Relion® 630 series
Load Shedding ControllerPML630IEC 61850 Communication Protocol Manual
Document ID: 1MRS757260Issued: 2011-11-03
Revision: BProduct version: 1.1.1
© Copyright 2011 ABB. All rights reserved
CopyrightThis document and parts thereof must not be reproduced or copied without writtenpermission from ABB, and the contents thereof must not be imparted to a thirdparty, nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under a licenseand may be used, copied, or disclosed only in accordance with the terms of suchlicense.
TrademarksABB and Relion are registered trademarks of the ABB Group. All other brand orproduct names mentioned in this document may be trademarks or registeredtrademarks of their respective holders.
WarrantyPlease inquire about the terms of warranty from your nearest ABB representative.
http://www.abb.com/substationautomation
DisclaimerThe data, examples and diagrams in this manual are included solely for the conceptor product description and are not to be deemed as a statement of guaranteedproperties. All persons responsible for applying the equipment addressed in thismanual must satisfy themselves that each intended application is suitable andacceptable, including that any applicable safety or other operational requirementsare complied with. In particular, any risks in applications where a system failure and/or product failure would create a risk for harm to property or persons (including butnot limited to personal injuries or death) shall be the sole responsibility of theperson or entity applying the equipment, and those so responsible are herebyrequested to ensure that all measures are taken to exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot becompletely ruled out. In case any errors are detected, the reader is kindly requestedto notify the manufacturer. Other than under explicit contractual commitments, inno event shall ABB be responsible or liable for any loss or damage resulting fromthe use of this manual or the application of the equipment.
ConformityThis product complies with the directive of the Council of the EuropeanCommunities on the approximation of the laws of the Member States relating toelectromagnetic compatibility (EMC Directive 2004/108/EC) and concerningelectrical equipment for use within specified voltage limits (Low-voltage directive2006/95/EC). This conformity is the result of tests conducted by ABB inaccordance with the product standards EN 50263 and EN 60255-26 for the EMCdirective, and with the product standards EN 60255-1 and EN 60255-27 for the lowvoltage directive. The product is designed in accordance with the internationalstandards of the IEC 60255 series.
Table of contents
Section 1 Introduction.......................................................................3This manual........................................................................................3Intended audience..............................................................................3Product documentation.......................................................................4
Product documentation set............................................................4Document revision history.............................................................5Related documentation..................................................................6
Symbols and conventions...................................................................6Symbols.........................................................................................6Manual conventions.......................................................................6Functions, codes and symbols......................................................7
Section 2 Introduction to IEC 61850.................................................9Related documentation to IEC 61850..........................................10
Section 3 Substation Configuration Language (SCL)....................13The Substation section.....................................................................14The Communication section.............................................................14The IED section................................................................................15Tool concept.....................................................................................17Engineering concept in IEC 61850-6................................................18
Section 4 Communication profile....................................................21
Section 5 Supported services.........................................................23
Section 6 Data sets and control blocks..........................................25Report control block (URCB/BRCB).................................................26GOOSE Control Blocks (GoCB).......................................................30
Section 7 Logical node data model................................................33Common data objects in each logical node......................................33Logical nodes for control..................................................................34
IEC61850 generic communication I/O functions DPGGIO..........34Logical node for monitoring..............................................................34
Station battery supervision SPVNZBAT......................................34IEC61850 generic communication I/O functions MVGGIO..........36IEC61850 generic communication I/O functions SPGGIO..........36
Logical node for power management...............................................37Input interface function for network circuit breaker dataNCBDCSWI.................................................................................37
Table of contents
PML630 1Communication Protocol Manual
Contingency based fast load shed function LSCACLS...............39Sheddable load trip command LSPTRC......................................49Input interface function for sheddable load data LDMMXU.........54Input interface function for network power source dataPWSMMXU.................................................................................67Output interface function for sub network data SNWRCLS.........79
Logical node for disturbance recorder function................................83Disturbance report DRRDRE.......................................................83
Load shedding power management function blocks........................84
Section 8 Glossary.........................................................................87
Table of contents
2 PML630Communication Protocol Manual
Section 1 Introduction
1.1 This manual
The communication protocol manual describes a communication protocolsupported by the IED. The manual concentrates on vendor-specific implementations.
1.2 Intended audience
This manual addresses the communication system engineer or system integratorresponsible for pre-engineering and engineering for communication setup in asubstation from an IED perspective.
The system engineer or system integrator must have a basic knowledge ofcommunication in protection and control systems and thorough knowledge of thespecific communication protocol.
1MRS757260 B Section 1Introduction
PML630 3Communication Protocol Manual
1.3 Product documentation
1.3.1 Product documentation set
Pla
nnin
g &
pur
chas
e
Eng
inee
ring
Inst
allin
g
Com
mis
sion
ing
Ope
ratio
n
Mai
nten
ance
Dec
omm
issi
onin
gde
inst
allin
g&
dis
posa
l
Application engineering
Operation manual
Installation manual
Service manual
Engineering manual
Commissioning manual
Communication protocolmanual
Technical manual
Pla
nnin
g &
pur
chas
e
Eng
inee
ring
Inst
allin
g
Com
mis
sion
ing
Ope
ratio
n
Mai
nten
ance
Dec
omm
issi
onin
gde
inst
allin
g&
dis
posa
l
Pla
nnin
g &
pur
chas
e
Eng
inee
ring
Inst
allin
g
Com
mis
sion
ing
Ope
ratio
n
Mai
nten
ance
Dec
omm
issi
onin
gde
inst
allin
g&
dis
posa
l
ApplicationApplication
Operation manualOperation manual
Installation manualInstallation manual
Service manualService manual
EngineeringEngineering
Commissioning Commissioning
Communication protocolmanualCommunication protocolmanual
Technical manualTechnical manual
engineeringengineeringguideguideguide
GUID-6D633E82-6FD1-46D4-B2EC-D93A3E2016D8 V1 EN
Figure 1: The intended use of manuals in different lifecycles
The engineering manual contains instructions on how to engineer the IED usingPCM600. The manual provides instructions on how to set up a PCM600 projectand insert IEDs to the project structure. The manual also recommends a sequencefor engineering of load shedding power management function, LHMI functions andcommunication engineering for IEC 61850.
The installation manual contains instructions on how to install the IED. Themanual provides procedures for mechanical and electrical installation. The chaptersare organized in chronological order in which the IED should be installed.
The commissioning manual contains instructions on how to commission the IEDwith the load shedding power management functions. The manual can also be usedby system engineers and maintenance personnel for assistance during the testingphase. The manual provides procedures for checking external circuitry andenergizing the IED, parameter setting and configuration. The manual describes theprocess of testing an IED in a substation that is not in service. The chapters areorganized in chronological order in which the IED should be commissioned.
Section 1 1MRS757260 BIntroduction
4 PML630Communication Protocol Manual
The application engineering guide provides information for IEC 61850 engineeringof the load shedding controller IED, protection and control IEDs and COM600Station Automation device using PCM600, IET600 and SAB600. With a practicalexample, the guide explains all the steps from system planning and engineering toapplication functionality and IED parameterization for realizing the load sheddingfunctionality using the IEDs.
The operation manual contains instructions on how to operate the IED once it hasbeen commissioned. The manual provides instructions for monitoring, controllingand setting the IED.
The service manual contains instructions on how to service and maintain the IED.The manual also provides procedures for de-energizing, de-commissioning anddisposal of the IED.
The technical manual contains application and functionality descriptions and listsfunction blocks, logic diagrams, input and output signals, setting parameters andtechnical data sorted per function. The manual can be used as a technical referenceduring the engineering phase, installation and commissioning phase, and duringnormal service.
The communication protocol manual describes a communication protocolsupported by the IED. The manual concentrates on vendor-specific implementations.
The point list manual describes the outlook and properties of the data pointsspecific to the IED. The manual should be used with the correspondingcommunication protocol manual.
The IED documentation set includes operation manual, engineeringmanual, application engineering guide, technical manual, point listmanual and IEC 61850 communication protocol manual. See the630 series documentation set for installation manual andcommissioning manual. The service manual is not available yet.
1.3.2 Document revision historyDocument revision/date Product version HistoryA/2011-05-04 1.1 First release
B/2011-11-03 1.1.1 Content updated
Download the latest documents from the ABB Web sitehttp://www.abb.com/substationautomation.
1MRS757260 B Section 1Introduction
PML630 5Communication Protocol Manual
1.3.3 Related documentationProduct-specific point list manuals and other product series- and product-specificmanuals can be downloaded from the ABB web site http://www.abb.com/substationautomation .
1.4 Symbols and conventions
1.4.1 Symbols
The caution icon indicates important information or warning relatedto the concept discussed in the text. It might indicate the presenceof a hazard which could result in corruption of software or damageto equipment or property.
The information icon alerts the reader of important facts andconditions.
The tip icon indicates advice on, for example, how to design yourproject or how to use a certain function.
Although warning hazards are related to personal injury, it is necessary tounderstand that under certain operational conditions, operation of damagedequipment may result in degraded process performance leading to personal injuryor death. Therefore, comply fully with all warning and caution notices.
1.4.2 Manual conventionsConventions used in IED manuals. A particular convention may not be used in thismanual.
• Abbreviations and acronyms in this manual are spelled out in the glossary. Theglossary also contains definitions of important terms.
• Push button navigation in the LHMI menu structure is presented by using thepush button icons.To navigate between the options, use and .
• HMI menu paths are presented in bold.Select Main menu/Settings.
• LHMI messages are shown in Courier font.To save the changes in non-volatile memory, select Yes and press .
• Parameter names are shown in italics.
Section 1 1MRS757260 BIntroduction
6 PML630Communication Protocol Manual
The function can be enabled and disabled with the Operation setting.• The ^ character in front of an input or output signal name in the function block
symbol given for a function, indicates that the user can set an own signal namein PCM600.
• The * character after an input or output signal name in the function blocksymbol given for a function, indicates that the signal must be connected toanother function block in the application configuration to achieve a validapplication configuration.
1.4.3 Functions, codes and symbolsTable 1: Functions included in PML630
Functionality IEC 61850Control
Double point indication DPGGIO1)
Monitoring
Station battery supervision SPVNZBAT1)
Generic measured values MVGGIO1)
Single point indication SPGGIO1)
Power management
Critical circuit breaker NCBDCSWI
Contingency based fast load shed LSCACLS
Sheddable load trip LSPTRC
Busbar with sheddable load LDMMXU
Network power source PWSMMXU
Subnetwork output SNWRCLS
Disturbance recorder function
Disturbance recorder DRRDRE1)
Analog channels 1-10 (samples) A1RADR1)
Analog channel 11-20 (samples) A2RADR1)
Analog channel 21-30 (samples) A3RADR
Analog channel 31-40 (calc. val.) A4RADR
Binary channel 1-16 B1RBDR
Binary channel 17-32 B2RBDR
Binary channel 33-48 B3RBDR1)
Binary channel 49-64 B4RBDR1)
1) The function is not used by default. However, it is kept enabled in the Application Configuration toolfor instantiation in any additional user defined logic other than the features offered by the IEDConnectivity Package.
1MRS757260 B Section 1Introduction
PML630 7Communication Protocol Manual
8
Section 2 Introduction to IEC 61850
The IEC 61850 protocol standard for substation enables the integration of allprotection, control, measurement and monitoring functions by one commonprotocol. It provides the means of high-speed substation applications, station wideinterlocking and other functions including load shedding, busbar protection and soon that need intercommunication between IEDs. The well-described datamodelling, the specified communication services for the most recent tasks in astation makes the standard to a key element in modern substation systems.
This manual describes how the IEC 61850 standard is applied in PML630 IED.References and brief descriptions of the IEC 61850 standard are also included. It isassumed that the reader has basic knowledge about the IEC 61850.
To understand the IEC 61850 standard and to be able to find the relatedinformation, read the following information:
• Station Configuration description Language (SCL) is described in IEC61850-6. The SCL is an XML based definition of how to describe the parts ofa substation. This part of the standard also includes the roles of different toolsas well as the engineering concepts.
• Communication profile (IEC 61850 stack) is described in IEC 61850-8-1. Thispart of the standard includes a number of possible communication profiles andhow the services defined in IEC 61850-7-2 are mapped to the communicationprofile.
• Communication services are described in IEC 61850-7-2. This part dealsmainly with the communication facilities from client and server point of view.It includes the different possibilities of communication functionality.
• Logical node data model. This is described in IEC 61850-7-3 and IEC61850-7-4.
• Conformance tests and the basis for conformance documents are handled inIEC 61850-10.
To get information and an understanding about the implemented possibilities ofIEC 61850 in the IED, see the IEC 61850 conformance documents.
• MICS, Modeling Information Conformance Statement, contains thedeclaration of the used logical node types.
• PICS, Protocol Information Conformance Statement, contains the details andwhat is supported regarding protocol facilities.
• PIXIT, Protocol Extra Information, contains additional information on how theIEC 61850 is implemented and used.
• TICS, Tissue Information Conformance Statement, contains the supportedTissues, which are handled in the Tissues process as defined by UCA, Utility
1MRS757260 B Section 2Introduction to IEC 61850
PML630 9Communication Protocol Manual
Communication Architecture forum. The Tissues handling is found in http://www.tissue.iec61850.com. The TICS for the 630 Series version 1.1 is alsoapplicable for the IED (as it is based on 630 Series version 1.1) and, hence, aseparate TICS document is not made for the IED.
The conformance documents are unique for each product release and refer to eachother; the identities included in the related documents refer to a specific version ofthe IED.
The communication profile in IEC 61850 uses the MMS standard, which usesEthernet and TCP/IP to handle the information transport within the substation.
The data modelling uses the concept of logical nodes to identify the publishedinformation for communication. The standard defines a set of logical nodes, eachrepresenting a communication view of a process function with a number of dataobjects. The standard cannot cover all possible information that is given, forexample, by a protection function of vendor A or vendor B or for the variants of aprotection function given by the process part which is protected. For example, atransformer differential - or line differential protection, because the standarddefines only a differential protection. Therefore, it is possible to adapt the logicalnode, which is defined in the standard, as a logical node class. The standard definesmethods to describe the actual used logical node as an logical node type which isthen based upon the logical node class. This allows all partners to interpret thelogical node type information because the description is completely given in thestandard. The type description of all logical nodes is part of the Data TypeTemplate (DTT) section in the SCL description file of a station or the IED.
Beside the information about the configuration of the communication facilities, thismanual contains the full description of all logical nodes available in the IED. Theinformation about the logical nodes and their data objects may be used to identifywhich signals are available for the function as described in the technical manual.The link to the technical manual is done in the logical node tables by listing thesignal name as given in the function block, as seen in PCM600 and in LHMI.
2.1.1 Related documentation to IEC 61850Use the latest revision of the documents listed, unless stated otherwise.
Document ID Title
IEC 61850-5First edition 2003-07Ref. number: IEC 61850-5:2003(E)
Communication networks and systems insubstations -Part 5:Communication requirements for functions anddevices models
IEC 61850-6First edition 2004-03Ref. number: IEC 61850-6: 2004(E)
Communication networks and systems insubstations -Part 6:Configuration description language forcommunication in electrical substations related toIEDs
Table continues on next page
Section 2 1MRS757260 BIntroduction to IEC 61850
10 PML630Communication Protocol Manual
IEC 61850-7-1First edition 2003-07Ref. number: IEC 61850-7-1: 2003(E)
Communication networks and systems insubstations -Part 7-1:Basic communication structure for substationsand feeder equipment -Principles and models
IEC 61850-7-2First edition 2003-05Ref. number: IEC 61850-7-2: 2003(E)
Communication networks and systems insubstations -Part 7-2:Basic communication structure for substationsand feeder equipment -Abstract communication service interface (ACSI)
IEC 61850-7-3First edition 2003-05Ref. number: IEC 61850-7-3: 2003(E)
Communication networks and systems insubstations -Part 7-3:Basic communication structure for substationsand feeder equipment -Common data classes
IEC 61850-7-4First edition 2003-05Ref. number: IEC 61850-7-4: 2003(E)
Communication networks and systems insubstations -Part 7-4:Basic communication structure for substationsand feeder equipment -Compatible logical node classes and data classes
IEC 61850-8-1First edition 2004-05Ref. number: IEC 61850-8-1: 2004(E)
Communication networks and systems insubstations -Part 8-1:Specific Communication Service Mapping(SCSM) - Mappings to MMS (ISO 9506-1 andISO 9506-2) and to ISO/IEC 8802-3
IEC 61850-10First edition 2005-05Ref. number: IEC 61850-10: 2005(E)
Communication networks and systems insubstations -Part 10:Conformance testing
IEC 61850 MICS 1MRS757324 IED version 1.1- IEC 61850 MICS:Modelling Implementation ConformanceStatement
IEC 61850 PICS 1MRS757325 IED version 1.1- IEC 61850 PICS:Protocol Implementation Conformance Statement
IEC 61850 PIXIT 1MRS757326 IED version 1.1- IEC 61850 PIXIT:Protocol Implementation Extra Information
IEC 61850 TICS 1MRS189728 IED version 1.1– IEC 61850 TICSTissue Implementation Conformance Statement
1MRS757260 B Section 2Introduction to IEC 61850
PML630 11Communication Protocol Manual
12
Section 3 Substation Configuration Language (SCL)
The SCL language is based on XML. However, detailed knowledge of the XMLcontents is not needed.
