Multi-turn actuators
for open-close and modulating duty
SA 07.1 – SA 48.1
SAR 07.1 – SAR 30.1
SAEx(C) 07.1 – SAEx(C) 40.1
SAREx(C) 07.1 – SAREx(C) 30.1
Torques up to 32,000 Nm
Product description
2 |
ApplicationsAUMA multi-turn actuators are used wherever the auto-
mation of a valve requires rotation, e.g. when using gate
valves. The actuators can be adapted to suit the require-
ments of nearly all valve applications. This is achieved by:
■ an extremely wide torque range,
■ various combination possibilities with AUMA valve gear-
boxes and controls,
■ a large variety of versions.
Energy: Power plants
: Air pollution control
: District heating
: Pipelines
Chemical industry: Chemical industry
: Petrochemical industry
: Pharmaceutical industry
Water/Wastewater: Water works
: Sewage treatment plants
: Pumping stations
: Dams
Others: Oil and gas industry
: Air conditioning
: Ship building industry
: Steel mills
: Cement plants
: Food industry
| 3
Solutions for a world in motion
Subject to change without notice.The product features and technical data provided do not express or imply any warranty.
This brochure will provide both the beginner and the
expert with an overview of the functions and applications
of AUMA SA/SAR multi-turn actuators. It is used as the
basis to determine whether a device is suitable for the
chosen application.
For detailed product selection refer to the separate data
sheets and price lists. On request, AUMA engineers within
field service and within our subsidiaries can help you to
find the correct device for the application.
The SA/SAR multi-turn actuator version has been avail-
able since 1986. Ever since, the actuators have been con-
tinuously improved. They can be combined with the latest
generation of AUMA actuator controls – enabled by the
modular design principle of the AUMA product range.
Both the mechanical interfaces as well as options for inte-
gration into a DCS are always up to date.
The latest detailed information on the SA and SAR
multi-turn actuators can be found on the Internet under
www.auma.com. All documents, including dimensional
drawings, wiring diagrams and final inspection records (for
supplied multi-turn actuators) are available on the Internet
in a digitalised form.
Table of contents
Applications/duty types 4
Modular design – versions 6
Design principle 8
Summary of applications,
functions, and equipment 9
Service conditions 10
Functions 12
Signals/indication 18
Integral controls 21
Electrical connectionfor non-explosion-proof actuators 22
Electrical connection
for explosion-proof actuators 23
Valve attachment 24
Combinations with valve gearboxes 25
Technical data 26
Certificates 29
Quality is not just a matter of trust 30
The actuator specialist 31
Literature 32
Index 33
AUMA worldwide 34
4 |
Applications/duty types
AUMA automates valves; to put it in a nutshell, this is
what AUMA actuators do. In other words: AUMA actuators
can be used for remote control of valves; either by an opera-
tion command manually triggered in the control room or
within the framework of an automated process-controlled
procedure. AUMA is an actuator specialist.
According to the different valve designs, there are
multi-turn, part-turn and linear actuators. This brochure puts
the focus on multi-turn actuators. Multi-turn actuators are
predominantly used for the automation of gate valves, for
example, where more than one rotation of the valve shaft is
required.
Shutting off, positioning, controlling
The second important selection criterion after the type of
movement is the type of duty. Is the valve to be used as
shut-off device (open-close duty), is the valve is to be posi-
tioned in mid-travel (positioning mode) or is the valve posi-
tion to be changed at short intervals, i.e. to control the flow
through a pipeline (modulating duty)? These are essential fac-
tors for sizing the valve and the actuator as the load may
vary considerably depending on the operation mode.
Consequently, there are AUMA actuators for open-close
and positioning duty as well as actuators which meet the
high requirements of modulating duty.
OPEN-CLOSE duty and positioning dutyOPEN-CLOSE duty
The valve is operated relatively seldom, the time intervals
can span between a few minutes up to several months.
Typical operation in open-close duty
[t1] Running time. The maximum permissible running time without inter-ruption is usually 15 min, optionally 30 min.
Positioning duty
The valve is operated to a specified intermediate position,
e.g. to set a consistent flow rate. The same running time lim-
its as in open-close duty apply.
Typical operation in positioning duty
t
t1
AUMA multi-turn actuators mounted on gate valves in the kerosene tankfarm at Chubu airport in Japan.
AUMA explosion-proof actuators distribute the crude oil to differenttanks in a tank farm in Northern Germany.
t
| 5
Modulating dutyThe most distinctive feature of a closed-loop application is
that changing conditions require frequent adjustment of the
MOV. Sensitive closed-loop applications require adjustments
within intervals of a few seconds.
The demands on the actuator are high. Mechanical com-
ponents and the motor must be designed correctly to with-
stand a large number of operations over a long time with no
decline in the modulating accuracy.
Typical operation in modulating dutyt
Gate valves with mounted AUMA actuator for a dam project in Australiabefore installation.
AUMA modulating actuator mounted on a control valve in a desalinationplant.
Types of duty for AUMA actuatorsThe correct AUMA actuator for the duty can be deter-
mined by the type designation.
Multi-turn actuators for open-close and positioning
duty
AUMA multi-turn actuators for open-close and positioning
duty are marked with the type designations SA, SAExC, and
SAEx.
Available sizes:
■ SA 07.1 – SA 48.1
■ SAExC 07.1 – SAExC 16.1
■ SAEx 25.1 – SAEx 40.1
As standard, the actuators conform to the types of duty
S2 - 15 min or S2 - 30 min as an option.
Multi-turn actuators for modulating duty
AUMA multi-turn actuators for modulating duty are
marked with the type designations SAR, SARExC, and SAREx.
Available sizes:
■ SAR 07.1 – SAR 30.1
■ SARExC 07.1 – SARExC 16.1
■ SAREx 25.1 – SAREx 30.1
As standard, the actuators conform to the types of duty
S4 - 25 % or S4 - 50 % as an option.
6 |
Modular design/versions
Modular design – with or without controlsEach application has its special requirements. For this rea-
son, AUMA only builds actuators on demand – tailor-made to
customer requirements. Due to the modular design of the
AUMA product range, different features can be combined.
For each actuator type, there is a large number of equipment
variants.
One of the fundamental benefits of AUMA’s modular
design is the ability to add integral controls to the basic
actuator.
Actuators without integral controls
If your plant design requires the control of the actuators
from a central point, e.g. from a PLC, AUMA supplies actua-
tors without controls, the so-called AUMA NORM version.
NORM actuators supply unprocessed signals; the external
controls have to process all signals to and from the actuators
according to the operation.
NORM actuators have no switchgear for switching the
actuator motor on or off. This switchgear, e.g. reversing
contactors, has to be included within the external controls to
ensure, for example, that the actuator motor is automatically
switched off if the actuator signals that an end position has
been reached.
AUMA NORM actuators have no operating elements to
operate the actuator electrically in the local mode. If this is
required, separate local controls have to be installed and inte-
grated into the control system.
Actuators with integral controls
After establishing the power supply, the actuators are
ready for operation immediately. The actuator signals are pro-
cessed locally. The required switching procedures are immedi-
ately performed within the integral controls, using the inte-
gral reversing contactors or thyristors.
After connecting the power supply, the actuator can be
operated immediately in the local mode, using the local con-
trols.
Extensive installation work for external controls is no lon-
ger required.
The automatic phase correction ensures the correct direc-
tion of rotation even if the phases are crossed over during
electrical installation.
The high functionality of the controls relieves the DCS, so
data exchange is reduced to a minimum.
Integral controls are a prerequisite when connecting actua-
tors to a fieldbus.
