Control
Parallel
→ Profibus DP
Modbus RTU
Part-turn actuators
PROFOX
PF-Q80 – PF-Q600
Assembly and commissioningOperation instructions
Read operation instructions first.● Observe safety instructions.● These operation instructions are part of the product.● Store operation instructions during product life.● Pass on instructions to any subsequent user or owner of the product.
Target group:
This document contains information for assembly, commissioning and maintenance staff.
Table of contents Page
41. Safety instructions.................................................................................................................41.1. Prerequisites for the safe handling of the product41.2. Range of application51.3. Warnings and notes51.4. References and symbols
62. Short description...................................................................................................................
83. Name plate..............................................................................................................................
104. Transport and storage...........................................................................................................104.1. Transport104.2. Storage
115. Assembly................................................................................................................................115.1. Mounting position115.2. Fit ball handle to handwheel115.3. Mount actuator to valve115.3.1. Overview on coupling variants125.3.2. Mount actuator (with coupling)
156. Electrical connection.............................................................................................................156.1. Basic information176.2. Open terminal compartment176.3. Cable connection206.4. Fieldbus cables: connect226.5. Close terminal compartment236.6. External earth connection
247. Commissioning......................................................................................................................247.1. End stops in part-turn actuator257.1.1. Set end stop CLOSED267.1.2. Set end stop OPEN267.2. End position setting (via push buttons)277.2.1. Set end position CLOSED287.2.2. Set end position OPEN297.3. Position indicator setting307.3.1. Position indication for 90°307.3.2. Position indication for 120°317.3.3. Position indication for 45° – 360°327.4. Configuration of further parameters327.4.1. Speed setting
2
PF-Q80 – PF-Q600Table of contents Profibus DP
347.4.2. Fieldbus
358. Operation................................................................................................................................358.1. Manual operation358.2. Motor operation358.2.1. Actuator operation via push buttons368.2.2. Actuator operation via AUMA Assistant App378.2.3. Actuator operation from Remote
399. FOX-EYE indication light and status indication..................................................................
4210. Corrective actions..................................................................................................................4210.1. Faults during commissioning4210.2. Fault indications
4411. Servicing and maintenance...................................................................................................
4612. Disposal and recycling..........................................................................................................
4713. Technical data.........................................................................................................................4713.1. Technical data Part-turn actuator with integral controls for open-close and modulating duty
5214. Spare parts.............................................................................................................................5214.1. Part-turn actuators PF-Q80 – PF-Q600
54Index........................................................................................................................................
3
PF-Q80 – PF-Q600 Profibus DP Table of contents
1. Safety instructions
1.1. Prerequisites for the safe handling of the product
Standards/directives The end user or the contractor must ensure that all legal requirements, directives,guidelines, national regulations and recommendations with respect to assembly,electrical connection, commissioning and operation are met at the place of installation.
They include among others:
● Applicable configuration guidelines for fieldbus applications.
Safety instructions/warnings All personnel working with this device must be familiar with the safety and warning
instructions in this manual and observe the instructions given. Safety instructionsand warning signs on the device must be observed to avoid personal injury or propertydamage.
Qualification of staff Assembly, electrical connection, commissioning, operation, and maintenance mustbe carried out by suitably qualified personnel authorised by the end user or contractorof the plant only.
Prior to working on this product, the staff must have thoroughly read and understoodthese instructions and, furthermore, know and observe officially recognised rulesregarding occupational health and safety.
Commissioning Prior to commissioning, imperatively check that all settings meet the requirementsof the application. Incorrect settings might present a danger to the application, e.g.cause damage to the valve or the installation. The manufacturer will not be heldliable for any consequential damage. Such risk lies entirely with the user.
Operation Prerequisites for safe and smooth operation:
● Correct transport, proper storage, mounting and installation, as well as carefulcommissioning.
● Only operate the device if it is in perfect condition while observing these instruc-tions.
● Immediately report any faults and damage and allow for corrective measures.● Observe recognised rules for occupational health and safety.● Observe national regulations.● During operation, the housing warms up and surface temperatures > 60 °C may
occur.To prevent possible burns, we recommend checking the surface temper-ature prior to working on the device using an appropriate thermometer andwearing protective gloves.
Protective measures The end user or the contractor are responsible for implementing required protectivemeasures on site, such as enclosures, barriers, or personal protective equipmentfor the staff.
Maintenance To ensure safe device operation, the maintenance instructions included in this manualmust be observed.
Any device modification requires prior written consent of the manufacturer.
1.2. Range of application
AUMA part-turn actuators are designed for the operation of industrial valves, e.g.butterfly valves and ball valves.
Other applications require explicit (written) confirmation by the manufacturer.
The following applications are not permitted, e.g.:
● Industrial trucks according to EN ISO 3691● Lifting appliances according to EN 14502● Passenger lifts according to DIN 15306 and 15309
4
PF-Q80 – PF-Q600Safety instructions Profibus DP
● Service lifts according to EN 81-1/A1● Escalators● Continuous duty● Buried service● Continuous underwater use (observe enclosure protection)● Potentially explosive atmospheres● Radiation exposed areas in nuclear power plantsNo liability can be assumed for inappropriate or unintended use.
Observance of these operation instructions is considered as part of the device'sdesignated use.
Information These operation instructions are only valid for the "clockwise closing" standardversion, i.e. driven shaft turns clockwise to close the valve.
1.3. Warnings and notes
The following warnings draw special attention to safety-relevant procedures in theseoperation instructions, each marked by the appropriate signal word (DANGER,WARNING, CAUTION, NOTICE).
Indicates an imminently hazardous situation with a high level of risk. Failureto observe this warning results in death or serious injury.
Indicates a potentially hazardous situation with a medium level of risk. Failureto observe this warning could result in death or serious injury.
Indicates a potentially hazardous situation with a low level of risk. Failure toobserve this warning could result in minor or moderate injury. May also beused with property damage.
Potentially hazardous situation. Failure to observe this warning could resultin property damage. Is not used for personal injury.
Safety alert symbol warns of a potential personal injury hazard.
The signal word (here: DANGER) indicates the level of hazard.
1.4. References and symbols
The following references and symbols are used in these instructions:
Information The term Information preceding the text indicates important notes and information.
Symbol for CLOSED (valve closed)
Symbol for OPEN (valve open)
➥ Result of a process step
Describes the result of a preceding process step.
5
PF-Q80 – PF-Q600 Profibus DP Safety instructions
2. Short description
Part-turn actuator AUMA part-turn actuators PF-Q80 – PF-Q600 are driven by an electric motor. Forcontrol in motor operation and for processing the actuator signals, controls areintegrated within the housing. Push buttons allow for local actuator operation. Ahandwheel is provided for occasional manual operation. Manual operation is possiblewithout change-over.
The swing angle is limited by internal end stops. Switching off in end positions maybe either by limit or torque seating.
The self-locking of the actuator is ensured by means of the braking function. As soonas the actuator is at standstill, the motor takes over the brake function for the first20 seconds. This period is defined through a parameter which can be set viaBluetooth. After this, the locking brake takes over the brake function by disconnectionfrom power and renewed engagement. Brake engagement generates a clicking noiseand is part of the standard operational behaviour.
AUMA part-turn actuatorPROFOX PF-Q150
Figure 1: PF-Q150
[1] Push buttons[2] Position indicator[3] Screw plug for end stop[4] FOX-EYE (indication LED)[5] Screw plug for manual emergency operation[6] Handwheel
Information Only smaller sizes without handwheel function areequipped with a manual drive option via Allen key, loc-ated below the screw plug for manual emergency oper-ation [5].
App and software
Using the AUMA CDT software for Windows-based computers (notebooks or tablets)and the AUMA Assistant App, actuator data can be uploaded and read, settingscan be modified and stored. The connection between computer and AUMA actuatoris established wireless via Bluetooth interface. With the AUMA Cloud, we providean interactive platform to collect and assess e.g. detailed device data of all actuatorswithin a plant.
6
PF-Q80 – PF-Q600Short description Profibus DP
Figure 2: Communication via Bluetooth
AUMA CDT AUMA CDT is a user-friendly setting and operation program for AUMA actuators.
Connection between computer (notebook, tablet) and actuator is wireless viaBluetooth interface.
AUMA CDT software can be downloaded free of charge from our websitewww.auma.com.
AUMA Cloud
The AUMA Cloud is the driving element of the digital AUMA world, acting asinteractive platform for efficient maintenance of AUMA actuators at moderate cost.The AUMA Cloud collects all device data of all actuators within one site and providesa clear overview at a glance. Detailed analysis provides valuable information onpotential maintenance requirements. Additional functions foster smooth assetmanagement.
AUMA Assistant AppThe AUMA Assistant App enables commissioning, configuration and diagnostics ofAUMA actuators via Bluetooth using either smartphone or tablet.
The AUMA Assistant App can be downloaded free of charge from the Play Store(Android) or App Store (iOS).
Figure 3: Link to AUMA Assistant App
7
PF-Q80 – PF-Q600 Profibus DP Short description
3. Name plate
Figure 4: Name plate arrangement
Figure 5: PROFOX name plate (example)
[1] Product name[2] Type designation[3] Order number[4] Actuator serial number[5] Torque range in direction OPEN/CLOSE[6] Control[7] Operating time range in [s] for a part-turn movement of 90°[8] Current type, mains voltage, mains frequency[9] Type of duty[10] Permissible ambient temperature[11] Manufacturer name and address (manufacturer logo: )[12] Data Matrix code[13] Swing angle[14] Nominal power and nominal current[15] Enclosure protection
8
PF-Q80 – PF-Q600Name plate Profibus DP
Descriptions referring to name plate indications
Type designation Table 1:Description of type designation (with the example of PROFOX PF-Q150-F07-F10)
F07 – F10150QPFPROFOX
Product namePROFOX
Type (abbreviation PROFOX)PF
Type of movement: Part-turn actuatorQ
Size (max. torque in Nm)150
Flange sizesF07 – F10
Order number The product can be identified using this number and the technical data as well asorder-related data pertaining to the device can be requested.