The SCL XML file (ied.ICD and/or station.SCD) contains five sections, which arespecified in IEC 61850–6 clause 9.
• Header• Substation section describes the functional structure and its relation to primary
devices.• Communication section describes the connection between the IED access
points to the respective subnetwork. and includes also the properties(addresses) of the access points.
• IED section contains a description of the supported communication services,the access point(s) and the IEDs logical devices, logical nodes and their attributes.
• Data type template section contains a declaration of all types used in the SCLfile, logical nodes type, DO types, attributes and enums.
The substation section and the communication section are tasks to organize theIEDs within the substation and to establish the communication. The systemstructure is defined by the organization of the plant structure in PCM600. Thesignal engineering and the signal routing are IET600 tasks. The IED needs to beconfigured with PCM600 before the system is configured with IET600.
The IED section contains the data sets and the control blocks configured byIET600. The data sets and the control blocks are logically defined as part of thelogical nodes (see IEC 61850–7–2 clause 9). IET600 also needs a correctlyconfigured communication section for GOOSE engineering.
The data type templates section provides the correct content description of eachlogical node type to all tools and users (clients) of the information. Each IED andvendor may have their own logical node type definitions included in the data typetemplate section together with all other logical node types based on the standard.
1MRS757260 B Section 3Substation Configuration Language (SCL)
PML630 13Communication Protocol Manual
IED(server)
- Access Point (AP)- Address- GSE; GoCBs
Communication
AP
IED(server)
- Access Point (AP)- Address- GSE; GoCBs
Communication
IED(server)
- Access Point (AP)- Address- GSE; GoCBs
Communication
AP
IED(client)
- Access Point (AP)- Address- GSE; GoCBs
Communication
IED(client)
- Access Point (AP)- Address- GSE; GoCBs
Communication
Subnetwork
GUID-CC043293-BBB3-4B96-A000-EA6BEFC9C460 V1 EN
Figure 2: IEC 61850: Principle structure of the SCL XML file
The arrows show the link between the different sections given when an IED isintegrated in the substation structure and/or in the communication structure. Allneeded logical nodes of an IED are linked to the substation section by the SC tool.
A reference to GOOSE Control Blocks (GoCB) is included in the communicationsection when GoCB is configured.
3.1 The Substation section
The Substation description in IEC 61850–6 clause 9 describes the organization ofthe primary equipment on one side. On the other side, it includes the used logicalnodes and their relation to the primary equipment.
3.2 The Communication section
The organization of the physical IEDs to the communication network isindependent of the substation structure. The IEC 61850 standard defines thecommunication network with no relation to an existing media and protocol. Themapping to an existing media and protocol is specified in IEC 61850–8–1.
The IEC 61850 standard describes in part 7–2 the ACSI in a media and protocolindependent form. Part 8–1 specifies the mapping of this ACSI to the existingMMS.
Section 3 1MRS757260 BSubstation Configuration Language (SCL)
14 PML630Communication Protocol Manual
The communication section describes how information is routed between the IEDsand contains the following parts:
• Subnetworks• IEDs connected to different subnetworks• Access points per IED to subnetworks• Address• IP address of LAN network (is exceptionally part of the address elements)• Link to GoCB message in transmission direction (extended during signal
engineering and routing)
IED(server)
- Access Point (AP)- Address- GSE; GoCBs
Communication
AP
IED(server)
- Access Point (AP)- Address- GSE; GoCBs
Communication
IED(server)
- Access Point (AP)- Address- GSE; GoCBs
Communication
AP
IED(client)
- Access Point (AP)- Address- GSE; GoCBs
Communication
IED(client)
- Access Point (AP)- Address- GSE; GoCBs
Communication
Subnetwork
GUID-CC043293-BBB3-4B96-A000-EA6BEFC9C460 V1 EN
Figure 3: IEC 61850–6: Communication network
Additional information about the server is part of the IED.
3.3 The IED section
The IED section describes the complete IED as it is needed for IEC 61850communication and signal engineering. The data type template part of an IED maybe seen as part of the IED, even when separated in its own section. The IED's ICDfiles include the description of the logical nodes, their data type templates and theused or supported services. The structure of the IED section follows the definitionsmade in the IEC 61850 standard.
Two basic IED types are used in system configuration:
• Station level IEDsare located on the station level and are identified as client IEDs when they reador write information from or to the bay IEDs. This functionality is represented
1MRS757260 B Section 3Substation Configuration Language (SCL)
PML630 15Communication Protocol Manual
by logical nodes of group “Information (I)”. These are the logical nodes (LN)= ITCI, IHMI and ITMI. Client IEDs are the receiver of information inmonitoring direction and sender of commands (control). These logical nodeshave no data objects. They are only used to link the report control blocks(BRCBs) from the server IEDs. They have to read their information about thesignals and the signal configuration from the bay IEDs. This is possible bychecking all control blocks for a link to it as a client.
• Bay level IEDsare located on the bay level and are identified as server IEDs when they reador write information vertically. When GOOSE messages are received, the baylevel IED also has the client role.
IED
SubnetworkAP -> S1
ServerLogical Device
LD0
LD_<n>
LS_<n>
SNW_<n>
LSC_1
PWS_1LSCLLN0
LPHD
LSCACLS
LSCCCLS1
LSCGAPC
LSCCCLS2
LSCCCLS3
LSCCCLS4
LSCRCLS
Logical Node
Mod
Beh
Health
NamPlt
Str
Op
Data Object
general
q
t
d
Data Attribute
GUID-76CB6EDD-208D-4F77-9EE6-6F3F9CA9D980 V1 EN
Figure 4: Organisation of LDs, LNs, DOs and DAs in an IED
• A server represents the communication interface to the subnetwork (Ethernet).• One or more logical device(s) (LD) are connected to a server.• A set of logical nodes belong to a LD.• The LN LLN0 is a special logical node per LD and contains for example the
data sets, the various control blocks, inputs (from GOOSE messages). Likeother ABB IEDs, even in the PML630, the data sets and the control blocksshall be located under LD0.
Section 3 1MRS757260 BSubstation Configuration Language (SCL)
16 PML630Communication Protocol Manual
• The LN LPHD is a special logical node per LD and contains data objects thatdescribe the status of the physical device (the IED).
• Each logical node represents a function and contains a number of data objects(DO).
• Each DO includes a number of data attributes (DA).
The data objects represent information signals that may be routed to station levelIEDs or to other bay IEDs that are communicating with GOOSE. The signalengineering task is to select the requested signals (DOs) and link them to the clientIEDs as receiver. The control services are not directly engineered. They areincluded in the data objects, which handle both directions the command (control)and the response (monitoring). When routing the DO in monitoring direction, thecontrol is also known by the clients.
The number of data objects and data attributes per DO is defined by the used LNtype in this IED. The content of logical node types and DO types are defined in theDTT. This also means that the definitions in the DTT section have to be uniquewith an SCD file.
3.4 Tool concept
The IEC 61850-6 defines a number of roles for tools. In the Relion® series,PCM600 is defined as IED tool, and IET600 is defined as system tool
The sections in SCL contain properties that are to be configured by these tools.There is no relation between one section and one specific tool. The task of the IEDtool is to configure all properties for the IED, while the system tool has the task todefine the place of the IED in the system and its communication dependencies. Forexample, the plant structure in PCM600 results in the subsystem section in SCLregarding the subsystem structure down to the IED level. The PCM600 alsoconfigures the IED section as a result of the IED configuration. In PCM600, theconfiguration properties for SCL are handled automatically as a result of theconfiguration, except for the receiving of GOOSE information that has adependency with the system tool.
Perform IEC 61850 engineering with PCM600 and IET600.
PCM600:
1MRS757260 B Section 3Substation Configuration Language (SCL)
PML630 17Communication Protocol Manual
• When an IED is instantiated, its place in the plant structure creates thecorresponding structure in the substation section in SCL. The communicationfacilities is also created in the communication section.
• The functionality of the IED is configured by using ACT in PCM600. For eachfunction, the corresponding logical device and logical node(s) is created in theIED section together with its type definition in data type template section.
• The above forms the IED capabilities from a communication perspective andwill then be included in the file exported from PCM600 as SCD, ICD or CIDfile.
IET600:
• Open a SCD file or import/merge a SCD, ICD or CID file for the particularIED(s).
• For each IED, the user defines the datasets, the control blocks for reporting(this means unbufffered/buffered reporting and GOOSE) and the properties foreach report control block.
• If client definitions (like client. ICD) are required in the system configuration,they are merged into IET600 and connected to the unbuffered/buffered reportcontrol blocks.
• For each IED, the primary/conducting equipment with their relation to theused logical nodes must be defined in the substation section.
• The resulting SCD file is exported from IET600.
PCM600:
Import the SCD file to PCM600 to receive GOOSE data. For each IED that shallreceive GOOSE information, the received data is connected to the applicationsusing SMT in PCM600.
3.5 Engineering concept in IEC 61850-6
• Top-down approach means that the system engineering tool has ICD filesavailable for each IED to be included in the system configuration. The ICDfiles may be of a template type and represent a pre-configured IED.
• Bottom-up approach means that the configurations are produced by the IEDtool, and are exported as ICD files (or SCD file) to be imported by system tools.
Section 3 1MRS757260 BSubstation Configuration Language (SCL)
18 PML630Communication Protocol Manual
….IED A IED B IED Z
Client A Client B
IEDtool
Systemtool
GUID-ACC3CE26-A7F7-4B88-A6DD-9B5104A5A10F V1 EN
Figure 5: Relation between system and IED tools
Regardless of engineering approach, the idea is that the IED tool provides the CIDor ICD file for each IED. These ICD/CID files are then imported into the systemtool and merged into a SCD file, representing the complete substation or a part ofthe substation, like one for each voltage level.
1MRS757260 B Section 3Substation Configuration Language (SCL)
PML630 19Communication Protocol Manual
20
Section 4 Communication profile
The IEC 61850 standard is conceptually written to be independent of an existingcommunication media and message transmission concept. Out of this, a specificcommunication profile is decided and is been commonly used. The actual decisionis for
• Ethernet as the media• TCP/IP• ISO session and presentation layer• MMS (Manufacturing Message Specification (ISO 9506-1 and ISO 9506-2)
The IEC 61850 standard describes its requested services in ACSI, which iscontained in part 7-2 of the standard. The mapping to the MMS for all aspects ofservices and Ethernet usage is specified in part 8-1 of IEC 61850.
Each device manufacturer, which is a partner of an IEC 61850 basedcommunication network, has to take these two specifications and adapt theirrespective product to the requirements and definitions given in the standard. Tomake this profile visible to all other partners, so they can check what they canexpect and what they have to support, the PICS document is defined. The PICScontains in a table based form the possibility of a product or product family.
IED (server )(61850 services part 7-2)
Communication(MMS services part 8-1)
- Access Point (AP) / Address- GSE
AP
IED (client )(61850 services part 7-2)
Subnetwork
IED (server)(61850 services part 7-2)
Communication(MMS services part 8-1)
Communication( MMS servicespart 8-1)
- Access Point (AP) / Address- GSE
- Access Point (AP) / Address- GSE
GUID-5E41938B-BF64-4A80-8012-77DFF0D9D92D V1 EN
Figure 6: IEC 61850 Protocol: related standards for communication
1MRS757260 B Section 4Communication profile
PML630 21Communication Protocol Manual
SV GOOSE TimeSync(SNTP) MMS Protocol Suite GSSE
TCP/IPT-Profile
ISO COT-Profile
ISO/IEC 8802-2 LLC
GSSET-ProfileUDP/IP
ISO/IEC 8802-3 Ethertype
SampledValues(Multicast)
GenericObjectOrientedSubstationEvent
TimeSync
CoreACSIServices
GenericSubstationStatusEvent
ISO/IEC 8802-3GUID-8CA0E976-7104-4170-A92F-188D333E4C25 V1 EN
Figure 7: Overview of functionality and profiles according to IEC 61850-8-1
Out of this content, the implementation in the PML630 supports:
• GOOSE for peer to peer communication, based on IEEE802.1P (PriorityTagging) and VLAN technology
• TimeSync using SNTP• Vertical communication using MMS protocol suite with the T-profile TCP/IP
For each of the above, the resulting underlying protocols are as stated in figure4.
For more information, see the PICS and PIXIT.
Section 4 1MRS757260 BCommunication profile
22 PML630Communication Protocol Manual
Section 5 Supported services
IEC 61850-7-2 describes the services in the standard. IEC 61850-8-1 describeshow the services are applied in the communication. The conformance documentscontain the main description about the supported services in the IED.
Services that are not mentioned in this chapter or in the conformance document arenot supported.
Data setDefine data sets by the SCD description.
Create data sets under LD0/LLN0.
Report control blockFor properties about report control blocks, see PIXIT.
UnBuffered reporting as well as Buffered reporting is supported.
The relation between the parameters BufTm and IntPrd is BufTm <IntPrd. For best efficiency, the BufTm must have IntPrd as commondenominator, like n*BufTm = IntPrd, n is an arbitrary number.
Generic substation event (GOOSE)The structured GOOSE is supported. This means that the data sets can be definedwith FCDA as well as explicit attributes.
When explicit attributes are defined in the data sets, the number of such items in adata set is limited to 150.
The supported data types to be published and received using GOOSE includemeasurement, single point and double point status information together with theirquality. On reception of GOOSE message there is one valid signal available for theapplications. The valid signal represents all data in the received GOOSE telegram.Invalid means that the correct message is not received within the 1.8*maxTimeparameter for the GOOSE Control Block (as defined in IEC 61850-6). An incorrectmessage includes T=true, NeedsCom, wrong order of attributes or any discrepancyin the GOOSE message layout.
The data sets that are used or referred to by GOOSE control blockscan only include a data attribute once. In other words, there may notbe the same data attribute in more than one data set.
1MRS757260 B Section 5Supported services
PML630 23Communication Protocol Manual
ControlOf the different control sequences, the direct-with-normal-security and SBO-withenhanced security are supported (defined by the ctlModel parameter, IEC61850-7-2).
The command model can be changed for some functions by using PCM600 or PST.From communication perspective, in IEC61850 this parameter is read-only.
Check bits; interlock check and synchrocheck check, are only valid for LN typesbased upon CSWI class.
Verification of Originator Category is supported, see PIXIT.
Time and time synchronizationFor properties about time synchronization, see PIXIT and Time synchronizationdescription in the Technical manual and the Application engineering guide.
File transferSee PIXIT.
Section 5 1MRS757260 BSupported services
24 PML630Communication Protocol Manual
Section 6 Data sets and control blocks
Data setsIEC 61850 has defined Data sets and Report control blocks for signal transmissionin monitoring direction. Data sets are also used for GOOSE messages in horizontaldirection. Which data objects or single data attributes can be collected in a Data setis not specified and can be done to rules which may be defined in a project. Thefollowing figure shows a Data set where all position information of the apparatusesof a bay are put into one Data set.
The vendor of an IED can define Data sets as defaults which are part of the IEDand always available. They need to be linked to the client IEDs when more thanone client is configured. The user can delete, modify or add Data set during systemengineering.