NORM actuators can also be retrofitted or supplemented
at a later date.
For further information on the integral controls refer to
page 21 and the separate brochures:
■ Product description
Actuator controls AUMA MATIC
■ Product description
Actuator controls AUMATIC
Due to the modular design principle, the multi-turn actuator may be sup-plied without controls or with AUMA MATIC or AUMATIC integralcontrols.
| 7
[1] Multi-turn actuatorsSA 07.1 – SA 16.1/SAR 07.1 – SAR 16.1without integral controls(AUMA NORM)■ Torques from 10 to 1,000 Nm
[2] Multi-turn actuatorsSA 25.1 – SA 48.1 /SAR 25.1 – SAR 30.1without integral controls(AUMA NORM)■ Torques from 630 to 32,000 Nm
[3] [4]
[5]
[1] [2]
[3] Multi-turn actuatorswith AUMA MATIC integral controls
The AUMA MATIC is ideal for simple OPEN -CLOSE applications (open-close duty) and forconventional control. If equipped accordingly, itmay also be used for closed-loop control.Further information on page 21.
[4] Multi-turn actuatorwith AUMATIC integral controls
The AUMATIC is the all-rounder amongAUMA controls. It is equipped with a microcontroller and has a lot more functions thanthe AUMA MATIC. The AUMATIC is ideal forclosed-loop control applications. And it is alsothe AUMATIC that is used for the implementa-tion of the latest fieldbus system developments.Further information on page 21.
[5] Multi-turn actuatorwith the controls on a wall bracket
The controls can also be mounted sepa-rately from the actuator on a wall bracket. Thisis recommended if:■ limited space restricts the access to directly
mounted controls■ high ambient temperatures in the surround-
ings of the actuator could affect the elec-tronics,
■ heavy valve vibration could influence thecontrols.
8 |
Design principle
[1]
[2]
[4]
[5]
[7b]
[1]
[2]
[3]
[4]
[5]
[6]
[7]MotorMost actuators are equipped with robust
3-phase asynchronous motors. 1-phase AC orDC motors are also available up to actuator size16.1.The motor is connected via an internalplug/socket connector (up to 16 A nominal cur-rent). This enables quick exchange of the mo-tor, e.g. for change of output speed.Further information on page 12.
Control unitThe control unit includes two measuring sys-
tems (limit switching and torque switching)which measure the travel or the torque presentat the output drive. Further information onpage 14.
GearingThe well proven principle of worm gearing,
sometimes combined with a planetary gear, isused to reduce the motor speed to the requiredactuator output speed. The sliding worm is po-sitioned between two stacks of springs on theworm shaft. The worm will be moved in rela-tion to the torque. This axial displacement, asmeasure for the torque, is transmitted to thecontrol unit via lever and gear wheels.
Valve attachmentThe mounting flange is according to
EN ISO 5210 or DIN 3210.Various output drive types are available. There-fore it is possible to adapt to different types ofvalves. For further information refer to page 24.
Handwheel with change-overmechanism
For commissioning or in an emergency themulti-turn actuator can be operated with thehandwheel. By operating the red change-overlever the motor drive is disconnected and themanual drive engaged. Decoupling is possiblewith little force, even if the actuator is operatedat full rated torque.When starting the motor the manual drive isautomatically disengaged. During electric opera-tion the handwheel does not rotate.
Electrical connectionThe electrical connection is made via a
plug/socket connector, no matter whether theactuator is equipped with or without controls.For maintenance work, the actuator can be dis-connected quickly from the power supply andcontrol cables and can easily be reconnected.
Further information on page 22.
Integral controls (option)AUMA actuators with AUMA MATIC [7a] or
AUMATIC [7b] integral controls are ready foroperation as soon as the supply voltage hasbeen connected. The actuator can easily be op-erated on site via the local controls.Via the installed switchgear, i.e. reversingcontactors or thyristors, the integral controlsautomatically and immediately perform the re-quired motor switching procedures.The electrical connection between integral con-trols and actuator is made by using aplug/socket connector.Further information on page 21.
[6]
[6]
[6]
[7a]
[3]
For multi-turn actuators from size 25.1, themotor cables are connected via terminals.
| 9
Summary of applications, functions, and equipment
Standard ●
Option ■
SA07.1 – 48.1
SAR07.1 – 30.1
SAEx(C)07.1 – 40.1
SAREx(C)07.1 – 30.1 Page
Applications/duty typeOpen-close duty ● – ● – 4Positioning duty ● – ● – 4Modulating duty – ● – ● 5Service conditionsEnclosure protection IP 67 ● ● ● ● 10Enclosure protection IP 68 ■ ■ ■ ■ 10High temperature version ■ – – – 10Low temperature version ■ ■ ■ ■ 10Corrosion protection KN ● ● ● ● 11Corrosion protection KS, KX ■ ■ ■ ■ 11Explosion protection – – ■ ■ 11FunctionsMotor operation ● ● ● ● 12Manual operation ● ● ● ● 8, 13Limit seating ● ● ● ● 13Torque seating ● ● ● ● 13Overload protection of the valve ● ● ● ● 15Protection against unauthorised operation ■ ■ ■ ■ 15Protection of the motor against overheating ● ● ● ● 16Protection against accidental changing of the valve position ● 1 ● 1 ● 1 ● 1 16Feedback signals2/indicationValve end positions ● ● ● ● 19Valve position ■ ■ ■ ■ 19, 20Intermediate positions ■ ■ ■ ■ 19Actuator/valve is running ■ ■ ■ ■ 19, 20Fault (excessive temperature) ● ● ● ● 19Fault (torque fault) ● ● ● ● 19Integral controls3
AUMA MATIC ■ ■ ■ ■ 21AUMATIC ■ ■ ■ ■ 21Electrical connection for non-explosion-proof devicesElectrical connection with plug/socket ● ● – – 22Expanded connection compartments ■ ■ – – 22Double sealed ■ ■ – – 22Protection cover ■ ■ – – 22Parking frame ■ ■ – – 22Electrical connection for explosion-proof devicesPlug/socket connector for explosion-proof actuators – – ● ● 23Plug-in terminal connection for explosion-proof actuators – – ■ ■ 23Double sealed – – ● ● 23Protection cover – – ■ ■ 23Parking frame – – ■ ■ 23Valve attachment according to EN ISO 5210/DIN 3210Output drive types B, B1 ● ● ● ● 24A, B2, B3, B3D, B4, C, D, DD, E ■ ■ ■ ■ 24Special output drives ■ ■ ■ ■ 24
1 For high output speeds, refer to separate technical data sheet2 For actuators without integral controls, the actuator signals have to be processed accordingly in the higher level control system.3 up to size 16.1
10 |
Service conditions
Enclosure protectionIP 67
AUMA actuators conform to enclosure protection IP 67
according to EN 60 529. IP 67 means protection against
immersion up to max. 1 m head of water for max.
30 minutes.
IP 68AUMA actuators are available with improved enclosure
protection IP 68 according to EN 60 529. IP 68 means pro-
tection against submersion up to 6 m head of water for max.
72 hours. During submersion up to 10 operations are
permissible.
In order to guarantee the enclosure protection IP 68, suit-
able cable glands must be used. They are not part of the
standard supply, but can be provided by AUMA on request.
AUMA devices are used worldwide; in all climate zones, in
industrial plants of all kinds under special local ambient con-
ditions. AUMA devices have to operate reliably and for a long
time under any conditions without requiring major mainte-
nance work. For this very reason, AUMA has focussed on
making AUMA devices resistant to the most unfavourable
conditions and have adapted their protective measures to the
state-of-the-art technology.