Please always state this number for any product inquiries.
On the Internet at http://www.auma.com > Service & Support >myAUMA, we offera service allowing authorised users to download order-related documents such aswiring diagrams and technical data (both in German and English), inspection certificateand the operation instructions when entering the order number.
Serial numberActuator
Table 2:Description of serial number (example of 0520NS12345)
NS123452005
Positions 1+2: Assembly in week = week 0505
Positions 3+4:Year of manufacture = 202020
Internal number for unambiguous product identificationNS12345
Data Matrix code When registered as authorised user, you may use our AUMA Assistant App to scanthe Data Matrix code and directly access the order-related product documents withouthaving to enter order number or serial number.
Figure 6: Link to AUMA Assistant App:
For further Service & Support, Software/Apps/... refer to www.auma.com
9
PF-Q80 – PF-Q600 Profibus DP Name plate
4. Transport and storage
4.1. Transport
For transport to place of installation, use sturdy packaging.
Suspended load!
Death or serious injury.
→ Do NOT stand below suspended load.→ Attach ropes or hooks for the purpose of lifting by hoist only to housing and NOT
to handwheel.→ Actuators mounted on valves: Attach ropes or hooks for the purpose of lifting
by hoist to valve and NOT to actuator.→ Actuators mounted to gearboxes: Attach ropes or hooks for the purpose of lifting
by hoist only to the gearbox using eyebolts and NOT to the actuator.→ Respect total weight of combination (actuator, gearbox, valve)→ Secure load against falling down, sliding or tilting.→ Perform lift trial at low height to eliminate any potential danger e.g. by tilting.
4.2. Storage
Risk of corrosion due to inappropriate storage!
→ Store in a well-ventilated, dry room.→ Protect against floor dampness by storage on a shelf or on a wooden pallet.→ Cover to protect against dust and dirt.→ Apply suitable corrosion protection agent to uncoated surfaces.
Long-term storage For long-term storage (more than 6 months), observe the following points:
1. Prior to storage:Protect uncoated surfaces, in particular the output drive parts and mountingsurface, with long-term corrosion protection agent.
2. At an interval of approx. 6 months:Check for corrosion. If first signs of corrosion show, apply new corrosion protec-tion.
10
PF-Q80 – PF-Q600Transport and storage Profibus DP
5. Assembly
5.1. Mounting position
The product described in this document can be operated without restriction in anymounting position.
5.2. Fit ball handle to handwheel
To avoid damage during transport, the ball handle is fitted at the rear of thehandwheel.
Prior to commissioning, mount the ball handle into correct position:
1. Remove cap nut [1] and pull out ball handle [2].2. Insert ball handle [2] in correct position and fasten with cap nut [1].
5.3. Mount actuator to valve
The actuator is mounted to the valve using a coupling.
Corrosion due to damage to paint finish and condensation!
→ Touch up damage to paint finish after work on the device.→ After mounting, immediately perform electrical connection of the device to min-
imise condensation cause by standby current.
5.3.1. Overview on coupling variants
Design Figure 7: Coupling variants
[1] Bore with keyway[2] Square bore[3] Bore with two-flats
Application ● For valve attachments according to EN ISO 5211● For rotating, non-rising valve stem
11
PF-Q80 – PF-Q600 Profibus DP Assembly
5.3.2. Mount actuator (with coupling)
Unbored couplings or couplings with pilot bore must be machined to match the valveshaft prior to mounting the actuator to the valve (e.g. with bore and keyway, two-flator square bore).
Assemble valve and actuator in the same end position. As standard, the actu-ator is supplied in end position CLOSED.
→ Recommended mounting position for butterfly valves: End position CLOSED.→ Recommended mounting position for ball valves: End position OPEN.
Assembly steps 1. If required, move actuator in same end position as valve using the handwheel.2. Clean mounting faces, thoroughly degrease uncoated mounting surfaces.3. Apply a small quantity of grease to the valve shaft [2].
12
PF-Q80 – PF-Q600Assembly Profibus DP
4. Place coupling [1] onto valve shaft [2] and secure against axial slipping by usinga grub screw [3] or a clamping washer and a screw with curved spring lockwasher [4]. Thereby, ensure that dimensions X, Y or L are observed (refer tofigure and table <Mounting positions for coupling>).
Figure 8: Examples: Fit coupling
[1] Coupling[2] Valve shaft[3] Grub screw[4] Clamping washer and screw with curved spring lock washer
Figure 9: Mounting positions for coupling
Table 3:Mounting position of the coupling within fitting dimensions according to AUMA definition
Q600Q300Q150Q80Dimensions[mm]
F10F07F10F07F10F07F05F10F07F05EN ISO 5211
4.54.54.54.5333333X max.
4.54.54.54.5222222Y max.
50505050381)/40381)/40381)/40381)/40381)/40381)/40L max.
Thread with grub screw1)
5. Apply non-acidic grease at splines of coupling (e.g. Gleitmo by Fuchs).
13
PF-Q80 – PF-Q600 Profibus DP Assembly
6. Fit actuator. If required, slightly turn actuator until splines of coupling engage.
Figure 10: Mounting the actuator onto valve
Information Ensure complete contact of flanges.
7. If flange bores do not match thread:
7.1 Slightly rotate handwheel until bores line up.
7.2 If required, shift actuator by one tooth on the coupling.8. Fasten actuator with screws.
Information: We recommend applying liquid thread sealing material to thescrews to avoid contact corrosion.
9. Fasten screws crosswise to a torque according to table.
Table 4:Tightening torques for screws
Tightening torque [Nm]Threads
Strength class A2-80/A4–80
10M6
24M8
48M10
82M12
200M16
392M20
14
PF-Q80 – PF-Q600Assembly Profibus DP
6. Electrical connection
6.1. Basic information
Electric shock due to presence of hazardous voltage!
Risk of death or serious injury!
→ The electrical connection must be carried out exclusively by suitably qualifiedpersonnel.
→ Prior to connection, observe basic information contained in this chapter.
Risk of immediate actuator operation when connecting to mains!
Risk of death, severe injury or damage to valve.
→ Check operation signals and operation behaviour prior to switching on the mainsvoltage.
→ Ensure that the tripping conditions for the failure behaviour are not fulfilled whenswitching on.
→ Ensure that the tripping conditions for the EMERGENCY behaviour are not ful-filled when switching on.
Reasons for immediate operation:
● The signal and fieldbus cables are connected and a respective operation com-mand has been issued.
● the “failure behaviour” function was configured as to ensure that this state resultsin an operation once the mains voltage is applied.
● the “EMERGENCY behaviour” function was configured as to ensure that thisstate results in an operation once the mains voltage is applied.
Wiring diagram/terminalplan
The pertaining wiring diagram/terminal plan (in German or English) is attached tothe device in a weather-proof bag, together with these operation instructions. It canalso be requested from AUMA (state order number, refer to name plate) ordownloaded directly from the Internet (http://www.auma.com).
Permissible networks(supply networks)
The actuators are suitable for use in TN and TT networks. For IT network, a suitable,approved insulation monitor measuring the pulse code is required.
Current type, mainsvoltage, mains fre-
quency
Type of current, mains voltage and mains frequency must match the data on thename plate.
For short-circuit protection and for disconnecting the actuator from the mains, fusesand disconnect switches or circuit breakers have to be provided by the customer.For circuit breakers, the following sizing/characteristics are recommended:
Sizing/characteristicsNumber of actuators
B061
B102
C134
D1610
Refer to electric data for the maximum current values of individual models andversions.
Potential of customerconnections
Refer to Technical data for options of isolated potentials.
Safety standards Safety measures and safety equipment must comply with the respectively validnational on site specifications. All externally connected devices shall comply withthe relevant safety standards applicable for the place of installation.
15
PF-Q80 – PF-Q600 Profibus DP Electrical connection
Connecting cables,cable glands, reducers,
blanking plugs
● We recommend using connecting cables and connecting terminals accordingto rated current (IN) (refer to motor or electrical data sheet).
● For device insulation, appropriate (voltage-proof) cables must be used. Specifycables for the highest occurring rated voltage.
● To avoid contact corrosion, we recommend the use of sealing agents for cableglands and blanking plugs made of metal.
● Use connecting cable with appropriate minimum rated temperature.● For connecting cables exposed to UV radiation (outdoor installation), use UV
resistant cables.● For the connection of position transmitters, screened cables must be used.
Cable installation in ac-cordance with EMC
Signal and fieldbus cables are susceptible to interference. Motor cables areinterference sources.
● Lay cables being susceptible to interference or sources of interference at thehighest possible distance from each other.
● The interference immunity of signal and fieldbus cables increases if the cablesare laid close to the earth potential.
● If possible, avoid laying long cables and make sure that they are installed inareas being subject to low interference.
● Avoid parallel paths with little cable distance of cables being either susceptibleto interference or interference sources.
Fieldbus cable Table 5:Cable recommendationOnly cables complying with IEC 61158 or IEC 61784, cable type A, may be used for Profibus DP wiring.