LD0 LLN0
LD_<n>
LS_1
SNW_<n>
LSC_1
PWS_1
LSLLN0
LPHD
LSPTRC1
LSPTRC2
LSPTRC3
LSPTRC4
LSPTRC5
LSPTRC6
LSPTRC7
LSPTRC8
LSPTRC9
LSPTRC10
Tr
Tr
Tr
Tr
Tr
Tr
Tr
Tr
Tr
Tr
LD0/LLN0.GCB_SL1
LS_1/LSPTRC1.Tr, FC = ST
LS_2/LSPTRC1.Tr, FC = ST
LS_3/LSPTRC1.Tr, FC = ST
LS_4/LSPTRC1.Tr, FC = ST
LS_5/LSPTRC1.Tr, FC = ST
LS_6/LSPTRC1.Tr, FC = ST
general
q
t
d
Data Set
LS_2
LS_3
LS_4
LS_5
LS_6
LD0/LLN0.GCB_SL2
LS_1/LSPTRC2.Tr, FC = ST
LS_2/LSPTRC2.Tr, FC = ST
LS_3/LSPTRC2.Tr, FC = ST
LS_4/LSPTRC2.Tr, FC = ST
LS_5/LSPTRC2.Tr, FC = ST
LS_6/LSPTRC2.Tr, FC = ST
Data Set
LD0/LLN0.GCB_SL3
LS_1/LSPTRC3.Tr, FC = ST
LS_2/LSPTRC3.Tr, FC = ST
LS_3/LSPTRC3.Tr, FC = ST
LS_4/LSPTRC3.Tr, FC = ST
LS_5/LSPTRC3.Tr, FC = ST
LS_6/LSPTRC3.Tr, FC = ST
Data Set
LD0/LLN0.GCB_SL4
LS_1/LSPTRC4.Tr, FC = ST
LS_2/LSPTRC4.Tr, FC = ST
LS_3/LSPTRC4.Tr, FC = ST
LS_4/LSPTRC4.Tr, FC = ST
LS_5/LSPTRC4.Tr, FC = ST
LS_6/LSPTRC4.Tr, FC = ST
LD0/LLN0.GCB_SL10
LS_1/LSPTRC40.Tr, FC = ST
LS_2/LSPTRC40.Tr, FC = ST
LS_3/LSPTRC10.Tr, FC = ST
LS_4/LSPTRC10.Tr, FC = ST
LS_5/LSPTRC10.Tr, FC = ST
LS_6/LSPTRC10.Tr, FC = ST
LD0/
LLN
0.G
CB
_SL5
LD0/
LLN
0.G
CB
_SL6
LD0/
LLN
0.G
CB
_SL7
LD0/
LLN
0.G
CB
_SL8
LD0/
LLN
0.G
CB
_SL9
Data Set Data Set
Data Sets
Data Sets
GUID-62C9029B-6DA8-4D40-9B54-28863BDB34B6 V1 EN
Figure 8: IEC 61850–7–2: Example of a Data set
General rules for Data set configuration:
1MRS757260 B Section 6Data sets and control blocks
PML630 25Communication Protocol Manual
• All data objects or their data attributes which are signals in monitoringdirection can be selected for a Data set.
• Items in a Data set is normally added by DO name + functional constraint.This means that all attributes within the DO with same functional constraintare included in the Dataset.
• Data objects with different FC can be selected for a Data set. For example,DOs with FC = ST and DOs with FC=MX can be member in one Data set.
• A single data attribute can be included in a Data set, thus defined with thecomplete attribute path. For example, the data attribute stVal of the data objectPos can be selected as a member of a Data set, because it is specified with thetrigger option data change detected (dchg).
The criteria for reporting is defined in the respective report controlblock. As the attributes have different trigger options, the mostfeasible configuration is to include attributes with same triggeroption, but it is also possible to define a number of reportingconditions for one report control block.
The description of the Data sets with name and the list of data object members(FCDAs = Functional Constraint Data Attributes) is included in the SCL file in theIED section in the Logical device subsection. As specified in IEC 61850–7–2clause 9, the Data sets are part of a Logical node. For the Relion series, the Datasets can be definded in LD0/LLN0.
6.1 Report control block (URCB/BRCB)
To be able to transmit the signals configured in a DataSet, a report control blockmust be configured to handle and specify how the events are transmitted to theclients. There are two types of report control blocks, unbuffered and buffered. Thebuffered report control block stores the events during a communication interrupt,while the unbuffered is sent upon data change and not stored during interruption.
The content of a BRCB is listed in IEC 61850-7-2 in clause 14. The BRCBcontains many attributes which are of interest to handle and secure thecommunication between the client and the server and may be set once as default ina project. Others are of application interest in the way events are handled in a project.
• Buffer time (valid only for BRCB)• This parameter describes how long the report must wait for other
expected events before it sends the report to the client. When it is knownthat additional events are generated as a follow up, it is useful to wait.For example, 500 ms for additional events stored in the report. Thisfeature reduces the number of telegrams transmitted in case of a burst ofchanges. But on the other side, it increases the overall transaction time
Section 6 1MRS757260 BData sets and control blocks
26 PML630Communication Protocol Manual
for events from IED input to presentation on HSI, which is normallydefined to be one second.
• Trigger options• The data attributes know three different trigger options (dchg, qchg,
dupd). Within the BRCB, the two other can be defined (integrity andgeneral interrogation). The attribute Trigger option is a multiple choiceand allows to mask the supported trigger options in this BRCB.
• Integrity period• When integrity is selected in the trigger option attribute, it is needed to
define an integrity period to force the transmission of all data listed inthe DataSet. This is done by the attribute Integrity period. This featurecan be used as a background cycle to ensure that the process image in allpartners is the same. Nobody is perfect and someone in the long chainfrom the contact up to the NCC may have lost an event. The backgroundcycle can repair it.
• General interrogation• A general interrogation is only done on request from a client. Not all
DataSets may contain information which is needed for a general updateof the client. For example, data with T(ransient) = TRUE are not part ofa GI. When the BRCB attribute general interrogation is set to TRUE, aGI request from the client is handled. The report handler transmits alldata defined in the Data-set with their actual values. The IEC 61850standard defines that all buffered events must be transmitted first beforethe GI is started. A running GI must be stopped and a new GI must bestarted, when a new GI request is received while a GI is running.
• Purge buffer (valid only for BRCB)• This BRCB attribute can be used by a client to clean the event buffer
from old events. The events are discarded on request of the client. Thisfeature can be used to delete old events not transmitted to the client dueto stopped communication. After the link is reestablished the client candecide to clean the buffer or to receive the history.
Trigger OptionsIEC 61850 has defined in total five different TrgOp. Three of them belongs to dataattributes and marked per data attribute in the column TrgOp of the CDC tables inpart 7–3. The other two belongs to the configuration of control blocks.
• dchg = data-change• The most commonly used trigger. Whenever a process value has
changed its value either binary or a measurement a transmission is done.The standard does not define how to detect and inform the logical node.
• qchg = quality change
1MRS757260 B Section 6Data sets and control blocks
PML630 27Communication Protocol Manual
• Looking to the possibilities of the quality data attribute type (q) anychanges in the quality description is transmitted.
• dupd = data value update• This trigger option gives the possibility to define that a transmission
must be done on a condition which can be controlled by the application.• integrity
• This trigger forces the transmission of all process values defined in thedata set when a timer value (the integrity period) expires. It can be usedfor example to update a process signal in the background (for example,every 15 minutes).
• general interrogation• This trigger is forced by the clients (= station level IED; NCC gateway,
station HMI, ...). Normally a GI is asked for, when the client and theserver start or restart a session. When the client is able to receive theactual values and when the logical device has scanned all process valuesat least once, an image of the actual process signal status can betransmitted to the client.
Note that the possible trigger options for each attributeare included and defined in the datatype template sectionin SCL.
Link BRCB to a client LNThe BRCB has to know to whom the events shall be transmitted. This is the signalrouting engineering step. The IEC standard 61850–6 describes that this is given byincluding the LN of the client IED in the ReportBlockEnabled option.
The selected client IED with the corresponding LN, for example, ITCI is includedin the SCL structure of the Report Control description of the IED section.
The description of the BRCB with selected DataSet, configured parameters andselected IEDs is included in the SCL file in the IED section in the LN0 structurefor the LD where this LN0 belongs to.
Section 6 1MRS757260 BData sets and control blocks
28 PML630Communication Protocol Manual
.
IEDHSI
Client 1
IEDNCC GW 1
Client 2
IEDNCC GW m
Client 5
IED 1
Server 1
Subnetwork
ITCI2ITCI1IHSI1
LLN0 LD0/LLN0.StatUrg (for feeder status, priority and load shed inhibit status)
LD_1/MMXU1.InhLSSt, FC = ST
LD_1/MMXU1.LodPrioSt, FC = ST
LD_1/CSWI1.Pos, FC = ST
LD_1/MMXU2.InhLSSt, FC = ST
LD_1/MMXU2.LodPrioSt, FC = ST
LD_1/CSWI2.Pos, FC = ST
LD_1/MMXU3.InhLSSt, FC = ST
LD_1/MMXU3.LodPrioSt, FC = ST
LD_1/CSWI3.Pos, FC = ST
LD_1/MMXU4.InhLSSt, FC = ST
LD_1/MMXU4.LodPrioSt, FC = ST
LD_1/CSWI4.Pos, FC = ST
LD_1/MMXU5.InhLSSt, FC = ST
LD_1/MMXU5.LodPrioSt, FC = ST
LD_1/CSWI5.Pos, FC = ST
LD_1/MMXU6.InhLSSt, FC = ST
LD_1/MMXU6.LodPrioSt, FC = ST
LD_1/CSWI6.Pos, FC = ST
LD_1/MMXU7.InhLSSt, FC = ST
LD_1/MMXU7.LodPrioSt, FC = ST
LD_1/CSWI7.Pos, FC = ST
LD_1/MMXU8.InhLSSt, FC = ST
LD_1/MMXU8.LodPrioSt, FC = ST
LD_1/CSWI8.Pos, FC = ST
LD_1/MMXU9.InhLSSt, FC = ST
LD_1/MMXU9.LodPrioSt, FC = ST
LD_1/CSWI9.Pos, FC = ST
LD_1/MMXU10.InhLSSt, FC = ST
LD_1/MMXU10.LodPrioSt, FC = ST
LD_1/CSWI10.Pos, FC = ST
GUID-228080DE-F70A-4E6C-AB08-F6ED10C320A3 V1 EN
Figure 9: Link BRCB to a client LN
1MRS757260 B Section 6Data sets and control blocks
PML630 29Communication Protocol Manual
6.2 GOOSE Control Blocks (GoCB)
Sen
d
Data-set
Rec
eive
Rec
eive
LNLN
LNLN
LN
Sen
d
Data-set
Rec
eive
Rec
eive
LNLN
LN LN
Sen
d
Data-setR
ecei
ve
Rec
eive
LN
LNLNLNLN
LN
Subnetwork
LN0
GoCB
DataSet
InputGoCBGoCB
DataSetDataSet
InputInput
Comm.GSE
LD1
Server
LN0
GoCB
DataSet
InputGoCBGoCB
DataSetDataSet
InputInput
Comm.GSE
LD1
Server
GUID-3AB50F10-A51C-4515-A936-74661339FC81 V1 EN
Figure 10: IEC 61850: Principle operation of GOOSE messages
The Generic object oriented substation event (GOOSE) class model is used todistribute input and output data values between IEDs on bay level (in horizontaldirection) through the use of multicast services. GOOSE messages bypass theserver and enable fast transmission from a publisher to one or several subscribers(receivers).
GOOSE messages are unidirectional, send only messages which request anapplication specific method to secure that the sender and the receiver of themessage operate safely. This implies that the receiver of the GOOSE messagedistributes also GOOSE messages and closes the loop for communication (request— respond on application level). The return message is not a must. It depends onthe application in which way a confirmation may be done.
Section 6 1MRS757260 BData sets and control blocks
30 PML630Communication Protocol Manual
The GOOSE service model of IEC 61850-7-2 provides the possibility for fast andreliable system-wide distribution of input and output data values. Thisimplementation uses a specific scheme of re-transmission to achieve theappropriate level of reliability. When a GOOSE server generates aSendGOOSEMessage request, the current data set values are encoded in a GOOSEmessage and transmitted on the multicast association. The event that causes theserver to invoke a SendGOOSE service is a local application issue as defined inIEC 61850-7-2. Each update may generate a message in order to minimizethroughput time.
Additional reliability is achieved by re-transmitting the same data (with graduallyincreasing SqNum and retransmission time).
T0 retransmission in stable conditions (no event for a long time)
(T0) retransmission in stable conditions may be shortened by an event
T1 shortest retransmission time after the event
T2, T3 retransmission times until achieving the stable conditions time
Time of transmission
T0 (T0) T1 T1 T2 T3 T0
eventGUID-2B4B6A9D-16F6-4D8A-804D-D964E57B580A V1 EN
Figure 11: Transmission time for events
Each message in the retransmission sequence carries a timeAllowedToLiveparameter that informs the receiver of the maximum time to wait for the next re-transmission. If a new message is not received within that time interval, thereceiver assumes that the association is lost. The specific intervals used by anyGOOSE publisher are a local issue. The timeAllowedToLive parameter informssubscribers of how long to wait. In series, (to which PML630 belongs to,), thedetection time is 1.8*timeAllowedToLive to cope with possible transmission delays.
The GOOSE message concept is used for all application functions where two ormore IEDs are involved. Typical example is the station-wide interlockingprocedure or breaker failure protection.
Figure 10 shows the GOOSE concept for three IEDs which interchange GOOSEmessages between each other.
1MRS757260 B Section 6Data sets and control blocks
PML630 31Communication Protocol Manual
To send GOOSE messages a GoCB must be defined and a data set is needed thatcontains the data objects of single data attributes to be send.
A GOOSE message is forced to be transmitted when a trigger change is detectedfor a data attribute. All members of the data set are copied in the send buffer withtheir actual value and the message is sent. The subscribers, who knows the addressof this GOOSE message, receives the telegram. The GOOSE message includes forexample sequence number to verify that all messages are received.
The concept that has to be done in case of for example a lost message is part of theapplication and not described in the standard.
A GoCB has to be defined per GOOSE-DataSet.
GOOSE messages bypass the server and send direct from the communication parton the Ethernet. This is identified for the communication in the SCLcommunication section in the GSE element, where the name of the GoCB is listedunder the ConnectedAP.
Link GoCB to an IEDThe IEDs that should receive the GOOSE message must be known and they haveto be informed in the engineering state that they receive GOOSE messages andwhich one. This is given when the external Reference, the name of the IED and themember of the data set is included in the LN0 under the structure of the LD of thereceiving IED. This part is identified as Inputs.
Section 6 1MRS757260 BData sets and control blocks
32 PML630Communication Protocol Manual
Section 7 Logical node data model
7.1 Common data objects in each logical node
The IEC 61850 standard describes in part 7-4, a Common Logical Node. The dataobjects contained in that LN are both mandatory and optional. The mandatory dataobjects have to be included in each LN. This clause describes the general handlingof the data objects within the series products.
The mandatory data objects as defined in IEC 61850-7-4 as part of the CommonLogical Node are Mode, Behavior, Health and NamePlate.
Mode
The operation modes ON (enabled) and BLOCKED are supported remotely by acommand or locally from the LHMI of the IED. The TEST and the TEST/BLOCKED mode can be operated locally from the LHMI or by using PCM600.
The state OFF can be set from the LHMI or by using PCM600 for the functionshaving the setting 'operation'.
Note also that for functions in other Logical devices than LD0, the Mod can onlybe controlled by communication on LLN0.
Behaviour
The operational mode as given by the Mode control is shown in the data object Behwith the priority rules as described for Beh in clause 6 of IEC 61850-7-4.
The Beh shows the actual state of the function, dependent upon the hierarchydescribed in IEC 61850-7-4, clause 6.
Health
The series products show always only the state "green" = Ok.
NamePlt
The name of the logical node and its relation to namespace definition are shown inthe data object NamePlt as specified for the SCL structure.
