Lecture 19: HVAC Outside Air Systems and Modeling Guidelines
Material prepared by GARD Analytics, Inc. and University of Illinoisat Urbana-Champaign under contract to the National Renewable Energy
Laboratory. All material Copyright 2002-2003 U.S.D.O.E. - All rights reserved
2
Purpose of this Lecture
Discuss Outside Air IAQ requirements force us to draw
fresh air in from the outside environment
Outside air (OA) can have a significant impact on the building energy requirements
Show how OA is specified in EnergyPlus
3
Keywords Covered in this Lecture
Air Loop Equipment ListOutside Air SystemOutside Air MixerController:Outside AirOutside Air Inlet Node ListReview of other related keywords
4
Components: Special Case - Outside Air System
OUTSIDE AIR SYSTEM is a subsystem component
OA System Controller ListOA System Equipment ListOA System Availability Manager
List
5
OA System Equipment List
System component type outside air mixer, coil, heat
exchanger
System component name
Repeat for each air loop component
6
Air Loop Equipment List - Example
AIR LOOP EQUIPMENT LIST,
OA Sys 1 Equipment, !- Name
OUTSIDE AIR MIXER, !- KEY--System Component 1
OA Mixing Box 1; !- Component Name 1
7
Outside Air System - Example
OUTSIDE AIR SYSTEM,
OA Sys 1, !- Name
OA Sys 1 Controllers, !- Name: Controller List
OA Sys 1 Equipment, !- Name of an Air Loop Equipment List
VAV Sys 1 Avail List; !- Name of a System Availability Manager List
8
Outside Air Mixer
Mixed_Air_NodeOutside_Air_Stream_NodeRelief_Air_Stream_NodeReturn_Air_Stream_Node
9
Outside Air Mixer - Example
OUTSIDE AIR MIXER, OA Mixing Box 1, !- Name Mixed Air Node 1, !- Mixed_Air_Node Outside Air Inlet Node 1, !- Outside_Air_Stream_Node Relief Air Outlet Node 1, !- Relief_Air_Stream_Node VAV Sys 1 Inlet Node; !- Return_Air_Stream_Node
10
CONTROLLER LIST, OA Sys 1 Controllers, !- Name CONTROLLER:OUTSIDE AIR, !- Controller Type 1 OA Controller 1; !- Controller Name 1
Outside Air Mixer – Controller List
11
Controller:Outside Air
Control_NodeActuated_NodeMinimum outside air flow rateMaximum outside air flow rateTemperature limitTemperature lower limit
12
Controller:Outside Air - Example
CONTROLLER:OUTSIDE AIR, OA Controller 1, !- Name ECONOMIZER, !- EconomizerChoice NO RETURN AIR TEMP LIMIT, !- ReturnAirTempLimit NO RETURN AIR ENTHALPY LIMIT, !- ReturnAirEnthalpyLimit NO LOCKOUT, !- Lockout FIXED MINIMUM, !- MinimumLimit Mixed Air Node 1, !- Control_Node Outside Air Inlet Node 1, !- Actuated_Node autosize, !- min outside air flow rate {m3/s} autosize, !- max outside air flow rate {m3/s} 19., !- temperature limit {C} 4., !- temperature lower limit {C} 0.0, !- enthalpy limit {J/kg} Relief Air Outlet Node 1, !- Relief_Air_Outlet_Node VAV Sys 1 Inlet Node, !- Return_Air_Node Min OA Sched; !- Minimum Outside Air Schedule Name
13
TermReheat with Outside Air Example
North
Zone
East
Zone
Resistive
Zone
Supply FanR
etu
rn A
ir M
ixe
r
Zo
ne A
ir Sp
litter
CC
VAV Box:ReHeat
VAV Box:ReHeat
Mixed OutsideAir Box
Relief Air
Outside Air
VAV Box: ReHeat
North
Zone
East
Zone
Resistive
Zone
Supply FanR
etu
rn A
ir M
ixe
r
Zo
ne A
ir Sp
litter
CC
VAV Box:ReHeat
VAV Box:ReHeat
Mixed OutsideAir Box
Relief Air
Outside Air
VAV Box: ReHeat
Air Loop contains the Mixed Air System
14
TermReheat Main Branch with OA
SystemSupply Fan
CCMixed OutsideAir Box
Relief Air
Outside AirSupply Fan
CCMixed OutsideAir Box
Relief Air
Outside Air
BRANCH, Air Loop Main Branch, !- Branch Name 1.3, !- Maximum Branch Flow Rate {m3/s} OUTSIDE AIR SYSTEM, !- Comp1 Type OA Sys 1, !- Comp1 Name VAV Sys 1 Inlet Node, !- Comp1 Inlet Node Name Mixed Air Node, !- Comp1 Outlet Node Name PASSIVE, !- Comp1 Branch Control Type FAN:SIMPLE:ConstVolume, !- Comp2 Type Supply Fan 1, !- Comp2 Name Mixed Air Node, !- Comp2 Inlet Node Name< cooling coil >
15
TermReheat Outside Air Node List
Mixed OutsideAir Box
Relief Air
Outside Air
Mixed OutsideAir Box
Relief Air
Outside Air
OUTSIDE AIR INLET NODE LIST,
OutsideAirInletNodes; !- 1st Node name or node list name
NODE LIST,
