Test Report issued under the responsibility of:
TEST REPORT
IEC 61008-1
Residual current operated circuit-breakers without integral
overcurrent protection for household and similar uses (RCCBs)
Part 1: General rules
Report Number. .............................: 3310153.50
Date of issue..................................: 2016-08-18
Total number of pages ..................: 34
Name of Testing Laboratory preparing the Report.....................:
DEKRA Testing Services (Zhejiang) Co., Ltd.
No.5, Changjiang Road, Great Bridge Industrial Park, North Baixiang, Wenzhou, Zhejiang, 325603, P.R. China
Applicant’s name...........................: ZHEJIANG MAXGE ELECTRIC TECHNOLOGY CO., LTD.
Address .........................................: NO. 299 EAST CHANGHONG ROAD, DEQING ECONOMIC ZONE, WUKANG, DEQING, ZHEJIANG, CHINA P.C: 313200
Test specification:
Standard ........................................: IEC 61008-1:2010 (Third Edition) +A1:2012 +A2:2013used in conjunction with IEC 61008-2-1:1990 (First Edition) or IEC 61008-2-2:1990 (First Edition)
Test procedure ..............................: Type test
Non-standard test method……….: N/A
Test Report Form No.....................: IEC61008_1H
Test Report Form(s) Originator ....: OVE
Master TRF ....................................: Dated 2015-11
Page 2 of 34 Report No. 3310153.50
TRF No. IEC61008_1H
Test item description ...................... : RCCB
Trade Mark ...................................... : MAXGE
Manufacturer ................................... : ZHEJIANG MAXGE ELECTRIC TECHNOLOGY CO., LTD.
NO. 299 EAST CHANGHONG ROAD, DEQING ECONOMIC ZONE, WUKANG, DEQING, ZHEJIANG, CHINA P.C: 313200
Model/Type reference ..................... : SGR, ALR, EPR, EPR-2
Ratings ............................................ : Ue: 240 V~ (1P+N), 415 V~ (3P+N); 50/60 Hz
In= 16, 20, 25, 32, 40, 50, 63, 80 A
Idn= 30, 100, 300 mA for 16 A to 80 A, 10 mA for 16 A to 25 A
type A and AC, no time-delay
Inc= Idc= 10000 A
Im= Idm: 500 A or 10 In whichever is greater
Responsible Testing Laboratory (as applicable), testing procedure and testing location(s):
Testing Laboratory: DEKRA Testing Services (Zhejiang) Co., Ltd.
Testing location/ address ........................... :No.5, Changjiang Road, Great Bridge Industrial Park, North Baixiang, Wenzhou, Zhejiang, 325603, P.R. China
Associated CB Testing Laboratory: N/A
Testing location/ address ........................... : N/A
Tested by (name, function, signature) ....... : Lester Wang
Approved by (name, function, signature) .. : Eric Wang
Testing procedure: CTF Stage 1: N/A
Testing location/ address ........................... : N/A
Tested by (name, function, signature) ....... : N/A
Approved by (name, function, signature) .. : N/A
Testing procedure: CTF Stage 2: N/A
Page 3 of 34 Report No. 3310153.50
TRF No. IEC61008_1H
Testing location/ address ........................... : N/A
Tested by (name + signature)..................... : N/A
Witnessed by (name, function, signature) . : N/A
Approved by (name, function, signature) .. : N/A
Testing procedure: CTF Stage 3: N/A
Testing procedure: CTF Stage 4: N/A
Testing location/ address ........................... : N/A
Tested by (name, function, signature) ....... : N/A
Witnessed by (name, function, signature) . : N/A
Approved by (name, function, signature) .. : N/A
Supervised by (name, function, signature) : N/A
Page 4 of 34 Report No. 3310153.50
TRF No. IEC61008_1H
List of Attachments (including a total number of pages in each attachment):No attachment.
Summary of testing:The following samples were chosen for the type test according to annex A of IEC/EN 61008-1 in consideration of LCIE CB test report:
No. Current IΔnNumber of
polesTest
voltage Type Test sequence
7# 80 A 30 mA 2P 240 V~ Aseq. A1: cl. 6
8# 80 A 30 mA 4P 415 V~ A
1#~3# 80 A 30 mA 4P 230 V~ ASeq. I: T2.5
4#~6# 80 A 30 mA 4P 400 V~ A
Notes:
1. This report is based on and shall be read in conjunction with LCIE CB certificate No. FR 685060
issued on 2016-04-07 with test reports no. B160008-00 to 08 issued on 2016-03-22, test reports no.