1MRS757260 B Section 7Logical node data model
PML630 33Communication Protocol Manual
7.2 Logical nodes for control
7.2.1 IEC61850 generic communication I/O functions DPGGIO
LN type LN prefix LN class Function block name
DPGGIO (revision 1) DP GGIO DPGGIO
Table 2: DPGGIO Logical node data (instance 0)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod a_dINC Oper.ctlVal CO - - Cmd Mode parameter
Oper.origin.orCat CO - - Cmd Mode parameter
Oper.origin.orIdent CO - - Cmd Mode parameter
Oper.ctlNum CO - - Cmd Mode parameter
Oper.T CO - - Cmd Mode parameter
Oper.Test CO - - Cmd Mode parameter
Oper.Check CO - - Cmd Mode parameter
stVal ST - - Mon Mode status parameter for 61850
q ST - - Mon Mode status parameter for 61850
t ST - - Mon Mode status parameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
DPCSO b_dDPC stVal ST - POSITION Mon Double point indication
q ST - POSITION Mon Double point indication
t ST - POSITION Mon Double point indication
7.3 Logical node for monitoring
7.3.1 Station battery supervision SPVNZBAT
LN type LN prefix LN class Function block name
SPVNZBAT (revision 0) SPVN ZBAT SPVNZBAT
Section 7 1MRS757260 BLogical node data model
34 PML630Communication Protocol Manual
Table 3: SPVNZBAT Logical node data
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod a_dINC Oper.ctlVal CO - - Cmd Mode parameter for 61850
Oper.origin.orCat CO - - Cmd Mode parameter for 61850
Oper.origin.orIdent CO - - Cmd Mode parameter for 61850
Oper.ctlNum CO - - Cmd Mode parameter for 61850
Oper.T CO - - Cmd Mode parameter for 61850
Oper.Test CO - - Cmd Mode parameter for 61850
Oper.Check CO - - Cmd Mode parameter for 61850
stVal ST - - Mon Mode status parameter for 61850
q ST - - Mon Mode status parameter for 61850
t ST - - Mon Mode status parameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
BatHi a_dSPS stVal ST - ST_UHIGH Mon Start signal when battery voltageexceeds upper limit
q ST - ST_UHIGH Mon Start signal when battery voltageexceeds upper limit
t ST - ST_UHIGH Mon Start signal when battery voltageexceeds upper limit
BatLo a_dSPS stVal ST - ST_ULOW Mon Start signal when battery voltagedrops below lower limit
q ST - ST_ULOW Mon Start signal when battery voltagedrops below lower limit
t ST - ST_ULOW Mon Start signal when battery voltagedrops below lower limit
Vol b_dMV mag.f MX - U_BATT Mon Service value of the batteryterminal voltage
q MX - U_BATT Mon Service value of the batteryterminal voltage
t MX - U_BATT Mon Service value of the batteryterminal voltage
OpBatLo v1_dSPS stVal ST - AL_ULOW Mon Alarm when voltage has beenbelow lower limit for a set time
q ST - AL_ULOW Mon Alarm when voltage has beenbelow lower limit for a set time
t ST - AL_ULOW Mon Alarm when voltage has beenbelow lower limit for a set time
OpBatHi v1_dSPS stVal ST - AL_UHIGH Mon Alarm when voltage hasexceeded higher limit for a set time
q ST - AL_UHIGH Mon Alarm when voltage hasexceeded higher limit for a set time
t ST - AL_UHIGH Mon Alarm when voltage hasexceeded higher limit for a set time
1MRS757260 B Section 7Logical node data model
PML630 35Communication Protocol Manual
7.3.2 IEC61850 generic communication I/O functions MVGGIO
LN type LN prefix LN class Function block name
MVGGIO (revision 1) MV GGIO MVGGIO
Table 4: MVGGIO Logical node data
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod a_dINC Oper.ctlVal CO - - Cmd Mode parameter
Oper.origin.orCat CO - - Cmd Mode parameter
Oper.origin.orIdent CO - - Cmd Mode parameter
Oper.ctlNum CO - - Cmd Mode parameter
Oper.T CO - - Cmd Mode parameter
Oper.Test CO - - Cmd Mode parameter
Oper.Check CO - - Cmd Mode parameter
stVal ST - - Mon Mode status parameter for 61850
q ST - - Mon Mode status parameter for 61850
t ST - - Mon Mode status parameter for 61850
AnIn a_dMV rangeC.hhLim.f CF - MV hhLim - High High limit
rangeC.hLim.f CF - MV hLim - High limit
rangeC.lLim.f CF - MV lLim - Low limit
rangeC.llLim.f CF - MV llLim - Low Low limit
rangeC.max.f CF - MV max - Maximum value
rangeC.min.f CF - MV min - Minimum value
mag.f MX - VALUE Mon Magnitude of deadband value
subMag.f SV - - - Substituted value
range MX - RANGE Mon Range
q MX - VALUE Mon Magnitude of deadband value
t MX - VALUE Mon Magnitude of deadband value
subEna SV - - - Enable substitution
db CF - MV db - Cycl: Report interval (s), Db: In %of range, Int Db: In %s
zeroDb CF - MV zeroDb - Zero point clamping in 0,001% ofrange
7.3.3 IEC61850 generic communication I/O functions SPGGIO
LN type LN prefix LN class Function block name
SPGGIO (revision 1) SP GGIO SPGGIO
Section 7 1MRS757260 BLogical node data model
36 PML630Communication Protocol Manual
Table 5: SPGGIO Logical node data (instance 0)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod a_dINC Oper.ctlVal CO - - Cmd Mode parameter
Oper.origin.orCat CO - - Cmd Mode parameter
Oper.origin.orIdent CO - - Cmd Mode parameter
Oper.ctlNum CO - - Cmd Mode parameter
Oper.T CO - - Cmd Mode parameter
Oper.Test CO - - Cmd Mode parameter
Oper.Check CO - - Cmd Mode parameter
stVal ST - - Mon Mode status parameter for 61850
q ST - - Mon Mode status parameter for 61850
t ST - - Mon Mode status parameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Ind c_dSPS stVal ST - OUT Mon Output status
q ST - OUT Mon Output status
t ST - OUT Mon Output status
7.4 Logical node for power management
7.4.1 Input interface function for network circuit breaker dataNCBDCSWI
LN type LN prefix LN class Function block name
NCBDCSWI instance 1 (revision 0) NCBD CSWI NCBDCSWI
NCBDLLN0 instance 1 (revision 0) - LLN0 NCBDCSWI
NCBDMMXU instance 1 (revision 0) NCBD MMXU NCBDCSWI
Table 6: NCBDCSWI Logical node data (instance 1)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Pos b_dDPC stVal ST - CB_POS_IND Mon Critical circuit breaker positionsignal indication
q ST - CB_POS_IND Mon Critical circuit breaker positionsignal indication
Table continues on next page
1MRS757260 B Section 7Logical node data model
PML630 37Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
Pos b_dDPC t ST - CB_POS_IND Mon Critical circuit breaker positionsignal indication
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Table 7: NCBDLLN0 Logical node data (instance 1)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod a_dINC Oper.ctlVal CO - - Cmd Mode parameter for 61850
Oper.origin.orCat CO - - Cmd Mode parameter for 61850
Oper.origin.orIdent CO - - Cmd Mode parameter for 61850
Oper.ctlNum CO - - Cmd Mode parameter for 61850
Oper.T CO - - Cmd Mode parameter for 61850
Oper.Test CO - - Cmd Mode parameter for 61850
Oper.Check CO - - Cmd Mode parameter for 61850
stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Table 8: NCBDMMXU Logical node data (instance 1)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Table continues on next page
Section 7 1MRS757260 BLogical node data model
38 PML630Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
TotW c_dMV mag.f MX - CRIT_CB_POW Mon Critical circuit breaker activepower
q MX - CRIT_CB_POW Mon Critical circuit breaker activepower
t MX - CRIT_CB_POW Mon Critical circuit breaker activepower
7.4.2 Contingency based fast load shed function LSCACLS
LN type LN prefix LN class Function block name
LSCACLS instance 1 (revision 0) LSC ACLS LSCACLS
LSCCCLS instance 1 (revision 0) LSC CCLS LSCACLS
LSCCCLS instance 2 (revision 0) LSC CCLS LSCACLS
LSCCCLS instance 3 (revision 0) LSC CCLS LSCACLS
LSCCCLS instance 4 (revision 0) LSC CCLS LSCACLS
LSCGAPC instance 1 (revision 0) LSC GAPC LSCACLS
LSCLLN0 instance 1 (revision 0) - LLN0 LSCACLS
LSCRCLS instance 1 (revision 0) LSC RCLS LSCACLS
Table 9: LSCACLS Logical node data (instance 1)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Op b_dACT general ST T FLS_OPR Mon Load shed operate due to autofast load shedding
q ST T FLS_OPR Mon Load shed operate due to autofast load shedding
t ST T FLS_OPR Mon Load shed operate due to autofast load shedding
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Str f_dACD general ST - FLS_START Mon Signal indicating fastloadshedstarted
q ST - FLS_START Mon Signal indicating fastloadshedstarted
t ST - FLS_START Mon Signal indicating fastloadshedstarted
Table continues on next page
1MRS757260 B Section 7Logical node data model
PML630 39Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
SNtw1Rs v4_dSPC Oper.ctlVal CO - - Cmd Command parameter forIEC61850
Oper.origin.orCat CO - - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO - - Cmd Command parameter forIEC61850
Oper.ctlNum CO - - Cmd Command parameter forIEC61850
Oper.T CO - - Cmd Command parameter forIEC61850
Oper.Test CO - - Cmd Command parameter forIEC61850
Oper.Check CO - - Cmd Command parameter forIEC61850
SNtw2Rs v4_dSPC Oper.ctlVal CO - - Cmd Command parameter forIEC61850
Oper.origin.orCat CO - - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO - - Cmd Command parameter forIEC61850
Oper.ctlNum CO - - Cmd Command parameter forIEC61850
Oper.T CO - - Cmd Command parameter forIEC61850
Oper.Test CO - - Cmd Command parameter forIEC61850
Oper.Check CO - - Cmd Command parameter forIEC61850
SNtw3Rs v4_dSPC Oper.ctlVal CO - - Cmd Command parameter forIEC61850
Oper.origin.orCat CO - - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO - - Cmd Command parameter forIEC61850
Oper.ctlNum CO - - Cmd Command parameter forIEC61850
Oper.T CO - - Cmd Command parameter forIEC61850
Oper.Test CO - - Cmd Command parameter forIEC61850
Oper.Check CO - - Cmd Command parameter forIEC61850
SNtw4Rs v4_dSPC Oper.ctlVal CO - - Cmd Command parameter forIEC61850
Oper.origin.orCat CO - - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO - - Cmd Command parameter forIEC61850
Table continues on next page
Section 7 1MRS757260 BLogical node data model
40 PML630Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
SNtw4Rs v4_dSPC Oper.ctlNum CO - - Cmd Command parameter forIEC61850
Oper.T CO - - Cmd Command parameter forIEC61850
Oper.Test CO - - Cmd Command parameter forIEC61850
Oper.Check CO - - Cmd Command parameter forIEC61850
Rs v4_dSPC Oper.ctlVal CO T - Cmd Command parameter forIEC61850
Oper.origin.orCat CO T - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO T - Cmd Command parameter forIEC61850
Oper.ctlNum CO T - Cmd Command parameter forIEC61850
Oper.T CO T - Cmd Command parameter forIEC61850
Oper.Test CO T - Cmd Command parameter forIEC61850
Oper.Check CO T - Cmd Command parameter forIEC61850
OpCntRs v4_dSPC Oper.ctlVal CO - - Cmd Command parameter forIEC61850
Oper.origin.orCat CO - - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO - - Cmd Command parameter forIEC61850
Oper.ctlNum CO - - Cmd Command parameter forIEC61850
Oper.T CO - - Cmd Command parameter forIEC61850
Oper.Test CO - - Cmd Command parameter forIEC61850
Oper.Check CO - - Cmd Command parameter forIEC61850
Table 10: LSCCCLS Logical node data (instance 1)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
Table continues on next page
1MRS757260 B Section 7Logical node data model
PML630 41Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod c_dINC q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
ManLSCmd v4_dSPC Oper.ctlVal CO - - Cmd Command parameter forIEC61850
Oper.origin.orCat CO - - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO - - Cmd Command parameter forIEC61850
Oper.ctlNum CO - - Cmd Command parameter forIEC61850
Oper.T CO - - Cmd Command parameter forIEC61850
Oper.Test CO - - Cmd Command parameter forIEC61850
Oper.Check CO - - Cmd Command parameter forIEC61850
Table 11: LSCCCLS Logical node data (instance 2)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
ManLSCmd v4_dSPC Oper.ctlVal CO - - Cmd Command parameter forIEC61850
Oper.origin.orCat CO - - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO - - Cmd Command parameter forIEC61850
Oper.ctlNum CO - - Cmd Command parameter forIEC61850
Oper.T CO - - Cmd Command parameter forIEC61850
Oper.Test CO - - Cmd Command parameter forIEC61850
Oper.Check CO - - Cmd Command parameter forIEC61850
Section 7 1MRS757260 BLogical node data model
42 PML630Communication Protocol Manual
Table 12: LSCCCLS Logical node data (instance 3)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
ManLSCmd v4_dSPC Oper.ctlVal CO - - Cmd Command parameter forIEC61850
Oper.origin.orCat CO - - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO - - Cmd Command parameter forIEC61850
Oper.ctlNum CO - - Cmd Command parameter forIEC61850
Oper.T CO - - Cmd Command parameter forIEC61850
Oper.Test CO - - Cmd Command parameter forIEC61850
Oper.Check CO - - Cmd Command parameter forIEC61850
Table 13: LSCCCLS Logical node data (instance 4)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
ManLSCmd v4_dSPC Oper.ctlVal CO - - Cmd Command parameter forIEC61850
Oper.origin.orCat CO - - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO - - Cmd Command parameter forIEC61850
Oper.ctlNum CO - - Cmd Command parameter forIEC61850
Table continues on next page
1MRS757260 B Section 7Logical node data model
PML630 43Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
ManLSCmd v4_dSPC Oper.T CO - - Cmd Command parameter forIEC61850
Oper.Test CO - - Cmd Command parameter forIEC61850
Oper.Check CO - - Cmd Command parameter forIEC61850
Table 14: LSCGAPC Logical node data (instance 1)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Op b_dACT general ST T LS_OPR Mon Loadshed oparate due tofastloadshed or slowloadshed
q ST T LS_OPR Mon Loadshed oparate due tofastloadshed or slowloadshed
t ST T LS_OPR Mon Loadshed oparate due tofastloadshed or slowloadshed
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Str f_dACD general ST - LS_START Mon Signal indicating loadshed started
q ST - LS_START Mon Signal indicating loadshed started
t ST - LS_START Mon Signal indicating loadshed started
Table 15: LSCLLN0 Logical node data (instance 1)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod a_dINC Oper.ctlVal CO - - Cmd Mode parameter for 61850
Oper.origin.orCat CO - - Cmd Mode parameter for 61850
Oper.origin.orIdent CO - - Cmd Mode parameter for 61850
Oper.ctlNum CO - - Cmd Mode parameter for 61850
Oper.T CO - - Cmd Mode parameter for 61850
Oper.Test CO - - Cmd Mode parameter for 61850
Oper.Check CO - - Cmd Mode parameter for 61850
stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
Table continues on next page
Section 7 1MRS757260 BLogical node data model
44 PML630Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod a_dINC t ST - - Mon Mode status value parameter for61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Table 16: LSCRCLS Logical node data (instance 1)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
SNtwGen1 v1_dINS stVal ST - PS3_SN_NO Mon Sub network number ofpowersource3