OutsideAirInletNodes, !- Node List Name
Outside Air Inlet Node 1; !- Node_ID_1
16
TermReheat Outside Air System
Mixed OutsideAir Box
Relief Air
Outside Air
Mixed OutsideAir Box
Relief Air
Outside Air
OUTSIDE AIR SYSTEM,
OA Sys 1, !- Name
OA Sys 1 Controllers, !- Name: Controller List
OA Sys 1 Equipment, !- Name of an Air Loop Equipment List
VAV Sys 1 Avail List; !- Name of a System Availability Manager List
17
TermReheat Outside Air Controller List
Mixed OutsideAir Box
Relief Air
Outside Air
Mixed OutsideAir Box
Relief Air
Outside Air
CONTROLLER LIST,
OA Sys 1 Controllers, !- Name
CONTROLLER:OUTSIDE AIR, !- Controller Type 1
OA Controller 1; !- Controller Name 1
18
TermReheat Outside Air Equipment List
Mixed OutsideAir Box
Relief Air
Outside Air
Mixed OutsideAir Box
Relief Air
Outside Air
AIR LOOP EQUIPMENT LIST,
OA Sys 1 Equipment, !- Name
OUTSIDE AIR MIXER, !- KEY--System Component 1
OA Mixing Box 1; !- Component Name 1
19
TermReheat Outside Air Controller
CONTROLLER:OUTSIDE AIR, OA Controller 1, !- Name ECONOMIZER, !- EconomizerChoice NO RETURN AIR TEMP LIMIT, !- ReturnAirTempLimit NO RETURN AIR ENTHALPY LIMIT, !- ReturnAirEnthalpyLimit NO LOCKOUT, !- Lockout FIXED MINIMUM, !- MinimumLimit Mixed Air Node 1, !- Control_Node Outside Air Inlet Node 1, !- Actuated_Node 0.468, !- minimum outside air flow rate {m3/s} 1.56, !- maximum outside air flow rate {m3/s} 19., !- temperature limit {C} 4., !- temperature lower limit {C} 0.0, !- enthalpy limit {J/kg} Relief Air Outlet Node 1, !- Relief_Air_Outlet_Node VAV Sys 1 Inlet Node, !- Return_Air_Node Min OA Sched; !- Minimum Outside Air Schedule Name
20
TermReheat Outside Air Mixer
Mixed OutsideAir Box
Relief Air
Outside Air
Mixed OutsideAir Box
Relief Air
Outside Air
OUTSIDE AIR MIXER,
OA Mixing Box 1, !- Name
Mixed Air Node 1, !- Mixed_Air_Node
Outside Air Inlet Node 1, !- Outside_Air_Stream_Node
Relief Air Outlet Node 1, !- Relief_Air_Stream_Node
VAV Sys 1 Inlet Node; !- Return_Air_Stream_Node
21
Outdoor Air Economizer
TermReheatOA.idf example file CONTROLLER:OUTSIDE AIR, OA Controller 1, !- Name ECONOMIZER, !- EconomizerChoice NO RETURN AIR TEMP LIMIT, !- ReturnAirTempLimit NO RETURN AIR ENTHALPY LIMIT, !- ReturnAirEnthalpyLimit NO LOCKOUT, !- Lockout FIXED MINIMUM, !- MinimumLimit Mixed Air Node, !- Control_Node Outside Air Inlet Node, !- Actuated_Node 0.4333, !- minimum outside air flow rate {m3/s} 1.3, !- maximum outside air flow rate {m3/s} 19., !- temperature limit {C} 4., !- temperature lower limit {C} 0.0, !- enthalpy limit {J/kg} Relief Air Outlet Node, !- Relief_Air_Outlet_Node VAV Sys 1 Inlet Node; !- Return_Air_Node
22
Outdoor Air Economizer (cont’d)
Scheduled mixed air setpoint
SET POINT MANAGER:SCHEDULED, Mixed Air Temp Manager, !- Name TEMP, !- Control variable Seasonal Reset Mixed Air Temp Sch, !- Schedule Name Mixed Air Nodes; !- Name of the set point Node List NODE LIST, Mixed Air Nodes, !- Node List Name Mixed Air Node; !- Node_ID_1
23
Outdoor Air Economizer (cont’d)
Mixed air setpoint adjusted for fan heat SET POINT MANAGER:SCHEDULED,
Supply Air Temp Manager 1, !- Name TEMP, !- Control variable Seasonal Reset Supply Air Temp Sch, !- Schedule Name Supply Air Temp Nodes 1; !- Name of the set point Node List
SET POINT MANAGER:MIXED AIR, Mixed Air Temp Manager 1, !- Name TEMP, !- Control variable: VAV Sys 1 Outlet Node, !- reference set point node name Main Heating Coil 1 Outlet Node, !- fan inlet node name VAV Sys 1 Outlet Node, !- fan outlet node name Mixed Air Node 1; !- Name of the set point Node or Node List
NODE LIST, Supply Air Temp Nodes 1, !- Node List Name VAV Sys 1 Outlet Node; !- Node_ID_1
24
Economizer with Furnace/DX
Furnace/DX does not set a supply air setpoint
Must use setpoint managers to establish a setpoint
25
Summary
Introduction of outside air into a forced air system is necessary to meet indoor air quality (IAQ) standards
Outside air (mixing box) in EnergyPlus is a component on an air loop branch
Outside air system also contains controllers that can be operated in economizer mode