Post on 01-Aug-2020
Page 1 of 2 Sanitary District #1
Agenda posted at Greenville Town Hall, Greenville Post Office, Town Website (www.townofgreenville.com) and emailed to Rachel Rausch. This is apublic meeting. As such, a quorum of the Town Board, Plan Commission, Park Commission, Board of Appeals, or other Town committee may bein attendance. However, the only business to be conducted is for the Sanitary District #1.
SANITARY DISTRICT #1MEETING AGENDA
DATE: Monday, August 26, 2019TIME: 7:30 PMLOCATION: Greenville Town Hall, W6860 Parkview Drive, Greenville, WI 54942
OPENING:
1. CALL TO ORDER/ROLL CALL
2. PUBLIC COMMENT FORUM:Members of the public are welcome to address the Sanitary District/Storm Water Utility. Individualswishing to speak on an item (whether on the agenda or not) must sign in prior to the start of themeeting and may speak during the Public Comment Forum segment of the meeting. This segment isplaced early in the agenda so the public may make their comments prior to any discussion or actionby the Sanitary District/Storm Water Utility. Individual comments are limited to no more than threeminutes each. The Public Input section is limited to a total of 15 minutes. Once the public inputsegment ends there will be no additional discussion from the audience. The Board may suspend thisrule if deemed necessary.
Note regarding non-agenda Town related matters: Pursuant to WI Statutes 19.83(2) and 19.84(2),the public may present matters; however, they cannot be discussed or acted upon until specificnotice of the subject matter of the proposed action can be given.
SANITARY DISTRICT #1 BUSINESS AGENDA:Notice is hereby given that the Greenville Town Board may take action on any item listed within thisagenda.
3. CONSENT AGENDA:
1
Page 2 of 2 Sanitary District #1
Agenda posted at Greenville Town Hall, Greenville Post Office, Town Website (www.townofgreenville.com) and emailed to Rachel Rausch. This is apublic meeting. As such, a quorum of the Town Board, Plan Commission, Park Commission, Board of Appeals, or other Town committee may bein attendance. However, the only business to be conducted is for the Sanitary District #1.
(Items on the Consent Agenda are routine in nature and require one motion to approve all itemslisted. Prior to voting on the Consent Agenda, items on the Consent Agenda may be removed at therequest of any Supervisor and addressed immediately following the motion to approve the otheritems on the Consent Agenda.)
4. NEW BUSINESS FOR DISCUSSION & POSSIBLE ACTION:
4.a. CB Trail Hydrant Relocation Contract Award to Vinton for $13,001.50M- CB Hydrant Relocation.pdf
4.b. Well 3 Progress UpdateM-Well 3 Progress Update 2019.08.22.pdf
CLOSING:
5. ADJOURNMENT
2
Page 1 of 1
“Town of Greenville”
AGENDA MEMORANDUM
To: From: Date: RE:
Honorable Town Chairperson and Town Supervisors Cody Simonis Utility Superintendent 7-26-2019CB Trail Hydrant Relocation
ACTION TYPE: This item is for possible Town Board Approval/Denial.
BACKGROUND & SUMMARY: The hydrant on CB and Design has to be relocated due to the CB trail being moved/redone. We reached out to 4 companies to get quotes for this work but only received bids from Vinton Construction Co. and Immel Excavation. Due to their already busy sceduels, Wood Excavation and Hieptas Construction chose not to bid on this project.
Vinton is not the cheapest option but they are the construction company that is doing all of the other work so it makes sense to have them do this work as well.
STAFF RECOMMENDATION: Staff recommends the Board approve as proposed. If the Board is in agreement, the following motion may be made: “Motion to approve Vinton to relocate the fire hydrant at CB and Design for the price of 13001.50”
POLICY/PLAN REFERENCE(S): 1. Town Purchasing Policy – Adopted August 2017
FISCAL IMPACT: Is there a fiscal impact? Yes, $13001.50 Is it currently budgeted or planned? No Amount budgeted: $0 Account #: 610-6510-290
###
Attachments: 1. Vinton Construction Co Quote2. Immel Excavation Quote
3
4
ROBERT J. IMMEL EXC., INC.
P.O. BOX 135
GREENVILLE,WI 54942
PHONE (920) 757-5906
FAX (920) 757-0189
Greenville, CTY CB, new valve & hydrant, 2019
Item No Name of Item Approx. Qty Total PricePrice per foot
1 remove existing valve, hydrant 1 $2,375.00$2,375.00ls
2 new 6" valve, & hydrant 1 $10,510.00$10,510.00ls
Total Cost of Bid: $12,885.00
Bid Note:
This hydrant, and valve is located by Design Dr. in front of School Specialty.No restoration included.Excavated material used as backfill.We could replace the bolts on the existing tee, and valve, as needed, while dug up. This will have to be done, on a time & material basis.The price quoted does not include replacing the bolts on the tee, and valve.
