Nagios in the Real WorldDave Williams Technical Architect
2 ©Bull, 2011 Presentation Title
Agenda
3 ©Bull, 2011 Presentation Title
Agenda
- Introduction- General Background- System Monitoring Background
- Example Implementations of Nagios- UK Customer Examples
- Datacentre Monitoring with Nagios- What is a Datacentre ?- Software & Hardware combinations- Vision
- Conclusions
4 ©Bull, 2011 Presentation Title
Background
- UK based- Mainframe (IBM & Honeywell)- Unix (HP-UX, AIX, Solaris)- Network (CASE, 3COM,
CISCO)
- Working for Bull- French Computer Manufacturer- Mainframes, Unix, HPC,
Security, Managed Services
5 ©Bull, 2011 Presentation Title
Background
- System Monitoring- OpenView- Netview- Open Master
- Open Source Monitoring- NetSaint on AIX- Nagios
6 ©Bull, 2011 Presentation Title
Example Implementations
7 ©Bull, 2011 Presentation Title
Crown Office Procurator Fiscal Service
- Responsible for the prosecution of crime in Scotland - Investigation of suspicious deaths- Complaints against the Police
- IT Locations in Glasgow & Edinburgh- Windows at every Courts of Justice in Scotland- AIX / Oracle DB at Glasgow & Edinburgh
8 ©Bull, 2011 Presentation Title
Crown Office Procurator Fiscal Service
- Already used Solarwinds for some network monitoring
- Strategy demanded AIX based monitoring & reporting- In a competitive tender Nagios selected- Main success points were – simplicity, ease of customisation- Fitted within AIX based distance data replication already in use
9 ©Bull, 2011 Presentation Title
Crown Office Procurator Fiscal Service
- 60+ Windows systems monitored for CPU, Disk Space etc
- 2 AIX servers monitored for CPU, Disk Space etc
- Two Oracle Instances monitored for performance and DBspace usage
- All alerts shown on monitor screen and if necessary SMS Text alerts- Installed 2005, still working- Provides ‘backstop’ to Solarwinds for capacity monitoring on
the WAN & LAN.
10 ©Bull, 2011 Presentation Title
Rother District Council
- “Working with the community to improve the overall well-being of the District “- Responsible for Waste Collection, Housing, Planning &
Building Control- The District covers some 200 square miles and serves a
population of around 90,000 inhabitants.
11 ©Bull, 2011 Presentation Title
Rother District Council
- Monitoring 20+ Windows Servers for CPU, Disk Utilsation etc
- Monitoring numerous disparate Applications- Reporting on Availability- Monitoring Printer status- Unexpected benefits
12 ©Bull, 2011 Presentation Title
North Yorkshire County Council
- Internet Access system for 30,000 pupils
- Monitoring e-mail, internet access, IDS, AV, Webservers- Reporting on Availability- Monitoring Service Level Indicators- Mix of application providers (Scalix, Plesk)- Mix of appliance systems – Cisco, Panda, Radware,
NetEnforcer, MyFilter
13 ©Bull, 2011 Presentation Title
North Yorkshire County Council
- System Schematic
14 ©Bull, 2011 Presentation Title
North Yorkshire County Council
- Uses NRPE to perform active checks on hosts
- Multi O/S support- Debian- RedHat
- Uses NSCA to accept check results from Windows- Via NagiosEventLog
15 ©Bull, 2011 Presentation Title
North Yorkshire County Council
- E-mail- Scalix running on Redhat
Cluster. Checking all processes, cluster state etc.
- PLESK Web server- Checking availability of web
sites via test installation- Monitoring disk utilsation
and processor utilisation
- AV systems- Monitoring availability- Checking on AV database
- Myfilter- Monitoring email filters
running- Checking that sufficient
email filters are available
16 ©Bull, 2011 Presentation Title
North Yorkshire County Council
- E-mail- Nagios server runs external
email loopback test every 20 minutes to confirm external reachability.
- PLESK Web server- Straightforward
implementation of check_http
- NetBackup- Monitoring that backups
have run- Checking that enough
backup tapes are available
- Business Availability- Define which services
constitute a business line- 07:00 check – tell support
before the customers come on line
17 ©Bull, 2011 Presentation Title
NYCC - Nagiosgraph
- Nagiosgraph- Uses process_performance
_data- Example of Unix load average
18 ©Bull, 2011 Presentation Title
NYCC – Nagios Monitoring
- Scalix Email System
19 ©Bull, 2011 Presentation Title
NYCC
- Alerts sent via email to customers as well as support
- Backup notifications via SMS Text
- Use Nagios Looking Glass for Customer View
- nagiosgraph used to catch all service performance data- Debian & Redhat perfomance metrics- Network throughput from LAN switches- LDAP response time
20 ©Bull, 2011 Presentation Title
Datacentre Monitoring with Nagios
21 ©Bull, 2011 Presentation Title
What is a DataCentre ?