135 to 165 Ohm, at a measurement frequency between 3 and 20 MHzImpedance
< 30 pF per metreCable capacity
> 0.64 mmWire diameter
> 0.34 mm², corresponds to AWG 22Cross section
< 110 Ohm per kmLoop resistance
CU shielding braid or shielding braid and shielding foilScreening
Prior to installation, please note:● Connect maximum 32 devices to one segment.● If more devices are to be connected:
- Allot devices to different segments.- Connect segments using repeaters.
● Install fieldbus cables at a distance of minimum 20 cm to other cables.● If possible, fieldbus cables should be laid in a separate, conductive, and earthed
cable tray.● Ensure absence of equipotential earth bonding differences between the indi-
vidual devices at fieldbus (perform an equipotential earth bonding).
1,500500187.5≥ 93.75Baud rate [kbit/s]
2004001,0001,200Maximum segment length [m]
16
PF-Q80 – PF-Q600Electrical connection Profibus DP
6.2. Open terminal compartment
Figure 11: Open terminal compartment
[1] Cover[2] Screws[3] Cable entry[4] Blanking plug[5] Cable gland (not included in scope of delivery)
Electric shock due to presence of hazardous voltage!
Death or serious injury.
→ Disconnect device from the mains before opening.→ Wait for 60 seconds after power cut-off prior to opening the housing.
1. Loosen screws [2] and remove cover [1].2. Insert cable glands [5].
➥ The enclosure protection IP… stated on the name plate is only ensured if suit-able cable glands are used.
Figure 12: Example: Name plate for enclosure protection IP68
3. Tighten cable glands and blanking plugs with the appropriate torque in compli-ance with the manufacturer's specifications.
6.3. Cable connection
Cable arrangement
Cable arrangement depends on the number of cables connected in addition to themains cable. There are two options:
17
PF-Q80 – PF-Q600 Profibus DP Electrical connection
Figure 13: Cable arrangement
[1] Cable arrangement for one mains cable and one fieldbus cable[2] Cable arrangement for one mains cable and two additional cables
For better accessibility, we recommend heeding the following order.
1. If a signal cable is connected in addition to the fieldbus cable: Insert signal cableinto cable gland on the right and push upward until the cable is visible.
2. Insert fieldbus cables through middle cable gland and push upward until thecable is visible.
3. Insert mains cable into left cable gland and also push upward until the cable isvisible.
Connection of mains and signal cables
4. Remove cable sheathing.5. Strip wires.
→ Controls approx. 6 mm, power supply unit approx. 10 mm6. For flexible cables: Use wire end sleeves according to DIN 46228.7. Connect mains cable according to order-related wiring diagram.
Table 6:Terminal cross sections
Cross sectionWire typeDesignation
max. [mm²]min. [mm²]
2.50.08rigid/flexibleMains cable
AWG 12AWG 28AWG
18
PF-Q80 – PF-Q600Electrical connection Profibus DP
8. Connect signal cables in push-in technology according to order-related wiringdiagram.Information: Only required if a signal cable is to be connected in addition tothe fieldbus cable.
Damage to push-in terminals by jamming of wire end sleeves with the housing!
Replacement of the complete component is required.
→ Use suitable crimping pliers (Crimpfox 6 by Phoenix Contact or similar model)to avoid unevenness of the wire end sleeve.
→ Always carefully remove signal cables.
Figure 14: Connect signal cables
Table 7:Terminal cross sections
Cross sectionWire typeDesignation
max. [mm²]min. [mm²]
1.50.2solidI/O signal cable
1.50.2flexible
1.50.2flexible with wire endsleeve without plasticsleeve
AWG 16AWG 24AWG
19
PF-Q80 – PF-Q600 Profibus DP Electrical connection
PE connection
In case of a fault, electric shock due to presence of hazardous voltage if thePE conductor is NOT connected!
Risk of death or serious injury!
→ Connect all protective earth conductors.→ Connect PE connection to external protective earth conductor of connecting
cables.→ Start running the device only after having connected the protective earth con-
ductor.
9. Fasten PE using spade lugs or wire end sleeves at protective earth connection( ) as shown. Do not completely loosen screw!
Figure 15: Protective earth connection (example)
Table 8:Terminal cross sections and tightening torques of PE connection
Tightening torquesTerminal cross sectionsDesignation
3 – 4 Nm1.0 – 6 mm2 (flexible) via spade lug orwire end sleeve1.5 – 4 mm2 (flexible) directly1.5 – 6 mm2 (rigid) directly
Protective earth connection (PE)
10. Connect fieldbus cables.
Refer to subsequent chapter!
6.4. Fieldbus cables: connect
If a PROFOX actuator is part of a complete line or loop topology, the connexionremains continuous even if the actuator is without power or defective.
20
PF-Q80 – PF-Q600Electrical connection Profibus DP
1. Observe characteristics of topology used.
Figure 16: Structure for line topology
further fieldbus devices will follow□last fieldbus device, termination must be activ-ated
■
from the previous device↑to the next device↓
In case of a fault, electric shock due to presence of hazardous voltage if thePE conductor is NOT connected!
Risk of death or serious injury!
→ Connect all protective earth conductors.→ Connect PE connection to external protective earth conductor of connecting
cables.→ Start running the device only after having connected the protective earth con-
ductor.
2. Strip fieldbus cables.
Shield connection 3. Remove fieldbus cable shield at a short section as shown and connect to shieldconnection. Ensure absence of electrical contact to the terminal.
Figure 17: Shield connection
21
PF-Q80 – PF-Q600 Profibus DP Electrical connection
Fieldbus cables 4. Connect fieldbus cables: Connect green wires with green terminal and red wirewith red terminal.
Table 9:Terminal cross sections
Cross sectionWire typeDesignation
max. [mm²]min. [mm²]
1.50.5solidFieldbus cables
1.50.5flexible
1.00.5flexible with wire endsleeve without plasticsleeve
AWG 16AWG 20AWG
Bus termination 5. If the actuator is the last fieldbus participant within the fieldbus segment: Activateparameter or function Bus termination channel 1 M2239 via AUMA AssistantApp or AUMA CDT software.Information: As soon as the bus termination is active, the connection to thenext fieldbus device is automatically interrupted to avoid multiple terminations.The bus termination is deactivated when leaving the factory.
6. Fasten cable glands with the torque as specified by the manufacturer to ensurerespect of required enclosure protection.
7. Connect power supply.
If the end position setting is carried out with the internal operation buttonsfollowing the connection to the power supply: Do not close cover!
6.5. Close terminal compartment
Figure 18: Terminal compartment: close
[1] Cover[2] Screws[3] O-ring
Short-circuit and electric shock due to pinching of cables!
Risk of death or serious injury!
→ Carefully assemble cover to avoid pinching the cables.
22
PF-Q80 – PF-Q600Electrical connection Profibus DP
1. Clean sealing faces of cover [1] and housing.2. Check whether O-ring [3] is mounted in the provided groove.3. Fit cover [1] and fasten screws [2] evenly crosswise at 24 Nm (M8).
6.6. External earth connection
Standard version: Without earth connection, with plastic plate and screw only.
Option: With earth connection consisting of metal plate and hex. socket cap headscrew with shaft bearing race.
The actuator is equipped with an earth connection consisting of a metal plate and ahex. socket cap head screw with shaft bearing race.
Insulating impact of the powder coating can lead to hazardous voltage andelectric shock!
Risk of death or serious injury!
→ Strip powder from actuator surface (file down).→ Connect all protective earth conductors.→ Connect earth connection to external protective earth conductor of connection
cable.→ Power the device only once the protective earth conductor has been connected.
Figure 19: Earth connection
Application External earth connection (U-bracket) for connection to equipotential compensation.
Table 10:Terminal cross sections and earth connection tightening torques
Tightening torquesTerminal cross sectionsConductor type
3 – 4 Nm2.5 mm² to 6 mm²solid
3 – 4 Nm1.5 mm² to 4 mm²flexible
For fine stranded (flexible) wires, connection is made via cable lugs/ring terminals. When connectingtwo individual wires with a U-bracket, cross sections have to be identical.
23
PF-Q80 – PF-Q600 Profibus DP Electrical connection
7. CommissioningCommissioning is made in four steps:
1. End stop setting2. End position setting3. Position indicator setting4. Configuration of further parameters
Besides end position settings, all other settings have already been made inthe factory in compliance with the order.
If correctly ordered, only end position setting is required.
The following table shows the most important parameters and how they can beconfigured.
PageAUMA CDTAUMA AssistantApp
At the actuatorParameter/desig-nation
SettingStep
page 25, Set endstop CLOSED
NoNoYesEnd stop CLOSEDSwing angle limita-tion
End stop setting
page 26, Set endstop OPEN
NoNoYesEnd stop OPEN
page 27, Set endposition CLOSED
YesYesYesEnd positionCLOSED setting
PositionsEnd position set-ting
page 28, Set endposition OPEN
YesYesYesEnd position OPENsetting
page 29, Positionindicator setting
NoNoYesIndication end posi-tion CLOSED
Indication for theend positions
Position indicatorsetting
NoNoYesIndication end posi-tion OPEN
—YesYesNoEnd positionCLOSED
Type of seatingConfiguration offurther parameters
YesYesNoEnd position OPEN
YesYesNoTripping torqueCLOSE
Torque switching
YesYesNoTripping torqueOPEN
page 32, Speedsetting
YesYesNoOperating timeSpeeds
—YesYesNoType and assign-ment
I/O signals (bin-ary/analogue)
—YesYesNoVarious paramet-ers
Positioner
page 34, FieldbusYesYesNoFieldbus addressFieldbus
Many further parameters can be configured using the AUMA Assistant App or AUMACDT.