AUMA actuators at work – in Siberia and in the Sahara
Ambient temperatures
Types Actuator types Versions Temperature range
SA Multi-turn actuatorsfor open-close duty
StandardLow temperature
Extreme low temperature1
High temperature
– 25 °C … + 80 °C– 40 °C … + 60 °C– 60 °C … + 60 °C0 °C ...+ 120 °C2
SAR Multi-turn actuatorsfor modulating duty
StandardLow temperature
Extreme low temperature1
– 25 °C … + 60 °C– 40 °C … + 60 °C– 60 °C … + 60 °C
SAExC Explosion-proof multi-turn actuators foropen-close duty
StandardLow temperature
Extreme low temperature1
High temperature
– 20 °C … + 40 °C/60 °C3/80 °C4
– 40 °C … + 40 °C/60 °C3
– 50 °C … + 40 °C/60 °C3
– 20 °C … + 80 °C4
SAExSARExCSAREx
Explosion-proof multi-turn actuators foropen-close and modulating duty
StandardLow temperature
Extreme low temperature1
– 20 °C … + 40 °C/60 °C3
– 40 °C … + 40 °C/60 °C3
– 50 °C … + 40 °C/60 °C3
If an actuator is equipped with directly mounted AUMA MATIC or AUMATIC integral controls, the maximum permissible
ambient temperature is to + 70 °C, unless the actuator requires a lower temperature limit.
1 Device contains heating system for connection to external power supply 230 V AC or 115 V AC.2 Valid for AUMA NORM version without electronic position transmitter RWG, with RWG max. + 80 °C3 For the temperature range + 60 °C, special sizing is required for temperature class T4.4 + 80 °C possible in combination with explosion group IIB and temperature class T3
| 11
Explosion protectionFor the installation of actuators in potentially hazardous or
explosive areas, special protective measures are required.
These are stipulated in the European Standards EN 50 014,
50 018, and 50 019. The PTB (Physikalisch Technische
Bundesanstalt, the German national test authority) and the
BVS (German Mining Test Facility) as European test authorities
have certified the conformity of the equipment with the
mentioned standards.
Explosion protection classification of the multi-turn
actuators
Types Classifications
SAExC 07.1 – SAExC 16.1SARExC 07.1 – SARExC 16.1with and without integral controls
■ II2G EEx de IIC T4■ II2G c IIC T4■ II2D Ex tD A21 IP6X T130°C
SAExC 07.1 – SAExC 10.1SARExC 07.1 – SARExC 10.1without integral controls
■ I M2 Ex de I
SAEx 25.1 – SAEx 40.1SAREx 25.1 – SAREx 30.1
■ II2G EEx ed IIB T41
■ II2G c IIB T4■ II2D Ex tD A21 IP6X T130°C
1 With electronic position transmitter RWG 5020 Ex, the explosion pro-tection classification corresponds to II2G EEx ed [ib] IIB T4(intrinsically safe)
Certificates of Conformity from national test authorities in
other countries, e.g. USA, Canada, CIS, Brazil, Japan, etc., are
also available.
Corrosion protection/colourStandard (KN)
The standard AUMA corrosion protection KN is a high
quality coating. This is suitable for outdoor installation and
for slightly aggressive atmospheres with a low level of
pollution.
KS
AUMA recommends this corrosion protection class for
installation in occasionally or permanently aggressive atmo-
spheres with a moderate pollutant concentration.
KX
AUMA recommends this corrosion protection class for
installation in aggressive atmosphere with high humidity and
a high pollutant concentration.
Colour
The standard colour of the finish coating is silver-grey (sim-
ilar to RAL 3037). Other colours are available on request.
12 |
Functions
The function of an actuator is to electrically set a defined
valve position, triggered by an operation command, e.g. from
a process control system.
This seemingly simple task has to be performed under the
most diverse conditions, depending on the application. This
includes different switch-off criteria and safety concepts. The
connection to the control system also requires special actua-
tor configuration to provide the optimum solution for this
task.
Furthermore, different protective equipment is required
protecting both actuator and valve against damage or even
destruction.
The functions described in the following can be used to
find a solution to more than 90 % of the possible tasks.
In all AUMA subsidiaries, engineers will help you in finding
the suitable actuator, especially for applications with special
requirements.
Motor operationDuring normal operation, the actuator is operated via the
actuator controls which receive operation commands from
the control room. If the actuator is also to be operated
locally, additional local controls are required. If the actuator is
equipped with optional integral AUMA controls, the local
controls and the motor controls are always included.
To meet the special valve automation requirements, AUMA
uses specially designed electric motors which have both a
compact design and a favourable torque curve. Starting from
standstill, they provide a high torque to unseat sticky valves
from their end position.
Torque T depending on the output speed n
[1] AUMA 3-ph AC motor[2] Standard motor with identical power and larger size
Actuators are generally supplied with 3-phase AC motors.
These asynchronous motors have a simple design and are
robust during operation.
The actuators can also be supplied with 1-phase AC or DC
motors.
T
n
[1]
[2]
| 13
Manual operationElectric actuators are always equipped with a handwheel.
During commissioning, the actuator is operated manually by
the handwheel for the purpose of setting the end
positions.
If the power supply fails, the valve can be operated via the
handwheel. The manual drive is engaged via a change-over
mechanism, the connection to the motor is disconnected at
the same time. The handwheel does not rotate during motor
operation.
If the electric motor is switched on, the manual drive is
automatically disconnected, and the transmission of torque
between motor and gearing is restored.
Switching off in the end positionsDepending on the design of the valve and/or the applica-
tion, the actuator is switched off in the end positions accord-
ing to one of the following procedures stipulated by the valve
manufacturer:
■ Limit seating, i.e. at one of the set switching positions
■ Torque seating. This type of seating is used if the valve has
to be moved to end position CLOSED at a defined torque.
AUMA actuators contain two independent measuring sys-
tems, limit switching and torque switching
(see page 14).
The type of seating has to be considered in the actuator
controls.
Limit seating
Output speed n depending on the travel
The actuator runs at nominal output speed up to tripping
point P. When setting P, you have to account for the overrun
of the actuator. The overrun is generated by the inertia of
both the actuator and the valve and the delay time of the
controls.
Torque seating
Torque T depending on the travel
[1] Set tripping torque
When reaching end position CLOSED the torque increases
within the valve seat until the actuator is switched off after
reaching the set value.
[1]T
P
n
14 |
Functions
Control unit with limit and torque switchingControls can switch off the actuator via limit and torque
seating in the end positions or in case of overload. The con-
trol unit (refer to illustration on page 8) includes two inde-
pendent measuring systems which measure the travel or the
torque present at the output drive.
Control unit with magnetic limit and torque
transmitter (option)
Position and the available torque are continuously
recorded via Hall sensors. The valve position and the torque
present within the valve are available as continuous signals.
The magnetic limit and torque transmitter is designed to
measure immediately the precise valve position once the
power supply has been restored after a power failure. A ref-
erence operation is not required. The system does not require
auxiliary energy, e.g. battery.
If the control unit is used with an MWG, the actuator has
to be equipped with the integral AUMATIC actuator controls.
A significant advantage of this combination is that all actua-
tor parameters can be set without opening the housing or
the use of any tools.
Control unit with micro switches
Travel and incoming torque are recorded via a counter
gear mechanism and a lever system within the control unit.
When the set switching points are reached, the correspond-
ing micro switches are operated via cams.
The control unit contains:
■ one torque switch each for the directions OPEN and
CLOSE,
■ one limit switch each for the end positions OPEN and
CLOSED.
The switch signals trip the actuator according to the type
of seating required.
