Humidification in Hospitals

Post on 13-Feb-2016

77 views 3 download

Tags:

description

Humidification in Hospitals. Nebraska Society of Healthcare Engineers. Presented By. Eric G. Sherman, P.E., LEED AP, CxA. Jonathon Spreeman, District Sales Engineer. Luke VanCamp, Sales Engineer. Nebraska Society of Healthcare Engineers. Agenda. Humidification of Hospitals - PowerPoint PPT Presentation

Transcript of Humidification in Hospitals

Humidification in HospitalsHumidification in Hospitals

Nebraska Society of Healthcare Engineers

Presented ByPresented By

Nebraska Society of Healthcare Engineers

Eric G. Sherman, P.E., LEED AP, CxA

Jonathon Spreeman, District Sales Engineer

Luke VanCamp, Sales Engineer

AgendaAgendaHumidification of Hospitals

Healthcare Humidification Code

Hospital Dehumidification

Strategy

Comparison

Case Studies

Hospital Humidification

Strategy

Comparison

Questions…..

Nebraska Society of Healthcare Engineers

Healthcare Humidification CodeHealthcare Humidification CodeEric ShermanEric Sherman

Nebraska Society of Healthcare Engineers

AIA / FGI Guidelines for Healthcare Construction

NFPA

The Never Ending Debate

Nebraska Society of Healthcare Engineers

Healthcare Humidification CodeHealthcare Humidification Code

Hospital DehumidificationHospital DehumidificationJonathon SpreemanJonathon Spreeman

Nebraska Society of Healthcare Engineers

Dehumidification StrategiesDehumidification Strategies

Common System Types

• Traditional Cooling & Reheat

• Split Dehumidification Unit

– Dedicated OA Coil

– Dedicated RA Coil

• Series Desiccant Wheel

• Heat Generated Desiccant

Nebraska Society of Healthcare Engineers

Basic CV systemCool & reheat (1 coil)Cool & reheat (2 coils)

Upstream coilDownstream coil

Split dehumidification unitOA coilRA coil

Trane CDQHeat Regenerated Desiccant

70% 26.6 55.3 0

60% 40.0 47.0 12.0

60% 40.0 12.020.0 55.020.0 47.0

60% 28.0 024.0 42.54.0 55.3

52% 29.3 50.3 0

52% 44.0 55.3 * 24.0

Space% RH

Coolingtons

lvg coil°F

Reheat“tons”

CHW°F

45 °F

39 °F

45 °F39 °F

45 °F34 °F

45 °F

45 °F*High Temperature Preheat

Based on 15,000 cfm

System ComparisonSystem Comparison

Nebraska Society of Healthcare Engineers

Cool & reheat (1 coil)Cool & reheat (2 coils)

Upstream coilDownstream coil

Split dehumidification unitOA coilRA coil

Trane CDQHeat Regenerated Desiccant

$5.07 3000 $15,250 $300K

$4.53 3000 $13,590 $272K

$3.07 3000 $9,210 $184K

$2.53 3000 $7,590 $152K$6.00 3000 $18,000 $360K

Oper $/hr @ design

AnnualOper Cost

Over 20

yearsCool Reheat

-11%

-39%

-50%

--

+18%

$0.058/kwh $0.78/therm

Annualhrs

Annual Oper Cost vs

System ComparisonSystem Comparison

Nebraska Society of Healthcare Engineers

CA

OA

RA

SA

MAMA'

WAT

ER V

APO

R

50F49F DPT

55F43F DPT

80F60F DPT

75F63F DPT

TRANE CDQ WHEEL

A “Series” Desiccant wheel used to improve the dehumidification ability of a cold coil

CONDENSATE

Application of Series Desiccant WheelApplication of Series Desiccant Wheel

Nebraska Society of Healthcare Engineers

Application ExamplesApplication Examples

Nebraska Society of Healthcare Engineers

Building Expansion (Existing Central Plant)Good Samaritan Hospital Expansion

– 30,000 CFM Dedicated Surgery Unit

– Existing 42 Degree Chilled Water

– Leaving Unit: 60 Degree DB and 41 Degree DP

Building Expansion (Existing Central Plant)Gothenburg Hospital Surgery Area

– 6,000 CFM Dedicated Surgery Unit

– DX condensing unit

– Leaving Unit: 57 Degree DB and 44 Degree DP

Hospital HumidificationHospital HumidificationLuke VanCampLuke VanCamp

Nebraska Society of Healthcare Engineers

Nebraska Society of Healthcare Engineers

Methods of HumidificationMethods of Humidification

• Direct Steam Injection• Evaporative Pan • Water Spray

Nebraska Society of Healthcare Engineers

Direct Steam InjectionDirect Steam Injection

Nebraska Society of Healthcare Engineers

Humidification GridHumidification Grid

Nebraska Society of Healthcare Engineers

Unfired Steam GeneratorsUnfired Steam Generators

Series RB

Series RB-H Series RB-V

Nebraska Society of Healthcare Engineers

Steam-to-Steam HumidifierSteam-to-Steam Humidifier

Nebraska Society of Healthcare Engineers

Humidification Grid with Atmospheric Humidification Grid with Atmospheric Steam GeneratorSteam Generator

Nebraska Society of Healthcare Engineers

Gas-Fired HumidifierGas-Fired Humidifier

• Will work on natural gas or Will work on natural gas or liquid propane gasliquid propane gas

• Includes models for both Includes models for both indoor and outdoor serviceindoor and outdoor service

• Provides steam production Provides steam production capacities up to 475 lbs/hrcapacities up to 475 lbs/hr

Nebraska Society of Healthcare Engineers

Energy SavingsEnergy Savings

Electricity vs. Gas

Electricity @ $0.08 / kW

Gas @$0.53 / Therm

Based on 150 Lbs/hr Output

$6,600

$2,500

$0$1,000$2,000$3,000$4,000$5,000$6,000$7,000

Operating Cost

ElectricityGas

Nebraska Society of Healthcare Engineers

Electrode Type HumidifierElectrode Type Humidifier

Nebraska Society of Healthcare Engineers

Water DependenciesWater Dependencies

• Conductivity (200-400 (umho)• Hardness (133-266 PPM)• Hardness (7.7-15.5 Grains/Gallon)

Nebraska Society of Healthcare Engineers

Water ImpuritiesWater Impurities

Nebraska Society of Healthcare Engineers

Resistive Heating Element TypeResistive Heating Element Type

Nebraska Society of Healthcare Engineers

Adiabatic HumidifiersAdiabatic Humidifiers

26 0 10 20 30 40 50 60 70 80 90

10

20

30

40

50

100 90 80 70 60 50 40 30

%RH

Gra

i ns

o f M

o ist

u re/

lb. D

ry A

ir

Wet

Bul

b F

20

30

40

50

Dry Bulb F

FOGGERSAVINGS

STEAM MIXING POINT

FOGGER MIXING POINT

RASA

OA

26

0 10 20 30 40 50 60 70 80 90

10

20

30

20

30

40

FOGGERSAVINGS

STEAM MIXING POINT

FOGGER MIXING POINT

OA

Spring/Fall Spring/Fall EconomizerEconomizer

1. O.A. Mixing2. Fogging3. Building Heat Gain

Nebraska Society of Healthcare Engineers

NozzleNozzle

Thank you for your time!Thank you for your time!

Questions please?Questions please?

Nebraska Society of Healthcare Engineers