Muon Annul ReviewCern 15 September 2003 RPC cabling
RPC cabling
RPC cablingRPC cabling
• HV & LV cables
• Signal cables
• Position and composition of racks in UXC and USC
PaolucciINFN-Napoli
PaolucciINFN-NapoliMuon Annul Review
Cern 15 September 2003
Muon Annul ReviewCern 15 September 2003 RPC cabling
RPC cabling
HV cable layout (from UXC55 vs USC55)HV cable layout (from UXC55 vs USC55)
Conductor @ 15 KV(DC)with individual insulating sheath
Braided shield
Signal return
Required characteristicCERN safety instruction IS23:•Flame retardant (IEC 60332-3 Cat. C)•Zero halogene (IEC 60754-1)•Smoke density (IEC 61034)•Corrosiveness of combustion gases (IEC 60754-1)•Maximum current per conductor: 500 uA•Maximum voltage per conductor: 15 KV-DC
External sheath
Internal sheath
PaolucciINFN-Napoli
PaolucciINFN-NapoliMuon Annul Review
Cern 15 September 2003
Muon Annul ReviewCern 15 September 2003 RPC cabling
RPC cabling
HV cables characteristicsHV cables characteristics
• Multiconductor cable 8 x (3x0.22) H2M1 Halogene Free 15 kV cc (from patch panels towards tower to patch panel on USC)– External diameter 26.2 mm (nominal)– Weight (indicative) 826 g/m
• Cable 1 x (3x0.22) H2M1 Halogene Free 15 kV cc (from detector towards patch panels on towers)– External diameter 7.7 mm (nominal)– Weight (indicative) 82 g/m
• Manufacturer: NOVACAVI
PaolucciINFN-Napoli
PaolucciINFN-NapoliMuon Annul Review
Cern 15 September 2003
Muon Annul ReviewCern 15 September 2003 RPC cabling
RPC cabling
LV cable characteristicsLV cable characteristics
• Cable 12 x 0.75 (RB2/3 case):– Braided shield: copper
– External diameter (nominal): 10.1 mm
– Weight (indicative): 175 g/m
• Cable 8 x 0.75 (RB2/2 case):– Braided shield: copper
– External diameter (nominal): 9.0 mm
– Weight (indicative): 156 g/m
• Manufacturer: NOVACAVI
PaolucciINFN-Napoli
PaolucciINFN-NapoliMuon Annul Review
Cern 15 September 2003
Muon Annul ReviewCern 15 September 2003 RPC cabling
RPC cabling
Signal cable characteristicsSignal cable characteristics
• 20 twisted pairs cable• Very low skew cable (1-2 ns between pairs for 25 m max length)• Conductor cross section: 28 AWG• Insulator: PE• Global shield: tinned copper braid• External shield: PE• Total external diameter: 12-13 mm• Rated voltage: 10 V (used for LVDS signal transmission)• Operating temperature: 0°/+60°C• Characteristic impedance: 110 (10%)• CERN safety instruction IS23 compliant:
– Flame retardant (IEC 60332-3 Cat. C)– Zero halogene (IEC 60754-1)– Smoke density (IEC 61034)– Corrosiveness of combustion gases (IEC 60754-1)
• Competitor manufacturers: Kabelwerk EUPEN - NOVACAVI
PaolucciINFN-Napoli
PaolucciINFN-NapoliMuon Annul Review
Cern 15 September 2003
Muon Annul ReviewCern 15 September 2003 RPC cabling
RPC cabling
Possible cabling layoutPossible cabling layout
Drawn by L. Roscilli
PaolucciINFN-Napoli
PaolucciINFN-NapoliMuon Annul Review
Cern 15 September 2003
Muon Annul ReviewCern 15 September 2003 RPC cabling
RPC cabling
Possible cabling layoutPossible cabling layout
Drawn by L. Roscilli
PaolucciINFN-Napoli
PaolucciINFN-NapoliMuon Annul Review
Cern 15 September 2003
Muon Annul ReviewCern 15 September 2003 RPC cabling
RPC cabling
Barrel RPC: sector cables (except sectors 4-9-10-11)
Barrel RPC: sector cables (except sectors 4-9-10-11)
RB2_OUT
RB2_IN
RB1_OUT
RB1_IN
RB3 RB3
RB4 RB4
6 LV 8 HV
To balconies
12
78 SGN6 DCS
To LBBOX
12
18 (12)
12 (18)
12
12
17p
17p
110p (17p)
17p
17p
Wheel 0, ±1 (Wheel ±2 )
18w
18w
112w (18w)
18w
18w
18w (112w) 17p (110p)
PaolucciINFN-Napoli
PaolucciINFN-NapoliMuon Annul Review
Cern 15 September 2003
Muon Annul ReviewCern 15 September 2003 RPC cabling
RPC cabling
Barrel RPC: sector cables (sector 4)Barrel RPC: sector cables (sector 4)
RB2_OUT
RB2_IN
RB1_OUT
RB1_IN
RB3 RB3
RB4
7 LV 10 HV
To balconies
12
90 SGN7 DCS
To LBBOX
12
18(12)
12(18)
12
RB4 RB4 RB4
Wheel 0, ±1 (Wheel ±2 )
17p
17p
110p (17p)
17p