q ST - PS3_SN_NO Mon Sub network number ofpowersource3
t ST - PS3_SN_NO Mon Sub network number ofpowersource3
SNtwGen2 v1_dINS stVal ST - PS4_SN_NO Mon Sub network number ofpowersource4
q ST - PS4_SN_NO Mon Sub network number ofpowersource4
t ST - PS4_SN_NO Mon Sub network number ofpowersource4
SNtwGen3 v1_dINS stVal ST - PS5_SN_NO Mon Sub network number ofpowersource5
q ST - PS5_SN_NO Mon Sub network number ofpowersource5
t ST - PS5_SN_NO Mon Sub network number ofpowersource5
SNtwGen4 v1_dINS stVal ST - PS6_SN_NO Mon Sub network number ofpowersource6
q ST - PS6_SN_NO Mon Sub network number ofpowersource6
t ST - PS6_SN_NO Mon Sub network number ofpowersource6
SNtwGen5 v1_dINS stVal ST - PS7_SN_NO Mon Sub network number ofpowersource7
q ST - PS7_SN_NO Mon Sub network number ofpowersource7
Table continues on next page
1MRS757260 B Section 7Logical node data model
PML630 45Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
SNtwGen5 v1_dINS t ST - PS7_SN_NO Mon Sub network number ofpowersource7
SNtwGen6 v1_dINS stVal ST - PS8_SN_NO Mon Sub network number ofpowersource8
q ST - PS8_SN_NO Mon Sub network number ofpowersource8
t ST - PS8_SN_NO Mon Sub network number ofpowersource8
SNtwGri1 v1_dINS stVal ST - PS1_SN_NO Mon Sub network number ofpowersource1
q ST - PS1_SN_NO Mon Sub network number ofpowersource1
t ST - PS1_SN_NO Mon Sub network number ofpowersource1
SNtwGri2 v1_dINS stVal ST - PS2_SN_NO Mon Sub network number ofpowersource2
q ST - PS2_SN_NO Mon Sub network number ofpowersource2
t ST - PS2_SN_NO Mon Sub network number ofpowersource2
SNtwLBB1 v1_dINS stVal ST - BB1_SN_NO Mon Sub network number ofloadbusbar1
q ST - BB1_SN_NO Mon Sub network number ofloadbusbar1
t ST - BB1_SN_NO Mon Sub network number ofloadbusbar1
SNtwLBB2 v1_dINS stVal ST - BB2_SN_NO Mon Sub network number ofloadbusbar2
q ST - BB2_SN_NO Mon Sub network number ofloadbusbar2
t ST - BB2_SN_NO Mon Sub network number ofloadbusbar2
SNtwLBB3 v1_dINS stVal ST - BB3_SN_NO Mon Sub network number ofloadbusbar3
q ST - BB3_SN_NO Mon Sub network number ofloadbusbar3
t ST - BB3_SN_NO Mon Sub network number ofloadbusbar3
SNtwLBB4 v1_dINS stVal ST - BB4_SN_NO Mon Sub network number ofloadbusbar4
q ST - BB4_SN_NO Mon Sub network number ofloadbusbar4
t ST - BB4_SN_NO Mon Sub network number ofloadbusbar4
SNtwLBB5 v1_dINS stVal ST - BB5_SN_NO Mon Sub network number ofloadbusbar5
q ST - BB5_SN_NO Mon Sub network number ofloadbusbar5
Table continues on next page
Section 7 1MRS757260 BLogical node data model
46 PML630Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
SNtwLBB5 v1_dINS t ST - BB5_SN_NO Mon Sub network number ofloadbusbar5
SNtwLBB6 v1_dINS stVal ST - BB6_SN_NO Mon Sub network number ofloadbusbar6
q ST - BB6_SN_NO Mon Sub network number ofloadbusbar6
t ST - BB6_SN_NO Mon Sub network number ofloadbusbar6
SNtwCB1 v1_dINS stVal ST - CB1_SN_NO Mon Sub network number of criticalbreaker1
q ST - CB1_SN_NO Mon Sub network number of criticalbreaker1
t ST - CB1_SN_NO Mon Sub network number of criticalbreaker1
SNtwCB10 v1_dINS stVal ST - CB10_SN_NO Mon Sub network number of criticalbreaker10
q ST - CB10_SN_NO Mon Sub network number of criticalbreaker10
t ST - CB10_SN_NO Mon Sub network number of criticalbreaker10
SNtwCB11 v1_dINS stVal ST - CB11_SN_NO Mon Sub network number of criticalbreaker11
q ST - CB11_SN_NO Mon Sub network number of criticalbreaker11
t ST - CB11_SN_NO Mon Sub network number of criticalbreaker11
SNtwCB12 v1_dINS stVal ST - CB12_SN_NO Mon Sub network number of criticalbreaker12
q ST - CB12_SN_NO Mon Sub network number of criticalbreaker12
t ST - CB12_SN_NO Mon Sub network number of criticalbreaker12
SNtwCB13 v1_dINS stVal ST - CB13_SN_NO Mon Sub network number of criticalbreaker13
q ST - CB13_SN_NO Mon Sub network number of criticalbreaker13
t ST - CB13_SN_NO Mon Sub network number of criticalbreaker13
SNtwCB14 v1_dINS stVal ST - CB14_SN_NO Mon Sub network number of criticalbreaker14
q ST - CB14_SN_NO Mon Sub network number of criticalbreaker14
t ST - CB14_SN_NO Mon Sub network number of criticalbreaker14
SNtwCB15 v1_dINS stVal ST - CB15_SN_NO Mon Sub network number of criticalbreaker15
q ST - CB15_SN_NO Mon Sub network number of criticalbreaker15
Table continues on next page
1MRS757260 B Section 7Logical node data model
PML630 47Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
SNtwCB15 v1_dINS t ST - CB15_SN_NO Mon Sub network number of criticalbreaker15
SNtwCB2 v1_dINS stVal ST - CB2_SN_NO Mon Sub network number of criticalbreaker2
q ST - CB2_SN_NO Mon Sub network number of criticalbreaker2
t ST - CB2_SN_NO Mon Sub network number of criticalbreaker2
SNtwCB3 v1_dINS stVal ST - CB3_SN_NO Mon Sub network number of criticalbreaker3
q ST - CB3_SN_NO Mon Sub network number of criticalbreaker3
t ST - CB3_SN_NO Mon Sub network number of criticalbreaker3
SNtwCB4 v1_dINS stVal ST - CB4_SN_NO Mon Sub network number of criticalbreaker4
q ST - CB4_SN_NO Mon Sub network number of criticalbreaker4
t ST - CB4_SN_NO Mon Sub network number of criticalbreaker4
SNtwCB5 v1_dINS stVal ST - CB5_SN_NO Mon Sub network number of criticalbreaker5
q ST - CB5_SN_NO Mon Sub network number of criticalbreaker5
t ST - CB5_SN_NO Mon Sub network number of criticalbreaker5
SNtwCB6 v1_dINS stVal ST - CB6_SN_NO Mon Sub network number of criticalbreaker6
q ST - CB6_SN_NO Mon Sub network number of criticalbreaker6
t ST - CB6_SN_NO Mon Sub network number of criticalbreaker6
SNtwCB7 v1_dINS stVal ST - CB7_SN_NO Mon Sub network number of criticalbreaker7
q ST - CB7_SN_NO Mon Sub network number of criticalbreaker7
t ST - CB7_SN_NO Mon Sub network number of criticalbreaker7
SNtwCB8 v1_dINS stVal ST - CB8_SN_NO Mon Sub network number of criticalbreaker8
q ST - CB8_SN_NO Mon Sub network number of criticalbreaker8
t ST - CB8_SN_NO Mon Sub network number of criticalbreaker8
SNtwCB9 v1_dINS stVal ST - CB9_SN_NO Mon Sub network number of criticalbreaker9
q ST - CB9_SN_NO Mon Sub network number of criticalbreaker9
Table continues on next page
Section 7 1MRS757260 BLogical node data model
48 PML630Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
SNtwCB9 v1_dINS t ST - CB9_SN_NO Mon Sub network number of criticalbreaker9
FLSCnt v1_dINS stVal ST - FLS_CNT Mon Counter indicating number of flstriggers generated
q ST - FLS_CNT Mon Counter indicating number of flstriggers generated
t ST - FLS_CNT Mon Counter indicating number of flstriggers generated
SNtw1Act v1_dSPS stVal ST - ACTIVE_SN1 Mon Sub network1 is active
q ST - ACTIVE_SN1 Mon Sub network1 is active
t ST - ACTIVE_SN1 Mon Sub network1 is active
SNtw2Act v1_dSPS stVal ST - ACTIVE_SN2 Mon Sub network2 is active
q ST - ACTIVE_SN2 Mon Sub network2 is active
t ST - ACTIVE_SN2 Mon Sub network2 is active
SNtw3Act v1_dSPS stVal ST - ACTIVE_SN3 Mon Sub network3 is active
q ST - ACTIVE_SN3 Mon Sub network3 is active
t ST - ACTIVE_SN3 Mon Sub network3 is active
SNtw4Act v1_dSPS stVal ST - ACTIVE_SN4 Mon Sub network4 is active
q ST - ACTIVE_SN4 Mon Sub network4 is active
t ST - ACTIVE_SN4 Mon Sub network4 is active
7.4.3 Sheddable load trip command LSPTRC
LN type LN prefix LN class Function block name
LSLLN0 instance 1 (revision 0) - LLN0 LSPTRC
LSPTRC instance 1 (revision 0) LS PTRC LSPTRC
LSPTRC instance 2 (revision 0) LS PTRC LSPTRC
LSPTRC instance 3 (revision 0) LS PTRC LSPTRC
LSPTRC instance 4 (revision 0) LS PTRC LSPTRC
LSPTRC instance 5 (revision 0) LS PTRC LSPTRC
LSPTRC instance 6 (revision 0) LS PTRC LSPTRC
LSPTRC instance 7 (revision 0) LS PTRC LSPTRC
LSPTRC instance 8 (revision 0) LS PTRC LSPTRC
LSPTRC instance 9 (revision 0) LS PTRC LSPTRC
LSPTRC instance 10 (revision 0) LS PTRC LSPTRC
1MRS757260 B Section 7Logical node data model
PML630 49Communication Protocol Manual
Table 17: LSLLN0 Logical node data (instance 1)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod a_dINC Oper.ctlVal CO - - Cmd Mode parameter for 61850
Oper.origin.orCat CO - - Cmd Mode parameter for 61850
Oper.origin.orIdent CO - - Cmd Mode parameter for 61850
Oper.ctlNum CO - - Cmd Mode parameter for 61850
Oper.T CO - - Cmd Mode parameter for 61850
Oper.Test CO - - Cmd Mode parameter for 61850
Oper.Check CO - - Cmd Mode parameter for 61850
stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Table 18: LSPTRC Logical node data (instance 1)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Tr c_dACT general ST - OPR_SL1 Mon Operate command for thesheddable load1
q ST - OPR_SL1 Mon Operate command for thesheddable load1
t ST - OPR_SL1 Mon Operate command for thesheddable load1
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Section 7 1MRS757260 BLogical node data model
50 PML630Communication Protocol Manual
Table 19: LSPTRC Logical node data (instance 2)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Tr c_dACT general ST - OPR_SL2 Mon Operate command for thesheddable load2
q ST - OPR_SL2 Mon Operate command for thesheddable load2
t ST - OPR_SL2 Mon Operate command for thesheddable load2
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Table 20: LSPTRC Logical node data (instance 3)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Tr c_dACT general ST - OPR_SL3 Mon Operate command for thesheddable load3
q ST - OPR_SL3 Mon Operate command for thesheddable load3
t ST - OPR_SL3 Mon Operate command for thesheddable load3
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Table 21: LSPTRC Logical node data (instance 4)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Table continues on next page
1MRS757260 B Section 7Logical node data model
PML630 51Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
Tr c_dACT general ST - OPR_SL4 Mon Operate command for thesheddable load4
q ST - OPR_SL4 Mon Operate command for thesheddable load4
t ST - OPR_SL4 Mon Operate command for thesheddable load4
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Table 22: LSPTRC Logical node data (instance 5)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Tr c_dACT general ST - OPR_SL5 Mon Operate command for thesheddable load5
q ST - OPR_SL5 Mon Operate command for thesheddable load5
t ST - OPR_SL5 Mon Operate command for thesheddable load5
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Table 23: LSPTRC Logical node data (instance 6)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Tr c_dACT general ST - OPR_SL6 Mon Operate command for thesheddable load6
q ST - OPR_SL6 Mon Operate command for thesheddable load6
t ST - OPR_SL6 Mon Operate command for thesheddable load6
Table continues on next page
Section 7 1MRS757260 BLogical node data model
52 PML630Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Table 24: LSPTRC Logical node data (instance 7)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Tr c_dACT general ST - OPR_SL7 Mon Operate command for thesheddable load7
q ST - OPR_SL7 Mon Operate command for thesheddable load7
t ST - OPR_SL7 Mon Operate command for thesheddable load7
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Table 25: LSPTRC Logical node data (instance 8)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Tr c_dACT general ST - OPR_SL8 Mon Operate command for thesheddable load8
q ST - OPR_SL8 Mon Operate command for thesheddable load8
t ST - OPR_SL8 Mon Operate command for thesheddable load8
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
1MRS757260 B Section 7Logical node data model
PML630 53Communication Protocol Manual
Table 26: LSPTRC Logical node data (instance 9)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Tr c_dACT general ST - OPR_SL9 Mon Operate command for thesheddable load9
q ST - OPR_SL9 Mon Operate command for thesheddable load9
t ST - OPR_SL9 Mon Operate command for thesheddable load9
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Table 27: LSPTRC Logical node data (instance 10)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Tr c_dACT general ST - OPR_SL10 Mon Operate command for thesheddable load10
q ST - OPR_SL10 Mon Operate command for thesheddable load10
t ST - OPR_SL10 Mon Operate command for thesheddable load10
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
7.4.4 Input interface function for sheddable load data LDMMXU
LN type LN prefix LN class Function block name
LDCSWI instance 1 (revision 1) LD CSWI LDMMXU
LDCSWI instance 2 (revision 1) LD CSWI LDMMXU
LDCSWI instance 3 (revision 1) LD CSWI LDMMXU
LDCSWI instance 4 (revision 1) LD CSWI LDMMXU
LDCSWI instance 5 (revision 1) LD CSWI LDMMXU
Section 7 1MRS757260 BLogical node data model
54 PML630Communication Protocol Manual
LDCSWI instance 6 (revision 1) LD CSWI LDMMXU
LDCSWI instance 7 (revision 1) LD CSWI LDMMXU
LDCSWI instance 8 (revision 1) LD CSWI LDMMXU
LDCSWI instance 9 (revision 1) LD CSWI LDMMXU
LDCSWI instance 10 (revision 1) LD CSWI LDMMXU
LDLLN0 instance 1 (revision 0) - LLN0 LDMMXU
LDMMXU instance 1 (revision 1) LD MMXU LDMMXU
LDMMXU instance 2 (revision 1) LD MMXU LDMMXU
LDMMXU instance 3 (revision 1) LD MMXU LDMMXU
LDMMXU instance 4 (revision 1) LD MMXU LDMMXU
LDMMXU instance 5 (revision 1) LD MMXU LDMMXU
LDMMXU instance 6 (revision 1) LD MMXU LDMMXU
LDMMXU instance 7 (revision 1) LD MMXU LDMMXU
LDMMXU instance 8 (revision 1) LD MMXU LDMMXU
LDMMXU instance 9 (revision 1) LD MMXU LDMMXU
LDMMXU instance 10 (revision 1) LD MMXU LDMMXU
Table 28: LDCSWI Logical node data (instance 1)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Pos b_dDPC stVal ST - CBPOSIND_L1 Mon CB compensted signal indicationposition for Load1
q ST - CBPOSIND_L1 Mon CB compensted signal indicationposition for Load1
t ST - CBPOSIND_L1 Mon CB compensted signal indicationposition for Load1
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Table 29: LDCSWI Logical node data (instance 2)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Table continues on next page
1MRS757260 B Section 7Logical node data model
PML630 55Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
Pos b_dDPC stVal ST - CBPOSIND_L2 Mon CB compensted signal indicationposition for Load2
q ST - CBPOSIND_L2 Mon CB compensted signal indicationposition for Load2
t ST - CBPOSIND_L2 Mon CB compensted signal indicationposition for Load2
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Table 30: LDCSWI Logical node data (instance 3)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Pos b_dDPC stVal ST - CBPOSIND_L3 Mon CB compensted signal indicationposition for Load3
q ST - CBPOSIND_L3 Mon CB compensted signal indicationposition for Load3
t ST - CBPOSIND_L3 Mon CB compensted signal indicationposition for Load3
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Table 31: LDCSWI Logical node data (instance 4)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Pos b_dDPC stVal ST - CBPOSIND_L4 Mon CB compensted signal indicationposition for Load4