- A data center (or datacentre) is a facility used to house computer systems and associated components, such as telecommunications and storage systems. It generally includes redundant or backup power supplies, redundant data communications connections, environmental controls and security devices.
(Wikipedia)
22 ©Bull, 2011 Presentation Title
How good is your DataCentre ?
- The TIA-942:Data Center Standards Overview describes the requirements for the data centre infrastructure. The simplest is a Tier 1 data centre, which is basically a server room, following basic guidelines for the installation of computer systems. The most stringent level is a Tier 4 data centre, which is designed to host mission critical computer systems, with fully redundant subsystems and compartmentalized security zones controlled by biometric access controls methods .
(Wikipedia)
23 ©Bull, 2011 Presentation Title
What is a DataCentre ?
- Tier 1 Requirements- Single non-redundant distribution path serving the IT equipment - Non-redundant capacity components - Basic site infrastructure guaranteeing 99.671% availability
- Tier 2 Requirements- Fulfills all Tier 1 requirements - Redundant site infrastructure capacity components guaranteeing 99.741% availability
- Tier 3 Requirements- Fulfills all Tier 1 and Tier 2 requirements - Multiple independent distribution paths serving the IT equipment - All IT equipment must be dual-powered and fully compatible with the topology of a site's architecture Concurrently maintainable
site infrastructure guaranteeing 99.982% availability
- Tier 4 Requirements- Fulfills all Tier 1, Tier 2 and Tier 3 requirements - All cooling equipment is independently dual-powered, including chillers and heating, ventilating and air-conditioning (HVAC)
systems - Fault-tolerant site infrastructure with electrical power storage and distribution facilities guaranteeing 99.995% availability
- ©Uptime Institute
24 ©Bull, 2011 Presentation Title
What is a Green DataCentre ?
- The most commonly used metric to determine the energy efficiency of a data centre is power usage effectiveness, or PUE. This simple ratio is the total power entering the data centre divided by the power used by the IT equipment.
- PUE = Total facility Power / IT Equipment Power
- Power used by support equipment, often referred to as overhead load, mainly consists of cooling systems, power delivery, and other facility infrastructure like lighting. The average data centre in the US has a PUE of 2.0, meaning that the facility uses one Watt of overhead power for every Watt delivered to IT equipment. State-of-the-art data centre energy efficiency is estimated to be roughly 1.2.
25 ©Bull, 2011 Presentation Title
Bull Datacentre BC1 ?
- New datacentre build on an already existing site
- Design criteria PUE 1.6
- Easily expanded on demand
- Tier 3
26 ©Bull, 2011 Presentation Title
Bull UK Datacentre BC1
- What do you get for £1.2m ?
27 ©Bull, 2011 Presentation Title
Bull UK Datacentre BC1
- New Mains Incomer- Took feed from 11Kv ring- Had to build own substation
- 1.2Mw Generator- Required 8000 litre fuel
tank- Switchgear to automatically
start generator if mains incomer fails (10-45 seconds)
- 3 x Ambient CRAC Units- Cooling via external
temperature differential- N+1 configuration- Hot Aisle Containment
- In-Line UPS- UPS only required to keep IT
equipment running until generator fires up
- Uses space in Cab rows, easily scalable according to load
28 ©Bull, 2011 Presentation Title
Bull UK Datacentre BC1 - Monitoring
- Physical Environment- APC Netbotz Devices
• Translate inputs from sensors• Humidity, Temperature, Dew
Point- SEAL I/O Dry Contact
• Voltage indicators• For CRAC, FM200, Generator,
UPS
- Electrical Efficiency- PowerLogic ION software
reads from power meters- Power meter on every
Distribution Board- Real-time calculation of PUE
- Power Distribution- Every PDU strip (2 per Cab)
monitored for power consumption & problems
- A number of PDU strips also have remote control down to socket level
- Management Network- LAN infrastructure required to
support the Datacentre- Servers required to support the
datacentre- External alert mechanisms
29 ©Bull, 2011 Presentation Title
Bull UK Datacentre BC1
- What does Netbotz look like ?
30 ©Bull, 2011 Presentation Title
Bull UK Datacentre BC1
- What does SeaLevel look like ?
31 ©Bull, 2011 Presentation Title
Bull UK Datacentre BC1
- What does ION look like ?
32 ©Bull, 2011 Presentation Title
Bull UK Datacentre BC1
- What does a metered PDU look like ?