7.1. End stops in part-turn actuator
The following description applies for clockwise closing standard version.
Separate instructions are available for counterclockwise special version.
24
PF-Q80 – PF-Q600Commissioning Profibus DP
The internal end stops limit the swing angle. They protect the valve in case of limitswitching failure during motor operation and serve the purpose as limitation formanual operation via handwheel. They may not be used for torque tripping in endpositions during standard operation.
End stop setting is generally performed by the valve manufacturer prior to installingthe valve into the pipework.
Exposed, rotating parts (discs/balls) at the valve!
Pinching and damage by valve or actuator.
→ End stops should be set by suitably qualified personnel only.→ Never completely remove the setting screws [2] and [4] to avoid grease leakage.→ Observe dimension Tmin.
Information ● The swing angle set in the factory is indicated on the name plate:
● The setting sequence depends on the valve:- Recommendation for butterfly valves: Set end stop CLOSED first.- Recommendation for ball valves: Set end stop OPEN first.
Figure 20: End stops
[1] Screw plug for end stop OPEN[2] Setting screw for end stop OPEN[3] Screw plug for end stop CLOSED[4] Setting screw for end stop CLOSED
Q600Q300Q150Q80Dimensions/sizes
18.518.514.514.5T (for 90°)
111199Tmin.
7.1.1. Set end stop CLOSED
With fitted handwheel: Dismantle handwheel prior to end stop CLOSED setting!
1. Remove screw plug [3].2. Move valve to end position CLOSED with handwheel.
25
PF-Q80 – PF-Q600 Profibus DP Commissioning
3. If the valve end position is not reached:
→ Slightly turn setting screw [4] counterclockwise until valve end positionCLOSED can be safely set.
➥ Turning the setting screw [4] clockwise results in a smaller swing angle.
➥ Turning the setting screw [4] counterclockwise results in a larger swingangle.
4. Turn setting screw [4] clockwise to the stop.
➥ This completes the setting of end stop CLOSED.
5. Check O-ring of screw plug for seat and condition, replace if damaged.6. Screw in screw plug [1] and fasten while applying the following torque:
➥ PF-Q80X – PF-Q150X: 13 Nm (M12)
➥ PF-Q300X – PF-Q600X: 13 Nm (M16)
Having completed this procedure, the end position detection CLOSED can be setimmediately.
7.1.2. Set end stop OPEN
Information In general, the end stop OPEN does not have to be set.
1. Remove screw plug [1].2. Move valve to end position OPEN with handwheel.3. If the valve end position is not reached:
→ Slightly turn setting screw [2] counterclockwise until valve end positionOPEN can be safely set.
➥ Turning the setting screw [2] clockwise results in a smaller swing angle.
➥ Turning the setting screw [2] counterclockwise results in a larger swingangle.
4. Turn setting screw [2] clockwise to the stop.
➥ This completes the setting of end stop OPEN.
5. Check O-ring of screw plug for seat and condition, replace if damaged.6. Screw in screw plug [1] and fasten while applying the following torque:
➥ PF-Q80X – PF-Q150X: 13 Nm (M12)
➥ PF-Q300X – PF-Q600X: 13 Nm (M16)
Having completed this procedure, the end position detection OPEN can be setimmediately.
7.2. End position setting (via push buttons)
In case of torque seating: Check factory torque setting!
The end positions may also be set using the AUMA Assistant App or the AUMACDT software.
26
PF-Q80 – PF-Q600Commissioning Profibus DP
Valve damage at valve/gearbox due to incorrect setting!
→ When setting with motor operation: Interrupt operation in time prior to reachingthe end stop.
→ Heed overrun when selecting actuator seating via positions.
7.2.1. Set end position CLOSED
Electric shock due to presence of hazardous voltage!
Failure to observe this warning results in death or serious injury.
→ Electrical connection and commissioning must be carried out exclusively bysuitably qualified personnel if circuit is live.
→ Do not touch any cables.
1. Remove cover from actuator.2. Operate in direction CLOSE via push button until complete valve closing.
Risk of passing set end positions!
→ During operation in directions OPEN/CLOSE, the actuator stops when reachingthe set end position. When pressing again the button, the actuator runs untilreaching a mechanical stop (end stop of the actuator or the valve) or passesthe end position when releasing the button.
➥ The operation in direction CLOSE is signalled by the LED flashing in red.
3. Once the desired end position CLOSED has been reached, release the pushbutton .
➥ The LED continues flashing in blue for approx. 10 seconds. This time span al-lows for end position setting.
27
PF-Q80 – PF-Q600 Profibus DP Commissioning
4. While LED is flashing in blue, hold down push button for at least two secondsuntil the LED is illuminated in red.
➥ The end position CLOSED setting has been successfully completed.
7.2.2. Set end position OPEN
Electric shock due to presence of hazardous voltage!
Failure to observe this warning results in death or serious injury.
→ Electrical connection and commissioning must be carried out exclusively bysuitably qualified personnel if circuit is live.
→ Do not touch any cables.
1. Remove cover from actuator.2. Operate in direction OPEN via push button until complete valve opening.
Risk of passing set end positions!
→ During operation in directions OPEN/CLOSE, the actuator stops when reachingthe set end position. When pressing again the button, the actuator runs untilreaching a mechanical stop (end stop of the actuator or the valve) or passesthe end position when releasing the button.
➥ The operation in direction OPEN is signalled by the LED flashing in green.
28
PF-Q80 – PF-Q600Commissioning Profibus DP
3. Once the desired end position OPEN has been reached, release the push button.
➥ The LED continues flashing in blue for approx. 10 seconds. This time span al-lows for end position setting.
4. While LED is flashing in blue, hold down push button for at least two secondsuntil the LED is illuminated in green.
➥ The end position OPEN setting has been successfully completed.
7.3. Position indicator setting
The position indicator shows the valve position through its rotating indication. Ifcorrectly set, the position indicator shows the colour red when in end positionCLOSED and green when in end position OPEN.
The following table provides an overview of the different positions indications andrefers to the chapter describing the respective setting.
Table 11: Position indicationsPageIndication rangeFigure
page 30, Position indication for 90°90°
page 30, Position indication for 120°120°
page 31, Position indication for 45° – 360°45° – 360°
29
PF-Q80 – PF-Q600 Profibus DP Commissioning
7.3.1. Position indication for 90°
Figure 21: Position indicator
1. Remove screw plug [1].2. Operate actuator to end position CLOSED.3. Turn inner shaft [2] using a suitable screwdriver until the display windows of
position indicator [3] are red.4. Operate actuator to end position OPEN.5. Check whether the windows of the position indicator [3] are completely green.
➥ If yes: Position indicator has been correctly set. If no: Resume as of step 1.
7.3.2. Position indication for 120°
Figure 22: Position indicator
1. Remove screw plug [1].2. Operate actuator to end position CLOSED.3. Turn inner shaft [2] using a suitable screwdriver until the complete display win-
dow of position indicator [3] is red.4. Operate actuator to end position OPEN.5. Check whether the window of the position indicator [3] is completely green.
➥ If yes: Position indicator has been correctly set. If no: Resume as of step 1.
30
PF-Q80 – PF-Q600Commissioning Profibus DP
7.3.3. Position indication for 45° – 360°
After successful setting, the black line of the position indicator should move acrossrange indicated by the red and green labels.
1. Operate actuator to end position CLOSED.
Wide swing angle range
Depending on the position of the first label, the second label will be on the back ofthe position indicator.
→ Check swing angle range and possible label position prior to actually stickingthe label onto the position indicator.
2. Stick the red label [1] included in the scope of supply at any position of the po-sition indicator.
3. Turn inside shaft [2] using an appropriate screwdriver until the black strip [3] isat the same position as the red label [1].
4. Operate actuator to end position OPEN.
31
PF-Q80 – PF-Q600 Profibus DP Commissioning
5. Stick the green label [3] onto the black strip [3] and make sure that they com-pletely overlap.
7.4. Configuration of further parameters
Either the AUMA Assistant App or AUMA CDT software is required to use thecomplete range of configuration options.
The user level defines which parameters are displayed or can be changed.
Information For further information relating to user levels and passwords, please refer to page37, Table 23
7.4.1. Speed setting
The speeds are determined by the motor speed. The motor speed and thus theactuator speed can be modified using the AUMA Assistant App or AUMA CDT.
Setting is made using a percentage value within the range of 10 % and 100 %.Thereby, 100 % corresponds to the maximum motor speed and thus to the maximumactuator speed.
Table 12: Assignment of power levels to the motors and power supply units usedPower supply unitMotorPower level
65 W18 WV1
65 W25 WV2
85 W50 WV3
The speeds can be individually set for the following functions:
● Standard speed for operations in directions OPEN and CLOSE and back(parameter: Motor speed 1).
● Alternative standard speed if different speeds are required for operation in dir-ections OPEN and CLOSE or if continuous changes between two specified arerequired (parameter: Motor speed 2).
● Speeds for “Failure behaviour” and “EMERGENCY behaviour” functions:- for operation in direction CLOSE (parameter: Mot. sp.FB+EMCY CL)- for operation in direction OPEN (parameter: Mot. sp.FB+EMCY OP)
Variable speeds
For standard operations between directions OPEN and CLOSE and back, the defaultpattern is made by an analogue input signal or the fieldbus.The analogue input mustbe configured to interpret this signal.
