2/12
central unit data sheet
NOX central
a) NOXCPU
NOXCPU main board with bus input from
power supply, MMC card slot, Ethernet RJ-
45 socket and three NOX bus outputs to
connect all other NOX Systems devices.
NOX data sheets, December 03, p 2 of 12
MMC slot
backupbattery
power in / bus 3
Etherne
bus 3
bus 2
bus 1
NOXPSU power supply
NOXCPU
NOXMIO
2x 17 Ah accumulators
7/28/2019 NOX E Datasheets
3/12
technical data:
min. nom. max.
supply voltage (VBUS) VDC 14.25 15.0 15.75
power consumption at 15 VDC mA ? ?
operating temperature range C 0 25 40
air humidity at +40C (non
condensing)
% rel. h 93
dimensions (L x B x H): mm 640 x 404 x 105
fuses (F1 to F4) 1A slow-blow order no.: 154.001T
maximum bus output current (bus 1to 3)
A 2.5
terminal assignment:
plugs description
terminal P1 MMC connector
terminal P2 RJ45 Ethernet connection
BAT1 Lithium battery CR2032S1 CPU reset button
terminal P7 + - A B
pin 15 5% VDC GND Bus A Bus B
description input from PSU device
terminal P3 + - A B
pin 15 5% VDC GND Bus A Bus B
description supply voltage (VBUS) bus connection
terminal P4 + - A Bpin 15 5% VDC GND Bus A Bus B
description supply voltage (VBUS) bus connection
terminal P6 + - A B
pin 15 5% VDCC
GND Bus A Bus B
description supply voltage (VBUS) bus connection
terminal P5 1 2 3
pin GND TX RX
description send receive
NOX data sheets, December 03, p 3 of 12
P5 for specialpurpose only!
7/28/2019 NOX E Datasheets
4/12
CPA data sheet
NOXCPA
The NOXCPA is the operating panel for the NOX alarmsystem with 128 x 64 pixels LCD graphic display, white
back light, integrated alarm buzzer, a numeric key padwith clear C and enter E keys and two scroll keyswith variable function.
technical data:
Min. Nom. Max.
supply voltage (VBUS) VDC 9.0 15.0 15.5
power consumption at 15 VDC mA 15 50
operating temperature range C 0 25 40
air humidity at +40C (non
condensing)
% rel. h 93
dimensions (L x B x H): mmon wall 175 x 110 x 24
in wall 212 x 148 x 23
protection class IP30
terminal assignment:
terminal P2 + - A B
pin 9-15.5 VDC GND Bus A Bus B
description supply voltage (VBUS) bus connection
NOX data sheets, December 03, p 4 of 12
7/28/2019 NOX E Datasheets
5/12
MIO data sheet
NOXMIO
NOXMIO is an input and output modulewith eight relay outputs plus four
resistance monitored inputs with driver forconnected flash lights or sirens. Althoughflexible in the programming, the outputsare often used to interface to alarmtransmission devices.
technical data:
min. nom. max.