q ST - CBPOSIND_L4 Mon CB compensted signal indicationposition for Load4
t ST - CBPOSIND_L4 Mon CB compensted signal indicationposition for Load4
Table continues on next page
Section 7 1MRS757260 BLogical node data model
56 PML630Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Table 32: LDCSWI Logical node data (instance 5)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Pos b_dDPC stVal ST - CBPOSIND_L5 Mon CB compensted signal indicationposition for Load5
q ST - CBPOSIND_L5 Mon CB compensted signal indicationposition for Load5
t ST - CBPOSIND_L5 Mon CB compensted signal indicationposition for Load5
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Table 33: LDCSWI Logical node data (instance 6)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Pos b_dDPC stVal ST - CBPOSIND_L6 Mon CB compensted signal indicationposition for Load6
q ST - CBPOSIND_L6 Mon CB compensted signal indicationposition for Load6
t ST - CBPOSIND_L6 Mon CB compensted signal indicationposition for Load6
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
1MRS757260 B Section 7Logical node data model
PML630 57Communication Protocol Manual
Table 34: LDCSWI Logical node data (instance 7)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Pos b_dDPC stVal ST - CBPOSIND_L7 Mon CB compensted signal indicationposition for Load7
q ST - CBPOSIND_L7 Mon CB compensted signal indicationposition for Load7
t ST - CBPOSIND_L7 Mon CB compensted signal indicationposition for Load7
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Table 35: LDCSWI Logical node data (instance 8)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Pos b_dDPC stVal ST - CBPOSIND_L8 Mon CB compensted signal indicationposition for Load8
q ST - CBPOSIND_L8 Mon CB compensted signal indicationposition for Load8
t ST - CBPOSIND_L8 Mon CB compensted signal indicationposition for Load8
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Table 36: LDCSWI Logical node data (instance 9)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Table continues on next page
Section 7 1MRS757260 BLogical node data model
58 PML630Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
Pos b_dDPC stVal ST - CBPOSIND_L9 Mon CB compensted signal indicationposition for Load9
q ST - CBPOSIND_L9 Mon CB compensted signal indicationposition for Load9
t ST - CBPOSIND_L9 Mon CB compensted signal indicationposition for Load9
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Table 37: LDCSWI Logical node data (instance 10)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Pos b_dDPC stVal ST - CBPOSIND_L10 Mon CB compensted signal indicationposition for Load10
q ST - CBPOSIND_L10 Mon CB compensted signal indicationposition for Load10
t ST - CBPOSIND_L10 Mon CB compensted signal indicationposition for Load10
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Table 38: LDLLN0 Logical node data (instance 1)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod a_dINC Oper.ctlVal CO - - Cmd Mode parameter for 61850
Oper.origin.orCat CO - - Cmd Mode parameter for 61850
Oper.origin.orIdent CO - - Cmd Mode parameter for 61850
Oper.ctlNum CO - - Cmd Mode parameter for 61850
Oper.T CO - - Cmd Mode parameter for 61850
Oper.Test CO - - Cmd Mode parameter for 61850
Oper.Check CO - - Cmd Mode parameter for 61850
stVal ST - - Mon Mode status value parameter for61850
Table continues on next page
1MRS757260 B Section 7Logical node data model
PML630 59Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod a_dINC q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Table 39: LDMMXU Logical node data (instance 1)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
TotW c_dMV mag.f MX - P_SHED_L1 Mon Delayed active power on thesheddable load1
q MX - P_SHED_L1 Mon Delayed active power on thesheddable load1
t MX - P_SHED_L1 Mon Delayed active power on thesheddable load1
LodPrioSt v1_dINS stVal ST - PRIO_SHD_L1 Mon Sheddable load1 priority fordisplay in COM 600
q ST - PRIO_SHD_L1 Mon Sheddable load1 priority fordisplay in COM 600
t ST - PRIO_SHD_L1 Mon Sheddable load1 priority fordisplay in COM 600
InhLSSt v1_dINS stVal ST - INBT_STS_L1 Mon Sheddable load1 inhibit status forload shedding
q ST - INBT_STS_L1 Mon Sheddable load1 inhibit status forload shedding
t ST - INBT_STS_L1 Mon Sheddable load1 inhibit status forload shedding
Section 7 1MRS757260 BLogical node data model
60 PML630Communication Protocol Manual
Table 40: LDMMXU Logical node data (instance 3)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
TotW c_dMV mag.f MX - P_SHED_L3 Mon Delayed active power on thesheddable load3
q MX - P_SHED_L3 Mon Delayed active power on thesheddable load3
t MX - P_SHED_L3 Mon Delayed active power on thesheddable load3
LodPrioSt v1_dINS stVal ST - PRIO_SHD_L3 Mon Sheddable load3 priority fordisplay in COM 600
q ST - PRIO_SHD_L3 Mon Sheddable load3 priority fordisplay in COM 600
t ST - PRIO_SHD_L3 Mon Sheddable load3 priority fordisplay in COM 600
InhLSSt v1_dINS stVal ST - INBT_STS_L3 Mon Sheddable load3 inhibit status forload shedding
q ST - INBT_STS_L3 Mon Sheddable load3 inhibit status forload shedding
t ST - INBT_STS_L3 Mon Sheddable load3 inhibit status forload shedding
Table 41: LDMMXU Logical node data (instance 2)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
TotW c_dMV mag.f MX - P_SHED_L2 Mon Delayed active power on thesheddable load2
q MX - P_SHED_L2 Mon Delayed active power on thesheddable load2
Table continues on next page
1MRS757260 B Section 7Logical node data model
PML630 61Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
TotW c_dMV t MX - P_SHED_L2 Mon Delayed active power on thesheddable load2
LodPrioSt v1_dINS stVal ST - PRIO_SHD_L2 Mon Sheddable load2 priority fordisplay in COM 600
q ST - PRIO_SHD_L2 Mon Sheddable load2 priority fordisplay in COM 600
t ST - PRIO_SHD_L2 Mon Sheddable load2 priority fordisplay in COM 600
InhLSSt v1_dINS stVal ST - INBT_STS_L2 Mon Sheddable load2 inhibit status forload shedding
q ST - INBT_STS_L2 Mon Sheddable load2 inhibit status forload shedding
t ST - INBT_STS_L2 Mon Sheddable load2 inhibit status forload shedding
Table 42: LDMMXU Logical node data (instance 7)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
TotW c_dMV mag.f MX - P_SHED_L7 Mon Delayed active power on thesheddable load7
q MX - P_SHED_L7 Mon Delayed active power on thesheddable load7
t MX - P_SHED_L7 Mon Delayed active power on thesheddable load7
LodPrioSt v1_dINS stVal ST - PRIO_SHD_L7 Mon Sheddable load7 priority fordisplay in COM 600
q ST - PRIO_SHD_L7 Mon Sheddable load7 priority fordisplay in COM 600
t ST - PRIO_SHD_L7 Mon Sheddable load7 priority fordisplay in COM 600
InhLSSt v1_dINS stVal ST - INBT_STS_L7 Mon Sheddable load7 inhibit status forload shedding
q ST - INBT_STS_L7 Mon Sheddable load7 inhibit status forload shedding
t ST - INBT_STS_L7 Mon Sheddable load7 inhibit status forload shedding
Section 7 1MRS757260 BLogical node data model
62 PML630Communication Protocol Manual
Table 43: LDMMXU Logical node data (instance 6)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
TotW c_dMV mag.f MX - P_SHED_L6 Mon Delayed active power on thesheddable load6
q MX - P_SHED_L6 Mon Delayed active power on thesheddable load6
t MX - P_SHED_L6 Mon Delayed active power on thesheddable load6
LodPrioSt v1_dINS stVal ST - PRIO_SHD_L6 Mon Sheddable load6 priority fordisplay in COM 600
q ST - PRIO_SHD_L6 Mon Sheddable load6 priority fordisplay in COM 600
t ST - PRIO_SHD_L6 Mon Sheddable load6 priority fordisplay in COM 600
InhLSSt v1_dINS stVal ST - INBT_STS_L6 Mon Sheddable load6 inhibit status forload shedding
q ST - INBT_STS_L6 Mon Sheddable load6 inhibit status forload shedding
t ST - INBT_STS_L6 Mon Sheddable load6 inhibit status forload shedding
Table 44: LDMMXU Logical node data (instance 5)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
TotW c_dMV mag.f MX - P_SHED_L5 Mon Delayed active power on thesheddable load5
q MX - P_SHED_L5 Mon Delayed active power on thesheddable load5
Table continues on next page
1MRS757260 B Section 7Logical node data model
PML630 63Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
TotW c_dMV t MX - P_SHED_L5 Mon Delayed active power on thesheddable load5
LodPrioSt v1_dINS stVal ST - PRIO_SHD_L5 Mon Sheddable load5 priority fordisplay in COM 600
q ST - PRIO_SHD_L5 Mon Sheddable load5 priority fordisplay in COM 600
t ST - PRIO_SHD_L5 Mon Sheddable load5 priority fordisplay in COM 600
InhLSSt v1_dINS stVal ST - INBT_STS_L5 Mon Sheddable load5 inhibit status forload shedding
q ST - INBT_STS_L5 Mon Sheddable load5 inhibit status forload shedding
t ST - INBT_STS_L5 Mon Sheddable load5 inhibit status forload shedding
Table 45: LDMMXU Logical node data (instance 4)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
TotW c_dMV mag.f MX - P_SHED_L4 Mon Delayed active power on thesheddable load4
q MX - P_SHED_L4 Mon Delayed active power on thesheddable load4
t MX - P_SHED_L4 Mon Delayed active power on thesheddable load4
LodPrioSt v1_dINS stVal ST - PRIO_SHD_L4 Mon Sheddable load4 priority fordisplay in COM 600
q ST - PRIO_SHD_L4 Mon Sheddable load4 priority fordisplay in COM 600
t ST - PRIO_SHD_L4 Mon Sheddable load4 priority fordisplay in COM 600
InhLSSt v1_dINS stVal ST - INBT_STS_L4 Mon Sheddable load4 inhibit status forload shedding
q ST - INBT_STS_L4 Mon Sheddable load4 inhibit status forload shedding
t ST - INBT_STS_L4 Mon Sheddable load4 inhibit status forload shedding
Section 7 1MRS757260 BLogical node data model
64 PML630Communication Protocol Manual
Table 46: LDMMXU Logical node data (instance 10)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
TotW c_dMV mag.f MX - P_SHED_L10 Mon Delayed active power on thesheddable load10
q MX - P_SHED_L10 Mon Delayed active power on thesheddable load10
t MX - P_SHED_L10 Mon Delayed active power on thesheddable load10
LodPrioSt v1_dINS stVal ST - PRIO_SHD_L10 Mon Sheddable load10 priority fordisplay in COM 600
q ST - PRIO_SHD_L10 Mon Sheddable load10 priority fordisplay in COM 600
t ST - PRIO_SHD_L10 Mon Sheddable load10 priority fordisplay in COM 600
InhLSSt v1_dINS stVal ST - INBT_STS_L10 Mon Sheddable load10 inhibit statusfor load shedding
q ST - INBT_STS_L10 Mon Sheddable load10 inhibit statusfor load shedding
t ST - INBT_STS_L10 Mon Sheddable load10 inhibit statusfor load shedding
Table 47: LDMMXU Logical node data (instance 9)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
TotW c_dMV mag.f MX - P_SHED_L9 Mon Delayed active power on thesheddable load9
q MX - P_SHED_L9 Mon Delayed active power on thesheddable load9
Table continues on next page
1MRS757260 B Section 7Logical node data model
PML630 65Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
TotW c_dMV t MX - P_SHED_L9 Mon Delayed active power on thesheddable load9
LodPrioSt v1_dINS stVal ST - PRIO_SHD_L9 Mon Sheddable load9 priority fordisplay in COM 600
q ST - PRIO_SHD_L9 Mon Sheddable load9 priority fordisplay in COM 600
t ST - PRIO_SHD_L9 Mon Sheddable load9 priority fordisplay in COM 600
InhLSSt v1_dINS stVal ST - INBT_STS_L9 Mon Sheddable load9 inhibit status forload shedding
q ST - INBT_STS_L9 Mon Sheddable load9 inhibit status forload shedding
t ST - INBT_STS_L9 Mon Sheddable load9 inhibit status forload shedding
Table 48: LDMMXU Logical node data (instance 8)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
TotW c_dMV mag.f MX - P_SHED_L8 Mon Delayed active power on thesheddable load8
q MX - P_SHED_L8 Mon Delayed active power on thesheddable load8
t MX - P_SHED_L8 Mon Delayed active power on thesheddable load8
LodPrioSt v1_dINS stVal ST - PRIO_SHD_L8 Mon Sheddable load8 priority fordisplay in COM 600
q ST - PRIO_SHD_L8 Mon Sheddable load8 priority fordisplay in COM 600
t ST - PRIO_SHD_L8 Mon Sheddable load8 priority fordisplay in COM 600
InhLSSt v1_dINS stVal ST - INBT_STS_L8 Mon Sheddable load8 inhibit status forload shedding
q ST - INBT_STS_L8 Mon Sheddable load8 inhibit status forload shedding
t ST - INBT_STS_L8 Mon Sheddable load8 inhibit status forload shedding
Section 7 1MRS757260 BLogical node data model
66 PML630Communication Protocol Manual
7.4.5 Input interface function for network power source dataPWSMMXU
LN type LN prefix LN class Function block name
PWSACLS instance 1 (revision 0) PWS ACLS PWSMMXU
PWSACLS instance 2 (revision 0) PWS ACLS PWSMMXU
PWSGCSWI instance 1 (revision 0) PWSG CSWI PWSMMXU
PWSGCSWI instance 2 (revision 0) PWSG CSWI PWSMMXU
PWSGCSWI instance 3 (revision 0) PWSG CSWI PWSMMXU
PWSGCSWI instance 4 (revision 0) PWSG CSWI PWSMMXU
PWSGCSWI instance 5 (revision 0) PWSG CSWI PWSMMXU
PWSGCSWI instance 6 (revision 0) PWSG CSWI PWSMMXU
PWSGMMXU instance 1 (revision 0) PWSG MMXU PWSMMXU
PWSGMMXU instance 2 (revision 0) PWSG MMXU PWSMMXU
PWSGMMXU instance 3 (revision 0) PWSG MMXU PWSMMXU
PWSGMMXU instance 4 (revision 0) PWSG MMXU PWSMMXU
PWSGMMXU instance 5 (revision 0) PWSG MMXU PWSMMXU
PWSGMMXU instance 6 (revision 0) PWSG MMXU PWSMMXU
PWSLLN0 instance 1 (revision 0) - LLN0 PWSMMXU
PWSTCSWI instance 1 (revision 0) PWST CSWI PWSMMXU
PWSTCSWI instance 2 (revision 0) PWST CSWI PWSMMXU
PWSTMMXU instance 1 (revision 2) PWST MMXU PWSMMXU
PWSTMMXU instance 2 (revision 2) PWST MMXU PWSMMXU
Table 49: PWSACLS Logical node data (instance 1)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Op b_dACT general ST T SLS_OP_GRD1 Mon Latched output indicating slowload trigger for grid 1
q ST T SLS_OP_GRD1 Mon Latched output indicating slowload trigger for grid 1
t ST T SLS_OP_GRD1 Mon Latched output indicating slowload trigger for grid 1
Str f_dACD general ST - SLOW_ST_GRD1 Mon Slow load shedding start in gridtransformer 1
q ST - SLOW_ST_GRD1 Mon Slow load shedding start in gridtransformer 1
t ST - SLOW_ST_GRD1 Mon Slow load shedding start in gridtransformer 1
MaxDmdTm v1_dINS stVal ST - T_INT_GRD1 Mon time interval for demand valuecalc of grid transformer 1
q ST - T_INT_GRD1 Mon time interval for demand valuecalc of grid transformer 1
Table continues on next page
1MRS757260 B Section 7Logical node data model
PML630 67Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
MaxDmdTm v1_dINS t ST - T_INT_GRD1 Mon time interval for demand valuecalc of grid transformer 1
MaxDmdExc v1_dSPS stVal ST - MD_OPR_GRD1 Mon Max demand operated for grid 1
q ST - MD_OPR_GRD1 Mon Max demand operated for grid 1
t ST - MD_OPR_GRD1 Mon Max demand operated for grid 1
TrfOvLod v1_dSPS stVal ST - OLS_OPR_GRD1 Mon Over load shed operated for gridtransformer 1
q ST - OLS_OPR_GRD1 Mon Over load shed operated for gridtransformer 1
t ST - OLS_OPR_GRD1 Mon Over load shed operated for gridtransformer 1
MaxDmdSEn v1_dSPS stVal ST - EN_MAXD_GRD1 Mon Maximum demand sheddingenabled grid1
q ST - EN_MAXD_GRD1 Mon Maximum demand sheddingenabled grid1
