Lighting as it should be. For everyone

Post on 11-Sep-2021

1 views 0 download

Transcript of Lighting as it should be. For everyone

Lighting as it should be. For everyone

www.sirijaya.com

Office Residential Industry Street Façade

Y W YEE

Senior Production and Engineering Manager–Production and Product Development Division.Sirijaya Industries Sdn.Bhd.

Approx. 1 mil sq ft. With total built up

area of 479,244 sq ft .

Locate :

9, Lebuh Perusahaan Klebang 9,

IGB Industries Park,

Chemor Perak Malaysia.

Yearly sales turnover RM 150 million (USD 50 million)

Emerging sales and service office

Sales office in Kuala Lumpur, Australia and Singapore

Our market shares

We are currently the local fluorescent lighting

fixtures market leader in Malaysia which

covered 60% of the local market shares.

With 55% distributed in Malaysia and 45% Overseas

Monthly Production Capacity

Luminaries – 300K Lamp and Starter holders – 5,000 K

Present & location

Our core revenue and well-being offeris powered by 3 businesses

Lighting fixtures (GFP & RE)

Lamp holder & Starter holder

Lighting Components

91%7%

2%

BUSINESS MODEL

How can we serve your agenda?A partnership designed around you

A lighting company of leading businesses creating value with meaningful innovationsthat improve people's health and well-being

The lighting industry is undergoing a

from analogue to digital

from conventional to LED

radical / remarkable transformation.

Major key factors towards - Green……

1. Energy efficiency (cost saving). Minimize the wattage and reduce the lighting power intensities.

Maximize natural light harvesting and utilization.

Implement the energy management control system for more saving.

Enhance the use of energy efficient luminaire and light source.

2. Protect environment. Life span the longer the better as

to reduce the disposal.

3. Reduce green house gas emission. Reduce of mercury vapor contents. LED are preferable.

www.greenbuildingindex.org

Rating system Buildings are divided into the following categories: The rating system for all 4 building categories is as follows: 1) Non Residential Existing Building (NREB).2) Non Residential New Construction (NRNC).3) Residential New Construction (RNC).4) Residential Existing Building (REB).

MS1525 – Overall ContentFirst Edition – 2001Second Edition – 2007Third Edition - 2014Section 1 ScopeSection 2 Normative referenceSection 3 Terms and definitionsSection 4 Architectural and passive design StrategySection 5 Building envelopeSection 6 Lighting designSection 7 Electric power and distributionSection 8 Air conditioning and mechanical ventilation (ACMV) systemSection 9 Energy management control systemSection 19 Building energy simulation method (an alternative compliance method)

MS 1525 Revision

Section 6 – Lighting Design

6.1 Scope

Lightings in outdoor, theatrical, medical & dental, emergency, outdoor

recreational, display, exterior monument, special lighting, emergency,

security, signage, store front application are out of scope.

6.2 Lighting Intensities

(a) Table 13 sets performance criteria for lighting illuminance (Lux).

(b) Ballast shall not exceed 6W

6.3 Lighting Intensities

(a) Table 14 sets performance criteria for lighting intensities W/m².

6.4 Exterior Building lighting

(a) Net area intensities shall not exceed 5 W/m²

6.5 Lighting Controls

(a) All lighting systems (except emergency) to be provided with

controls.

(b) Lighting loads exceeding 100W should have automatic control.

(c) Lighting zones for daylighting control, switching zones < 30m².

6.6 Operation & Maintenance

Reviewing Section 6

MS 1525 Revision

Lighting Level is determined by the age of users

A person 60 years

old will need about

15 times higher

lighting level than a

10 year old.

Lighting Level

Maximium of LPD through lux design level

Method of Practiced

Traditional

Electronic T5

SSL (LED)

Good Practiced

Best Practiced

Best Advance Technology

DLM-Food with only CRI 70 for instance has very good color rendering of meat.

MS 1525 Revision

Section 4 Architectural and Passive

Design Strategy.

4.01 Sustainable design approach

4.02 Passive design strategy

4.03 Site planning and orientation

4.04 Daylighting

4.05 Façade design

4.06 Natural ventilation

4.07 Thermal insulation

4.08 Strategic landscaping

4.09 Renewable energy

4.10 Other considerations

How do we transform to LED ???Retrofit……. LED Tube During T8 Florescent lamp replacement in existing building…..