supply voltage (VBUS) VDC 9.0 15.0 15.5power consumption 15 VDC mA 15 83
operating temperature C 0 25 40
air humidity at +40C (noncondensing)
% rel. h 93
input impedance range 1-4 k 3.5 12 50
electrical data relay 1-4 each contact max. 30VDC/1A
fuses (F1 to F4) 500mA slow-bloworder no.: 154.500T
dimensions (L x B): mm 47.5 x 65
terminal assignment:
terminal P2 + - A Bpin 9-15.5 VDC GND Bus A Bus B
description supply voltage (VBUS) bus connection
terminal P3 1 2 3 4 5 6
pin VBUS Input 1 O.C. (1) VBUS Input 2 O.C. (1)
description input 1 input 2
7 8 9 10 11 12
pin VBUS Input 3 O.C. (1) VBUS Input 4 O.C. (1)
description input 3 input 4
terminal P4 1 2 3 4 5 6
pin NO (2) COM (3) NC (4) NO (2) COM (3) NC (4)
description relay 1 relay 2
7 8 9 10 11 12
pin NO (2) COM (3) NC (4) NO (2) COM (3) NC (4)
description relay 3 relay 4
terminal P5 1 2 3 4 5 6
pin NO (2) COM (3) NC (4) NO (2) COM (3) NC (4)
description relay 5 relay 6
7 8 9 10 11 12
pin NO (2) COM (3) NC (4) NO (2) COM (3) NC (4)
description relay 7 relay 8
O.C.: open collector, NO: normally open, COM: common, 4 NC: normally closed
NOX data sheets, December 03, p 5 of 12
7/28/2019 NOX E Datasheets
6/12
IN4 data sheet
NOXIN4
NOXIN4 is a universal input module connectable to the NOXalarm bus with four resistance monitored inputs.
technical data:
min. nom. max.
supply voltage (VBUS) VDC 9.0 15.0 15.5power consumption 15 VDC mA 12 16
operating temperature C 0 25 40
air humidity at +40C (noncondensing)
% rel. h 93
input impedance range 1-4 k 3.5 12 50
dimensions (L x B x H): mm 85 x 66 x 27
protection class IP30
terminal assignment:
terminal P2 + - A B
pin 9-15.5 VDC GND Bus A Bus Bdescription supply voltage (VBUS) bus connection
terminal P3 1 2 3 4 5 6
pin VBUS Input 1 GND VBUS Input 2 GND
description input 1 input 2
7 8 9 10 11 12
pin VBUS Input 3 GND VBUS Input 4 GND
description input 3 input 4
NOX data sheets, December 03, p 6 of 12
7/28/2019 NOX E Datasheets
7/12
RE4 data sheet
b) NOXRE4
The NOXRE4 offers four programmable relay outputs totransmit alarms or the status of detector groups to supervising
systems.
technical data:
Min. Nom. Max.supply voltage (VBUS) VDC 9.0 15.0 15.5
power consumption at 15 VDC mA 12 30
operating temperature range C 0 25 40
air humidity at +40C (noncondensing)
% rel. h 93
electrical data relay 1-4 each contact max. 30 VDC/1A
dimensions (L x B x H): mm 85 x 66 x 27
protection class IP30
terminal assignment:
terminal P2 + - A Bpin 9-15.5 VDC GND Bus A Bus B
description supply voltage (VBUS) bus connection
terminal P3 1 2 3 4 5 6
pin NO (1) COM (2) NC (3) NO (1) COM (2) NC (3)
description relay 1 relay 2
7 8 9 10 11 12
pin NO (1) COM (2) NC (3) NO (1) COM (2) NC (3)
description relay 3 relay 4
1 NO: normally open, 2 COM: common, 3 NC: normally closed
NOX data sheets, December 03, p 7 of 12
7/28/2019 NOX E Datasheets
8/12
CRD data sheet
NOXCRD with Wiegand 26 Bit interface
The NOXCRD is a universal input/output module connected tothe NOX alarm bus with one resistance monitored input, one
relay output and a card reader port with Wiegand 26 Bitinterface.
technical data:
min. nom. max.
supply voltage (VBUS) VDC 9.0 15.0 15.5power consumption at 15 VDC mA 12 18
operating temperature range C 0 25 40
air humidity at +40C % rel. h 93
input impedance range (noncondensing)
k 3.5 12 50
electrical data relay max. 30VDC/1A
dimensions (L x B x H): mm 85 x 66 x 27
protection class IP30
terminal assignment:
terminal P2 + - A Bpin 9-15.5 VDC GND Bus A Bus B
description supply voltage (VBUS) bus connection
terminal P3 1 2 3 4 5 6
pin VBUS Input GND 5 VDC GND LED 1
description input card reader
7 8 9 10 11 12
pin LED 2 Data 0 Data 1 NO (1) COM (2) NC (3)
description card reader relay
1 NO: normally open, 2 COM: common, 3 NC: normally closed
NOX data sheets, December 03, p 8 of 12
7/28/2019 NOX E Datasheets
9/12
RPT data sheet
NOXRPT
The NOXRPT is a universal module configurable as repeater(RS485) or as serial gateway (RS232) to connect a personal
computer to the NOX alarm bus.