Limit and torque switches are available in several versions:
■ Single switch
one NC and one NO contact, not galvanically isolated.
■ Tandem switch (option)
for switching two different potentials.
A tandem switch provides the electrical connection with
the signal for switching off the actuator and another gal-
vanically isolated signal.
■ Triple switches (option)
For applications where three different potentials are to be
switched. The switch consists of one single and one tan-
dem switch.
■ Intermediate position switch (option)
The so-called DUO limit switching contains an additional
switch for setting intermediate switching points outside
the end positions for each direction.
In the basic version the switch contacts are made of silver.
For voltages between 5 V and 50 V and extremely low cur-
rents, switches with gold plated contacts are recommended.
| 15
Overload protection of the valveThe torque switching acts as overload protection for the
whole travel. Thereby the valve is protected against damage
or destruction due to excessive torques.
If excessive torque builds up at the valve’s closing element
in an intermediate position, e.g. due to a trapped object, the
torque switches will trip as soon as the set tripping torque
is exceeded.
Correct processing of the torque signal is the prerequisite
for fully functional overload protection. This is automatically
ensured for actuators with AUMA integral controls.
Torque T depending on the travel
[1]T
Protection against unauthorised operation(option)
The position of freely accessible valves may not be
changed by unauthorised personnel.
This can be prevented by securing the actuator handwheel
by means of a locking device.
16 |
Functions
Protection of the motor against overheatingThe windings of the 3-phase AC and 1-phase AC motors
contain thermoswitches or PTC thermistors which trip as
soon as the temperature within the motor exceeds 140 °C.
Should this be the case, the controls have to switch off the
actuator.
[1] Tripping point[2] Switch-on point
Thermoswitches or PTC thermistors offer far better protec-
tion than thermal overload relays, since the temperature rise
is directly measured at the motor windings.
140 °C
90 °C
115 °C
T
t
[1]
[2]
Actuator type ThermoswitchPTCthermistor2
SA 07.1 – SA 48.1 Standard OptionSAR 07.1 – SAR 30.1 Standard OptionSAExC 07.1 – SAExC 16.1 Option1 StandardSARExC 07.1 – SARExC 16.1 – StandardSAEx 25.1 – SAEx 40.1 Option1 StandardSAREx 25.1 – SAREx 30.1 – Standard
1 According to EN 60079-14, a thermal overload relay (e.g. motor pro-tection switch) must be installed for these actuators in addition to thethermoswitches.
2 For AUMA NORM actuators, a suitable PTC tripping device has to beincluded in the external controls. If the actuator is equipped with inte-gral controls, the PTC tripping device is already included.
Protection against accidental changing of thevalve position
Gravity, vibration or forces acting upon the medium within
a pipeline may lead to accidental changes in the valve posi-
tion. This has to be prevented.
Self-locking
Due to their design, actuators counteract torques acting
upon the output side with a load. If the load prevents the
valve position from being changed from standstill, this is
called self-locking.
Most AUMA actuators are self-locking as standard. For
actuators with high output speeds and certain actuator/gear-
box combinations, self-locking can be achieved by mounting
an anti-backdrive device.
Self-braking
If the valve is effectively brought to a standstill after opera-
tion, this is called self-braking. The braking torque of the
actuator has to correspond to at least the maximum output
torque.
This requirement can also be met by using an
anti-backdrive device or a brake motor.
| 17
Anti-backdrive deviceBy using an LMS 07.1 – LMS 16.1 anti-backdrive device
both self-locking and self-braking can be achieved. The
retaining or braking torque corresponds to at least the maxi-
mum settable tripping torque of the actuator.
With anti-backdrive devices, the use of expensive brake
motors is no longer required for many applications. The
anti-backdrive device is less expensive, much simpler and
safer to use.
[1]
[3] [4]
[2]
[1] The anti-backdrive device is directly mounted to the output drive ofthe actuator.
[2] The actuator with anti-backdrive device can either be directlymounted to the valve or a valve gearbox, in our example a GK multi-turngearbox [3] and a GS part-turn gearbox [4]. In this case, particularly highretaining or braking torques are available, since only the comparativelylow torques at the gearbox input act upon the anti-backdrive device.The only exception are small-size gearboxes where the anti-backdrive de-vice is installed at the gearbox output.
18 |
Signals/indication
Signals are the foundation for controlling a process flow.
For this reason, actuators provide a number of signals which
indicate the operational status of the actuator and of the
valve.
Many applications require that the actuator or the valve
status can be provided locally. Depending on the equipment,
the actuator offers various possibilities.
Feedback signalsThe actuator signals are sent and evaluated by the actua-
tor controls. For an AUMA NORM actuator, the signals are
processed via external actuator controls, e.g. a PLC. For
AUMA MATIC or AUMATIC actuators, the actuator signals are
processed directly and locally; the higher level controls are
provided with evaluated signals.
Actuator signals
AUMA actuator fully equipped[1] Actuator controls, e.g. PLC[2] Feedback signals to the DCS[TSC] Torque switch signal in direction CLOSE[LSC] Limit switch signal in end position CLOSED[TSO] Torque switch signal in direction OPEN[LSO] Limit switch signal in end position OPEN[LSA] Intermediate position switch signal
in direction CLOSE (option)[LSB] Intermediate position switch signal in direction OPEN (option)[BL] Blinker transmitter signal, option for actuators
for modulating duty[RWG] Electronic position transmitter 0/4 – 20 mA (option)[Th] Thermoswitch
TSC
LSA
Th
LSC
LSB
TSO
BL
LSO
RWG
[1][2]
| 19
Feedback signals
Feedback Actuators without integral controls (AUMA NORM)
When using tandem switches instead of the common single switches, the signals can be fed back twiceas galvanically isolated signals.
Valve end positions Limit and torque switch signals have to be evaluated within the external controls. When processing the signals ithas to be considered whether the actuator is limit or torque seated in the end positions.
For limit seating, the end position signal is generated by evaluating the limit switch signals.
For torque seating, the end position feedback signal is generated by combining limit and torque switch signals.
Valve position An optional position transmitter provides the external controls with the valve position either as a voltage signalor as a 0/4 – 20 mA current signal.
Intermediate positions, e.g. forstarting up a pump whenreaching a particular valveposition
As an option, the actuator contains two additional intermediate position switches, one for each direction(DUO limit switching)
Actuator/valve is operated Can be provided by a blinker switch which is included in the basic version of open-close actuators and optionallyavailable for modulating actuators.
Fault (excessive temperature) The higher level controls have to monitor the thermoswitches installed in the actuator motor. Tripping of thethermoswitches has to switch off the actuator immediately to prevent it from being damaged. Consequently, theexternal controls have to generate a fault signal to be able to detect and eliminate a fault.
Fault (torque fault) Tripping of a torque switch in mid-travel has to lead to immediate switching off of the actuator. Torque switchtripping in one of the end positions can also be part of normal operation. This is identified by the limit switchtripping at the same time. In all other cases, the tripping of the torque switch is to be interpreted as a fault. Tobe able to identify and eliminate a fault, the external controls have to provide a fault signal.
Feedback signals for actuators with integral controls
Integral controls have the following advantages:
■ For actuators with integral controls, the above mentioned
feedback signals are directly made available. This reduces
the number of signals to be led to the higher level
controls.
■ By means of enhanced diagnostic functions, the AUMATIC
provides a number of other feedback signals which can be
used if required.
■ The controls have binary and analogue outputs or alterna-
tively a fieldbus interface which can be used to transmit
the signals to the DCS.