B120048-00 Amendment No.1:2016-01-07, B120048 -19 and 20 issued on 2016-01-07 and test
reports no. B120048-00 to 18 issued on 2013-05-28.
2. The type reference ALR, EPR and EPR-2 are same with SGR except the shape of cover, all tests
were performed on SGR in LCIE CB test reports, sequence I - T2.5 was performed on model SGR to
verify the compliance.
Testing location:
1) Sequence A1: DEKRA Testing Services (Zhejiang) Co., Ltd.
No.5, Changjiang Road, Great Bridge Industrial Park, North Baixiang, Wenzhou, Zhejiang, 325603, P. R. China
2) Sequence I: Zhejiang Fangyuan Test Group Co., Ltd.
Guangqiong Road, Jiaxing City, Zhejiang Province, China
Summary of compliance with National Differences
List of countries addressed:
European standard deviation is considered, RCCB complies with the requirement, and test result refers to annex 1 of this report.
The product fulfils the requirements of
IEC 61008-1: 2010 + A1: 2012 + A2: 2013
IEC 61008-2-1: 1990
EN 61008-1: 2012 + A1: 2014 + A2: 2014 + A11: 2015
EN 61008-2-1:1994 + A11:1998
Page 5 of 34 Report No. 3310153.50
TRF No. IEC61008_1H
Copy of marking plate
The artwork below may be only a draft. The use of certification marks on a product must be authorized by the respective NCBs that own these marks.
Marking for 2P
Marking for 4P
Page 6 of 34 Report No. 3310153.50
TRF No. IEC61008_1H
Test item particulars : Residual current circuit breakers without integral overcurrent protection (RCCB)
Classification of RCCBs functionally dependent on the
line voltage ..............................................................:
No
Opening automatically in case of failure of the line
voltage.....................................................................:
No
- reclosing automatically when the line voltage is
restored...................................................................: No
- not reclosing automatically when the line voltage is
restored...................................................................: No
Not opening automatically in case of failure of the line
voltage.....................................................................:
Yes
- able to trip in a hazardous situation arising on failure
of line voltage...........................................................: No
- not able to trip in a hazardous situation arising on
failure of line voltage ................................................: Yes
Type of RCCB .........................................................:
- type AC .................................................................: Yes
- type A....................................................................: Yes
- independent of the line voltage ...............................: Yes
- dependent on the line voltage.................................: No
- without time delay ..................................................: Yes
- with time delay: type S ...........................................: No
- enclosed................................................................: No
- unenclosed............................................................: Yes
- IP number..............................................................: 20
- for fixed installation ................................................: Yes
- for mobile installation..............................................: No
Page 7 of 34 Report No. 3310153.50
TRF No. IEC61008_1H
Number of poles.......................................................: 2 (1P + N) or 4 (3P + N)
Ambient air temperature (C)....................................: -25 oC to 40
oC
Method of mounting .................................................: Flush-type
Method of connection...............................................:the connections of which are not associated with the mechanical mounting
Rated residual operating current (A)..........................: 30, 100, 300 mA for 16 A to 80 A
10 mA for 16 A to 25 A
Rated current (A) .....................................................: 10, 16, 20, 25, 32, 40, 50, 63, 80 A
Rated voltage (V) .....................................................: 240 V~ (2P) and 415 V~ (4P)
Rated impulse withstand voltage (Uimp) 4 kV
Nature of supply.......................................................: AC
Rated frequency (Hz) ...............................................: 50 / 60 Hz
Rated making and breaking capacity (A).................. : 10 In or 500 A whichever is greater
Rated residual making and breaking capacity (A)..... : 10 In or 500 A whichever is greater
Rated conditional short-circuit current (A) ................ : 10 kA
Rated conditional residual short-circuit current (A) ... : 10 kA
Type of terminal....................................................... : Pillar terminal for copper conductors
Possible test case verdicts:
- test case does not apply to the test object.......... : N/A
- test object does meet the requirement................ : P (Pass)
- test object does not meet the requirement.......... : F (Fail)
Testing ................................................................... :
Date of receipt of test item..................................... : 2016-07
Date (s) of performance of tests ............................ : 2016-07
General remarks:
Page 8 of 34 Report No. 3310153.50
TRF No. IEC61008_1H
"(see Enclosure #)" refers to additional information appended to the report.