Thank you forb the opportunity to quote this project. Todd Immel
Monday, July 15, 2019 Page 1 of 15
Page 1 of 1
“Town of Greenville”
AGENDA MEMORANDUM
To: Honorable Town Chairperson and Town Supervisors From: Cody Simonis Sanitary District Superintendent Date: 7-26-2019 RE: Well 3 Progress Update
ACTION TYPE: This item is for Town Board discussion only BACKGROUND & SUMMARY: The work done so far by CTW includes the pulling of the pump head and removal of 300 feet of 8 inch piping column. This is the column that the pump is hung from. The crew will also be going through the pump head to determine what has to be fixed. Due to the excessive wear, they are going to replace the pump with one that is very similar to the one that is currently there.
CTW will also be doing cleaning methods including mechanical air blasting and a chemical wash to break up the iron bacteria, or biofilm. Air impulse blasting is shot down in the well casing to break up the iron bacteria. After air blasting, they will scrub the casing with a stiff bristle brush to get any loose biofilm. Once that is done, they will do a spinner test to see were the water is flowing. Lastly they will chemically clean the casing of iron bacteria to get the bore holes reopened.
After the pipes when they were pulled, it was determined that three pieces of the 8” piping that should also be replaced. The biofilm is so bad that Troy from CTW said out of a scale of 1 to 10 it was about a 9. POLICY/PLAN REFERENCE(S):
1. Town Purchasing Policy – Adopted August 2017 FISCAL IMPACT:
Is there a fiscal impact? Yes, $6,735.00 Is it currently budgeted or planned? No Amount budgeted: $0 Account #:
### Attachments:
1. CTW Report
6
21500 W. Good Hope Road, Lannon, WI 53046 www.ctwcorporation.com (262) 253-6613 Locations: Baraboo, Eau Claire, Green Bay, La Crosse
August 11, 2019
Mr. Thad Majkowski
Cedar Corporation
1695 Bellevue Street
Green Bay, WI 54311
RE: Greenville Well #3 – Phase 1 Update 1
Mr. Majkowski,
As of 8/11/19, we have completed the following:
• All pumping components have been removed from the well, pump was hung on 8” pipe
to 300’
• 25’ of 8” column needs to be replaced, one was cut due to being too tight to remove and
the others were due to excessive biofilm corrosion
• 2 new stainless steel bearing retainers will be needed to go in conjunction with the
column pipe replacement
• Stainless steel head shaft is worn beyond repair and will need to be replaced
• Stuffing box will need to be rebuilt including: GFO packings and a new brass bushing
• 28 rubber bearings will be replaced at each ten foot shaft bearing
• Well has been televised and excessive biofilm is present in the entire well…water was
added prior to the well being televised and clarity was only established to 151’ deep
• The 12M 4 stage pump from 2009 has been disassembled and is not
repairable/rebuildable – see below
View of the pump
suction…clearly full of
biofilm deposition
7
21500 W. Good Hope Road, Lannon, WI 53046 www.ctwcorporation.com (262) 253-6613 Locations: Baraboo, Eau Claire, Green Bay, La Crosse
Cleaned
bowl
assembly,
this is the
down view
of the
impeller
wear ring
and the
bowl…large
volumes of
casting are
missing due
to biofilm
induced
corrosion
Down view of brass
impeller wear
ring…casting is
completely eroded
below the wear ring
8
21500 W. Good Hope Road, Lannon, WI 53046 www.ctwcorporation.com (262) 253-6613 Locations: Baraboo, Eau Claire, Green Bay, La Crosse
Side view of
3rd brass
impeller and
bowl, erosion
wear induced
by biofilm
induced
corrosion has
almost
removed
enough
material to
make a hole
through the
pump
Additional side view of
3rd brass impeller with
close up of casting
erosion beyond repair or
reuse
9
21500 W. Good Hope Road, Lannon, WI 53046 www.ctwcorporation.com (262) 253-6613 Locations: Baraboo, Eau Claire, Green Bay, La Crosse
We have requested pricing for a NEW 11CHC-5 stage Goulds pump that will produce 700gpm
@ 304TDH.
Please let us know if any additional information is needed and thank you for your patience