33 ©Bull, 2011 Presentation Title
Bull UK Datacentre BC1
- What does a managed PDU look like ?
34 ©Bull, 2011 Presentation Title
Bull UK Datacentre BC1
- Nagios Map
35 ©Bull, 2011 Presentation Title
Bull UK Datacentre BC1
- Nagios Host Groups
36 ©Bull, 2011 Presentation Title
Bull UK Datacentre BC1
- Do things go wrong - yes
37 ©Bull, 2011 Presentation Title
Bull UK Datacentre BC1
- Do things go wrong - yes & no
38 ©Bull, 2011 Presentation Title
Datacentre Monitoring Schematic
39 ©Bull, 2011 Presentation Title
Nagios Products in use
- Nagios Core- NRPE- NSCA
- Nagios Looking Glass
- Nagvis
- EventDB
- SNMPTT
- Nagmap
- NDO
40 ©Bull, 2011 Presentation Title
Other Open Source Products in use
- Nedi
- Arpwatch
- PSAD
- SMS-Client
- Bacula
- Confluence (Wiki)
- i-doit (ITIL CMDB)
- MRTG
- Routers2cgi
41 ©Bull, 2011 Presentation Title
BC1 Datacentre Monitoring Elements
- Nagios Core- Normal install with direct
polling of devices- Only looking at Datacentre
- Nagios Display System- Central reporting Nagios - Absorbs updates from other
Nagios instances
- Information Display- Normal system with 5
heads
- Nagios Customer System- Running on an appliance
connected to Customer network
- Sends data via encrypted secured link to Display System
- Backup System- Use tape library- Hosts CMDB & WiKi
42 ©Bull, 2011 Presentation Title
BC1 Datacentre Nagios Core
- Hardware Platform - Intel- O/S Centos 5- Xeon 2.8Ghz , 8Gb memory, 72GB RAID-1 disk
- Nagios 3.2.0- Built from source tarball
- Nagios Plugins 1.4.15-2- Installed from RPM
43 ©Bull, 2011 Presentation Title
BC1 Datacentre Nagios Display System
- Hardware Platform - Intel- O/S Fedora Core 9- P4 2.8Ghz , 2.5Gb memory, 76GB RAID-1 disk- Nvidia dual monitor display Card – DVI interfaces
- Nagios 3.0.6- Built from source tarball
- Nagios Plugins 1.4.13-9- Installed from RPM
44 ©Bull, 2011 Presentation Title
BC1 Datacentre Normal Display System
- Hardware Platform - AMD- O/S Centos 5- Athlon 1.2Ghz , 1.0 Gb memory, 3GB disk- Matrox G200 Quad Head
- Runs console displays – http/RDP/ssh
45 ©Bull, 2011 Presentation Title
BC1 Datacentre Customer System
- Hardware Platform – Motion Tablet- O/S Ubuntu 10.04 LTS- Pentium M 1.5Ghz , 0.5 Gb memory, 30GB disk- Touch Screen tablet system
- Nagios 3.2.3- Built from tarball
- Nagios Plugins 1.4.15- Built from tarball
- Nagios NSCA- Sends status (encrypted) to central reporting system
46 ©Bull, 2011 Presentation Title
BC1 Datacentre Backup System
- Hardware Platform – Intel- O/S Centos 5- Xeon 3.06Ghz , 2.0 Gb memory, 108GB disk
- Uses Bacula 5.0.3- Controls SDLT 20 slot tape library- Backs up all Datacentre Infrastructure
• Windows• Centos• Ubuntu
47 ©Bull, 2011 Presentation Title
Conclusions
48 ©Bull, 2011 Presentation Title
Conclusions
- Strategic Overall Design- Know what you need to
monitor- Know who needs to be told
- Expect to throw the first version away- Only when you have fully
engineered the solution will you understand all of the issues
- Keep a record of design decisions
- You will have to make it pretty for management- Accept that an attractive
display will be required- Reporting will become key
- It must be reliable- Make backups- Consider clustering &
recovery options
49 ©Bull, 2011 Presentation Title
& Hints
50 ©Bull, 2011 Presentation Title
Hints & Experience
- Separate Display systems from Monitoring systems- If you are tracking 10,000’s of
services you don’t want processor heavy graphics as well
- Escalation & Alerting take time- Firstly to get right with your
organisation- Secondly to actually physically
do !
- Suppliers go out of their way to make it difficult- Don’t give in – there is always
a way to get Nagios involved- Screen scrape, email,
telnet,RS232 are all possible
- SNMP is your friend- When in doubt use SNMP to
help you out- SNMP V3 with AES cypher is
suitably secure for most implementations