technical data:
min. nom. max.
supply voltage (VBUS) VDC 9.0 15.0 15.5power consumption at 15 VDC mA 13 14
operating temperature range C 0 25 40
air humidity at +40C (noncondensing)
% rel. h 93
dimensions (L x B x H) mm 85 x 66 x 27
protection class IP30
terminal assignment:
terminal P1 1 2 3 4
pin 5 VDC GND RX TX
description reserve serial interface (RS232)
terminal P2 + - A B
pin 9-15.5 VDC GND Bus 1 A Bus 1 B
description supply voltage 1 (VBUS1) bus 1 - input
terminal P3 + - A B
pin 9-15.5 VDC GND Bus 2 A Bus 2 B
description supply voltage 2 (VBUS2) bus 2 - output
jumper assignment:
JP1 1-2 2-3 JP2 ON OFF
function repeater serialinterface
function VBUS1=VBUS2
VBUS2external
output Bus 2output
RS232
NOX data sheets, December 03, p 9 of 12
7/28/2019 NOX E Datasheets
10/12
THS data sheet
NOXTHS
The NOXTHS module connects an internal or externalcombined sensor for temperature and humidity to the NOxbus.
The module contains a freely programmable relay outputon the board.
This device is not approved by the SVV.
technical data:
min. nom. max.
supply voltage (VBUS) VDC 9.0 15.0 15.5
power consumption at 15 VDC mA 12 14
operating temperature range C 0 25 40
air humidity at +40C % rel. h 93
electrical data relay max. 30VDC / 1A
dimensions (L x B x H) mm 85 x 66 x 27
protection class IP30
terminal assignment:
terminal P2 + - A B
pin 9 - 15.5VDC GND Bus A Bus B
description supply voltage (VBUS) bus connection
terminal P3 1 2 3 4 5 6
pinX X X Sensor
5VGND Data1
description X= not used Sensor
7 8 9 10 11 12
pin Data2 X X NO (1) COM (2) NC (3)
description Sensor X= do not use relay
1 NO: normally open, 2 COM: common, 3 NC: normally closed
NOX data sheets, December 03, p 10 of 12
7/28/2019 NOX E Datasheets
11/12
technical data sensor (SHT71)
Tested for temperature range from:-25 to +75 C for the externalsensor
Tested for temperature range from:0 to +40 C for the internal sensor
Tested for humidity range from: 0to 100% RHfor both, the internal and theexternal sensor
NOX data sheets, December 03, p 11 of 12
7/28/2019 NOX E Datasheets
12/12
M31 data sheet
NOXM31
NOXM31 is a compact module with one output and threeinputs for integration into the housing of a detector.
technical data:
min. nom. max.
supply voltage (VBUS) VDC 9.0 15.0 15.5
power consumption 15 VDC mA 12 16
operating temperature C 0 25 40
air humidity at +40C (non
condensing)
% rel. h 93
electrical data open collector output max. 15 VDC/ 50 mA (to GND)
dimensions (L x B x H): mm 16 x 23 x 10
terminal assignment:
terminal P? A B
pin Bus A Bus B
description bus connection
wire red black yellow green 1
pin + - OUT IN 1
description supply voltage output inputwire green 2 green 3
pin IN 2 IN 3
description input
All three input are equipped with a 10k pull up resistor. The inputs are triggered bytying them down to GND.
attention: It is not allowed to lengthen the pre-connected wires!
NOX data sheets, December 03, p 12 of 12