"(see appended table)" refers to a table appended to the report.
Throughout this report a comma / point is used as the decimal separator.
Manufacturer’s Declaration per sub-clause 4.2.5 of IECEE 02:
The application for obtaining a CB Test Certificate
includes more than one factory location and a
declaration from the Manufacturer stating that the
sample(s) submitted for evaluation is (are)
representative of the products from each factory has
been provided...........................................................:
Yes
Not applicable
When differences exist; they shall be identified in the General product information section.
Name and address of factory (ies)........................ : ZHEJIANG MAXGE ELECTRIC TECHNOLOGY
CO., LTD.
NO. 299 EAST CHANGHONG ROAD, DEQING
ECONOMIC ZONE, WUKANG, DEQING,
ZHEJIANG, CHINA P.C: 313200
General product information:
Refer to page 7 and 8 for technical data.
The grid distance “a”: 45 mm.
Additional information
Nomenclature breakdown:
SGR 2 80 30 A
a b c d e
a - code denoting the series name: SGR, ALR, EPR or EPR-2
b - code denoting the number of pole: 2= 1P+N, 4= 3P+N
c - code denoting the current rating: 16, 20, 25, 32, 40, 50, 63, 80 A
d - code denoting the residual current rating: 10, 30, 100, 300 mA
e - code denoting the type of RCCB: A= type A, AC= type AC
Page 9 of 34 Report No. 3310153.50
IEC 61008-1
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC61008_1H
TEST SEQUENCE A1 (1 sample) 7#: 2P/ 80 A/ 30 mA/ type A --
6. MARKING --
a) manufacturer's name or trademark .................: MAXGE P
b) type designation, catalogue number or serial number ................................................................ :
SGR/2 P
c) rated voltage(s) (V) .........................................: 240 V~ P
d) rated frequency (Hz) .......................................: 50 / 60 Hz P
e) rated current (A) .............................................: 80 A P
f) rated residual operating current (A) .................: 30 mA P
h) rated making and breaking capacity (A) ..........: 800 A P
j) degree of protection ........................................: N/A
k) position of use ................................................: N/A
l) rated residual making and breaking capacity (A) : Same as Im N/A
m) symbol S for type S N/A
n) symbol of the method of operation ..................: N/A
o) operating means of test device .......................: T P
p) wiring diagram ................................................: P
q) operating characteristic ..................................: P
Marking on the RCCB itself or on nameplate or nameplates attached to the RCCB and located so that for small devices at least e), f), o) and q) (only for type A) are legible when the RCCB is installed :
P
Joule integral withstand capacity (A²s) ................: Table 18 P
Peak current withstand capacity (A) ....................: Table 18 P
Time delay when opening in case of failure of the line voltage (s) ...................................................... :
N/A
Open position indicated by "0" and closed position by "I" .................................................................... :
O / I P
For push-buttons the OFF push-button shall either be red or marked with "0" ..................................... :
N/A
If necessary to distinguish between supply and load terminals they shall be clearly marked ........... :
N/A
Page 10 of 34 Report No. 3310153.50
IEC 61008-1
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC61008_1H
Terminals for neutral conductor marked by "N" N P
Terminals for protective conductor marked by [symbol IEC 417-5019 a]
N/A
Marking indelible, easy legible and not on removable parts
P
9.3 Test: 15 s with water, 15 s with hexane P
For universal terminals (rigid-solid, rigid-stranded and flexible conductors:
P
-no markings P
For non-universal terminals: N/A
-terminals for rigid-solid conductors only, markedby the letters “s” or “sol”
N/A
-terminals for rigid (solid and stranded) conductorsonly, marked by the letter “r”
N/A
marking on the RCCB or if the space available is not sufficient, on the smallest package unit or in technical information
P
Page 11 of 34 Report No. 3310153.50
IEC 61008-1
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC61008_1H
