Course: SHMTF
Simultaneous Heat and Mass Transfer
Humidification/Dehumidification
2Course: SHMTDepartment of Chemical Engineering , U.E.T. Lahore
Industrial Applications & Equipment
3Course: SHMTDepartment of Chemical Engineering , U.E.T. Lahore
The Fume Scrubber
Throat pieces are used to assure close contact of gas and liquid streams.
Open area allows separation of the two phases. Nozzle capacities are normally 5-10 gal/min of
water Throat pieces capacity is 300 ft3/min of gas per
gallon per minute of liquid. Scrubbers are often applied to removing dust
from gas stream
4Course: SHMTDepartment of Chemical Engineering , U.E.T. Lahore
Spray pond
Spray nozzle delivers 50 gals/min each. Pressure is about 7 psig. Located about 6ft above the pond surface. Spaced about every 4 ft. Pond is surrounded by a louvered fence about 12 ft
high to reduce wind losses. Typical water loading rates for spray ponds are about
500 Ib/hr ft2 of pond area. Advantage:
Low Cost.
Disadvantage: Low capacity for a given pond area. Large water losses.
5Course: SHMTDepartment of Chemical Engineering , U.E.T. Lahore
Cooling Towers (Types)
Cooling towers are a very important part of many chemical plants. They represent a relatively inexpensive and dependable means of removing low grade heat from cooling water.
Cooling towers fall into two main sub-divisions:
1) Natural Draft.2) Mechanical Draft.
Natural draft :Designs use very large concrete chimneys to introduce air through the media. Due to the tremendous size of these towers (500 ft high and 400 ft in diameter at the base) they are generally used for water flowrates above 200,000 gal/min. The tower is built of reinforced concrete varying from 5 to 12in. Thick.Usually these types of towers are only used by utility power stations.
6Course: SHMTDepartment of Chemical Engineering , U.E.T. Lahore
Natural Draft.Cooling Tower
7Course: SHMTDepartment of Chemical Engineering , U.E.T. Lahore
8Course: SHMTDepartment of Chemical Engineering , U.E.T. Lahore
Mechanical draft Cooling Towers Mechanical draft: This type of cooling towers are much more widely used.
These towers utilize large fans to force air through circulated water. The water falls downward over fill surfaces which help increase the contact time between the water and the air. This helps maximize heat transfer between the two.
Mechanical draft towers offer control of cooling rates in their fan diameter and speed of operation. These towers often contain several areas (each with their own fan) called cells.
9Course: SHMTDepartment of Chemical Engineering , U.E.T. Lahore
Mechanical draft Cooling Towers
10Course: SHMTDepartment of Chemical Engineering , U.E.T. Lahore
Types of Mechanical Draft Towers
Figure 2: Mechanical Draft Counterflow Tower Figure 3: Mechanical Draft Crossflow Tower
Mechanical Draft Counterflow Tower Mechanical Draft Crossflow Tower
11Course: SHMTDepartment of Chemical Engineering , U.E.T. Lahore
Types of Mechanical Draft Towers
12Course: SHMTDepartment of Chemical Engineering , U.E.T. Lahore
Natural Draft
13Course: SHMTDepartment of Chemical Engineering , U.E.T. Lahore
Mechanical Draft Towers
14Course: SHMTDepartment of Chemical Engineering , U.E.T. Lahore
Simplified diagram
15Course: SHMTDepartment of Chemical Engineering , U.E.T. Lahore
Natural Draft
16Course: SHMTDepartment of Chemical Engineering , U.E.T. Lahore
Natural draft towers in action
17Course: SHMTDepartment of Chemical Engineering , U.E.T. Lahore
Component Description
Condenser pump & distribution systems
Hot water from a chilled water system is delivered to the top of the cooling tower by the condenser pump through distribution piping. The hot water is sprayed through nozzles onto the heat transfer media (fill) inside the cooling tower. Some towers feed the nozzles through pressurized piping; others use a water distribution basin and feed the nozzles by gravity.
Cooling loop system A cold-water collection basin at the base of the tower gathers cool water after it has passed through the heat transfer media. The cool water is pumped back to the condenser to complete the cooling water loop
Components of a cooling tower
18Course: SHMTDepartment of Chemical Engineering , U.E.T. Lahore
Heat transfer media
Cooling towers use evaporation to release waste heat from a HVAC system. Hot water flowing from the condenser is slowed down and spread out in the heat transfer media (fill). A portion of the hot water is evaporated in the fill area, which cools the bulk water. Cooling tower fill is typically arranged in packs of thin corrugated plastic sheets or, alternately, as splash bars supported in a grid pattern.