17p
17p (110p)
17p
18w
18w
112w (18w)
18w
18w
18w (112w)
18w
12
12
PaolucciINFN-Napoli
PaolucciINFN-NapoliMuon Annul Review
Cern 15 September 2003
Muon Annul ReviewCern 15 September 2003 RPC cabling
RPC cabling
Barrel RPC: sector cables (sector 10)Barrel RPC: sector cables (sector 10)
RB2_OUT
RB2_IN
RB1_OUT
RB1_IN
RB3 RB3
RB4 RB4
7 LV 8 HV
To balconies
12
86 SGN7 DCS
To LBBOX
12
12
10
Wheel 0, ±1 (Wheel ±2 )
18w
18w
112w (18w)
18w
18w
18w (112w)
18w
18(12)
12(18)
17p
17p
110p (17p)
17p
17p
17p (110p)
17p
10
PaolucciINFN-Napoli
PaolucciINFN-NapoliMuon Annul Review
Cern 15 September 2003
Muon Annul ReviewCern 15 September 2003 RPC cabling
RPC cabling
Barrel RPC: sector cables (sectors 9-11)Barrel RPC: sector cables (sectors 9-11)
RB2_OUT
RB2_IN
RB1_OUT
RB1_IN
RB3 RB3
RB4
6 LV 7 HV
To balconies
12
72 SGN6 DCS
To LBBOX
12
12
6
Wheel 0, ±1 (Wheel ±2 )
18w
18w
112w (18w)
18w
18w
18w (112w)
18(12)
12(18)
17p
17p
110p (17p)
17p
17p
17p (110p)
PaolucciINFN-Napoli
PaolucciINFN-NapoliMuon Annul Review
Cern 15 September 2003
Muon Annul ReviewCern 15 September 2003 RPC cabling
RPC cabling
Numbers and lengthsNumbers and lengthsUpdated by F. Montecassiano
PaolucciINFN-Napoli
PaolucciINFN-NapoliMuon Annul Review
Cern 15 September 2003
Muon Annul ReviewCern 15 September 2003 RPC cabling
RPC cabling
Numbers and lengthsNumbers and lengthsUpdated by F. Montecassiano
PaolucciINFN-Napoli
PaolucciINFN-NapoliMuon Annul Review
Cern 15 September 2003
Muon Annul ReviewCern 15 September 2003 RPC cabling
RPC cabling
Cables length specification (Wheel 0/ Z-)Cables length specification (Wheel 0/ Z-)
updated by L. Roscilli
PaolucciINFN-Napoli
PaolucciINFN-NapoliMuon Annul Review
Cern 15 September 2003
Muon Annul ReviewCern 15 September 2003 RPC cabling
RPC cabling
Cables length specification (Wheel 0/ Z+)Cables length specification (Wheel 0/ Z+)
updated by L. Roscilli
PaolucciINFN-Napoli
PaolucciINFN-NapoliMuon Annul Review
Cern 15 September 2003
Muon Annul ReviewCern 15 September 2003 RPC cabling
RPC cabling
Rack composition in USCRack composition in USC
EASY4000
EASY3000
EASY4000
EASY3000
HV Patch Panel
1. SY1527:9 or 11 A1676 Branch Controllers
1. EASY crates2. HV modules (A3512):
7 modules/crate
Full Option:1020 HV channels
Chamber Option:480 HV channels
Station Option:360 HV channels
170 HV modules
25 EASY crates+ 1 SY1527 + 20 HV patch panel
80 HV modules
12 EASY crates+ 1 SY1527 + 20 HV patch panel
60 HV modules
9 EASY crates+ 1 SY1527 + 20 HV patch panel
+
PaolucciINFN-Napoli
PaolucciINFN-NapoliMuon Annul Review
Cern 15 September 2003
Muon Annul ReviewCern 15 September 2003 RPC cabling
RPC cabling
Rack position in USCRack position in USC
PaolucciINFN-Napoli
PaolucciINFN-NapoliMuon Annul Review
Cern 15 September 2003
Muon Annul ReviewCern 15 September 2003 RPC cabling
RPC cabling
Rack composition in UXCRack composition in UXC
Calculation per quadrant (Barrel)• 3 LV modules (A3003)/quadrant (6 EASY crate slots)• Current absorption calculations:
– 2 Lbboxes x 13 LBs = 26 LBs– 1 Lbbox x 15 LBs = 15 LBs– 41 LBs/quadrant– Current absorption: 14A/LB (estimation)– 14A x 41 LBs = 574 A/quadrant– We need 6 A3100 CAEN LV module (4 slots width each)– We need a total of 24 slots 1 + 1/5 EASY crates per
tower– This fit with the 2 x 6U crates foreseen for RPC.
PaolucciINFN-Napoli
PaolucciINFN-NapoliMuon Annul Review
Cern 15 September 2003
Muon Annul ReviewCern 15 September 2003 RPC cabling
RPC cabling
Rack composition in UXC towersRack composition in UXC towers
PaolucciINFN-Napoli
PaolucciINFN-NapoliMuon Annul Review
Cern 15 September 2003
Muon Annul ReviewCern 15 September 2003 RPC cabling
RPC cabling
ConclusionsConclusions
• We are ready for asking a cable PRR– we are just collecting all necessary documentations
• Before the end of this year we start tenders– this implies to know exactly total lengths
• Open issues:– Cable path (to be approved very soon)