Further information on these actuator types is available in
the brochures:
■ Product description
Actuator controls AUMA MATIC
■ Product description
Actuator controls AUMATIC
20 |
Signals/indication
Local indicationActuators without integral controls
(AUMA NORM)
On request, the actuator is equipped with a mechanical
position indicator which can be used to view the valve posi-
tion and also as running indication. The mechanical position
indicator is clear and fully legible, even from a long distance.
For AUMA NORM actuators, the actuator signals are exclu-
sively processed by the external actuator controls. If signals
generated within these controls are required as local indica-
tion, additional display elements and signal channels become
necessary.
Actuators with integral controls
Actuators with integral controls can also be equipped with
the mechanical position indicator. Furthermore, the controls
are complete with indication lights, or, in the case of the
AUMATIC, a display, which indicate the operation status
locally.
For more detailed information on local indication, refer to
the following brochures:
■ Product description
Actuator controls AUMA MATIC
■ Product description
Actuator controls AUMATIC
| 21
Integral controls
AUMA MATIC AMIn its basic version, the AUMA MATIC is ideal for simple
OPEN - CLOSE applications.
The AUMA MATIC provides end position indication, the
selector switch position and a collective fault signal, all as
feedback signals.
The behaviour of the AUMA MATIC can be adapted to the
application via programming switches, e.g. programming of
the type of seating.
Options:
■ Three-position controller
■ Fieldbus interface (Profibus DP or Modbus RTU)
AUMA MATIC local controls with push buttons, selector switches and in-dication lights
Further literature
Detailed information can be found in the brochure ‘Prod-
uct description, Actuator controls AUMA MATIC’
AUMATIC ACAs well as the AUMA MATIC’s basic functionality, the
AUMATIC offers some other advantages, e.g.
■ Programmable signal relays
■ Non-intrusive setting (option)
■ Adaptive positioner (option)
■ Fieldbus interfaces for Profibus DP, Modbus RTU,
DeviceNet, Foundation Fieldbus (option)
■ Monitoring and diagnostics
■ Logging of operating data
■ Cable-based or wireless programming interface for con-
necting a programming device
AUMATIC local controls with push buttons for operation and program-ming, selector switch, display with plain text display, indication lights andprogramming interface.
Further literature
Detailed information can be found in the brochure ‘Prod-
uct description, Actuator controls AUMATIC
The integral controls evaluate the actuator signals and
operation commands and perform the required switching
procedures automatically and without delay, using the
installed switchgear, reversing contactors or thyristors. The
controls make the evaluated actuator signals available to the
higher level controls as feedback signals.
Actuators with integral controls are ready for operation
immediately after establishing the power supply and can be
operated via the operating elements.
22 |
Electrical connection for non-explosion-proof actuators
[1]
AUMA non-explosion-proof actuators use a “plug-in” type
electrical connection. This applies to both power supply and
signal cables . The wiring made during installation remains
undisturbed, even if the actuator has to be disconnected
from the mains or the DCS, e.g. for maintenance purposes.
The actuator can be quickly reconnected, wiring errors are
avoided.
The electrical connection is available in different sizes. The
number of cable entries may vary. The cable entries usually
have metric threads, Pg- or NPT-threads are also available.
The electrical connections can be used for actuators with
or without controls.
[2] [3]
[4]
[5]
All electric connections are based on theAUMA plug/socket connector with 50screw-type terminals for connecting the signalcables and three screw-type connections forconnecting the supply voltage.
[1] Standard S
with three cable entries. The diameter is100 mm.
[2] Enlarged terminal compartment SH (op-tion)
with up to six cable entries
[3] Enlarged terminal compartment SE (op-tion)
with three cable entries. The diameter is135 mm. An intermediate frame is required foradapting to the actuator housing.
[4] Double sealed intermediate frame(option)
When removing the plug cover or due toleaky cable glands, ingress of dust and waterinto the housing is possible. This is preventedby inserting the double sealed intermediateframe between the electrical connection andactuator housing. The enclosure protection, IP67 or IP 68, will not be affected, even if theelectrical connection is removed. The doublesealed intermediate frame can be combinedwith any of the illustrated electricalconnections.
[5] Fieldbus connection SD
If the actuator is equipped with actuatorcontrols with a fieldbus interface, a special elec-trical connection is required. The connection ofthe power supply does not differ from theother electrical connections, a connectionboard for connecting the fieldbus cables isintegrated into the plug.
[6] Protection cover
for protecting the plug compartment whenplug is removed.
[7] Parking frame
for safe mounting of a disconnected plug.
11 For sizes SA 25.1 and larger the motor is connected to screw type
terminals in the actuator terminal compartment. The controls are stillwired to the AUMA plug/socket connector.
[6]
[7]
| 23
Electrical connection for explosion-proof actuators
AUMA explosion-proof actuators use a “plug-in” type elec-
trical connection. This applies to both power supply and sig-
nal cables. The wiring made during installation remains undis-
turbed, even if the actuator has to be disconnected from the
mains or the DCS, e.g. for maintenance purposes. The actua-
tor can be quickly reconnected and wiring errors are avoided.
Explosion-proof connections are always double sealed: The
flameproof enclosure inside the actuator remains intact even
after removing the plug cover.
The electrical connection is either designed in the protec-
tion type “Increased safety” or “Flameproof
enclosure”.
The electrical connections can be used for actuators with
or without controls.
1
1 For the explosion-proof multi-turn actuators SAEx 25.1 û SAEx 40.1 theterminal connection cannot be plugged in.
[1] Plug/socket connector with screw-typeterminals KP
with 38 screw-type connections for the sig-nal cables. This connection type is the standardconnection for explosion-proof actuators, evenfor those with a fieldbus interface. The connec-tion can be supplied with a standard plug cover(s) with three cable entries or with a high (h)plug cover with up to six cable entries.The connection with the high (h) cover is alsoused for devices with integral controls andfieldbus interface.
[2] Plug/socket connector with spring cageterminal blocks KES
with up to 50 spring-cage terminal blocksfor connecting signal cables. Used with operat-ing voltages exceeding 525 V and/or if a largenumber of terminals are required. The electricalconnection has up to 6 cable entries.The connection is available in protection type“Increased safety” [2a] or “Flameproofenclosure’”[2b].
[3] Plug/socket connector with FO couplerKES
This connection type is used for actuatorswith AUMATIC integral controls with a fieldbusinterface and signal transmission via fibre op-tics. The design basically corresponds to theplug/socket connector with spring cage termi-nals with the addition of an FO coupler.
[4] Protection cover
for protecting the plug compartment whenthe plug is removed.
[5] Parking frame
for safe mounting of a disconnected plug.The parking frame with mounted plug is pro-tected against the ingress of both dust and wa-ter.
[1]
[3]
[4]
[5]
[s] [h]
[2a] [2b]
24 |
Valve attachment
The actuator is mounted to the valve using a mounting
flange standardised according to EN ISO 5210 or DIN 3210.
The output drive types are also manufactured according to
these standards. They establish the mechanical connection
between the output drive of the actuator and the valve stem
or the valve shaft. The torque is transmitted from the actua-
tor to the valve using this connection. There are various out-
put drive types for available different valve types. The most
common output drive types are illustrated below.
[1] Output drive types B1, B2(EN ISO 5210), or B (DIN 3210)
The output drive is integrated into the hol-low shaft of the actuator. The torque is trans-mitted via a parallel key. Low radial loads canbe accepted.
[2] Output drive types B3 or B4 (EN ISO5210), or E (3210)
The torque is transmitted via a parallel key.By using a plug sleeve, output drive type B1can easily be converted to output drive typesB3 or B4.