TEST SEQUENCE A1 (1 sample) 8#: 4P/ 80 A/ 30 mA/ type A --
6. MARKING --
a) manufacturer's name or trademark .................: MAXGE P
b) type designation, catalogue number or serial number ................................................................ :
SGR/4 P
c) rated voltage(s) (V) ........................................... : 415 V~ P
d) rated frequency (Hz) ........................................ : 50 / 60 Hz P
e) rated current (A) ............................................... : 80 A P
f) rated residual operating current (A) ................... : 30 mA P
h) rated making and breaking capacity (A) ............ : 800 A P
j) degree of protection .......................................... : N/A
k) position of use .................................................. : N/A
l) rated residual making and breaking capacity (A) : Same as Im N/A
m) symbol S for type S N/A
n) symbol of the method of operation .................... : N/A
o) operating means of test device ......................... : T P
p) wiring diagram ................................................. : P
q) operating characteristic .................................... : P
Marking on the RCCB itself or on nameplate or nameplates attached to the RCCB and located so that for small devices at least e), f), o) and q) (only for type A) are legible when the RCCB is installed :
P
Joule integral withstand capacity (A²s) .................. : Table 18 P
Peak current withstand capacity (A) ..................... : Table 18 P
Time delay when opening in case of failure of the line voltage (s) ...................................................... :
N/A
Open position indicated by "0" and closed position by "I" .................................................................... :
O / I P
For push-buttons the OFF push-button shall either be red or marked with "0" ..................................... :
N/A
If necessary to distinguish between supply and load terminals they shall be clearly marked .......... :
N/A
Page 12 of 34 Report No. 3310153.50
IEC 61008-1
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC61008_1H
Terminals for neutral conductor marked by "N" N P
Terminals for protective conductor marked by [symbol IEC 417-5019 a]
N/A
Marking indelible, easy legible and not on removable parts
P
9.3 Test: 15 s with water, 15 s with hexane P
For universal terminals (rigid-solid, rigid-stranded and flexible conductors:
P
- no markings P
For non-universal terminals: N/A
- terminals for rigid-solid conductors only, markedby the letters “s” or “sol”
N/A
- terminals for rigid (solid and stranded) conductors only, marked by the letter “r”
N/A
marking on the RCCB or if the space available is not sufficient, on the smallest package unit or in technical information
P
Page 13 of 34 Report No.: 331053.50
IEC 61008-1
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC61008_1H
TEST SEQUENCE I (3 samples) 1# -3#: 4P/ 25 A/ 10 mA/
type A
IEC 61543: P
table5-T2.5 Radiated high-frequency phenomena P
2.5 Radiated electromagnetic field P
Test level ………………………………………..…..: 10 V/m P
Frequency range………………………………..…..: 80 MHz – 1G, 1,4 – 2 GHz P
RCCBs were loaded with 0,3 I∆n………………….:
Sweeping the frequecney rang, the RCCBs shall not trip.
1#: no trip
2#: no trip
3#: no trip
P
Then RCCBs were loadedwith 1,25I I∆n……..…..: 12,5 mA P
First sample shall trip at spot frequency 80, 100,120, 160, 200 MHz within 300 ms……….…..:
1#: 31, 29, 34, 33, 31 ms (Hor);
27, 34, 29, 33, 31 ms (Vert)
P
Second sample shall trip at spot frequency 240, 320, 400, 450, 600 MHz within 300 ms…………..:
2#: 28, 36, 31, 27, 29 ms(Hor);
34, 29, 33, 31, 28 ms (Vert)
P
Third sample shall trip at spot frequency 720, 900, 1000, 1400, 2000 MHz within 300 ms………:
3#: 31, 27, 29, 37, 35 ms (Hor);
34, 29, 36, 31, 29 ms (Vert)
P
No value exceeds the specified limiting value P
Page 14 of 34 Report No.: 331053.50
IEC 61008-1
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC61008_1H
TEST SEQUENCE I (3 samples) 4# -6#: 4P/ 80 A/ 30 mA/
type A
IEC 61543: P
table5-T2.5 Radiated high-frequency phenomena P
2.5 Radiated electromagnetic field P
Test level ………………………………………..…..: 10 V/m P
Frequency range………………………………..…..: 80 MHz – 1G, 1,4 – 2 GHz P
RCCBs were loaded with 0,3 I∆n………………….:
Sweeping the frequecney rang, the RCCBs shall not trip.