t ST - EN_MAXD_GRD1 Mon Maximum demand sheddingenabled grid1
SlwLSEn v1_dSPS stVal ST - SLS_EN_GRD1 Mon Enable signal for slow load triggerfor grid transformer 1
q ST - SLS_EN_GRD1 Mon Enable signal for slow load triggerfor grid transformer 1
t ST - SLS_EN_GRD1 Mon Enable signal for slow load triggerfor grid transformer 1
MaxCurTrf v2_dMV mag.f MX - MAX_I_GRD1 Mon Maximum current of grid1
q MX - MAX_I_GRD1 Mon Maximum current of grid1
t MX - MAX_I_GRD1 Mon Maximum current of grid1
MaxDmdS v2_dMV mag.f MX - MAX_DEM_GRD1 Mon Maximum power demand for grid1
q MX - MAX_DEM_GRD1 Mon Maximum power demand for grid1
t MX - MAX_DEM_GRD1 Mon Maximum power demand for grid1
TmElaTrf v2_dMV mag.f MX - ETIME_GRD1 Mon Elapsed time after overloadtrigger start up from grid 1
q MX - ETIME_GRD1 Mon Elapsed time after overloadtrigger start up from grid 1
t MX - ETIME_GRD1 Mon Elapsed time after overloadtrigger start up from grid 1
TmIDMTTrf v2_dMV mag.f MX - IDMTIME_GRD1 Mon Total time after which Slow loadtrigger will be generated from grid1
q MX - IDMTIME_GRD1 Mon Total time after which Slow loadtrigger will be generated from grid1
t MX - IDMTIME_GRD1 Mon Total time after which Slow loadtrigger will be generated from grid1
Table continues on next page
Section 7 1MRS757260 BLogical node data model
68 PML630Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
Rs v4_dSPC Oper.ctlVal CO T - Cmd Command parameter forIEC61850
Oper.origin.orCat CO T - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO T - Cmd Command parameter forIEC61850
Oper.ctlNum CO T - Cmd Command parameter forIEC61850
Oper.T CO T - Cmd Command parameter forIEC61850
Oper.Test CO T - Cmd Command parameter forIEC61850
Oper.Check CO T - Cmd Command parameter forIEC61850
Table 50: PWSACLS Logical node data (instance 2)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Op b_dACT general ST T SLS_OP_GRD2 Mon Latched output indicating slowload trigger for grid 2
q ST T SLS_OP_GRD2 Mon Latched output indicating slowload trigger for grid 2
t ST T SLS_OP_GRD2 Mon Latched output indicating slowload trigger for grid 2
Str f_dACD general ST - SLOW_ST_GRD2 Mon Slow load shedding start in gridtransformer 2
q ST - SLOW_ST_GRD2 Mon Slow load shedding start in gridtransformer 2
t ST - SLOW_ST_GRD2 Mon Slow load shedding start in gridtransformer 2
MaxDmdTm v1_dINS stVal ST - T_INT_GRD2 Mon time interval for demand valuecalc of grid transformer 2
q ST - T_INT_GRD2 Mon time interval for demand valuecalc of grid transformer 2
t ST - T_INT_GRD2 Mon time interval for demand valuecalc of grid transformer 2
MaxDmdExc v1_dSPS stVal ST - MD_OPR_GRD2 Mon Max demand operated for grid 1
q ST - MD_OPR_GRD2 Mon Max demand operated for grid 1
t ST - MD_OPR_GRD2 Mon Max demand operated for grid 1
TrfOvLod v1_dSPS stVal ST - OLS_OPR_GRD2 Mon Over load shed operated for gridtransformer 2
q ST - OLS_OPR_GRD2 Mon Over load shed operated for gridtransformer 2
t ST - OLS_OPR_GRD2 Mon Over load shed operated for gridtransformer 2
Table continues on next page
1MRS757260 B Section 7Logical node data model
PML630 69Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
MaxDmdSEn v1_dSPS stVal ST - EN_MAXD_GRD2 Mon Maximum demand sheddingenabled grid2
q ST - EN_MAXD_GRD2 Mon Maximum demand sheddingenabled grid2
t ST - EN_MAXD_GRD2 Mon Maximum demand sheddingenabled grid2
SlwLSEn v1_dSPS stVal ST - SLS_EN_GRD2 Mon Enable signal for slow load triggerfor grid transformer 2
q ST - SLS_EN_GRD2 Mon Enable signal for slow load triggerfor grid transformer 2
t ST - SLS_EN_GRD2 Mon Enable signal for slow load triggerfor grid transformer 2
MaxCurTrf v2_dMV mag.f MX - MAX_I_GRD2 Mon Maximum current of grid2
q MX - MAX_I_GRD2 Mon Maximum current of grid2
t MX - MAX_I_GRD2 Mon Maximum current of grid2
MaxDmdS v2_dMV mag.f MX - MAX_DEM_GRD2 Mon Maximum power demand for grid2
q MX - MAX_DEM_GRD2 Mon Maximum power demand for grid2
t MX - MAX_DEM_GRD2 Mon Maximum power demand for grid2
TmElaTrf v2_dMV mag.f MX - ETIME_GRD2 Mon Elapsed time after overloadtrigger start up from grid 2
q MX - ETIME_GRD2 Mon Elapsed time after overloadtrigger start up from grid 2
t MX - ETIME_GRD2 Mon Elapsed time after overloadtrigger start up from grid 2
TmIDMTTrf v2_dMV mag.f MX - IDMTIME_GRD2 Mon Total time after which Slow loadtrigger will be generated from grid2
q MX - IDMTIME_GRD2 Mon Total time after which Slow loadtrigger will be generated from grid2
t MX - IDMTIME_GRD2 Mon Total time after which Slow loadtrigger will be generated from grid2
Rs v4_dSPC Oper.ctlVal CO T - Cmd Command parameter forIEC61850
Oper.origin.orCat CO T - Cmd Command parameter forIEC61850
Oper.origin.orIdent CO T - Cmd Command parameter forIEC61850
Oper.ctlNum CO T - Cmd Command parameter forIEC61850
Table continues on next page
Section 7 1MRS757260 BLogical node data model
70 PML630Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
Rs v4_dSPC Oper.T CO T - Cmd Command parameter forIEC61850
Oper.Test CO T - Cmd Command parameter forIEC61850
Oper.Check CO T - Cmd Command parameter forIEC61850
Table 51: PWSGCSWI Logical node data (instance 2)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Pos b_dDPC stVal ST - CB_IND_GEN2 Mon Position indication of the CBconnecting generator2 to thesystem
q ST - CB_IND_GEN2 Mon Position indication of the CBconnecting generator2 to thesystem
t ST - CB_IND_GEN2 Mon Position indication of the CBconnecting generator2 to thesystem
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Table 52: PWSGCSWI Logical node data (instance 1)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Pos b_dDPC stVal ST - CB_IND_GEN1 Mon Position indication of the CBconnecting generator1 to thesystem
q ST - CB_IND_GEN1 Mon Position indication of the CBconnecting generator1 to thesystem
t ST - CB_IND_GEN1 Mon Position indication of the CBconnecting generator1 to thesystem
Table continues on next page
1MRS757260 B Section 7Logical node data model
PML630 71Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Table 53: PWSGCSWI Logical node data (instance 3)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Pos b_dDPC stVal ST - CB_IND_GEN3 Mon Position indication of the CBconnecting generator3 to thesystem
q ST - CB_IND_GEN3 Mon Position indication of the CBconnecting generator3 to thesystem
t ST - CB_IND_GEN3 Mon Position indication of the CBconnecting generator3 to thesystem
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Table 54: PWSGCSWI Logical node data (instance 4)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Pos b_dDPC stVal ST - CB_IND_GEN4 Mon Position indication of the CBconnecting generator4 to thesystem
q ST - CB_IND_GEN4 Mon Position indication of the CBconnecting generator4 to thesystem
t ST - CB_IND_GEN4 Mon Position indication of the CBconnecting generator4 to thesystem
Table continues on next page
Section 7 1MRS757260 BLogical node data model
72 PML630Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Table 55: PWSGCSWI Logical node data (instance 5)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Pos b_dDPC stVal ST - CB_IND_GEN5 Mon Position indication of the CBconnecting generator5 to thesystem
q ST - CB_IND_GEN5 Mon Position indication of the CBconnecting generator5 to thesystem
t ST - CB_IND_GEN5 Mon Position indication of the CBconnecting generator5 to thesystem
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Table 56: PWSGCSWI Logical node data (instance 6)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Pos b_dDPC stVal ST - CB_IND_GEN6 Mon Position indication of the CBconnecting generator6 to thesystem
q ST - CB_IND_GEN6 Mon Position indication of the CBconnecting generator6 to thesystem
t ST - CB_IND_GEN6 Mon Position indication of the CBconnecting generator6 to thesystem
Table continues on next page
1MRS757260 B Section 7Logical node data model
PML630 73Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Table 57: PWSGMMXU Logical node data (instance 6)
DO name DO type DA name FC T Signal Mon/Cmd
Description
TotW c_dMV mag.f MX - ACTPOW_GEN6 Mon Active Power on generator 6
q MX - ACTPOW_GEN6 Mon Active Power on generator 6
t MX - ACTPOW_GEN6 Mon Active Power on generator 6
GovMod v1_dINS stVal ST - GOV_MOD_GEN6 Mon Generator 6 governor mode
q ST - GOV_MOD_GEN6 Mon Generator 6 governor mode
t ST - GOV_MOD_GEN6 Mon Generator 6 governor mode
AvaW v2_dMV mag.f MX - AVA_POW_GEN6 Mon Available power from Generator 6
q MX - AVA_POW_GEN6 Mon Available power from Generator 6
t MX - AVA_POW_GEN6 Mon Available power from Generator 6
Table 58: PWSGMMXU Logical node data (instance 5)
DO name DO type DA name FC T Signal Mon/Cmd
Description
TotW c_dMV mag.f MX - ACTPOW_GEN5 Mon Active Power on generator 5
q MX - ACTPOW_GEN5 Mon Active Power on generator 5
t MX - ACTPOW_GEN5 Mon Active Power on generator 5
GovMod v1_dINS stVal ST - GOV_MOD_GEN5 Mon Generator 5 governor mode
q ST - GOV_MOD_GEN5 Mon Generator 5 governor mode
t ST - GOV_MOD_GEN5 Mon Generator 5 governor mode
AvaW v2_dMV mag.f MX - AVA_POW_GEN5 Mon Available power from Generator 5
q MX - AVA_POW_GEN5 Mon Available power from Generator 5
t MX - AVA_POW_GEN5 Mon Available power from Generator 5
Table 59: PWSGMMXU Logical node data (instance 4)
DO name DO type DA name FC T Signal Mon/Cmd
Description
TotW c_dMV mag.f MX - ACTPOW_GEN4 Mon Active Power on generator 4
q MX - ACTPOW_GEN4 Mon Active Power on generator 4
t MX - ACTPOW_GEN4 Mon Active Power on generator 4
Table continues on next page
Section 7 1MRS757260 BLogical node data model
74 PML630Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
GovMod v1_dINS stVal ST - GOV_MOD_GEN4 Mon Generator 4 governor mode
q ST - GOV_MOD_GEN4 Mon Generator 4 governor mode
t ST - GOV_MOD_GEN4 Mon Generator 4 governor mode
AvaW v2_dMV mag.f MX - AVA_POW_GEN4 Mon Available power from Generator 4
q MX - AVA_POW_GEN4 Mon Available power from Generator 4
t MX - AVA_POW_GEN4 Mon Available power from Generator 4
Table 60: PWSGMMXU Logical node data (instance 3)
DO name DO type DA name FC T Signal Mon/Cmd
Description
TotW c_dMV mag.f MX - ACTPOW_GEN3 Mon Active Power on generator 3
q MX - ACTPOW_GEN3 Mon Active Power on generator 3
t MX - ACTPOW_GEN3 Mon Active Power on generator 3
GovMod v1_dINS stVal ST - GOV_MOD_GEN3 Mon Generator 3 governor mode
q ST - GOV_MOD_GEN3 Mon Generator 3 governor mode
t ST - GOV_MOD_GEN3 Mon Generator 3 governor mode
AvaW v2_dMV mag.f MX - AVA_POW_GEN3 Mon Available power from Generator 3
q MX - AVA_POW_GEN3 Mon Available power from Generator 3
t MX - AVA_POW_GEN3 Mon Available power from Generator 3
Table 61: PWSGMMXU Logical node data (instance 1)
DO name DO type DA name FC T Signal Mon/Cmd
Description
TotW c_dMV mag.f MX - ACTPOW_GEN1 Mon Active Power on generator 1
q MX - ACTPOW_GEN1 Mon Active Power on generator 1
t MX - ACTPOW_GEN1 Mon Active Power on generator 1
GovMod v1_dINS stVal ST - GOV_MOD_GEN1 Mon Generator 1 governor mode
q ST - GOV_MOD_GEN1 Mon Generator 1 governor mode
t ST - GOV_MOD_GEN1 Mon Generator 1 governor mode
AvaW v2_dMV mag.f MX - AVA_POW_GEN1 Mon Available power from Generator 1
q MX - AVA_POW_GEN1 Mon Available power from Generator 1
t MX - AVA_POW_GEN1 Mon Available power from Generator 1
1MRS757260 B Section 7Logical node data model
PML630 75Communication Protocol Manual
Table 62: PWSGMMXU Logical node data (instance 2)
DO name DO type DA name FC T Signal Mon/Cmd
Description
TotW c_dMV mag.f MX - ACTPOW_GEN2 Mon Active Power on generator 2
q MX - ACTPOW_GEN2 Mon Active Power on generator 2
t MX - ACTPOW_GEN2 Mon Active Power on generator 2
GovMod v1_dINS stVal ST - GOV_MOD_GEN2 Mon Generator 2 governor mode
q ST - GOV_MOD_GEN2 Mon Generator 2 governor mode
t ST - GOV_MOD_GEN2 Mon Generator 2 governor mode
AvaW v2_dMV mag.f MX - AVA_POW_GEN2 Mon Available power from Generator 2
q MX - AVA_POW_GEN2 Mon Available power from Generator 2
t MX - AVA_POW_GEN2 Mon Available power from Generator 2
Table 63: PWSLLN0 Logical node data (instance 1)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod a_dINC Oper.ctlVal CO - - Cmd Mode parameter for 61850
Oper.origin.orCat CO - - Cmd Mode parameter for 61850
Oper.origin.orIdent CO - - Cmd Mode parameter for 61850
Oper.ctlNum CO - - Cmd Mode parameter for 61850
Oper.T CO - - Cmd Mode parameter for 61850
Oper.Test CO - - Cmd Mode parameter for 61850
Oper.Check CO - - Cmd Mode parameter for 61850
stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Table 64: PWSTCSWI Logical node data (instance 1)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Pos b_dDPC stVal ST - CB_IND_GRD1 Mon Position indication of the CBconnecting grid transformer 1 tothe system
Table continues on next page
Section 7 1MRS757260 BLogical node data model
76 PML630Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
Pos b_dDPC q ST - CB_IND_GRD1 Mon Position indication of the CBconnecting grid transformer 1 tothe system
t ST - CB_IND_GRD1 Mon Position indication of the CBconnecting grid transformer 1 tothe system
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Table 65: PWSTCSWI Logical node data (instance 2)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Pos b_dDPC stVal ST - CB_IND_GRD2 Mon Position indication of the CBconnecting grid transformer 2 tothe system
q ST - CB_IND_GRD2 Mon Position indication of the CBconnecting grid transformer 2 tothe system
t ST - CB_IND_GRD2 Mon Position indication of the CBconnecting grid transformer 2 tothe system
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Table 66: PWSTMMXU Logical node data (instance 2)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
TotW c_dMV mag.f MX - ACTPOW_GRD2 Mon Active power on grid transformer 1
q MX - ACTPOW_GRD2 Mon Active power on grid transformer 1
Table continues on next page
1MRS757260 B Section 7Logical node data model
PML630 77Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
TotW c_dMV t MX - ACTPOW_GRD2 Mon Active power on grid transformer 1
SlwLSBlk v1_dSPS stVal ST - SLS_BLK_GRD2 Mon Slow load shed trigger block forgrid 2
q ST - SLS_BLK_GRD2 Mon Slow load shed trigger block forgrid 2
t ST - SLS_BLK_GRD2 Mon Slow load shed trigger block forgrid 2
AvaW v2_dMV mag.f MX - AVA_POW_GRD2 Mon Available power from gridtransformer 2
q MX - AVA_POW_GRD2 Mon Available power from gridtransformer 2
t MX - AVA_POW_GRD2 Mon Available power from gridtransformer 2
GriAMax v2_dMV mag.f MX - ST_IMAX_GRD2 Mon Setting above which over loadshed is initiated in grid2
q MX - ST_IMAX_GRD2 Mon Setting above which over loadshed is initiated in grid2
t MX - ST_IMAX_GRD2 Mon Setting above which over loadshed is initiated in grid2
Table 67: PWSTMMXU Logical node data (instance 1)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