[3] Output drive type A(EN ISO 5210/DIN 3210)
Stem nut for rising and non-rotating valvestems. The mounting flange together with thestem nut and thrust bearings form an assembly,which is suitable for accepting thrust. The unitis screwed to the actuator. Output drive type Acannot accept any radial loads.
[4] Output drive type AF(EN ISO 5210/DIN 3210)
Spring-loaded stem nut for rising andnon-rotating valve stems. The springs compen-sate for dynamic thrust at high speeds or evenfor thermal expansion of the valve stem. Thisunit is screwed to the actuator which containsa hollow shaft with internal teeth.
[5] Special output drive types(without illustration)
Further output drive types are available be-sides those described:■ Pendulum stem nut AK■ Stem nut with plain bearings AG■ Hexagon in hollow shaft■ Insulated output drives IB1 and IB3
For detailed information on special outputdrive types refer to the separate data sheetsand price lists.
[1] [2]
[3]
[4]
| 25
Combinations with valve gearboxes
The different valve gearboxes are an essential part of the
modular AUMA product range. They can be combined with
virtually any AUMA multi-turn actuator.
Detailed information on gearboxes can be found in sepa-
rate brochures and on separate technical data sheets.
[1] Multi-turn actuator with spur gearboxGST 10.1 – GST 40.1■ Torques up to 16,000 NmThe GST meets the following criteria:■ Expansion of the torque range of an actuator
size. The combination of a small actuatorwith gearbox is often more cost-effectivethan a large actuator.
■ Adaptations to special mounting conditions
[2] Multi-turn actuator with bevel gearboxGK 10.2 – GK 40.2■ Torques up to 16,000 Nm
The GK basically has the same functionalityas the GST. Furthermore, so-called double-stemsolutions can be provided by using two GKgearboxes and an SA actuator.
[3] Multi-turn actuator with worm gearboxGS 50 – GS 500■ Torques up to 360,000 Nm
The GS worm gearboxes convert themulti-turn movement at the output shaft of themulti-turn actuator into a part-turn movement,generally 90°. The combination of a multi-turnactuator and worm gearbox forms a part-turnactuator. Solutions are therefore available forlarge part-turn valves with high torquerequirements.
[4] Multi-turn actuator with lever gearboxGF 50.3 – GF 250.3■ Torques up to 32,000 Nm
These combinations can be used to auto-mate valves which are operated via a lever ar-rangement.
[5] Multi-turn actuator with linear thrustunit LE 12.1 – LE 200.1■ Thrusts up to 217 kN■ Strokes up to 500 mm
The linear thrust unit converts the rotarymovement of the actuator output shaft into alinear movement. The combination of amulti-turn actuator and linear thrust unit formsa linear actuator.
[1] [2] [3]
[4] [5]
Multi-turn actuators for open-close dutyThe following data is valid for actuators with 3-phase AC motors with an S2 - 15 min duty type. For detailed information,
restrictions for actuators with high output speeds as well as data on other motor types and types of duty refer to separate
technical data sheets.
TypeOutput speeds at 50Hz1
Setting range for trippingtorque Valve mounting flange
[rpm] [Nm] Standard (EN ISO 5210) Option (DIN 3210)SA/SAExC 07.1 4 – 180 10 – 30 F07 or F10 G0SA/SAExC 07.5 4 – 180 20 – 60 F07 or F10 G0SA/SAExC 10.1 4 – 180 40 – 120 F10 G0SA/SAExC 14.1 4 – 180 100 – 250 F14 G½SA/SAExC 14.5 4 – 180 200 – 500 F14 G½SA/SAExC 16.1 4 – 180 400 – 1,000 F16 G3SA/SAEx 25.1 4 – 90 630 – 2,000 F25 G4SA/SAEx 30.1 4 – 90 1,250 – 4,000 F30 G5SA/SAEx 35.1 4 – 45 2,500 – 8,000 F35 G6SA/SAEx 40.1 4 – 32 5,000 – 16,000 F40 G7SA 48.1 4 – 16 10,000 – 32,000 F48 –
1 Fixed output speeds, where each output speed is 1.4 times higher than the previous
26 |
Technical data
Multi-turn actuators for modulating dutyThe following data is valid for actuators with 3-phase AC motors with an S4 - 25 % duty type. For detailed information and
data on other motor types and types of duty refer to separate technical data sheets.
TypeOutput speedsat 50 Hz1
Setting range fortripping torques
Permissible average torque formodulating duty Valve mounting flange
[rpm] [Nm] [Nm]Standard(EN ISO 5210)
Option(DIN 3210)
SAR/SARExC 07.1 4 – 45 15 – 30 15 F07 or F10 G0SAR/SARExC 07.5 4 – 45 30 – 60 30 F07 or F10 G0SAR/SARExC 10.1 4 – 45 60 – 120 60 F10 G0SAR/SARExC 14.1 4 – 45 120 – 250 120 F14 G½SAR/SARExC 14.5 4 – 45 250 – 500 200 F14 G½SAR/SARExC 16.1 4 – 45 500 – 1,000 400 F16 G3SAR/SAREx 25.1 4 – 11 1,000 – 2,000 800 F25 G4SAR/SAREx 30.1 4 – 11 2,000 – 4,000 1,600 F30 G5
1 Fixed output speeds, where each output speed is 1.4 times higher than the previous
| 27
Lifetime of multi-turn actuatorsfor open-close duty
An operation cycle is based on an operation from CLOSED
to OPEN and back to CLOSED, with a travel of 30 turns per
stroke.
Type Operation cycles
SA/SAExC 07.1 – 10.1 20,000SA/SAExC 14.1 – 16.1 15,000SA/SAEx 25.1 – 30.1 10,000SA/SAEx 35.1 – 48.1 5,000
Lifetime of multi-turn actuatorsfor modulating duty
The lifetime depends on the load and the number of
starts. A high starting frequency will rarely improve the mod-
ulating accuracy. To reach the longest possible maintenance
and fault-free operating time, the number of starts per hour
chosen should be as low as possible for the process. This can
be achieved by setting the modulating parameters
accordingly.
TypeModulating stepsin millions
Number ofstarts1
min. max/hSAR 07.1 – 10.1 5 1,200SARExC 07.1 – 10.1 5 900SAR 14.1 – 14.5 3.5 1,2002
SARExC 14.1 – 14.5 3.5 9002
SAR 16.1 3.5 9002
SARExC 16.1 3.5 6002
SAR 25.1 – 30.1 2.5 300SAREx 25.1 – 30.1 2.5 300
1 Based on the permissible average torque in the modulating duty ac-cording to ‘Technical data SAR’
2 Reduced number of starts for high output speeds
Supply voltages/mains frequenciesThe standard supply voltages are listed below. Not all actuator versions or sizes are available with all motor types or volt-
ages/frequencies. For detailed information refer to the separate electric data sheets.
3-phase AC
Voltages Frequency
[V] [Hz]220; 230; 240; 380; 400; 415; 500 50440; 460; 480 60
1-phase AC
Voltages Frequency
[V] [Hz]230 50115 60
DC current
Voltages
[V]24; 48; 60; 110; 220
28 |
Technical data
Motor duty types (according to IEC 34-1)Depending on service conditions, open-close or modulat-
ing duty and running time, the motors are available with dif-
ferent duty types. The motors are not designed for perma-
nent operation S1, but for short-time duty S2 or intermittent
duty S4. Additional cooling of the motors is not required
whilst a high enclosure protection is maintained.
The time information for short-time duty S2 indicates the
maximum permissible running time without interruption; the
motor then has to cool down to ambient temperature. The
percentages given for intermittent duty S4 indicate the per-
centage of the operation time in relation to the pause time.