Current Major Retrofit Transformation

LED System portfolio – today

TLD T8 TLD T5 T8 TLED LED Strip LED Square

Size 26 mm dia. 16 mm dia. 26 mm dia. 2 ft per strip 1’ x 1’

Ballast / Driver EM / EL EM / EL Built in driver External driver External driver

Nominal lumen

output

3250 lm 2600 lm 2100 lm 1300 / 2200 lm 1250 lm

Power 36 W 28 W 18 W 9 / 19 W 11.8 W

Efficiency (System) 2015

~90 lm/W ~93 lm/W ~116 lm/W ~144 / 115 lm/W ~ 104 lm/W

Mercury contents > 10 mg 1.4 mg No No No

UV / IR Yes Yes No No No

System Lifetime 14 k hrs 24k hrs 30k hrs 30k / 50k hrs 50k hrs

ROI

How do we transform to LED ???Retrofit……. LED Bulb. During Halogen bulb lamp replacement in existing buliding…..

Current Major Transformation

LED System portfolio – today

Halogen Incandescent LED MR16 LED Bulb

Size GU 5.3 E27 GU 5.3 E27

Transformer / Driver Magnetic /electronic No Magnetic/electronic Built in driver

Nominal lumen output 1000 - 1450 lm 210 - 2700 lm 290 / 490 lm 600 / 806 / 1055 lm

Power 35 / 50 W 25 - 150 W 5 / 7 W 8 / 11 / 13 W

Efficiency (System) 2015

~28 - 29 lm/W ~8 – 18 lm/W ~58 / 70 lm/W ~75 / 73 / 81 lm/W

Gas contents Yes Yes No No

UV / IR Yes Yes No No

System Lifetime 2k hrs 1k hrs 15k hrs 25k hrs

ROI

Strategy 1+2+3+4 –

1. Up-lamping + 2. Up-gearing + 3. Up-design concept +

4. Up-Energy Mgt system control

Solution for office lighting

Performance

Provide optimum lighting illuminance and meet many &

diversify task requirements. Creating a visually satisfying

environment with good lighting design.

Efficiency

Minimise misused of unnecessary energy and maximize

ambient performance.

Visual Comfort

Primary consideration to put at their ease for a calm

reassurance ambient .

Sustainability

Reducing environment footprint by minimising resources and

energy.

Selection of Luminaires & Type of Lamps

Indoor High/Low bay

Warehouse,

ProductionsOffice

Lighting level and distribution.

Visual Comfort

Key illumination parameters in office lighting

Key parameters for office lighting, acc. to EN 2464-1 (European Standard)

DESIGN SIMULATION DETAILS

AREA : 10m X 10m

MOUNTING HEIGHT : 3.00 metres

WORKING PLANE : 0.80 Metres

REFLECTANCE : Ceiling:70%

Walls :50% Floor:20%

Model Name SRU 128 (1 X 28W T5) SAC LED LINE VDU (2 X 11W LED LINE)

Light Source 2600 lm 2980 lm

CRI 80 80

Design Area (m²) 100m² 100m²

Design Lighting Fixtures 24 units 24 units

Average lux 456.59 lx 462.15 lx

UGR -Viewing Direction=0

-Viewing Direction=90

14

16

15

15

System Wattage 31.5 W 27.5 W

System Lumen 2318 lm 2358 lm

Total System Wattage Consumption

(W)756 W 660 W

Lighting Power Density (W/m²) 7.56 W/m² 6.6 W/m²

DLM-Food with only CRI 70 for instance has very good color rendering of meat.

INTRODUCTION TO HEALTHCARE INTERNAL LIGHTING

Hospital & Healthcare Building General Illuminance Standards – CIBSE LG2, EN2464-1

COI≤ 3.3

a. Application scope:

1) Lighting recommendations for a variety of tasks carried out within hospitals and medical

premises, particularly tasks associated with clinical observation, treatment and care.

2) A room within which surgical, obstetrical and endoscopic procedures are preferred.

b. COI: an open-ended numerical scale ranking the suitability of a lamp for the purpose of visual

detection of the presence or onset of cyanosis.

In general, an index used to measure the comfort/suitability of a light source

c. The lower the value of the index, the better the lamp is deems to be for that purpose

d. Recommend values:

1. The CCT of lamps should between 3300K and 5300K. (Preferable 4000K)

2. CRI > 90

3. A recommended cyanosis observation index(COI) should not greater than 3.3.

General introduction of cyanosis observation index

660 nm

660 nmR9

380nm 800nm

Violet Red

• Wavelength of 380nm-

800nm is occupied by Light

waves.

