Post on 17-Feb-2018
7/23/2019 guia conector rj45
http://slidepdf.com/reader/full/guia-conector-rj45 1/4
INSTALLATION INSTRUCTIONS PN375B © Panduit Corp. 2009
For Technical Support: www.panduit.com/resources/install_maintain.asp
TX6 PLUS Shielded Modular Plug
T568B & T568APart Number: SPS688-C
• First thread on the Boot and Collar.
• Remove 1.5" of the outer jacket from the cable end using wirestripping tool (CJAST).
• Cut foil flush to cable jacket end. If cable is braided, form into
a drain wire. Bend the drain wire back so it is against thecable jacket.
• Fan twisted pairs into respective quadrants. The brown pairshould be opposite the orange pair.
• When a cable spline (X-shaped filler) is present, cut splineflush to fanned pairs using wire snipping tool (CWST).
1 Thread on Bootand Collar first!(Cable ends 1 & 2)
90°
CWST
Specifications• Cable jacket diameter .225-.250 in.
• 24 AWG Stranded conductor maximum
insulated diameter .040 in.
• PANDUIT recommends T568B wiring scheme fo
use with cable constructed with the brown pair
opposing the orange pair.
• For use with FTP, ScTP, SFTP and STP/PIMF
type cables. Cable must have drain wire or braid
Conductor holes and Contact slots
Page 1 of 4
Strain Relief Boot
Strain Relief Collar
Divider
Load Bar
Plug Housing with Shield
Load Bar
18
DividerConductor slots and “V” channel
• The “V” channel should be aligned with the green pair.
• Insert Divider posts into the cable. If the cable has an internalspline, insert Divider posts into the brown and orangequadrants of the spline.
2
BLU
GRN
“V” channel
BRN
ORG
GRN
BLU
BRN
ORG
(Cable end 2)
(Cable end 1)
“V” channel
• Arrange conductors to T568B Wiring Scheme while minimizinguntwist and smooth conductors.
• Seat conductors into proper Divider slots while holding Dividernear the end of the cable jacket.
3
“V” channel
(Cable end 1) (Cable end 2)
T568B Wiring Scheme
T568B BRN
8
WHT
7
BRN/
6
GRNWHT
5
BLU/
4
BLUWHT
3
GRN/
2
ORGWHT
1
ORG/
Pin #(Cable end 2)
(Cable end 1)
“V” channel
Conductor holes
Contact slotsDivider post
Pins
7/23/2019 guia conector rj45
http://slidepdf.com/reader/full/guia-conector-rj45 2/4
INSTALLATION INSTRUCTIONS PN375B
For Technical Support: www.panduit.com/resources/install_maintain.asp
• Guide conductors into Load Bar holes while holdingconductors in the Divider.
• Slide Load Bar towards Divider until flush.
• Ensure the Divider/Load Bar is centered and perpendicularto the cable axis.
• Trim conductors flush with Load Bar face.
6
(Cable end 1)
7
• Orient Load Bar with contact slots facing downward.
VerifyLoad Barorientation
5
(Cable end 1)
(Cable end 2)
1
8Pins
1
8Pins
• While holding conductors in respective Divider slots,straighten and align untwisted conductors using a circularmotion.
• Do not release grip of conductors until Load Bar is appliedin order to maintain conductor alignment.
• Trim conductors on an angle approximately 1.00" fromDivider leading edge.
4
1.00"
T568B BRN
8
WHT
7
BRN/
6
GRNWHT
5
BLU/
4
BLUWHT
3
GRN/
2
ORGWHT
1
ORG/
Pin #
(Cable end 1)
10 MPT5-8A9 • Grip and squeeze across Collar arms as sub-assembly isinserted into Plug Housing. (Fig. 9)
• Push sub-assembly into Housing until Collar locking tabs clearthe Plug Housing pocket. Although not required, TX6 PLUS Plug Assembly Tool (CSPT) is available to facilitate this step.
• Use tool MPT5-8A to complete termination. (Fig. 10)
• Press any excess drain wire between the Collar Latches andthe cable jacket. Pull up Boots and engage with Collar. Latchesof the Collar should be engaged on the window slot of the boot.
• Assembly is complete. Visually check plug.
Drain Wire
(Cable end 2)
(Cable end 1)
Strain CollarGuides
Collar Latches
Boot positionwhen usingCSPTPins
Collar Barbs
1
8
Pins
1
8
Collar LockingTabs
• Orient cable so drain wire is facing up. While holding the LoadBar and Divider stationary, slide the Collar towards thetermination point until there is no gap between the Collar andDivider. Ensure the drain wire is routed through the StrainCollar Guides. Do not exert pressure onto the Divider, theCollar can push the Load Bar off the conductors.
• Confirm orientation of Collar. Cable jacket should extendbeyond Collar barbs.
• Align Pin #1 of cable sub-assembly (Cable, Load Bar, Divider,Collar with Boot) with Pin #1 of Plug Housing.
