Grouted Post-Tensioning: Protection Levels

Presented by: Jacob Myer2013 PTI Convention: Scottsdale, AZ

Title Text

History of Protection Levels

Title Text

Protection Level Categories 

Levels 1A, 1B, 2,3Tensile Elements

Duct TypeDuct Connection Requirements

GroutEmbedment Coating

Anchorage CapEncapsulation Type

Title Text

Protection Level 1 : Tensile Elements

Unless the project requires otherwise main tensile elements must conform to the following:

Strand must conform to ASTM A416, Grade 270, low‐relaxation, seven‐wire strand.

High Strength Bar must conform to ASTM A722, Grade 150

Title Text

Protection Level 1: Duct

Duct for PL1 can consist of of the following:Galvanized Duct

Seamless Plastic DuctSmooth HDPE Pipe

Title Text

Galvanized Spiral Duct

Fabricated of galvanized sheet conforming to ASTM A653/A653M, coating designation G90

26 Ga for Duct up to 2.625” Dia24 Ga for Duct over 2.625” Dia

Title Text

Plastic Duct

Seamless Corrugated Plastic DuctFabricated from virgin, unfilled, non‐colored 

polypropylene or polyethylene.

Title Text

Smooth HDPE Pipe• SDR 17• 100 psi Working Pressure• 100% Virgin HDPE with 40 min OIT 

Title Text

Protection Level 1A: Grout

Basic grout Type B per PTI’s “Specification for Grouting of Post‐Tensioned Structures”;

Engineered grout Type A per PTI’s “Specification for Grouting of Post‐Tensioned Structures”;

Grout filling procedure to leave no voids in duct.

Title Text

Protection Level 1: Embedment Coating

No Special Coating Requirements

Title Text

Protection Level 1: Anchorage CapNo Permanent Cap Requirement

Title Text

Protection Level 1: Duct Connections

• Must Be Concrete Paste Tight• Smooth Interior Alignment• Capable Of Withstanding 10ft 

Concrete Fluid Pressure• Mechanical Couplers, Plastic Sleeves, 

Or Heat Shrink Are Typically Used

Title Text

Protection Level 2

(Picture of PL2 system)

Title Text

Protection Level 2: DuctDuct must provide for a air/water tight envelope around 

the tensile element .Duct for PL2 can consist of of the following:

Seamless Plastic DuctSmooth HDPE Pipe

Title Text

Protection Level 2: Grout

Engineered grout Type A per PTI’s “Specification for Grouting of Post‐Tensioned Structures”

Thixotropic in nature

Grout filling procedure to leave no voids in duct.

Title Text

Protection Level 2: Embedment CoatingEmbedded Components must be Galvanized or 

Epoxy Coated

Title Text

Protection Level 2: Anchorage Cap• Approved Materials:Stainless 316 ASTM A240,

nylon, acrylonitrile butadiene styrene (ABS), or polyester• Must hold 150psi working pressure

Title Text

Protection Level 2: Duct Connections

• Must Create Air and Water Tight Seal• Smooth Interior Alignment

• Capable Of Withstanding 10ft Concrete Fluid Pressure• Tape Seals not allowed

Title Text

Protection Level 3

• Air Tight System equal to PL2• Includes Electric Isolation of Tensile elements

• Allows PT system to be monitorable and inspectable

Title Text

FIB Testing Plastic Duct Performance Spec

Title Text

Dimensional Test

Title Text

Flexural Behavior Test

Title Text

Flexibility of Duct

Title Text

Lateral Load Resistance of Duct

Title Text

Longitudinal Load Resistance

Title Text

Leak Tightness Of Duct

Title Text

Wear Resistance Of Duct

Title Text

Bond Behavior of Tendon

Title Text

Area’s for Improvement

Title Text

Any Questions?