The speed can be set within the range of 10 % and 100 % of the maximum motorspeed:
0/4 mA = 10 % of the maximum motor speed
20 mA = 100 % of the maximum motor speed
32
PF-Q80 – PF-Q600Commissioning Profibus DP
The applicable scaling limits are identical for the fieldbus. A respective field withinthe process representation is available.
Table 13: Example values for Q80 size settingSpeed in % of the maximum motor speed
V116 s – 160 s
V28 s – 80 s
V34 s – 40 s
Operating timeOutput drive
——100 %4 s
——71 %5.6 s
—100 %50 %8 s
—73 %36 %11 s
100 %50 %25 %16 s
72 %36 %18 %22 s
50 %25 %13 %32 s
40 %20%10 %40 s
35 %18 %—45 s
25 %13 %—63 s
22 %11 %—72 s
20 %10 %—80 s
18 %——90 s
13 %——125 s
11 %——150 s
10 %——160 s
Table 14: Example values for Q150 size settingSpeed in % of the maximum motor speed
V132 s – 320 s
V216 s – 160 s
V38 s – 80 s
Operating timeOutput drive
——100 %8 s
——73 %11 s
—100 %50 %16 s
—73 %36 %22 s
100 %50 %25 %32 s
71 %36 %18 %45 s
51 %25 %13 %63 s
44 %22 %11 %72 s
40 %20 %10 %80 s
36 %18 %—90 s
26 %13 %—125 s
21 %11 %—150 s
20 %10 %—160 s
18 %——180 s
15 %——210 s
13 %——250 s
10 %——320 s
33
PF-Q80 – PF-Q600 Profibus DP Commissioning
Table 15: Example values for Q300 size settingSpeed in % of the maximum motor speed
V163 s – 630 s
V245 s – 450 s
V322 s – 220 s
Operating timeOutput drive
——100 %22 s
——69 %32 s
—100 %50 %45 s
100 %71 %35 %63 s
88 %63 %31 %72 s
70 %50 %24 %90 s
50 %36 %18 %125 s
42 %30 %15 %150 s
35 %25 %12 %180 s
30 %21 %10 %210 s
29 %20 %10 %220 s
25 %18 %—250 s
20 %14 %—320 s
14 %10 %—450 s
10 %——630 s
Table 16: Example values for Q600 size settingSpeed in % of the maximum motor speed
V290 s – 750 s
V345 s – 450 s
Operating timeOutput drive
—100 %45 s
—71 %63 s
—63 %72 s
100 %60 %75 s
83 %50 %90 s
60 %36 %125 s
50 %30 %150 s
42 %25 %180 s
36 %21 %210 s
30 %18 %250 s
23 %14 %320 s
17 %10 %450 s
10 %—750 s
7.4.2. Fieldbus
Signals Feedback signals via fieldbus are defined by the GSD file.
Information If required, download the GSD file (General Station Description) from the Internet:www.auma.com
Refer to Technical data of the actuator for the Profibus DP ident no.
Fieldbus address For information on the feedback signals via fieldbus and the configuration of theparameters via fieldbus interface, refer to Manual (Device integration fieldbus) ProfibusDP.
Information Profibus DP address setting is carried out via parameter (AUMA CDT software orAUMA Assistant App)
34
PF-Q80 – PF-Q600Commissioning Profibus DP
8. Operation
8.1. Manual operation
The following description applies for clockwise closing standard version.
Separate instructions are available for counterclockwise special version.
The handwheel allows actuator operation even in case of power failure. Handwheeloperation is only provided for occasional manual valve operation.
The handwheel does not rotate during motor operation. Change-over from motoroperation to manual operation is not required.
1. Close valve: Turn handwheel clockwise.
➥ Drive shaft (valve) turns clockwise in direction CLOSE.
2. Open valve: Turn handwheel counterclockwise.
➥ Drive shaft (valve) turns counterclockwise in direction OPEN.
Information Turning the handwheel during motor operation extends or reduces the operatingtime, depending on the direction of rotation.
8.2. Motor operation
Valve damage due to incorrect settings!
→ Check the parameters configured in the factory prior to electrical actuator oper-ation.
→ In case of deviations, adapt the parameters according to the valve and applicationrequirements.
Frozen valves when used in low temperatures below –15 °C
→ Recommendation: Activate (parameter ) excessive torque to allow using a peaktorque of up to 127 % of the max. tripping torque when leaving the end position.
8.2.1. Actuator operation via push buttons
The actuator can be locally operated by means of four push buttons.
35
PF-Q80 – PF-Q600 Profibus DP Operation
Figure 23: Push buttons
[1] Set end position OPEN push button[2] Set operation in direction OPEN push button[3] Set operation in direction CLOSE push button[4] Set end position CLOSED push button[5] LED
Risk of passing set end positions!
→ During operation in directions OPEN/CLOSE, the actuator stops when reachingthe set end position. When pressing again the button, the actuator runs untilreaching a mechanical stop (end stop of the actuator or the valve) or passesthe end position when releasing the button.
1. Run actuator in direction OPEN: Hold down button [2].
➥ The LED flashes in green during operation in direction OPEN.
2. Run actuator in direction CLOSE: Hold down button [3].
➥ The LED flashes in red during operation in direction CLOSE.
8.2.2. Actuator operation via AUMA Assistant App
Functions Alternatively, actuator operation is possible using the “AUMA Assistant” smartphoneApp. The following table shows an overview of the menus of the AUMA AssistantApp and the AUMA CDT software.
DescriptionMenu
Display of all available warnings and faults includingrespective details.Actuator diagnostics and detailed diagnostics
Diagnostics
Operation in direction of end positionsResetting the fault log
Operation function
Setting the positions for end positions CLOSED andOPEN
Setting end positions
Device designationOrder number, serial number
Device ID
Configuration of all parametersConfiguration
Factory settingsRebooting the actuator
Service functions
36
PF-Q80 – PF-Q600Operation Profibus DP
User level User level (1), (2), (3), ... defines which menu items or parameters can be displayedor modified by the active user.
6 different users/user levels are available. User level (1), (2), (3), ... is indicated inthe top display row.
Figure 24: User level display (example user level 4)
Password A specific password is assigned to each user level and allows different actions. Thepassword must comprise 6 characters.
Table 17: User level and passwordUser levels and authorisations
Authorisation/passwordUser (user level)
Verify settingsNo password required
Observer (1)
Change configuration parameters (low level)Factory password: 000000
Operator (2)
Reserved for future useMaintenance (3)
Change configuration parameters (high level)e.g. type of seating, assignment of output contactsFactory password: 000000
Specialist (4)
Service staffChange configuration parameters (service level)
Service (5)
AUMA administratorAUMA (6)
Unauthorised access due to insecure password!
→ We recommend changing the password during initial commissioning.
8.2.3. Actuator operation from Remote
Operation mode Remote For remote control, actuator operation mode must be set to Remote.
The operation mode can be activated via AUMA Assistant App or AUMA CDTsoftware:
AUMA Assistant App
ConfigurationOperation modeSelector
Or directly via the menu Remote operation in:
Operation functionDefault setting: Operation mode = REMOTEAUMA CDT
Configuration M0053Operation mode M2919Selector M2264
Or directly via the tool bar in the “Device” tab in:
Selectoror:
Remote controlDefault setting: Operation mode = REMOTE
37
PF-Q80 – PF-Q600 Profibus DP Operation
→ Set operation mode to Remote.
➥ Now, the actuator can be remote-controlled via fieldbus.
Change-over betweenfieldbus control and
OPEN - CLOSE via I/Osignals
As standard, the actuator is supplied with fieldbus and binary signals. A binary inputis used to define which source is active, this means whether the actuator is controlledvia fieldbus or via I/O signals. It is not possible to use both sources to activesimultaneously. For this, the factory setting assigns the “I/O interface” signal to thethird binary input:
Not live (= 0 V) means that control is made from REMOTE via fieldbus.
Live (= 24 V) means that control is made from REMOTE via binary I/O interface.
Commands for the oper-ation function
OPEN/CLOSE operation commands can be issued via fieldbus or a setpoint can besent for any position:
● Setpoint control:Command bit Fieldbus SETPOINT = 1 = Remote SETPOINTThe actuator reacts to the setpoint E1 transmitted via the fieldbus.
● OPEN/CLOSE control:Command bit Fieldbus SETPOINT = 0 = Remote OPEN-CLOSEactuator can be operated via command bits in Fieldbus OPEN/Fieldbus CLOSEin direction OPEN or CLOSE.
EMERGENCY operation: ● An EMERGENCY operation is initiated by the Fieldbus EMERGENCY commandbit.
● The actuator moves to a predefined EMERGENCY position (i.e. end positionOPEN or end position CLOSED).
● During EMERGENCY operation, the actuator does not react to other operationcommands such as Fieldbus/OPEN/Fieldbus/CLOSE or Fieldbus SETPOINT.
38
PF-Q80 – PF-Q600Operation Profibus DP
9. FOX-EYE indication light and status indication
Figure 25: FOX-EYE LED colours
[1] FOX-EYE indication light[2] Position indicator
FOX-EYE indication light
Various profiles can be selected for the FOX-EYE indication light. Depending on theprofile, colours and states of the indication light provide a different signal.
Use the following menu for active profile setting:
Device configuration M0053Indication M2269Internal control unit M2684Configuration FOX-EYE M2685
The following profiles can be selected by means of the AUMA Assistant App or AUMACDT:
Default value: CUSTOMERSetting values: CUSTOMER, AUMA, NAMUR, FLEXIBLE
Information The “Flexible” profile allows setting of colours and states of the signals as required.Also refer to the table at the end of the section.