3-phase AC 1-phase AC DC current
SA 07.1 – 48.1S2 - 15 minS2 - 30 min
S2 - 10 min1 S2 - 15 min
SAR 07.1 – 30.1S4 - 25 %S4 - 50 %
S4 - 25 %2 –
SAEx(C) 07.1 – 40.1S2 - 15 minS2 - 30 min
S2 - 15 min1
S2 - 30 min1 S2 - 15 min3
SAREx(C) 07.1 – 30.1 S4 - 25 % S4 - 25 %2 –1 up to size 14.52 up to size 14.13 for size 07.1
Mounting positionAUMA actuators (with or without integral controls), can be
operated without restriction in any mounting position.
Noise levelThe noise level caused by the multi-turn actuator does not
exceed 72 dB (A).
Vibration resistanceaccording to EN 60068-2-6.
The actuators are resistant to vibrations during start-up or
failure of the plant up to 2 g, for a frequency range of 10 to
200 Hz. However, a fatigue strength may not be derived
from this.
This data is valid for multi-turn actuators without integral
controls with AUMA plug/socket connector or Ex-plug/socket
connector (KP), but not in combination with gearboxes.
| 29
Certificates
EU directivesDeclaration of incorporation in accordance with
Machinery Directive
According to this EU directive, AUMA actuators, actuator
controls and valve gearboxes are not complete machines. This
means that a Declaration of conformity in accordance with
the Machinery Directive cannot be issued by AUMA. AUMA’s
Declaration of Incorporation confirms that during the design
stage of the devices, the standards mentioned in the Machin-
ery Directive were applied. The Declarations of Incorporation
are included in the operation instructions of the devices.
Only by mounting the devices to other components
(valves, pipelines etc.) a ‘machine’ within the meaning of the
directive is formed. Before commissioning this machine a Cer-
tificate of Conformity must be issued.
Certificate of conformity in accordance with Low
Voltage, EMC, and ATEX directive
AUMA actuators fulfil the requirements of these EU direc-
tives, which has been proved in extensive tests. Therefore
AUMA offers a Declaration of Conformity.
The Declarations of Conformity are included in the opera-
tion instructions of the devices.
Final inspection recordAfter assembly, all actuators are thoroughly tested accord-
ing to AUMA’s inspection specification and the torque
switches are calibrated. The procedure is recorded on the
final inspection record.
Compulsory marking with CE mark
AUMA products meet the requirements of the mentioned
EU directives. The name plate is therefore marked with the
CE mark.
CertificatesTo prove the suitability of the devices for special applica-
tions, notified bodies perform type tests on the devices. One
example are the tests to which explosion-proof devices are
subjected. If a device has passed the test, this is recorded in
a certificate. For all explosion-proof devices mentioned in this
brochure, the relevant certificates can be provided.
Where can I get the certificates?All certificates and records are provided by AUMA on
request either as a hard or digital copy.
The documents can be downloaded from the AUMA
website around the clock; some of them are password pro-
tected.
■ www.auma.com
30 |
Quality is not just a matter of trust
Actuators must be reliable and dependable. They deter-
mine the cycle of accurately defined work processes.
But reliability does not begin in production. It begins with
a well thought out design and careful selection of materials.
This continues with conscientious production.
At AUMA, quality management is monitored on a daily
basis. Numerous customer and independent audits, backed
by ISO 9001 and ISO 14001 certification confirm these high
standards.
| 31
The actuator specialist
At AUMA, everything revolves around the electric actuator.
In a world where industrial processes have become increas-
ingly complex, concentration is an asset – while still being
able to see the bigger picture.
AUMA has to cope with a multitude of requirements from
the most different applications and from every corner of the
world - this is our daily business. We rise to this challenge by
pursuing a clear but flexible product policy – supplying the
ideal actuator to every customer.
For this purpose, you have to know your markets. Thinking
globally means acting regionally. A comprehensive worldwide
sales and service network ensures that there is a competent
local contact for every customer.
Since 1964, AUMA has established an excellent brand
name in the world of actuators. Reliability and innovation are
concepts which are closely linked with AUMA. This is above
all to be credited to AUMA’s dedicated employees who work
enthusiastically on the future of the actuator.
32 |
Literature
Further literatureBrochures■ Information
Electric actuators and valve gearboxes according to ATEX
directive 94/9/EC for the use in potentially explosive
atmospheres
■ Information
Electric part-turn actuators SA/GS combinations
■ Product description
Actuator controls AUMA MATIC
■ Product description
Actuator controls AUMATIC
Technical data■ Multi-turn actuators for open-close duty
with 3-phase AC motors
SA 07.1 – SA 48.1
■ Multi-turn actuators for open-close duty
with 1-phase AC motors
SA 07.1 – SA 14.5
■ Multi-turn actuators for open-close duty
with DC motors
SA 07.1 – SA 16.1
■ Multi-turn actuators for open-close duty
with 3-phase AC motors
SAExC 07.1 – SAExC 16.1
■ Multi-turn actuators for open-close duty
with 3-phase AC motors
SAEx 25.1 – SAEx 40.1
■ Multi-turn actuators for modulating duty
with 3-phase AC motors
SAR 07.1 – SAR 30.1
■ Multi-turn actuators for modulating duty
with 1-phase AC motors
SAR 07.1 – SAR 14.1
■ Multi-turn actuators for modulating duty
with 3-phase AC motors
SARExC 07.1 – SARExC 16.1
■ Multi-turn actuators for modulating duty
with 3-phase AC motors
SAREx 25.1 – SAREx 30.1
Furthermore, there are electrical data sheets, dimension
sheets, proposed wiring diagrams and wiring diagrams avail-
able.
The latest issues of all documentation can be downloaded
as PDF files from www.auma.com.
