CYRUSSTRUCTURAL ENGINEERING, CONSTRUCTION AND PROPERTIESKM 38 Lagos/Abeokuta Exp. Rd, Owoyemi House, Sango Ota, Ogun State, Nigeria.Email:gbengaomole@gmail.com Mobile: +234-08034006525;+234-07036438781
Postal: P. O. Box 1814, Ota, Ogun State
Our Ref CR/008/13 Your Ref Date 7th
September 2011
The Managing DirectorGT Homes, 28 Saka Tinubu Street,
Victoria Island, Lagos.
Sir,
REPORT ON SITE VISIT TO THE HIGH RISE PROPERTY SITUATED
AT 38/40, STRACHAN STREET, OFF IGBOSERE ROAD, OBALENDE,
LAGOS STATE
PREAMBLE
The said property is a seven storey building with a penthouse which was
affected by an inferno. The ground and first floors were un-affected by the
inferno. The effects of the flames on the structural members were noticeable at
the second floor and on to the seventh floor as well as the penthouse. The
destructive effect of the fire varied from floor to floor.
8/4/2019 Report on Igbosere
2/7
2
DETAILED OBSERVATIONS
Table 1: Second Floor
s/n Defect Description Recommended Solution
1 Spalling effects could beobserved on the cover to
the concrete walls and
the partition sandcreteblockwalls.
The partition sandcrete blockwalls (which hasbeen weakened by the flames) should be
completely removed and replaced. The
damaged mortar cover on the concrete wallsshould also be exfoliated completely and
replaced with high grade mortar
2 The lintel to the door thatleads to the main hall
(close to the internalstaircase) has beenweakened
It can be re-cast
3 Some portions of the
cover to the top slab had
fallen off
See general observation No. 1
Table 2: Third Floor
s/n Defect Description Recommended Solution
1 The partition wall on this floor (close to theinternal staircase) are extremely weakened
and may collapse any moment or at theslightest disturbance (Figure 1)
It should be removed withutmost caution to avoid
impact on the floor slab
2 Portions of the top slab reinforcement are
seriously compromised. Part of thereinforcement is twisted and weakened(Figures 2 and 3).
See general observation No.
2 and generalrecommendation No. 2
3 The lintel to the door that leads to the main
hall (close to the internal staircase) has beenweakened
It can be re-cast
8/4/2019 Report on Igbosere
3/7
3
Fig. 1: Partition wall close to the stairwell about to disintegrate
Fig. 2: Seriously compromised slab reinforcement
8/4/2019 Report on Igbosere
4/7
4
Fig. 3: Slab affected by the flames
Table 3: Fourth Floor
s/n Defect Description Recommended Solution
1 The partition walls on this floor areweakened
All internal partition walls are tobe removed and replaced
2 Spalling effects could be observed on
the covers to the concrete members(Figure 4)
See general recommendation
No. 1
3 The lintel to all the doors on this floor
are weak
They should be re-cast
Figure 4: An exposed bottom reinforcement in a beam
8/4/2019 Report on Igbosere
5/7
5
Table 4: Fifth Floor
s/n Observation Recommendation
1 The structural members on this floor wererelatively unaffected by the flames with theexception of soot on the walls and top slab.
All concrete covers were in place and noexposed reinforcements could be observed.
The soot on the walls andceiling on this floor may bescrubbed off and
redecorated
2 The partition walls are also in order.
Table 5: Sixth Floor
s/n Defect Description Recommended Solution
1 Portions of the top slab and beams haveexposed reinforcements
See generalrecommendation No. 1
2 The partition walls showed signs of
weakening
See general
recommendation No. 3
Table 6: Seventh Floor
s/n Defect Description Recommended
Solution
1 The effect of the fire on this floor is not much.However, some minor portions of the top slab and
beams have lost their cover to the reinforcements
See generalrecommendation No.
1
2 Portions of the flat roof are leaking It could be felted
Table 7: Penthouse
s/n Observation Recommendation
1 The structural members on this floor were
relatively unaffected by the flames with theexception of soot on the walls and top slab.All concrete covers were in place and no
exposed reinforcements could be observed.
The soot on the walls and
ceiling on this floor may bescrubbed off andredecorated
2 Portions of the flat roof are leaking It could be felted
8/4/2019 Report on Igbosere
6/7
6
Table 8: Others minor observations
s/n Defect Description Recommended Solution
1 The perimeter fence at the back of thebuilding is weak and about to fall on thebuilding behind the property.
The wall should be removedand replaced to avoid thesecondary cost of repairing an
adjacent building
2 The septic tank to the property (whichwas cleverly covered with concrete slab)appears filled up. It could be observed
through the vents on the floor just in frontof the generator house
The waste matter here couldbe suctioned away
GENERAL OBSERVATIONS
1. The flames had very serious impact on the partition walls and causeddamage to the covers to much of the concrete structural members on the
identified floors.
2. The greatest structural concern in this entire property is on the third floortop slab (the base of the fourth floor slab).
3. The effect of the fire appeared to be concentrated around the elevatorshaft area. Access could not be made into the elevator because it waslocked.
4. The structural integrity of the building in general is still intact.
GENERAL RECOMMENDATIONS
1. All damaged covers to concrete members should be replaced with highgrade mix of mortar.
2. The damage to the third floor top slab (Table 2, No. 2) demands that allextreme loadings on this isolated portion (situated between the two beams
that flank the stair well) should be avoided. Definition of extreme loading
here include but is not limited to:
8/4/2019 Report on Igbosere
7/7
7
i. Crowds such as church activities where large numbers of excitedpeople jump around.
ii. Heavy machineries such as printing presses etc.
This problem can be remediated by considering two alternatives.
i. Cut off the slab in the seriously affected area using concrete saw.However, the attendant vibrations on other weakened sections of
the property and the aesthetic appeal would not be welcome. So
this leads to the second and more welcome solution.
ii. Replace the cover to the slab but cordon off the weakened sectionon the fourth floor using light weight aluminium partition and just
leave access ways for people to pass from one section of the floor
to another. That way, no dead loads would be imposed on the
affected slab.
3. All affected partition walls should be removed and replaced.4. Further investigation should be conducted on the elevator systems and
fire installation systems by specialist mechanical and electrical Engineers.
Yours faithfully,
Dr. David Omole (PhD, MNSE, COREN Reg.)
For: CYRUS