Nominal cooling loads: 10.0 kW / 25.0 kW • Fresh-water-cooled through plate heat exchanger• Refrigerant R404a • Ducted, filtered rear inlet and vertical discharge• Electro-coated mild-steel casing with powder-coated paint finish RAL 9018 (grey)• Removable panels for access and maintenance• Units supplied factory pre-charged only requiring suitable water and electrical connections• Electrical supply o 380V 3ph 50Hz o 440V 3ph 60Hz• Available options o Stainless-steel 316 casing with powder-coated paint finish o Color to suit operating environment o Alternative fan pressures o Split system version o Hot-water heating o Refrigerant: R134a or R407c o Sea-water-cooled through coaxial condenser
KWG10 KWG15 KWG20 KWG25
Nominal cooling load (kW) 10.0 15.0 20 25
Nominal heating load (kW) 9.0 12.0 13.5 18.0
Nominal air flow (m3/h) 600 700 1100 1550
External pressure (kW) 600 600 600 600
Fan motor rating (kW) 0.37 0.37 0.55 0.75
Compressor motor power (kW) 3.55 4.72 6.45 9.79
Nominal water quantity 1.08 1.56 3.12 3.70
Dimensions H (mm) 1500 1750 1750 1750
W (mm) 550 700 700 700
D (mm) 550 750 750 750
Weight (kg) 230 320 340 370
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
fc marine fan coil unit
• Nominal cooling loads: 10 kW - 70 kW • Spigoted duct connection• Electro-coated mild-steel casing with powder-coated paint finish• Removable front panels for access and maintenance• Quick-release grille for air filter cleaning and replacement• Electrical supply o 380V 3ph 50Hz o 440V 3ph 60Hz• Available options o Plenum and Grille discharge o Color to suit operating environment o Alternative fan pressures o Electric or hot-water heating o Fresh-air connection o Stainless-steel casing
FC10 FC15 FC20 FC30 FC40 FC50 FC70
Nominal cooling load (kW) 10 15 20 30 40 50 70
Nominal air flow (m3/h) 1600 2600 3600 4800 6300 8000 11250
Nominal water flow (m3/h) 0.4 0.6 0.79 1.19 1.59 1.98 2.78
Fan motor rating 0.37 0.55 0.75 1.10 1.50 1.50 2.20
Dimensions H (mm) 1500 1750 1750 1750 1750 2000 2000
W (mm) 500 700 700 700 1200 1200 1500
D (mm) 500 750 750 750 750 750 750
P (mm) 260 270 330 340 340 400 450
Weight (kg) 121 168 185 221 278 303 372
Electric heating (optional) (kW) 1 x 4.5 2 x 4.5 2 x 6.0 2 x 9.0 2 x 9.0 3 x 9.0 4 x 9.0
Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.
cl 3000 tobacco smoke filtration unit • The Clearstar CL 300 reduces tobacco smoke concentration, odors and other airborne contaminates• Environmentally friendly, being non-electrostatic there is no increase in low level ozone in the atmosphere• 3-stage filter assembly: pre-filter, ultra-filter and activated carbon filter• 3-speed fan operation: low, medium and boost• The Clearstar CL300 under normal conditions will effectively deal with a compartment of approximately 50 m3
• Electrical supply o 110V 1ph 60Hz o 220V 1ph 60Hz• Weight: 35 kg
www.heinenhopman.com
Heinen & Hopman encourages a more
sustainable world. By providing eco-friendly solutions and serviceswe offer our clients
the option of reducing energy consumption
and thus co2 emissions. Visit
greenmanifest.info for more information.
BrazilT: +5521 3587 4241/4244E: info@br.heinenhopman.com
france - la ciotatT: +334 4204 8685E: info@heinenhopmanfrance.com
france - GrasseT: +336 3090 7786 E: info@heinenhopmanfrance.com
GermanyT:+49 4073 1680E: info@drewsmarine.com
indiaT: +9133 6499 1293E: info@heinenhopmanindia.com
italyT: +3901 8745 7970E: info@it.heinenhopman.com
the netherlands (HQ)T: +313 3299 2500E: info@heinenhopman.com
the netherlands (Rotterdam)T: +317 8890 8050E: binnenvaart@heinenhopman.nl
norwayT: +47 6919 0900E: admin@teknotherm.no
Peoples Republic of chinaT: +8621 3253 2896E: info@cn.heinenhopman.com
Peoples Republic of chinaT: +86 510 8528 1763E: ivo.klaric@teknotherm.no
PolandT: +489 1433 1800E: tmh@teknotherm.no
RomaniaT: +402 3644 8222E: office@ro.heinenhopman.com
RussiaT: +7 (4012) 308 801E: info@heinenhopman.ru
SingaporeT: +65 6897 7879E: info@sg.heinenhopman.com
South KoreaT: +8270 4901 0000E: info@kr.heinenhopman.com
SpainT: +349 3225 9668E: info@es.heinenhopman.com
SwedenT: +46 3121 7500E: mats.uden@teknotherm.no
turkeyT: +9021 6493 8118E: info@tr.heinenhopman.com
uae (abu dhabi) T:+971 2550 4147E: info@caspuae.com
uae (dubai)T: +971 4263 5453E: info@caspuae.com
uSa - fort lauderdale, floridaT: +195 4463 0110E: info@arwmaritime.com
uSa - Houma, louisiana T: +198 5876 7989E: leblanc@leblancandassociates.com