| 33
Index
A
Ambient temperatures 10
AUMA MATIC 7,21
AUMA plug/socket connector 8
AUMATIC 7,21
B
Bevel gearbox 25
C
CE mark 29
Colour 11
Controls 7
Corrosion protection 11
E
Electrical connection 8
EMC directive 29
Enclosure protection IP 10
EU directives 29
Explosion protection 11
F
Functional test 29
I
Integral controls 7
L
Lifetime 27
Limit seating 13
Limit switches 14
Limit switching 13
Linear thrust unit 25
Literature 32
M
Manual operation 8
Modulating duty 5
Motor protection 16
Motors 8,16
Mounting position 28
N
Noise level 28
O
Open-close duty 5
Overload protection 15
P
Painting 11
Parking frame 22 - 23
Plug sleeve 24
Plug/socket connector 8,23
Protection cover 22 - 23
PTC thermistors 16
S
Spur gearbox 25
T
Thermoswitches 16
Torque seating 13
Torque switches 14
Torque switching 13,15
Type of seating 13
V
Valve attachment 8
Vibration resistance 28
W
Wall bracket 7
Worm gearbox 25
34 |
AUMA worldwide
EuropeAUMA Riester GmbH & Co. KGPlant MüllheimDE-79373 MüllheimTel +49 7631 809 - 0riester@auma.comwww.auma.comPlant Ostfildern-NellingenDE-73747 OstfildernTel +49 711 34803 - 0riester@wof.auma.comService Center CologneDE-50858 KölnTel +49 2234 2037 - 9000Service@sck.auma.comService Center MagdeburgDE-39167 NiederndodelebenTel +49 39204 759 - 0Service@scm.auma.comService Center BavariaDE-85386 EchingTel +49 81 65 9017- 0Riester@scb.auma.com
AUMA Armaturenantriebe GmbHAT-2512 TribuswinkelTel +43 2252 82540office@auma.atwww.auma.at
AUMA (Schweiz) AGCH-8965 BerikonTel +41 566 400945RettichP.ch@auma.com
AUMA Servopohony spol. s.r.o.CZ-10200 Praha 10Tel +420 272 700056 / 704125auma-s@auma.czwww.auma.cz
OY AUMATOR ABFI-02230 EspooTel +358 9 5840 22auma@aumator.fiwww.aumator.fi
AUMA France S.A.R.L.FR-95157 Taverny CedexTel +33 1 39327272info@auma.frwww.auma.fr
AUMA ACTUATORS Ltd.GB- Clevedon North Somerset BS21 6QHTel +44 1275 871141mail@auma.co.ukwww.auma.co.uk
AUMA ITALIANA S.r.l. a socio unicoIT-20023 Cerro Maggiore (MI)Tel +39 0331 51351info@auma.itwww.auma.it
AUMA BENELUX B.V.NL-2314 XT LeidenTel +31 71 581 40 40office@benelux.auma.comwww.auma.nl
AUMA Polska Sp. z o.o.PL-41-310 Dabrowa GórniczaTel +48 32 261 56 68R.Ludzien@auma.com.plwww.auma.com.pl
OOO Priwody AUMARU-141400 Moscow regionfor mail: 124365 Moscow a/ya 11Tel +7 495 221 64 28aumarussia@auma.ruwww.auma.ru
ERICHS ARMATUR ABSE-20039 MalmöTel +46 40 311550info@erichsarmatur.sewww.erichsarmatur.se
GRØNBECH & SØNNER A/SDK-2450 København SVTel +45 33 26 63 00GS@g-s.dkwww.g-s.dk
IBEROPLAN S.A.ES-28027 MadridTel +34 91 3717130iberoplan@iberoplan.com
D. G. Bellos & Co. O.E.GR-13671 Acharnai AthensTel +30 210 2409485info@dgbellos.gr
SIGURD SØRUM A. S.NO-1300 SandvikaTel +47 67572600post@sigurd-sorum.no
INDUSTRAPT-2710-297 SintraTel +351 2 1910 95 00jpalhares@tyco-valves.com
MEGA Endüstri Kontrol Sistemieri Tic. Ltd. Sti.TR-06810 AnkaraTel +90 312 217 32 88megaendustri@megaendustri.com.tr
CTS Control Limited Liability CompanyUA-02099 KiyivTel +38 044 566-9971, -8427v_polyakov@cts.com.ua
AfricaAUMA South Africa (Pty) Ltd.ZA-1560 SpringsTel +27 11 3632880aumasa@mweb.co.za
A.T.E.C.EG- CairoTel +20 2 23599680 - 23590861atec@intouch.com
| 35
AmericaAUMA ACTUATORS INC.US-PA 15317 CanonsburgTel +1 724-743-AUMA (2862)mailbox@auma-usa.comwww.auma-usa.com
AUMA Chile Respresentative OfficeCL-9500414 BuinTel +56 2 821 4108aumachile@adsl.tie.cl
LOOP S. A.AR-C1140ABP Buenos AiresTel +54 11 4307 2141contacto@loopsa.com.ar
Asvotec Termoindustrial Ltda.BR-13190-000 Monte Mor/ SP.Tel +55 19 3879 8735atuador.auma@asvotec.com.br
TROY-ONTOR Inc.CA-L4N 5E9 Barrie OntarioTel +1 705 721-8246troy-ontor@troy-ontor.ca
MAN Ferrostaal de Colombia Ltda.CO- Bogotá D.C.Tel +57 1 401 1300dorian.hernandez@manferrostaal.comwww.manferrostaal.com
PROCONTIC Procesos y Control AutomáticoEC- QuitoTel +593 2 292 0431info@procontic.com.ec
IESS de Mexico, S.A. de C.V.MX-C.P. 02900 Mexico D.F.Tel +52 55 55 56 1701informes@iess.com.mx
Corsusa International S.A.C.PE- Miralflores - LimaTel +511444-1200 / 0044 / 2321corsusa@corsusa.comwww.corsusa.com
PASSCO Inc.PR-00936-4153 San JuanTel +18 09 78 77 20 87 85Passco@prtc.net
SuplibarcaVE- Maracaibo Estado, ZuliaTel +58 261 7 555 667suplibarca@intercable.net.ve
AsiaAUMA Actuators (Tianjin) Co., Ltd.CN-300457 TianjinTel +86 22 6625 1310mailbox@auma-china.comwww.auma-china.com
AUMA (INDIA) PRIVATE LIMITEDIN-560 058 BangaloreTel +91 80 2839 4655info@auma.co.inwww.auma.co.in
AUMA JAPAN Co., Ltd.JP-210-0848 Kawasaki-ku,Kawasaki-shi KanagawaTel +81 44 329 1061mailbox@auma.co.jpwww.auma.co.jp
AUMA ACTUATORS (Singapore) Pte Ltd.SG-569551 SingaporeTel +65 6 4818750sales@auma.com.sgwww.auma.com.sg
Al Ayman Industrial. EqptsAE- DubaiTel +971 4 3682720auma@emirates.net.ae
PERFECT CONTROLS Ltd.HK- Tsuen Wan, KowloonTel +852 2493 7726joeip@perfectcontrols.com.hk
DW Controls Co., Ltd.KR-153-803 Seoul KoreaTel +82 2 2113 1100sichoi@actuatorbank.comwww.actuatorbank.com
Al-Arfaj Engineering Co WLLKW-22004 SalmiyahTel +965 481-7448info@arfajengg.comwww.arfajengg.com
Petrogulf W.L.LQA- DohaTel +974 4350 151pgulf@qatar.net.qa
Sunny Valves and Intertrade Corp. Ltd.TH-10120 Yannawa BangkokTel +66 2 2400656sunnyvalves@inet.co.thwww.sunnyvalves.co.th/
Top Advance Enterprises Ltd.TW- Jhonghe City Taipei Hsien (235)Tel +886 2 2225 1718support@auma-taiwan.com.twwww.auma-taiwan.com.tw
AustraliaBARRON GJM Pty. Ltd.AU-NSW 1570 ArtarmonTel +61 294361088info@barron.com.auwww.barron.com.au
2008-05-13
AUMA Riester GmbH & Co. KG
[1] [2] [3]
[4] [5]
[6] [7] [8]
[1] Multi-turn actuatorsSA 07.1 – SA 48.1Torques from 10 to 32,000 NmOutput speeds from 4 to 180 rpm
[2] Multi-turn actuators SA/SARwith controls AUMATICTorques from 10 to 1,000 NmOutput speeds from 4 to 180 rpm
[3] Linear actuators SA/LECombination of multi-turn actuator SAwith linear thrust unit LEThrusts from4 kN to 217 kNStrokes up to 500 mmLinear speedsfrom 20 to 360 mm/min
[4] Part-turn actuatorsSG 05.1 – SG 12.1Torques from 100 to 1,200 NmOperating times for 90° from 4 to 180 s
[5] Part-turn actuators SA/GSCombination of multi-turn actuator SA withpart-turn gearbox GSTorques up to 675,000 Nm
[6] Bevel gearboxesGK 10.2 – GK 40.2Torques up to 16,000 Nm
[7] Spur gearboxesGST 10.1 – GST 40.1Torques up to 16,000 Nm
[8] Worm gearboxes with base and leverGF 50.3 – GF 250.3Torques up to 32,000 Nm
Subject to change without notice.The product features and technical data provided do not express or imply any warranty.Y000.038/002/en/1.06Certificate Registration No.
12 100/104 4269