Table 18: Customer profileDescriptionSignalColour/state
The actuator:● is in operation mode REMOTE.● is ready for operation.● is not in any end position.
Ready for opera-tion (REMOTE)
Illuminated in white
The actuator is connected via Bluetooth.Bluetooth activeIlluminated in blue
The actuator is in end position CLOSED.End positionCLOSED
illuminated in red
The actuator is in end position OPEN.End positionOPEN
illuminated in green
The actuator:● is in operation mode LOCAL or OFF.● is ready for operation.● is not in any end position.
Ready for opera-tion (LOC-AL/OFF)
blinking in white(double flash)
The Bluetooth interface is provisionally activated.Safety function: refer to Manual Operation & Setting PROFOX.
Bluetooth inter-face ready for re-ception
blinking in blue
The actuator runs in direction CLOSE.Operation in direc-tion CLOSE
blinking in red
Refer to Corrective action chapter.Faultflashing in red (fast)
The actuator runs in direction OPEN.Operation in direc-tion OPEN
blinking in green
39
PF-Q80 – PF-Q600 Profibus DP FOX-EYE indication light and status indication
Table 19: AUMA profileDescriptionSignalColour/state
The actuator:● is in operation mode REMOTE.● is ready for operation.● is not in any end position.
Ready for opera-tion (REMOTE)
Illuminated in white
The actuator is connected via Bluetooth.Bluetooth activeIlluminated in blue
The actuator:● is in operation mode LOCAL or OFF.● is ready for operation.● is not in any end position.
Ready for opera-tion (LOC-AL/OFF)
blinking in white(double flash)
The Bluetooth interface is provisionally activated.Safety function: refer to Manual Operation & Setting PROFOX.
Bluetooth inter-face ready for re-ception
blinking in blue
Refer to Corrective action chapter.Faultflashing in red (fast)
Refer to Corrective action chapter.Warningblinking in red(double flash)
Table 20: NAMUR profileDescriptionSignalColour/state
The actuator is connected via Bluetooth.Bluetooth activeIlluminated in blue
Refer to Corrective action chapter.Failureilluminated in red
The actuator:● is in operation mode REMOTE.● is ready for operation.● is not in any end position.
Ready for opera-tion (REMOTE)
illuminated in green
The Bluetooth interface is provisionally activated.Safety function: refer to Manual Operation & Setting PROFOX.
Bluetooth inter-face ready for re-ception
blinking in blue
Refer to Corrective action chapter.Function checkorOut of specifica-tion
blinking in red
Maintenance is required.Maintenance re-quired
blinking in green
Table 21: Flexible profile: Default values and optionsOptionsDefault valueSignal
illuminated in greenIlluminated inwhite
Ready for operation(REMOTE)
blinking in redblinking in red (double flash)blinking in orange
blinking in white(double flash)
Ready for operation(LOCAL/OFF)
—Illuminated in blueBluetooth active
—blinking in blueBluetooth interfaceready for reception
illuminated in redilluminated in greenilluminated in magenta
illuminated in or-ange
End positionCLOSED
illuminated in orangeilluminated in redilluminated in magenta
illuminated ingreen
End position OPEN
blinking in redblinking in greenblinking in magenta
blinking in orangeOperation in direc-tion CLOSE
40
PF-Q80 – PF-Q600FOX-EYE indication light and status indication Profibus DP
OptionsDefault valueSignal
blinking in orangeblinking in redblinking in magenta
blinking in greenOperation in direc-tion OPEN
illuminated in redflashing in red(fast)
Fault
blinking in redblinking in orange
blinking in red(double flash)
Warning
Position indicator
Mechanical position indicator:
● Independent of power supply● continuously indicates the valve position● indicates whether the actuator is moving (running indication)● indicates that end positions have been reached
First, perform the position indicator setting to match the valve!
Refer to the Commissioning chapter.
Table 22: Position indicatorDescriptionSignificationColour/state
The actuator is in end position CLOSED.CLOSEDcompletely red
The actuator is in end position OPEN.OPENcompletely green
The actuator is not in any of the end positions.Intermediate posi-tion
red/green
41
PF-Q80 – PF-Q600 Profibus DP FOX-EYE indication light and status indication
10. Corrective actions
10.1. Faults during commissioning
Table 23:Faults during operation/commissioning
RemedyDescription/causeFaults
Modify operating time.Operating time setting is incorrect.Actuator operation is either too fastor to slow.
Set speed reduction and/or adapt parameter.Speed reduction switched off or incorrectly set be-fore reaching end positions.
Actuator suddenly stops in end posi-tions.
Advance electronic end position switch by theoverrun margin or adapt the parameters to an ex-tended speed reduction curve in the “Speedred.pr.end pos.” [speed reduction prior to end pos-ition] section.
Overrun due to excessive speed.Actuator exceeds the end position.
Adapt the speed reduction prior to setpoint positionparameters to an extended speed reduction curvein the positioner menu or adjust optimally theparameters for the positioner.
Overrun due to excessive speed.Actuator repeatedly corrects the set-point position during positioning.
10.2. Fault indications
Faults interrupt or prevent the electrical actuator operation. If a fault occurs, theFOX-EYE indication light is quickly flashing in red.
Warnings have no influence on the electrical actuator operation. They only servefor information purposes. The FOX-EYE remains white.
Collective signals include further indications. The FOX-EYE remains white.
Faults and warnings may exclusively be read via AUMA Assistant App or AUMACDT software.
Table 24:Faults and Failure
RemedyDescription/causeDisplay (App or CDT)
Perform one of the following measures:● Issue an operation command in direction OPEN
either via push buttons or AUMA Assistant App.● Reset the fault signal either via AUMA Assistant
App or AUMA CDT software “Diagnostics”menu.
● Execute reset command via fieldbus.
The actuator has reached the preset tripping torquein direction CLOSE.
Torque fault CLOSE
Perform one of the following measures:● Issue an operation command in direction
CLOSE either via push buttons or AUMA Assist-ant App.
● Reset the fault signal either via AUMA AssistantApp or AUMA CDT software “Diagnostics”menu.
● Execute reset command via fieldbus.
The actuator has reached the preset tripping torquein direction OPEN.
Torque fault OPEN
The fault can be configured for both types of beha-viour1. Fault reset must be performed manually.2. The fault is automatically reset once the motor
temperature falls below the maximum permiss-ible value.
For explosion-proof actuators, only the second typeof behaviour is permissible.
The motor exceeds the maximum permissible tem-perature.
Thermal fault
Check the Rot. dir. motor parameter whether it issuitable for the gearbox. The fault may only occurafter modification of the actuator/gearbox.
The actual direction of rotation does not match thecontrols’ direction of rotation.
Incorrect rotary direct.
42
PF-Q80 – PF-Q600Corrective actions Profibus DP
Faults and Failure
RemedyDescription/causeDisplay (App or CDT)
Check movement at actuator.No actuator reaction to operation commands withinthe set reaction time.
Fault no reaction
Use AUMA Assistant App or AUMA CDT to visualisethe individual signals by means of the Diagnosticsmenu.If a memory overflow occurs, reboot the actuator.Otherwise, please contact the AUMA Service.
Collective signal 14:Internal error has occurred.Different causes can be the reason: Memory over-flow in firmware, firmware error, electronic sub-as-sembly defective.
Internal error
Use AUMA Assistant App or AUMA CDT to visualisethe individual signals by means of the Diagnosticsmenu.Check the applicable configuration parameters.Contact AUMA service if appropriate.
Collective signal 11:A configuration fault has occurred preventing actu-ator operation.
Configuration error
Use AUMA Assistant App or AUMA CDT to visualisethe individual signals by means of the Diagnosticsmenu.Check the configuration parameters for the sub-as-sembly.In case the problem persists: Contact AUMA Ser-vice.
Collective signal 22:Configuration error has occurred.The additional fieldbus or I/O board fails either dueto incorrectly set configuration parameters or causedby defective hardware.
Config. error REMOTE
Contact AUMA service.Collective signal 28:Hardware or software faults of motor or motor con-trols
Fault motor controls
43
PF-Q80 – PF-Q600 Profibus DP Corrective actions
11. Servicing and maintenance
Damage caused by inappropriate maintenance!
→ Servicing and maintenance must be carried out exclusively by suitably qualifiedpersonnel having been authorised by the end user or the contractor of the plant.We recommend contacting our service for any interventions.
→ Only perform servicing and maintenance tasks when the device is switched off.
AUMAService & Support
AUMA offers extensive service such as servicing and maintenance as well ascustomer product training. For the contact addresses, refer to our website(www.auma.com).
The following actions are at least required to ensure safe device function duringoperation:
Enclosure protection IP68
After submersion:
● Check actuator.● In case of ingress of water, locate leaks and repair. Dry device correctly and
check for proper function.
6 months after commissioning and then once a year
● Carry out visual inspection:Cable entries, cable glands, blanking plugs, etc. have to be checked for correcttightness and sealing. If required, tighten cable glands and blanking plugs withtorque in compliance with the manufacturer's specifications.
● Check fastening screws between actuator and gearbox/valve for tightness. Ifrequired, fasten screws while applying the tightening torques as indicated inchapter <Assembly>.
● When rarely operated: Perform test run.
Seals
Preventive actions to ensure the IP protection degree.The seals of seal kit S1 shouldbe replaced within a period of 4 – 8 years:
After 4 years: In case of outdoor installation (frequent changes of temperature andhumidity, extreme weathers)
After 8 years: In case of indoor installation (constant or virtually constantenvironmental conditions)
If original AUMA screw plugs are used, original AUMA seals must also be used.They are included with the AUMA seal kit S1.The seal kit can be ordered with AUMA.