4#: no trip
5#: no trip
6#: no trip
P
Then RCCBs were loadedwith 1,25I I∆n……..…..: 37,5 mA P
First sample shall trip at spot frequency 80, 100,120, 160, 200 MHz within 300 ms……….…..:
4#: 33, 34, 33, 30, 31 ms (Hor);
29, 28, 34, 29, 27 ms (Vert)
P
Second sample shall trip at spot frequency 240, 320, 400, 450, 600 MHz within 300 ms…………..:
5#: 33, 34, 28, 34, 36 ms (Hor);
26, 31, 29, 29, 33 ms (Vert)
P
Third sample shall trip at spot frequency 720, 900, 1000, 1400, 2000 MHz within 300 ms………:
6#: 29, 31, 28, 29, 34 ms (Hor);
34, 27, 33, 34, 31ms (Vert)
P
No value exceeds the specified limiting value P
Page 15 of 34 Report No.: 3310153.50
IEC 61008_1H - ATTACHMENT
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC61008_1H
Annex 1:
ATTACHMENT TO TEST REPORT IEC 61008-1
EUROPEAN GROUP DIFFERENCES AND NATIONAL DIFFERENCES
Residual current operated circuit-breakers without integral overcurrent protection
for household and similar uses (RCCBs)
Differences according to .............. : EN 61008-1:2012 + A1:2014 + A2:2014 + A11:2015 used in
conjunction with EN 61008-2-1:1994 + A11:1998
Attachment Form No. ................... : EU_GD_IEC61008_1H
Attachment Originator.................. : OVE
Master Attachment ....................... : Dated 2015-11
Copyright © 2015 IEC System for Conformity Testing and Certification of Electrical Equipment
(IECEE), Geneva, Switzerland. All rights reserved.
CENELEC COMMON MODIFICATIONS (EN) --
GENERAL --
9.11 Short circuit tests --
9.11.2.1 d)Value of power frequency recovery voltage shall be equal to 110% of the rated voltage --
9.11.2.1 b) Tolerances and test quantities --
voltage (including recovery voltage): 0, -5% --
--
Page 16 of 34 Report No.: 3310153.50
IEC 61008_1H - ATTACHMENT
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC61008_1H
TEST SEQUENCE "A1" --
6 MARKING (REPLACE CLAUSE 6 BY) --
6.Z1 STANDARD MARKING --
Each RCCB shall be marked in a durable manner according to the following Table Z3. P
RCCB marked with: --
a) The manufacturer's name or trademark MAXGY P
b) Type designation, catalogue number or serial number
SGR P
c) Rated voltage(s) with the symbol 240 V~ (2P), 415 V~ (4P) P
d) Rated frequency, if the RCCB is designed for frequencies other than 50Hz 50 / 60 Hz P
e) rated current 80 A P
f) Rated residual operating current (In) in A or in mA 30 mA P
h) *) Rated making and breaking capacity (Im) 800 A P
j) The degree of protection (only if different from IP20) N/A
k) The position of use, if necessary N/A
l) *) Rated residual making and breaking capacity (Im), if different from rated short-circuit capacity (Im)
N/A
m) The symbol S (S in a square) for type S devices N/A
n) symbol of the method of operation according to Table Z1 of 4.1 if the RCCB is functionally dependent on the line voltage
N/A
o) Operating means of the test device, by the letter T(It is recommended to advise the user to test the device regularly)
T P
p) Wiring diagram unless the correct mode of operation is evident P
r) Operating characteristic in presence of residual currents with d.c. components --
- RCCBs of type AC with the symbolN/A
Page 17 of 34 Report No.: 3310153.50
IEC 61008_1H - ATTACHMENT
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC61008_1H
- RCCBs of type A with the symbol P
s) RCCBs according to 4 Z2 marked with the symbol (snowflake enclosing -25)
P
t) Indication of the terminal for the neutral with "N" N P
u) Additional marking of performance to other standards or additional requirements according to 6.Z2
P
*) IM and Im (if different of IM) may be anywhere on the device or in the catalogue but shall be together.
N/A
If a degree of protection higher than IP20 is marked on the device, it shall comply with it, whichever the method of installation. If the higher degree of protection is obtained only by a specific method of installation and/or with the use of specific accessories this shall be specified in the manufacturers literature
N/A
The manufacturer shall state the Joule integral I²t and the peak current Ip withstand capability of the RCCB. Where this are not stated, minimum values as given in table 15 apply.