8
Page 2 of 4
7/23/2019 guia conector rj45
http://slidepdf.com/reader/full/guia-conector-rj45 3/4
INSTALLATION INSTRUCTIONS PN375B
For Technical Support: www.panduit.com/resources/install_maintain.asp
T568A Wiring Scheme
T568A BRN
8
WHT
7
BRN/
6
ORG WHT
5
BLU/
4
BLU WHT
3
ORG/
2
GRN WHT
1
GRN/
Pin #
• The “V” channel should be aligned with the orange pair.
• Insert Divider posts into the cable. If the cable has an internalspline, insert Divider posts into the brown and greenquadrants of the spline.
2
BLU
ORG
“V” channel
BRN
GRN
ORG
BLU
BRN
GRN
(Cable end 2)
(Cable end 1)
“V” channel
• Arrange conductors to T568A Wiring Scheme whileminimizing untwist and smooth conductors.
• Seat conductors into proper Divider slots while holdingDivider near the end of the cable jacket.
3
“V” channel
(Cable end 1) (Cable end 2)
Conductor holes and Contact slots
Load Bar DividerConductor slots and “V” channel
“V” channelDivider post
18
Conductor holes
Contact slots
Pins
Specifications
• Cable jacket diameter .225-.250 in.• 24 AWG Stranded conductor maximum
insulated diameter .040 in.
• PANDUIT recommends T568A wiring scheme fo
use with cable constructed with the brown pair
opposing the green pair.
• For use with FTP, ScTP, SFTP and STP/PIMF
type cables. Cable must have drain wire or braid
Page 3 of 4
Strain Relief Boot
Strain Relief Collar
Divider
Load Bar
Plug Housing with Shield
(Cable end 2)
(Cable end 1)
• First thread on the Boot and Collar.
• Remove 1.5" of the outer jacket from the cable end using wirestripping tool (CJAST).
• Cut foil flush to cable jacket end. If cable is braided, form intoa drain wire. Bend the drain wire back so it is against thecable jacket.
• Fan twisted pairs into respective quadrants. The brown pairshould be opposite the green pair.
• When a cable spline (X-shaped filler) is present, cut splineflush to fanned pairs using wire snipping tool (CWST).
1 Thread on Bootand Collar first!(Cable ends 1 & 2)
90°
CWST
7/23/2019 guia conector rj45
http://slidepdf.com/reader/full/guia-conector-rj45 4/4
E-mail:cs@panduit.com
Fax: (708) 444-6993
For Instructions in Local Languagesand Technical Support:
www.panduit.com/resources/install_maintain.aspwww.panduit.com
INSTALLATION INSTRUCTIONS PN375B
4
1.00"T568A BRN
8
WHT
7
BRN/
6
ORGWHT
5
BLU/
4
BLUWHT
3
ORG/
2
GRNWHT
1
GRN/
Pin #
(Cable end 1)
• While holding conductors in respective Divider slots,straighten and align untwisted conductors using a circularmotion.
• Do not release grip of conductors until Load Bar is appliedin order to maintain conductor alignment.
• Trim conductors on an angle approximately 1.00” fromDivider leading edge.
5(Cable end 1)
(Cable end 2)
1
8Pins
VerifyLoad Barorientation
1
8Pins
• Orient Load Bar with contact slots facing downward.
6
(Cable end 1)
7 • Guide conductors into Load Bar holes while holdingconductors in the Divider.
• Slide Load Bar towards Divider until flush.
• Ensure the Divider/Load Bar is centered and perpendicularto the cable axis.
• Trim conductors flush with Load Bar face.
10MPT5-8A9 • Grip and squeeze across Collar arms as sub-assembly is
inserted into Plug Housing. (Fig. 9)
• Push sub-assembly into Housing until Collar locking tabs clearthe Plug Housing pocket. Although not required, TX6 PLUS Plug Assembly Tool (CSPT) is available to facilitate this step.
• Use tool MPT5-8A to complete termination. (Fig. 10)
• Press any excess drain wire between the Collar Latches andthe cable jacket. Pull up Boots and engage with Collar. Latchesof the Collar should be engaged on the window slot of the boot.
• Assembly is complete. Visually check plug.
Drain Wire
(Cable end 2)
(Cable end 1)
Strain CollarGuides
Collar Latches
Boot positionwhen usingCSPTPins
Collar Barbs
1
8
Pins
1
8
Collar LockingTabs
• Orient cable so drain wire is facing up. While holding the Load
Bar and Divider stationary, slide the Collar towards thetermination point until there is no gap between the Collar andDivider. Ensure the drain wire is routed through the StrainCollar Guides. Do not exert pressure onto the Divider, theCollar can push the Load Bar off the conductors.
• Confirm orientation of Collar. Cable jacket should extendbeyond Collar barbs.
• Align Pin #1 of cable sub-assembly (Cable, Load Bar, Divider,Collar with Boot) with Pin #1 of Plug Housing.
8
Page 4 of 4