Lubrication
● Within the device lifetime, no additional lubrication of the gear housing is requiredduring operation.
Lifetime
The maximum lifetime depends on the number of operating cycles or the number ofstarts (refer to technical data) as well as the respectively applicable AUMA loadprofiles. Distinction is made between actuators in open-close or modulating duty:
Open-close duty(OPEN/CLOSE)
The load is measured by means of the number of operating cycles at a defined torquecharacteristics, the AUMA load profile.
An operating cycle corresponds to an angular stroke of 90° in both directions (e.g.OPEN - CLOSE - OPEN).
AUMA load profile:
10 % of the travel at 100 % of maximum torque.
44
PF-Q80 – PF-Q600Servicing and maintenance Profibus DP
90 % of the travel at 35 % of maximum torque.
Modulating duty The load is measured by means of the switching frequency, e.g. the number ofstarts/hour at a defined torque, the AUMA load profile.
One start corresponds to a movement of 1° in both directions.
AUMA load profile:
35 % of maximum actuator torque.
DeterminationKey figures
Operating cycles and number of starts for PROFOX actuators can be determinedusing the AUMA CDT software.
Operating cycles
The number of operating cycles can be further determined using the AUMA CDTsoftware and the AUMA Cloud. For this, create an actuator snapshot and upload itto the AUMA Cloud. The AUMA Cloud menu “My devices” indicates the value for“Number of Full Stroke Equivalent” for the actuator.
Number of starts
The number of starts in indicated in starts/h.The exact sum of this key figure is madein the actuator and can be read via AUMA Assistant App or the AUMA CDT softwarein “Operational info”.
AUMA recommendationWe recommend contacting the AUMA Service for an inspection of the actuator if oneof the following conditions is reached:
● The actuator life is more than 12 years● The maximum number of operating cycles has been reached at a lower load
profile than specified by AUMA (for open-close duty).● The maximum number of starts has been reached at a lower load profile than
specified by AUMA (for modulating duty).
An inspection by the AUMA Service can also be carried out using digital snapshotsfrom the AUMA Assistant App or the AUMA CDT software.
Mechanical position indicator
Both indicator glass and screw plug of mechanical position indicator are made ofplastic. To ensure enclosure protection and a long lifetime, both components mustbe fastened at a defined torque:
Indicator glass cover: 6 Nm (special tool art. no. V004.027-02, available with AUMA)
Screw plug: 1.6 Nm
45
PF-Q80 – PF-Q600 Profibus DP Servicing and maintenance
12. Disposal and recyclingOur devices have a long lifetime. However, they have to be replaced at one point intime. The devices have a modular design and may, therefore, easily be separatedand sorted according to materials used, i.e.:
● Electronic scrap● Various metals● Plastic materials● Greases and oilsThe following generally applies:
● Greases and oils are hazardous to water and must not be released into theenvironment.
● Arrange for controlled waste disposal of the disassembled material or for sep-arate recycling according to materials.
● Observe the national regulations for waste disposal.
46
PF-Q80 – PF-Q600Disposal and recycling Profibus DP
13. Technical data
Information The following tables include standard and optional features. For detailed informationon the customer-specific version, refer to the order-related data sheet.The technicaldata sheet can be downloaded from the Internet in both German and English at ht-tp://www.auma.com (please state the order number).
13.1. Technical data Part-turn actuator with integral controls for open-close and modulating duty
Features and functions
Classes A and B according to EN 15714-2, short-time duty S2 - 15 minOpen-closeduty:
Type of duty
Class C according to EN 15714-2, intermittent duty S4 - 50 %, with maximum number of1,200 starts/h
Modulatingduty:
For nominal voltage and +40 °C ambient temperature and at load with 35 % of the maximum torque.The type of duty must not be exceeded.
Variable speed, brushless motorMotor
F, tropicalizedInsulation class
Via calculated temperature valueMotor protection
Yes, at standstill with spring-applied brakeSelf-locking
90° ±15° adjustable between min. and max. values (with mechanical end stops)Standard:Swing angle
120° ±15° adjustable between min. and max. values (with mechanical end stops)Option:
45° – 360° adjustable between min. and max. values (without mechanical end stops)
Via hall sensorsLimit switching
Via electronic current measurement. Tripping torques adjustable in 8 stepsTorque switching
Continuous indication, for 90° or 120°Via own markings at indication 45° – 360°
Standard:Mechanical position indicator
Without mechanical position indicatorOption:
Manual drive for setting and emergency operation, handwheel does not rotate duringelectrical operation
Standard:Manual operationPF-Q80 – PF-Q600
Without manual operation, this means handwheel and handwheel shaft are obsolete.Theend stops are included except version with swing angle 45° – 360°.
Option:
Coupling unboredStandard:Coupling
● Coupling unbored extended● Finish machining of coupling (standard or extended)
- Bore according to EN ISO 5211 with 1 keyway according to DIN 6885-1- Square bore according to EN ISO 5211- Two-flat according to EN ISO 5211
Options:
Dimensions according to EN ISO 5211Valve attachment
Features and functions
Standard voltages:1-phase AC current:100 – 240 V / 50 – 60 HzThe voltage range may be exceeded or undercut by max. 10 %The frequency range may be exceeded or undercut by max. 5 %Option:DC current: 24 V DC ±10 %For current consumption, refer to Electrical data PROFOX Part-turn actuators
Power supply
Category III according to IEC 60364-4-443Overvoltage category
With integral motor controller (current consumption in standby mode < 3 W)Power electronics
Access to parameters, the electronic name plate and the operating and diagnostic services with acyclicwrite/read servicesGalvanically isolated towards I/O interfaces.
Profibus DP-V1 (option)
Operation commands and setpoint via fieldbus interfaceControl fieldbus(input signals)
47
PF-Q80 – PF-Q600 Profibus DP Technical data
Features and functions
Via Profibus DP interfaceStatus signals fieldbus(output signals)
● Via opto-isolator, with one common● Control voltage 24 V DC, current consumption: approx. 15 mA per input● Minimum pulse duration for shortest operation pulse: 100 ms● All digital inputs must be supplied with the same potential.● All inputs can be configured as required● Standard assignment:
OPEN, CLOSE, I/O interfaceI/O interface: Selection of control source (fieldbus interface or I/O input signals).Factory setting of “I/O Interface” signal: Input signal 0 V = fieldbus interface is active
3 digital in-puts:
I/O control(input signals)
● 0/4 – 20 mA or 0 – 10 V● No galvanic isolation● Used as input for the position setpoint (then, definition is made via 2 binary inputs
which command source is active for the positioning: fieldbus or analogue input) or fora sensor signal which can be further transmitted via fieldbus.
Analogue in-put(option)
● Freely configurable semi-conductor output contacts, per contact max. 24 V DC, 100 mA(resistive load)
● Outputs can be configured as required● Standard assignment:
End position CLOSED (high active), end position OPEN (high active), collective faultsignal (low active)
3 digital out-puts:
Status signals via I/O(Input signals)
● Position feedback signal 0/4 – 20 mA (load maximum 500 Ω) or 0 – 10 V● No galvanic isolation
Analogueoutput:
Auxiliary voltage 24 V DC, max. 80 mA for supply of control inputs, without galvanic isolation.Voltage output (option)
● Switch-off mode adjustable:Limit or torque seating for end positions OPEN and CLOSED
● Torque monitoring across the whole travel● Torque by-pass● Programmable EMERGENCY behaviour
- Digital input low active,- Reaction can be selected: Stop, run to end position CLOSED, run to end position
OPEN
● Speed control- Ramps- Program operation profiles- Programming specific speed for OPEN and CLOSE operations or one digital input
● Positioner- Automatic adaptation of dead band (adaptive behaviour selectable)
Standard:Functions
Bluetooth class II chip, with a range of min. 3 m in industrial environments.Required accessories:● AUMA CDT (Commissioning and Diagnostic Tool for Windows-based PC)● AUMA Assistant App (Commissioning and Diagnostic Tool for Android and iOS devices)
BluetoothCommunication interface
Cable entry: 3 x M20x1.5 threads for cable glands.Inside rail with spring clamp terminals for wire connection.
Electrical connection
Refer to name plateWiring diagram (basic version)
Setting/programming the Profibus DP interface
Automatic baud rate recognitionBaud rate setting
The setting of the Profibus DP address is made via parameters using the AUMA Software CDT or AUMAAssistant App.
Setting the Profibus DP interface
48
PF-Q80 – PF-Q600Technical data Profibus DP
General Profibus DP interface data
Profibus DP according to IEC 61158 and IEC 61784-1Communication protocol
● Line (fieldbus) structure.● When using repeaters, tree structures can also be implemented● Coupling and uncoupling of devices during operation without affecting other devices is possible
Network topology
Twisted, screened copper cable according to IEC 61158Transmission medium
EIA-485 (RS485)Fieldbus interface
● Baud rate and maximum cable length (segment length) without repeater:- between 9.6 and 93.75 kbit/s: 1,200 m- for 187.5 kbit/s: 1,000 m- for 500 kbit/s: 400 m- for 1,500 kbit/s: 200 m
● Baud rate and possible cable length with repeater (total network cable length):- between 9.6 and 93.75 kbit/s: approx. 10 km- for 187.5 kbit/s: approx. 10 km- for 500 kbit/s: approx. 4 km- for 1,500 kbit/s: approx. 2 km
Transmission rate/cable length
● DP master class 1, e.g. central controllers such as PLC, PC,.● DP master class 2, e.g. parts programming/configuration tools● DP slave, e.g. devices with digital and/or analogue inputs/outputs such as actuators, sensors
Device type
32 devices without repeater, with repeater expandable to 126Number of devices
● Token-passing between masters and polling for slaves● Mono-master or multi-master systems are possible.