Cooling tower fan system Large volumes of air flowing through the heat transfer media help increase the rate of evaporation and cooling capacity of the tower. This airflow is generated by fans powered by electric motors. The cooling tower fan size and airflow rate are selected for the desired cooling at the design conditions of hot water, cold water, water flow rate, and wet bulb air temperature.
HVAC cooling tower fans may be propeller type or squirrel cage blowers, depending on the tower design. Small fans may be connected directly to the driving motor, but most designs require an intermediate speed reduction provided by a power belt or reduction gears. The fan and drive system operates in conjunction with a starter and control unit that provides start/stop and speed control.
Components of a cooling Syatem
19Course: SHMTDepartment of Chemical Engineering , U.E.T. Lahore
Components of a cooling tower Drift eliminators As cooling air moves through the
fill, small droplets of cooling water become entrained and can exit the cooling tower as carry-over or drift. Devices called drift eliminators are used to remove carry-over water droplets. Cooling tower drift becomes an annoyance when the droplets fall on people and surfaces downwind from the cooling tower. Efficient
drift eliminators remove virtually all of the entrained cooling water droplets from the
air stream.
20Course: SHMTDepartment of Chemical Engineering , U.E.T. Lahore
Induced draft cooling tower
21Course: SHMTDepartment of Chemical Engineering , U.E.T. Lahore
Cut- view of a tower
22Course: SHMTDepartment of Chemical Engineering , U.E.T. Lahore
Cooling towers in action (induced draft)
23Course: SHMTDepartment of Chemical Engineering , U.E.T. Lahore
Properties of humid air
• Humid air can be said to be a mixture of two ideal gases - dry air (d.a.) and water vapor. • The dry air can be treated as one component
since its composistion does not change in the temperature and pressure interval considered here.
• Dry air can be assumed to consist of:
Nitrogen: 78 % by volume, M=28 kg/kmol
Oxygen: 21 % by volume, M=32 kg/kmol
Argon: 1 % by volume, M=40 kg/kmol
• Mean molecular weight of dry air, M=29 kg/kmol
24Course: SHMTDepartment of Chemical Engineering , U.E.T. Lahore
Amount of water in humid air
The amount of water in humid air can be
expressed in several ways;
• Relative humidity, Y
• Water content, xw
• Dew point
• Dry, and wet bulb temperature
25Course: SHMTDepartment of Chemical Engineering , U.E.T. Lahore
Dew point
Aircool.gif
Cooling Air
When air is cooled, relative humidity increases as shown to the right. Cooling air that is 90oF/20% RH causes the relative humidity to increase until it reaches 100%; the temperature known as the dew point (43.6oF in this example). At the dew point, moisture begins to condense out of the air and is transformed from vapor to liquid.Most everyone has witnessed bathroom mirrors 'fogging' during a hot shower or iced-drink glasses 'sweating' on the outside. The cool surfaces are simply condensing moisture out of humid air.This aspect of psychrometrics is very important when it comes to analyzing indoor conditions as temperatures and humidity levels within our environments are very dynamic.
26Course: SHMTDepartment of Chemical Engineering , U.E.T. Lahore
Relative Humidity
The amount of moisture in air can be expressed in a number of ways but the most common reference is relative humidity. This value, expressed as a percentage, represents the amount of moisture in the air relative to the amount of moisture air could hold at that temperature.
Therefore, the relative humidity at a given temperature will range from 0% (dry air) to 100% (fully saturated air). (When you exceed 100%, moisture starts falling out of the air and it rains.)
27Course: SHMTDepartment of Chemical Engineering , U.E.T. Lahore
Relative Humidity
In other words, air at 70 degrees Fahrenheit (70oF) and 50% relative humidity (50% RH) is holding half of what it could hold when completely saturated (100% RH) as shown on the right.
28Course: SHMTDepartment of Chemical Engineering , U.E.T. Lahore
PERCENT SATURATION
100 Y . Ma/Mb
Percent saturation = 100 Y/Ys
Ys . Ma / Mb
Y = mole ratio of condensable to non-condensable component
Ys = mole ratio present at saturation
Ma, Mb= Molecular weight.
29Course: SHMTDepartment of Chemical Engineering , U.E.T. Lahore
The Humidity Chart
30Course: SHMTDepartment of Chemical Engineering , U.E.T. Lahore
Example
100%
60%
31Course: SHMTDepartment of Chemical Engineering , U.E.T. Lahore
Determination of bulk-gas phase temperature
V
A
P
O
R
P
H
A
S
E
E
N
T
H
A
L
P
Y
Hv
Temperature (Tl,Tv,or Ti) , 0F
Interface condition
locus
Operating Line
C(Tl,Hv)
F(Tv,Hv)
D
GH
I
J
L M N
O P Q