• It is identified by colours

Violet to Red

“Best Of Nature, Best of Science”“Refresh. Replenish. Revitalise.”

“Transform Yourself. Bring Out The Inner Beauty”

Dr KentConsultation Group

Dr. Kent Cheong, MDDoctor of Medicine

American Association of Aesthetic Medicine (AAAM)

Beauty Health Consultant

Coordinator of Infection & Antibiotic Control

Life Support Instructor

Mobile : +6014 646 1352

Email : fokusmylive87@hotmail.com

Skype : cheong.yee.hung

Facebook: www.facebook.com/kent.cheong.9

Blog : livewithtruehealth.blogspot.com

Dr Kent Cheong

Medical Doctor

Serviced in Sarawak previously,

currently

Back in Selangor

Privileging in Anesthesiology and

Intensive Care

Coordinator In charge of Infection and

Antibiotic Control in regional hospital

Life Support Instructor

Human body color changes

&

Assessment in Medical

illness

Neonatal Jaundice

Kernicterus

Neonatal Cyanosis

Skin Rashes

Viral Exanthem

Idiopathic Thrombocytopenic Purpura

Eczema

Pink Puffer

Blue Bloater

Adult Jaundice

Cellulitis

The principle is based on the magnitude of the calculated change in the color appearance of fully

oxygenated blood(100% oxygen saturation) and of oxygen-reduced blood(50% oxygen saturation), resulting

from the application of the lamp under evaluation when compared with a reference illuminant.

For detailed calculation method, please refer to the Interior lighting of Australian/New Zealand Standard, Part 2.5: Hospital and medical tasks.

COI mathematical calculation method

Testing facilities at our lab

• Goniophotometer

• Spectrophotocolorimeter

• EMC Test

• Glow Wire Test

• Needle flame Test

• Dustproof Test

• Salt spray Test

• Power Analyzer

• Temperature Test

Spectral power distribution colour / 940

50% 100% COI

1.4341 2.6848 2.0595

REFLECTANCE VALUES OF BLOOD AND CIE DISTRIBUTION COEFFICIENTS

Spectral power distribution colour / 840

50% 100% COI

5.6705 9.7412 7.7058

REFLECTANCE VALUES OF BLOOD AND CIE DISTRIBUTION COEFFICIENTS

Sensors + Control

LED Light Source Efficacy

Daylight Diming

The luminaire will be dim

down to a dim level when

enough daylight is present.

Occupancy Control

The luminaire will be

switched OFF when no

presence is detected.

Ask Specific

Programming of switching or

dimming where task area are

needed and where are not

need.

Welcome to Digital Light Solutions.

The next step in energy efficient lighting

Intelligent Lighting Control - truly adaptive

individual and system control that delivers

maximum energy efficiency.

Added Value to lighting solution for more energy saving

Dimming via Mains

Use Case: Non-dimmable Installation

Added Value to lighting solution for more energy saving

Dimming via Mains

Use Case: Non-dimmable Installation

Added Value to lighting solution for more energy saving

Dimming via Mains

Use Case: 1-10V Installation

Added Value to lighting solution for more energy saving

Use Case: Car Park

Dimming via Mains

Added Value to lighting solution for more energy saving

Use Case: Office with Sensor

Dimming via Mains

luxCONTROL lighting control system

Compact control module with ambient light

sensor and motion sensor

Continuous Suspension Trunking Lighting (Direct / Indirect)

Aluminum Extrusion Trunking Lighting (direct / Indirect)

Extrusion Plaster Recessed Trunking Lighting

Extrusion Plaster Recessed Continuous Trunking Lighting

Continuous Suspension Curve Lighting (Direct / Indirect)

Green Batten (2R) SGB B5 (120) SGB D5 (140)

Eclipse Double Ended suspension Batten

Eclipse Direct / Indirect recessed fitting

References

1) THE HORIZON (PHASE 2) 2A – Certified

2) THE HORIZON (PHASE 2) B3 – Certified

3) THE HORIZON (PHASE 2) 5.2 – Certified

4) THE HORIZON (PHASE 2) B1 – Gold

5) THE HORIZON (PHASE 2) B4 – Gold

6) MENARA BINJAI - Certified

7) SHAFTSBURY SQUARE, CYBERJAYA, - Gold

8) ELKEN DISTRIBUTION CENTRE - Gold

9) JAYA 33 (PHASE 2) - Certified

10) MENARA TECHNIP - Gold