Bus access
Cyclic data exchange, sync mode, freeze mode, fail safe modeSupported fieldbus functions
0x1146. Standard applications with Profibus DP-V0 and DP-V1Profibus DP ident no.
Commands and signals of the Profibus DP interface
OPEN, STOP, CLOSE, position setpoint, RESET, EMERGENCY operation commandProcess representation output(command signals)
● End positions OPEN, CLOSED● Actual position value● Selector in position LOCAL/REMOTE/OFF● Torque switches OPEN, CLOSED● Limit switches OPEN, CLOSE
Process representation input(feedback signals)
● Torque switch tripped in mid-travelProcess representation input(fault signal)
The behaviour of the actuator is programmable:● Stop at current position● Execute operation to end positions OPEN and CLOSED● Travel to any intermediate position● Execute last received operation command
Behaviour on loss of communication
49
PF-Q80 – PF-Q600 Profibus DP Technical data
Operation and Display
FOX-EYE (indication LED)Status indications: OK, end positions, faults and “Bluetooth connection active”
Status indica-tion
Basicat the actuator
4 buttons and 1 LED are located below the hood.Run actuator in directions OPEN and CLOSE. Set end position once mounted to the valve.
End positionsetting
Run actuator in directions OPEN and CLOSE. Set end position once mounted to the valve.End positionsetting
Smartvia Bluetooth using AUMA AssistantApp or AUMA CDT software
● Rotation speed● Type of seating for end positions,
torque switching● Assignment of signal inputs and outputs● Fieldbus parameter (if fieldbus option has been selected)
Basic settings for opera-tion:
Configura-tion
For applications, safety and service, e.g.:● Positioner● EMERGENCY behaviour● Torque by-pass● Failure behaviour● Signal configuration
Additional functions:
Monitoring key figures and measured values for preventive maintenance and consequentlyincreasing process safety. Limit values can be set. Deviations generate warning signalswhich can be transmitted to the DCS via binary outputs or fieldbus.
Diagnostics
Temperature value within actuatorKey figures regarding lifetime of electronics, brake, gearboxand seals.
Actuator:
Method for identifying changes in torque requirement: Performreference operation and save torque as reference profile. Definetolerance range. Perform comparison operation if required.Values outside tolerance initiate a signal which is communicatedas described above.
Actuator and valve:
Furthermore, the actuator monitors and records further figuresand conditions. The generated fault and warning signals aresaved within the event log. These signals can be configuredas requested. An overview in the AUMA Assistant App or theCDT software shows all available fault/warning signals withoption to enter the details.
Further key figures:
Service conditions
Any positionMounting position
≤ 2,000 m above sea level> 2 000 m above sea level on request
Installation altitude
–30 °C to +70 °CAmbient temperature
Up to 100 % relative humidity across the entire permissible temperature rangeHumidity
IP67StandardEnclosure protection in accordancewith IEC 60529
According to AUMA definition, enclosure protection IP68 meets the following requirements:● Depth of water: maximum 8 m head of water● Continuous immersion in water: maximal 96 hours● Up to 10 operations during immersion● Modulating duty is not possible during immersion
Option:
Pollution degree 4 (when closed), pollution degree 2 (internal)Pollution degree according toIEC 60664-1
2 g, from 10 Hz to 200 HzResistant to vibration during start-up or for failures of the plant. However, a fatigue strength may not bederived from this. Not valid in combination with gearboxes.
Vibration resistance according toIEC 60068-2-6
Test proof for application class 3Seismic resistance according toIEC 60068-3-3
50
PF-Q80 – PF-Q600Technical data Profibus DP
Service conditions
KSSuitable for use in areas with high salinity, almost permanent condensation, and highpollution.
Standard:Corrosion protection
KXSuitable for use in areas with extremely high salinity, permanent condensation, and highpollution.
Option:
Double layer powder coatingTwo-component iron-mica combination
Coating
AUMA silver-grey (similar to RAL 7037)Standard:Colour
Available colours on requestOption:
10,000 operating cycles OPEN - CLOSE - OPENAn operating cycle is based on an operation from CLOSED to OPEN and back to CLOSED,at a respective rotary movement of 90°.
Open-closeduty:
Lifetime
1.8 million modulating stepsModulatingduty:
The lifetime depends on the load and the number of starts. A high starting frequency will rarely improvethe modulating accuracy. To reach the longest possible maintenance and fault-free operating time, thenumber of starts per hour chosen should be as low as permissible for the process.
Further information
Machinery Directive 2006/42/ECLow Voltage Directive 2014/35/EUEMC Directive 2014/30/EURoHS Directive 2011/65/EU
EU Directives
51
PF-Q80 – PF-Q600 Profibus DP Technical data
14. Spare parts
14.1. Part-turn actuators PF-Q80 – PF-Q600
52
PF-Q80 – PF-Q600Spare parts Profibus DP
Please state device type and our order number (see name plate) when ordering spare parts. Only original AUMA spare parts should be used.Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Only the designated spare parts with referencenumbers or spare parts sets for replacement are available for the customer. The are specified in the following list. The parts shown in theexploded view without reference numbers may only be replaced by AUMA. Representation of spare parts may slightly vary from actual delivery.
TypeDesignationRef. no.
Power supply unit006.0
Coupling525.0
Sub-assemblyProtective earth connection541.0
Sub-assemblyHandwheel with ball handle542.0
Sub-assemblyBall handle542.1
Sub-assemblyMechanical position indicator1)553.0
Sub-assemblyScrew plug M40553.1
Sub-assemblyScrew plug for end stop612.0
I/O board as option658.0
Sub-assemblyFieldbus boards (fieldbus and connection board)659.0
Sub-assemblyScrew plug for manual emergency operation2)663.0
Sub-assemblyScrew plug for cable gland663.0
Sub-assemblyInternal protective earth connection664.0
Sub-assemblyCover for electronics housing665.0
Sub-assemblyHandwheel bearing flange666.0
Sub-assemblyAuxiliary voltage output 24 V DC670.0
SetSeal kitS1
A special tool is required for disassembly/assembly of mechanical position indicator. This can be ordered from AUMA (parts number:V004.027-02).
1)
The manual emergency operation is only available for models PF-Q20 and PF-Q40, which are not equipped with a handwheel.2)
53
PF-Q80 – PF-Q600 Profibus DP Spare parts
Index
AAmbient temperature 8App functions 36Applications 4Assembly 11Assistant App 9AUMA Assistant App 7, 9AUMA Cloud 7
BBlanking plug 16Bluetooth 7
CCable connection 17, 20Cable glands 16Cable path 17Cables 16CDT 7Commands and signals of theProfibus DP interface
49
Commissioning 4, 24Connecting cables 16Control inputs Potential 15Corrective actions 42Corrosion protection 10Coupling 11, 12Cross section (fieldbus cable) 16Current type 15
DData Matrix code 9Directives 4Disposal 46
EEarth connection 23Electrical connection 15EMC 16EMERGENCY operation 38End position CLOSED 27End position OPEN 28End position setting 26End stops 24
FFault 42Features and functions 47, 48Fieldbus cable 16Fieldbus cables 20Flange size 9FOX-EYE 39Further information 51Fuse 15
GGeneral Profibus DP interfacedata
49
GSD file 34
HHandwheel 11
IIndication lights 39Input signals Potential 15Inspection certificate 9
LLEDs (indication lights) 39Lubrication 44
MMains cable 17Mains connection 15Mains frequency 8, 15Mains voltage 8, 15Maintenance 4, 44, 44Maintenance intervals 44Manual operation 35Mechanical position indicator 29, 39Motor operation 35
NName plate 8, 15
OOpen terminal compartment 17Operating time 8, 32Operation 4, 35Operation and Display 50Order number 8, 9Output signals Potential 15
PPassword 37PE connection 17Position indication 120° 30Position indication 45°– 360° 31Position indication 90° 30Position indicator 29Power supply 17Protective measures 4Push buttons 35
QQualification of staff 4
RRange of application 4Rated current 8Rated power 8Recycling 46reductions 16Remote 37Remote operation 37Running indication 39
54
PF-Q80 – PF-Q600Index Profibus DP
SSafety instructions 4Safety instructions/warnings 4Safety measures 15Safety standards 15Screening (fieldbus cable) 16Screw plugs 16Serial number 8, 9Service 44Service conditions 51Setting/programming theProfibus DP interface
48
Short description 6Signal cable 17Size 9Spare parts 52Speed 32Speeds 32Standards 4Status signals Potential 15Storage 10Supply networks 15Support 44Swing angle 8
TTechnical data 47Terminal compartment: close 22Terminal plan 15Termination resistance 20Torque range 8Transport 10Type 9Type designation 8Type of current 8Type of duty 8Type of networks 15
UUser 37User level 37
WWire diameter (fieldbus cable) 16Wiring diagram 8, 9, 15
YYear of manufacture 9Year of production 9
55
PF-Q80 – PF-Q600 Profibus DP Index
AUMA Riester GmbH & Co. KG
P.O. Box 1362DE 79373 MuellheimTel +49 7631 809 - 0Fax +49 7631 809 - 1250info@auma.comwww.auma.com
Y009.946/003/en/1.21
For detailed information on AUMA products, refer to the Internet: www.auma.com