TotW c_dMV mag.f MX - ACTPOW_GRD1 Mon Active power on grid transformer 1
q MX - ACTPOW_GRD1 Mon Active power on grid transformer 1
t MX - ACTPOW_GRD1 Mon Active power on grid transformer 1
SlwLSBlk v1_dSPS stVal ST - SLS_BLK_GRD1 Mon Slow load shed trigger block forgrid 1
q ST - SLS_BLK_GRD1 Mon Slow load shed trigger block forgrid 1
t ST - SLS_BLK_GRD1 Mon Slow load shed trigger block forgrid 1
AvaW v2_dMV mag.f MX - AVA_POW_GRD1 Mon Available power from gridtransformer 1
q MX - AVA_POW_GRD1 Mon Available power from gridtransformer 1
t MX - AVA_POW_GRD1 Mon Available power from gridtransformer 1
Table continues on next page
Section 7 1MRS757260 BLogical node data model
78 PML630Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
GriAMax v2_dMV mag.f MX - ST_IMAX_GRD1 Mon Setting above which over loadshed is initiated in grid1
q MX - ST_IMAX_GRD1 Mon Setting above which over loadshed is initiated in grid1
t MX - ST_IMAX_GRD1 Mon Setting above which over loadshed is initiated in grid1
7.4.6 Output interface function for sub network data SNWRCLS
LN type LN prefix LN class Function block name
SNWARCLS instance 1 (revision 0) SNWA RCLS SNWRCLS
SNWLLN0 instance 1 (revision 0) - LLN0 SNWRCLS
SNWLRCLS instance 1 (revision 0) SNWL RCLS SNWRCLS
Table 68: SNWARCLS Logical node data (instance 1)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
PrioSt v1_dINS stVal ST - MAN_SHD_PRIO Mon Manual load shed Priority
q ST - MAN_SHD_PRIO Mon Manual load shed Priority
t ST - MAN_SHD_PRIO Mon Manual load shed Priority
ALodPrio1 v2_dMV mag.f MX - CUM_LOD_PR1 Mon Cumulative load priority 1
q MX - CUM_LOD_PR1 Mon Cumulative load priority 1
t MX - CUM_LOD_PR1 Mon Cumulative load priority 1
ALodPrio10 v2_dMV mag.f MX - CUM_LOD_PR10 Mon Cumulative load priority 10
q MX - CUM_LOD_PR10 Mon Cumulative load priority 10
t MX - CUM_LOD_PR10 Mon Cumulative load priority 10
ALodPrio11 v2_dMV mag.f MX - CUM_LOD_PR11 Mon Cumulative load priority 11
q MX - CUM_LOD_PR11 Mon Cumulative load priority 11
t MX - CUM_LOD_PR11 Mon Cumulative load priority 11
ALodPrio12 v2_dMV mag.f MX - CUM_LOD_PR12 Mon Cumulative load priority 12
q MX - CUM_LOD_PR12 Mon Cumulative load priority 12
Table continues on next page
1MRS757260 B Section 7Logical node data model
PML630 79Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
ALodPrio12 v2_dMV t MX - CUM_LOD_PR12 Mon Cumulative load priority 12
ALodPrio13 v2_dMV mag.f MX - CUM_LOD_PR13 Mon Cumulative load priority 13
q MX - CUM_LOD_PR13 Mon Cumulative load priority 13
t MX - CUM_LOD_PR13 Mon Cumulative load priority 13
ALodPrio14 v2_dMV mag.f MX - CUM_LOD_PR14 Mon Cumulative load priority 14
q MX - CUM_LOD_PR14 Mon Cumulative load priority 14
t MX - CUM_LOD_PR14 Mon Cumulative load priority 14
ALodPrio15 v2_dMV mag.f MX - CUM_LOD_PR15 Mon Cumulative load priority 15
q MX - CUM_LOD_PR15 Mon Cumulative load priority 15
t MX - CUM_LOD_PR15 Mon Cumulative load priority 15
ALodPrio16 v2_dMV mag.f MX - CUM_LOD_PR16 Mon Cumulative load priority 16
q MX - CUM_LOD_PR16 Mon Cumulative load priority 16
t MX - CUM_LOD_PR16 Mon Cumulative load priority 16
ALodPrio17 v2_dMV mag.f MX - CUM_LOD_PR17 Mon Cumulative load priority 17
q MX - CUM_LOD_PR17 Mon Cumulative load priority 17
t MX - CUM_LOD_PR17 Mon Cumulative load priority 17
ALodPrio18 v2_dMV mag.f MX - CUM_LOD_PR18 Mon Cumulative load priority 18
q MX - CUM_LOD_PR18 Mon Cumulative load priority 18
t MX - CUM_LOD_PR18 Mon Cumulative load priority 18
ALodPrio19 v2_dMV mag.f MX - CUM_LOD_PR19 Mon Cumulative load priority 19
q MX - CUM_LOD_PR19 Mon Cumulative load priority 19
t MX - CUM_LOD_PR19 Mon Cumulative load priority 19
ALodPrio2 v2_dMV mag.f MX - CUM_LOD_PR2 Mon Cumulative load priority 2
q MX - CUM_LOD_PR2 Mon Cumulative load priority 2
t MX - CUM_LOD_PR2 Mon Cumulative load priority 2
ALodPrio3 v2_dMV mag.f MX - CUM_LOD_PR3 Mon Cumulative load priority 3
q MX - CUM_LOD_PR3 Mon Cumulative load priority 3
t MX - CUM_LOD_PR3 Mon Cumulative load priority 3
ALodPrio4 v2_dMV mag.f MX - CUM_LOD_PR4 Mon Cumulative load priority 4
q MX - CUM_LOD_PR4 Mon Cumulative load priority 4
t MX - CUM_LOD_PR4 Mon Cumulative load priority 4
ALodPrio5 v2_dMV mag.f MX - CUM_LOD_PR5 Mon Cumulative load priority 5
q MX - CUM_LOD_PR5 Mon Cumulative load priority 5
t MX - CUM_LOD_PR5 Mon Cumulative load priority 5
ALodPrio6 v2_dMV mag.f MX - CUM_LOD_PR6 Mon Cumulative load priority 6
q MX - CUM_LOD_PR6 Mon Cumulative load priority 6
t MX - CUM_LOD_PR6 Mon Cumulative load priority 6
ALodPrio7 v2_dMV mag.f MX - CUM_LOD_PR7 Mon Cumulative load priority 7
q MX - CUM_LOD_PR7 Mon Cumulative load priority 7
Table continues on next page
Section 7 1MRS757260 BLogical node data model
80 PML630Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
ALodPrio7 v2_dMV t MX - CUM_LOD_PR7 Mon Cumulative load priority 7
ALodPrio8 v2_dMV mag.f MX - CUM_LOD_PR8 Mon Cumulative load priority 8
q MX - CUM_LOD_PR8 Mon Cumulative load priority 8
t MX - CUM_LOD_PR8 Mon Cumulative load priority 8
ALodPrio9 v2_dMV mag.f MX - CUM_LOD_PR9 Mon Cumulative load priority 9
q MX - CUM_LOD_PR9 Mon Cumulative load priority 9
t MX - CUM_LOD_PR9 Mon Cumulative load priority 9
Table 69: SNWLLN0 Logical node data (instance 1)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod a_dINC Oper.ctlVal CO - - Cmd Mode parameter for 61850
Oper.origin.orCat CO - - Cmd Mode parameter for 61850
Oper.origin.orIdent CO - - Cmd Mode parameter for 61850
Oper.ctlNum CO - - Cmd Mode parameter for 61850
Oper.T CO - - Cmd Mode parameter for 61850
Oper.Test CO - - Cmd Mode parameter for 61850
Oper.Check CO - - Cmd Mode parameter for 61850
stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Table 70: SNWLRCLS Logical node data (instance 1)
DO name DO type DA name FC T Signal Mon/Cmd
Description
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
Mod c_dINC stVal ST - - Mon Mode status value parameter for61850
q ST - - Mon Mode status value parameter for61850
t ST - - Mon Mode status value parameter for61850
NtwLSPrio v1_dINS stVal ST - SN_SHED_PRIO Mon subnetwork shed priority
Table continues on next page
1MRS757260 B Section 7Logical node data model
PML630 81Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
NtwLSPrio v1_dINS q ST - SN_SHED_PRIO Mon subnetwork shed priority
t ST - SN_SHED_PRIO Mon subnetwork shed priority
LSOpSt v1_dINS stVal ST - LS_OPR_STS Mon Load shed operator status
q ST - LS_OPR_STS Mon Load shed operator status
t ST - LS_OPR_STS Mon Load shed operator status
LSBlkSt v1_dSPS stVal ST - SN_FLS_BLK Mon Fast Load shed block
q ST - SN_FLS_BLK Mon Fast Load shed block
t ST - SN_FLS_BLK Mon Fast Load shed block
NtwSt v1_dSPS stVal ST - LS_MOD_INFO Mon Load shed enable and active
q ST - LS_MOD_INFO Mon Load shed enable and active
t ST - LS_MOD_INFO Mon Load shed enable and active
SlwLSBlkSt v1_dSPS stVal ST - SLOW_LS_BLK Mon Slow Load shed block
q ST - SLOW_LS_BLK Mon Slow Load shed block
t ST - SLOW_LS_BLK Mon Slow Load shed block
NtwLoad v2_dMV mag.f MX - SN_LOAD Mon Total load in the subnetwork
q MX - SN_LOAD Mon Total load in the subnetwork
t MX - SN_LOAD Mon Total load in the subnetwork
NtwLodInhM v2_dMV mag.f MX - LOD_INBT_OPR Mon Total inhibited Power by theoperator in the subnetwork
q MX - LOD_INBT_OPR Mon Total inhibited Power by theoperator in the subnetwork
t MX - LOD_INBT_OPR Mon Total inhibited Power by theoperator in the subnetwork
NtwLodInhS v2_dMV mag.f MX - LOD_INBT_SYS Mon Total inhibited Power by thesystem in the subnetwork
q MX - LOD_INBT_SYS Mon Total inhibited Power by thesystem in the subnetwork
t MX - LOD_INBT_SYS Mon Total inhibited Power by thesystem in the subnetwork
NtwLodMm v2_dMV mag.f MX - LOD_MISMATCH Mon Total load mismatch in thesubnetwork
q MX - LOD_MISMATCH Mon Total load mismatch in thesubnetwork
t MX - LOD_MISMATCH Mon Total load mismatch in thesubnetwork
NtwALodShd v2_dMV mag.f MX - ACTU_SHD Mon Actual Load shed
q MX - ACTU_SHD Mon Actual Load shed
t MX - ACTU_SHD Mon Actual Load shed
NtwMLodShd v2_dMV mag.f MX - MUST_SHD Mon Must be load shed
q MX - MUST_SHD Mon Must be load shed
t MX - MUST_SHD Mon Must be load shed
Table continues on next page
Section 7 1MRS757260 BLogical node data model
82 PML630Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
NtwPwrBal v2_dMV mag.f MX - LOD_IMBAL Mon Load generation balance at thetime of previous load shed prioritycalculation
q MX - LOD_IMBAL Mon Load generation balance at thetime of previous load shed prioritycalculation
t MX - LOD_IMBAL Mon Load generation balance at thetime of previous load shed prioritycalculation
NtwPwrDiff v2_dMV mag.f MX - DIF_MUSTACTU Mon Difference between the must beload shed and actual load shed
q MX - DIF_MUSTACTU Mon Difference between the must beload shed and actual load shed
t MX - DIF_MUSTACTU Mon Difference between the must beload shed and actual load shed
NtwShbLod v2_dMV mag.f MX - SN_TOT_SL Mon Total amount of sheddable loadin sub network
q MX - SN_TOT_SL Mon Total amount of sheddable loadin sub network
t MX - SN_TOT_SL Mon Total amount of sheddable loadin sub network
NtwAvbPwr v2_dMV mag.f MX - SN_AVA_POW Mon Total Available power in thesubnetwork
q MX - SN_AVA_POW Mon Total Available power in thesubnetwork
t MX - SN_AVA_POW Mon Total Available power in thesubnetwork
7.5 Logical node for disturbance recorder function
7.5.1 Disturbance report DRRDRE
LN type LN prefix LN class Function block name
DRRDRE (revision 0) DR RDRE DRRDRE
Table 71: DRRDRE Logical node data
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod a_dINC Oper.ctlVal CO - - Cmd Mode parameter for 61850
Oper.origin.orCat CO - - Cmd Mode parameter for 61850
Oper.origin.orIdent CO - - Cmd Mode parameter for 61850
Oper.ctlNum CO - - Cmd Mode parameter for 61850
Oper.T CO - - Cmd Mode parameter for 61850
Table continues on next page
1MRS757260 B Section 7Logical node data model
PML630 83Communication Protocol Manual
DO name DO type DA name FC T Signal Mon/Cmd
Description
Mod a_dINC Oper.Test CO - - Cmd Mode parameter for 61850
Oper.Check CO - - Cmd Mode parameter for 61850
stVal ST - - Mon Mode status parameter for 61850
q ST - - Mon Mode status parameter for 61850
t ST - - Mon Mode status parameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Behaviour parameter for 61850
t ST - Beh Mon Behaviour parameter for 61850
FltNum b_dINS stVal ST - Fault number Mon Disturbance fault number
q ST - Fault number Mon Disturbance fault number
t ST - Fault number Mon Disturbance fault number
MemUsed b_dINS stVal ST - Memory used Mon Memory usage (0-100%)
q ST - Memory used Mon Memory usage (0-100%)
t ST - Memory used Mon Memory usage (0-100%)
RcdMade d_dSPS stVal ST - RECMADE Mon Disturbance recording made
q ST - RECMADE Mon Disturbance recording made
t ST - RECMADE Mon Disturbance recording made
RcdStr d_dSPS stVal ST - RECSTART Mon Disturbance recording started
q ST - RECSTART Mon Disturbance recording started
t ST - RECSTART Mon Disturbance recording started
RcdClr v2_dSPS stVal ST - CLEARED Mon All disturbances in thedisturbance report cleared
q ST - CLEARED Mon All disturbances in thedisturbance report cleared
t ST - CLEARED Mon All disturbances in thedisturbance report cleared
MemUsedAlm v2_dSPS stVal ST - MEMUSED Mon More than 80% of memory used
q ST - MEMUSED Mon More than 80% of memory used
t ST - MEMUSED Mon More than 80% of memory used
7.6 Load shedding power management function blocks
The table Function block and logical device instances describes the relationshipbetween the load shedding power management function blocks and the logicaldevices in the IEC 61850 structure. Also mentioned are the maximum number ofpossible instances of the function blocks, which depend on the power networkconfiguration. These function blocks are automatically instantiated in the ACT ofPCM600 by the IED Connectivity package (Configuration Wizard feature).
Section 7 1MRS757260 BLogical node data model
84 PML630Communication Protocol Manual
Table 72: Function block and logical device instances
Function block name Maximum number ofinstances
Associated logicaldevice and instancenumber
Description
NCBDCSWI 15 NCBD_<instancenumber, based onnetwork circuit breakerindex>
For network circuitbreaker index number,see ApplicationEngineering Guide
LSCACLS 1 LSC_1 -
LSPTRC 6 LS_<1..6> Instance numberdepends on number ofload busbars
LDMMXU 6 LD_<1..6> Instance numberdepends on number ofload busbars
PWSMMXU 1 PWS_1 One instance for allpower sources
SNWRCLS 4 SNW_<1..4> Instance numberdepends on maximumnumber ofsubnetworks (numberof busbars with powersources)
1MRS757260 B Section 7Logical node data model
PML630 85Communication Protocol Manual
86
Section 8 Glossary
ACSI Abstract communication service interfaceBeh BehaviorBRCB Report control blockCID Configured IED descriptionDA Data attributeDO Data objectEMC Electromagnetic compatibilityEthernet A standard for connecting a family of frame-based
computer networking technologies into a LANFCDA Functional constraint data attributeGI General interrogationGoCB GOOSE control blockGOOSE Generic Object-Oriented Substation EventGSE Generic substation eventHMI Human-machine interfaceICD IED capability descriptionIEC International Electrotechnical CommissionIEC 61850 International standard for substation communication and
modelingIEC 61850-8-1 A communication protocol based on the IEC 61850
standard seriesIED Intelligent electronic deviceIET600 Integrated Engineering Toolbox in PCM600IP address A set of four numbers between 0 and 255, separated by
periods. Each server connected to the Internet is assigneda unique IP address that specifies the location for the TCP/IP protocol.
ISO International Standard OrganizationLAN Local area networkLD Logical deviceLD0 Logical device zero (0)LHMI Local human-machine interface
1MRS757260 B Section 8Glossary
PML630 87Communication Protocol Manual
LLN0 Logical node zero (0)LN Logical nodeLogical device Also known as LD. Representation of a group of functions.
Each function is defined as a logical node. A physicaldevice has one or several LDs.
MICS Model implementation conformance statementMMS Manufacturing message specification; Metering
management systemNCC Network control centerPCM600 Protection and Control IED ManagerPICS Protocol implementation conformance statementPIXIT Protocol implementation extra information for testingSAB600 Substation automation builder toolSC Single commandSCD Substation configuration descriptionSCL XML-based substation description configuration language
defined by IEC 61850SMT Signal Matrix tool in PCM600SNTP Simple Network Time ProtocolTCP/IP Transmission Control Protocol/Internet ProtocolXML Extensible markup language
Section 8 1MRS757260 BGlossary
88 PML630Communication Protocol Manual