P
RCCB classified acc. 4.1.2.1:Time delay when opening in case of failure of the line voltage (s) :
N/A
RCCB´s other than operated by means of push button, open position indicated by "0" and closed position by ""
N/A
Additional national symbols are allowedProvisionally the use of national indications only is allowed These indication visible when RCCB is installed
N/A
For push-buttons the OFF push-button shall either be red and/or marked with "O" N/A
RED shall not be uses for any other push-buttonN/A
If a push-button is used for closing the contacts and is evidently identified as such, its depressed position is sufficient to indicate the closed position.
N/A
If a single push-button is used for closing and opening the contacts and is identified as such, the button remaining in its depressed position is sufficient to indicate the closed position. On the
N/A
Page 18 of 34 Report No.: 3310153.50
IEC 61008_1H - ATTACHMENT
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC61008_1H
other hand, if the button does not remain depressed, an additional means indicating the position of the contacts shall be provided.
If necessary to distinguish between supply and load terminals they shall be clearly marked
N/A
Terminals for neutral circuit N P
Terminal for protective conductor N/A
The suitability for isolation, which is provided by all RCCBs of this standard, may be indicated by the symbol on the device
P
The base for plug-in RCCBs shall be marked with the following: N/A
- rated current or maximum rated current N/A
- trade mark N/A
Marking indelible, easy legible and not on removable parts P
Labels not easy to remove and no curling. Test acc. to cl. 9.3: 15 s with water and 15 s with hexane
P
For universal terminals (rigid-solid, rigid-stranded and flexible conductors: P
-no markings P
For non-universal terminals: N/A
-terminals for rigid-solid conductors only, markedby the letters “s” or “sol”
N/A
-terminals for rigid (solid and stranded) conductorsonly, marked by the letter “r”
N/A
marking on the RCCB or if the space available is not sufficient, on the smallest package unit or in technical information
P
6.Z2 additional marking --
Additional marking to other standards (EN or IEC or other) or additional requirements are allowed under the following conditions:
N/A
- The RCCB shall comply with all the requirements of the additional standard. N/A
Page 19 of 34 Report No.: 3310153.50
IEC 61008_1H - ATTACHMENT
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC61008_1H
- The relevant standards to which the additional marking refers shall be indicated adjacent to this marking and shall be clearly differentiated or separated from the standard marking according to 6.Z.1.
N/A
Compliance is checked by inspection and by carrying out all the test sequences required by the relevant standard. Equivalent or less severe testsequences need not be repeated.
N/A
Page 20 of 34 Report No. 331053.50
TRF No. IEC61008_1H
Photographs:
Front view of SGR
Side view of SGR
Page 21 of 34 Report No. 331053.50
TRF No. IEC61008_1H
Side view of SGR
Internal view of SGR
Page 22 of 34 Report No. 331053.50
TRF No. IEC61008_1H
Front view of SGR
Side view of SGR
Page 23 of 34 Report No. 331053.50
TRF No. IEC61008_1H
Side view of SGR
Internal view of SGR
Page 24 of 34 Report No. 331053.50
TRF No. IEC61008_1H
Front view of ALR
Side view of ALR
Page 25 of 34 Report No. 331053.50
TRF No. IEC61008_1H
Side view of ALR
Internal view of ALR
Page 26 of 34 Report No. 331053.50
TRF No. IEC61008_1H
Side view of ALR
Side view of ALR
Page 27 of 34 Report No. 331053.50
TRF No. IEC61008_1H
Internal view of ALR
Front view of EPR
Page 28 of 34 Report No. 331053.50
TRF No. IEC61008_1H
Side view of EPR
Side view of EPR
Page 29 of 34 Report No. 331053.50
TRF No. IEC61008_1H
Internal view of EPR
Side view of EPR
Page 30 of 34 Report No. 331053.50
TRF No. IEC61008_1H
Side view of EPR
Internal view of EPR
Page 31 of 34 Report No. 331053.50
TRF No. IEC61008_1H
Front view of EPR-2
Side view of EPR-2
Page 32 of 34 Report No. 331053.50
TRF No. IEC61008_1H
Side view of EPR-2
Internal view of EPR-2
Page 33 of 34 Report No. 331053.50
TRF No. IEC61008_1H
Side view of EPR-2
Side view of EPR-2
Page 34 of 34 Report No. 331053.50
TRF No. IEC61008_1H
Internal view of EPR-2